Avoid icing on your counterflow cooling tower this winter. Follow these 12 rules for operating

your cooling tower in winter.

Page 3: The 12 Rules for Operating Your Cooling Tower in Winter

Rule #1

Page 4: The 12 Rules for Operating Your Cooling Tower in Winter

Complete a Fall Inspection

Rule #1

Page 5: The 12 Rules for Operating Your Cooling Tower in Winter

1. distribution headers

Inspect…

Page 6: The 12 Rules for Operating Your Cooling Tower in Winter

1. distribution headers 2. laterals

Inspect…

Page 7: The 12 Rules for Operating Your Cooling Tower in Winter

1. distribution headers 2. laterals 3. nozzles

**Ensure nozzles are clean and intact to provide even water distribution over tower fill. This will help to prevent icing.

Inspect…

Page 8: The 12 Rules for Operating Your Cooling Tower in Winter

Rule #2

Page 9: The 12 Rules for Operating Your Cooling Tower in Winter

Protect air-inlet opening

Rule #2

Page 10: The 12 Rules for Operating Your Cooling Tower in Winter

falls below 55 degrees, start implementing cold weather operations.

This begins with protecting the air inlet opening / louver area (if installed).

When water temperature…

Page 11: The 12 Rules for Operating Your Cooling Tower in Winter

falls below 55 degrees, start implementing cold weather operations.

This begins with protecting the air inlet opening / louver area (if installed).

When water temperature…

The most effective way to protect the air inlet opening, is to install tarpaulins on the windward side of the tower.

Page 12: The 12 Rules for Operating Your Cooling Tower in Winter

Rule #3

Page 13: The 12 Rules for Operating Your Cooling Tower in Winter

High heat load & water circulation rate

Rule #3

Page 14: The 12 Rules for Operating Your Cooling Tower in Winter

needs to be maintained at the highest possible level.

Once the air inlet opening is protected, all other components are protected if there is a substantial amount of plant heat load.

Plant heat load…

Page 15: The 12 Rules for Operating Your Cooling Tower in Winter

Circulating water flow should also be maintained at the highest possible rate by operating all usable pumps. This is to ensure a full warm water wash of the internal components.

Page 16: The 12 Rules for Operating Your Cooling Tower in Winter

Rule #4

Page 17: The 12 Rules for Operating Your Cooling Tower in Winter

What if there is no heat load?

Rule #4

Page 18: The 12 Rules for Operating Your Cooling Tower in Winter

the circulating water should be bypassed directly to the cold water basin.

If your tower is not equipped with a bypass capability, then shut down your tower completely.

If there is no heat load…

Page 20: The 12 Rules for Operating Your Cooling Tower in Winter

Rule #5

Page 21: The 12 Rules for Operating Your Cooling Tower in Winter

Complete visual inspections

Rule #5

Page 22: The 12 Rules for Operating Your Cooling Tower in Winter

under winter operations,

complete a visual

inspection of the tower

every 2 - 4 hours

depending on if the

ambient temperature is

within the rage of 20 -

40 degrees or below 20

degrees.

While running your tower…

Page 23: The 12 Rules for Operating Your Cooling Tower in Winter

While running your tower…

20 - 40

inspect every 4 hours

under winter operations,

complete a visual

inspection of the tower

every 2 - 4 hours

depending on if the

ambient temperature is

within the rage of 20 -

40 degrees or below 20

degrees.

Page 24: The 12 Rules for Operating Your Cooling Tower in Winter

While running your tower…

< 20inspect every

2 hours

under winter operations,

complete a visual

inspection of the tower

every 2 - 4 hours

depending on if the

ambient temperature is

within the rage of 20 -

40 degrees or below 20

degrees.

Page 25: The 12 Rules for Operating Your Cooling Tower in Winter

Rule #6

Page 26: The 12 Rules for Operating Your Cooling Tower in Winter

Maintain cold water temperature by regulating airflow

Rule #6

Page 27: The 12 Rules for Operating Your Cooling Tower in Winter

fans can be cycled from

full speed to half speed or

be completely turned off.

This is the most effective way to maintain cold water temperature and control ice formation.

To regulate airflow…

Page 28: The 12 Rules for Operating Your Cooling Tower in Winter

The cold return water should NOT

drop below 55 degrees

Fahrenheit.55fans can be cycled from

full speed to half speed or

be completely turned off.

This is the most effective way to maintain cold water temperature and control ice formation.

To regulate airflow…

Page 29: The 12 Rules for Operating Your Cooling Tower in Winter

Rule #7

Page 30: The 12 Rules for Operating Your Cooling Tower in Winter

When reverse fan operations are necessary

Rule #7

Page 31: The 12 Rules for Operating Your Cooling Tower in Winter

is still occurring, switch to

reverse fan operations.

Reverse mode should be

monitored continuously

and should only be used

for severe ice buildup

with systems that are

capable of this option.

If significant ice build up…

Page 32: The 12 Rules for Operating Your Cooling Tower in Winter

Rule #8

Page 33: The 12 Rules for Operating Your Cooling Tower in Winter

When shutting fans down

Rule #8

Page 34: The 12 Rules for Operating Your Cooling Tower in Winter

from rotating in the normal direction, allow at least 2 minutes before starting in reverse direction.

When fans are shut off…

{2 min.

Page 35: The 12 Rules for Operating Your Cooling Tower in Winter

Rule #9

Page 36: The 12 Rules for Operating Your Cooling Tower in Winter

Check the fan blades

Rule #9

Page 37: The 12 Rules for Operating Your Cooling Tower in Winter

for any ice buildup. If

your fan blades are free

from ice buildup, you

can now begin reverse

direction.

Check fan blades…

Page 38: The 12 Rules for Operating Your Cooling Tower in Winter

for any ice buildup. If

your fan blades are free

from ice buildup, you

can now begin reverse

direction.

Check fan blades…

**Even if the fans are still wind milling in the

forward direction, they can be reversed. Minimal

torque will be applied to the mechanical system.

Page 39: The 12 Rules for Operating Your Cooling Tower in Winter

Rule #10

Page 40: The 12 Rules for Operating Your Cooling Tower in Winter

Reverse operation timeline

Rule #10

Page 41: The 12 Rules for Operating Your Cooling Tower in Winter

ONLY for a maximum of

20 - 30 min.

Operate in reverse direction…

20 – 30 minutes{

Page 42: The 12 Rules for Operating Your Cooling Tower in Winter

Rule #11

Page 43: The 12 Rules for Operating Your Cooling Tower in Winter

Competing reverse fan operations

Rule #11

Page 44: The 12 Rules for Operating Your Cooling Tower in Winter

When reverse operation is complete… let the fan come to a complete stop before re-starting.

Page 45: The 12 Rules for Operating Your Cooling Tower in Winter

let the fan come to a complete stop before re-starting.

When reverse operation is complete…

Now with the fans shut off, flow water for 15 min to prevent ice

buildup in the plenum area. Again, visually check the fan

blades for ice buildup.

Page 46: The 12 Rules for Operating Your Cooling Tower in Winter

Rule #12

Page 47: The 12 Rules for Operating Your Cooling Tower in Winter

Never physically remove ice from structure!

Rule #12

Page 48: The 12 Rules for Operating Your Cooling Tower in Winter

Or try to physically strip the framework of the ice.

NEVER remove ice…

Page 49: The 12 Rules for Operating Your Cooling Tower in Winter

any ice buildup on the perimeter columns or the bottom of the fill.

**It is important to inspect this every 2-4 hours to prevent ice build up this heavy. (see photo to right)

Monitor frequently…

Remember:Melting will leave components in good condition where as physical removal of ice will generally cause

more damage.