Post on 15-Jan-2016
description
Theme:Theme:
Power plant C&I (IPC) systems
&
Tending to Zero Forced Outage
by
Internalization of Best Practices
Presentation Outline:Presentation Outline:
1.Some definitions & basics of Pressure, Flow & Temp. measurement
2. Categorization of C&I systems based on location of application
3. Division of power plant C&I systems based on functionality & type of application
4.Evolution of C&I systems and latest trend in technology
5.NTPC at a glance and maintenance practices of C&I systems
6. Some case studies
Measurement: PressureMeasurement: Pressure
Outline: Some Definitions
Pressure Units
Manometers
Elastic Pressure Sensors
Electrical Pressure Sensors
Pressure Switches
Snubbers & Siphon Tubes
Measurement: PressureMeasurement: Pressure
Terminology Accuracy : Closeness with which an instrument reading
approaches the true value of the variable being measured.
Precision : A measure of reproducibility of the measurements; i.e. given a fixed value of a variable, precision is a measure of the degree which successive measurements differ from one another.
Sensitivity : The ratio of output signal or response of the instrument to a change of input or measured variable.
Resolution : The smallest change in measured value to which the instrument will respond.
Error : Deviation from the true value of the measured variable.
Measurement: PressureMeasurement: Pressure
Repeatability refers to the ability of a pressure sensor to provide the same output with successive applications of the same pressure.
Hysteresis is a sensor's ability to give the same output at a given pressure while increasing and decreasing the pressure.
Measurement: PressureMeasurement: Pressure
Pressure : Definitions Definition: Force per unit area
Absolute pressure
Atmospheric pressure
Differential pressure
Gauge pressure
Importance : Pressure measurement is critical for safe and optimum operation of processes such as steam generation, hydraulic equipment operation, air compression, vacuum processing etc.
Measurement: PressureMeasurement: Pressure
Zero Reference , Gauge, Absolute, Atmospheric Pressure
Any pressure above atmosphere is called gauge pressure Any pressure below atmosphere is a vacuum (negative gauge pressure) Absolute pressure (psia) is measured from a perfect vacuum
Differential Pressure has no reference to either absolute vacuum or atmospheric pressure
Measurement: PressureMeasurement: Pressure
Units
The SI unit for pressure is the Pascal (Pa);1Pa= 1 N·m-2
Non-SI unit pound (Lb) per square inch (psi) and bar are commonly used Pressure is sometimes expressed in grams-force/cm2or as kgf/cm2 (KSC)
1 atm=1.03 ksc=14.696 psi=760mmHg=10000 mmWC
=101325 Pa
Standard pressure:Pressure of normal (standard) atmosphere is defined as standard pressure
Measurement: PressureMeasurement: PressurePressurePressure Measuring devicesMeasuring devices
Manometers using water ,mercury and other liquids of known density For measuring low pressures.
Mechanical/Elastic Pressure Sensors Electrical Pressure Transducers
For measuring pressure of all ranges for telemetering purposes.
Manometer: A simple pressure standard
May be used for gauge, differential, and absolute measurements with a suitable reference.
Useful mainly for lower pressure work because the height of the column of mercury will otherwise become very high.
The difference in column heights gives the pressure reading
Measurement: PressureMeasurement: PressureElastic Pressure Sensors
The basic pressure sensing elements:
A: C-shaped Bourdon tube , B: Helical Bourdon tube , C: flat diaphragm
D: Convoluted diaphragm, E: Capsule , F: Set of bellows
Measurement: PressureMeasurement: Pressure
Electrical Pressure Sensors 1. Potentiometer Sensor
2. Inductive
3. Capacitive
4. Piezoelectric
5. Strain Gauge
Usually generate output signals in the mV range (spans of 100 mV to 250 mV).
In transmitters, these are amplified to the voltage level (1to 5 V) and converted to
current loops, usually 4-20 mA dc
Measurement: PressureMeasurement: Pressure
Pressure SwitchesApplications
• Alarm (Status)
• Shutdown (Hi/Lo Limits)
• Control (ON/OFF)
A “switch” is an instrument that automatically senses some process variable (such as pressure) and provides an on/off signal relative to some reference point.
Sensing Element
ConditioningCircuit
Bourdon TubeBellows
DiaphragmStrain Gauge
Mechanical Switch
Transistor
Set Point
Measurement: PressureMeasurement: Pressure
High Pressure In High Temperature
* When high process temperatures are present, various methods of isolating the pressure instrument from the process are used.
* These include siphons, chemical seals with capillary tubing for remote mounting, and purging.
Snubbers & its use Chemical Seal
Siphon
Measurement: PressureMeasurement: PressurePressure SnubbersPressure Snubbers
To filter out pressure spikes, or to average out pressure pulses, snubbers are installed between the process and the instrument
Instrument indicates avg pr.
Snubber Before use After use
when one is interested in the measurement of fast, transient pressures (such as to initiate safety interlocks on rising pressures), snubbers must not be used, as they delay the response of the safety system.
Measurement: PressureMeasurement: Pressure
Chemical Seal or diaphragm Protector Chemical seals are used when media can falsify the
pressure measurements due to high temperature, high viscosity or their property to crystallise
Measurement: PressureMeasurement: Pressure
Siphon A siphon is a coiled tube. This coil provides a large cooling surface and
the trap created prevents the condensate from draining away.
A siphon is required for hot condensing. fluids, such as steam, to assure a liquid trap.
It is used to prevent live steam from entering and damaging the device.
It is used to protect the instrument from hydraulic or thermal shocks.
The two most common forms of siphon tube are the 'U' and Pigtail types.
Measurement: FlowMeasurement: Flow
Types of flow meters:1. Orifice Flow meter
2. Vortex flow meter
3. Ultrasonics flow meter
4. Coriolis Mass Flow meter
5. Major issues for selecting flow meters
Orifice Flow-meters
Several sensors rely on the pressure drop or head occurring as a fluid flows by a
resistance. The relationship between flow
rate and pressure difference is determined
by the Bernoulli equation.
Measurement: FlowMeasurement: Flow
Orifice Flow-meters• An orifice plate is a restriction with an opening smaller than the pipe diameter
which is inserted in the pipe; the typical orifice plate has a concentric, sharp edged opening.
• Because of the smaller area the fluid velocity increases, causing a corresponding decrease in pressure.
• The flow rate can be calculated from the measured pressure drop across the orifice plate, P1-P3.
• The orifice plate is the most commonly used flow sensor, but it creates a rather large non-recoverable pressure due to the turbulence around the plate, leading to high energy consumption.
Measurement: FlowMeasurement: Flow
Venturi Tube
The change in cross-sectional area in the venturi tube causes a pressure change between the convergent section and the throat, and the flow rate can be determined from this pressure drop. Although more expensive that an orifice plate; the venturi tube introduces substantially lower non-recoverable pressure drops
Measurement: FlowMeasurement: Flow
Pitot Tubes Pitot tubes were invented by Henri Pitot in 1732 to measure the
flowing velocity of fluids. Basically a differential pressure (dp) flow meter, a pitot tube measures two pressures: the static and the total impact pressure.
Pitot tubes are used to measure air flow in pipes, ducts, stacks, and liquid flow in pipes, open channels.
While accuracy and rangeability are relatively low, pitot tubes are
simple, reliable, inexpensive, and suited for a variety of environmental conditions, including extremely high temperatures and a wide range of pressures.
Measurement: FlowMeasurement: Flow
Pitot Tubes A single-port pitot tube can measure the flow velocity at only a single point
in the cross-section of a flowing stream. The probe must be inserted to a point in the flowing stream where the flow
velocity is the average of the velocities across the cross-section, and its impact port must face directly into the fluid flow.
Measurement: FlowMeasurement: FlowPitot Tubes
The point velocity of approach (VP) can be calculated by taking the square root of the difference between the total impact pressure (PT) and the static pressure (P) and multiplying that by the C/D ratio, where C is a dimensional constant and D is density:
The pitot tube measures the static and dynamic (or impact) pressures of the fluid at one point in the pipe.
The flow rate can be determined from the difference between the static and dynamic pressures which is the velocity head of the fluid flow.
Measurement: FlowMeasurement: Flow
Vortex Flow-meters This measuring principle is based on the fact that vortices are
formed downstream of an obstacle in a fluid flow, e.g. behind a bridge pillar.
This phenomenon is commonly known as the Kármán vortex street.
Measurement: FlowMeasurement: Flow
Vortex Flow-meters
This is detected by a sensor, such as capacitive sensor and fed to the electronic processor as a primary, digitized, linear signal.
Capacitive sensors with integrated temperature measurement can directly register the mass flow of saturated steam as well.
Universally suitable for measuring liquids, gases and steam Largely unaffected by changes in pressure, temperature and
viscosity High long-term stability (lifetime K factor), no zero-point drift No moving parts Marginal pressure loss
Measurement: FlowMeasurement: Flow
Ultrasonic flow-meters Swimming against the flow requires more power and more time
than swimming with the flow. Ultrasonic flow measurement is based on this elementary transit time difference effect.
Two sensors mounted on the pipe simultaneously send and receive ultrasonic pulses.
At zero flow, both sensors receive the transmitted ultrasonic wave at the same time, i.e. without transit time delay.
When the fluid is in motion, the waves of ultrasonic sound do not reach the two sensors at the same time.
Measurement: FlowMeasurement: Flow
Ultrasonic flow-meters
This measured "transit time difference" is directly proportional to the flow velocity and therefore to flow volume.
By using the absolute transit times both the averaged fluid velocity and the speed of sound can be calculated.
Ultrasonic flow meters measure the difference of the propagation time (transit time) of ultrasonic pulses propagating in (normally an inclination angle around 30 to 45° is used) flow direction and against the flow direction.
This time difference is a measure for the averaged velocity of the fluid along the path of the ultrasonic beam
Measurement: FlowMeasurement: Flow
Ultrasonic flow-meters
Advantages: With homogeneous fluids, the principle is independent of
pressure, temperature, conductivity and viscosity
Usable for a wide range of nominal diameters Direct meter installation on existing pipes
Non-invasive measurement
No pipe constrictions, no pressure losses
No moving parts. Minimum outlay for maintenance and upkeep
Measurement: FlowMeasurement: FlowCoriolis Mass Flow-meters
If a moving mass is subjected to an oscillation perpendicular to its direction of movement, Coriolis forces occur depending on the mass flow.
A Coriolis mass flow meter has oscillation measuring tubes to precisely achieve this effect.
Coriolis forces are generated when a fluid (= mass) flows through these oscillating tubes. Sensors at the inlet and outlet ends register the resultant phase shift in the tube's oscillation geometry.
Measurement: FlowMeasurement: Flow
Coriolis Mass Flow-meters The processor analyzes this information and uses it to
compute the rate of mass flow.
Advantage
This principle is used in a huge range of industry sectors, including pharmaceuticals, chemicals and petrochemicals, oil and gas, food etc.
Measurement: FlowMeasurement: Flow
Major issues for selecting flow-meters
Accuracy
Repeatability
Linearity
Reliability
Range/Span
Dynamics(Response time)
Safety
Maintenance
Cost
Measurement: Temp.Measurement: Temp.
Measurement Devices
Thermocouples
Resistance Thermometers
Thermistors
Bimetallic Thermometers
Acoustic Pyrometers
Local Instruments
Measurement: Temp.Measurement: Temp.
Thermocouple IT IS BASED ON ‘SEEBECK’ EFFECT WHICH SAYS THAT
WHEN HEAT IS APPLIED TO A JUNCTION OF TWO DISSIMILAR METALS AN ‘EMF’ IS GENERATED WHICH CAN BE MEASURED AT THE OTHER JUNCTION
T/C Connection
COMPENSATING CABLE
HOT JUNCTION
TO DDC CARDS
TERMINAL END CJC BOX
Measurement: Temp.Measurement: Temp.Thermocouple
Types of T/C:E,J,K,T,R,S,B
K (Chromel & Alumel; Ni-Cr &Ni-Al) Type: mostly used in power plant for low temp. application )
R (Platinum & Platinum-Rhodium) Type: Used for high temp. application. Highly resistant to oxidation & corrosion
Advantages: - Disadvantages: - - Low Cost - Sensitivity low & low voltage output
- No moving parts, less likely to be broken. susceptible to noise
-Wide temperature range. - Accuracy not better than 0.5 °C
-Reasonably short response time. - Requires a known temperature
- Reasonable repeatability and accuracy. reference
Measurement: Temp.Measurement: Temp.
RESISTANCE THERMOMETER (RTD) THE RESISTANCE OF A CONDUCTOR CHANGES WHEN ITS TEMPERATURE IS
CHANGED .THIS PROPERTY IS UTILISED TO MEASURE THE TEMPERATURE.
Rt = Ro (1+βdT)
WHERE β = TEMP CO- EFFICIENT OF RESISTANCE ; dT = TEMPERATURE DIFFERENCE
When discussing RTDs, following must be considered:• Wiring configuration (2, 3 or 4-wire) • Self-heating • Accuracy RTD types:• Stability 1. Platinum (Range -200 °C to 600 °C )• Repeatability 2. Copper (Range -100 °C to 100 °C ) • Response time 3. Nickel (Range -60 °C to 180 °C )
Measurement: Temp.Measurement: Temp.THERMISTORS
THERMISTORS ARE GENERALLY COMPOSED OF SEMICONDUCTOR MATERIALS.THEY HAVE A NEGATIVE COEFFICIENT OF TEMPERATURE SO RESISTANCE DECREASES WITH INCREASE IN TEMP.
Making use of Negative Temperature Coefficient characteristics, thermistor and can be applied in temperature compensation, inrush current limit, precision temp. control (temp. coefficient very large compared to RTC & T/C) etc.
BIMETALLIC THERMOMETERS ALL METALS EXPAND OR CONTRACT WITH TEMPERATURE THE TEMPERATURE COEFFICIENT OF EXPANSION IS NOT THE SAME FOR ALL
METALS AND SO THEIR RATES OF EXPANSION AND CONTRACTION ARE DIFFERENT
USAGE: IN PROCESS INDUSTRIES FOR LOCAL TEMPERATURE MEASUREMENTS OVERLOAD CUTOUT SWITCH IN ELECTRICAL APPARATUS
Measurement: Temp.Measurement: Temp.ACOUSTIC PYROMETER
Acoustic Pyrometer is a non-contact measurement device that obtains highly accurate instantaneous gas temperature data in any area of the boiler, helping improve combustion efficiency.
For measurement of temperatures across large spaces of known distance in a noisy, dirty and corrosive environment such as a coal-fired utility boiler, or a chemical recovery boiler.
The Velocity of Sound in a medium is proportional to the Temperature.
LOCAL INDICATION
LIQUID IN GLASS THERMOMETER
MERCURY IN STEEL THERMOMETER
BIMETALLIC THERMOMETER
Power Plant C&I systemsPower Plant C&I systems
1.Field instruments/ input & output instruments
a) Various measuring instruments like Transmitters, RTD, Thermocouples, Pr. & temp. gauges, speed & vibration pick ups etc. (Analog inputs)
b) Various Pr., Temp. & limit switches, for Interlock , protections & feedback of control element (Binary inputs)
c) Output devices like solenoids, EP converters, Positioners etc. for controlling final control element
d) Final control elements like Power cylinder, Pneumatic/ motorized actuators etc.
Power Plant C&I systemsPower Plant C&I systems
2. Control Systemsa) Various control cabinets for acquiring field signal (both analog
& binary inputs), processing the signals as per control logic and issuing output command to output devices (Binary & analog).
b) Various control desk devices like command consoles, Push button modules, indicators, recorders, CRTs, PC based Operator Work Stations (OWS) etc. for human machine interface for monitoring & control of the plant
c) Power supply system(UPS)/ chargers with battery backups to ensure uninterrupted power supply of desired quality for the control system
Power Plant C&I systemsPower Plant C&I systems3. Analyzers The availability, reliability & efficiency of boiler unit hinge around the
close control of chemical regimes of working fluid i.e. water/steam as well as combustion in the boiler. The instruments monitoring the chemical regimes and combustion are generally called analytical instruments. These instruments fall under three category
i) Water/ Steam Analyzers
ii) Gas analyzers
iii) Smoke monitors
HIGH PURITY WATER IS ESSENTIAL TO MINIMISE SCALING CORROSION CARRY OVER EMBRITTLEMENT
Power Plant C&I systemsPower Plant C&I systems
ANALYZERS AND MEASURMENT LOCATION
a) ON LINE gas analyzers for measurement of flue gas oxygen, carbon mono-oxides, carbon di-oxides, oxides of sulpher & nitrogen at various location of boiler.
b) ON LINE analyzers for measurement of conductivity, pH, silica, dissolved oxygen, phosphate, hydrazine, chloride, sodium etc. at various points in the water & steam cycle of boiler & turbine area (SWAS-steam & water analysis system).
c) ON-LINE opacity monitors for measurement of dust concentration in flue gas
d) ON LINE analyzers for measurement of conductivity, pH, silica, dissolved oxygen etc. at various ION exchangers of DM plant .
Power Plant C&I systemsPower Plant C&I systems
TYPICAL VALUES OF CHEMICAL PARAMETERS BEING MEASURED (SWAS)TYPICAL VALUES OF CHEMICAL PARAMETERS BEING MEASURED (SWAS)
SAMPLE PARAMETER UNIT LIMIT
DM WATER a) Conductivityb) Cation Conductivity µS/cm
<0.3
Condensate pump discharge (CEP)
a) Conductivityb) Cation Conductivity µS/cm <5
<0.3
c) pH 9.0-9.2
d) Na+ ppb <5ppb
e) Dissolve oxygen (DO) ppb <10
Economizer Inlet
a) Conductivityb) Cation Conductivity µS/cm <5
<0.3
c) Hydrazine ppb 10-20
Boiler water a) Conductivity µS/cm 100
b) pH 9.1-9.4
c) Silica ppb 100Sat & Main steam a) Conductivity
b) Cation Conductivity µS/cm <5<0.3
Power Plant C&I systemsPower Plant C&I systems
4. Laboratory Instruments & Setup
Activities of C&I Lab
CALIBRATION
REPAIR
TESTING with proper documentation & records
CALIBRATION: Pressure switch , Transmitter , Gauge
Temperature switch , Transmitter , Gauge
Flow Transmitter
Level Switch
Power Plant C&I systemsPower Plant C&I systems
4. Laboratory Instruments & SetupREPAIR:
1. ELECTRONIC CARDS
3. POWER SUPPLY MODULES
TESTING:1. ELECTRONIC MODULES
2. RELAYS
3. POWER SUPPLY MODULES
Power Plant C&I systemsPower Plant C&I systems
4. Laboratory Instruments & Setupa) Different standard instruments with traceability up to national
standard . These insts. include Standard Gauges, Multimeters, Resistance boxes, mA sources, oscilloscope, signal generator etc. for calibration of measuring instruments.
b) Dead Weight tester, Comparator, Temperature bath, Vacuum pump, manometer, soldering stations etc.
c) Test benches with standard power supply sockets (e.g. 24VDC, 48VDC, 220VDC, 110VAC, 230VAC etc.) in each bench depending on requirement.
d) Laboratory should be air-conditioned with monitoring of temp., humidity and barometric pressure. Also, proper provision for handling electronic cards (floor mats, ESD protective bags/ anti static bags etc.)
Power Plant C&I systemsPower Plant C&I systems
4. Laboratory Instruments & Setup
Essential Tools/ Infrastructure for Repairing & testing1. IN-CITCUIT IC TESTER2. ESD WORK STATION3. ULTRASONIC CARD CLEANER4. STORRAGE OSCILLOSCOPE5. LOGIC ANALYSER6. THERMOCOUPLE SIMULATOR7. VIDEO PATTERN GENERATOR8. EPROM PROGRAMMER
Power Plant C&I systemsPower Plant C&I systems
C&I systems of Boiler
- FSSS (Furnace safeguard supervisory system)
- Open loop control system (interlock & protections) of boiler auxiliaries
- Secondary Air Damper control system (SADC)
- Hydrastep for drum level measurement
- Measurements, Protection & Control of Coal Feeders
Power Plant C&I systemsPower Plant C&I systems
FSSSFUNCTIONS OF F.S.S.S
1. FURNACE PURGE SUPERVISION
2. OIL GUNS ON/OFF CONTROL
3. PULVERISERS/FEEDERS ON/OFF CONTROL
4. SECONDARY AIR DAMPERS CONTROL
5. FLAME SCANNER INTELLIGENCE
6. BOILER TRIP PROTECTIONS
Power Plant C&I systemsPower Plant C&I systems
FSSS WHY AT ALL A PROTECTIVE SYSTEM IS REQUIRED FOR THE
BOILER?
THE BOILER’S FURNACE IS CONTINUOUSLY FED WITH HIGH CALORIFIC VALUE ATOMISED FUEL WHICH IS IN THE PROCESS OF CONTINUOUS BUT CONTROLLED COMBUSTION.
COMBUSTION-THE PROCESS COMBUSTION IS A RAPID BURNING OF OXYGEN WITH FUEL RESULTING IN
RELEASE OF HEAT. AIR IS ABOUT 21% OXYGEN AND 78% NITROGEN BY VOLUME. MOST FUELS CONTAIN CARBON, HYDROGEN AND SULPHUR. A SIMPLIFIED COMBUSTION PROCESS COULD BE
CARBON+OXYGEN=CARBONDIOXIDE+ HEAT HYDROGEN+DO =WATER VAPOUR + HEAT SULPHUR +DO =SULPHURDIOXIDE+ HEAT WHICH MEANS THAT THE FINAL DESIRED PRODUCT OF THE PROCESS IS
HEAT WHICH WE REQUIRE TO BOIL THE WATER
Power Plant C&I systemsPower Plant C&I systemsFSSS
COMBUSTION-THE PROBLEM : WHEN THIS CONTROLLED BURNING GOES
OUT OF CONTROL DUE TO AN IMBALANCE IN THE FUEL/AIR RATIO, THERE IS EITHER A FUEL RICH MIXTURE OR A FUEL LEAN MIXTURE. IN BOTH CASES THE FLAME QUALITY BECOMES POOR. THERE IS A CHANCE OF FUEL ACCUMULATION WHICH CAN LATER ON IGNITE SUDDENLY AND CAUSE EXPLOSIONS.
SO FSSS IS USED FOR SAFE AND ORDERLY STARTUP AND SHUTDOWN OF BOILER THROUGH VARIOUS INTERLOCKS AND PROTECTIONS
THE PROTECTIVE SYSTEM IN THE BOILER IS DESIGNED BASICALLY TO PREVENT OCCURRENCE OF SUCH SITUATIONS BY TAKING ADVANCE ACTIONS.
Power Plant C&I systemsPower Plant C&I systems
N.F.P.A Guide line & Boiler Protection N.F.P.A- National Furnace Protection Association,
USA
Deals with protection for various types of furnace Protection of Pulverized fuel fired boiler is governed by
Section-85c
Different categories of protection:
a) Mandatory, b)Mandatory & automatically generated, c) Optional but alarm has to be there
Power Plant C&I systemsPower Plant C&I systems
BOILER FLAME & FLAME SCANNERS
It looks rather static, but in reality the fire energy
fluctuates rapidly. The Fuel and Oxygen in the uncontrolled fire constantly burn as in small explosions and then sucks new Fuel & Oxygen to the flames. This process causes the flame flicker.
Flicker frequency for oil
flame is more than that of coal flame.
Power Plant C&I systemsPower Plant C&I systems
INTENSITY RELATIVE TO WAVELENGTH
Power Plant C&I systemsPower Plant C&I systems
FLAME SCANNERS
-UV Scanners
-Visible Range Scanners (Safe scan-1&2)-Used for both Oil & Coal Flame
-IR Scanners (UR600 of ABB)
SAFE FLAME SCANNER
Power Plant C&I systemsPower Plant C&I systems
C&I systems of Turbine
- ATRS (Automatic Turbine Runup system)- Turbine Governing System
- Turbovisory Instruments & turbine protections
- Interlock, Protection & Control of HPBP system
- Open loop control system (interlock & protections) of turbine auxiliaries
- Interlock & protections of Seal Oil & Stator water system
Power Plant C&I systemsPower Plant C&I systems
C&I systems for control & MIS-Automatic Control System (ACS)
-DATA Acquisition system(DAS)
-Distributed Digital Control Monitoring
and Information System
Power Plant C&I systemsPower Plant C&I systemsAUTOMATIC CONTROL SYSTEM & POWER PLANT CONTROL LOOP
PROCESS: Process refers to the method of changing or refining raw materials to create the desired end product. The raw materials may undergo physical, chemical, or thermal state changes during the Process.
Process is of Two Types :
A) Continuous and B) Batch
Continuous Process is one where the change of state of Input into Output occurs continuously.
Ex.: Power Plant Process, Petroleum Industry etc.
Batch Process is one where a Batch of the Product is produced and the Process stops till production of next Batch is started.
Ex.: Automobile Production
Power Plant C&I systemsPower Plant C&I systemsAUTOMATIC CONTROL SYSTEM & POWER PLANT CONTROL LOOP
PROCESS CONTROL: Process control techniques are developed over the years to have
Quality of the end product Economy of production Ability to cater to emergencies and bring the process to safe shutdown.
CONTROLLED CONDITION: The physical quantity or condition of a process or machine which is to be controlled
CONTROL SYSTEM: An arrangement of elements interconnected and interacting in such a way that it can maintain some condition of a process or machine in a prescribed manner
Power Plant C&I systemsPower Plant C&I systemsAUTOMATIC CONTROL SYSTEM & POWER PLANT CONTROL LOOP
OPEN AND CLOSED LOOP CONTROL:
A Closed Loop Control (CLCS) is one where a Process Variable is measured, compared to a Set Value and action is taken to correct any Deviation or Error from Set Value. The continuous Measurement of PV and its’ comparison to Set Point closes the Loop.
An Open Loop Control(OLCS) is one where the PV is not compared with Set Value and action taken, but action is taken without regard to conditions of PV.
Power Plant C&I systemsPower Plant C&I systems
AUTOMATIC CONTROL SYSTEM & POWER PLANT CONTROL LOOP
OPEN LOOP CONTROL:
Open Loop Control is accomplished by the following means:
Group Control Sub-Group Control Sub-Loop Control Drive Level Control Programmable Logic Control(PLC)
Group Control : Start and Stoppage of a Group of equipment is accomplished by Group Control(GC).
Ex. :CEP GC, Equipment Cooling GC etc.
Power Plant C&I systemsPower Plant C&I systems
AUTOMATIC CONTROL SYSTEM & POWER PLANT CONTROL LOOP
OPEN LOOP CONTROL:
Sub-Group Control : Start and Stoppage of an equipment with its’ associated auxiliaries in Step-Sequence manner is done by Sub-Group Control. Operator intervention is not required in Sub-Group Control(SGC).
Sub-Loop Control: Start and Stoppage of auxiliaries of an equipment is carried out by Sub-Loop Control(SLC)
Drive Level Control : Start and Stop or Opening and Closure of a Drive is carried out by Drive Control. The Drive logic shall have Protection, release ,auto and manual commands and these are executed as per pre-determined logic.
Power Plant C&I systemsPower Plant C&I systemsAUTOMATIC CONTROL SYSTEM & POWER PLANT CONTROL LOOP
CLCS TERMINOLOGY: Desired Value or Set Point : The value of the variable/parameter which needs
to be controlled at the required condition.
Process Variable(PV) : The present value of the Parameter of Process at that particular instant. This is sometimes referred as Measured Value.
Error/Deviation : It is the Difference between Set Point and Process Variable, and can be +ve or –ve. It has three components: a) Magnitude b) Duration and c) Rate of change.
Controller : A Controller is a device that receives data from a Measurement Instrument, compares the data with the Set Point and if necessary, signals a Control element to take Corrective action. This Corrective action ensures that the PV shall always be maintained at the Set Value.
The Controller can be a) Electronic, b) Pneumatic and c) Hydraulic type.
Power Plant C&I systemsPower Plant C&I systemsAUTOMATIC CONTROL SYSTEM & POWER PLANT CONTROL LOOP
Controller types: Functionally, Controllers can be a) Continuous and b) Step Controllers.
Depending on the control loop; controller action can be adjusted as (i) Direct acting:-Increase of process value increases controller output
(ii) Reverse acting:- Increase of process value decreases controller output
Control Element : The Control or Correcting Element is the part of
the Control System that acts to physically change the Manipulated Variable.
Ex. : Control Valves, Louvers or Dampers, Solenoids, Pump Motors etc.
Power Plant C&I systemsPower Plant C&I systemsAUTOMATIC CONTROL SYSTEM & POWER PLANT CONTROL LOOP
Bump less Transfer : The arrangement where the transfer from auto to manual mode does not affect the process.
Proportional Control : The Proportional (P) action responds only to a change in the magnitude of Error(e) i.e. controller output changes by an amount which is proportional to error.
Output change of Controller in % = (Error change in %)(Gain), where Gain is called the Controller gain. The reciprocal of Gain is termed as Proportional Band(PB) and is expressed in %.
Proportional Band(PB): The change in deviation required to cause the output of the controller to change from one extreme to the other.
Integral Control : In Integral Control, the Controller output is a function of the Duration of Error(e).
Power Plant C&I systemsPower Plant C&I systems
AUTOMATIC CONTROL SYSTEM & POWER PLANT CONTROL LOOP
Hence, the Controller output is the time Integral of Error and the time set is Integral Action Time(IAT) i.e. IAT can be defined as time taken for the integral action to change output by the same amount as the proportion action .
Usually, both P and I Controls are combined and the Controllers are tuned to minimize Error(e) and controller is termed as PI controller.
Derivative Control : Derivative or Rate Controller’s output is Proportional to the rate of change of Error(e). The Control action is termed as D. The action is to apply an immediate response that is equal to the P+I action that would have occurred some time in the future.
Power Plant C&I systemsPower Plant C&I systems
AUTOMATIC CONTROL SYSTEM & POWER PLANT CONTROL LOOP
Important Closed Loop Controls in a Thermal Power Plant:
a) Furnace Draft Control
b) Boiler Drum Level Control
c) HOT well & D/A level control
d) Main Steam Temperature Control
e) Air and Fuel Flow to Boiler Control
f) SH & RH spray control
g) Coordinated Master Control(CMC)
h) Turbine Speed, Pressure and Load Control
Power Plant C&I systemsPower Plant C&I systems
AUTOMATIC CONTROL SYSTEM & POWER PLANT CONTROL LOOP
Coordinated Master Control
This is an integrated automatic control of unit operation. There is a continuous co ordination between boiler and turbine control to maintain a balance between steam generation and steam consumption.
• Boiler Follow Mode (BFM)
• Turbine Follow Mode (TFM)
• Co-ordinated Master Control (CMC)
• Runback Mode
Power Plant C&I systemsPower Plant C&I systems
AUTOMATIC CONTROL SYSTEM & POWER PLANT CONTROL LOOP
Boiler Follow Mode (BFM)
• Unit load control from turbine local load set point
• Change in turbine load set point will modulate turbine CVs
• Boiler master output gets corrected to maintain throttle pr dev.
• Boiler control will follow turbine control
• BLI signal as feed forward signal for boiler firing rate control
• Result - Boiler acts as throttle pr controller where turbine is in load controller mode
Power Plant C&I systemsPower Plant C&I systems
AUTOMATIC CONTROL SYSTEM & POWER PLANT CONTROL LOOP
Turbine Follow Mode (TFM)
• Unit target load set point goes to boiler master
• Change in BLI will modulate turbine CVs
• Boiler master output gets corrected to maintain Unit load dev.
• Turbine control will follow boiler control
• Load deviation as feed orward signal for boiler firing rate control
• Result - Boiler acts as load controller where turbine is in pressure controller mode
Power Plant C&I systemsPower Plant C&I systemsAUTOMATIC CONTROL SYSTEM & POWER PLANT CONTROL LOOP
Coordinated Master Control
• Unit load is set from unit master.
• Unit master demand is limited by unit capability , TSE margins and unit max/min load set points.
• Unit target load is derived from unit master after the limitations.
• Unit target load is used as feed forward signal to the boiler firing rate control.
• Turbine control utilises the unit load as turbine load set point after adapting the same by steam generation delay.
• In TG throttle pressure is maintained by correcting the BMD output depending on the throttle pr dev.
• Result: Balance is achieved between steam generation and steam consumption PROPER COORDINATION BETWEEN BOILER CONTROL AND TURBINE CONTROL
Power Plant C&I systemsPower Plant C&I systems
DATA ACQUISITION SYSYTEM-DAS
WHY DAS IS REQUIRED IN THERMAL POWER PLANTS ?
SAFE & RELIABLE OPERATION OF THE UNIT OR EQUIPMENTS
ASSIST CONTROL ROOM OPERATORS BY PROVIDING TIMELY ANNUNCIATION OF ALL ABNORMAL CONDITIONS
PROVIDE DETAILED INFORMATION ON THE PLANT PERFORMANCE
PROVIDE MANAGEMENT WITH ACCURATE RECORDS ON THE PAST PLANT PERFORMANCE FOR ANALYSIS
Power Plant C&I systemsPower Plant C&I systems
DATA ACQUISITION SYSYTEM
3 MAJOR FUNCTIONS OF DAS:
DATA ACQUISITION
DATA PROCESSING
DATA REPRESENTATION
The Major Parts
Process Control Units ( PCU ) Computer Interface Unit ( CIU ) Termination Units ( TU ) Buffer Terminal Cabinets ( BTC )
Power Plant C&I systemsPower Plant C&I systems
DATA ACQUISITION SYSYTEMTYPES OF DATA (Input): Analog & Digital
Analog inputs: 1. Thermocouple Input ( mV )
K-Type T/C ( Cr-Al ) : For temp < 600 Deg C& used in Flue Gas path after FSH outlet.
R-Type T/C ( Pt-Pt-Rh ) : For temp > 600 Deg C used in PSH & FSH region of FG path.
2. RTD Input ( Resistance ) Pt-100 RTD : For Brg. Temp measurement. Cu-53 RTD : For HT motor & Generator Stator winding temp.
measurement.
Power Plant C&I systemsPower Plant C&I systems
DATA ACQUISITION SYSYTEM
Analog inputs: 3. 4 – 20 Ma Input
Coming from Pr. / Flow Transmitters. Coming from Signal Distribution Cards of automatic
control system 4. 0 – 10 Volt Input Coming from ATRS cabinets Used for Turbine Brg. Temp. /Vibration measurement.
DIGITAL INPUTS These are coming directly from switches or relay contacts of
other systems (FSSS, ATRS, ACS etc.)
Power Plant C&I systemsPower Plant C&I systems
DATA ACQUISITION SYSYTEM
DIGITAL INPUTS (TYPES)
LOW RESOLUTION : The scanning time of inputs is 1 second.
HIGH RESOLUTION : The scanning time is 1 millisecond. These are called Sequence Of Events ( SOE ) Inputs.
PULSE INPUT : For calculation of Total Coal Flow, Total Air Flow etc.
Power Plant C&I systemsPower Plant C&I systems
DATA ACQUISITION SYSYTEM
FUNCTIONS OF DAS: Alarm Management.Alarm Management. Production of hardcopy print outs in different Production of hardcopy print outs in different
printers.printers. Operator Guidance Messages.Operator Guidance Messages. Graphic Displays of plant sub-systems.Graphic Displays of plant sub-systems. Trending of analog variables on recorders.Trending of analog variables on recorders. Sequence Of Events ( SOE ) recording following Sequence Of Events ( SOE ) recording following
unit / equipment trip conditions.unit / equipment trip conditions. Efficiency calculationsEfficiency calculations
Power Plant C&I systemsPower Plant C&I systemsDATA ACQUISITION SYSYTEM
DATA PROCESSING: It has the following parts
COMPUTER PROCESSING UNIT ( CPU )
BULK ( SOLID STATE ) MEMORY WITH BATTERY BACKUP
MAGTAPE UNIT
COMMUNICATION CABINET & MODEM
MOVING HEAD DISC DRIVE
VIDEO HARD COPIER
TREND RECORDER
UNIT CONTROL DESK & PROG. ROOM CRT
PRINTERS
Power Plant C&I systemsPower Plant C&I systemsDATA ACQUISITION SYSYTEM
Features:
REAL TIME VARIABLE CALCULATION Summing, Subtraction, Maximum , Minimum, Averaging,
Hourly & Daily integration, rate of changes & comparison of limits etc.
ON-LINE DATABASE EDITION 1. Assign points to any process parameter 2. Scan, Off-scan , Delete , Activate , inactivate a process parameters , calculated points when reqd.3. Change the Engg. Unit4. Change the range , alarm limits & dead bands5. Change the scan frequency6. Review total analog and digital points depending on its quality flag like alarm , channel failure , off-scan etc.
Power Plant C&I systemsPower Plant C&I systems
DATA ACQUISITION SYSYTEM
ALARM MANAGEMENT: All the analog points which cross their normal limits or all the
digital points which go into their alarm state come on the alarm CRT with associated time & blink as long as the alarms remain unacknowledged.
Alarm will come in RED colour
If all the pages are full (normally no. of alarm pages & alarm per page is predefined) and any new alarm comes , then oldest alarm will disappear from the alarm page as FIFO basis
Alarm print out will be available in alarm printer
Power Plant C&I systemsPower Plant C&I systems
DATA ACQUISITION SYSYTEM
DATA REPRESENTATION:
Printed outputs of displays /collection of data in different formats like :1. Copy Screen2 Alarm Print out3. Log Print out
CRT Displays1. Alarm CRT display2. Utility CRT display
Power Plant C&I systemsPower Plant C&I systems
DATA ACQUISITION SYSYTEM
DATA REPRESENTATION:
TYPES OF TREND LOG PRINOUTS
TIME ACTIVATED
EVENT ACTIVATED
DEMAND LOGS
SOE PRINTOUT
TIME ACTIVATED LOG: Automatic Triggered Logs Sample frequency is 1 Hour.(Normally) Time of trigger can be specified
Power Plant C&I systemsPower Plant C&I systems
DATA ACQUISITION SYSYTEM
TIME ACTIVATED LOG:
Max. 15 nos. of points can be assigned Normally printed in the logging printer in UCB Examples :
1. Shift Log2. Efficiency Log3. Boiler Drum / Tube Metal Temp. Log4. FSH / RH Metal temp. excursion Log
EVENT ACTIVATED LOG: Automatic Triggered Logs Used for Unit or Equipment Outage Analysis Minimum Sample frequency is 10 seconds.
Power Plant C&I systemsPower Plant C&I systems
DATA ACQUISITION SYSYTEM
EVENT ACTIVATED LOG: Max. 36 points can be assigned in a log Logs are triggered by a Trip flag Normally printed on Logging Printer in UCB Pre & Post triggered points can be specified Examples :
1. Post Trip Analysis Log ( PTL ) 2. TG. Shutdown Analysis Log 3. Boiler Startup Log. 4. Turbine / Generator Diagnostic Logs
Power Plant C&I systemsPower Plant C&I systems
DATA ACQUISITION SYSYTEM
DEMAND LOG:
Not Automatic Triggered Logs
Logs can be printed on operator’s demand
Sample frequency is generally 1 Hour.
Logs are printed in Logging Printer in UCB
Power Plant C&I systemsPower Plant C&I systems
DATA ACQUISITION SYSYTEM
SEQUENCE OF EVENTS ( SOE )
THE MAIN FEATURES ARE:
Determines First Cause Of Trip
Determines sequence of events or alarms
Scanning Time is 1 millisecond.
It is a Stand Alone System
Max. 256 nos. of Protection related digital points can be
assigned
Automatic Triggered when any point in alarm
Power Plant C&I systemsPower Plant C&I systems
DDCMIS
WHAT IS DDCMIS ?
DISTRIBUTED DIGITAL CONTROL MONITORING &
INFORMATION SYSTEM
Distributed means there is no centralized control and control is spread across multiple units
Digital means processing of process information is done in digital form using micro-processor based hardware
MIS interfaces the human with process using computers
Power Plant C&I systemsPower Plant C&I systems
DDCMISTECHNOLOGICAL BACKGROUND
PROGRESS OF INSTRUMENTATION USED TO IMPLEMENT AUTOMATIC PROCESS CONTROL
LOCAL PNEUMATIC CONTROLLERS
MINIATURIZED AND CENTRALIZED PNEUMATIC CONTROLLERS
AT CONTROL PANELS AND CONSOLES
SOLID-STATE CONTROLLERS
COMPUTERISED CONTROLS
DISTRIBUTED MICROPROCESSOR BASED CONTROL
Power Plant C&I systemsPower Plant C&I systems
DDCMIS
Components
MAN MACHINE INTERFACE & PROCESS INFORMATION SYSTEM
DATA COMMUNICATION SYSTEM (DATA HIGH WAY)
CONTROL SYSTEM
Power Plant C&I systemsPower Plant C&I systems
DDCMIS
MAN-MACHINE INTERFACE AND PLANT INFORMATION SYSTEM (MMIPS)
LATEST STATE-OF-THE-ART WORKSTATIONS AND SERVERS BASED ON OPEN-ARCHITECTURE AND INDUSTRY STANDARD HARDWARE AND SOFTWARE TO ENSURE BETTER CONNECTIVITY.
e.g. HARDWARE FROM COMPAQ/DIGITAL, HP, SUN MICRO-SYSTEM OR OTHER MAJOR SUPPLIERS (LESS DEPENDENCE ON THE C&I SYSTEM SUPPLIER IN THE LONG RUN)
OPERATING SYSTEM WINDOWS-NT, OPEN-VMS OR UNIX.
PROVISION OF LVS
CONNECTION TO OTHER SYSTEM THROUGH STATIONWIDE WAN
Power Plant C&I systemsPower Plant C&I systems
DDCMISMMIPIS FUNCTIONALITIES
VARIOUS PLANT EQUIPMENT OPERATION
OPERATOR INFORMATIONS THROUGH VARIOUS DISPLAYS
ALARMS, LOGS, HISTORICAL AND LONG TERM STORAGE.
PERFORMANCE AND OTHER CALCULATIONS
Power Plant C&I systemsPower Plant C&I systems
DDCMIS
DATA COMMUNICATION SYSTEM
LOCAL SYSTEM BUS – It is just lines on the backplane of control panel to which all the modules are connected directly. It serves as communication medium between the modules.
INTRAPLANT BUS(IPB) – It is a coaxial cable which runs through all the panels of control system and interconnects them.
LOCAL AREA NETWORK(LAN) – It is a network of computers which are connected to a single point (HUB).
FOR ALL BUSES REDUNDANCY IS PRESENT
Power Plant C&I systemsPower Plant C&I systems
DDCMIS
CONTROL SYSTEM
FUNCTIONAL DIVISION SG-C&I SYSTEM TG-C&I SYSTEM BOP-C&I SYSTEM
HARDWARE COMPONENTS POWER SUPPLY CONTROL PANEL ELECTRONIC MODULES
Power Plant C&I systemsPower Plant C&I systemsDDCMIS
PROGRAMMING & MMIPIS M & SCONFIGURATION SYSTEM CLOCK
SG- C&I BOP- C&I TG- C&ISYSTEM SYSTEM SYSTEM
DCS
CONTROL SYSTEM
Power Plant C&I systemsPower Plant C&I systemsDDCMIS
SG-C&I SYSTEM BURNER MANAGEMENT SYSTEM (BMS) SOOT BLOWER CONTROL SYSTEM (SBC) SECONDARY AIR DAMPER CONTROL SYSTEM (SADC) AUXILIARY PRDS CONTROLS (APRDS)
TG-C&I SYSTEM ELECTRONIC TURBINE PROTECTION (ETP) AUTOMATIC TURBINE RUN-UP SYSTEM (ATRS) AUTOMATIC TURBINE TESTING SYSTEM (ATT) ELECTRO- HYDRAULIC TURBINE CONTROL SYSTEM (EHTC) TURBINE STRESS CONTROL SYSTEM (TSC) LP BYPASS SYSTEM (LPBP) HP BYPASS SYSTEM(HPBP) GLAND STEAM PRESSURE CONTROL GENERATOR AUXILIARY MONITORING PANEL (GAMP)
Power Plant C&I systemsPower Plant C&I systems
DDCMISBOP-C&I SYSTEM
CONSISTS OF OPEN LOOP CONTROL SYSTEM (OLCS) AND CLOSED LOOP CONTROL SYSTEM (CLCS)
OLCS - THE SEQUENCE CONTROL, INTERLOCK OF ALL THE PLANT SYSTEMS WHICH
ARE NOT COVERED IN THE SG-C&I AND TG-C&I. THIS INCLUDES MAJOR AUXILIARIES LIKE
FD/ID/PA FANS, AIR-PREHEATER, BFP/CEP/CWP/ BCWP , DMCWP/CLCWP AND
ELECTRICAL BREAKERS.
CLCS - THE MODULATING CONTROL FOR VARIOUS IMPORTANT PLANT PARAMETERS,
LIKE FW FLOW (DRUM LEVEL), FURNACE DRAFT, COMBUSTION CONTROL (FUEL FLOW
AND AIR FLOW), PA HDR PRESSURE CONTROL, DEAERATOR/HOTWELL/HEATER LEVEL
CONTROLS ETC.
Power Plant C&I systemsPower Plant C&I systems
DDCMIS
WHY DDCMIS ?
VERY HIGH FLEXIBILITY FOR MODIFICATION IN CONTROL STRATEGY
VERY HIGH SELF-DIAGNOSTIC
VERY LOW DRIFT (ONLY IN I/O CARDS) , HENCE NO NEED OF
FREQUENT RE-CALIBRATION
MUCH HIGHER RELIABILITY (BASED ON MTBF)
BETTER LONG TERM SUPPORT DUE TO CHANGING TECHNOLOGY
MUCH BETTER OPERATOR INTERFACE
Power Plant C&I systemsPower Plant C&I systems
DDCMIS
SALIENT FEATURES OF DDCMIS
INTEGRATED PLANT CONTROL FOR SG, TG AND BALANCE OF PLANT CONTROL
IT MAY BE REMEMBERED THAT HISTORICALLY THE TERM DDCMIS USED REFER TO THE SO-CALLED “BOP-C&I” . THE SG-C&I, i.e. FSSS etc. TG-C&I i.e. ATRS, TURBINE PROTECTION etc. ORIGINALLY WERE NOT CONSIDERED UNDER DDCMIS OR DCS AS PER MANY SUPPLIERS. ONLY RECENTLY THE TYPE OF SYSTEMS FOR ALL THE SYSTEMS HAVE BECOME SIMILAR (WITH SOME DIFFERENCE WHICH WILL BE DISCUSSED LATER), WE TEND TO CONSIDER THESE SYSTEMS UNDER DDCMIS.
Power Plant C&I systemsPower Plant C&I systems
DDCMIS
SALIENT FEATURES OF DDCMIS INTEGRATED PLANT OPERATION THROUGH FULLY INTERCHANGEABLE
OPERTAOR WORK STATIONS (OWS) FOR SG, TG AND BALANCE OF PLANT
PROVISION OF EXTENSIVE SELF-DIAGNOSTICS
USE OF LARGE VIDEO SCREENS FOR PROJECTIONS OF VARIOUS PLANT MIMICS ETC.
PROVISION OF FAULT ALARM ANALYSIS TO GUIDE THE OPERATOR TO THE MOST LIKELY EVENT
PROVISION OF ADEQUATE RELIABILITY AND AVAILABILITY WITH PROPER REDUNDANCY IN SENSOR, I/O AND CONTROLLER LEVELS.
Power Plant C&I systemsPower Plant C&I systems
Global & National Power Scenario
Global:
Global electricity consumption 69% higher in 2020 than 2003
80% of energy provided from thermal sources
Emerging trend from Thermal to Hydel and Renewable Energy sources
Indian:Total installed capacity only 1362 MW in 1947
Per Capita consumption 631 units (2005-06) only with installed capacity of 1,77,000 MW
GDP growth of 8%, power growth required 10%
To add 1,00,000MW capacity by 2017
Liberalizations of the sector
Power Plant C&I systemsPower Plant C&I systems
NTPC at a glance:
Installed Capacity 34199 MW
Target 75000MW by 2017
Performance:
Annual Availability 91.62%
Annual PLF 88.29%
11 stations among top 20 in the country
NTPC Practices to achieve goalNTPC Practices to achieve goal
KEY THRUST AREAS
Zero Human ErrorZero Human Error
Implementation of trip committee recommendations judiciously / rigorouslyImplementation of trip committee recommendations judiciously / rigorously
Identification of trip committee recommendations of other stationsIdentification of trip committee recommendations of other stations which are relevant and implement them which are relevant and implement them
Implementation of operation memorandum wherever applicableImplementation of operation memorandum wherever applicable
Dissemination of information about best practices followed acrossDissemination of information about best practices followed across NTPC and other Power StationsNTPC and other Power Stations
Providing proper environment for C&I equipment to reduce probability of Providing proper environment for C&I equipment to reduce probability of card and equipment failurecard and equipment failure
C&I Trip TrendC&I Trip Trend
2009-10: FORCED OUTAGE DISTRIBUTION (COAL)
9%22%
28%
2%9%
17%
7% 2% 4%
Coal 09-10Relay Malfunction
Tx / Sw /Fld Dev
Control System
EHC / ATRS
Power Supply / CableSoftware / Card failureHuman Error
UPS
RTD / Tc
INFERENCE : 2009-10 C&I OUTAGE ANALYSIS INFERENCE : 2009-10 C&I OUTAGE ANALYSIS
Major factors contributing to C&I outage in 2009-10:
1.Control System related failure
2. Field Device Failure
3. Soft ware/Card Failure
4. Power Supply/Relay failure
5. Human error
BEST PRACTICES COMPILED/ADOPTED IN NTPC C&IBEST PRACTICES COMPILED/ADOPTED IN NTPC C&I
All ‘unit protections’ are provided with 2/3 logic and audio visual alarm is provided on 1/3 to operator on actuation of any one sensor wherever possible with proper approval.
Use of headless RTD in tripping circuit of ID/PA/FD fans & BFPs.
Resistance mapping of critical solenoids including cable during overhauls and monitoring trend to identify any defects.
Marking of trip related devices and Junction Boxes marked in RED color.
Regular calibration of all important instruments which have a bearing on unit safety, reliability and efficiency. Instruments are calibrated against standard instruments with traceability to NABL.
BEST PRACTICES COMPILED/ADOPTED IN NTPC C&IBEST PRACTICES COMPILED/ADOPTED IN NTPC C&I
For handling of electrostatic sensitive electronic hardware, electrostatic bags, wrist straps and other ESD handling devices are employed in control panels and lab. All Laboratories are provided with ESD proof workstations.
Disable removable drives of servers and workstations.
Single source responsibility for software backup of DCS and storage in fire proof cabinets in two different locations.
Detailed work instruction are prepared and followed for working on all trip related devices.
BEST PRACTICES COMPILED/ADOPTED IN NTPC C&IBEST PRACTICES COMPILED/ADOPTED IN NTPC C&I
A single source responsibility is fixed for the generation and maintenance of system passwords so as to maintain system security
Internal quality inspection for critical checks during overhauls to ensure quality in overhaul works
Near miss situations are monitored and analyzed. The learning from this area used to formulate strategies to avoid spurious outages.
All power supply voltages are monitored with a fixed periodicity and maintained within /- 10% of the rated value.
BEST PRACTICES COMPILED/ADOPTED IN NTPC C&IBEST PRACTICES COMPILED/ADOPTED IN NTPC C&I
Fuses used in UPS and protection circuits are replaced with
new fuses of same rating and type during every overhaul Earth voltages in control panels are monitored on a predetermined frequency and the values are recorded for trending
All bus terminators are checked during every overhaul for All bus terminators are checked during every overhaul for ensuring integrity of bus communication in DDCMIS systemsensuring integrity of bus communication in DDCMIS systems
Load testing of power supplies for critical applications and replacement of power supply modules or electrolytic capacitor and power transistors used in power supply if found deteriorated.
Other important actions taken for forced outage reductionOther important actions taken for forced outage reduction
Rerouting of control & power cables in hot zones
Panel power supply monitoring in regular intervals.
CER/UCB temperature and humidity monitoring online. Insisting for performance of the A/C system
Checking and tightening power supply cables during overhaul
Ensuring healthiness of cabinet cooling fans.
Other important actions taken for forced outage reductionOther important actions taken for forced outage reduction
Panel cooling fans supply segregation from system supply with MCB / fuse.
Cleaning of air filters on panels periodically
Servo valve replacement/ servicing in hydraulic drives.
Individual fuse protection in 220VDC MFT for HOTV, LOTV, HORV, Scanner emergency air damper solenoids
1.1.Commissioning of non commissioned systemsCommissioning of non commissioned systems
a)a)Soot blowing Steam Pr. Control valve: Soot blowing Steam Pr. Control valve:
Status- Actuator damaged while commissioning. BHEL has placed PO on Status- Actuator damaged while commissioning. BHEL has placed PO on OEM M/s MIL for procurement of damaged partsOEM M/s MIL for procurement of damaged parts
b) b) Commissioning of SWAS analyzers:Commissioning of SWAS analyzers:
Status-Procurement of Reagents for reagent based measurement (i.e. Silica Status-Procurement of Reagents for reagent based measurement (i.e. Silica etc.) is in process. etc.) is in process.
Suggested to take up with OEM (Forbes Marshall) through BHEL for Suggested to take up with OEM (Forbes Marshall) through BHEL for commissioning of electrode based measurements (i.e. conductivity etc.)commissioning of electrode based measurements (i.e. conductivity etc.)
Looking from WBPDCL Santaldih PerspectiveLooking from WBPDCL Santaldih Perspective
KEY THRUST AREAS
Looking from WBPDCL Santaldih PerspectiveLooking from WBPDCL Santaldih Perspective
c) Electromatic Relief Valve (ERV): c) Electromatic Relief Valve (ERV):
Status- Solenoid Installed and cabling doneStatus- Solenoid Installed and cabling done
d) APH Rotor stop alarm:d) APH Rotor stop alarm:
Status- Issue pending with BHEL for longtime. Alternative scheme Status- Issue pending with BHEL for longtime. Alternative scheme through DDCMIS suggested by fixing proximity switch on APH rotor through DDCMIS suggested by fixing proximity switch on APH rotor shaft at support brg. end.shaft at support brg. end.
e)e) APH fire detection alarm:APH fire detection alarm:
Status- Issue pending with BHEL for longtime. Alternative scheme by Status- Issue pending with BHEL for longtime. Alternative scheme by measuring APH metal temp. using thermocouples in Air & Gas path measuring APH metal temp. using thermocouples in Air & Gas path may be thought of. may be thought of.
Looking from WBPDCL Santaldih PerspectiveLooking from WBPDCL Santaldih Perspective
f) Commissioning/testing of Back up (Back up of MAX DNA f) Commissioning/testing of Back up (Back up of MAX DNA system work stations)Push Button console for unit control:system work stations)Push Button console for unit control: Suggested to test the operation of various push buttons at the time of Start Suggested to test the operation of various push buttons at the time of Start up/ Shutdown of unit jointly with operation. up/ Shutdown of unit jointly with operation.
2. Rectification of long pending problems:2. Rectification of long pending problems:
a) Problem of SADC systemsa) Problem of SADC systems
Status: Operation of some of the dampers erratic and needed frequent Status: Operation of some of the dampers erratic and needed frequent adjustment due to unreliable performance of actuator/positioneradjustment due to unreliable performance of actuator/positioner
Suggested to procure 04 nos. actuator with positioner of reputed Suggested to procure 04 nos. actuator with positioner of reputed manufacturer for replacement in one elevation on trial basismanufacturer for replacement in one elevation on trial basis
Looking from WBPDCL Santaldih Perspective
b) High PA flow to Mills:b) High PA flow to Mills:
In auto PA flow of all mills are about 30% more than characteristic flow. In auto PA flow of all mills are about 30% more than characteristic flow. PA flow curve for sliding set point may be set as per mill design.PA flow curve for sliding set point may be set as per mill design.
Also provision of manual set point may be explored to cater poor coal Also provision of manual set point may be explored to cater poor coal qualityquality
3. Setting up of C&I Lab with requisite facilities3. Setting up of C&I Lab with requisite facilities
4.Enhancing reliability of Field Instruments4.Enhancing reliability of Field Instruments
a)a) Proper glanding/ sealing of field instruments, control valves, routing Proper glanding/ sealing of field instruments, control valves, routing & dressing of cables, ensuring cleanliness & closure of all LIEs etc.& dressing of cables, ensuring cleanliness & closure of all LIEs etc.
Looking from WBPDCL Santaldih Perspective
5. 5. Sealing & Cable dressing in MAX DNA panels during unit ShutdownSealing & Cable dressing in MAX DNA panels during unit Shutdown
6. 6. Disabling various ports for removable drives of MAX DNA work Disabling various ports for removable drives of MAX DNA work stations for system reliabilitystations for system reliability
7. Installation of ON Line printers of MAX DNA system for daily LOGs. 7. Installation of ON Line printers of MAX DNA system for daily LOGs. Daily LOGs are essential for analysis of different plant parameters by Daily LOGs are essential for analysis of different plant parameters by O&E dept.O&E dept.
b)b) Replacement of unreliable instruments by quality instrumentsReplacement of unreliable instruments by quality instruments
c) Marking of protection related JBs to avoid human errorc) Marking of protection related JBs to avoid human error
Regular walk down check in various areas to ensure the healthiness of field Regular walk down check in various areas to ensure the healthiness of field instruments.instruments.
9.Implementation of regular cleaning schedule & preventive mtc. Schedule 9.Implementation of regular cleaning schedule & preventive mtc. Schedule for Boiler, Turbine and common systemsfor Boiler, Turbine and common systems
10.Prepartion of detail job list for unit overhauling10.Prepartion of detail job list for unit overhauling
11. 11. Review of spares status and timely action for procurement for Review of spares status and timely action for procurement for breakdown(corrective), preventive and overhauling maintenancebreakdown(corrective), preventive and overhauling maintenance..
Looking from WBPDCL Santaldih Perspective
8. 8. Cleanliness of NETWORK ROOM & EWS room to be ensured. Cleanliness of NETWORK ROOM & EWS room to be ensured. Monitoring of Temp. & Humidity of CER, UCB , NETWORK & EWS Monitoring of Temp. & Humidity of CER, UCB , NETWORK & EWS rooms.rooms.