1 Class I Leak Detection Systems - Highest level of monitoring and prevention of double walled tanks and pipes, according EU Standard EN 13160-2 Overpressure systems working principle… www.thomas-leak-detection.com

Transcript of 1 Class I Leak Detection Systems - Highest level of monitoring and prevention of double walled tanks...

Page 1: 1 Class I Leak Detection Systems - Highest level of monitoring and prevention of double walled tanks and pipes, according EU Standard EN 13160-2 Class.

1

Class I Leak Detection Systems - Highest level of monitoring and prevention of

double walled tanks and pipes, according EU Standard EN 13160-2

Overpressure systems

working principle…

www.thomas-leak-detection.com

Page 2: 1 Class I Leak Detection Systems - Highest level of monitoring and prevention of double walled tanks and pipes, according EU Standard EN 13160-2 Class.

Interstitial space

Pressure line Measuring

line

Air flow

OFF ON

PumpPressure in the

Interstitial

Green operation light

- Leak detector shows normal operation by green light

Normal Operation

- Interstitial space of the double walled tank (or pipe) is pressurized up to system setup „Pump OFF“

- Normal pressure variations, caused by the system or temperature changes balanced by the pump

OFF ONNote:If the operating frequency of the

pump increases more and more, this points to an increasing leakage.

Double walled tank (or pipe)

Leak Detection acc. EN 13160 Class IWorking principle - overpressure system Pressure leak detector

(e.g. THOMAS-ASF D9)

Page 3: 1 Class I Leak Detection Systems - Highest level of monitoring and prevention of double walled tanks and pipes, according EU Standard EN 13160-2 Class.

… in theouter tank wall

or

PumpPressure in the

Interstitial

OFF ON

Air flow

OFF ON

Leakage in the system…

- Air is pressed through the inner wall into the tank, or through the outer wall

- Pressure level in the interstitial space is decreasing

- At set point “Pump ON”, pump starts

- Pump can‘t balance the leakage, the pressure level changes down to the set point “Alarm ON”- Alarm situation indicated by visual red light and acoustic buzzer

- Switch off the buzzer, call for service

Alarm buzzer switch

„Buzzer disabled” indicated by yellow light

Red alarm light

Prevention time

… in theinner tank wall

Pressure leak detector(e.g. THOMAS-ASF D9)

Leak Detection acc. EN 13160 Class IWorking principle - overpressure system

- For a certain period of time, the pressure in the interstitial remains higher than the max. hydrostatical pressure inside the tank prevents leaking into the environment

Page 4: 1 Class I Leak Detection Systems - Highest level of monitoring and prevention of double walled tanks and pipes, according EU Standard EN 13160-2 Class.