Case 1

Proposed 6 blocks of 17-storey

condominium with basement (total 378

units) and communal facilities

Page 3: Sharing of RI Non-Compliant Cases - SCDF

Non-Compliant 1

Breeching inlet between ME building and block T1

not located on external wall of building – SS575

Clause 2.3

3/<Total>

Page 4: Sharing of RI Non-Compliant Cases - SCDF

Dry rising

main

breeching

inlets not

house in a

glass-fronted

box – Clause

2.3.2.4 SS575

Non-Compliant 2

Page 5: Sharing of RI Non-Compliant Cases - SCDF

Emergency door

release not installed in

the direction of escape

at FFL – Clause

2.3.9(h)(iv)(2)

Non-Compliant 3

Page 6: Sharing of RI Non-Compliant Cases - SCDF

Proposed development of a 7-storey nursing

home with lower first storey carpark

Case 2

Page 7: Sharing of RI Non-Compliant Cases - SCDF

Non-Compliant 1

Bath room located along the naturally-

ventilated internal corridor was not

compartmented with 0.5-hour fire rated doors

and fitted with automatic self-closing device -

Clause 2.9.3(a)

Page 8: Sharing of RI Non-Compliant Cases - SCDF
Page 9: Sharing of RI Non-Compliant Cases - SCDF

Non-Compliant 2

Fire Command Centre provided with 1hr fire-

rated door instead of 2hrs - Table 6.4A

Page 10: Sharing of RI Non-Compliant Cases - SCDF
Page 11: Sharing of RI Non-Compliant Cases - SCDF

Non-Compliance 3

Internal corridor at the staff dormitory floor is not

cross-ventilated & ventilation opening is more

than 12m – Clause 2.9.3(c),(d) & (e)

Page 12: Sharing of RI Non-Compliant Cases - SCDF
Page 13: Sharing of RI Non-Compliant Cases - SCDF

Condominium housing development

comprising 4 blocks (E1, E2, E3, & F) of 3

storey flats and 6 blocks (A, B, C, D, G & H) of

5 storey flats (total 393 units) with basement

carparks and communal facilities

Case 3

Page 14: Sharing of RI Non-Compliant Cases - SCDF

CB’s labels to all fire-rated doors not

provided – Clause 8 SS332

Non-Compliant 1

Page 15: Sharing of RI Non-Compliant Cases - SCDF

Hydrant not readily accessible and clear of

obstruction – Clause 2.1.2(f) SS575

Non-Compliant 2

Page 16: Sharing of RI Non-Compliant Cases - SCDF

Dry rising main breeching inlets not house in a glass-fronted box –Clause 2.3.2.4 SS575

Non-Compliant 3

Page 17: Sharing of RI Non-Compliant Cases - SCDF

DR piping

passing through

basement

carpark not

protected –

Clause 2.2.3.1

SS575

Non-Compliant 4

Page 18: Sharing of RI Non-Compliant Cases - SCDF

Fire engine

turning facilities

not readily

accessible

(obstructed by

pond, trees and

plants) – Clause

4.2.2(d)(ix)

Non-Compliant 5

Page 19: Sharing of RI Non-Compliant Cases - SCDF

Hydrant not installed in accordance to the approved

plan (unit 01-56, H – 9-9)

Non-Compliant 6

Page 20: Sharing of RI Non-Compliant Cases - SCDF

Services other

than sprinkler

piping mounted

above the fire

hydrant

pipework –

Clause 4.4.3(b)

Non-Compliant 7

Page 21: Sharing of RI Non-Compliant Cases - SCDF

Proposed residential development comprising

of 2 blocks of 22-storey apartments, 3 blocks of

20-storey apartments and 8 units of strata

landed houses (total: 495 units) with one shop,

common basements carparks, landscape deck

& communal facilities

Case 4

Page 22: Sharing of RI Non-Compliant Cases - SCDF

Insufficient distance for the

fire engine turning facility

between Blk 21 & 23 and in-

between strata landed

houses. The distance

measured at site is 18.5m &

18m respectively, not

meeting the 20m

requirement for the fire

engine turning facility. –

Cl.4.2.2(d)(v)

Non-Compliant 1

Page 23: Sharing of RI Non-Compliant Cases - SCDF
Page 24: Sharing of RI Non-Compliant Cases - SCDF

Insufficient hosereel coverage for the function

room at B1. Short of 7m hosereel coverage

when nearest hosereel was fully extended from

the nearest block 21. – Cl.6.2.8(a)

Non-Compliant 2

Page 25: Sharing of RI Non-Compliant Cases - SCDF
Page 26: Sharing of RI Non-Compliant Cases - SCDF

Distance between fire engine access road and

entrance of exit staircase at B2 exceeded 18m

for Blk 27 & 29. (19m & 28m) - Cl.4.2.2(a)(iii)

Non-Compliant 3

Page 27: Sharing of RI Non-Compliant Cases - SCDF

28m

Page 28: Sharing of RI Non-Compliant Cases - SCDF

>18m

Page 29: Sharing of RI Non-Compliant Cases - SCDF

Unprotected opening within external exit staircase between Blk 21 & 23 – Cl 2.3.3

Non-Compliant 4

Page 30: Sharing of RI Non-Compliant Cases - SCDF

Exit discharge not directly to external at exit staircases at 4 blocks – Cl 2.3.3

Non-Compliant 5

Page 31: Sharing of RI Non-Compliant Cases - SCDF

Deadendexceeded46m. Site –52m – Cl4.2.2(d)(v)

Non-Compliant 6

Page 32: Sharing of RI Non-Compliant Cases - SCDF

Blk

25

Hose reel not adjacent to exit staircase. –SS575 Cl 6.2.2.1

Non-Compliant 7

Page 33: Sharing of RI Non-Compliant Cases - SCDF

Blk

23

Page 34: Sharing of RI Non-Compliant Cases - SCDF

Case 5

Proposed erection of 4 storey single-user warehouse and ancillary office

Page 35: Sharing of RI Non-Compliant Cases - SCDF

Non-Compliant 1

Dotted rectangle markings for PWD holding point on the floor not provided. – Cl 3.2.7 (d) Appendix 20

Page 36: Sharing of RI Non-Compliant Cases - SCDF

Non-Compliant 2

Smoke-stop lobby and fire-fighting lobby not ventilated by permanent fixed ventilation openings in the external wall of the lobby. – Cl 2.2.13 (b)

Page 37: Sharing of RI Non-Compliant Cases - SCDF

Non-Compliant 3Smoke vents not permanent open type in the warehouse at 2nd and 3rd storey. – Appendix 4 Cl 6.2

Page 38: Sharing of RI Non-Compliant Cases - SCDF

Non-Compliant 4Smoke-stop lobby shall be located not more than 9m from an air-well or external recessed space of minimum clear area 93m² and minimum width of 6m. (site – 14.7m). - Cl 2.2.13 (b)

Page 39: Sharing of RI Non-Compliant Cases - SCDF

Fire doors not

provided to

MDF room at

1st storey and

service shafts

on all floors. –

Table 6.4A

Non-Compliant 5

Page 40: Sharing of RI Non-Compliant Cases - SCDF

Non-Compliant 6

Fire rated door for FCC not provided with 2hr rating (site -1hr rating). – Cl 6.4A

Page 41: Sharing of RI Non-Compliant Cases - SCDF

Case 6

Proposed additions and alterations to existingunit at 3rd storey and attic

Page 42: Sharing of RI Non-Compliant Cases - SCDF

One-way travel distance at

3rd Storey (including attic).

More than 13m to exit.

Non-Compliant 1

>13m

(about 14.5m)

Page 43: Sharing of RI Non-Compliant Cases - SCDF

Staircase was

not protected

with fire-rated

wall and door

at 3rd Storey.

Non-Compliant 2

Page 44: Sharing of RI Non-Compliant Cases - SCDF

Hosereel (at 3rd Storey)

was obstructing the

staircase leading to

attic storey.

Non-Compliant 3

Page 45: Sharing of RI Non-Compliant Cases - SCDF

Case 7

Proposed change of use to KTV and additionsand alterations of existing internal layout tounit #02-01

Page 46: Sharing of RI Non-Compliant Cases - SCDF

46/<Total>

Page 47: Sharing of RI Non-Compliant Cases - SCDF

47/<Total>

Page 48: Sharing of RI Non-Compliant Cases - SCDF

48/<Total>

Page 49: Sharing of RI Non-Compliant Cases - SCDF

49/<Total>

Occupant passing through the spaces or

rooms occupied by other occupants or

tenants. - Clause 2.2.12(b)

Non-Compliant 1

Page 50: Sharing of RI Non-Compliant Cases - SCDF

Case 8

Proposed erection of a 4-storey nursing homewith roof terrace and sub-basement car park

Page 51: Sharing of RI Non-Compliant Cases - SCDF

FAP not accessible from fire engine accessway at 4th

storey and obstructed by companion suites unit. – Clause 4.2.3

51/<Total>

Non-Compliant 1

Page 52: Sharing of RI Non-Compliant Cases - SCDF

Breeching inlets (sprinkler and dry rising main) not located

within 18m (site about 25m), not visible from the fire

engine access ways & not on external wall of building. -

Clause 4.3 & SS575 2.3.1.2

52/<Total>

Non-Compliant 2

Page 53: Sharing of RI Non-Compliant Cases - SCDF

Staircases ST 02 landing width/depth that serve patient accommodation not comply (site measurement is 2.74m and 1.695m). – Table 2.5.1(a)(viii)(2)

53/<Total>

Non-Compliant 3

Page 54: Sharing of RI Non-Compliant Cases - SCDF

Exit door opening into exit staircase (ST 02) impeded the egress of occupants when door swing outwards.(site measure is 890mm clearance) – Clause 2.3.9 (d)(i)

54/<Total>

Non-Compliant 4

Page 55: Sharing of RI Non-Compliant Cases - SCDF

2nd, 3rd & 4th storey - Remoteness of 2 exit staircases is grossly under 1/3 maximum diagonal of the building footprint. (require 1/3D = 19.6m, provision = 8.5m). –Clause 1.2.60(a)

55/<Total>

Non-Compliant 5

Page 56: Sharing of RI Non-Compliant Cases - SCDF

56/<Total>

Page 57: Sharing of RI Non-Compliant Cases - SCDF

2nd, 3rd & 4th storey - 1-way travel distance exceeded from most remote point at Gridline E/27 and A/1 – Clause 1.2.60 (d)

57/<Total>

Non-Compliant 6

Page 58: Sharing of RI Non-Compliant Cases - SCDF

58/<Total>

Page 59: Sharing of RI Non-Compliant Cases - SCDF

Fresh air duct supply to the lobby (PL01 and PL 02) between area of refuge 1a not drawn directly from external of building and located inside the building. –Clause 7.1.4

59/<Total>

Non-Compliant 7

Page 60: Sharing of RI Non-Compliant Cases - SCDF

60/<Total>

Page 61: Sharing of RI Non-Compliant Cases - SCDF

FAD passing through this lobby not installed with fire damper (GL G to O+/14 to 15). – Clause 7.1.1(e)

61/<Total>

Non-Compliant 8

Page 62: Sharing of RI Non-Compliant Cases - SCDF

Proposed new erection of 12 storey international school with multi-storey carpark and swimming pool

62/<Total>

Case 9

Page 63: Sharing of RI Non-Compliant Cases - SCDF

No provision of e-lights in the whole block of MSCP – Clause 8.1.3

63/<Total>

Non-Compliant 1

Page 64: Sharing of RI Non-Compliant Cases - SCDF

DR breeching inlet for DR 3-9 not installed on external wall of building. – SS575 Clause 2.3.1.2

64/<Total>

Non-Compliant 2

Page 65: Sharing of RI Non-Compliant Cases - SCDF

Door (staircases/ FFL/ corridor) for re-entry floor locked with electro-magnetic device and not provided with emergency door release on both sides of entry.

Door to all exit access door not installed with electro-magnetic device.

Clause 2.3.9 (k)

65/<Total>

Non-Compliant 3

Page 66: Sharing of RI Non-Compliant Cases - SCDF

No testing of e-lights carried out in the whole block of MSCP. – RI Regulation 1st Schedule Part 2

66/<Total>

Non-Compliant 4

Page 67: Sharing of RI Non-Compliant Cases - SCDF