Cast Iron Commercial Water or Steam Boiler
837 to 5733 MBH Input
Oil, Gas, or Oil/Gas Combination
30, 50, or 80 PSI
Cast Iron Sectional Design
Water or Steam
Top or Rear Venting
Exclusive Optional SBC Boiler Controlª
Ð M aximizes System Efficiency
V11 Series
1
Installation & Service FlexibilityThecastironsectionaldesignoftheV11boilermakesiteasytomaneuver through doorways and into the boiler room. In addi-tion to being shipped as loose sections, the boiler is available with factory-assembled sections or as a completely packaged and fire-tested unit.
• Hassle-free Section Assembly V11boilersectionshavereinforcedlugsthatareused to assemble the sections with individual draw rods resulting in fast, strain-free assembly.
The sections can be assembled using two common toolsÑ a 3/4" drive ratchet with a 1-1/16" deep socket and wrench. The sections are surface ground to ensure smooth surface mating. An elastic sealant and fiberglass rope are used on all section joints for a completely sealed and pressure-tight assembly.
• extensive Testing Methods Each boiler section is hydrostatically tested at 2-1/2 times theratedworkingpressureatthefoundry.Factory- assembled sections are tested a second time at 1.5 times the rated working pressure.
• Rear or Top Venting Asaforceddraftboiler,theV11 provides optimum draft for controlled efficiency, eliminating the need for high chimneys or induced draft fans. AuniquefeatureoftheV11boiler is that it can be vented from the rear or the top. This enables easy chimney or sidewall venting for maximum installation flexibility. Top outlet venting saves floor space and reduces installation time and materials. A plugged tapping is provided to take flue outlet pressure readings.
Available in twenty sizes with gross output ratings from 667to4551MBH,theV11Seriesiscommonlyusedinschools, hospitals, and other large commercial applications where comfort and reliability are critical. The product meets theenergyefficiencyrequirementsofASHRAE90.1withcombustion efficiencies up to 85%.
Cast iron construction, ease of assembly, two venting options, andstringenttestingmethodsmaketheV11SeriesboilerbyBurnham Commercial your commercial heating solution.
American-Made Cast Iron ConstructionÐBC25-HSiBurnham CommercialÕ s unique BC25-HSicastironformulahasan extremely high silicon content, making it stronger and more flexible than the iron used in competitor's boiler sections. It offers better thermal shock resistance and greater heat transfer capabilities than other cast iron products. BC25-HSi'spropertiesallowBurnhamCommercialtomaintain the highest level of quality from start to finish, and provide a product that is optimized for hydronic heating applications.
• Manufactured with Quality Cast iron sections are produced at BurnhamFoundryLLCinOhio, ensuring quality and availability of boiler sections.
• Cast Iron nipple Difference V11sectionsareheldtogether using cast iron nipples, which are well known as being of the highest standard for boiler construction. Unlike gaskets used by many other boiler manufacturers, cast iron nipples are impervious to flue gases, oils, petroleum-based chemicals and other contaminants, which means fewer costly repairs and a longer lasting boiler.
Cast Iron Commercial Water or Steam BoilerCast Iron Commercial Water or Steam BoilerV11 Series
Your Commercial Heating Solution!
2
Front Mounted Controlsfor easy adjustment and maintenance
Top or Rear Outletwith adjustable lock-type damper (not shown); includes plugged tapping for outlet pressure readings
Cast Iron Sections
Verticalfluedesignwith pinned heating surface for maximum heat extraction
Removable Side Jacket panelsEasy access to all cleanouts and flue surfaces
Burner Mounting platewith flame observation port
4 Burner ManufacturersOptionstobest fit your needs
Individual Draw Rodswith reinforced lugs for strain free assembly
Optional Tankless Heater Providesdomestichotwater
Aluminized Steel Canopy
Cast Iron nipplesensure the integrity of the section assembly and resistpetroleum based chemicals and flue gases
Rear Observation portIncludes plugged tapping for over-fire draft readings
Wet BaseSide wall insulation creates improved thermal circulation
Commitment to QualityBurnham Commercial, "America's Boiler Company," has earned a reputation for quality and dependability. Built for a variety of applications,theV11Seriesisrightforyournextjob.
The SBC Boiler Control SystemÉOnly available from Burnham Commercial!
thermal circulationthermal circulation
SBCTM
Integrated Boiler Control System
Burnham CommercialÕ s SBC is a complete boiler monitoring and automation system. Available as an option, this exclusive feature wasdesignedanddevelopedbyBurnhamCommercial’sengineersandisavailableONLYon Burnham Commercial products.
Designedtomaximizesystemefficiency and minimize energy usage
Easily connected to building management systems
Provencontrolplatform,usedsuccessfully for years at other Burnham companies
Fail-safedesigninsuresboileroperation
Also AvailableÉ
SBC Exclusives•AdvancedAdaptability•Peer-To-PeerNetwork •Fail-Safe System Operations•BoilerMonitoring&DiagnosticDisplays•ModulationRateandOn/OffModes•Outdoor Air Temperature Reset•Warm Weather Shutdown (WWSD)•Domestic Hot Water Priority (DHWP)
•System Control Outputs
3
all dimensions in inches
* Burnercontrolpanelconfigurationmaychangethisdimension
BOILeR MODeL
nUMBeROF
SeCTIOnS 'A' 'B' 'C' 'D' 'e' 'F' 'G' 'H' 'J' 'K' 'L'
BURneR DIMenSIOn - 'M' *AppROX.
WeIGHT OF SeCTIOn
(Assembly Only)
BeCKeTT
CARLIn
pOWeRFLAMe WeBSTeR
CF CG CR JR** JBV1104V1105V1106V1107V1108V1109V1110
45678910
26-5/832-3/438-7/8
4551-1/857-1/463-3/8
18-7/825
31-1/837-1/443-3/849-1/255-5/8
ÑÑ
31-1/837-1/443-3/849-1/224-3/4
ÑÑÑÑÑÑ
30-7/8
ÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑ
13-13/1619-15/1626-1/1632-3/1638-5/1644-7/1650-9/16
55555554545453
88810101012
1223344
24-3/424-3/424-3/424-1/424-1/424-1/424-1/4
21-3/421-3/428-3/429-1/429-1/429-1/429-1/4
Ñ19-3/419-3/420-1/220-1/220-1/225-5/8
30303535353535
20-1/420-1/423-3/423-3/423-3/4
ÑÑ
25252525252525
1833222626183010340337954188
V1111V1112V1113V1114V1115V1116V1117
11121314151617
69-1/275-5/881-3/487-7/8
94100-1/8106-1/4
61-3/467-7/8
7480-1/886-1/492-3/898-1/2
373737
24-3/424-3/430-7/830-7/8
24-3/430-7/8
3724-1/224-1/236-3/436-3/4
ÑÑÑ
30-7/837
24-3/430-7/8
ÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑ
56-11/1656-5/8
53-5/1653-5/1653-5/1653-5/1653-5/16
53535352525252
12121214141414
4555666
24-1/425-3/425-3/4
272726Ñ
29-5/829-5/829-5/829-5/829-5/829-5/829-5/8
25-5/825-5/826-1/826-1/826-1/826-1/826-1/8
40404040404040
ÑÑÑÑÑÑÑ
29292929292929
4580497253655757615065426934
V1118V1119V1120V1121V1122V1123
181920212223
112-3/8118-1/2124-5/8130-3/4136-7/8
143
104-5/8110-3/4116-7/8
123129-1/8135-1/4
30-7/830-7/830-7/830-7/830-7/830-7/8
24-1/224-1/224-1/224-1/224-1/224-1/2
24-1/224-1/236-3/436-3/424-1/224-1/2
24-3/430-7/824-3/430-7/824-1/224-1/2
ÑÑÑÑ
24-3/430-7/8
53-5/1653-5/1653-5/1653-5/1653-5/1653-5/16
515151515050
161616161818
778899
ÑÑÑÑÑÑ
29-5/829-5/8
ÑÑÑÑ
ÑÑÑÑÑÑ
404040404646
ÑÑÑÑÑÑ
292929292929
732777198112850488969289
V11 Series Dimensions
FRONT OBSERVATION
PORT
4
nOTeS:1.Allpipingisschedule40.2. Pipesizelistedarebasedona20°For40°F differential (temperature drop). Select one to match application.3.Whenspecifiedreturnpipingsizeislessthan3", install 3" x 12" nipple and appropriate size bell reducer directly into boiler return tapping as shown.4.Drainvalve-ballvalvepreferable,gatevalveacceptable alternative (supplied by others). MinimumvalvesizeperASMEcodeis3/4"NPT.5. Swing joints on two riser systems may be piped over the top of the boiler if space is limited.6. Boilers require protection from flue gas condensation and thermal shockwhenoperatingbelow135°Freturnwatertemperatures
pipe Sizing and notes
BOILeRMODeL
SUppLy pIpInG SIZe In InCHeS ReTURn pIpInG SIZe In InCHeS
(1)SUppLy
(1A)SUppLy HeADeR
(1B) SUppLy RISeR
(QTy.) SIZe(2)
ReTURn
(2A)ReTURn HeADeR
(2B) ReTURn BRAnCH
(QTy.) SIZe20¡ FDROp
40¡ FDROp
20¡ FDROp
40¡ FDROp
20¡ FDROp
40¡ FDROp
20¡ FDROp
40¡ FDROp
20¡ FDROp
40¡ FDROp
20¡ FDROp
40¡ FDROp
V1104V1105V1106V1107V1108V1109V1110
2-1/22-1/22-1/2
3344
22222
2-1/22-1/2
ÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑ
2-1/22-1/22-1/2
3344
22222
2-1/22-1/2
ÑÑÑÑÑ33
ÑÑÑÑÑÑÑ
ÑÑÑÑÑ
(2) 3(2) 3
ÑÑÑÑÑÑÑ
V1111V1112V1113V1114V1115V1116V1117
4444455
2-1/2333333
ÑÑÑÑÑ33
ÑÑÑÑÑÑÑ
ÑÑÑÑÑ
(2) 3(2) 3
ÑÑÑÑÑÑÑ
4444455
2-1/2333333
3333333
ÑÑÑÑÑÑÑ
(2) 3(2) 3(2) 3(2) 3(2) 3(2) 3(2) 3
ÑÑÑÑÑÑÑ
V1118V1119V1120V1121V1122V1123
555555
444444
444444
ÑÑÑÑÑÑ
(2) 4(2) 4(2) 4(2) 4(2) 4(2) 4
ÑÑÑÑÑÑ
555555
444444
444555
333333
(3) 3(3) 3(3) 3(3) 3(3) 3(3) 3
(2) 3(2) 3(2) 3(2) 3(2) 3(2) 3
V11 Series Piping RecommendationsWater Boiler
5
nOTeS:1. Allpipingisschedule40.2. To prevent condensate from being trapped in header, do not reduce equalizer elbow at header connection.3. Drain/blowoffvalve—ballvalvepreferable,gatevalveacceptable alternative (supplied by others). -MinimumvalvesizeperASMEcodeis1"NPT(V1104-1106),1-1/4" NPT(V1107-1112),1-1/2"NPT(V1113-1123). - Increasing the valve size will improve the blowdown operation - In all cases, piping connecting blowoff valve to boiler shall be full size to the point of discharge.4. Headerpipingmayberunoverthetopofboilerifspacedoesnot allow for piping arrangement shown. However,increasedservicerequirementswillresult.5. Supply from boiler header must be connected between the first boiler riserandtheheaderdrip(orhartfordloop).Donotconnectsupply between risers or opposite end of boiler header.6. Forpumpedreturnsystems,seeV11installationmanual.
'A'
'A'
'B''C'
'A'
'B'
'C'
'A'
'B'
'C'
'D'
18"MIN.
24"MIN.
HEADER3
'E''D'
V1104 AND V1105
V1114 THRU V1117 V1118 THRU V1121 V1122 AND V1123
V1106 THRU V1109
'A''B'
V1 110 THRU V1113
EQUALIZER
CLOSE NIPPLE
HARTFORD LOOP(REQ'D ON GRAVITYRETURN SYSTEM)
4
RETURN2
BLOWOFF/DRAIN VALVE(SEE NOTE 3)
REAR OF BOILER
2" TO 4"WATER LINE
SUPPLY(SEE NOTE 5)
5
RISER1
BOILeRMODeL
pIpInG SIZe In InCHeS RISeR SpACInG In InCHeS(1)
RISeR (QTy.) SIZe
(2) ReTURn
(3)HeADeR
(4)eQUALIZeR ÔAÕ ÔBÕ ÔCÕ ÔD Õ Ô eÕ
V1104V1105V1106V1107V1108V1109V1110
(1) 4(1) 4(2) 4(2) 4(2) 4(2) 4(3) 4
22
2-1/22-1/22-1/22-1/22-1/2
4466666
2-1/22-1/22-1/22-1/22-1/22-1/22-1/2
ÑÑ
31-1/837-1/443-3/849-1/224-3/4
ÑÑÑÑÑÑ
30-7/8
ÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑ
V1111V1112V1113V1114V1115V1116V1117
(3) 4(3) 4(3) 4(4) 4(4) 4(4) 4(4) 4
3333333
8888888
4444444
373737
24-3/424-3/430-7/830-7/8
24-3/430-7/8
3724-1/224-1/236-3/436-3/4
ÑÑÑ
30-7/837
24-3/430-7/8
ÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑ
V1118V1119V1120V1121V1122V1123
(5) 4(5) 4(5) 4(5) 4(6) 4(6) 4
333333
81010101010
444444
30-7/830-7/830-7/830-7/830-7/830-7/8
24-1/224-1/224-1/224-1/224-1/224-1/2
24-1/224-1/236-3/436-3/424-1/224-1/2
24-3/430-7/824-3/430-7/824-1/224-1/2
ÑÑÑÑ
24-3/430-7/8
V11 Series Piping RecommendationsSteam Boiler
6
STANDARD BURNER MOTOR VOLTAGE: Beckett–CF1400,andCF2300are120/60/1.CF2500andCF3500are240/60/3.Carlin–Allsizes240/60/1.power Flame–CR1-OSis120/60/1.CR2-OASis240/60/1.Allothersare240/60/3.Webster–JB10-03,JB10-05andJB10-07are120/60/1.JB20-10is240/60/1.Allothersare240/60/3.
GAS BURneRS*
STANDARD BURNER MOTOR VOLTAGE: power Flame C Series–CR1-G-12andCR2-G-15are120/60/1.CR2-G-20Ais240/60/1.Allothersare240/60/3.power Flame JR Series –Allburnersare120/60/1.Webster–JB1G-03,JB1G-05andJB1G-07are120/60/1.JB2G-10is240/60/1.Allothersare240/60/3.*Forinletgasconnectionsize,seeGas/OilBurnerChart=Forminimumgaspressurerequirements,seeGas/OilBurnerChart.
GAS/OIL BURneRS
STANDARD BURNER MOTOR VOLTAGE: power Flame-CR1-GO-12is120/60/1.CR-2-GO-15andCR2-GO-20Aare240/60/1.Allothersare240/60/3.Webster–JB1C-03,JB1C-05,JB1C-07are120/60/1.JB2C-10is240/60/1.Allothersare240/60/3.**Forminimumgaspressurerequirements,seeGasBurnerChart.NOTES:1.TheminimumgaspressuresshownareforstandardULburnerswiththestandardfiringsequence.IRI,FMandCSD-1requirementsmayresultindifferentpressuresandprices.
BOILeRnUMBeR
BeCKeTT CARLIn pOWeR FLAMe WeBSTeRBURneR MODeL H.p. BURneR MODeL H.p. BURneR MODeL H.p. BURneR MODeL H.p.
V1104V1105V1106V1107V1108V1109V1110V1111V1112V1113V1114V1115V1116V1117V1118V1119V1120V1121V1122V1123
CF1400CF1400CF1400CF2300CF2300CF2300CF2300CF2300CF2500CF2500CF3500CF3500CF3500
ÑÑÑÑÑÑÑ
1/21/21/23/43/43/43/43/422222
ÑÑÑÑÑÑÑ
Ñ702CRD702CRD801CRD801CRD801CRD1050FFD1050FFD1050FFD1050FFD1150FFD1150FFD1150FFD1150FFD
ÑÑÑÑÑÑ
Ñ1/21/23/43/43/411
1-1/21-1/21-1/21-1/21-1/21-1/2
ÑÑÑÑÑÑ
CR1-OSCR1-OSCR2-OASCR2-OASCR2-OASCR2-OASCR2-OASCR3-OCR3-OCR3-OCR3-OCR3-OCR3-OCR3-OCR3-OBCR3-OBCR3-OBCR3-OBCR4-OACR4-OA
1/21/23/43/43/43/4
1-1/22222233333355
JB1O-03JB1O-03JB1O-03JB1O-05JB1O-05JB1O-07JB1O-07JB2O-10JB2O-10JB2O-10JB2O-10JB2O-10JB2O-15JB2O-30JB2O-30JB2O-30JB2O-30JB2O-50JB2O-50JB2O-50
1/31/31/31/21/23/43/411111
1-1/23333555
BOILeRnUMBeR
BeCKeTT pOWeR FLAMe - 'CR'= pOWeR FLAMe - 'JR'= WeBSTeRBURneRMODeL H.p.
MIn. GASpReSS. (In.)
BURneRMODeL H.p.
BURneRMODeL H.p.
BURneRMODeL H.p.
MIn. GASpReSS. (In.)
V1104V1105V1106V1107V1108V1109V1110V1111V1112V1113V1114V1115V1116V1117V1118V1119V1120V1121V1122V1123
CG10.6SCG10.6SCG15.4SCG25.2SCG25.3SCG25.4SCG25.5SCG50.2SCG50.3SCG50.3SCG50.4SCG50.5SCG50.5SCG50.5SCG50.5SCG50.5S
ÑÑÑÑ
1/31/31/23/43/43/43/4222222222
ÑÑÑÑ
4.66.66.25.25.05.25.25.74.35.75.75.05.36.16.97.3ÑÑÑÑ
CR1-G-12CR1-G-12CR2-G-15CR2-G-15CR2-G-15CR2-G-15CR2-G-20ACR3-G-20CR3-G-20CR3-G-20CR3-G-20CR3-G-20CR3-G-25CR3-G-25CR3-G-25BCR3-G-25BCR3-G-25BCR3-G-25BCR4-G-25CR4-G-25
1/31/21/21/21/21/21
1-1/21-1/21-1/21-1/21-1/2
33333333
JR30A-10JR30A-12JR50A-15JR50A-15JR50A-15
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
1/31/31/31/21/2ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
JB1G-03JB1G-03JB1G-03JB1G-05JB1G-05JB1G-07JB1G-07JB2G-10JB2G-10JB2G-10JB2G-15JB2G-30JB2G-30JB2G-30JB2G-30JB2G-30JB2G-30JB2G-50JB2G-50JB2G-50
1/31/31/31/21/23/43/4111
1-1/2333333555
64655888678889101112141516
BOILeRnUMBeR
pOWeR FLAMe - 'CR' SeRIeS WeBSTeRBURneRMODeL H.p.
InLeT GASCOnneCTIOn (In.)
MIn. GASpReSS. (In.)
BURneRMODeL H.p.
InLeT GASCOnneCTIOn (In.)
MIn. GASpReSS. (In.)
V1104V1105V1106V1107V1108V1109V1110V1111V1112V1113V1114V1115V1116V1117V1118V1119V1120V1121V1122V1123
CR1-GO-12CR1-GO-12CR2-GO-15CR2-GO-15CR2-GO-15CR2-GO-15CR2-GO-20ACR3-GO-20CR3-GO-20CR3-GO-20CR3-GO-20CR3-GO-20CR3-GO-25CR3-GO-25CR3-GO-25BCR3-GO-25BCR3-GO-25BCR3-GO-25BCR4-GO-25CR4-GO-25
1/21/23/43/43/43/4
1-1/22222233333355
11111
1-1/41-1/4
21-1/21-1/21-1/21-1/2
222
2-1/22-1/22-1/22-1/22-1/2
4.74.85.46.47.56.45.85.86.06.87.47.36.67.17.76.57.07.06.36.9
JB1C-03JB1C-03JB1C-03JB1C-05JB1C-05JB1C-07JB1C-07JB2C-10JB2C-10JB2C-10JB2C-10JB2C-10JB2C-15JB2C-30JB2C-30JB2C-30JB2C-30JB2C-50JB2C-50JB2C-50
1/31/31/31/21/23/43/411111
1-1/23333555
11-1/41-1/41-1/41-1/21-1/21-1/2
2222222
2-1/22-1/22-1/22-1/22-1/22-1/2
7.04.97.06.26.97.07.06.35.66.37.06.87.07.38.19.210.011.012.413.1
OIL BURneRS
V11 Series Burner Schedule
7
Specifications
1. Suffix“S”indicatessteamboiler,“W”indicateswaterboiler.Suffix“G”indicatesgas-fired,“O”indicatesoilfiredand“GO”indicatescombination gas/oil fired.2. Boilerratingsarebasedon13%CO2onoil;10.0%CO2ongas,and+.10in.watercolumnpressureatboilerflueoutlet.3. I=B=Rnetratingsshownarebasedonpipingandpickupallowanceswhichvaryfrom1.333to1.288forsteamand1.15forwater.Consult manufacturer for installations having unusual piping and pick up requirements, such as intermittent system operation, extensive piping systems, etc.4. TheI=B=RburnercapacityinGPHisbasedonoilhavingaheatvalueof140,000BTUpergallon.Ratingsshownaboveapplytoaltitudesupto1000feetforoiland2000feetforgas.Foraltitudesabovethoseindicated,theratingsshouldbereducedattherateof4%foreach1000feetabovesealevel.nOTe: Maximumallowableworkingpressure(MAWP): Steam: 15PSI Water–USA: 80PSI(Standardreliefvalveprovidedis50PSI)(80PSI/30PSIOptional) Water–Canada: 50PSI(Standardreliefvalveprovidedis50PSI)(30PSIOptional)
STAnDARD eQUIpMenTALL BOILeRS:Sectionsunassembled,flushinsulatedjacket,burnermountingplate,rearobservationportcover,firewallplates,targetwall(V1104-1106only), rear flue outlet damper (top outlet optional), flue canopy, trim, and miscellaneous plugs, bushing and fittingsSTeAM TRIM:15PSIsafetyvalve,L404Fpressuretrol,gaugeglassassembly,steamgaugeWATeR TRIM:50PSIsafetyreliefvalve,L4006Ahighlimit,pressuretemperaturegaugeOIL BOILeRS:Flangemountedflameretentionoilburnerfurnishedwith2stagefuelunit,primarycontrolanddualoilvalvesGAS BOILeRS:FlangemountedgasburnerwithstandardcontrolsmeetingthelatestULrequirements,dualgasvalves,gas-electricignitionwithprovengaspilot,flamerodonJRburner,ultravioletflamedetectoronothers,electronicprogrammingcontrolsandcomponentsarefactorywiredinaburnermountedcontrolpanel(exceptJR-panelavailableasanoption)GAS/OIL BURneRS:Flangemountedcombinationgas/oilburnerwithstandardcontrolsmeetinglatestULrequirements,manuallyoperatedfueltransferswitch for dual fuel changeover, dual gas valves and oil valves, electric ignition with proven gas pilot on both fuels (direct spark ignition of oil is op-tional), ultra-violet flame detector, electronic programming controls and components are factory wired in a burner mounted control panel
OpTIOnAL eQUIpMenTAssembled sections; completely packaged (includes manual reset high limit and manual reset low water cutoff); packaged and fire-tested; top outlet flue damper;tanklessheaters;sideinspectiontappingswithbrassplugs;pressurereliefdoor;30PSIand80PSIsafetyreliefvalves;combustionandhydroniccontrolstomeetspecialapplicationsincludingF.M.,I.R.I.,andASMECSD-1.
V11 RATInGS
BOILeRMODeL
(1)BOILeR
H.p.
GROSSOUTpUT
MBH(2)
I=B=R neT RATInG (3) BURneR InpUT neTFIReBOXVOLUMe(In. WTR.COLUMn)
pReSSUReIn
FIReBOX(In. WTR.COLUMn)
I=B=RVenT DIA.
(In.)
AppROX.SHIppInG
AnD LIFTInGWeIGHT(LBS.)
STeAM
WATeRMBH
OILGpH(4)
GASMBHMBH SQ. FT.
V1104V1105V1106V1107V1108V1109V1110
19.925.631.938.345.351.758.0
66785710691281151717291941
500643802963115913351507
2083267933424013482955636279
5807459301114131915031688
5.87.49.211.013.014.816.6
837106813281588187621362396
7.910.613.215.918.521.123.8
.35
.36
.37
.42
.42
.39
.42
88810101012
2105251029203325373341474557
V1111V1112V1113V1114V1115V1116V1117
64.369.774.881.688.393.4100.2
2154233425032730295731293353
1672181219432120229624272603
696775508096883395671011310846
1873203021772374257127182916
18.420.021.523.525.527.029.0
2656288731033392368038974186
26.529.131.834.437.139.742.4
.40
.42
.40
.38
.36
.38
.41
12121214141414
4964537457716184660170087417
V1118V1119V1120V1121V1122V1123
106.9111.7118.2124.7129.5136.0
358037393957417443344551
278029033072324133653533
115831209612800135041402114721
311332513441363037693957
31.032.534.536.538.040.0
447446914979526854855733
45.047.750.353.055.658.3
.39
.38
.38
.40
.41
.43
161616161818
782382318638905394569865
BurnhamCommercial-Lancaster,PA
www.burnhamcommercial.comPhone: �-888-791-3790
8