DeltaV S-Serie V11.3DeltaV S-Serie V11.3

Petr Horák

Ff DST Counting SimplifiedFf DST Counting SimplifiedFf DST Counting SimplifiedFf DST Counting Simplified

l Beginning with DeltaV v10.3.1, the system counts a maximum of 1 DST per FOUNDATION fieldbus (Ff) device referenced in the DeltaV control strategy.– Multiplexed function blocks will require only 1 DST.– A Ff device with one/multiple function blocks referenced in

one/multiple DeltaV control modules will require only 1 DST.– Existing DeltaV Ff customers will have their available DST

counts incremented when migrating to v10.3.1.

1 DST!1 DST! 1 DST!1 DST!

SS--series hardware in v11series hardware in v11SS--series hardware in v11series hardware in v11

New H1 with Integrated Segment PowerNew H1 with Integrated Segment PowerNew H1 with Integrated Segment PowerNew H1 with Integrated Segment Power

Foundation FieldBusFoundation FieldBusFoundation FieldBusFoundation FieldBusl Simplified installation

– Eliminate segment Power design and hardware– Use standard Bulk 24 VDC power to H1 Card– Redundant Power with Redundant H1 Cards– Reduced footprint– Simplified segment wiring– Enhanced segment diagnostics

Foundation FieldbusFoundation FieldbusFoundation FieldbusFoundation FieldbusBEFORE NOW

DeltaV makes Fieldbus Easy

- 2 powered H1 segments- Isolated power- 450 mA per segment - Fully redundant

Simplified H1 Segment installationSimplified H1 Segment installationSimplified H1 Segment installationSimplified H1 Segment installationl Both H1 and H1 with integrated power are

available with S-series I/O– Use Integrated power H1 card for safe area

installations of FF devices.– Use IS barrier on segment trunk with integrated power

H1– Implement FISCO and FINICO with non-powered H1

and proven in use solutions.

l Both H1 and integrated power H1 have the same functional capacity:– 2 segments per card– 16 devices per segment (total 32)– Execute DeltaV function blocks within Macro cycle

H1 Card with Integrated Power serves Zone 2 H1 Card with Integrated Power serves Zone 2 Devices (Ex Devices (Ex nLnL) via Segment Protector) via Segment ProtectorH1 Card with Integrated Power serves Zone 2 H1 Card with Integrated Power serves Zone 2 Devices (Ex Devices (Ex nLnL) via Segment Protector) via Segment Protector

Trunk 28-30 VDC 400 mA max.Ex nA

Spurs Ex nL Spurs Ex nL

Terminator switchbuilt in

H1 Card with Integrated Power serves Zone 2 H1 Card with Integrated Power serves Zone 2 Devices (Ex Devices (Ex nLnL) via Segment Protector) via Segment ProtectorH1 Card with Integrated Power serves Zone 2 H1 Card with Integrated Power serves Zone 2 Devices (Ex Devices (Ex nLnL) via Segment Protector) via Segment Protector

H1 Card with Integrated Power serves Zone 1 H1 Card with Integrated Power serves Zone 1 and Zone 0 Devices (Ex and Zone 0 Devices (Ex iaia) via Field Barriers) via Field BarriersH1 Card with Integrated Power serves Zone 1 H1 Card with Integrated Power serves Zone 1 and Zone 0 Devices (Ex and Zone 0 Devices (Ex iaia) via Field Barriers) via Field Barriers

Trunk 28-30 VDC 400 mA max.Ex e

Spurs Ex ia Spurs Ex ia

Terminator switchbuilt in Exe Parts are all Covered

H1 Card with Integrated Power serves Zone 1 H1 Card with Integrated Power serves Zone 1 and Zone 0 Devices (Ex and Zone 0 Devices (Ex iaia) via Field Barriers) via Field BarriersH1 Card with Integrated Power serves Zone 1 H1 Card with Integrated Power serves Zone 1 and Zone 0 Devices (Ex and Zone 0 Devices (Ex iaia) via Field Barriers) via Field Barriers