Seminario Técnico Pentágono de Duval - Diagnóstico DGA

Post on 14-Apr-2017

889 views 16 download

Transcript of Seminario Técnico Pentágono de Duval - Diagnóstico DGA

111

Practicing DGA

1

222

Fault Gas Formation

Note: For faults T3 in paper (C), curve for H2 is a bit higher.

Ref: Duval, TSUG 2013.

2Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION

333

3

Occurrence of Faults in Service at CIGRE

3Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION

444

Triangle Method

4Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION

555

Triangle 4 (using H2, CH4 and C2H6)

Allows to distinguish between:

-Stray gassing of oil at T < 200°C (in zone S)

-Overheating at T < 250°C (in zone O)

-Possible carbonization of paper at T > 300°C, with a probability of 80%, not 100% (in zone C)

-Corona partial discharges (in zone PD).

5Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION

666

Triangle 5 (using CH4, C2H4 and C2H6)

Allows to distinguish between:

-Hot spots in oil only at T > 300°C or 700°C (in zones T2 or T3)

-Possible carbonization of paper, with a probability of 90%, not 100%

-For faults O, S, PD, use rather Triangle 4.

6Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION

777

Use of Triangles 4 and 5

Triangle 4 should be used only for faults identified first with Triangle 1 as faults PD, T1 or T2, or when there is a high level of H2.

Triangle 5 should be used only for faults identified first with Triangle 1 as thermal faults T2 or T3.

Neither Triangle 4 nor Triangle 5 should be used in case of electrical faults D1 (including sparking PDs) or D2.

When Triangles 4 and 5 do not agree, this often indicates a mixture of faults.

7Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION

8

8

Duval Pentagon 1 (2014):

-The order of gases at the 5 summits of the pentagon corresponds to the increasing energy required to produce these gases, i.e., from H2 to C2H2 counter-clockwise.

Material Of Dr. DuvalDO NOT REPRODUCE WITHOUT PERMISSION

9

9

Duval Pentagon 2 (2014):

-Free algorithms for Pentagons 1 and 2 are available from duvalm@ireq.ca.

Material Of Dr. DuvalDO NOT REPRODUCE WITHOUT PERMISSION

101010

Detection of Multiple Faults in Transformers:

10Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION

-First clue is if there is a change in gas pattern. Second clue is if

Triangles 1,4, 5 and Pentagons 1, 2 do not provide the same

diagnosis. This may be an indication of multiple faults.

-this is because each graphical representation is more sensitive to

some gases. For instance, Triangle 4 is more sensitive to H2 and

therefore to faults S or PD than even the Pentagons.

-similarly, Triangle 5 is more sensitive to C2H4 and to faults T3 in oil

than Triangle 1 and the Pentagons.

11

11

Material Of Dr. DuvalDO NOT REPRODUCE WITHOUT PERMISSION

When to Use the Pentagons and Triangles?-Ask software to indicate for each set of DGA results the fault indicated by Pentagons 1,2 and Triangles 1,4,5 (following the rules for the use of Triangles 4,5).

Display graphically in Pentagon 1 the evolution of DGA points with time. If some of them are in thermal fault zones, switch to Pentagon 2.

When DGA points move with time from one fault zone to another, this means a new fault is appearing. If interested to more precisely identify this new fault, subtract the last gas formation from the new one and add it as DGA point “Delta”.

When the Pentagons and Triangles do not provide the same fault diagnosis for some DGA results, this may indicate multiple faults. If interested to identify them more precisely, display graphically Triangles 1, 4 and/or 5 providing different fault diagnosis (or all of them), in addition to Pentagon 1 or 2.

See examples 19-19 for the interpretation of intermediate mixtures of faults.

121212

Risk of failure vs. type and location of fault

12Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION

131313

Detection of Low DPs of Paper-CO2, (> 10,000 ppm), CO2/CO (> 20) and furans 2-FAL (> 1 ppm) are

more sensitive than methanol to detect DPs < 400:

13Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION

1414

Cases of Transformers with Low DPs of Paper

Material Of Dr. DuvalDO NOT REPRODUCE WITHOUT PERMISSION

1515

Cases of Transformers with Low DPs of Paper

Note: no cases of mechanical failure of paper at low DPs have been reported to CIGRE so far.

Material Of Dr. DuvalDO NOT REPRODUCE WITHOUT PERMISSION

161616

90% Typical Concentration Values

at IEC, in ppm

(vs. source)

16Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION

171717

90% Condition 1 Concentration Values

at IEEE, in ppm

(vs. kV, MVA, age, %O2)

17Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION

181818

Probability of having a

failure-related event in

service (PFS) in %, vs. the

concentration of all gases

in ppm. T = 90% typical

value; P = pre-failure

value.

CIGRE Gas Concentrations above Typical Values

18Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION

191919

CIGRE Sampling Intervals between Typical

and Prefailure Concentrations, in ppm

(based on revised condition 1 values in the US of 2010 and

pre-failure values of CIGRE)

19Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION

202020

CIGRE Sampling Intervals between Typical

and Prefailure Gassing Rates, in ppm/month

(based on gassing rates for condition 1 in the US and pre-

failure gassing rates of CIGRE)

20Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION

212121

CIGRE Approach Applied to the IEEE

Transformers of 2014

21Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION

222222

22

90% Condition 1 Concentration Values

vs. Type of Thermal Fault at CIGRE:

(ppm)

(ppm)

22Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION

232323

23

Condition 4 Concentration Values

vs. Type of Fault at CIGRE:

(in ppm, using previous adjustment factors)

23Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION

242424

24

Comparison with Cases of High Gas Levels

without Failure at CIGRE:

(in ppm)

24Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION

252525

#2 - Attempt a fault diagnosis

• Compare lab results or monitor readings with in-house typical values of concentration and gassing rate, or compare with published values (e.g., from IEEE and CIGRE)

• If measured DGA values are above typical values, a fault diagnosis may be attempted

25Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION

262626

#3a - Evaluate the severity of the fault

•The severity of the fault will depend on:

• The rate of gas formation

• The concentration of gases

• The nature of the fault (electrical or thermal)

• The location of the fault (paper or oil only)

26Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION

272727

#4 - Actions on the equipment-Increase the frequency of oil sampling

• (as values move from typical values to pre-failure values)

-Determine the dependence of gas formation on load

-Consider complementary tests • (UHF detection of partial discharges, detection of hot spots by infra-red

cameras and acoustic tests)

-For critically located or severely affected equipment, install on-line gas monitors

-For the most severe cases, plan the replacement of the transformer and/or its removal from service and inspection

-Ask for advise of DGA experts

27Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION

2828

Concentration Limits for Multi-Gas Monitors

Material Of Dr. DuvalDO NOT REPRODUCE WITHOUT PERMISSION

2929

Gassing Rate Limits for Multi-Gas Monitors

Material Of Dr. DuvalDO NOT REPRODUCE WITHOUT PERMISSION

3030

Fault Detection with Hydrogen Monitors

Material Of Dr. DuvalDO NOT REPRODUCE WITHOUT PERMISSION

313131

31

DGA in LTCs at IEEE:

Triangle 2 for compartment types Triangles 2 for in-tank types

31Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION

323232

32

Normal operation zones for in-tank types:

• N or N1 for MR types M and D.

• N or N3 for MR types VR and VV.

• N or N4 for MR types R and V.

• N or N5 for MR types G and UZDs.

• Depending on operating conditions.

• Other DGA examples would be needed for the normal and faulty

operation of these LTCs.

32Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION

333333

Pentagon 3 for FR3

33Material Of Dr. Duval

DO NOT REPRODUCE WITHOUT PERMISSION