INTRODUCTION

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 4/97

VIDEO

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 5/97

AIR CONDITIONING

o PHFKDQLFDO SURFHVV IRU FRQWUROOLQJ

WKH KXPLGLW\ WHPSHUDWXUHFOHDQOLQHVV DQG FLUFXODWLRQ RI DLULQ EXLOGLQJV DQG URRPV

o PDQ\ W\SHV DQG EUDQGV <25.3DQDVRQLF 6DQ\R /* 0LWVXELVKL1DWLRQDO %UDQG DQG RWKHUV

o GLIIHUHQW LQ VL]HV KRUVH SRZHU +3

GHVLJQV FKDUDFWHULVWLF DQG UDQJH RI

INTRODUCTION

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 6/97

INTRODUCTION (CONT'D)

INDOOR OUTDOOR

SPLIT UNIT SYSTEM

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 7/97

8VHVWKHFROGUHIULJHUDQWWR

FRROWKHDLULQVSDFH

INDOOR

I I ( ' )

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 8/97

OUTDOOR

o *HQHUDWHVWKHFROGUHIULJHUDQWJDV

o &RQWUROVWHPSHUDWXUHKXPLGLW\

PRLVWXUHDQGFOHDQOLQHVV

o 7RUHJXODWHDFRQVWDQW

WHPSHUDWXUHWKHDLUFRQGLWLRQHU

ILOWHUVRXWDVPXFKPRLVWXUHDV

INTRODUCTION (CONT'D)

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 9/97

o(IILFLHQW DLU FRQGLWLRQLQJ

V\VWHPV FRQWULEXWH WR D FOHDQHU

KRPH HQYLURQPHQW E\ DOORZLQJ WKH

RFFXSDQWV WR NHHS ZLQGRZV DQG

GRRUV FORVHG IRUFLQJ EXJV

LQVHFWV DQG RWKHU RXWGRRU

DQQR\DQFHV WR VWD\ RXWVLGH

OUTDOOR (cont'd)

INTRODUCTION (CONT'D)

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 10/97

CASE STUDIES

INTRODUCTION (CONT'D)

1. Single storey bungalow house- Paya Jaras Dalam, Sungai Buloh

2. Two storey bungalow house- Kelab Golf Sultan Abdul Aziz

Shah,

Shah Alam..

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 11/97

CHARACTERISTIC

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 12/97

Power of cooling

� An air-conditioner that

-has suitable power, save money

-less power, the conditioner will use

additional electric power and willpermanently work at the highest speed and

will make a lot of noise.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 13/97

Inverting conditioner 

� Inverting conditioner has automatic power to theindoor temperature.

� If the difference with set temperature is very big,then the compressor works on the highest

speed.� When the difference decreases, the compressor 

speed also decreases. As the set temperature isgained, the compressor doesn¶t stop its work,but continue working so the conditioner  

maintains the set temperature and economizeselectricity.

� The fan working on the lower speed and ismaking less noise. It also affects the level of  

comfort.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 14/97

Conditioner refilling

� Conditioner is filled with refrigerating

gas which circulates in the pipes to

absorbing heat. After depressurization,

gas evaporates and the quality of  cooling liquid changes so the work of 

the conditioner worsens.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 15/97

Conditioner noise

� The noise level and comfort depend on thefans and compressors.

� Use fans with low level of noise and good

isolation.

� Sometimes conditioner won¶t be able to

provide a necessary temperature without

high speed.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 16/97

Conditioner mounting

� The conditioner¶s life strongly depends on itscorrect mounting. Normally, the external block is

mounted under the window.

� The good idea is to mount it in the place, where

the noise of the working block will be minimal.

� Conditioner should be also accessible to the

service to future maintained . Besides, external

block should be fixed on special bearings, which

absorb the vibration.

� The internal block can mounted in any place in the

room on the fixed distance from the ceiling. The

block should be mounted on the distance from

heaters, door openings, and don¶t have any

barriers.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 17/97

Performance of Split Air-conditioner Unit

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 18/97

Low noise air intake system

� The best performance of split

aircond system is to ensure that

the low noise air intake system toget better and smoother air flows

that will provide a quiet and

refreshing environment.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 19/97

Fuzzy control

� The timer control will always switch on at apredetermined time that could cause over 

cooling.

� However, with this advanced fuzzy controlsystem, the air conditioner will be either 

switched on before preset time or delayed

depending on the indoor temperature

changes� It allowing the room temperature to reach the

preset temperature within an optimal time

frame

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 20/97

 Automatic adjustable temperature 

controls

� In split system, there is sleep mode.

� It is held after adjusting the sleep mode timer 

before sleep and after that, the temperature

will be automatically controlled and adjustedaccordingly to the lowering or body

temperature during sleep

� lower temperature throughout the night, to

provide a conducive environment for a good

sleep.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 21/97

Temperature sensing automatic

dehumidification

� Split unit also specially equipped with

précised and reliable temperature sensing

automatic dehumidification function that

automatically operates the dehumidificationwhenever the room temperature exceeds the

preset temperature

� It stops whenever the room temperature falls

back within the preset temperature as such itstabilizes the temperature and provides a

more conducive environment for the user 

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 22/97

DESIGN CRITERIA

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 23/97

a) The performance requirement of 

the system

The performance of the air conditioner shouldcomfort the occupant, it should not too noisy,

friendly user easy handling.

b) Capacity requirementNot all rooms have the same cooling requirement

because they can be small or large or they can be

located in hot corners or the opposite.

Design criteria

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 24/97

Design Criteria (cont'd)

c) Energy consumption

� Low-energy ventilation systems, electricity

costs can be up to eight times lower than in

high-consumption systems.

d) The humidity control

� Designed to control or limit the growth of microscopic

germ that thrives in certain humidity levels.� So that, the most criteria that air conditioner should

have are to prevent dust from outside and to limit the

growth of the microscopic organism in the room.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 25/97

 ± The decreasing of the air quality caused by

the occupants ± Emissions from materials in the room

 ± Activities in the room (e.g. : smoking)

 ± The quality of the outside air ± The thermal load

 ± Type of space

Parameters influence on the

design of air conditioner 

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 26/97

COMPONENTS

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 27/97

MAJOR COMPONENTS OF AIR COND

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 28/97

OUTDOOR COMPONENTS

COMPRESSOR � The compressor pulls in low-pressure, temperature

from the evaporator .

� compresses that gas to high-pressure, high

temperature superheats to the condenser.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 29/97

COMPRESSOR In/Suction:

Low Pressure,about 30 psi

& Low

Temperature,

close to

freezing.

Out/Discharge:

High Pressure, about 200 psi & High

Temperature, above

ambient.

OUTDOOR COMPONENTS (Cont'd)

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 30/97

OUTDOOR COMPONENTS (Cont'd)

CONDENSER � Receives the high-pressure, temperature vapor

refrigerant from the compressor and rejects that

heat to the surrounding air.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 31/97

OUTDOOR COMPONENTS (Cont'd)

FA  N� Moves outdoor air across the condensing

coil to cool it and assist in condensing the

high pressure, high temperature

refrigerant gas back into a liquid

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 32/97

INDOOR COMPONENTS (Cont'd)

EV A POR AT OR � Air conditioner evaporator is a heat exchange. It takes in low

temperature, low-pressure liquid refrigerant from theexpansion device and changes it into low-pressure, low

temperature vapor refrigerant.

� It responsible for absorbing heat from whatever places that

needs to be cool

� Since, the AC evaporator coil contains refrigerant that

absorbs heat from the surrounding air, the refrigerant

temperature must be lower than the air.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 33/97

EV A POR AT OR 

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 34/97

INDOOR COMPONENTS

EXPA  NSION V AL  VE � Its also known as meter devices. The meter devices

are near the evaporator coil which is within the airhandler.

� .Its responsible for providing the correct amount of 

refrigerant to the evaporator coil.

� Expansion valves work by controlling the amount of refrigerant flows to the evaporator coils. It acts as

restriction to provide a specific amount of refrigerant

flows into the evaporator coils

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 35/97

INDOOR COMPONENTS (cont'd)

EXPA  NSION V AL  VE � There are different types of expansion valves used in

air conditioner units, but the function are samewhich to:

� It controls the amount of liquid refrigerant entering

the evaporator coils.

� It maintains a pressure difference between the highand low pressure sides of the system to permit the

refrigeration to vaporize.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 36/97

EXPA  NSION V AL  VE 

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 37/97

INSTALLATION

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 38/97

PROCEDURE

� Done by expert technician

� INDOOR UNIT

 ± LOCATED INSIDE THE ROOM

 ± INSTALLED ABOVE THE BED

 ± 8-10 FEET FROM FLOOR

 ±ACCESSIBLE EASILY

 ± ABOVE WINDOW

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 39/97

PROCEDURE (cont'd)

OUTDOOR UNIT- LOCATED IN AN OPEN SPACE ON

THE TERRACE, ABOVE THE WALL,HANG ON THE EXTERNAL WALL

SUPPORTED BY ANGLE- EASILY ACCESSIBLE FOR

MAINTENANCE WORK, GASCHARGING AND INSTALLATION

- RIGID SURFACE AVOID VIBRATION- KEEP ABOVE THE INDOOR UNIT

(MAX DISTANCE 15 meter)

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 40/97

INSTALLATION (cont'd)

INDOOR

� Position

� Install at strong wall

� near electr ic outlet/branch cir cuit

� not exposed direct to sunlight� Drain pipe easily installed

� leave spaces f or servicing

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 41/97

INSTALLATION PROCESS

1.Cutting the holes.

2. Install wall hook bracket

3.F

orming drain hose and pipe4.Connecting piping

5.electircal wiring

6. Finishing -insluates pipes overlap

7.Earthing

8. Testing running

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 42/97

VIDEO

VIDEO

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 43/97

TESTING RUNNING

INDOOR UNIT

- Is operation of each button on remote 

control unit finctional?

-Does each lamp light normally?

- Do the air -f low operate normally?

- Is the drain normal

OUTDOOR

- is there any abnormal 

noise and vibration 

dur ing operation

- will noise,wind or  

drainwater  disturb the nieghbour s?

- Is there any gas

leakage?

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 44/97

TESTING RUNNING (cont'd)

OUTDOOR

- Is there any abnormal noise and 

vibration dur ing operation

- Will noise,wind or  drainwater  

disturb the nieghbour s?

- Is there any gas leakage?

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 45/97

EARTHING

� Connecting with earth wires properly

according to the technical standards.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 46/97

PRECAUTIONS

WHEN WIRING

- No power supply

- Connect all wir ing tightly.

- Following the local electr icity 

codes.

WHEN TRANSPORTING

-Careful in picking up and moving units-Call par tner s to lift up units

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 47/97

PRECAUTIONS (cont'd)

WHEN INSTALLING

- Ceiling/wall strong enough

- Cosntr uct strong wood /metal f rame to provide 

added suppor t- In a ceiling/wall - strong enough hold unit's

weight

- In a room -tubing r un inside room insulate

properly avoid sweating- In Moist / uneven locations- Raised conrete

pad blocks prevents water damage andabnormal vibration

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 48/97

PRECAUTIONS(cont'd)

WHEN INSTALLING (CONT'D)

� In an area high winds -anchor  

down with bolts and metal f rame.

� In snowy Area -outdoor  raised 

platf orm higher than dr ifting snow, 

provide snow vents

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 49/97

VIDEO

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 50/97

COST OF INSTALLATION

� EQUIPMENT PRICE

� BUILDING CONDITION

� LABOUR

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 51/97

OPERATION

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 52/97

OPER ATION

COMPRESSOR

When the temperature in the room gets higher  than the set

point f or  the thermostat, the outside compressor  is

automatically switched on.

When the compressor  is switched on, the ref r igerant

begins to cir culate through the unit. It will star ts out as a

low-temperature and low-pressure gas.

Operation of the Split Unit Air -conditioning System (Emily Beach, 2011)

The operation of a split air -conditioner  is controlled by

using a thermostat to set the desired temperature.

 As the ref r igerants passes through the compressor, it is

squeezed through a small network of  pipes which raises

both the temperature and the pressure of the ref r igerant.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 53/97

OPERATION (Cont'd)

COMPRESSOR

When excess heat is removed, the ref r igerant istransf ormed into a cool liquid.

This cool liquid travels into the room that is going to be air -

conditioned through tubes connecting the compressor and

the indoor evaporator.

Operation of the Split Unit Air -conditioning System (Emily Beach, 2011)

This gas then moves into the condenser  where a f an extracts heat f rom the ref r igerant and exhausts it to the outside. 

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 54/97

OPER ATION (Cont'd)

EVAPORATOR

 A f an unit within the evaporator draws warm air  f rom inside

the room so that it passes through the inside of theevaporator.

 As this warm air  is exposed to the cool ref r igerant, the

ref r igerant absorbs excess heat f rom the air.

Operation of the Split Unit Air -conditioning System (Emily Beach, 2011)

 As the cool liquid ref r igerant enter s the evaporator, its

pressure is reduced.

This cooled air  is then blown back into the room in order  tomake the space cooler and more comf or table.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 55/97

OPER ATION (Cont'd)

EVAPORATOR

The ref r igerant and the excess heat energy it contains are thentransf erred back to the compressor where the cycle repeats itself .

Both the compressor and evaporator will continue to operate under 

this cycle until the temperature in the room matches the level that

the thermostat i s set to.

Operation of the Split Unit Air -conditioning System (Emily Beach, 2011)

These units do not add cool air  to a room but rather remove heat

energy f rom air that is already within the space.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 56/97

OPER ATION (cont'd)

Operation of the Split Air -conditioning System (Howstuff works, 2003)

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 57/97

OPER ATION (Cont'd)

oRef r igerant leaks

oInadequate maintenance

oElectr ic control f ailure

oSensor problemso Drainage problems

F ACTORS INFLUENCE THE F AILURE OF THE OPER ATION

Problems of the Air -conditioning System (U.S. Depar tment of Energy -

Energy Efficiency and Renewable Energy, 2010)

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 58/97

VIDEO

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 59/97

MAINTENANCE

o Maintenance, repair, and operations (

MRO)involve fixing any sor t of mechanical or electr ical

device should it become out of  order or broken

(known as repair, unscheduled or   casualty

maintenance) (Wikipedia, 2011).

o It also includes per f orming routine actions which

keep the device in working order  (known as

scheduled maintenance) or prevents trouble f rom

ar ising (preventive maintenance) (Wikipedia,

2011).

o MRO may be defined as all actions which have

the objective of  retaining or restor ing an item in

or  to a state in which it can per f orm its required

function Wiki edia, 2011 .

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 60/97

M AINTEN ANCE (cont'd)

TYPE OF M AINTEN ANCE

EXPL AN ATION

Preventive

maintenance

Preventive maintenance is the maintenance per f ormed in an attempt to

avoid f ailures, unnecessary production loss and saf ety violations.  As

equipment cannot be maintained at all times, some way is needed to

decide when it is proper  to per f orm maintenance. Normally, this is done

by deciding some inspection or maintenance intervals, and sticking to

this interval more or less aff ected by what you find dur ing these

activities.

Corrective maintenance

Corrective maintenance can be defined as the maintenance which is

required when an item has f ailed or worn out, to br ing it back to workingorder. Corrective maintenance is carr ied out on all items where the

consequences of f ailure or wear ing out are not significant and the cost

of this maintenance is not greater than preventive maintenance.

The Types of Maintenances (Wikipedia, 2011)

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 61/97

ADVANTAGES AND DISADVANTAGES

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 62/97

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 63/97

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 64/97

CASE STUDY 1

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 65/97

CASE STUDY 1

Particulars :

Owner Jamil Nordin and Nor Fadzilah Ashaari

Address Lot 38935, Jalan Tempayan Emas 3,

47000 Sungai Buloh,

Selangor Darul Ehsan.

Type of House One Storey Bungalow

Type of Air Conditioner System Split Unit

Numbers of Air Conditioner Used 8 numbers

Location Bedrooms (5 numbers), Living hall (1

number), Dining hall (1 number) and

Family area (1 number).

G l t

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 66/97

5/13/2011

General FeaturesEach brand of air conditioner has its own features.

ECO patrol :

Senses human presence and adjust the temperature f or  more comf or t and savings.

Intelligent inver ter :

Saves up to 50% energy, enables optimum power control and extremely

efficient operation

 Advanced power ful mode :

It provides f ast comf or t with power  and strong air f low 

Super Quiet

Specially-designed air  vent efficiently reduces noise.

Blue fin condenser :

Tr ipled the lif e of its condenser  with anti-r ust coating

 Advanced + Plus e-ion air  pur if ying system with patrol sensor :

Patrol sensor  detect the dir t.

E-ions catch and deactivate micro-organism in dust Air Sweep Control :

The air sweep function moves the f lap up and down in the air  outlet, directing air  in

a sweeping motion around the room and providing comf or t to every corner.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 67/97

5/13/2011

SpecificationPANASONICCS-PS9MKH (CU-PS9MKH) ~ 1.0HP

PANASONICCS-C12KKH (CU-C12KKH) ~ 1.5HP SANYOSAP K12-AG-2.0HP

Product Dimension :Indoor 290 x 870 x 240 mmOutdoor - 510 x 650 x 230 mmProduct Dimension :

Indoor 290 X 870 X 204 mm

Outdoor - 540 X 780 X 289 mm

Product Dimension :

Indoor 275 x 845 x 180 mm

Outdoor - 540 x 848 x 320 mm

Product Weight :Indoor - 9 kgOutdoor - 24 kg

Product Weight :Indoor - 9 kg

Outdoor - 29 kg

Product Weight :

Indoor - 10 kg

Outdoor - 35 kg

Air Circulation (Indoor/Hi) :

M3/min - 10.1

Air Circulation (Indoor/Hi) :

M3/min - 11.2

Air Circulation :

M2/min - 10.5

Electricity :

Rated voltage - 230V

Running current - 3.6A

Power input - 760W

Electricity :

Rated voltage - 230V

Running current - 4.8A

Power input - 1070W

Electricity :

Rated voltage - 220-240V

Running current - 5.95A

Power input - 1290W

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 68/97

5/13/2011

Installation of the wall mounted

indoor unit

Once the location of the indoor unit isdecided, the installation can be made.It

can be installed on the wall of the room

or the partition at the height of about

8-10 feets from the floor. The steps of

installation :-

1. Make the markings as per the wall hook bracket

It is a sort of the aluminum template with all the

necessary holes and the attachments where the

template will be fit with screws.2. Fit the bracket

After making the markings for the holes, remove

the wall hook bracket and make the holes in the

wall with drilling machine at these markings.

After that, keep the bracket in place again on the

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 69/97

5/13/2011

3. Make a hole in the wall or partition:

Make a small hole of about 3 inches

near the bracket across the wall or

partition.

Through this hole the refrigerant

tubing connecting the indoor and the

outdoor will pass. These tubing are

insulated hence they need hole of large

diameter.

Refrigerant

tubing

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 70/97

5/13/2011

Figure : Shows power supply cable and electric

cable connect the indoor and outdoor unit

4. Installing the indoor unit

There are some male extensions on the bracket on which the

female counterpart of the indoor unit can be fitted. When

fitting the indoor unit the copper tubing extending from the

unit has to be passed through the hole and to outside the

room for connecting it do the outdoor unit.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 71/97

5/13/2011

The drain pipe is connected to one end of the

indoor unit; it is passed through the hole and left

free in the open space where the water can be

drained.

The power supply cable connecting the indoor and

outdoor unit and to the main supply is also passed

through the hole.

Figure : Tubing from outdoor unit to Figure : Drain pipe bedded in concrete todrain drain

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 72/97

5/13/2011

5. Tilting the indoor unit

The indoor unit is given slight tilt of about 2-3 

degree towards the drain pipe. This enablesunhindered flow of dew water towards the water

space where drain water is collected and drain

pipe is connected for removal of water.

This angle should be just sufficient to enable

flow of water without disturbing the looks of the

indoor unit due to high angle of tilt.

With this the installation of the indoor unit is

almost over and ready to be connected to the

refrigerant tubing and the outdoor unit.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 73/97

5/13/2011

Installing the outdoor unit on the external wall

The installation for outdoor unit also is quit

similar with the indoor installations and it is agood idea to keep the distance between the indoor

and outdoor units as close as possible.

The outdoor unit can also be hanged on the external

wall on some angle supports. The angles can be

fitted on the wall by using special bolts calledanchor bolts. Make sure that he wall on which the

outdoor unit is being fitted is strong enough to

bear its weight and vibrations.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 74/97

5/13/2011

Operation and function of Split unit System

A split system conditioner splits the hot

side from the cold side of the system. The

cold side, consisting of the expansion

valve and the cold coil, is generally

placed into a furnace or some other air

handler. The air handler blows air throughthe coil and routes the air throughout the

build using a series of ducts. The hot

side, known as the condensing unit,

allocated outside the house. The unit

consists of a long, spiral coil shaped

like a cylinder. Inside the coil is a fan,

to blow air through the coil, along with a

weather-resistant compressor and some

control logic.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 75/97

5/13/2011

Cost of installation

Based on this case study for residential split unit

system, the house is mainly using 8 numbers of air

conditioning system for several different areas

which is family area, living hall, dining hall and

bedrooms. The cost of installation are :

Table : Cost of Installation The cost of installation basically is influenced by the length

of wire need to be tapped off from the existing wire. The longer

the length of the wire, thus the higher the cost is. Besides

that, it is also influenced by the degree, if difficulties of

installing the air conditioner. Normally, the air conditioner is

installed before the plaster is being applied as to maintain theappearance and the aesthetic value of the house.

Air ±

conditioning(Horse Power)

Cost of Air ±

conditioning( RM )

Cost of 

Installation(RM )

Total

( RM )

1 H.P 800 ++ 180 1000

2 H.P 1600 ++ 300 2000

i

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 76/97

5/13/2011

Maintenance

The maintenance operation would be done every 6

Months. The maintenance includes the work of

chemical cleaning, filter cleaning and top up the

gas.

The cost of maintenance is basically influenced by ;

-types of maintenance

-the degree of maintaining it

-the Horse Power of the Air-conditioner.

Basically it will cost around RM120++/unit for 1HP

and RM180++ for 2HP. Further, the more refrigerantor gas that needed to be topped up, the more cost

it will incur.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 77/97

CASE STUDY2

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 78/97

2 STOREY BUNGALOW HOUSE

1R-DODQ.HODE*ROI

.HODE*ROI6XOWDQ$EGXO

$]L]6KDK.*6$$6

6HNV\HQ6KDK$ODP

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 79/97

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 80/97

BACKGROUND

� The owner of these bungalow is .DSWHQ0RKG

0D]ODQ$VKDDUL0LULD+M+DVELH

� Located at Kelab Golf Sultan Abdul Aziz Shah,

Seksyen 13, Shah Alam.� Price of the bungalow is about RM 2.2 mil

� There are 10 air conditioner installed

� Brand used: National brand (taken from the previoushouse).

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 81/97

MAINTENANCE

� Maintenance done once in 3 month.

� Cost of the maintenance is about RM120++/unit

� The maintenance include FKHPLFDOFOHDQLQJ

ILOWHUFOHDQLQJDQGWRSXSWKHJDV

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 82/97

INSTALLATION

� The installation done by the contractor that appoint

by the owner of these bungalow.

� The location of the air conditioner is decided by the

owner and sometimes advice from the specialist.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 83/97

INDOOR UNIT

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 84/97

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 85/97

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 86/97

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 87/97

OUTDOOR UNIT

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 88/97

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 89/97

PROBLEMS ENCOUNTERED

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 90/97

Air conditionerruns constantly

but doesnt cool

well

AirConditioner

wont turn

on

PROBLEMS ENCOUNTERED

Air

Conditioner

run but

doesnt cool

at all

PROBLEMSAir

Conditioner

cycles on and

off 

frequentlyOther

problems

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 91/97

RECOMMENDATIONS

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 92/97

RECOMMENDATION

Energy Efficient Cooling Systems

� Ice cooling is as simple as it sounds. Large

tanks of water freeze into ice at night, whenenergy demands are lower

�pumps the cool air from the ice into the

building�saves money, cuts pollution, eases the strain on

the power grid and can be used alongside

traditional systems.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 93/97

RECOMMENDATION (Cont'd)

Design

Compressors are allocated facing the sunrise

Operation of the condensers become inefficiency

Maintenance work

Maintenance works need to be done once a month

The best time to service an air conditioner  is

bef ore it's actually needed.

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 94/97

COST

Split unit ; different types and brand

/* 9&)

1.0HP

RM 1549

/* 9&)1.5HP

RM1849

/* +($/7+

3/861.5HP

RM1999

/* */(2HP

RM2200

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 95/97

CONCLUSION

h i THE RIGHT i diti i i

8/6/2019 FINALISED BS

http://slidepdf.com/reader/full/finalised-bs 96/97

choosing THE RIGHT air  conditioning is animpor tant decision.  A poor  choice may be costly

and f ail to provide the desired level of cooling.T

hebest system will absolutely depends on the climate,cooling needs and the design of the house.Bigger is not better .  An over sized air  conditioner does not provide more comf or t; in f act it may make

the house f eel clammy. All in all, it¶s actually up to the user s. Some maypay more when buying the air  conditioner and endup they will save the cost of  maintaining it and

likewise. Whatever  it is, it is also depend on theusage of the air conditioner  itself . If you use it moreand f requent, no matter how much you pay initiallywhen buying it, you still need to maintain itregularly.

8/6/2019 FINALISED BS