Case 1
Proposed 6 blocks of 17-storey
condominium with basement (total 378
units) and communal facilities
Non-Compliant 1
Breeching inlet between ME building and block T1
not located on external wall of building – SS575
Clause 2.3
3/<Total>
Dry rising
main
breeching
inlets not
house in a
glass-fronted
box – Clause
2.3.2.4 SS575
Non-Compliant 2
Emergency door
release not installed in
the direction of escape
at FFL – Clause
2.3.9(h)(iv)(2)
Non-Compliant 3
Proposed development of a 7-storey nursing
home with lower first storey carpark
Case 2
Non-Compliant 1
Bath room located along the naturally-
ventilated internal corridor was not
compartmented with 0.5-hour fire rated doors
and fitted with automatic self-closing device -
Clause 2.9.3(a)
Non-Compliant 2
Fire Command Centre provided with 1hr fire-
rated door instead of 2hrs - Table 6.4A
Non-Compliance 3
Internal corridor at the staff dormitory floor is not
cross-ventilated & ventilation opening is more
than 12m – Clause 2.9.3(c),(d) & (e)
Condominium housing development
comprising 4 blocks (E1, E2, E3, & F) of 3
storey flats and 6 blocks (A, B, C, D, G & H) of
5 storey flats (total 393 units) with basement
carparks and communal facilities
Case 3
CB’s labels to all fire-rated doors not
provided – Clause 8 SS332
Non-Compliant 1
Hydrant not readily accessible and clear of
obstruction – Clause 2.1.2(f) SS575
Non-Compliant 2
Dry rising main breeching inlets not house in a glass-fronted box –Clause 2.3.2.4 SS575
Non-Compliant 3
DR piping
passing through
basement
carpark not
protected –
Clause 2.2.3.1
SS575
Non-Compliant 4
Fire engine
turning facilities
not readily
accessible
(obstructed by
pond, trees and
plants) – Clause
4.2.2(d)(ix)
Non-Compliant 5
Hydrant not installed in accordance to the approved
plan (unit 01-56, H – 9-9)
Non-Compliant 6
Services other
than sprinkler
piping mounted
above the fire
hydrant
pipework –
Clause 4.4.3(b)
Non-Compliant 7
Proposed residential development comprising
of 2 blocks of 22-storey apartments, 3 blocks of
20-storey apartments and 8 units of strata
landed houses (total: 495 units) with one shop,
common basements carparks, landscape deck
& communal facilities
Case 4
Insufficient distance for the
fire engine turning facility
between Blk 21 & 23 and in-
between strata landed
houses. The distance
measured at site is 18.5m &
18m respectively, not
meeting the 20m
requirement for the fire
engine turning facility. –
Cl.4.2.2(d)(v)
Non-Compliant 1
Insufficient hosereel coverage for the function
room at B1. Short of 7m hosereel coverage
when nearest hosereel was fully extended from
the nearest block 21. – Cl.6.2.8(a)
Non-Compliant 2
Distance between fire engine access road and
entrance of exit staircase at B2 exceeded 18m
for Blk 27 & 29. (19m & 28m) - Cl.4.2.2(a)(iii)
Non-Compliant 3
28m
>18m
Unprotected opening within external exit staircase between Blk 21 & 23 – Cl 2.3.3
Non-Compliant 4
Exit discharge not directly to external at exit staircases at 4 blocks – Cl 2.3.3
Non-Compliant 5
Deadendexceeded46m. Site –52m – Cl4.2.2(d)(v)
Non-Compliant 6
Blk
25
Hose reel not adjacent to exit staircase. –SS575 Cl 6.2.2.1
Non-Compliant 7
Blk
23
Case 5
Proposed erection of 4 storey single-user warehouse and ancillary office
Non-Compliant 1
Dotted rectangle markings for PWD holding point on the floor not provided. – Cl 3.2.7 (d) Appendix 20
Non-Compliant 2
Smoke-stop lobby and fire-fighting lobby not ventilated by permanent fixed ventilation openings in the external wall of the lobby. – Cl 2.2.13 (b)
Non-Compliant 3Smoke vents not permanent open type in the warehouse at 2nd and 3rd storey. – Appendix 4 Cl 6.2
Non-Compliant 4Smoke-stop lobby shall be located not more than 9m from an air-well or external recessed space of minimum clear area 93m² and minimum width of 6m. (site – 14.7m). - Cl 2.2.13 (b)
Fire doors not
provided to
MDF room at
1st storey and
service shafts
on all floors. –
Table 6.4A
Non-Compliant 5
Non-Compliant 6
Fire rated door for FCC not provided with 2hr rating (site -1hr rating). – Cl 6.4A
Case 6
Proposed additions and alterations to existingunit at 3rd storey and attic
One-way travel distance at
3rd Storey (including attic).
More than 13m to exit.
Non-Compliant 1
>13m
(about 14.5m)
Staircase was
not protected
with fire-rated
wall and door
at 3rd Storey.
Non-Compliant 2
Hosereel (at 3rd Storey)
was obstructing the
staircase leading to
attic storey.
Non-Compliant 3
Case 7
Proposed change of use to KTV and additionsand alterations of existing internal layout tounit #02-01
46/<Total>
47/<Total>
48/<Total>
49/<Total>
Occupant passing through the spaces or
rooms occupied by other occupants or
tenants. - Clause 2.2.12(b)
Non-Compliant 1
Case 8
Proposed erection of a 4-storey nursing homewith roof terrace and sub-basement car park
FAP not accessible from fire engine accessway at 4th
storey and obstructed by companion suites unit. – Clause 4.2.3
51/<Total>
Non-Compliant 1
Breeching inlets (sprinkler and dry rising main) not located
within 18m (site about 25m), not visible from the fire
engine access ways & not on external wall of building. -
Clause 4.3 & SS575 2.3.1.2
52/<Total>
Non-Compliant 2
Staircases ST 02 landing width/depth that serve patient accommodation not comply (site measurement is 2.74m and 1.695m). – Table 2.5.1(a)(viii)(2)
53/<Total>
Non-Compliant 3
Exit door opening into exit staircase (ST 02) impeded the egress of occupants when door swing outwards.(site measure is 890mm clearance) – Clause 2.3.9 (d)(i)
54/<Total>
Non-Compliant 4
2nd, 3rd & 4th storey - Remoteness of 2 exit staircases is grossly under 1/3 maximum diagonal of the building footprint. (require 1/3D = 19.6m, provision = 8.5m). –Clause 1.2.60(a)
55/<Total>
Non-Compliant 5
56/<Total>
2nd, 3rd & 4th storey - 1-way travel distance exceeded from most remote point at Gridline E/27 and A/1 – Clause 1.2.60 (d)
57/<Total>
Non-Compliant 6
58/<Total>
Fresh air duct supply to the lobby (PL01 and PL 02) between area of refuge 1a not drawn directly from external of building and located inside the building. –Clause 7.1.4
59/<Total>
Non-Compliant 7
60/<Total>
FAD passing through this lobby not installed with fire damper (GL G to O+/14 to 15). – Clause 7.1.1(e)
61/<Total>
Non-Compliant 8
Proposed new erection of 12 storey international school with multi-storey carpark and swimming pool
62/<Total>
Case 9
No provision of e-lights in the whole block of MSCP – Clause 8.1.3
63/<Total>
Non-Compliant 1
DR breeching inlet for DR 3-9 not installed on external wall of building. – SS575 Clause 2.3.1.2
64/<Total>
Non-Compliant 2
Door (staircases/ FFL/ corridor) for re-entry floor locked with electro-magnetic device and not provided with emergency door release on both sides of entry.
Door to all exit access door not installed with electro-magnetic device.
Clause 2.3.9 (k)
65/<Total>
Non-Compliant 3
No testing of e-lights carried out in the whole block of MSCP. – RI Regulation 1st Schedule Part 2
66/<Total>
Non-Compliant 4