OVERVIEW OF SHAMS MA’AN 52.5 MWAC SOLAR PV PLANT IN … · 2018. 8. 28. · (Microgrid) PV Power...

Post on 30-Mar-2021

1 views 0 download

Transcript of OVERVIEW OF SHAMS MA’AN 52.5 MWAC SOLAR PV PLANT IN … · 2018. 8. 28. · (Microgrid) PV Power...

OVERVIEW OF SHAMS MA’AN 52.5 MWAC

SOLAR PV PLANT IN JORDAN

FS ME INSTALLATIONS

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

3

Name Watania

Size 800kWdc Diesel Hybrid (Microgrid) PV Power Plant

FS Scope EPCM

Status

Year

Complete

2015

LEADING MIDDLE EAST PV TECHNOLOGY: 350MWDC OF EXECUTED CONTRACTS

Name Sheikh Mohammed Solar Park – Phase I

Phase II

Size 13MWac 260MWdc

FS Scope EPC, O&M Module Supply

Status

Year

Complete

2013

Complete

2017

Name Masdar City PV Plant

Size 5MWdc

FS Scope Module Supply

Status

Year

Complete

2009

Name Shams Ma’an

Size 52.5MWac

FS Scope EPC, O&M

Status

Year

Complete

2016Name SADAFCO Log. Center

Size 300kWac Diesel Hybrid

FS Scope Equipment Supply

Status

Year

Complete

2016

Regional HQ

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

4Field condition efficiency is an approximate normalization for energy yield performance in Dubai on tracker

LAB VS FIELD CONDITIONS

Lab Condition (STC)

First Solar CdTe Efficiency 16.5%

mc-Si Efficiency 16.5%

Cell Temp 25°C

Energy Gain 0%

15.5%

13.86%

65°C

+6% for CdTe

Field Condition (Energy Normalized)

© Copyright 2013, First Solar, Inc.

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

6

PROJECT LOCATION

Solar Data for Shams Ma’an – Long-Term Mean

Global Horizontal Irradiance 2302 kWh/m2/yrDiffuse Irradiance 593 kWh/m2/yrWind Speed 3.38 m/sAir Temperature 17.6 ̊CRelative Humidity 44.0%

Precipitable Water 1.13 cm

The southern region representing Ma’an and Aqaba area, which has the highest solar insolation in the country and has the lowest values of diffuse irradiance. The annual average daily global irradiance is between 6-7 kWh/m2

- Source: NERC

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

7

Shams Ma’an 52.5 MWac tracker PV power plant

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

8

LOT PLAN FOR ROUND ONE: 163 MWAC / 190 MWDC

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

9

KEY PLAYERS

Off-taker MEMR/NEPCO

Land LessorMa’an Development Company

Project CompanyShams Ma’an Power Generation PSC

Project DeveloperKawar / First Solar / DGE / Nebras Power

Technology Provider /EPC / O&M Contractor

First Solar

Investors DGE / QEWC

© Copyright 2013, First Solar, Inc.

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

11

SITE LAYOUT

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

12

SITE LAYOUT – ARRAY DETAILS

© Copyright 2013, First Solar, Inc.

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

14

PROJECT SCHEDULE

© Copyright 2013, First Solar, Inc.

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

16

Survey. Grading. Road Works. Storm water Channel. Fence Works. Material delivery. Structural installations for tracker systems. Module Installation. Trenching and under ground cabling works. Above ground cable works. Combiner Boxes and Tracker Controllers installations. Instrumentations. PCS installations. PVCS installation including Capacitor Bank and Statcom. Operation and Maintenance building work. Testing, Commissioning and performance testing Final handover to client.

Project Construction Phases

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

17

Original Site Condition

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

18

Site Preparation

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

19

Storm Water Channel Works

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

20

Post Ramming

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

21

Bearing installations: (4 bearing for a single table tracker)

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

22

Torque tubes and actuator assembly

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

23

PV Modules

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

24

PCSs Installations (34nos.)

The Power Conversion Stations convert DC voltage to LV AC voltage by inverters and LV AC voltage will be raised up to 33kV by transformer and looped with other PCSs by Ring Main Units

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

25

SCADA Screen Shot shows the plant output

SOILING AND CLEANING

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

27

SOILING MONITORING STATION

Two Reference Modules:

VUWUn‐Washed

Washed

I

V

ISC

VOC

VW

AUW

AW

Daily Soiling Level

Dat

a Fi

lterin

g

Washed

Un‐washed

Un‐washedWashed

MET00

IVB13IVB02

Short‐circuited Modules:

RS

RS

÷ RS

÷ RS

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

28

LOCATION OF SOILING STATIONS

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

29

• FS modules are frameless and maintain less soiling comparatively with the framed modules.• Since the Ma’an area is a low-cost labor market with a low water availability, cleaning with

Manual Dry Brush Trolley (MDBT) is more appropriate.

MODULE DRY CLEANING

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

30

SOILING SHAMS MAAN

REAL LIFE PLANT PERFORMANCE

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

32

OVERALL PLANT PERFORMANCE

Average Performance Ratio: 80.86%Average Effective Availability 99.59%Average Energy over performance: 2.60%

LESSONS LEARNED

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

34

• First Solar participated in providing and supporting local communities with jobs to increase employment

• First Solar Participating in CSR activities in Ma’an area along with Client SMPG

Local Karate Club sponsorship Local orphanage Center Outdoor Park and Playground Area Hiring Technician from local community College

CSR IS VERY CRUCIAL FOR LOCAL COMMUNITY

© C

opyr

igh

t Fi

rst

Sol

ar,

Inc.

S

epte

mb

er 2

01

7

35

APPROVAL OF GRID IMPACT STUDIES

• Conservative approach by NEPCO on grid code compliance

• Emphasis on statcoms though not needed

• Plant included 68 inverters, Post, Tracking system, Torque Tubes,Bearings, Combiner Boxes, Transformers, Substation equipment,Capacitor Banks and STATCOM

• The Plant is connected to 33/132 kV NEPCO substation through 3nos. of 33kV feeders