Sharing of RI Non-Compliant Cases - SCDF

Post on 16-Oct-2021

9 views 3 download

Transcript of Sharing of RI Non-Compliant Cases - SCDF

Sharing of RI

Non-Compliant Cases

1/<Total>

Case 1

Proposed 6 blocks of 17-storey

condominium with basement (total 378

units) and communal facilities

Non-Compliant 1

Breeching inlet between ME building and block T1

not located on external wall of building – SS575

Clause 2.3

3/<Total>

Dry rising

main

breeching

inlets not

house in a

glass-fronted

box – Clause

2.3.2.4 SS575

Non-Compliant 2

Emergency door

release not installed in

the direction of escape

at FFL – Clause

2.3.9(h)(iv)(2)

Non-Compliant 3

Proposed development of a 7-storey nursing

home with lower first storey carpark

Case 2

Non-Compliant 1

Bath room located along the naturally-

ventilated internal corridor was not

compartmented with 0.5-hour fire rated doors

and fitted with automatic self-closing device -

Clause 2.9.3(a)

Non-Compliant 2

Fire Command Centre provided with 1hr fire-

rated door instead of 2hrs - Table 6.4A

Non-Compliance 3

Internal corridor at the staff dormitory floor is not

cross-ventilated & ventilation opening is more

than 12m – Clause 2.9.3(c),(d) & (e)

Condominium housing development

comprising 4 blocks (E1, E2, E3, & F) of 3

storey flats and 6 blocks (A, B, C, D, G & H) of

5 storey flats (total 393 units) with basement

carparks and communal facilities

Case 3

CB’s labels to all fire-rated doors not

provided – Clause 8 SS332

Non-Compliant 1

Hydrant not readily accessible and clear of

obstruction – Clause 2.1.2(f) SS575

Non-Compliant 2

Dry rising main breeching inlets not house in a glass-fronted box –Clause 2.3.2.4 SS575

Non-Compliant 3

DR piping

passing through

basement

carpark not

protected –

Clause 2.2.3.1

SS575

Non-Compliant 4

Fire engine

turning facilities

not readily

accessible

(obstructed by

pond, trees and

plants) – Clause

4.2.2(d)(ix)

Non-Compliant 5

Hydrant not installed in accordance to the approved

plan (unit 01-56, H – 9-9)

Non-Compliant 6

Services other

than sprinkler

piping mounted

above the fire

hydrant

pipework –

Clause 4.4.3(b)

Non-Compliant 7

Proposed residential development comprising

of 2 blocks of 22-storey apartments, 3 blocks of

20-storey apartments and 8 units of strata

landed houses (total: 495 units) with one shop,

common basements carparks, landscape deck

& communal facilities

Case 4

Insufficient distance for the

fire engine turning facility

between Blk 21 & 23 and in-

between strata landed

houses. The distance

measured at site is 18.5m &

18m respectively, not

meeting the 20m

requirement for the fire

engine turning facility. –

Cl.4.2.2(d)(v)

Non-Compliant 1

Insufficient hosereel coverage for the function

room at B1. Short of 7m hosereel coverage

when nearest hosereel was fully extended from

the nearest block 21. – Cl.6.2.8(a)

Non-Compliant 2

Distance between fire engine access road and

entrance of exit staircase at B2 exceeded 18m

for Blk 27 & 29. (19m & 28m) - Cl.4.2.2(a)(iii)

Non-Compliant 3

28m

>18m

Unprotected opening within external exit staircase between Blk 21 & 23 – Cl 2.3.3

Non-Compliant 4

Exit discharge not directly to external at exit staircases at 4 blocks – Cl 2.3.3

Non-Compliant 5

Deadendexceeded46m. Site –52m – Cl4.2.2(d)(v)

Non-Compliant 6

Blk

25

Hose reel not adjacent to exit staircase. –SS575 Cl 6.2.2.1

Non-Compliant 7

Blk

23

Case 5

Proposed erection of 4 storey single-user warehouse and ancillary office

Non-Compliant 1

Dotted rectangle markings for PWD holding point on the floor not provided. – Cl 3.2.7 (d) Appendix 20

Non-Compliant 2

Smoke-stop lobby and fire-fighting lobby not ventilated by permanent fixed ventilation openings in the external wall of the lobby. – Cl 2.2.13 (b)

Non-Compliant 3Smoke vents not permanent open type in the warehouse at 2nd and 3rd storey. – Appendix 4 Cl 6.2

Non-Compliant 4Smoke-stop lobby shall be located not more than 9m from an air-well or external recessed space of minimum clear area 93m² and minimum width of 6m. (site – 14.7m). - Cl 2.2.13 (b)

Fire doors not

provided to

MDF room at

1st storey and

service shafts

on all floors. –

Table 6.4A

Non-Compliant 5

Non-Compliant 6

Fire rated door for FCC not provided with 2hr rating (site -1hr rating). – Cl 6.4A

Case 6

Proposed additions and alterations to existingunit at 3rd storey and attic

One-way travel distance at

3rd Storey (including attic).

More than 13m to exit.

Non-Compliant 1

>13m

(about 14.5m)

Staircase was

not protected

with fire-rated

wall and door

at 3rd Storey.

Non-Compliant 2

Hosereel (at 3rd Storey)

was obstructing the

staircase leading to

attic storey.

Non-Compliant 3

Case 7

Proposed change of use to KTV and additionsand alterations of existing internal layout tounit #02-01

46/<Total>

47/<Total>

48/<Total>

49/<Total>

Occupant passing through the spaces or

rooms occupied by other occupants or

tenants. - Clause 2.2.12(b)

Non-Compliant 1

Case 8

Proposed erection of a 4-storey nursing homewith roof terrace and sub-basement car park

FAP not accessible from fire engine accessway at 4th

storey and obstructed by companion suites unit. – Clause 4.2.3

51/<Total>

Non-Compliant 1

Breeching inlets (sprinkler and dry rising main) not located

within 18m (site about 25m), not visible from the fire

engine access ways & not on external wall of building. -

Clause 4.3 & SS575 2.3.1.2

52/<Total>

Non-Compliant 2

Staircases ST 02 landing width/depth that serve patient accommodation not comply (site measurement is 2.74m and 1.695m). – Table 2.5.1(a)(viii)(2)

53/<Total>

Non-Compliant 3

Exit door opening into exit staircase (ST 02) impeded the egress of occupants when door swing outwards.(site measure is 890mm clearance) – Clause 2.3.9 (d)(i)

54/<Total>

Non-Compliant 4

2nd, 3rd & 4th storey - Remoteness of 2 exit staircases is grossly under 1/3 maximum diagonal of the building footprint. (require 1/3D = 19.6m, provision = 8.5m). –Clause 1.2.60(a)

55/<Total>

Non-Compliant 5

56/<Total>

2nd, 3rd & 4th storey - 1-way travel distance exceeded from most remote point at Gridline E/27 and A/1 – Clause 1.2.60 (d)

57/<Total>

Non-Compliant 6

58/<Total>

Fresh air duct supply to the lobby (PL01 and PL 02) between area of refuge 1a not drawn directly from external of building and located inside the building. –Clause 7.1.4

59/<Total>

Non-Compliant 7

60/<Total>

FAD passing through this lobby not installed with fire damper (GL G to O+/14 to 15). – Clause 7.1.1(e)

61/<Total>

Non-Compliant 8

Proposed new erection of 12 storey international school with multi-storey carpark and swimming pool

62/<Total>

Case 9

No provision of e-lights in the whole block of MSCP – Clause 8.1.3

63/<Total>

Non-Compliant 1

DR breeching inlet for DR 3-9 not installed on external wall of building. – SS575 Clause 2.3.1.2

64/<Total>

Non-Compliant 2

Door (staircases/ FFL/ corridor) for re-entry floor locked with electro-magnetic device and not provided with emergency door release on both sides of entry.

Door to all exit access door not installed with electro-magnetic device.

Clause 2.3.9 (k)

65/<Total>

Non-Compliant 3

No testing of e-lights carried out in the whole block of MSCP. – RI Regulation 1st Schedule Part 2

66/<Total>

Non-Compliant 4

Thank You