The 12 Rules for Operating Your Cooling Tower in Winter

Post on 09-Jan-2017

1.158 views 6 download

Transcript of The 12 Rules for Operating Your Cooling Tower in Winter

A publication of

Avoid icing on your counterflow cooling tower this winter. Follow these 12 rules for operating

your cooling tower in winter.

Rule #1

Complete a Fall Inspection

Rule #1

1. distribution headers

Inspect…

1. distribution headers 2. laterals

Inspect…

1. distribution headers 2. laterals 3. nozzles

**Ensure nozzles are clean and intact to provide even water distribution over tower fill. This will help to prevent icing.

Inspect…

Rule #2

Protect air-inlet opening

Rule #2

falls below 55 degrees, start implementing cold weather operations.

This begins with protecting the air inlet opening / louver area (if installed).

When water temperature…

falls below 55 degrees, start implementing cold weather operations.

This begins with protecting the air inlet opening / louver area (if installed).

When water temperature…

The most effective way to protect the air inlet opening, is to install tarpaulins on the windward side of the tower.

Rule #3

High heat load & water circulation rate

Rule #3

needs to be maintained at the highest possible level.

Once the air inlet opening is protected, all other components are protected if there is a substantial amount of plant heat load.

Plant heat load…

Circulating water flow should also be maintained at the highest possible rate by operating all usable pumps. This is to ensure a full warm water wash of the internal components.

Rule #4

What if there is no heat load?

Rule #4

the circulating water should be bypassed directly to the cold water basin.

If your tower is not equipped with a bypass capability, then shut down your tower completely.

If there is no heat load…

Rule #5

Complete visual inspections

Rule #5

under winter operations,

complete a visual

inspection of the tower

every 2 - 4 hours

depending on if the

ambient temperature is

within the rage of 20 -

40 degrees or below 20

degrees.

While running your tower…

While running your tower…

20 - 40

inspect every 4 hours

under winter operations,

complete a visual

inspection of the tower

every 2 - 4 hours

depending on if the

ambient temperature is

within the rage of 20 -

40 degrees or below 20

degrees.

While running your tower…

< 20inspect every

2 hours

under winter operations,

complete a visual

inspection of the tower

every 2 - 4 hours

depending on if the

ambient temperature is

within the rage of 20 -

40 degrees or below 20

degrees.

Rule #6

Maintain cold water temperature by regulating airflow

Rule #6

fans can be cycled from

full speed to half speed or

be completely turned off.

This is the most effective way to maintain cold water temperature and control ice formation.

To regulate airflow…

The cold return water should NOT

drop below 55 degrees

Fahrenheit.55fans can be cycled from

full speed to half speed or

be completely turned off.

This is the most effective way to maintain cold water temperature and control ice formation.

To regulate airflow…

Rule #7

When reverse fan operations are necessary

Rule #7

is still occurring, switch to

reverse fan operations.

Reverse mode should be

monitored continuously

and should only be used

for severe ice buildup

with systems that are

capable of this option.

If significant ice build up…

Rule #8

When shutting fans down

Rule #8

from rotating in the normal direction, allow at least 2 minutes before starting in reverse direction.

When fans are shut off…

{2 min.

Rule #9

Check the fan blades

Rule #9

for any ice buildup. If

your fan blades are free

from ice buildup, you

can now begin reverse

direction.

Check fan blades…

for any ice buildup. If

your fan blades are free

from ice buildup, you

can now begin reverse

direction.

Check fan blades…

**Even if the fans are still wind milling in the

forward direction, they can be reversed. Minimal

torque will be applied to the mechanical system.

Rule #10

Reverse operation timeline

Rule #10

ONLY for a maximum of

20 - 30 min.

Operate in reverse direction…

20 – 30 minutes{

Rule #11

Competing reverse fan operations

Rule #11

When reverse operation is complete… let the fan come to a complete stop before re-starting.

let the fan come to a complete stop before re-starting.

When reverse operation is complete…

Now with the fans shut off, flow water for 15 min to prevent ice

buildup in the plenum area. Again, visually check the fan

blades for ice buildup.

Rule #12

Never physically remove ice from structure!

Rule #12

Or try to physically strip the framework of the ice.

NEVER remove ice…

any ice buildup on the perimeter columns or the bottom of the fill.

**It is important to inspect this every 2-4 hours to prevent ice build up this heavy. (see photo to right)

Monitor frequently…

Remember:Melting will leave components in good condition where as physical removal of ice will generally cause

more damage.