DAIKINAIRCON TRAINING CENTER
Using
DAIKINAIRCON TRAINING CENTER
Bahasan
1. General Information
2. Refrigerant Circuit
3. Functional Parts
4. Installation
5. Field Settings
6. Functions
7. Troubleshooting
DAIKINAIRCON TRAINING CENTER
1. General Information: Indoor Unit
11 Types
79 Models
Ref: ED34-762; Pg 4
DAIKINAIRCON TRAINING CENTER
1. General Information: Combination Of Outdoor Unit
7 Base Model
5 ~ 54 HP
41 Combinations:
25 - Normal Series
(Space Saving)
16 High COP Series
(Energy Saving)
Max. 64 FCUs connectable
Ref: ED34-762; Pg 5
DAIKINAIRCON TRAINING CENTER
Hi-COP (energy saving) type
RXQ-PHY1 Energy Saving Type
Normal (space saving) type
RXQ-PY1
1. General Information: Outdoor Unit Nomenclature
Ref: ED34-762; Pg 10
DAIKINAIRCON TRAINING CENTER
1. General Information: Model Selection Connectable Indoor Units No. & Capacity:
5 8 10 12 14 16 18
5HP 1 1 8 1
8HP 1 1 13 1
10HP 1 1 16 2
12HP 1 1 19 2
14HP 1 1 23 3
16HP 1 1 26 3
18HP 1 1 29 3
20HP 2 1 1 32 3
22HP 2 1 1 35 4
24HP 2 1 1 39 4
26HP 2 1 1 42 4
28HP 2 1 1 45 5
30HP 2 1 1 49 5
32HP 2 2 52 6
34HP 2 1 1 55 6
36HP 2 2 58 6
38HP 3 1 1 1 61 6
40HP 3 1 2 7
42HP 3 1 1 1 7
44HP 3 1 2 7
46HP 3 1 2 8
48HP 3 1 2 8
50HP 3 1 2 9
52HP 3 1 2 9
54HP 3 3 9
64
No. of
Compressor
Normal Series (Space Saving Series)
System
Capacity
No. of
Units
Module No. of Connectable
Indoor Units
Ref: ED34-762; Pg 11
: Single Module : Double Module : Triple Module
DAIKINAIRCON TRAINING CENTER
Connectable Indoor Units No. & Capacity:
5 8 10 12 14 16 18
16HP 2 2 26 2
18HP 2 1 1 29 3
24HP 3 3 39 3
26HP 3 2 1 42 3
28HP 3 2 1 45 3
30HP 3 1 1 1 48 5
32HP 3 1 2 52 5
34HP 3 1 2 55 6
36HP 3 3 58 6
38HP 3 2 1 61 7
40HP 3 2 1 7
42HP 3 2 1 7
44HP 3 1 2 8
46HP 3 1 1 1 8
48HP 3 3 9
50HP 3 2 1 9
64
System
Capacity
No. of
Units
Module No. of
Connectable
High COP Series (Energy Saving Series)
No. of
Compressor
16 Models
1. General Information: Model Selection
Ref: ED34-762; Pg 11
: Single Module : Double Module : Triple Module
DAIKINAIRCON TRAINING CENTER
1. General Information: Compatibility
Ref: ED34-762; Pg 11
Outdoor Indoor
Series Refrigerant Type K, M (R22) MA, P (R410A)
K R22 YES NO
M R22 YES NO
MA NO YES
P NO YES
DAIKINAIRCON TRAINING CENTER
2. Refrigerant Circuit
RXQ5P
Ref: ED34-762; Pg 395
DAIKINAIRCON TRAINING CENTER
2. Refrigerant Circuit
RXQ8P
Ref: ED34-762; Pg 396
DAIKINAIRCON TRAINING CENTER
2. Refrigerant Circuit
RXQ10P,12P
Ref: ED34-762; Pg 397
DAIKINAIRCON TRAINING CENTER
2. Refrigerant Circuit
RXQ14P,16P,18P
Ref: ED34-762; Pg 398
DAIKINAIRCON TRAINING CENTER
4. Installation: Flexible Design
Ref: ED34-762; Pg 15
(RXQ8P-54P)
(RXQ5P)
DAIKINAIRCON TRAINING CENTER
4. Installation: Field Refrigerant Piping
Ref: ED34-762; Pg 16
DAIKINAIRCON TRAINING CENTER
4. Installation: Field Refrigerant Piping
Ref: ED34-762; Pg 528
DAIKINAIRCON TRAINING CENTER
4. Installation: Field Refrigerant Piping
Ref: ED34-762; Pg 528
New Calculation Method
DAIKINAIRCON TRAINING CENTER
Outdoor Unit Multi Connection Piping Kit:
BHFP22P100.151
4. Installation: Field Refrigerant Piping
Ref: ED34-762; Pg 516
DAIKINAIRCON TRAINING CENTER
Outdoor Unit Multi Connection Piping Kit:
RX(Y)Q18-32MA (BHFP22MA90)
RX(Y)Q34-48MA (BHFP22MA135)
Normal Series (Space Saving Series)
RX(Y)Q20-36P (BHFP22P100)
RX(Y)Q38-54P (BHFP22P151)
High COP Series (Energy Saving Series)
RX(Y)Q16-18PH (BHFP22P100)
RX(Y)Q24-50PH (BHFP22P151)
4. Installation: Field Refrigerant Piping
Ref: ED34-762; Pg 516
DAIKINAIRCON TRAINING CENTER
Outdoor Unit Multi Connection Piping Kit:
A View
7.5
7.5
1. Install the branch pipe of an
Outdoor unit Multi Connection
Piping Kit horizontally.
2. If not installed correctly, there is
a possibility of break down.
3. Angle tolerance is 15o
A View
Wrong Good
Floor
4. Installation: Field Refrigerant Piping
Ref: ED34-762; Pg 516
DAIKINAIRCON TRAINING CENTER
Outdoor Unit Multi Connection Piping Kit:
Pastikan terdapat jalur yang lurus sekitar 500 mm atau lebih di depan tempat
masuk cabang y.
Jalur lurus cabang ke dua harus dalam jarak
dengan unit outdoor.
10HP 930mm
16HP 1240mm
Cabang Y dan elbow adalah accessories standar dari connection kit.
Elbow
Brazing:Field Piping
500mm
or more
Outdoor Unit Outdoor Unit Outdoor Unit
1st Branch 2nd Branch
Y branch
4. Installation: Field Refrigerant Piping
Ref: ED34-762; Pg 516
DAIKINAIRCON TRAINING CENTER
Outdoor Unit Multi Connection Piping Kit:
4. Installation: Field Refrigerant Piping
Ref: ED34-762; Pg 516
500
Dibutuhkan
500mm pipa lurus T Joint
Pencabutan dari
depa juga
memungkinkan
Y Joint
DAIKINAIRCON TRAINING CENTER
Outdoor Unit Multi Connection Piping Kit:
4. Installation: Field Refrigerant Piping
Pemipaan pada sisi kiri
500 Konstruksi
memungkinkan di
bagian dalam casing
Y Joint
Spesifikasi dimensi pipa untuk instalasi
DAIKINAIRCON TRAINING CENTER
500
500 mm pipa lurus
sebelum Y-joint !
Y Joint
Konstruksi pemipaan ke belakang
Spesifikasi dimensi pipa untuk instalasi
4. Installation: Field Refrigerant Piping
DAIKINAIRCON TRAINING CENTER
Persiapan
sambungkan tabung N2, tabung refrigerant & pompa vacuum ke outdoor unit.
4. Installation: Air Tight Test & Vacuum Drying
DAIKINAIRCON TRAINING CENTER
Persiapan :
sambungkan tabung N2 , tabung refrigerant & pompa vacuum ke outdoor unit.
shutoff valve & valve A~C harus terbuka atau tetutup sesuai dengan tabel
Test press di lakukan hanya pada service port liquid & gas .
4. Installation: Air Tight Test & Vacuum Drying
DAIKINAIRCON TRAINING CENTER
Test presst:
test press di papa liquid & gas dengan tekanan 40kg/cm2 or 568Psi (Max.) dengan N2 gas.
test pressure dilakukan 24hrs. Jika tekanan tidak turun sistem tidak bocor
jika tekanan turun,cari kebocoran dan test kembali.
Pemvakuman:
pemvakuman dilakukan pada pipa gas & liquid dengan menggunakan pompa vakum selama 2jam atau lebih samapai mendekati 760mmHg.
biarkan selama 1hr & periksa kembali.
jika tidak ada masalah, tambah refrigerant & check operation.
4. Installation: Air Tight Test & Vacuum Drying
Ref: ED34-762; Pg 538
DAIKINAIRCON TRAINING CENTER
4. Installation: Additional Refrigerant Charge Additional Refrigerant Charge:
Calculate additional charge amount as below.
Ref: ED34-762; Pg 527
DAIKINAIRCON TRAINING CENTER
4. Installation: Additional Refrigerant Charge Additional Refrigerant Charge:
Calculate additional charge amount as below.
ALWAYS charge using R410A refrigerant gas. (Charge in liq. State ONLY!)
Below is the pre-charge amount of refrigerant in the respective system.
HP
Type 5 8 10 12 14 16 18
M-Series (R22)
8.5 13.1 13.9 15.6 17.1 18.6 ---
MA-series
5.6 7.6 8.6 10.4 11.6 12.4 ---
P-Series
6.2 7.7 8.4 10.0 12.3 12.5 12.7
(Kg) Ref: ED34-762; Pg 374
DAIKINAIRCON TRAINING CENTER
4. Installation: Additional Refrigerant Charge Additional Refrigerant Charge:
Calculate additional charge amount as below.
ALWAYS charge using R410A refrigerant gas. (Charge in liq. State ONLY!)
Below is the pre-charge amount of refrigerant in the respective system.
Connect as below & perform manual refrigerant charging from liq. side.
Ref: ED34-762; Pg 543
DAIKINAIRCON TRAINING CENTER
4. Installation: Additional Refrigerant Charge Additional Refrigerant Charge:
Calculate additional charge amount as below.
ALWAYS charge using R410A refrigerant gas. (Charge in liq. State ONLY!)
Below is the pre-charge amount of refrigerant in the respective system.
Connect as below & perform manual refrigerant charging from liq. side.
If additional charge above is not able to be charged fully, perform by field setting (Setting Mode 2 item no. 20).
Ref: ED34-762; Pg 543
DAIKINAIRCON TRAINING CENTER
4. Installation: Additional Refrigerant Charge Additional Refrigerant Charge:
Calculate additional charge amount as below.
ALWAYS charge using R410A refrigerant gas. (Charge in liq. State ONLY!)
Below is the pre-charge amount of refrigerant in the respective system.
Connect as below & perform manual refrigerant charging from liq. side.
If additional charge above is not able to be charged fully, perform by field setting (Setting Mode 2 item no. 20).
Perform Check operation by pressing the button on the outdoor PCB.
Press & Hold for 5sec
Ref: ED34-762; Pg 544
DAIKINAIRCON TRAINING CENTER
4. Installation: Additional Refrigerant Charge Additional Refrigerant Charge:
Calculate additional charge amount as below.
ALWAYS charge using R410A refrigerant gas. (Charge in liq. State ONLY!)
Below is the pre-charge amount of refrigerant in the respective system.
Connect as below & perform manual refrigerant charging from liq. side.
If additional charge above is not able to be charged fully, perform by field setting (Setting Mode 2 item no. 20).
Perform Check operation by pressing the button on the outdoor PCB.
Check operation will last for about 40mins and stops automatically.
Check operation must be performed if not U3 error code will appear.
After Check operation completes, perform test run of the system.
Ref: ED34-762; Pg 545
DAIKINAIRCON TRAINING CENTER
6. Functions: Compressor PI Control
Ref: Si34-601; Pg 98
DAIKINAIRCON TRAINING CENTER
Outdoor Unit Type
(HP)
Max No. of Steps Max Freq. (Hz)
5 20 18
210
188
8 37 24 266
10 37 37 210
12 37 37 210
14 35 51 266
16 35 51 266
18 55 266
* Note: Compressor Steps variation depends on the compressor PI Control.
Ref: Si34-601; Pg 98
6. Functions: Compressor PI Control
DAIKINAIRCON TRAINING CENTER
Single Unit Sys. Max No. of Steps Max Freq. (Hz)
35 210
55 266
2-Unit Multi Sys. Max No. of Steps Max Freq. (Hz)
52 210
60 266
3-Unit Multi Sys. Max No. of Steps Max Freq. (Hz)
67 210
71 266
* Note: Compressor Steps variation depends on the compressor PI Control.
Ref: Si34-601; Pg 98
6. Functions: Compressor PI Control
DAIKINAIRCON TRAINING CENTER
* Note: Figures above will vary when system is set to high static pressure or capacity
precedence mode
Step
No.
Fan revolution (rpm)
RXYQ5P RXYQ8P RXYQ10P
RXYQ12P,14P RXYQ16P RXYQ18P
FAN1 FAN2 FAN1 FAN2 FAN1 FAN2
0 0 0 0 0 0 0 0 0 0
1 285 350 350 230 0 230 0 395 0
2 315 370 370 380 0 380 0 460 0
3 360 400 400 290 260 290 260 570 0
4 450 450 460 375 345 375 345 385 355
5 570 540 560 570 540 570 540 550 520
6 710 670 680 720 690 720 690 800 770
7 951 760 821 1091 1061 1091 1061 1136 1106
8 951 796 821 1136 1106 1136 1106 1166 1136
6. Functions: Step Control Of Outdoor Unit Fans
Ref: Si34-601; Pg 107
DAIKINAIRCON TRAINING CENTER