Post on 27-Apr-2020
1 Part - A : Building works
2 Part - B : Internal Sanitary & Water Supply Installation
3 Part - C : Site Development Works
4 Part - D(i): Fire Fighting works
Part - D(ii) : Fire Detection & Alarm System
5 Part - E : Electrical Works including Lift
6 Part - F: HVAC works
Total
Rebate if any
Grand Total
Sl. No. Particulars
COST ABSTRACT
Name of Work: Construction of Research Park at IITG Campus.
Amount (Rs.)
Item no. Description Unit Quantity Rate in figure (Rs.) Rate in words Total Amount(Rs.)
1 BORED CAST IN SITU PILES
a
Boring, providing and installation bored cast-in-situ
reinforced cement concrete piles of grade M-30 of
specified diameter and length below the pile cap, to
carry a safe working load not less than specified,
excluding the cost of steel reinforcement but
including the cost of boring with bentonite solution
and temporary casing of appropriate length for
setting out and removal of same and the length of
the pile to be embedded in the pile cap etc. by
percussion drilling using Direct mud circulation
(DMC) or Bailer and chisel technique by tripod and
mechanical Winch Machine all complete, including
removal of excavated earth with all its lifts and
leads (length of pile for payment shall be measured
up to bottom of pile cap and all operations shall be
as per the requirements of IS:2911 part-I and good
engineering practice).
600 mm dia piles Rm 16100.00
b
Vertical load testing of piles in accordance with IS
2911 (Part IV) including installation of loading
platform by Kentledge/Anchor piles method and
preparation of pile head or construction of test cap
and dismantling of test cap after test etc. complete
as per specification & the direction of Engineer in-
charge.Note: 1. Initial and Routine Load Test shall not be
carried out by Dynamic method of testing.
Note: 2. Testing agency shall submitt the design of
loading platform for the approval of Engineer-in-
charge.
Initial load Test shall be done upto 2.5 times the
Safe Load capacity or up to the penetration of 10%
of the stem diameter.)
iInitial load test on Single pile above 50 tonne and
upto 100 tonne Safe capacity Per test 4
Bill of Quantity
Name of Work: Construction of Research Park at IITG Campus.
Part-A(Building works)
ii
Initial load test on Single pile above 100 tonne and
upto 150 tonne capacity (As per Design required) Per test 4
iii
Routine load test on single piles above 50 tonne
and upto 100 tonne Safe capacity pile in
accordance with IS Code of practice IS: 2911 (part
IV) by Kentledge method including preparation of
pile head etc forSingle pilePer test 12.00
c
Integrity testing of Pile using Low Strain/ Sonic
Integrity Test/ Sonic Echo Test method in
accordance with IS 14893 including surface
preparation of pile top by removing soil, mud, dust
& chipping lean concrete lumps etc. and use of
computerised equipment and high skill trained
personal for conducting the test & submission of
results, all complete as per direction of Engineer-in-
charge. Per test 629.00
2 EARTH WORKS
a
Earth work in excavation by mechanical means
(Hydraulic excavator) / manual means in foundation
trenches or drains (not exceeding 1.5 m in width or
10 sqm on plan), including dressing of sides and
ramming of bottoms, including all lifts and leads
and getting out the excavated soil and disposal of
surplus excavated soil as directed, within the IITG
campus.All kinds of soil. Cum. 3695.00
b
Filling with available excavated earth (excluding
rock) in trenches, plinth, sides of foundations etc. in
layers not exceeding 20cm in depth, consolidating
each deposited layer by ramming and watering
including all lifts and leads. Cum 3374.00
c
Supplying and filling in plinth with imported granular
soil of approved quality sand under floors, including
watering, ramming, consolidating and dressing
complete. Cum 2416.00
3 ANTI TERMITE TREATMENT
Supplying and injecting chemical emulsion for pre-
constructional anti-termite treatment and creating a
chemical barrier under & all-round the column pits,
wall trenches, basement excavation, top surface of
plinth filling, junction of wall and floor, along the
external perimeter of building, expansion joints,
surroundings of pipes and conduits etc. complete.
Stages shall be treated as per CPWD specification.
(Plinth area of the building at ground floor level only
shall be measured for payments).- With
Chlorpyriphos Emulsifiable concentrate 20%
with 1% concentration./ or sqm 2757.00
4 CEMENT CONCRETE WORK
Providing and laying in position cement concrete
of specified grade excluding the cost of centering
and shuttering - All work up to plinth level :
a1:2:4 (1 cement : 2 coarse sand (zone-III) : 4
graded stone aggregate 20 mm nominal size). Cum 371.00
b1:3:6 (1 Cement : 3 coarse sand (zone-III): 6
graded stone aggregate 40 mm nominal size). Cum 437.00
c
Providing and laying damp-proof course 50mm
thick with cement concrete 1:2:4 (1 cement : 2
coarse sand(zone-III) : 4 graded stone aggregate
20mm nominal size) with approved water proofing
compound as per manufacturers' specifications. Sqm 114.00
d
Providing and laying of cement concrete of
proportion 1:5:10 (1cement : 5 sand : 10 AAC block
bats of size 40mm) in sunken floors at all floors,
heights and levels cum 105.00
e
Making plinth protection 50mm thick of cement
concrete 1:3:6 (1 cement : 3 coarse sand : 6
graded stone aggregate 20 mm nominal size) over
75mm thick bed of dry brick ballast 40 mm nominal
size, well rammed and consolidated and grouted
with fine sand, including necessary excavation,
levelling & dressing & finishing the top smooth.Sqm 198.00
5 CENTERING AND SHUTTERING WORK
Centering and shuttering including strutting,
propping etc. and removal of form for all heights :a Foundations, footings, bases for columns Sqm 591.00
bWalls (any thickness) including attached pilasters,
butteresses, plinth and string courses etc. Sqm 8651.00
cSuspended floors, roofs, landings, balconies and
access platform. with water proof ply 12 mm thick Sqm 17774.00
dLintels, beams, plinth beams, girders, bressumers
and cantilevers. with water proof ply 12 mm thick Sqm 18100.00
eColumns, Pillars, Piers, Abutments, Posts and
Struts Sqm 9804.00
fStairs, (excluding landings) except spiral-staircases
Sqm 1214.00
g Extra for shuttering in circular work. Sqm 1390.00
h
Extra for additional height in centering, shuttering
where ever required with adequate bracing,
propping etc., including cost of de-shuttering and
decentering at all levels, over a height of 3.6 m, for
every additional height of 1 metre or part thereof
(Plan area to be measured).
iSuspended floors, roofs, landing, beams and
balconies (Plan area to be measured) Sqm 2179.00
6 STEEL REINFOCEMENT WORKS
Steel reinforcement for R.C.C. work including
straightening, cutting, bending, placing in position
and binding all complete upto plinth level & above
as per specifications and relevant IS Codes.
Thermo-Mechanically Treated bars of grade Fe-
500D Kg 2655621.00
7 RCC WORKS IN M-25 GRADE
Providing and laying in position machine batched
and machine mixed design mix M-25 grade
cement concrete for reinforced cement concrete
work, using cement content as per approved design
mix, including pumping of concrete to site of laying
but excluding the cost of centering, shuttering,
finishing and reinforcement, including admixtures in
recommended proportions as per IS: 9103 to
accelerate, retard setting of concrete, improve
workability without impairing strength and durability
as per direction of Engineer-in-charge.a All works upto plinth level Cum 253.00
b All works from plinth level upto floor V level Cum 120.00
8 RCC WORKS IN M-30 GRADE
Providing and laying in position machine batched
and machine mixed design mix M-30 grade
cement concrete for reinforced cement concrete
work, using cement content as per approved design
mix, including pumping of concrete to site of laying
but excluding the cost of centering, shuttering,
finishing and reinforcement, including admixtures in
recommended proportions as per IS: 9103 to
accelerate, retard setting of concrete, improve
workability without impairing strength and durability
as per direction of Engineer-in-charge.a All works upto plinth level Cum 3189.00
b All works from plinth level upto floor V level Cum 4758.00
c
Including extra for R.C.C./ B.M.C/ R.M.C. work
above floor V level for each four floors or part
thereof.d All works above V level upto floor IX level Cum 3441.00
9 MASONRY WORKS
a
Brick work with common burnt clay F.P.S. (non
modular) bricks of class designation 7.5 in
foundation and plinth in Cement mortar 1:6 (1
cement : 6 coarse sand) Cum 410.00
b
Providing and laying autoclaved aerated cement
blocks masonry with 100 mm thick AAC blocks in
super structure above plinth level up to floor V level
in cement mortar 1:4 (1 cement : 4 coarse sand ).
The rate includes providing and placing in position
2 Nos 6 mm dia M.S. bars at every third course of
masonry work. Cum 37.00
c
Providing and laying autoclaved aerated cement
blocks masonry with 150mm/200mm/230 mm thick
AAC blocks in super structure above plinth level up
to floor V level with RCC band at sill level and lintel
level with approved block laying polymer modified
adhesive mortar all complete as per direction of
Engineerin- Charge. (The payment of RCC band
and reinforcement shall be made for seperately).Cum 1732.00
d
Extra over item no-9(c) above for works above floor-
V level up to floor-IX level (Including extra for each
four floors or part thereof by mechanical means). Cum 700.00
e
Half brick masonry with common burnt clay F.P.S.
(non modular) bricks of class designation 7.5 in
superstructure above plinth level up to floor V level
Cement mortar 1:4 ( 1 cement :4 coarse sand) sqm 546.00
f
Extra over item 9e above for half brick masonry in
superstructure, above floor V level for every four
floors or part thereof . sqm 273.00
g
Extra for Providing and placing in position two
numbers 6mm dia. M.S. bars or equivalent hoop
iron at every third coarse of all half brick masonry
works at all floors, heights, levels. sqm 546.00
h
Making circular opening for exhaust fan upto 600
mm dia in AAC masonry work by providing proper
precast RCC ring of required diameter on edgeat all
floors, heights and levels. each 100.00
i
Honey-comb brick work 10/11.4 cm thick with
common burnt clay bricks of class designation 7.5
in super structure with cement mortar 1:4 (1
cement : 4 coarse sand)at all floors, heights, levels.
sqm 100.00
10 FLOORING
a
Providing flat brick soling under foundation, floor,
plinth beam including packing with coarse sand and
watering etc complete as directed with bricks class
designation-75 in cement mortar in proportion 1:4
including curing complete as specified and as
directed. sqm 500.00
b
Providing and laying (double charged full body)
vitrified floor tiles of minimum 600mmx600mm
sizes (thickness as per manufacturer's
specifications) conforming to IS : 15622 of
approved make in all colours and shades, laid on
20mm thick cement mortar 1:4 (1 cement : 4 coarse
sand) including grouting the joints with EPOXY tile
jointing compounds of matching colours etc.,
complete at all floors, levels and
heights.(rooms,balcony,kitchen)
(i)in floors including use of specified sizes of spacers
sqm 3661.50
(ii) in Skirting and Risers of steps sqm 350.00
c
Providing and laying rectified Glazed Ceramic floor
tiles of size 400x400 mm or more (thickness to be
specified by the manufacturer), of 1st quality
conforming to IS : 15622, of approved make, in all
colours, shades, except White, Ivory, Grey, Fume
Red Brown, laid on 20 mm thick Cement Mortar 1:4
(1 Cement : 4 Coarse sand), in floors including
Filling the joints with EPOXY tiles jointing
compound of matching colours at toilets at all
floors. sqm 50.00
d
Providing and laying in floor heavy duty vitrified
antiskid matt finish tiles of minimum thickness 10
mm without warpage of approved design and
manufacturer laid on 20mm thick cement mortar
1:4 (1 cement:4 coarse sand) including filling the
joints with pigmented tile joint filler Nitotile-GR or
equivalent of matching shade and approved
manufacturer as per manufacturers specification
etc. and cleaning the surface with detergent and
water complete (size 300mm x 300mm) (Laundry
and Gym.) sqm 85.00
e
Providing and fixing 18mm thick mirror polish
granite slab of approved colour etc. over 20mm
cement mortar 1:3 (1 cement : 3 coarse sand) all
complete at all floors, heights, levels.
(i)
In Floors, landings,lift lobby,podium, kitchen slabs
etc of all sizes etc in approved patterns.(Area of
slab above 0.50sqm) sqm 1019.25
(ii)In kitchen platform, wash basin counter,steps,
risers,skirting etc.(Area of slab up to 0.50sqm). sqm 20.00
(iii) In lift facade (Area of slab over 0.50sqm). sqm 30.00
(iv)
Extra for providing edge moulding to 18mm thick
marble stone counters,Vanities etc. including
machine polishing to edge to give high gloss finish
etc. complete as per design approved by Engineer-
in-Charge Granite work Metre 30.00
(v)
Extra for providing opening of required size &
shape for wash basins/kitchen sink in kitchen
platform, vanity counters and similar location in
marble/stone work including necessary holes for
pillar taps etc .including rubbing and polishing of cut
edges to bring to the original colour etc. complete.each 19.00
(vi)
Extra for fixing marble /granite stone over and
above corresponding basic item, in facia and drops
of width upto 150 mm with epoxy resin based
adhesive including cleaning etc. complete. m 19.00
f
Providing and laying CC pavement of mix M25 with
ready mixed concrete from batching plant. The
ready mixed concrete shall be laid and finished with
screed board vibrator, vacuum dewatering process
and finally finished by floating, brooming with wire
brush etc. complete as per specification and
directions of Engineer-incharge.(Parking area)cum 150.00
g
Providing and fixing markana Chak doongri marble
stone 18 mm thick, (average) over 20 mm thick
base mortar of proportion 1:4 (1 cement: 4 coarse
sand) laid and jointed with cement slurry including
rubbing and polishing complete in all respects
including cutting the stone to make noutch/ offset
on all corners vertical and horizontal and make as
per noutch details in drawing and directed (in
door/window sill) of required sizes in single piece.sqm 134.00
h
Cement plaster skirting of all height with cement
mortar 1:3 ( 1 cement : 3 coarse sand) finished with
floating coat of neat cement including rounding of
junctions with floor where required. 18 mm thick
sqm 1050.00
i
52 mm thick cement concrete flooring with
concrete hardener topping, under layer 40 mm
thick cement concrete 1:2:4 (1 cement : 2 coarse
sand : 4 graded stone aggregate 20 mm nominal
size) and top layer 12 mm thick cement hardener
consisting of mix 1:2 (1 cement hardener mix : 2
graded stone aggregate 6 mm nominal size) by
volume, hardening compound mixed @ 2 litre per
50 kg of cement or as per manufacturer's
specifications. This includes cost of cement slurry,
but excluding the cost of nosing of steps etc.
complete.(Electrical room & AHU) Sqm 76.00
j
25 mm thick Kota stone slab flooring over 20
mm (average) thick base laid over and jointed with
grey cement slurry mixed with pigment to match the
shade of the slab, including rubbing and polishing
complete with base of cement mortar 1 : 4 (1
cement : 4 coarse sand) Sqm 315.00
k
8 mm thick Laminated wooden flooring of National
finish with classic look of AC4 grade, LWF-
CLASSICA 832 OAK BRIONE PLANK laid over 40
mm thick leveling layer of cement concrete 1:2:4 (1
cement : 2 coarse sand : 4 graded stone aggregate
10 mm nominal size) to be paid separately, levelled
smooth and finished complete with tongue &
groove joint, end and T profile wherever required
with adhesive bonding quality conforming to IS :
2046 Type S, including cost of adhesive of
approved quality. (Seminar rooms )Sqm 133.00
l
8 mm thick Laminated wooden flooring of National
finish with classic look of AC4 grade, LWF-
CLASSICA 832 OAK BRIONE PLANK laid over 25
mm thick waterproof ply base over M. S. frame
work paid separately,levelled smooth and finished
complete with tongue & groove joint, end and T
profile wherever required with adhesive bonding
quality conforming to IS : 2046 Type S, including
cost of adhesive of approved quality.(Gymnasium)Sqm 40.00
m
12 mm thick Laminated wooden flooring of
National finish with classic look of AC4 grade, LWF-
CLASSICA 832 OAK BRIONE PLANK laid over 15
mm thick Cement Plaster 1:4 (1 cement : 4 coarse
sand ) to be paid separately, levelled smooth and
finished complete with tongue & groove joint, end
and T profile wherever required with adhesive
bonding quality conforming to IS : 2046 Type S,
including cost of adhesive of approved
quality.(Seminar rooms skirting) Rm 67.00
n
Providing and laying Antiskid Vitrified floor tiles
in sizes (600 x 600) mm (thickness to be specified
by the manufacturer) with water absorption less
than 0.08% and conforming to IS: 15622, of
approved make, in all colours and shades, laid on
20mm thick cement mortar 1:4 (1 cement : 4 coarse
sand), jointing with grey cement slurry @ 3.3kg/sqm
including grouting the joints with white cement and
matching pigments etc., complete.(Toilets)Sqm 103.00
o
Providing and fixing PVC sheet flooring of thickness
of 2 mm with HOF-TORO SC/TARKETT the size of
2m x 20m . The product should be homogeneous
and single layered with PUR (Clean Sweep)range.
The wear surface shall consist of impregnated
polyurethane homogeneous mixture of PVC with
TRUESHIELD technology, Plasticizers without
DOP, Urethane, color pigments and filler
calendared to form a sheet. Color and pattern
details shall be dispersed throughout the thickness
of the wear layer. It should conform to group "T"
wear resistance as per EN 685, Flammability
resistance of class Bfl-s1 as per GB8624-2006,
Dynamic coefficient of friction of class DS as per
EN 13893, Thermal Resistance of 0.072m2K/W as
per EN 12667, Thermal conductivity of 0.071W/mK
as per EN12524, impact sound reduction of 3dB as
per ISO 10140, Slip Resistance of class R9 as per
DIN 51130, Residual indentation of 0.03mm as per
GB/T 4085-2005, Color fastness rating of ≥6 as per
ISO 105-B02, total weight being 3.3kg/m2 as per
EN430. The product shall be suitable for
applications in class 23/34/43 areas as per EN685.
Product shall exhibit antistatic behavior, resistance
to bacteria, resistance to chemical, resistance to
staining, suitability to castor chair. The product shall
be Floor Score certified with no SVHC content
published by European Chemicals Agency
(REACH). Product shall contribute to LEED points
under Indoor environmental quality category.
Equivalent to Armstrong Medintech Plus. Sqm 227.00
p
Extra for joining of PVC sheets by Hot Weelding
Chord. Rm 150.00
11 DADO
Providing and fixing 1st class degital ceramic tiles
of approved designs and makes of minimum
thickness 5.6 mm in dado in any pattern over 12
mm thick cement plaster 1:3 (1 cement : 3 coarse
sand) and jointed with tile jointing compound of
approved manufacturer complete as directed.a 300mm x 600mm in kitchen,toilets,OHT. sqm 750.00
b
Kota stone slabs 20 mm thick in risers of steps,
skirting, dado and pillars laid on 12 mm (average)
thick cement mortar 1:3 (1 cement: 3 coarse sand)
and jointed with grey cement slurry mixed with
pigment to match the shade of the slabs, including
rubbing and polishing complete. Sqm 25.00
cExtra for pre finished nosing in treads of steps
of Kota stone/ sand stone slab. Rm 10.00
dExtra for Kota stone/ sand stone in treads of steps
and risers using single length up to 1.05 metre. Sqm 25.00
e
18 mm thick Cement plaster skirting up to 30 cm
height, with cement mortar 1:3 (1 cement : 3 coarse
sand), finished with a floating coat of neat cement.Sqm 379.00
f
Extra for making chequers of approved pattern on
cement concrete floors, steps, landing, pavements
etc. Sqm 105.00
12 DOORS AND WINDOWS
a
Providing and fixing pressed steel door frames
conforming to IS: 4351, manufactured from
commercial mild steel sheet of 1.60 mm thickness,
including hinges, jamb, lock jamb, bead and if
required angle threshold of mild steel angle of
section 50x25 mm, or base ties of 1.60 mm,
pressed mild steel welded or rigidly fixed together
by mechanical means, including M.S. pressed
butt hinges 2.5 mm thick with mortar guards, lock
strike plate and shock absorbers as specified and
applying a coat of approved steel primer after pre-
treatment of the surface as directed by Engineerin-
charge: [Profile E] Fixing with adjustable lugs with
split end tail to each jamb Rm 50.00
b
Providing and fixing of WPC (Wood Polyster
Composite)Door frame of size 125 x 65mm solid
with special wooden hot stamping/pigmented of
similar colour of door shutterduly attached with
Architrave of same colour of 64.2mm width and
12mm thickness on all the borders of the door
frame. The Door Frame should be, insect
,pest,water,acid proof and it should also be certified
by IGBC. Rm 595.00
c
Providing and fixing of WPC ( Wood Polyster
Composite)Door Panel/shutter made of extruded
multicavity one piece having over all thickness of
30mm with side thickness portion of 15mm, with
high pressure laminate of desired colour duly
compressed with closing of bottom and upper side
and suitable reinforced at hinges side to hold
screws. The door panel should be insect
,pest,water,acid proof and it should also be certified
by IGBC. The product should be paintable and
polishable. 30 mm thick sqm 285.00
d
Providing and fixing Hollow metal fire rated doors
as per IS 3614 part-1 & part-2 for stability and
integrity. Pressed Galvanized steel confirming to IS
277 with the following specification. Recommended
fire door shall have doors tested at CBRI for
maximum rating of 2 hrs tested . Individual Test
certificates should also be available for glass used
in vision lites confirming the required fire ratings
/panels being a part of the fire door assembly.
Doors should be finished in Thermosetting Powder
Coating desired RAL Shades. Manufacturer test
certificate shall cover doors both single & double
leaf doors and Hardwares should pass European
certificate "CE" of conformity / UL with required fire
ratings. Any deviation in specification and sheet
thickness other than what is mentioned in the test
certificates are not allowed. Proper label confirming
the type of door and the hourly rating is mandatory.
Approved manufacturer Navair International Ltd or
equivalent subject to approval. And should be ISO
Certified company. The approved manufacturer are
Navair,AGNI suraksha, Godrej or equivalent .
Door frame shall be double rebate profile of
minimum size 154mm X 77 mm made out of
1.60mm (16gauge) minimum thick galvanized steel
sheet. NDRF 154x77 Frames shall be Butt jointed
and field assembled with self bolted. The frames
should be finished with Thermosetting Powder
Coating in desired RAL Shade. All provision should
be mortised, drilled and tapped for receiving
appropriate hardware. Frames should be provided
with back plate bracket and anchor fasteners for
installation on a finished plastered masonry wall
opening.
Door leaf shall be minimum 49mm thick fully flush
double skin door with or without vision lite. Door
leaf shall be manufactured from 1.20mm minimum
thick galvanised steel sheet. The internal
construction of the door should be rigid
reinforcement pads for receiving appropriate
hardware. The infill material shall be Rockwool
treated with Viper FRS 881 LH. All doors NSD
12049 shall be factory prepped for receiving
appropriate hardware and provided with necessary
reinforcement for hinges, locks, and door closers.
The edges should be interlocked with a bending
radius of 1.4mm. For pair of doors astragals has to
be provided on the meeting stile for both active and
inactive leaf. Vision lite shall be as per direction
of engineer in charge with a beeding and screws
from inside.The glass should be contraflam Door
Lite 11 mm of minimum size 350mm x 500mm clear
120 min fire rated and partially insulated (EW120),
Clear Toughened, interlatered glass having a
sound reduction of >37dB, LT of 86% and
compliant to class 2(B)2 category of Impact
Resistance as per EN 12600 standard from Saint
Gobain. ( Vision panel All doors and frames shall be finished with Powder
coating in desired Shades. Rate should include
supply and installation of door and hardware as per
application
The rate includes the cost of all the materials, labor
& T & P required for proper completion of the item
decribed above. (For payment purpose the area of
opening including door frame shall only be
measured). The agency shall provide one number
additional door alongwith all frame and fittings for
getting it tested from CBRI Roorkee and in case
sample fails, additional sets after improvement shall
be provided for testing till the item passes in tests,
which shall not be included in measurements for
payment. (Main entry Door) sqm 94.00
e
Providing and fixing glazing in fire resistant door
shutters, fixed panels, ventilators and partitions
etc., with G.I. beading of appropriate size, made out
of 20 SWG G.I.sheet (zinc coating not less than
120 gm/m2), fire resistant sealant, including
applying a coat of approved fire resistant primer on
G.I. beading etc., complete all as per direction of
Engineer-incharge.With clear fire resistant glass panes 6mm thick of
approved brand, having minimum 60 minutes fire
resistance Sqm 71.00
e
Providing and fixing ISI marked flush door shutters
conforming to IS : 2202 (Part I) non-decorative
type, core of block board construction with frame of
1st class hard wood and well matched commercial
3 ply veneering with vertical grains or cross bands
and face veneers on both faces of shutters:
35 mm thick including ISI marked Stainless Steel
butt hinges with necessary screws. Sqm 112.00
f
Providing & Fixing decorative high pressure
laminated sheet of plain / wood grain in gloss /
matt/ suede finish with high density protective
surface layer and reverse side of adhesive bonding
quality conforming to IS : 2046 Type S, including
cost of adhesive of approved quality.
1.5 mm thick Sqm 225.50
g
Providing and fixing Pre-laminated flat pressed 3
layer (medium density) particle board or graded
wood particle board IS : 3087 marked, with one
side decorative and other side balancing lamination
Grade I, Type II exterior grade IS : 12823 marked,
in shelves with screws and fittings wherever
required, edges to be painted with polyurethane
primer (fittings to be paid separately).
25 mm thick Sqm 127.00
h
Providing and fixing cup board shutters 25 mm
thick, with Pre-laminated flat pressed three layer
particle board or graded wood particle board IS:
12823 marked, exterior grade (Grade l Type ll),
having one side decorative lamination and other
side balancing lamination, including IInd class teak
wood lipping of 25 mm wide x12 mm thick with
necessary screws and bright finished stainless
steel piano hinges, complete as per direction of the
Engineer-in-Charge Sqm 130.00
i
Extra for providing lipping with 2nd class teak
wood battens 25 mm minimum depth on all edges
of flush door shutters (over all area of door shutter
to be measured). Sqm 208.00
j
Providing, fitting and fixing transparent P.V.C. sheet
of 1 mm thickness to be fixed to door shutter of
toilet as per drawings and directions of Engineer-
in–charge. (In toilet doors). sqm 216.00
k
Extra for providing vision panel of Rectangular
or square not exceeding 0.1 sqm in all type of flush
doors (cost of glass excluded) (overall area of door
shutter to be measured): Sqm 112.00
l
Providing and fixing bright /matt finished Stainless
Steel handles of approved quality & make with
necessary screws etc all complete with 125 mm.Each 232.00
m
Providing and fixing bright /matt finished Stainless
Steel handles of approved quality & make with
necessary screws etc all complete with 200 mm.Each 224.00
n
Providing and fixing IS : 12817 marked stainless
steel butt hinges (heavy weight) with stainless
steel screws etc. complete :i 125x64x2.50 mm Each 344.00
ii 100x60x2.50 mm Each 168.00
iii 75x50x2.50 mm Each 204.00
o
Providing and fixing Stainless steel tower bolts
with necessary screw etc. complete.
(i)300x10 mm long(Make Model code 8577 of Godrej)
each 266.00
(ii)150x10 mm long(Make Model code 8576 of Godrej)
each 126.00
p
Providing and fixing special quality bright finished
brass cupboard or ward robe locks with four levers
of approved quality including necessary screws etc.
complete. 65mm Each 52.00
q
Providing and fixing bright finished brass hanging
type floor door stopper with necessary screws,
etc. complete. Each 196.00
r
Providing and fixing aluminium extruded section
body tubular type universal hydraulic door closer
(having brand logo embossed on the body, door
weight upto 80 kg to 120 kg with double speed
adjustment with necessary accessories and screws
etc. complete. Each 48.00
s
Providing and fixing chromium plated brass 100
mm mortice latch and lock with 6 levers and a
pair of lever handles of approved quality with
necessary screws etc. complete. Each 66.00
t
Providing and fixing chromium plated brass 50 mm
cupboard or wardrobe knobs with nuts complete.
Each 104.00
u
Supply of Pad locks ( Make: Model Ultra Sherlock
code 3293 of Godrej) each 70.00
v
Providing and fixing stainless steel sliding bolt with
nuts and screws etc. in entrance door shutters
including necessary arrangement for fixing in door
shutters with additional hook for providing lock in
open position of the door complete 250x16mm.
i 300x16mm (Make: Model code 8541 of Godrej) each 87.00
ii 200x16mm (Make: Model code 8539 of Godrej) each 30.00
w
Providing and fixing magnetic catcher of approved
quality in cupboard / ward robe shutters, including
fixing with necessary screws etc. complete. Triple
strip vertical type Each 200.00
x
Providing and fixing PVC 32mm dia Door buffer in
doors including necessary screws etc
complete.(Make : Model code 8618 of Godrej) each 62.00
y
Providing and fixing stainless steel curtain rod
including finial,bracket,rings etc. complete.(make
Vista,MAC or equivalent) m 245.00
13
Structural steel work in single section, fixed with or
without connecting plate, including cutting, hoisting,
fixing in position and applying a priming coat of
approved steel primer all complete. Kg 1410.00
14
Supplying and fixing rolling shutters of approved
make, made of required size M.S. laths, interlocked
together through their entire length and jointed
together at the end by end locks, mounted on
specially designed pipe shaft with brackets, side
guides and arrangements for inside and
outside locking with push and pull operation
complete, including the cost of providing and fixing
necessary 27.5 cm long wire springs manufactured
from high tensile steel wire of adequate strength
conforming to IS: 4454 - part 1 and M.S. top cover
of required thickness for rolling shutters.
i
80x1.25 mm M.S. laths with 1.25 mm thick top
cover Sqm 18.00
ii
Providing and fixing ball bearing for rolling shutters.
Each 6.00
15
Extra for providing grilled rolling shutters
manufactured out of 8 mm dia M.S. bar instead of
laths as per design approved by Engineer-in-
charge, (area of grill to be measured). Sqm 4.00
16
Providing and fixing circular/ Hexagonal cast iron
or M.S. sheet box for ceiling fan clamp, of
internal dia 140 mm, 73 mm height, top lid of 1.5
mm thick M.S. sheet with its top surface hacked for
proper bonding, top lid shall be screwed into the
cast iron/ M.S. sheet box by means of 3.3 mm dia
round headed screws, one lock at the corners.
Clamp shall be made of 12 mm dia M.S. bar bent to
shape as per standard drawing. Each 75.00
17
Steel work in built up tubular ( round, square or
rectangular hollow tubes etc.) trusses etc.,
including cutting, hoisting, fixing in position and
applying a priming coat of approved steel primer,
including welding and bolted with special shaped
washers etc. complete. Kg 7648.00
18Providing and fixing mild steel round holding down
bolts with nuts and washer plates complete. Kg 450.00
19
Steel work welded in built up sections/ framed work,
including cutting, hoisting, fixing in position and
applying a priming coat of approved steel primer
using structural steel etc. as required.
In gratings, frames, guard bar, ladder, railings,
brackets, gates, grill and similar works Kg 27721.00
20
Providing and fixing stainless steel ( Grade 304)
railing made of Hollow tubes, channels, plates etc.,
including welding, grinding, buffing, polishing and
making curvature (wherever required) and fitting
the same with necessary stainless steel nuts and
bolts complete, i/c fixing the railing with necessary
accessories & stainless steel dash fasteners ,
stainless steel bolts etc., of required size, on the top
of the floor or the side of waist slab with suitable
arrangement as per approval of Engineer-incharge, Kg 9151.00
21
Providing and fixing carbon steel galvanised (
minimum coating 5 micron) dash fastener of 10 mm
dia double threaded 6.8 grade (yield strength 480
N/mm2), counter sunk head, comprising of 10 m
dia polyamide PA 6 grade sleeve, including drilling
of hole in frame , concrete/ masonry, etc. as per
direction of Engineer-in-charge.
a 10 x 60 mm Each 2400.00
b 10 x 140 mm Each 1196.00
22
Providing and fixing thermal insulation of ceiling
(under deck insulation) with Resin Bonded Fibre
glass wool conforming to IS : 8183, density 24kg /
m3, 50mm thick, wrapped in 200 G Virgin
Polythene bags, fixed to ceiling with metallic cleats
(50x50x3 mm) @ 60 cm and wire mesh of 12.5 mm
x 24 gauge wire mesh, for top most ceiling of
building. Sqm 99.00
FINISHING
66
15 mm cement plaster on rough side of single or
half brick wall of mix 1:6 (1 cement: 6 coarse sand)
Sqm 12912.00
6720 mm cement plaster of mix 1:4 (1 cement: 4
coarse sand)
Note :- Rates for external plaster are for height upto
10m from ground level in less otherwise stated. Ie.
Upto 3rd floor Lv Sqm 5075.00
68
Including extra for plastering exterior walls of height
more than 10 m from ground level for every
additional height of 3.6m or part thereof.a 3rd. FLOOR Sqm 1353.21
b 4th. FLOOR Sqm 1293.65
c 5th. FLOOR Sqm 1293.65
d 6th. FLOOR Sqm 1293.65
e 7th. FLOOR Sqm 1293.65
f 8th. FLOOR Sqm 1231.21
g 9th. FLOOR Sqm 735.21
696 mm cement plaster of mix 1:3 (1 cement : 3 fine
sand) Sqm 6748.00
70
Providing and fixing 150mm wide 12 guage
25mmx25mm wire mesh over joints between RCC
columns, beams, lintels facias and brick wall with U
type MS nails and spread cement mortar 1:3 (1
cement : 3 coarse sand) to fix in position. m 5080.00
71
Making of 12mmx25mm groove in exterior
plastered surface or RCC projection at all heights,
floors and levels. Grooves shall be made by fixing
of alluminum channels of required sizes in the
required paterns to the walls before plastering and
shall be removed after plastering. m 500.00
72
Providing and applying white cement based water
proof putty of approved brand and manufacturer,
over the exterior plastered wall surface to prepare
the surface even and smooth complete. Sqm 28296.00
73
Finishing walls with fungus and algae resistant
superior grade water proof acrylic paint of approved
brands and manufacturers and of required shades
after surface preparation to give an even shade to
all external surfaces of exterior walls (minimum two
or more coats) including application of one coat of
exterior primer at all heights, floors and levels.Sqm 13294.00
74 Neat cement punning. Sqm 272.00
75Extra for plastering on circular work not exceeding
6 m in radius:76 In one coat Sqm 317.00
77
Wall painting with acrylic emulsion paint of
approved brand and manufacture to give an even
shade with Two or more coats on new work Sqm 15349.00
78
Applying one coat of water thinnable cement primer
of approved brand and manufacture on wall
surface. Sqm 15349.00
79Finishing walls with textured exterior paint of
required shade
a
New work (Two or more coats applied @ 3.28 ltr/10
sqm) over and including priming coat of exterior
primer applied @ 2.20kg/10 sqm Sqm 647.00
b
Applying priming coat with ready mixed red oxide
zinc chromate primer of approved brand and
manufacture on steel galvanised iron/ steel works Sqm 111.00
c
Wall painting with acrylic emulsion paint of
approved brand and manufacture to give an even
shade with Two or more coats on new work Sqm 300.00
d
Painting with synthetic enamel paint of approved
brand and manufacture to give an even shade with
Two or more coats on new work Sqm 155.00
e
Finishing walls with water proofing cement paint of
approved brand and manufacture and of required
shade to give an even shade -Three or more coats
sqm 661.00
f
Extra for plastering exterior walls of height more
than 10 m from ground level for every additional
height of 3 m or part thereof. sqm 24221.72
Roofing Work
80
Providing gola 75mmx75mm in cement concrete
1:2:4 ( 1 cement : 2 coarse sand : 4 stone
aggregate 10mm and down gauge) including
finishing with cement mortar 1:3 ( 1 cement : 3 fine
sand) as per standard design 75x75mm deep
chase. metre 400.00
81
Making Khurras 45cmx45cm with average min.
thickness of 5cm cement concrete 1:2:4 ( 1 cement
: 2 coarse sand : 4 graded stone aggregate of
20mm nominal size) over PVC sheet 1mx1mx400
micron, finished with 12mm cement plaster 1:3 ( 1
cement : 3 coarse sand ) and a coat of neat cement
rounding the edges and making and finishing the
outlet complete. each 50.00
82 WATER PROOFING
a
Providing water proofing treatment with best quality
acrylic polymer modified cementitious composite
slurry coating and fibre glass cloth of approved
brand over sunken floors & terraces as per
manufacturer’s specifications and as approved by
Engineer-in-charge. The waterproofing membrane
applied shall be subjected to water ponding test by
filling minimum 50 mm water for 2-3 days or as
specified by Engineer - In charge. Areas to be
observed from bottom and all wet spots & water
leakage area should be marked for treatment. If the
wet areas are observed, they should be treated by
reapplication of waterproofing membrane.(sunken
floor of toilet & kitchen, tiolet walls, )Sqm 1152.00
b
Providing 12mm thick plaster to protect
waterproofing treatment in cement mortar 1:4 (
1cement : 4 coarse sand) . sqm 1152.00
c
Grading roof for water proofing treatment with;
Cement concrete 1:2:4 ( 1cement:2 coarse sand: 4
graded stone aggregate 20mm nominal size) cum 234.00
d
Providing and mixing water proofing material in
cement concrete/cement mortar in proportion as
recommended by the manufacturer. bag 1872.00
83 Water proofing Treatment at Roof surface.
a
Labour for cleaning of concrete surface to remove
dust, oil, grease including removal of existing loose
paint / coating, and cement laitance by cleaning
with compressed air, including all materials, labour,
tools and tackles complete Repairing surface
irregularities, damaged concrete in base slab, if
any, with a styrene butadiene polymer, Sika Latex
or equivalent modified repair mortar including a
coat of bonding agent of the same with cement
slurry including all material, labour, tools and
tackles complete Sqm 2614.00
b
Providing and applying 2 coats of Sikatop seal
109hi - 2 or approved equivalent, componant
polymer modified coating after application of
Sikatop seal 109hi primer over the roof after proper
surface preparation.A glass fibre cloth shall be put
in between two coats including labour tools and
tackles etc all complete. Sqm 2614.00
c
Supply and application of 1:3 cement-sand mortar,
mixed with Sika-Top 77 or approved equivalent the
polymer modified high quality emultion,as a coving
the corners of floors and the vertical surface in the
sunken area, and between floor and walls in the
remaining area. Sqm 2614.00
84 uPVC Windows
a
Providing, supplying & fixing of Fixed Window
made out of multi chambered uPVC sections with
TPV gaskets having isolated drainage and
reinforced with Galvanized Iron of 120 GSM
profiles through out the window. The outer frame
having a overall size of 60 x 55 mm with
reinforcement of 1 mm thickness and Mullion with
overall size of 74 x 60 mm with reinforcement of
1mm thickness. Composition of profile shall
consists a minimum of 6 PHR of TiO₂ for every 100
parts of PVC resin.Window panels shall be
provided with 20mm DG Glass . Wall thickness of
frame & Mullion shall be 2.2 - 2.4 mm. Cost is
inclusive of all taxes, materials, labour, hire charges
of manchineries all lead and lifts etc.,complete as
per the directions of the Engineer-in charge of
work. Sqm 136.00
b
Providing, supplying & fixing of Openable Door
made out of multi chambered uPVC sections with
TPV gaskets having isolated drainage and
reinforced with Galvanized Iron of 120 GSM
profiles through out the window. The outer frame
having a overall size of 60 x 55 mm with
reinforcement of 1 mm thickness and sash with
overall size of 60 x 102 mm with reinforcement of 2
mm thickness. Glazing bead for fixing of glass shall
be of size 20 x 18mm and coextruded with gasket.
Composition of profile shall consists a minimum of
6 PHR of TiO₂ for every 100 parts of PVC resin.
Doors shall be provided with 20mm DG Glass ,
standard hardware & Multi point locking system of
Espag type adn 3D hinges. Wall thickness of frame
& sash shall be 2.2 - 2.4 mm. Cost is inclusive of all
taxes, materials, labour, hire charges of
manchineries all lead and lifts etc., complete as per
the directions of the Engineer-in charge of work.Sqm 60.80
c
Providing, supplying & fixing of 2Track - 2Panel
Sliding Window With Bottom Fixed made out of
multi chambered uPVC sections with TPV gaskets
having isolated drainage and reinforced with
Galvanized Iron of 120 GSM profiles through out
the window. The top/bottom outer frame shall be
provided with 60 x 55 mm profile and reinforced
with 1.0 mm thickness. The outer frame having a
overall size of 60 x 45 mm with reinforcement of 1
mm thickness and sash with overall size of 39 x 58
mm with reinforcement of 1.5 mm thickness.
Glazing bead for fixing of glass shall be of size 20 x
18mm and coextruded with gasket. Composition of
profile shall consists a minimum of 6 PHR of TiO₂ for every 100 parts of PVC resin. Windows shall be
provided with 20mm DG glass, standard hardware
& Flush locking system. Wall thickness of frame &
sash shall be 2.2 - 2.4 mm.Cost is inclusive of all
taxes, materials, labour, hire charges of
manchineries all lead and lifts etc.,complete as per
the directions of the Engineer-in charge of work.Sqm 25.60
d
Providing, supplying & fixing of 3 Track - 3 Panel
Sliding Window with Top Fixed made out of multi
chambered uPVC sections with TPV gaskets
having isolated drainage and reinforced with
Galvanized Iron of 120 GSM profiles through out
the window. The fixed window having a overall size
of 60 x 55 mm with reinforcement of 1 mm
thickness and sliding frame with outer frame of 108
x 45mm with sash of size 39 x 58mm with
reinforcement of 1.5mm .Glazing bead for fixing of
glass shall be of size 20 x 18mm and coextruded
with gasket. Composition of profile shall consists a
minimum of 6 PHR of TiO₂ for every 100 parts of
PVC resin. Windows shall be provided with 20mm
DG glass, standard hardware & Flush locking
system. Wall thickness of frame & sash shall be 2.2
- 2.4 mm.Cost is inclusive of all taxes, materials,
labour, hire charges of manchineries all lead and
lifts etc.,complete as per the directions of the
Engineer-in charge of work.Sqm 63.20
e
Providing, supplying & fixing of Fixed Window
made out of multi chambered uPVC sections with
TPV gaskets having isolated drainage and
reinforced with Galvanized Iron of 120 GSM
profiles through out the window. The outer frame
having a overall size of 60 x 55 mm with
reinforcement of 1 mm thickness and Mullion with
overall size of 74 x 60 mm with reinforcement of
1mm thickness. Composition of profile shall
consists a minimum of 6 PHR of TiO₂ for every 100
parts of PVC resin.Window panels shall be
provided with 20mm DG Glass . Wall thickness of
frame & Mullion shall be 2.2 - 2.4 mm. Cost is
inclusive of all taxes, materials, labour, hire charges
of manchineries all lead and lifts etc.,complete as
per the directions of the Engineer-in charge of
work. Sqm 100.80
f
Providing, supplying & fixing of 2Track - 2Panel
Sliding Window made out of multi chambered
uPVC sections with TPV gaskets having isolated
drainage and reinforced with Galvanized Iron of
120 GSM profiles through out the window.The
outer frame having a overall size of 60 x 45 mm
with reinforcement of 1 mm thickness and sash with
overall size of 39 x 58 mm with reinforcement of 1.5
mm thickness. Glazing bead for fixing of glass shall
be of size 20 x 18mm and coextruded with gasket.
Composition of profile shall consists a minimum of
6 PHR of TiO₂ for every 100 parts of PVC resin.
Windows shall be provided with 20mm DG glass,
standard hardware & Flush locking system. Wall
thickness of frame & sash shall be 2.2 - 2.4
mm.Cost is inclusive of all taxes, materials, labour,
hire charges of manchineries all lead and lifts
etc.,complete as per the directions of the Engineer-
in charge of work. Sqm 141.00
g
Providing, supplying & fixing of 2Track - 2Panel
Sliding Window made out of multi chambered
uPVC sections with TPV gaskets having isolated
drainage and reinforced with Galvanized Iron of
120 GSM profiles through out the window.The
outer frame having a overall size of 60 x 45 mm
with reinforcement of 1 mm thickness and sash with
overall size of 39 x 58 mm with reinforcement of 1.5
mm thickness. Glazing bead for fixing of glass shall
be of size 20 x 18mm and coextruded with gasket.
Composition of profile shall consists a minimum of
6 PHR of TiO₂ for every 100 parts of PVC resin.
Windows shall be provided with 20mm DG glass,
standard hardware & Flush locking system. Wall
thickness of frame & sash shall be 2.2 - 2.4
mm.Cost is inclusive of all taxes, materials, labour,
hire charges of manchineries all lead and lifts
etc.,complete as per the directions of the Engineer-
in charge of work. Sqm 122.00
h
Providing, supplying & fixing of 2Track - 2Panel
Sliding Window made out of multi chambered
uPVC sections with TPV gaskets having isolated
drainage and reinforced with Galvanized Iron of
120 GSM profiles through out the window.The
outer frame having a overall size of 60 x 45 mm
with reinforcement of 1 mm thickness and sash with
overall size of 39 x 58 mm with reinforcement of 1.5
mm thickness. Glazing bead for fixing of glass shall
be of size 20 x 18mm and coextruded with gasket.
Composition of profile shall consists a minimum of
6 PHR of TiO₂ for every 100 parts of PVC resin.
Windows shall be provided with 20mm DG glass,
standard hardware & Flush locking system. Wall
thickness of frame & sash shall be 2.2 - 2.4
mm.Cost is inclusive of all taxes, materials, labour,
hire charges of manchineries all lead and lifts
etc.,complete as per the directions of the Engineer-
in charge of work. Sqm 26.00
i
Providing, supplying & fixing of 2Track - 2Panel
Sliding Window With Top & Bottom Fixed made
out of multi chambered uPVC sections with TPV
gaskets having isolated drainage and reinforced
with Galvanized Iron of 120 GSM profiles through
out the window. The top/bottom outer frame shall
be provided with 60 x 55 mm profile and reinforced
with 1.0 mm thickness. The outer frame having a
overall size of 60 x 45 mm with reinforcement of 1
mm thickness and sash with overall size of 39 x 58
mm with reinforcement of 1.5 mm thickness.
Glazing bead for fixing of glass shall be of size 20 x
18mm and coextruded with gasket. Composition of
profile shall consists a minimum of 6 PHR of TiO₂ for every 100 parts of PVC resin. Windows shall be
provided with 20mm DG glass, standard hardware
& Flush locking system. Wall thickness of frame &
sash shall be 2 - 2.2 mm.Cost is inclusive of all
taxes, materials, labour, hire charges of
manchineries all lead and lifts etc.,complete as per
the directions of the Engineer-in charge of work.Sqm 208.80
j
Providing, supplying & fixing of Top Hung Window
made out of multi chambered uPVC sections with
TPV gaskets having isolated drainage and
reinforced with Galvanized Iron of 120 GSM
profiles through out the window. The outer frame
having a overall size of 60 x 55 mm with
reinforcement of 1 mm thickness and sash with
overall size of 60 x 75 mm with reinforcement of 1.5
mm thickness. Glazing bead for fixing of glass shall
be of size 20 x 18mm and coextruded with gasket.
Composition of profile shall consists a minimum of
6 PHR of TiO₂ for every 100 parts of PVC resin.
They shall be provided with 5mm Clear glass,
standard hardware & Multi point locking system of
Espag type/ Wall thickness of frame & sash shall
be 2 - 2.2 mm.Cost is inclusive of all taxes,
materials, labour, hire charges of manchineries all
lead and lifts etc.,complete as per the directions of
the Engineer-in charge of work.Sqm 42.40
k
Providing, supplying & fixing of Top Hung Window
made out of multi chambered uPVC sections with
TPV gaskets having isolated drainage and
reinforced with Galvanized Iron of 120 GSM
profiles through out the window. The outer frame
having a overall size of 60 x 55 mm with
reinforcement of 1 mm thickness and sash with
overall size of 60 x 75 mm with reinforcement of 1.5
mm thickness. Glazing bead for fixing of glass shall
be of size 20 x 18mm and coextruded with gasket.
Composition of profile shall consists a minimum of
6 PHR of TiO₂ for every 100 parts of PVC resin.
They shall be provided with 5mm Clear glass,
standard hardware & Multi point locking system of
Espag type/ Wall thickness of frame & sash shall
be 2 - 2.2 mm.Cost is inclusive of all taxes,
materials, labour, hire charges of manchineries all
lead and lifts etc.,complete as per the directions of
the Engineer-in charge of work.Sqm 8.00
MISCELLANEOUS ITEMS
85
Providing and fixing 40mm dia G.I. pipe for spout
including cutting holes in walls and making good
the same.
600mm long each 80.00
86
Providing and fixing false ceiling tiles of
Dexune/Armstrong/Nittobo make of size 595x595
mm in true horizontal level suspended in inter
locking metal grid of hot dipped galvanised steel
sections (galvanised @170gsm/sqm) consisting of
main "T" runner suitably spaced at joints to get
required length and size of 15x32mm made from
0.30 mm thk (minimum) sheet spaced at 1200 mm
c/c and cross tee of size 15x27mm made of 0.3mm
thk (minimum) sheet, 1200 mm long spaced
between main Tat 600 mm c/c to form a grid of
1200x600mm and secondary cross T of length
600mm and size 15x27 mm made of 0.30 mm thk
(minimum) sheet to be interlocked at middle of the
1200x600 mm panel to form grids of 600x600mm
and laying false ceiling tiles of approved texture in
the grid including, wherever, required,
cutting/making,opeings for services like
diffusers,grills,light fittings, fixtures, smoke
detectors etc. Main T runners to be suspended
from ceiling using GI slotted cleats fixed to the
ceiling with 6mm dia and 50mm long dash
fastners,4mm GI adjustable rods with galvanised
level clips spaced at 1200 mmc/c along main T , bottom exposed width of 15 mm
of all the T sections shall be prepainted with
polyester paint, all complete t all heights as per
specifications drawings & as directed by engineer
incharge. the rate is including cost of mineral fibre
600mmx600mm Armstrong/Dexune/Nittobo ceiling
tiles dune 15mm thk micro look white colour sqm 2610.00
87
Supply and fixing of approved brand 150F Plain
Aluminum Panel Facade Cladding of approved
manufacturer manufactured of approved colour
consisting of panels150mm wide x17mm deep x
0.7mm thick panel length up to 6 mtrs, Coil Coated
on a Continuous Paint Line, Double-baked and roll
farmed from enameled Corrosion Resistance
Aluminium Alloy AA3005 (Al.Mn) for higher
Strength and good Roll Forming characteristics.
Panel shall be clipped to Baked enamel!ed
Aluminium Panel Carrier of 34.5 mm wide x 48mm
deep x0.95mm thick in Standard lengths of 5metrs
made of double baked enameled Aluminum Alloy
AA'5050(Al..Mg).The panel Carrier Shall be
mounted by Means of suitableSub-Structure (shall
be charged as extra as separate item).
Paint Finish: Aluminium panels :shall be
chromatised for Maximum bond between metal and
paint enameled twice under high temperature one
side with full primer and Luxacote finish the other
side (innerside)with a primer coat and skin coat on
a Continuous Paint Line Sqm 457.60
88
Drilling with core cutting machine in RCC
beams,slabs,floorsetc.,for laying pipes and
rendering the same in RCC 1:2:4 finishing the
same to the satisifaction of the owner or his
authorised representative etc.,including nominal
reinforcement wherever required,complete,at all
levels The quote shall also include for providing
EPOXY based water proofing compound for sealing
the joints around the pipes upto 250mm max depth
at all heights & levels
aAbove 75mm dia and upto 100mm dia. (depth of
hole 100 mm to 200 mm) Nos 37.00
bAbove 101mm dia. and up to 200mm dia (depth of
hole 100 mm to 200 mm) Nos 66.00
ALUMINIUM WORKS
89
Providing and fixing aluminium work for doors,
windows, ventilators and partitions with extruded
built up standard tubular sections/ appropriate Z
sections and other sections of approved make
conforming to IS: 733 and IS: 1285, fixing with dash
fasteners of required dia and size, including
necessary filling up the gaps at junctions, i.e. at top,
bottom and sides with required EPDM rubber/
neoprene gasket etc. Aluminium sections shall be
smooth, rust free, straight, mitred and jointed
mechanically wherever required including cleat
angle, Aluminium snap beading for glazing /
paneling, C.P. brass / stainless steel screws, all
complete as per architectural drawings and the
directions of Engineer-in-charge. (Glazing, paneling
and dash fasteners to be paid for separately) :
a For fixed portion
Polyester powder coated aluminium
(minimum thickness of polyester powder
coating 50 micron) Kg 404.00
b
For shutters of doors, windows & ventilators
including providing and fixing hinges/ pivots and
making provision for fixing of fittings wherever
required including the cost of EPDM rubber /
neoprene gasket required (Fittings shall be paid for
separately)
Polyester powder coated aluminium
(minimum thickness of polyester powder
coating 50 micron) Kg 880.00
c
Providing and fixing glazing in aluminium door,
window, ventilator shutters and partitions etc. with
PVC/ neoprene gasket etc. complete as per the
Architectural drawings and the direction of Engineer
- in - Charge (Coast of aluminium snap beading
shall be paid in basic item) :(i) With frosted glass panes of 4.0 mm thickness sqm 43.00
(ii) With float glass panes of 5.0 mm thickness sqm 162.00
(iii) Extra for providing toughening of glass sqm 162.00
d
Filling the gap in between aluminium frame &
adjacent RCC/ Brick/ Stone work by providing
weather silicon sealant over backer rod of
approved quality as per architectural drawings and
direction of Engineer-in-charge complete.
Upto 5mm depth and 5 mm width Rm 1713.00
e
Providing and fixing 12 mm thick prelaminated
particle board flat pressed three layer or graded
wood particle board conforming to IS: 12823 Grade
l Type ll, in panelling fixed in aluminum doors,
windows shutters and partition frames with C.P.
brass / stainless steel screws etc. complete as per
architectural drawings and directions of Engineer-in-
charge.
f
Pre-laminated particle board with decorative
lamination on both sides Sqm 114.00
90
Providing & fixing double action hydraulic floor
spring of approved brand and manufacturer
(conforming IS:6315) for aluminium doors including
cost of cutting floors as required, embedding in
floors and cover plates etc. as per direction of
Engineer-in-Charge.(With stainless steel cover
plate minimum 1.25 mm thickness of D60 Floor
spring (60 kg) LKYGDF0FS 7477 Godrej Make)
With SS cover plate minimum 1.25 mm thickness Each 128.00
91 EXPANSION JOINT
a
Expansion Joints Treatment with Sikadur Combiflex
System
Step-1. Removal of extra topping between the
expansion joint area: Preparation of Expansion
Joint edge by grinding and removal of all loose
particles, dirt, dust etc to make the surface clean
including scaffolding , tools tackles etc all complete
Step-2. Providing and Mixing of epoxy adhesive
sikadur 31 C (2:1) by mechanical mixture and apply
on the 50 mm surface of both sides as per the
manufacturer specification including tools, labour,
machines etc all complete
Step-3. Providing and Fixing of Hypalon based
Sikadur Combiflex SG strip (200 mm width x 2mm
thickness on the expansion joint as per the
manufacturer specification including tools, labour,
machines scaffoldings etc all complete
Step-4. Finally Providing and Mixing of epoxy
adhesive sikadur 31 C (2:1) by mechanical mixture
and apply on the 50 mm surface of both sides as
per the manufacturer specification including tools,
labour, machines etc all complete as a protective
coating Rm 450.00
b
Preparing the surface by cleaning and chipping the
surface for removing loose, laitance etc. All the
construction joints should be cut in a groove and
wash the entire surface thoroughly by water making
the surface saturated dry condition and filling the
gaps with polymer modified mortar with Asian MPP.
Applying polysulphide Sealant primer on both the
edges. Finally application of polysulphide Sealant in
the gap of 6 mmx 40 mm depth. Rm 450.00
c
Providing and fixing machine moulded aluminium
covering of approved pattern & design, made out of
machine cut aluminium sheet and machine holed
for receiving dash fastener, over expansion joints
on vertical surfaces/ceiling floors, the fixing on plate
in one row on one side of joint only shall be done
with stainless steel dash fasteners of 8 mm dia and
75 mm long bolt including providing aluminium
washers 2 mm thick & 15 mm dia , at a staggered
pitch of 200mm centre to centre including drilling
holes in the receiving surface and providing
expandable plastic sleeves in holes etc. complete
as per direction of Engineer-in-charge.
Powder coated aluminium sheet 2.5mm thick
(minimum thickness of powder coating 50 micron), [
7.00 kg/ sqm ] Kg 496.00
STRUCTURAL GLAZING
92
Providing and supplying aluminium extruded tubular
and other aluminium sections as per the
architectural drawings and approved shop drawings
, the aluminium quality as per grade 6063 T5 or T6
as per BS 1474,including super durable powder
coating of 60-80 microns conforming to AAMA 2604
of required colour and shade as approved by the
Engineer-in-Charge. (The item includes cost of
material such as cleats, sleeves, screws etc.
necessary for fabrication of extruded aluminium
frame work. Nothing extra shall
be paid on this account).Kg 617.00
93
Providing, assembling and supplying vision glass
panels (IGUs) comprising of hermetically-sealed 6-
12- 6 mm insulated glass (double glazed) vision
panel units of size and shape as required and
specified, comprising of an outer heat strengthened
float glass 6mm thick, of approved colour and
shade with reflective soft coating on surface # 2 of
approved colour and shade, an inner Heat
strengthned clear float glass 6mm thick, spacer
tube 12mm wide, dessicants, including primary seal
and secondary seal (structural silicone sealant) etc.
all complete for the required performances, as per
the Architectural drawings, as per the approved
shop drawings, as specified and as directed by the
Engineer-in-Charge. The IGUs shall be assembled
in the factory/ workshop of the glass
processor.“(Payment for fixing of IGU Panels in the
curtain glazing is included in cost of item
No.26.2)“For payment, only the actual area of glass
on face # 1 of the glass panels (excluding the areas
of the grooves and weather silicone sealant)
provided and fixed in position, shall be measuredin
sqm.“
a
Coloured tinted float glass 6mm thick substrate
with reflective soft coating on face # 2, + 12mm
Airgap + 6mm Heat Strengthened clear Glass of
approved make having properties as visible Light
transmittance (VLT) of 25 to 35 %, Light reflection
internal 10 to 15%, light reflection external 10 to 20
%, shading coefficient (0.25- 0.28) and U value of
3.0 to 3.3 W/m2 degree K etc. The properties of
performance glass shall be decided by technical
sanctioning authority as per the site requirement.Sqm 190.00
b
Extra for openable side / top hung vision glass
panels (IGUs) including providing and supplying at
site all accessories and hardwares for the openable
panels as specified and of the approved make such
as heavy duty stainless steel friction hinges, min 4 -
point cremone locking sets with stainless steel
plates, handles, buffers etc. including necessary
stainless steel screws/ fasteners, nuts, bolts,
washers etc. all complete as per the Architectural
drawings, as per the approved shop drawings, as
specified and as directed by the Engineer- in-
Charge. Sqm 61.00
Total of Part-A
Item
no.
Description Unit Quantity Rate in figure (Rs.) Rate in words Total Amount(Rs.)
1Providing and fixing white vitreous china three pieces
water closet (European type W.C. pan) with dual flush
fitting, of flushing capacity 2 litre/ 4 litre including flush
pipe,cistern with lid, conforming to IS : 7231, with all
fittings and fixtures complete, including cutting and
making good the walls and floors wherever required(
Make Model No.Hindware cornice wall mounted
92055, cist : 92121 of Hindware or equivalent)
Each 69.00
2Providing and fixing water closet squatting pan (Indian
type W.C. pan ) with 100 mm sand cast Iron P or S
trap, 10 litre low level white P.V.C. flushing cistern,
including flush pipe, with manually controlled device
(handle lever) conforming to IS : 7231, with all fittings
and fixtures complete, including cutting and making
good the walls and floors wherever required:
(a) White Vitreous china Orissa pattern W.C. pan of
size 580x440 mm with integral type foot restsEach 2.00
3
Providing and fixing white vitreous china oval wash
basin of size 560 x 450 mm, for under counter
mounting, specially fabricated brackets,C.P.brass 32
mm CP brass waste coupling including cutting and
making good the walls, wherever required.( Make
Hindware Cat No. 10049, C.P.brass 32 mm CP, brass
waste coupling ,Model No. 709 / 705 , jaquar or
equivalent )
each 74.00
4
Providing and fixing glazed vitreous china flat back
urinals approx. size 375X315X620 mm with
infrared /ultra violet electric operated concealed
auto flush sensor 15mm dia. complete including
making connection with CP brass pipe to CP
spreaders, 32mm domical waste with 32mm
brass bottle trap and pipe to wall, wall flanges
comp. including cutting and making good the
walls and floors complete wherever required.
(Make: Model URS-WHT-132530 of Jaquar or
equivalent )
each 35.00
Bill of Quantity
Name of Work: Construction of Research Park at IITG Campus.
Part-B(Sanitary and water supply works)
5
Providing and fixing CP brass urinal valve auto
closing system with built in control cock & wall
flange of approved quality with wall flanges
complete.-15mmNB,98mm long weighing not less
than 75gm.
each 35.00
6
Providing and fixing urinal partition with frosted
safety glass of 8mm thick of size 900mm(height)
x 450 mm(width) corner chamfered fixed in brick
wall with stainless steel clips of grade 304 all
complete.(Model 1810-US or 1810-UC of Jaquar
or equivalant)
sqm 31.00
7
Providing & fixing 32 mm dia CP brass bottle trap
including fisher union for wash basins complete Cal no
ALD 769 of Jaquar or equivalent)each 109.00
8
Providing & fixing 1mm thick Stainless steel kitchen
sink of grade-304 as per IS: 13983 with 32 mm C.P.
brass waste coupling complete including the fittings,
cutting and making good the wall wherever required,
1000 x 500 x 178 bowl size with drain board.(Make:
Nirali Elegance unique or equivalent)
No. 24.00
9
Providing and fixing PVC waste pipe of standard
pattern for wash basins, sinks etc. of approved make.
(a) 40 mm dia each 24.00
10
Supply and fixing 15mm CP brass Sink Cock with
swinging casted spout wall flange and suitable length
CP brass extension pipe all of approved make (CP
fittings CAT No. FLR5347ND of Jaquar or equvalent).
each 24.00
11
Providing and fixing 600x120x5mm glass shelf with
edges rounded off fixed with necessary screws, raw
plugs etc. all complete. (Make: Model ACN1171N of
Jaquar continental)
each 74.00
12
Providing and fixing 600x450 mm beveled edge mirror
of superior glass (of approved quality) complete with 6
mm thick hard board ground fixed to wooden cleats
with C.P. brass screws and washers complete.
each 74.00
13
Providing and fixing of 600mm long towel rail Jaquar
Cat No. AKP-35711P or equivalent make all complete
with required acceessories as directed by the Engineer-
in-Charge.
each 24.00
14
Providing & fixing CP towel ring of size 150mm dia of
approved make ( Make : Model AKP35721P of
Jaquaer Queen's)each 48.00
15
Providing & fixing stainless steel soap tray of approved
make and design with necessary screws for wash
basin (Make : Model AKP-35731P of Jaquar)
each 122.00
16
Providing and fixing CP brass toilet paper holder as
directed by Engineer in Charge (Make: Model-
AKP35753P of Jaquar or Equivalent).Each 69.00
17
Providing & fixing stainless steel Shower basket of
approved make and design with necessary screws for
toilets (Make : Model ACN 1177N of Jaquar OR
equivalent)
each 24.00
18
Providing and fixing C.P. brass wall mixer 3-in-1
system with provision for both hand shower and
overhead shower complete with 115mm long bend
pipe , connecting legs & wall flange ( without hand and
overhead shower) etc complete.( Jquar Cat No
FLR5281N or equivalent)
each 24.00
19
Providing and fixing C.P bib cock with wall flange
including cutting and making good the walls wherever
required all complete as directed by the Engineer-in-
Charge.Charge.
(a) 2- way bib cock Jaquar Cat No.FLR-5041N or
equivalenteach 76.00
(b) Standard Bib cock (Make Model FLR 5047N of
Jaquar or equivalent)each 48.00
20
Providing and fixing C.P. angular stop cock of 15mm
nominal bore complete with flange and C.P. copper
connection (Make Model FLR 5053 N of Jaquar
Florentine)
each 199.00
21
Providing and fixing C.P. brass overhead shower 100
mm round shape multi flow (ABS Body chrome plated
with gray face plate ) with rubit cleaning system with
wall flange etc ( Jquar Cat No OHS-1999 or
equivalent)
each 24.00
22
Providing and fixing C.P. brass pillar cock of approved
quality conforming to I.S. standards - 15mm nominal
bore.(Make Model FLR 5015 N of Jaquar or
equivalent)
each 74.00
23
Providing and fixing C.P. brass close hole basin mixer
pillar tap of approved quality and make, weighting not
less 1-970kg - 15mm nominal bore of standard back
type .(Make Model FLR 5001B of Jaquar Florentine).
each 24.00
24
Providing and fixing health faucet with 8mm dia,1m
long flexible tube & wall hook with NRV (back flow
preventer) of approved quality and make,(Make Model
ALD 577 of Jaquar or equivalent).
each 76.00
25
Supply and fixing 450 mm long braided connection
pipe with two15mm nuts & rubber washers etc. of
approved make ( CAT No.ALD 803AB of Jaquar or
Equivalent )
each 145.00
26
Providing, fitting and fixing of foldable horizontal Grab
Bar of stainless ateel (Make Jaquar or equivalent) for
person with disabilities (for WC)Each 4.00
27
Providing, fitting and fixing of vertical Grab Bar long
satin 692 mm of Jaquar or Equivalent for person with
disabilities. (for wash basin & WC)Each 12.00
28
Providing and fixing Hot water GEYSER of approved
Make- Havells including with two nos connection pipe
450 mm long.
(a) 10 Ltrs capacity Each 24.00
29
Providing, fixing, testing & commissioning of Bathroom
Drain (Make-Viega model no.-4935.1) Article Code-
557119 with Sealing flange,with removable
trap,(Storage Water Height 50 mm-Water
Seal),without top,with protection plug, with rotable
supply DN40, with horizontal drain socket,with outlet
100 mm. Drain capacity 1.7-1.1L/s WITH height
adjustable and rotratable TOP FRAME Model-4922.4
Article Code-534523(Height adjustment piece) 150x
150 (suitable for 143x143 GRATE) WITH BACK
PRESSURE SEAL.WITH STAINLESS STEEL
GRATE(143x143)Model- 4933.4 Article Code-
554040. LOADING CAPACITY CLASS K=300KG
Quality controlled in accordance with DIN EN -
1253(Body and Top Frame made of environmentall
friendly PP (poly propylene)
each 24.00
30
Providing & fixing in position uPVC P"or S" trap/elbow
of self cleaning design of following sizes for the
embedded areas. Making proper connection with drip-
seal joints, cutting chase / hole in floors /slabs and
bringing the same in proper condition in cement
concrete 1:2:4 mix complete as required. including
cost of cutting and making good the walls and floors
where required.
(a) 110 mm inlet and 110 mm outlet each 210.00
(b) 110 mm inlet and 63 mm outlet (Floor Drains only)each 40.00
31
Providing and fixing 100 mm dia S.S grating (with or
without hole) for floor or Nahani trap.each 250.00
32
Providing and fixing on wall face un-plasticised - Rigid
PVC sewer pipes conforming to IS:13592 Type-B
including jointing with seal ring conforming to IS:5382
leaving 10mm gap for thermal expansion single
socketed pipes with all accessories as bend, door
bend, horn bend etc., complete as directed.
(a) 110 mm nominal bore m 750.00(b) 150 mm nominal bore m 692.00
33
Providing & fixing in position un-plasticised-Rigid PVC
waste pipes with necessary fittings, cutting & chasing
walls/floors etc. and making good the same.
(a) 40 mm dia metre 75.00
34
Providing, fitting and fixing of three layered white
outside ,black middle and blue inside PVC storage
water tank of approved make as per IS:12701 of all
capacity with cover and locking arrangement complete
as directed.
per litre
capacity15000.00
35
Providing and fixing Chlorinated Polyvinyl Chloride
(CPVC) pipes, having thermal stability for hot & cold
water supply, including all CPVC plain & brass
threaded fittings, i/c fixing the pipe with clamps at 1.00
m spacing. This includes jointing of pipes & fittings with
one step CPVC solvent cement and the cost of cutting
chases and making good the same including testing of
joints complete as per direction of Engineer in Charge.
Concealed work, including cutting chases and making
good the walls etc.
(a) 15 mm nominal outer dia Pipes m 150.00(b) 20 mm nominal outer dia Pipes m 650.00
36
Providing and fixing Chlorinated Polyvinyl Chloride
(CPVC) pipes, having thermal stability for hot & cold
water supply including all CPVC plain & brass threaded
fittings This includes jointing of pipes & fittings with one
step CPVC solvent cement, trenching, refilling &
testing of joints complete as per direction of Engineer
in Charge. Internal work – Exposed on wall.
(a) 25 mm OD meter 54.00(b) 32 mm OD meter 750.00(c) 40 mm OD meter 900.00(d) 50 mm OD meter 130.00(e) 75 mm nominal inner dia Pipes meter 110.00
37
Providing and fixing G.I. pipes complete with G.I.
fittings and clamps, including cutting and making good
the walls etc. (rising main)
(a) 65 mm dia. nominal bore meter 90.00(b) 80 mm dia. nominal bore meter 150.00
38
Providing, fixing, testing and commissioning etc. of G.I.
Pipes of all diametres complete with G.I. fittings and
clamps including painting with anti corrosive bitumastic
paint etc., including trenching and refilling etc.
(external work)
(a) 80 mm nominal bore Heavy Duty metre 750.00(b) 100 mm nominal bore Heavy Duty metre 135.00
39
Making connection of G.I. distribution branch with G.I.
main 50 mm to 80 mm nominal bore by providing and
fixing tee, including cutting and threading the pipe etc.
complete
each 1.00
40
Providing and fixing ball valves (Brass) of approved
quality with high pressure plastic floats,25mm nominal
diametereach 3.00
41
Providing and fixing brass full way valve with hard
chrome plated ball inside PTFE (Teflon) seat & ring
with chrome plated centre handle with female BSP
threads complete in all respects.( Make Zoloto or
equivalent)
(a) 25 mm dia. nominal bore each 12.00(b) 32 mm dia. nominal bore each 45.00(c) 40 mm dia. nominal bore each 70.00(d) 50 mm dia. nominal bore each 25.00(e) 65 mm dia. nominal bore each 4.00(f) 80 mm dia. nominal bore each 8.00
42
Providing and fixing square mouth SW gully traps
grade-A complete with C.I. grating brick masonry
chamber with bricks of class designation 75 and water
tight C.I. cover with frame of size 300 x 300 (inside) the
weight of cover to be not less than 4.50kg and frame to
be not less than 2.70kg as per standard design 180 x
150 mm size P and S type with FPS bricks
each 16.00
43
Providing and fixing un-plasticised -hollow core PVC
structured wall pipes conforming to IS:16098:Part1 SN-
8 designation including jointing with all accessories
etc., complete as directed. Eco drain pipe of Suprenme
or equivalent. (Sewer Pipe)
(a) 150 mm nominal bore m 190.00(b) 200 mm nominal bore m 730.00(c) 250 mm nominal bore m 30.00(d) 315 mm nominal bore m 20.00
44
Providing an laying cement concrete 1:5:10 ( 1 cement
: 5 coarse sand : 10 stone aggregate 40mm nominal
size) upto hunches of hollow core PVC pipe including
bed concrete as per standard design.
(a) 150 mm nominal bore m 190.00(b) 200 mm nominal bore m 730.00(c) 250 mm nominal bore m 30.00(d) 315 mm nominal bore m 20.00
45
Constructing brick masonry manhole with 75 class
designation bricks in cement mortar 1 : 5 ( 1 cement :
5 coarse sand) R.C.C. top slab with 125mm thick
RCC in proportion 1 : 2 : 4 ( 1 cement : 2 coarse sand :
4 graded stone aggregate 20 mm nominal size),
125mm thick RCC bed concrete 1:2:4 mix ( 1 cement :
2 coarse sand: 4 graded stone aggregate 20 mm
nominal size) with reinforcement, inside plastering 12
mm thick with cement mortar 1: 3 (1 cement : 3 coarse
sand ) finished with a floating coat of neat cement and
making channels in cement concrete 1 : 2 : 4 mix ( 1
cement : 2 coarse sand : 4 graded stone aggregate 20
mm nominal size) neatly finished complete as per
design but excluding the cost of reinforcement but
including the cost of centering and shuttering.
(a) Inside size 90 cm x 80 cm and 60 cm deep
including circular FRP composite manhole cover with
frame (heavy duty) 530 mm dia With F.P.S. bricks.each 23.00
(b) Inside size 120 cm x 90 cm and 90 cm deep
including circular FRP composite manhole cover with
frame (heavy duty) 530 mmdia With F.P.S. bricks.each 30.00
(c) Extra depth for manhole of size
120cmX90cmX90cmm 25.00
46
Making connection of drain or sewer line with existing
manhole including breaking into and making good the
walls floors with cement concrete 1:2:4 ( 1 cement : 2
coarse sand : 4 grade stone aggregate 20mm nominal
size),cement plastered on both sides with cement
mortar 1:3 (1 cement: 3 coarse sand) finished with a
floating coat of neat cement and making necessary
channels for drain etc.250-300mm dia
each 2.00
47
Constructing brick masonry gully chamber 50 x 45 x 60
cm with bricks of class designation 75 with 500 x 450
mm C.I. horizontal gratings with frame complete as per
standard design with F.P.S. brick
each 16.00
BORE WELL
48
Boring/drilling bore well of required dia for casing/
strainer pipe, by suitable method prescribed in IS: 2800
(part I), including collecting samples from different
strata, preparing and submitting strata chart/ bore log,
including hire & running charges of all equipments,
tools, plants & machineries required for the job, all
complete as per direction of Engineer-in-charge, upto
90 metre depth below ground level.
(a) 300 mm dia Metre 180.00
49
Boring/drilling bore well of required dia for casing/
strainer pipe, by suitable method prescribed in IS: 2800
(part I), including collecting samples from different
strata, preparing and submitting strata chart/ bore log,
including hire & running charges of all equipments,
tools, plants & machineries required for the job, all
complete as per direction of Engineer -in-charge,
beyond 90 metre & upto 150 metre depth below
ground level.
(a) 300 mm dia Metre 80.00
50
Gravel packing in tubewell construction in accordance
with IS: 4097, including providing gravel fine/ medium/
coarse, in required grading & sizes as per actual
requirement, all complete as per direction of Engineer-
in-charge.
Cum 36.80
51
Development of tube well in accordance with IS : 2800
(part I) and IS: 11189, to establish maximum rate of
usable water yield without sand content (beyond
permissible limit), with required capacity air
compressor, running the compressor for required time
till well is fully developed, measuring yield of well by "V"
notch method or any other approved method,
measuring static level & draw down etc. by step draw
down method, collecting water samples & getting
tested in approved laboratory, i/c disinfection of
tubewell, all complete, including hire & labour charges
of air compressor, tools & accessories etc., all as per
requirement and direction of Engineer-in-charge.
Hour 144.00
52
Providing and fixing Bail plug/ Bottom plug of required
dia to the bottom of pipe assembly of tubewell as per
IS:2800 (part I).
(a) 200 mm dta Each 2.00
53
Providing and fixing M.S. clamp of required dia to the
top of casing/ housing pipe of tubewell as per IS: 2800
(part I), including necessary bolts & nuts of required
size complete.
(a) 200 mm clamp Each 2.00
54
Supplying, assembling, lowering and fixing in vertical
position in bore well, unplasticized PVC medium well
casing (CM) pipe of required dia, conforming to IS:
12818, including required hire and labour charges,
fittings & accessories etc. all complete, for all depths,
as per direction of Engineer -in-charge.
(a) 150 mm nominal size dia Rm 120.00(b) 200 mm nominal size dia Rm 80.00
Total Amount of Part -B =
Item
no.
Description Unit Quantity Rate in figure (Rs.) Rate in words Total Amount(Rs.)
1
Earth work in excavation by mechanical
means (Hydraulic excavator) / manual
means over areas (exceeding 30cm in
depth. 1.5m in width as well as 10 sqm
on plan) including disposal of excavated
earth, lead upto 50m and lift upto 1.5m,
disposed earth to be levelled and neatly
dressed.
All types of soil cum 500
2
Earth work in filling for site preparation
with approved quality of earth including
filling the portion within plinth area upto
the formation level, peripheral apron &
drains etc. complete upto formation
level. in layers not exceeding 20 cm in
depth including watering, ramming,
consolidating to the acceptable density
and dressing complete as directed
including obtaining earth and removal of
top vegetation, dressing the surface
upto proper grade and slope. (The rate
shall be inclusive of providing earth
including all leads and lifts, payment of
land compensation for obtaining earth,
payment of royalty and taxes etc. The
payment will be made in profile
measurement)
a)
With the earth from outside the campuscum 50000
Bill of Quantity
Name of Work: Construction of Research Park at IITG Campus.
PART - C Site Development
2
Providing & laying grass turf with earth
50mm to 60mm thickness of existing
ground prepared with proper level and
ramming with tools wooden and than
rolling the surface with light roller make
the surface smoothen and light watering
the same, with sprinkler and
maintenance for 30 days or more till the
grass established properly as per
direction of officer in charge.
sqm 5000
3
Providing and laying cement concrete in
footings and bases for column in string
or lacing courses, parapets, copings,
bed blocks, anchor blocks, plain window
sills & the like upto floor two level
excluding the cost of centering,
shuttering but including finishing the
exposed surface with cement mortar
1:3 (1 cement : 3 fine sand ) with
a
with mix 1:3:6 ( 1, cement : 3, coarse
sand : 6, graded stone aggregate 20mm
nominal size )
Cum 100
b
with mix 1:2:4 ( 1, cement : 2, coarse
sand : 4, graded stone aggregate 20mm
nominal size )
Cum 180
4
Centering and shuttering including
strutting, propping etc., & removal of
form at all heights for : Foundations,
footings, bases of columns, mass
concrete , precast shelves etc.
sqm 600
5
Random rubble masonry with hard
stone in foundation and plinth including
leveling up with cement concrete 1:6:12
(1 cement : 6 coarse sand : 12 graded
stone aggregate 20 mm nominal size)
at plinth level with cement mortar 1:6 (1
cement : 6 coarse sand) including
providing weep holes with 50mm PVC
pipes and making good the same as
directed.
cum 500
6
Random rubble masonry with hard
stone in super structure above plinth
level and upto floor two level, including
leveling up with cement concrete 1:6:12
(1 cement : 6 coarse sand : 12 graded
stone aggregate 20 mm nominal size)
including providing weep holes with
50mm PVC pipes and making good the
same as directed.
cum 750
Approach Road
7
Preparation and consolidation of sub
grade with power road roller of 8 to 12
tonne capacity after excavating earth to
an average of 22.5 cm depth, dressing
to camber and consolidating with road
roller including making good the
undulations etc. and re-rolling the sub
grade and disposal of surplus earth with
lead upto 50 metres.
Sqm. 4550
Construction of granular sub-base by
providing close graded Material
conforming to specifications, mixing in a
mechanical mix plant at OMC, carriage
of mixed material by tippers to work
site, for all leads & lifts, spreading in
uniform layers of specified thickness
with motor grader on prepared surface
and compacting with vibratory power
roller to achieve the desired density,
complete as per specifications and
directions of Engineer-in-Charge.
With material conforming to Grade-II
(size range 53 mm to 0.075 mm )
having CBR Value-25
Cum 180
8
Providing, laying, spreading and
compacting stone aggregates of
specific sizes to water bound macadam
specification including spreading in
uniform thickness, hand packing, rolling
with 3 wheels steel/ vibratory roller 8-10
tonnes in stages to proper grade and
camber, applying and brooming
requisite type of screening/ binding
materials to fill-up the interstices of
coarse aggregate, watering and
compacting to the required density.
(boulder will be issued free of cost
inside the campus)
a
By mechanical means : Hand broken
metal from blasted boulder grading-I
90mm to 45mm using screening Type-A
(13.2mm aggregate)
cum 360
b
By mechanical means : Hand broken
metal from blasted boulder grading II
63mm to 45mm using screening Type-B
(11.2mm aggregate)
cum 240
c
By mechanical means : Hand broken
metal from blasted boulder grading III
53mm to 22.4mm using screening Type-
B (11.2mm aggregate)
cum 180
9
Providing and applying tack coat with
bitumen emulsion at the rate of 0.50 kg
per sqm on the prepared bituminous/
granular surface cleaned with broom
sqm 2392
10
Providing, laying and rolling of close-
graded premix surfacing material of
20mm thickness composed of 11.2 mm
to 0.09mm aggregates using
penetration grade bitumen to the
required line, grade and level to serv as
wearing course on a previoulsy
prepared base, including mixing in a
suitable hot mix plant laying and rolling
with a smooth wheeled roller 8-10 tonne
capacity, and finishing to required level
and grad.
sqm 2392
11
Providing and laying seal coat sealing
the voids in a bituminous surface laid to
the specified levels, grade and cross fall
using type A seal coats (11.2mm to
0.09mm).
sqm 2392
12
Providing and fixing following pipes in
ground for cable crossing in road/
paved areas including excavation, back
fillilng, jointing with sockets etc. as
required.
a 100 mm. GI Pipe (medium) M 100
b 50 mm G.I.pipe (medium) M 100
Internal Foot path
13
Providing and laying interlocking
precast cement concrete paver of
approved design and compressive
strength of 300kg/sqcm laid on a bed of
40mm thick coarse sand including filling
the joints with local sand complete
80mm
sqm 3000
14
Providing and laying factory made
chamfered edge Cement Concrete
paver blocks In foot path, park & lawns
driveway or light & traffic parking etc. of
required strength, thickness & size/
shape, made by table vibratory method
using PU mould, laid in required colour
& pattern over 50mm thick compacted
bed of course sand, compacting and
proper embedding/laying of inter locking
paver blocks into the sand bedding
layer through vibratory compaction by
using plate vibrator, filling the joints with
sand and cutting of paver blocks as per
required size and pattern, finishing and
sweeping extra sand, all complete as
per manufacturer's specifications &
direction of Engineerin-
Charge.
a
80mm thick Cement concrete paver
block of M-30 grade with approved
colour, design & pattern.
Sqm 2098
b
80mm thick Cement concrete paver
block of M-40 grade with non colour,
design & pattern for provition of Grass
growth into the holes.
Sqm 1178
STORM WATER DISPOSAL
15
Providing and laying non-pressure NP3
class RCC pipes and collar jointed with
stiff mixure of cement morter in the
proportion of 1:2 (1 cement : 2 fine
sand) inccluding testing of joints etc.,
complete.
a 450mm dia metre 50
b 600mm dia metre 50
c 900mm dia metre 30
d 1200mm dia metre 30
16
Brick work with bricks of class
designation 75 in foundation & plinth in
cement mortar 1:6 (1 cement : 6 coarse
sand) including curing.
cum 320
17
12mm thick, cement plaster finished
with a floating coat of neat cement of
1:4(1 cement: 4 coarse sand).
Sqm 1800
18
Providing and fixing G.I. chain link fabric
fencing of required width in mesh size
50x50 mm including strengthening with
2 mm dia wire or nuts, bolts and
washers as required complete as per
the direction of Engineer-in-charge.
Made of G.I. wire of dia. 4 mm Sqm 31
19
Providing and laying non-pressure NP2
class (light duty) R.C.C. pipeswith
collars jointed with stidd mixture of
cement mortar in the proportionof 1:2 (1
cement : 2 dine sand) including testing
of joints etc. complete :
a 150 mm dia. R.C.C. pipe m 50
b 250 mm dia. R.C.C. pipe m 150
Total of Part-C
Item
no.
Description Unit Quantity Rate in figure (Rs.) Rate in words Total Amount(Rs.)
Sub-head -I Hydrants & Spinklers
1 Supplying and Fixing Single Headed Internal Hydrant
Valve oblique pattern with intantanneous S S
coupling of 63 mm dia with cast iron wheel ISI marked,
conforming to IS: 5290 (Type A), with 80 mm dia flanged
inlet,with ABS cap and chain complete with all
accessroies etc. as required.
Make : GETECH/NEWAGE/SAFEX each 8
2 Providing RRL Hose with ISI Marked (IS:636) 63 mm dia X15
M long complete with instantaneous type Gun Metal 3 mm dia
ISI Marked male & female couplings (IS:903) bound & riveted
to hose pipes with copper rivets and copper wire complete as
reqd.
( MAKE: NIRMAL RUBBER/NEWAGE/BRG) each 16
3 Supplying and fixing 63mm dia, S S Branch Pipe with
16/20mm dia copper nozzle confirming to IS : 903 suitable
for instantaneous connection, interconnect hose pipe,
coupling as required. (Type A) as required.
MAKE:GETECH/NEWAGE/SAFEX each 8
4Supplying and Fixing First Aid Hose Reel, wall mounting
swinging type complete with drum & bracket of MS
construction, spray painted in Post office Red, confirming to
IS 884/1995 with upto date amendments, complete with the
following as required. 36 Meter long 20 mm dia water
hose Thermoplastic (Textile reinforced) Type - 2 as per IS :
12585 20 mm dia gun metal globe valve & nozzle. Drum and
brackets for fixing the quimpments on wall.
Connection from riser with stop valve (gun metal) & M.S. Pipe
MAKE : GETECH/NEWAGE/SAFEX each 16
Bill of Quantity
Name of Work: Construction of Research Park at IITG Campus.
PART - C Site Development
5Supplying and Fixing of Weather Proof Hose Cabinet
suitable for external yard hydrant / FBIC fabricated out of 2
mm thick M.S. sheet with 4
mm thick glazed glass door in front having locking
arrangements, suitable to accommodate external hydrant
with valve, hose reels, branch
pipe / FBIC with all the necessary pipes, accessories,
fittings etc., mounted on wall or raised brick platform and
duly painted with PO Red externally and white internally with
synthetic enamel paint, sign writing etc. complete in all
respects as required at site and having minimum following
dimensions. 900 mm x 600 mm x 450 mm deep
MAKE:GETECH OR SELF FEBRICATED each 16
6 Providing, Fixing, Testing and Commissioning of
Sprinkler Installation Control Valve of Cast
iron body and brass / bronze working parts
comprising of water motor, alarm, bronze seat
clapper and clapper arm, hydraulically driven
mechanical gong bell to sound continuous alarm
when the Sprinkler system activates, pressure
gauges, emergency releases, strainer, pressure
switch, cock valve complete with drain valve and
bypass, test control box, ball valves, MS pipe of
required size, flanges, orifice plate, gasket etc. of
size 150 mm dia, as required.
MAKE:GETECH/NEWAGE/SAFEX each 4
7 Providing and Fixing 15 mm dia gunmetal / brass
quartzoid type Sprinkler Head with quartz bulb
and set to operate at specified temperature.
MAKE:GETECH/NEWAGE/SAFEX
a Pendent / Upright type, 68 C, Chrome plated each 320
b Side wall 68 C, Chrome plated each 75
Sub Head - II Piping, Valves and Accessories
8 Providing, Laying, Testing and Commissioning of 'B' class (
Medium ) MS pipe on surface confirming to IS 3589 and
1239 including cutting and welding with fittings like elbows,
reducer, hanger, tees, flanges, tapers, nuts bolts, gaskets
etc., fixing the pipe on the wall / ceiling with suitable
clamps and painting with two coats of synthetic enamel
paint after primer coat of required shade, cutting hole
and chase in brick wall / RCC slab and making good the
same etc. complete as required.
MAKE: TATA,JINDAL,NEZONE
a 200 mm dia mtr. 15
b 150 mm dia mtr. 415
c 80 mm dia mtr. 75
d 65 mm dia mtr. 230
e 50 mm dia mtr. 122
f 40 mm dia mtr. 10
g 32 mm dia mtr. 152
h 25mm dia mtr. 450
j 20mm dia mtr. 60
9 Supplying, Installation, Testing and
Commissioning of cast iron sluice valves of PN
1.6 rating flanged at both ends of following sizes
complete with rubber insertion, nuts, bolts and
washers etc. as required.
MAKE: KARTAR,AUDCO,SANT
a 200 mm dia each 4
b 150 mm dia each 4
c 100 mm dia each 8
d 80 mm dia each 8
10 Supplying, Installation, Testing and Commissioning
of butterfly valves of PN 1.6
rating of following sizes with nitrile seat and stainless steel
stem with lever/gear operation and cast iron body in powder
coated finish for fire fighting application complete in all
respects as required.
MAKE: KARTAR,AUDCO,SANT
a 150 mm dia nos. 4
b 100 mm dia nos. 4
c 80mm dia nos. 8
d 65 mm dia nos. 8
e 50 mm dia nos. 4
11 Providing, Installation, Testing and
Commissioning of double flanged cast iron Non-Return
Valve, PN 1.6 of following sizes confirming to IS :
5312 complete with rubber gasket, Gl bolts, nuts, washers
etc. as required.
MAKE: KARTAR,AUDCO,SANT
a 200 mm dia each 2
b 150 mm dia each 4
c 80 mm dia each 4
12 Providing, Installation, Testing and
Commissioning of forged brass / Gun Metal Ball
Valves with brass body chrome plated of following
sizes as required.
MAKE: KARTAR,AUDCO,SANT
a 50mm dia each 6
b 25mm dia each 16
13 Supply, Installation, Testing and Commissioning of 100 mm
dia Bourden type, Stainless Steel dial type Pressure Gauge
including brass isolation valve and siphon pipe having
caliberation of 0 -16 Kg / cm2
MAKE:H.GURU/FEBEC each 8
14Supplying and Fixing of Fire Man's axe with heavy
insulated rubber as per standard conforming to IS 926
MAKE:GETECH/NEWAGE/SAFEX each 16
15 Constructing masonary chamber for external sluice valve
of 90 x 90 x 100 cm, inside finish with II class
designation brick work in cement mortar 1:5 (1 cement :
5 fine sand) for sluice valve, with C.I. main hole cover &
frame of 600 mm dia. and RCC top slab ( 1:2:4 mix, 1 cement:
2 coarse sand : 4 graded stone aggregate 20 mm nominal
size) necessary excavation foundation concrete 1:5:10
(1 cement : 5 fine sand : 10 graded stone aggregate
40 mm nominal size) inside plastering with cement
mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick
finished with a floating coat of neat cementcomplete as
required. each 8
B EXTERNAL FIRE FIGHTING SYSTEM (MAIN PUMP).
16 Supply, Erection, Testing & commissioning of
Electrical Motor Driven Pump centrifugal end
section type pump complete with bronze
impeller, mechanical seal capable of delivering
2280 liters/minute against a total head of 70
metres, induction motor suitable for 415V, 50 Hz,
AC supply min. 60 HP with speed of 2900 RPM ,
TEFC type conforming to IP: 55, flexible coupling,
coupling guard. Common bedplate fabricated
from mild steel channel, vibration pads, isolation
arrangement & RCC foundation. MAKE :KIRLOSKAR OR
EQUIV.
set 1
17 DIESEL ENGINE DRIVEN FIRE PUMP:
Supply, Erection, Testing & commissioning of
Diesel Engine Driven Pump Horizontal end
section, centrifugal type pump complete with
bronze impeller, mechanical seal capable of
delivering 2280 liters/minute against a total
head of 70 metres, Diesel Engine Min.Cap. of
93 BHP with speed of 1800 RPM , flexible
coupling, coupling guard. Common bed plate
fabricated from mild steel channel, starter motor,
batteries, battery charger & cabling, fuel piping,
instrumental panel, exhaust piping with
residential type silencer, cooling arrangements
including 200 Litres Diesel Tank Complete,
vibration pads, isolation arrangement, heat
exchanger & RCC foundation.
MAKE: KIRLOSKAR OR EQUIV. set 1
18 JOCKEY PUMPS:
Supply, Erection, Testing & commissioning of Jockey
Pump Horizontal end section single stage centrifugal
type pump complete with bronze impeller, mechanical
seal capable of delivering 180 liters/minute against a total
head of 70 metres, induction motor suitable for 415V, 50 Hz,
Min 15 HP with 2900 RPM, TEFC type conforming to IP: 55,
flexible coupling, coupling guard. Common bedplate
fabricated from mild steel channel, vibration pads,
isolation arrangement & RCC foundation.
MAKE:KIRLORKAR OR EQUIV. set 1
19 TERRACE PUMPS:
Supply, Erection, Testing & commissioning of Terrace
Pump Horizontal end section single stage centrifugal
type pump complete with bronze impeller, mechanical
seal capable of delivering 27 (M3/Hr) against a total head of
30 metres, induction motor suitable for 415V, Min 5.5KW
with 2900 RPM, TEFC type
conforming to IP: 55, flexible coupling, coupling guard.
Common bedplate fabricated from mild steel channel,
vibration pads, isolation
arrangement & RCC foundation.
MAKE:KIRLORKAR OR EQUIV. 2
20 SITC of industrial type pressure switch having
1/4" BSP(F) connection IP:32 enclosure
protection, phosphor bronze bellows as sensing
element, SDPT contact system, switch rating 6A
Inductive/10A resistive 380 V AC, 0.2A
Inductive/10A resistive 250V DC suitable for
maximum pressure range of 230 PSI with
isolation cock and interconnecting cables using
copper conductor between pressure switch and
panels completed as required.
MAKE:INDFOS OR DANFOSS nos. 4
21 Supply, Erection, Testing & commissioning of Air
Vessel made of 10 mm M.S. Sheet size 450 x
2000 mm including supply & fixing of Gun metal
32 mm dia Air release Valve, 32 mm dia Gun
Metal gate valve, 40 mm dia gun metal gate
valve including 2Mts of M.S 40 mm dia G. I
(Heavy pipe for drainage and 1 no. 65 mm dia
Butterfly valve with all necessary accessories as
per IS 2825
MAKE:GETECH / SELF FEBRICATED. nos. 5
22 PIPING ABOVE GROUND FOR EASY MAINTENANCE
Supply, Erection, Testing & commissioning of
M.S pipe (Medium) ISI marked 1239-part-1 and
ISI : 3589 including cutting, welding/threading
with accessories like tees, elbows, flanged joints, reducers,
rubber gaskets, nuts & bolts including fixing the pipe with
suitable clamps/bracket,
complete as required including painting of one coat of red
oxide & 2 coats of P.O. red paint
MAKE: TATA,JINDAL,NEZONE.
a 80 mm dia mtr. 40
b 150 mm dia mtr. 300
23 Supply, Erection, Testing & commissioning of Single
headed hydrant S S valves
conforming to ISI: 5290 with flanged inlet with 63 mm female
instantaneous of gun metal coupling with blank cap & chain,
nuts, bolts, washers &
5mm thick rubber gasket etc.
MAKE:GETECH/NEWAGE/SAFEX nos. 26
24 Supply, Erection, Testing & commissioning of 63 mm dia, 15
M long RRLhose pipe conforming to ISI-636 type A Mark fire
hose pipe conforming to IS 901 mark with S S male &
female coupling wire wound with the pipe
MAKE:GETECH/NEWAGE/SAFEX nos. 26
25 Supply, Erection, Testing & commissioning of S Sshort
branch pipes conforming to ISI
spec 903 with 16 mm dia nozzle.
MAKE:GETECH/NEWAGE/SAFEX nos. 8
26 Supply & Erection of M.S.Fire Hose Box of size 900 x 600x
450 mm approx.) fabricated from 16 SWG. M.S. Sheet of
fully welded construction with hinge front door with locking
arrangement & partially glazed with 5 mm thick
glass
powder coated fire red finish paint with Fire Hose Box
written on the front side of the glass for internal hydrants to
house 2 nos. hose pipes, 1 no. Branch pipe, 1 no. Hose
reel & Landing valve 1 No.
MAKE:GETECH/NEWAGE/SAFEX nos. 8
27 Supply, Erection, Testing & commissioning of
Drawl of connection with CI foot valve 150 mm
dia (for fire tank)and 3 Meter G.I. 100 mm dia (H)
pipe, nuts, bolts, washers & 5mm thick rubber
gasket etc.
MAKE:GETECH/NEWAGE/SAFEX nos. 1
28 Fire brigade Two Way Inlet Valve with 2 nos.
G.M 63 mm dia Male instantaneous coupling with
100 mm flanged out let connection and built in
check valves
MAKE:GETECH/NEWAGE/SAFEX nos. 4
Main Fire Pump Panel
29 Fabricating, supplying, erection, testing and
commissioning of cubicle type floor mounted panel made
from 14 CRCA Sheet complete with contactors,Auxillary
contacts ,indicating lamps,Ammeters with selector
switches, voltmeters with selector switches,fuses,
automatic delta type motor starter including connections
complete as required for 1 No Fire hydrant and sprinkler
pump, 1 No. Jockey pump, 1 No Battery charger and 1
Set of Battery complete in all respect including
neccessary control wiring as per the details given below:
Incoming
1) 500 Amps MCB - 1 No.
2) Voltmeter (0-500) V (size 96mm x 96mm) - 1No.
3) Voltmeter Selector Switch - 1 No.
4) Indication Lamps (LED type) -1 sets (1 set of 03
Nos.RYB)
5) Ammeters(0-200A) - 1 No.
6)Ammeter selector switch -1 No
7)Current transformer (300/5A) -3Nos
8)Bus bar chamber with 900 Amps Aluminim bus bar
,suitable for 3 phase and neutral system - 01set.
9)Required number of Auxillary contacts
set
Outgoing
1)200 Amps MCB , -2 Nos
2) 100 Amps MCB - 1 No
3) Fully Automatic delta starter (60 hp ) with LED
illuminated ON-OFF push button -2Nos.
4) Fully Automatic delta starter (15hp ) with LED
illuminated ON-OFF push button - 1 No.
5)Auxillary contactors for main, sprinkler and
jockey pumps
6) Auto/ manual selector switch with control
wiring for main, sprinkler and jockey pump
7) Annunciator with hooter, accept/ reset push
button with control wiring
8) Currect Transformer (200/5A) --6 Nos
9) Currect Transformer (100/5A) --3 Nos
10) Ammeter 0-150 --3 Nos
11) Volt Meter 0-500--3 Nos
12) Single phase preventer--3 Nos
13) 3 Set Phase indication Lamps with Phuses
Control Panel Engine
a) 15 Amp Battery charges with trickle and boost
facility
b) 0-32 volts/ meter--1 No
c) 0-15 Amps ammeter--1 No
d) Auto Starting contractor with relay
e) Auto/ Manual selector switch with push button
for manual start--1 No
f) 63 MCB - 1No
g) Buzzer--1 N0
h) Indication Lamp--3 No
I) Push Button--2 No30 TERRACE PUMP PANEL to start the Terrace Pump
Automaic Nos 2
31 Supply of fire buckets Set of four nos. with MS
stand with sand etc. as required. Nos. 20
set 1
32 Supply, Installation, Fixing of ABC stored Pressure Fire
Extinguisher with built – In Pressure Gauge to know the
Ready ness of the Extinguisher Squeeze Grip Handle as per
IS:15683 with ISI mark.
(6 kg capacity)
BRAND : GETECH / MINIMAX/ SAFEX Nos 46
33 Supply, Installation, Fixing of CARBON DIOXIDE Fire
Extinguisher confirming to IS: 15683 with ISI Mark.(4.5
LITERS)
BRAND: GETECH /MINIMAX / SAFEX Nos 16
34 Manual Call Point & Hooter each floor area. Make:Agni
Suraksha Nos 16
35 12 Zone Panel for Manual Call Box & Hooter to identify the Nos 4
Location/ floor area Zone wise.Make :Agni Suraksha
36 Exit Board Auto Glow type for easy evcuation floor wise. Nos 24
37Providing & fixing angle iron (40mm x 40mm x 5mm) door
frame and M.S sheet (2mm thick) sum glass shutter of size
2.1 mtr. X 1.2 mtr. (N.S) with 25 mm x 3 mm angleframe all
around & stiffenced in between i/c hinges, handle, locking
arrangement, painting with approved synthetic enamle paint
i/c sign writing on glass at internal hydrant including providing
& fixing M.S. Sheet 2 mm thick on remaing portion above door
to close opening i/c painting etc. as required. each 44
Total of Part -D
Item no. Description Unit Quantity Rate in figure (Rs.) Rate in words Total Amount(Rs.)
1
Supply, installation, testing & commissioning of short -
circuit - Isolators.
Nos 49
2
Supply, installation, testing & commissioning of Control
Modules (CMX) for controlling Hooters/ speakers, Strobe
(Flasher) Lamps, Manual Call Points (MCP), etc.
Research Block Each 12
3
Supply, installation, testing & commissioning of 'Rise'
type Heat Detectors, approved make, with Operating
Temperature of ( - ) 10OC to ( + ) 70
OC and OPERATING
VOLTAGE OF 18 TO 28 V D.C.
Research Block Each 18
4
Supply, installation, testing & commissioning of 'Rise'
type Multicriteria Detectors, approved make, with
Operating Temperature of ( - ) 10OC to ( + ) 70
OC and
OPERATING VOLTAGE OF 18 TO 28 V D.C.
Each 670
5
Supplying, fitting & fixing Base of Dectector,Model no-
B501
Each 694
6 Supplying, fitting & fixing Duck Dectector.
Research Block Each 24
7 Supplying, fitting & fixing Beam Dectector.
Research Block Each 4
8
Supply, installation, testing & commissioning of manual
push button station break glass type - Manual call points
(MCP) with MS / ABS body, with chain & hammer, and
also with Blinking facility, completely compatible with the
main Fire Alarm Panel.
Each 24
9
Supply , installation, testing & commissioning of Monitor
Modules for Manual call points - (MMX)
Research Block
Each 6
PART-D(ii) (FIRE DETECTION, ALARM SYSTEM)
Name of work: Construction of Research Park Building at IITG campus
Bill of Quantity
Research Block : FIRE DETECTION, ALARM & P.A. SYSTEM
10
Supply , installation, testing & commissioning of M.S.
Junction Boxes. NOS 23
11
Supplying & laying 2 core x 1.5 sq.mm copper conductor
PVC insulated, sheathed armoured cable - ISI marked.
Rm 5347
12 Supplying & laying Telephone wire
Research Block Rm 900
13
Supply, installation, Testing, Commissioning of Field
Handset for Both way Communication system.
Research Block Set 12
14
Supply, installation, Testing, Commissioning of Fire
Fighter Telephone Jack.
Research Block Each 12
15
Supply, installation, Testing, Commissioning of
Telephone Module.
Research Block Each 12
16
Supply, installation, Testing & Commissioning of Digital
Voice Evacuaition.
Research Block Set 12
17
Supply, installation, Testing & Commissioning of 50 Wat
Amplifer.
Research Block Each 1
18
Providing, Installing, Testing & Commissioning Horn with
Strobe, complete.
Research Block Each 12
19
Providing, Installing, Testing & Commissioning Relay
Moudle, all complete.
Research Block Each 12
20
Sprinklers - Supply, installation, testing & commissioning
of open type spray nozzles ( sprinkler jets)) - pendent
type - with 1/2" inch inlet connection (male threaded)
with deflector and quartzoid bulb of (MAKE :- "Tyco" /
"Viking"/ "Central" - Model :ELO-16 / "Crawlie & Ray" /
"Omex"), Conventional "Pendent" - "UL" Listed
Sprinklers. (For Sprinkler system)
(a)
("Pendent" only - in all Floors below False Ceiling / True
ceiling) Each 399
(b)
("Up-Right" only - in respective Floors, above False
Ceiling only). Each 335
Gross Total (Research Block)
FIRE DETECTION, ALARM & P.A. SYSTEM
1
Supply, installation, testing & commissioning of short -
circuit - Isolators.
Nos 23
2
Supply, installation, testing & commissioning of Control
Modules (CMX) for controlling Hooters/ speakers,
Strobe (Flasher) Lamps, Manual Call Points (MCP), etc.
Each 8
3
Supply, installation, testing & commissioning of 'Rise'
type Heat Detectors, approved make, with Operating
Temperature of ( - ) 10OC to ( + ) 70
OC and OPERATING
VOLTAGE OF 18 TO 28 V D.C.
Kitchen Each 6
4
Supply, installation, testing & commissioning of 'Rise'
type Multicriteria Detectors, approved make, with
Operating Temperature of ( - ) 10OC to ( + ) 70
OC and
OPERATING VOLTAGE OF 18 TO 28 V D.C.
Nos 330
5
Supplying, fitting & fixing Base of Dectector,Model no-
B501
Nos 342
6 Supplying, fitting & fixing Duck Dectector.
Apartment Block
Kitchen Nos 6
7
Supply, installation, testing & commissioning of manual
push button station break glass type - Manual call
points (MCP) with MS / ABS body, with chain &
hammer, and also with Blinking facility, completely
compatible with the main Fire Alarm Panel.
Apartment Block
Each 20
8
Supply , installation, testing & commissioning of Monitor
Modules for Manual call points - (MMX)
Apartment Block
Each 8
9
Supply , installation, testing & commissioning of M.S.
Junction Boxes. NOS 20
Apartment block (FIRE DETECTION, ALARM SYSTEM)
10
Supplying & laying 2 core x 1.5 sq.mm copper conductor
PVC insulated, sheathed armoured cable - ISI marked.
Rm 3581.3
11 Supplying & laying Telephone wire
Apartment Block Rm 400
12
Supply, installation, Testing, Commissioning of Field
Handset for Both way Communication system.
Apartment Block Set 8
13
Supply, installation, Testing, Commissioning of Fire
Fighter Telephone Jack.
Apartment Block Each 8
14
Supply, installation, Testing, Commissioning of
Telephone Module.
Apartment Block Each 8
15
Supply, installation, Testing & Commissioning of Digital
Voice Evacuaition.
Apartment Block Set 8
16
Supply, installation, Testing & Commissioning of 50 Wat
Amplifer.
Apartment Block Set 1
17
Providing, Installing, Testing & Commissioning Horn with
Strobe, complete.
Apartment Block Each 8
18
Providing, Installing, Testing & Commissioning Relay
Moudle, all complete.
Apartment Block Each 8
19
Sprinklers - Supply, installation, testing & commissioning
of open type spray nozzles ( sprinkler jets)) - pendent
type - with 1/2" inch inlet connection (male threaded)
with deflector and quartzoid bulb of (MAKE :- "Tyco" /
"Viking"/ "Central" - Model :ELO-16 / "Crawlie & Ray" /
"Omex"), Conventional "Pendent" - "UL" Listed
Sprinklers. (For Sprinkler system)
(a)
("Pendent" only - in all Floors below False Ceiling / True
ceiling)
Each 222
(b)
("Up-Right" only - in respective Floors, above False
Ceiling only).
Each 136
20
Providing, Installing, Testing & Commissioning of cyling /
wall mounted Baffle Speaker of 6 watts each, complete.
Apartment Block Each 40
Gross Total (Apartment Block)
Item no. Description Unit Quantity Rate in figure (Rs.) Rate in words Total Amount(Rs.)
1 Wiring for light point/ fan point/ exhaust fan point/ call bell
point with 1.5 sq.mm FRLS PVC insulated copper conductor
single core cable in surface / recessed medium class PVC
conduit, with modular switch, modular plate, suitable GI box
and earthing the point with 1.5 sq.mm FRLS PVC insulated
copper conductor single core cable etc. as required.
1.1 Group B Point 3.00
1.2 Group C Point 20.00
2 Wiring for circuit/ submain wiring alongwith earth wire with
the following sizes of FRLS PVC insulated copper conductor,
single core cable in surface/ recessed medium class PVC
conduit as required.
-
2.1 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire meter 80.00
2.2 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire meter 190.00
4 Supplying and fixing following modular switch/ socket on the
existing modular plate & switch box including connections but
excluding modular plate etc. as required.
-
4.1 5/6 A switch Each 1.00
4.2 15/16 A switch Each 6.00
4.3 3 pin 5/6 A socket outlet Each 1.00
4.4 6 pin 15/16 A socket outlet Each 6.00
7 Supplying and fixing following size/ modules, GI box alongwith
modular base & cover plate for modular switches in recess etc.
as required.
7.2 3 Module (100 mmX75 mm) Each 1.00
7.3 4 Module (125 mmX75 mm) Each 6.00
8 Supplying and fixing 3 pin, 5 A ceiling rose on the existing
junction box/ wooden block including connections etc. as
required.
Each 3.00
-
Bill of Quantity
Name of Work: Construction of Research Park at IITG Campus.
Part-E(Electrical works)
Basic Infra Part-A
WIRING IN STEEL & PVC CONDUIT
CHAPTER-2-MCCB, MCB & DB’S
10 Supplying and fixing following way, single pole and neutral,
sheet steel, MCB distribution board, 240 V, on surface/ recess,
complete with tinned copper bus bar, neutral bus bar, earth
bar, din bar, interconnections, powder painted including
earthing etc. as required. (But without MCB/RCCB/Isolator)
-
10.1 6 way, Double door Each 1.00
11 Supplying and fixing following way, horizontal type three pole
and neutral, sheet steel, MCB distribution board, 415 V, on
surface/ recess, complete with tinned copper bus bar, neutral
bus bar, earth bar, din bar, interconnections, powder painted
including earthing etc. as required. (But without
MCB/RCCB/Isolator)
-
11.1 4 way (4 + 12), Double door Each 1.00
13 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C”
curve, miniature circuit breaker suitable for inductive load of
following poles in the existing MCB DB complete with
connections, testing and commissioning etc. as required.
-
13.1 Single pole Each 18.00
13.2 Double pole Each 1.00
13.3 Triple pole and neutral Each 1.00
13.3 Supplying and fixing single pole blanking plate in the
existing MCB DB complete etc. as required.
Each 4.00
-
-
19.1 Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia
including accessories, and providing masonry enclosure with
cover plate having locking arrangement and watering pipe etc.
with charcoal/coke and salt as required.
Each 41.00
19.2 Earthing with copper earth plate 600 mm X 600 mm X 3 mm
thick including accessories, and providing masonry enclosure
with cover plate having locking arrangement and watering pipe
of 2.7 meter long etc. with charcoal/ coke and salt as required.
Set 10.00
WIRING IN STEEL & PVC CONDUIT
CHAPTER -5- EARTHING
19.3 Supplying and laying 25 mm X 5 mm copper strip at 0.50 meter
below ground as strip earth electrode, including
connection/terminating with nut, bolt, spring, washer etc. as
required.(Jointing shall be done by overlapping and with 2 sets
of brass nut bolt & spring washer spaced at 50 mm)
meter 150.00
19.4 Supplying and laying 25 mm X 5 mm G.I strip at 0.50 meter
below ground as strip earth electrode, including
connection/terminating with G.I. nut, bolt, spring, washer etc.
as required.(Jointing shall be done by overlapping and with 2
sets of G.I. nut bolt & spring washer spaced at 50 mm)
meter 660.00
19.5 Providing and fixing 25 mm X 5 mm copper strip on surface or
in recess for connections etc. as required.
meter 72.00
19.6 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in
recess for connections etc. as required.
meter 304.00
19.7 Providing and fixing 6 SWG dia G.I. wire on surface or in recess
for loop earthing as required.
meter 1,060.00
-
20.1 Providing and fixing of lightning conductor finial, made of 25
mm dia 300 mm long, G.I. tube, having single prong at top, with
85 mm dia 6 mm thick G.I. base plate including holes etc.
complete as required.
Each 7.00
20.2 Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet
or on surface of wall for lightning conductor complete as
required.(For horizontal run)
meter 410.00
20.3 Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet
or on surface of wall for lightning conductor complete as
required. (For vertical run)
meter 235.00
20.4 Providing and fixing testing joint, made of 20 mm X 3 mm thick
G.I. strip, 125 mm long, with 4 Nos. of G.I. bolts, nuts, chuck
nuts and spring washers etc. complete as required
Each 107.50
-
21 Laying of one number PVC insulated and PVC sheathed / XLPE
power cable of 1.1 kV grade of following size direct in ground
including excavation, sand cushioning, protective covering and
refilling the trench etc. as required.
-
21.1 Upto 35 sq. mm meter 400.00
21.2 Above 95 sq. mm and upto 185 sq. mm meter 966.00
CHAPTER 6-LIGHTNING CONDUCTOR
CHAPTER 7-MV CABLE LAYING
21.3 Above 185 sq. mm and upto 400 sq. mm meter 1,796.00
22 Laying of one number PVC insulated and PVC sheathed / XLPE
power cable of 1.1 kV grade of following size in the existing
RCC/ HUME/ METAL pipe as required.
-
22.1 Upto 35 sq. mm meter 66.00
22.2 Above 95 sq. mm and upto 185 sq. mm meter 76.00
22.3 Above 185 sq. mm and upto 400 sq. mm meter 40.00
23 Laying and fixing of one number PVC insulated and PVC
sheathed / XLPE power cable of 1.1 kV grade of following size
on wall surface as required.
-
23.1 Upto 35 sq. mm (clamped with 1mm thick saddle) meter 1,504.00
24 Laying and fixing of one number PVC insulated and PVC
sheathed / XLPE power cable of 1.1 kV grade of following size
on cable tray as required.
-
24.1 Upto 35 sq. mm (clamped with 1mm thick saddle) meter 2,238.00
24.2 Above 95 sq. mm and upto 185 sq. mm (clamped with 25/
40x3mm MS flat clamp)
meter 128.00
24.3 Above 185 sq. mm and upto 400 sq. mm (clamped with
40x3mm MS flat clamp)
meter 600.00
-
25 Supplying and making end termination with brass compression
gland and aluminium lugs for following size of PVC insulated
and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV
grade as required.
-
25.1 3½ X 35 sq. mm (32mm) each 48.00
25.2 3½ X 120 sq. mm (45 mm) each 8.00
25.3 3½ X 185 sq. mm (57mm) each 16.00
25.4 3½ X 300 sq. mm (70 mm) each 56.00
25.5 4 X 10 sq. mm (25 mm) each 230.00
25.6 4 X 16 sq. mm (28mm) each 4.00
-
-
26 Providing, laying and fixing following dia G.I. pipe (medium
class) in ground complete with G.I. fittings including trenching
(75 cm deep) and re-filling etc. as required
-
26.1 50 mm dia meter 100.00
CHAPTER 14- MISC. CIVIL ITEMS
CHAPTER 9-MV CABLE JOINTING & END TERMINATION
27Providing, laying and fixing following dia RCC pipe NP2 class
(light duty) in ground complete with RCC collars, jointing with
cement mortar 1:2 (1 cement : 2 fine sand) including trenching
(75 cm deep) and refilling etc. as required.
-
27.1 300 mm dia meter 300.00
1.00 MV SWITCHGEAR / POWER PANEL / DISTRIBUTION BOARDS.
1.10 POWER PANEL:
Supply, installation, testing and commissioning of cubicle type
panels as specified and shown on drawing no. WTE2233/STAGE
2/901 SHEET 1 TO 6 with :
i) Main Aluminium busbars with bar type feeder connections &
all internal wiring and connections.
ii) Earthing all components, frame etc. to a common internal
earth bar.
iii) Powder Coat painting of all sheet metal works.
iv) All accessories & supporting structure.
v) Brass glands and crimping lugs for sending and receiving
ends.
vi) All ammeters with C.T's and voltmeter and energy meters
with necessary fuses.
vii) Panel components as specified.
viii) MS base frame.
ix) All switch gear to have short circuit levels as specified.
1.1 MAIN LT PANEL each 1.00
1.2 APFC PANEL(700KVAR) each 2.00
1.3 LAB BLOCK MAIN PANEL each 1.00
1.4 APARTMENT BLOCK MAIN PANEL each 1.00
1.5 FEEDER PILLAR PANEL each 1.00
1.6 UPS PANEL each 1.00
1.14 UTILITY PANEL each 1.00
2.00 MV CABLE
2.1 Supply of heavy duty 1100V grade LT XLPE insulated sheathed
& armoured cables with aluminium / copper conductors as
specified and required.
2.1.1 4C X 10sq.mm. Al. Ar. XLPE Cable rm 2,324.00
Basic Infra Part-B
2.1.2 4C X 16sq.mm. Al. Ar. XLPE Cable rm 66.00
2.1.3 3.5C X 35sq.mm. Al. Ar. XLPE Cable rm 1,770.00
2.1.4 3.5C X 120sq.mm. Al. Ar. XLPE Cable rm 276.00
2.1.5 3.5C X 185sq.mm. Al. Ar. XLPE Cable rm 894.00
2.1.6 3.5C X 300sq.mm. Al. Ar. XLPE Cable rm 2,436.00
2.1.7 4C X 4sq.mm. CU. Ar. XLPE Cable rm 50.00
2.1.8 12C X 1.5sq.mm. CU.pvc control Cable rm 30.00
2.1.9 3C X 1.5sq.mm. CU. AR. XLPE Cable rm 48.00 3 INTERNAL LIGHT, CEILING AND EXHAUST FAN FITTINGS
3.1.5
Surface mounted 1200mm high effiecency 20W integrated
LED batten, with minimum 100 Lumens/Watt efficacy. CCT
6500K, CRI> 80. Luminaire driver should be Isolated and
multistage constant current type. Driver Input voltage range
of 150V to 270V ( nominal rated voltage – 240V) with
minimum 2.5KV surge protection, PF >0.90, THD <20%,
Similar to Wipro Make LL20-221-XXX-65NE1 or equivalent.each
12.00
3.1.9
Supply of Bulkhead LED enclosed in die cast Aluminium
housing for superior heat management and Polycarbinate
opul diffuser. The maximum system wattage should be 10W.
CCT 5700K, CRI> 80. Luminaire driver should be Isolated and
multistage constant current type. Driver Input voltage range
of 150V to 270V ( nominal rated voltage – 240V) with
minimum 2.5KV surge protection, PF >0.9, THD <20%,.
Luminaire should be IP65 Protected. Similar to Wipro Make
LW07-141-XXX-57-XX or equivalent.each
8.00
3.1.11 450mm sweep exhaust fan heavy duty each 3.00
5 SUBSTATION AUXILIARIES INSTALLATION -
5.1 Supply and fixing of MS chequered plate 6mm thick of different
size for covering trench inside substation area including MS
angle of section 35 x 35 x 5mm for support of plate and
necessary civil work and painting
SqM 60.00
5.2 Supply and fixing of shock treatment chart with glass and
aluminium frame on wall in Bengali, Hindi and English
each 2.00
5.3 Supply of First Aid box with all necessary materials and
medicines
each 1.00
5.4 Supply,installation of 4.5kg CO2 fire extinguisher complete with
intial charges discharge hose, horn and bracket
each 2.00
5.5 Supply and fixing of fire bucket filled with sand each 8.00
5.6 Supply and erection of fire bucket stand 1500mm wide and
1000mm height, made of 50mm x 50mm x 6mm angle iron with
cross bracing and 4nos. Hook for hanging the bucket as
completed with painting (2 coats of Red paint over one coat of
red oxide primer)
each 2.00
6 EXTERNAL LIGHTING -
6.1 Supply & fixing of Top Maintainable LED Street Light luminaire
enclosed in pure polyester powder coated Pressure Die Cast
aluminium housing suitable to mounted on 55 mm OD bracket
arm. The maximum wattage of luminaire shall be 70W with
minimum system efficacy 110lm/W. Luminaire shall have two
separate compartments for LEDs and driver and both
compartments should be hermitically sealed to achieve IP 66
ingress protection. Optical compartment shall be provided with
heat resistant clear toughened glass to withstand IK 07 impact
rating, while control gear shall be provided with die cast
aluminium cover for safety. Potted LED Driver shall be SELV,
Isolated type, multistage Constant Current Constant Voltage
topology driver with proper heat sink for heat dissipation
suitable to operate in input voltage range of 100V to 300V
(nominal rated voltage – 240V) with 4 KV internal surge
protection in both CM and DM mode. Similar to Wipro make
LR02-781-XXX-57-G2 or Equivalent.
40.00
6.2 Supply & fixing of 45W top maintanable LED Post-top housed in
die cast aluminium housing and HET diffuser. Luminaire is
suitable for pole diameter of
65-75 mm. Protected with IP65 protection. CCT 5700K, CRI >70.
Similar to wipro make LP02-501-XXX-57-XX and Equivalent
4.00
6.3 Supply, installation , testing & commisioning of Steel 9 Mtr GI
Octagonal Pole -Top dia -70 mm, Bottom Dia-155 mm, Section-
1 (Section Length - 7000 mm) Thick-3mm. Base Plate - 260mm x
260mm x 16mm. hole in pole at a height of 300mm above the
planting depth with Single Arm Bracket 1 Mtr long with
33.7mm OD GI Pipe and coated with two coats of black
bituminous paint through out internally and externally upto
the planting depth and the remaining portion above ground
shall be painted with two coat of aluminium painting over one
coat of red oxide primer and individual spike earthing with 8
SWG wire inclusive of civil foundation work. Foundation Bolt-
M24 x 750 mm (4Nos)
-
6.3.1 Single arm (9 MTR) no. 44.00
6.4 Supply & fixing of Junction box with clamp on street light pole /
recessed in gate pillars, comprising of 6A SP MCB with elmex
terminals suitable for terminating incoming and out going
cables of upto 3 core 10 sq.mm 1.1 kV grade armoured PVC
insulated and covered cables including bolt,nut & screws, D -
clamp etc. as complete and as directed by Engineer - in -
charge.
no. 44.00
6.5 Wiring with 3 X 1.5sqmm 600 V grade FRLS insulated flexible Cu
conductor wire from looping junction boxes at the base of the
pole to the light fittings through prelaid rigid PVC conduit, as
required to be completed in all respect and as directed by
Engineer - in - Charge.
rm 360.00
6.6 Supply and fixing of integral LED AVIATION Light with double
lamp including all necessary accessories as required.
nos 1.00
7.0 Providing and fixing following capacity 4 pole automatic on
load ON/OFF -Load changeover switches with side handle
operation, in sheet enclosure in metal board including drilling
holes in metal board, making connection , earthing the body
etc. as required.
-
7.1 100 A , 4 POLE nos -
7.2 630 A , 4 POLE nos -
18.0 TELEPHONE, CCTV, ACCES CONTROL -
18.1 Supply testing commessioning of IP DIGITAL Indoor/Outdoor
Type MEGAPIXEL CAMERA-(IR Camera , 4.9 MEGAPIXEL SONY
CHIPSET LOW ILLUMINATION HIGH COLOR RESOLUTION AUDIO
MIC SUPPORT,POE SUPPORT , /MM lens, 50 mts (works in zero
Light)- video output• ONVIF technology• True day / night •
DNR, Smart IR• Up to 25m IR distance H.265 With Smart
Analytics & embedded Intelligence)
nos 65.00
18.2 Supply testing commessioning of HD NVR : Recording Unit For
Cameras 36 Channel 4K NVR - with support for 4 SATA Hard
Disk And Audio Mic Support in 36 Channels H.265 With Smart
Analytics & embedded Intelligence (1) 4K NVR WIith Preview /
Recording Resolution upto 12MP 2) Recording frame rate: 3)
SATA port: H.265 With Smart Analytics & embedded
Intelligence , 4 SATA HDD support 4)USB 2.0 Ports, VGA output,
HDMI port . 5) Support Onvif; Third-party IP cameras Supports
3G, 6) Support 15 x digital zoom in preview/ playback channel
Support IE, mobile phone remote monitoring)
nos 2.00
18.3 Supply testing commessioning of INTERCOM SYSTEM P&T Ports
: 08 ; Digital Extension : 08 ; Extension Ports : 184
nos 1.00
18.4 Supply testing commessioning of INTERCOM SYSTEM P&T Ports
: 08 ; Extension Ports : 136
nos 1.00
18.5 Supply testing commessioning of ACCESS CONTROL SYSTEM
ACCESS CONTROL WITH SINGLE LEAF LOCK ALONG WITH
ACCESSORIES , 4PC CARD PER DEVICE ,EXIT
SWITCHFINGER+CARD BASED STAND ALONE ACCESS CONTROL
WITH LOCK AND ACCESSORIES of Toshiba/Western Digital /
Seagate make
nos 24.00
18.6 Supply testing commessioning of Hard Disk Internal
Surveillance Hard Disk For Recording unit- 4TB of
Toshiba/Western Digital / Seagate make
pcs 4.00
18.7 Supply testing commessioning of Power Supply LOCAL POWER
POINT TO BE PROVIDED NEAR EACH CAMERA of GPTRON make
port 100.00
18.8 Supply testing commessioning of 8 Port Network Switch of
DLINK/REPUTED make
pcs 280.00
18.9 Supply testing commessioning of 16 Port Network Switch of
DLINK/REPUTED make
pcs 2.00
18.10 Supply testing commessioning of telephone reciever of
REPUTED make
pcs 136.00
18.11 Supply testing commessioning of KTS reception phone of
REPUTED make
pcs 2.00
18.12 Supply testing commessioning of krone module for intercom of
REPUTED make
pcs 7.00
18.13 Supply testing commessioning of Desktop Computer For
Viewing Cameras from the reception for intercom of REPUTED
make
pcs 2.00
18.14 Supply testing commessioning of Camera Connectors lot 1.00
18.15 Supply & laying of Camera Network Cable rm 2,500.00
18.16 Supply & laying of Power Cable rm 1,000.00
18.17 Supply & laying Telephone cable rm 5,200.00
18.18 Supply & laying Conduit Pipe rm 8,700.00
18.19 Supply testing commessioning of Rack 6u nos 2.00
18.20 Supply testing commessioning of LED 42 INCH LED nos 2.00
18.21 Accessories for keeping camera /network switch accessories at
the place of installation
pcs 80.00
18.22 Laying Charges with accessories rm 8,700.00
18.23 Training /Installation Charges job 1.00
4.00 DIESEL GENERATOR SET
4.1 Supply, installation, testing, commissioning of DG set with
accoustic enclosure including supply and installation of exhaust
pipe with 48kg/cum density fibreglass white wool along with all
MS support structure (The insulation shall be held in position
with galvanised steel wire mesh 0.63dia and finished neatly
with 26SWG aluminium cladding) as required from engine to
residential silencer and thereafter upto termination point 3 M
above the roof level or as per lattest PCB norms and as
specified in equipment data sheet.
4.1,1 160 KVA (with Auto mains failure Panel) each 1.00
4.1.2 1250 KVA each 1.00
4.1.2.1 1250 KVA Auto mains failure, Auto load sharing & Auto
synchronization Panel
DIESEL GENERATOR
4.1.3 500 KVA (with Auto mains failure Panel) each 1.00
7.00 LIFT7.1 Supply, installation testing and commissioning of lifts of
maximum rated load 15 passenger, speed 1.75mps of triplex
system travelleing for G +10 floors of travel height. Hair line
stainlesssteel venyle floor finish, centre opening automatic
door of fire retardent capacity not less than 2hours without
machine room, gear less system inclusive of all accessories,
gadgets, emergency light car operating panel indicator door
close and open button alarms, colour LCD display, emergency
phone, handicapped COP, braille push buttons, star light ceiling
finish inside the car, PVC floor finish, and all other devices
complying to fire escape, emergency evacuation control, NBC
etc. complete in all respect inclusive of taxes duties etc.
EACH 2.00
7.4 Supply, installation testing and commissioning of lifts of
maximum rated load 544Kg, speed 1.00mps, travelleing for G
+ 7 floors of travel height hair line stainlesssteel venyle floor
finish, centre opening automatic door of fire retardent capacity
not less than 2hours with machine room, gear less system
inclusive of all accessories, gadgets, emergency light car
operating panel indicator door close and open button alarms,
colour LCD display, emergency phone, handicapped COP,
braille push buttons, star light ceiling finish inside the car, PVC
floor finish, and all other devices complying to fire escape,
emergency evacuation control, NBC etc. complete in all respect
inclusive of taxes duties etc.
EACH 1.00
1.7 LAB BLOCK LIFT PANEL each 1.00
1.8 APARTMENT BLOCK LIFT PANEL each 1.00
Internal Electrification (Part-A)
1 Wiring for light point/ fan point/ exhaust fan point/ call bell
point with 1.5 sq.mm FRLS PVC insulated copper conductor
single core cable in surface / recessed medium class PVC
conduit, with modular switch, modular plate, suitable GI box
and earthing the point with 1.5 sq.mm FRLS PVC insulated
copper conductor single core cable etc. as required.
1.1 Group B Point 169.00
1.2 Group C Point 749.00
2 Wiring for circuit/ submain wiring alongwith earth wire with
the following sizes of FRLS PVC insulated copper conductor,
single core cable in surface/ recessed medium class PVC
conduit as required.2.1 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire meter 6,050.00
2.2 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire meter 10,265.00
2.3 2 X 4 sq. mm + 1 X 4 sq. mm earth wire meter 6,819.00
2.4 4 X 4 sq. mm + 2 X 4 sq. mm earth wire meter 250.00
3 Supplying and fixing of following sizes of medium class PVC
conduit along with accessories in surface/recess including
cutting the wall and making good the same in case of recessed
conduit as required. 3.1 25 mm meter 850.00
3.2 32 mm meter 550.00
4 Supplying and fixing following modular switch/ socket on the
existing modular plate & switch box including connections but
excluding modular plate etc. as required.
4.1 5/6 A switch Each 134.00
4.2 15/16 A switch Each 568.00
4.3 3 pin 5/6 A socket outlet Each 1,430.00
4.4 6 pin 15/16 A socket outlet Each 136.00
4.5 Bell push Each 24.00
5 Supplying and fixing two module stepped type electronic fan
regulator on the existing modular plate switch box including
connections but excluding modular plate etc. as required.
Each 78.00
6 Supplying and fixing modular blanking plate on the existing
modular plate & switch box excluding modular plate as
required.
Each 432.00
7 Supplying and fixing following size/ modules, GI box alongwith
modular base & cover plate for modular switches in recess etc.
as required.
7.2 3 Module (100 mmX75 mm) Each 134.00
7.3 4 Module (125 mmX75 mm) Each 136.00
7.4 8 Module (125 mmX125 mm) Each 432.00
8 Supplying and fixing 3 pin, 5 A ceiling rose on the existing
junction box/ wooden block including connections etc. as
required.
Each 44.00
9 Wiring for group controlled (looped) light point/fan
point/exhaust fan point/ call bell point (without independent
switch etc.) with 1.5 sq. mm FRLS PVC insulated copper
conductor single core cable in surface/ recessed PVC conduit,
and earthing the point with 1.5 sq. mm FRLS PVC insulated
copper conductor single
core cable etc. as required.9.1 Group C Point 422.00
10 Supplying and fixing following way, single pole and neutral,
sheet steel, MCB distribution board, 240 V, on surface/ recess,
complete with tinned copper bus bar, neutral bus bar, earth
bar, din bar, interconnections, powder painted including
earthing etc. as required. (But without MCB/RCCB/Isolator)
10.1 6 way, Double door Each 32.00
11 Supplying and fixing following way, horizontal type three pole
and neutral, sheet steel, MCB distribution board, 415 V, on
surface/ recess, complete with tinned copper bus bar, neutral
bus bar, earth bar, din bar, interconnections, powder painted
including earthing etc. as required. (But without
MCB/RCCB/Isolator)11.1 4 way (4 + 12), Double door Each 32.00
11.2 6 way (4 + 18), Double door Each 17.00
13 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C”
curve, miniature circuit breaker suitable for inductive load of
following poles in the existing MCB DB complete with
connections, testing and commissioning etc. as required.
13.1 Single pole Each 816.00
MCCB, MCB & DB’S
13.2 Double pole Each 41.00
13.3 Triple pole and neutral Each 44.00
13.3 Supplying and fixing single pole blanking plate in the
existing MCB DB complete etc. as required.
Each 112.00
15 Supplying and fixing 30 A, 415 V, TPN Industrial type socket
outlet, with 4 pole and earth, metal enclosed plug top
alongwith 30 A, “C” curve, TPMCB, in sheet steel enclosure, on
surface or in recess, with chained metal cover for the socket
out let and complete with connections, testing and
commissioning etc. as
required.
Each 16.00
16 Supplying and installing following size of perforated Hot Dipped
Galvanised Iron cable tray (galvanisation thickness not less than
50 microns) with perforation not more than 17.5%, in
convenient sections, joined with connectors, suspended from
the ceiling with G.I. suspenders including G.I. bolts & nuts, etc.
as required.16.1 150 mm width X 50 mm depth X 1.6 mm thickness Each 115.00
16.2 300 mm width X 50 mm depth X 1.6 mm thickness Each 640.00
17 Supplying and installing following size of perforated Hot Dipped
Galvanised Iron cable tray “bends” (galvanisation not less than
50 microns) with perforation not more than 17.5%, in
convenient sections, joined with connectors, suspended from
the ceiling with G.I. suspenders including G.I. bolts & nuts, etc.
as required.17.1 150 mm width X 50 mm depth X 1.6 mm thickness Each 13.00
17.2 300 mm width X 50 mm depth X 1.6 mm thickness Each 36.00
18 Supplying and installing following size of perforated Hot Dipped
Galvanised Iron cable tray “Tee” (galvanisation not less than 50
microns) with perforation not more than 17.5%, in convenient
sections, joined with connectors, suspended from the ceiling
with G.I. suspenders including G.I. bolts & nuts, etc. as
required.18.1 150 mm width X 50 mm depth X 1.6 mm thickness Each 4.00
18.1 300 mm width X 50 mm depth X 1.6 mm thickness Each 8.00
Internal Electrification (Part-B)
1.00 MV SWITCHGEAR / POWER PANEL / DISTRIBUTION BOARDS.
1.10 POWER PANEL:
Supply, installation, testing and commissioning of cubicle type
panels as specified and shown on drawing no. WTE2291/STAGE
2/7.001 SHEET 1
i) Main Aluminium busbars with bar type feeder connections &
all internal wiring and connections.
ii) Earthing all components, frame etc. to a common internal
earth bar.
iii) Powder Coat painting of all sheet metal works.
iv) All accessories & supporting structure.
v) Brass glands and crimping lugs for sending and receiving
ends.
vi) All ammeters with C.T's and voltmeter and energy meters
with necessary fuses.
vii) Panel components as specified.
viii) MS base frame.
ix) All switch gear to have short circuit levels as specified.
1.9 LAB BLOCK LIGHTING & POWR FLOOR PANEL (L1, L2, L3) each 2.00
1.10 APARTMENT BLOCK LIGHTING & POWR FLOOR PANEL A1 each 1.00
1.11 APARTMENT BLOCK LIGHTING & POWR FLOOR PANEL A2, A3 each 1.00
1.12 KITCHEN & DINNING DB each 1.00
1.13 LAB DB (1 TO 8) each 16.00
3.1 Supply & fixing of light fixtures complete with:
a) Lamps and Ballasts
b) all necessary accessories as required
C) all necessary Down rods & fixing accessories for suspending
type light fittings
3.1.1 600 x 600 mm recess mounting decorative direct/indirect LED luminaire enclosed in powder coated CRCA deep drawn housing with unique floating spherical direct diffuser and surrounding indirect light chamber. The luminaire comprised with two optical compertment and it should be controlled seperately. The maximum system wattage should be 34W with minimum system efficacy 100lm/w, CCT 5700K, CRI> 80. . Luminaire driver should be Isolated and multistage constant current constant voltage type. input voltage range of 150V to 270V ( nominal rated voltage – 240V) with minimum 3KV surge protection, PF >0.95, THD <10%, Similar to Wipro Make LM38-461-XXX-57-XX or Equivalent.each 96.00
3.1.2 Supply of recess mounted LED Downlight enclosed in preseure die cast aluminum housing for superior heat management and HET diffuser for better light output and uniform light distribution without glare. The maximum system wattage should be 11W with minimum system efficacy 95lm/w, CCT 6500K, CRI> 80. Luminaire driver should be Isolated and multistage constant current type. Driver Input voltage range of 150V to 270V ( nominal rated voltage – 240V) with minimum 2.5KV surge protection, PF >0.95, THD <20%, Similar to Wipro Make LD91-141-XXX-65-XX or equivalent.each 130.00
3.1.3 Supply of recess mounted LED Downlight enclosed in preseure die cast aluminum housing for superior heat management and HET diffuser for better light output and uniform light distribution without glare. The maximum system wattage should be 15W with minimum system efficacy 95lm/w, CCT 6500K, CRI> 80. Luminaire driver should be Isolated and multistage constant current type. Driver Input voltage range of 150V to 270V ( nominal rated voltage – 240V) with minimum 2.5KV surge protection, PF >0.95, THD <20%, Similar to Wipro Make LD91-201-XXX-65-XX or equivalent.each 422.00
3.1.4 Surface mounted 600mm high effiecency 10W integrated LED
batten, with minimum 100 Lumens/Watt efficacy. CCT 6500K,
CRI> 80. Luminaire driver should be Isolated and multistage
constant current type. Driver Input voltage range of 150V to
270V ( nominal rated voltage – 240V) with minimum 2.5KV
surge protection, PF >0.90, THD <20%, Similar to Wipro Make
LL20-111-XXX-65-NE or equivalent.
each 75.00
3.1.5 Surface mounted 1200mm high effiecency 20W integrated LED batten, with minimum 100 Lumens/Watt efficacy. CCT 6500K, CRI> 80. Luminaire driver should be Isolated and multistage constant current type. Driver Input voltage range of 150V to 270V ( nominal rated voltage – 240V) with minimum 2.5KV surge protection, PF >0.90, THD <20%, Similar to Wipro Make LL20-221-XXX-65NE1 or equivalent.each 161.00
3.1.6 Surface/Suspended integrated LED Channel enclosed in CRCA housing for superior heat management and highly effective extruded Polycarbonate diffuser for maximum effective illumination. The maximum system wattage should be 39W with minimum system efficacy 100lm/w, CCT 5700K, CRI> 80. Luminaire driver should be Isolated and multistage constant current type. Driver Input voltage range of 150V to 270V ( nominal rated voltage – 240V) with minimum 3KV surge protection, PF >0.95, THD <10%, Similar to Wipro Make LE10-491-XXX-57-XX or equivalent.each 176.00
3.1.7 Suspended circular decorative LED Luminaire enclosed in CRCA housing for superior heat management and highly effective PMMA diffuser for maximum effective illumination. The maximum system wattage should be 26W, CCT 5700K, CRI> 80. Luminaire driver should be Isolated and multistage constant current type. Driver Input voltage range of 150V to 270V ( nominal rated voltage – 240V) with minimum 3KV surge protection, PF >0.95, THD <10%, Similar to Wipro Make LM71-341-XXX-57-XX or equivalent.each 23.00
3.1.8 Surface mounted LED Downlight enclosed in CRCA housing for superior heat management and HET diffuser for better light output and uniform light distribution. The maximum system wattage should be 9W. CCT 5700K, CRI> 80. Luminaire driver should be Isolated and multistage constant current type. Driver Input voltage range of 150V to 270V ( nominal rated voltage – 240V) with minimum 2.5KV surge protection, PF >0.9, THD <20%, Similar to Wipro Make LW01-101-XXX-57-XX or equivalent.each 39.00
3.1.9 Supply of Bulkhead LED enclosed in die cast Aluminium housing for superior heat management and Polycarbinate opul diffuser. The maximum system wattage should be 10W. CCT 5700K, CRI> 80. Luminaire driver should be Isolated and multistage constant current type. Driver Input voltage range of 150V to 270V ( nominal rated voltage – 240V) with minimum 2.5KV surge protection, PF >0.9, THD <20%,. Luminaire should be IP65 Protected. Similar to Wipro Make LW07-141-XXX-57-XX or equivalent.each 43.00
3.1.10 Supply of 2W recessed mounted LED Footlamp with all mounting accsessories. Similar To Wipro Make FL921or equivalent.each 24.00
3.1.12 300mm sweep exhaust fan each 46.00
3.1.13 BUZZER each 24.00
3.1.14 1200 mm sweep ceiling Fan each 64.00
3.1.15 600 mm sweep hi- speed ceiling Fan each 14.00
3.1.16 KEY card switch 3 PHASE each 8.00
3.1.17 KEY card switch single PHASE each 16.00
8 LAN SYSTEM
LAN NETWORK SYSTEM
8.1 PoE+ 24 Port Switch
The switch should have 24 x 10/100/1000Base t ports plus 4x
1000x SFP ports .Min 370 Watt PoE power budget and support
for IEEE 802.3af and IEEE 802.3at, Switch should have 16K MAC
entries table.Should have 8 Hardware QOS Queues per port ,OS
should support individual process (eg ssh , snmp, telnet, dhcp
etc) restart to prevent reboot in case of Software Process Crash
by running processes on top of Kernel.Switch should have
switching fabric performance of minimum 56Gbps switch
fabric. Layer 2, IP v4 & IP v6 - Switch should be upgradeable to
Open Shortest Path First (OSPF) and VRRP.Should support less
than 50 Millisecond convergance for ring based architecture
based on RFC 3619/REP/ERPS/G.8032 etc, Switch should have
Port, vlan, IPv4, IPv6, and time based Access Control Lists for
both directions. Switch should have Operating temperature:
32 to 122°F (0°C to 45°C). Preffered Make : CISCO/Extreme
/Juniper /Avaya
NOS 21.00
8.2 Core Switch
Switch should support stacking up to 8 switches or more with
stacking bandwidth of 40Gbps . The switch should have24x
10/100/1000Base t ports with 8x 1000x SFP ports .Min 4 10 G
based SFP+ port , Scalable to min 2 QSFP+ port , The switch
should be upgraded to 4 x SFP+ ports in future without
changing the base hardware . Should have min 2x Stacking port
with min 40 Gbps stacking bandwidth from day 1 .Stacking
should be ready from day 1 with accessorries /cables.Stacking
mechanism could be achieved over a diversified location as
minimum 800 Meters . Switch should have dedicated 1 x
10/100/1000 BaseT port for Out of band Management port.
Switch should have Operating temperature: 32 to 122°F
(0°C to 50°C). Preffered Make : CISCO/Extreme /Juniper /Avaya
NOS 1.00
8.3 CAT6 UTP cable - 4 pairs PVC - 23 AWG - 305 mtr Box4 Pair CAT6 Unshielded, Twisted Pair (U/UTP) Cable 305 mtr per Box. Blue/Orange/White/Green in colour conforming to the following standards like 23AWG, ANSI EIA/TIA 568 C.2, EN50173, IEC 11801 3rd ED, frequency tested upto 700Mhz with Third Party Certificate etc. Cable Dia 6.1 ± 0.3, Cross-member (+) fluted Spine/isolator for uniform separation for all pairs. (Make : Legrand /Systemax/Hubbel)Box 46.00
8.4 CAT6 RJ45 socket - User EndCat 6 UTP RJ 45 Sockets Tool Less Crimping, as per - ISO/IEC 11801 Edition 2; ANSI/EIA/TIA 568-C.2; IEC series 60603-7, should have transparent shutter for protection against dust, Contacts :gold/nickel, minimum thickness of gold > 0.8 μm , Body should PBT Polycarbonate plastic material, IEEE 802.3af standard and PoE+, Endurance 2500 movements (plug insertion/withdrawal). IK03. Operating Temp -40 Deg C to +70 Deg C, Maximum no of Connections/ Re connections 5 without refreshing the wiring. (Make : Legrand /Systemax/Hubbel)Nos 325.00
8.5 CAT6 UTP patch panel - 24 port loaded - Toolless
CAT6 UTP RJ45 Loaded patch panel & connector - 24 port
loaded 19" panel - 1 U, Panel: DC01 galvanised sheet steel,
Compliant with standards: ISO/IEC 11801 Edition 3.0 CENELEC
EN 50173-1 2007 ANSI/EIA/TIA 568 C2-1 IEC series 60603-7,
NFC 20730, Standard 8877 – 603.7, Contacts: gold/nickel,
thickness of gold > 0.8 μm minimum, Equipped with rear cable
guide to hold cable during maintenance,The connectors are
connected from the front without a special tool. Equipped with
4 cassettes of 6 RJ45 Cat. 6 connectors with toolless fast
connection, marked 568 A/B, Max. number of connections and
disconnections: 5 without replacing the wire, Endurance: 2500
operations (plug-in/pull-out) IK03, Operating temperature: -
40°C to +70°C (Make : Legrand /Systemax/Hubbel)
Nos 15.00
8.6 CAT6 UTP patch cord - 1 mtr - Rack End
1 Meter Cat 6 U/ UTP Patch Cord, PVC,Performance at 250MHz
Should be as per Standards - IEC 61935-2 - Ed. 3.0 ISO/IEC
11801, Usage Temp – 20 to + 60°C, No of Twists 500, No of
insertions 750, 24 AWG (Make : Legrand /Systemax/Hubbel)
Nos 325.00
8.7 CAT6 UTP patch cord - 2 mtr - User End
2 Meter Cat 6 U/ UTP Patch Cord, PVC ,Performance at
250MHz Should be as per Standards - IEC 61935-2 - Ed. 3.0
ISO/IEC 11801, Usage Temp – 20 to + 60°C, No of Twists 500,
No of insertions 750, 24 AWG (Make : Legrand
/Systemax/Hubbel)
Nos 325.00
8.8 Single port face plate
Single Port Face Plate 1 Module in white colour. (Make :
Legrand /Systemax/Hubbel)
Nos 325.00
8.9 Plastic surface box - 1/2 module
Plastic Flush Mounting Box 1/2 Module. (Make : Legrand
/Systemax/Hubbel)
Mtr 325.00
9.0 6 Core OM3 Unarmoured LSZH OFC
6 Core - Optic fiber cable OM3 - Unitube Single Jacket Unarmor
Lite, Jelly Filled Loose Tube Optical Fiber Cable 50 μm /125
μm , Glass Roving Yarn provide tensile strength and
antibuckling properties. LSZH Aqua RAL-6027, IEC 60793-2-10
category A1a.2; EN 60793-2-10: type A1a.2, TIA/EIA-492 AAAB,
ITU Recommendation G.651, EN 50 173:2002 category
OM3,ISO/IEC 11801:2002 category OM3, IEEE 802.3-2002 incl.
amendment 802.3ae - 2002. Maximum installation tensile
strength - E1 1000 N, - Short term tensilestrength - E1 650 N, -
Permanent tensilestrength - E1 350 N , Compressive
strength(crush) - E3 1500 N, Min. Bending radius,unloaded -
E11 10 D, Min. Bending radius,loaded 20 D, Operating temp : -
30°C to +70°C (Make : Legrand /Systemax/Hubbel)
Nos 400.00
9.1 19" Modular optic drawer
6 to 96 Port Rack mount Sliding Fibre optic drawer (LIU) with
trasperent cover, Metal 19” fibre optic drawers, 4 cable entries,
supplied with screw fixing kit, 2 cable glands (Ø 13.5 and 16
mm), coiling system, Sliding: end stop at a 30° angle for easier
wiring with lock with lock. Depth: 220 mm, height 1 U (Make :
Legrand /Systemax/Hubbel)
Nos 3.00
9.2 SC pigtails - OM3 - 1 mtr
SC pigtails - OM3 - 1 mtr, ITU-G651, standards TIA / EIA
492AAAD , 900 μm tight structure, Crush Resistance 500N
Operating temp : - 20°C to +60°C (Make : Legrand
/Systemax/Hubbel)
Nos 54.00
9.3 Unit of 3 duplex SC adapters loaded with adapter plate - MM
6 port Adapter plate, loaded with 3 nos. of duplex SC unit for
multi mode fiber adapters to be compatible to fit in 19" U/UTP
24 port modular patch panel or 24 port LIU. (Make : Legrand
/Systemax/Hubbel)
Nos 9.00
9.4 Splice Tray - 24 fibre capacity
Stackable Splice Tray - 24 fibre capacity, Stack upto 2 Splice
Tray In Single LIU (Make : Legrand /Systemax/Hubbel)
Nos 3.00
9.5 Blanking plate for LIU
Blanking plate for LIU and Modular Patch Panel (6XRJ45
Blanking plate for 19" panel - Black in colour). (Make : Legrand
/Systemax/Hubbel)
Nos 4.00
9.6 SC/LC duplex fibre patch cord - OM3 - 3 mtr
3 Meter SC/LC Optic Fiber Patch Cords – Multimode (OM3)
Operating temp : - 20°C to +60°C. Insertion loss: 0.15dB, 500
matings. Conform to IEC, EIA-TIA, and Telecordia performances
requirements. (Make : Legrand /Systemax/Hubbel)
Nos 9.00
9.7 Racks : 42U 800x800 Free standing cabinet with all standard accessoriesWidth (mm) 800, Depth (mm) 800, Approx.Net Wt (kg) 150, CRCA 'D' Grade thickness (mm) 1.2, RAL 9017 (Matt Black), Glass: 4mm Toughened Tinted Glass Door, Injected one piece polyurethane gasket on frame, Accessories: Cooling Fan (230V A/C 90 CFM) - 4 Nos, Cable Manager Metal- 4 Nos, PDU 230VAC - 1 No (12 nos. 6A/16A sockets with plugs 6A/16A - 1/1pc & MCB 16A/32A - 0/1 Pc), Cable Channel 100mm wide 42U- 2 Nos, Heavy Duty Stationary Shelf 600W x 475D - 1 No., Mounting Hardware (20 sets of M6 screws,washer,cage nuts (nickel coated)) - 3 Nos., Earthing Strips 150mm H - 1 No, Door Lock - 1 No, Castor Wheels (with Brake) - 2 Nos, Castor Wheels (without Brake) - 2 Nos, Front Metal Band - 1 No. Packing: 5 ply cardboard & Inside 28 ply EP foam. In the rack there must be maintained 1 U = 1.75 inches space. ( Make :Legrand/ Rittal / Valrack)Nos 1.00
9.8 27U 800x800 Free standing cabinet with all standard accessoriesWidth (mm)-800, Depth (mm) - 800, Approx.Net Wt (kg) - 100, CRCA 'D' Grade thickness (mm) - 1.2, RAL 9017 (Matt Black), Glass - 4mm Toughened Tinted Glass Door, Accessories:, Cooling Fan (230V A/C 90 CFM) - 4 Nos, PDU 230V AC - 1, Cable Channel 100mm wide 22U - 2 No, Cable Manager Metal - 2 Nos, Heavy Duty Stationary Shelf 600W x 475D - 1 No., Earthing Strips 150mm H - 1 No, Mounting Hardware (20 sets of M6 screws,washer,cage nuts (nickel coated)) - 3 No, Door Lock - 1 No, Front Metal Band -1 No., Castor Wheels (with Brake) - 2 Nos., Castor Wheels (without Brake) - 2 Nos. Packing: 5 ply cardboard & Inside 28 ply EP foam. In the rack there must be maintained1 U = 1.75 inches space. Nos 2.00
11.0 RISING MAIN
11.1 Supplying, installing on wall, testing and commissioning of
following capacity 1000 volt grade, 3phase 4 wire ( 100% N), IP-
55 Sandwich Type Rising mains made of 1.5 mm thick Hot-
galvanized sheet Steel confirming IK-10 impact strength duly
painted with RAL 7035 Resin , wall straps, fully insulated by
Class F ( 155 deg ) PET Film 4 Nos aluminium bus bars ( Cu+ Tin
Plating) in convenient sections and suitable for 415 volts, 3
phase, 4 wire, 50 Hz, A.C. supply with factory fitted joint
monobloc, expansion joints ( if length more than 40 mtrs), joint
cover, End Cover, Spring brackets and earthing with 2 runs of
Aluminium Earth strips etc. and provision for 2 nos. tap-off box
in each floor as required. (Rising mains confirming to IS 8623,
IEC 61439- 6, DIN VDE 0660 PART 500 AND 502)
11.1.1 1600 amps (S.C. rating for 1 sec - 50 KA) meter 22.50
11.1.2 630 amps (S.C. rating for 1 sec - 50 KA) meter 13.50
11.1.3 Elbow ( fabrication Cost) for 1600A NOS 4.00
11.1.4 Elbow ( fabrication Cost) for 630A NOS 4.00
11.1.5 Flanged End (fabrication Cost) for 1600A NOS 2.00
11.1.6 Flanged End (fabrication Cost) for 630A NOS 1.00
11.1.7 1600A Braided Cu Flexible ( electro-tinned with silver coated Socket) TPNSETS 2.00
11.1.8 630A Braided Cu Flexible ( electro-tinned with silver coated Socket) TPNSETS 1.00
11.1.9 Adopter Box for 1600A/ 630A NOS 3.00
12.0 Supplying, installing, testing and commissioning of following
capacity 4P tap off box / plug-in box made of 1.5mm thick
sheet steel enclosure duly painted with powder coating on
existing bus bar system complete with 4P MCCB, 36KA T/M
release , connection, earthing etc. as follows.
12.1 Tap-off-Box with 250A, FP, ( I cs = Icu = 36kA ) , incomer MCCB each 4.00
12.2 Tap-off-Box with 100A, FP, ( I cs = Icu = 36kA ) , incomer MCCB each 2.00
13.0 Supplying and fixing following modular switch / socket on the
modular plate & switch box including connections modular
plate etc. as required.
13.1 20 amps switch WITH 6 pin 20 amp socket outlet each 32.00
14.0 Supply, installation, testing & commissioning of 20 kva true
online double conversion UPS system with 30 mins & with
inbuilt isolation Transformer, SMF battery backup, MS rack
Links and accessories as required
each 2.00
C Providing and fixing following capacity 4 pole automatic on
load ON/OFF -Load changeover switches with side handle
operation, in sheet enclosure in metal board including drilling
holes in metal board, making connection , earthing the body
etc. as required.16.1 100 A , 4 POLE nos 1.00
17.0 supply, laying, testing, commissioning, of under floor GI race
ways with all accsesaries of following dimention DLP
TRUNKING
17.1 PLASTIC TRUNKING 105MMX50MMX 2MTR EACH 175.00
17.2 FLEXIBLE COVER 85MM WIDTH EACH 118.00
17.3 4 MOSAIC MOD.FRA FOR 85MM COVE EACH 128.00
17.4 JOINT FOR 85MM WIDTH COVER EACH 352.00
17.5 BASE JOINT EACH 352.00
17.6 END CAP EACH 64.00
17.7 INTERNAL ANGLES-ADJ FRM 80 DEG EACH 448.00
17.8 EXTERNAL ANGLES-ADJ FRM 60 DEG EACH 448.00
17.9 FLAT ANGLES EACH 224.00
17.10 SOCKET SHUTTERED 6/16 3 PIN INDIAN 3 MODULE EACH 128.00
17.11 SWITCH 20 A SP 1 WAY 1 MODULE EACH 128.00
18.0 supply, laying, testing, commissioning, of under floor GI race
ways with all accsesaries of following dimention
18.1 225mmx38 mm 3 compartments race way (2.44 mtr) EACH 200.00
18.2 GI FIXING BRACKET 225X25 MM (1 No. for 2mtr) EACH 208.00
18.3 COUPLING 38 (For joining 2 pieces of raceway) EACH 100.00
18.4 225x225 mm height adjustable junction box 50-70mm EACH 160.00
Total of Part-E
Item no. Description Unit Quantity Rate in figure (Rs.) Rate in words Amount (Rs.)
Sub Head-A
1 Laying and fixing of one number PVC insulated and PVC
sheathed / XLPE power cable of 1.1 kV grade of following
size on cable tray as required.
1.1 Upto 35 sq. mm (clamped with 1mm thick saddle) meter 1566.00
1.2 Above 95 sq. mm and upto 185 sq. mm (clamped with 25/
40x3mm MS flat clamp)
meter 120.00
1.3 Above 185 sq. mm and upto 400 sq. mm (clamped with
40x3mm MS flat clamp)
meter 160.00
2 Supplying and making end termination with brass
compression gland and aluminium lugs for following size
of PVC insulated and PVC sheathed / XLPE aluminium
conductor cable of 1.1 kV grade as required.
2.1 3½ X 35 sq. mm (32mm) each 8.00
2.2 3½ X 185 sq. mm (57mm) each 2.00
2.3 3½ X 300 sq. mm (70 mm) each 6.00
2.4 4 X 10 sq. mm (25 mm) each 10.00
2.5 4 X 16 sq. mm (28mm) each 30.00
3 Supplying and installing following size of perforated Hot
Dipped Galvanised Iron cable tray (galvanisation thickness
not less than 50 microns) with perforation not more than
17.5%, in convenient sections, joined with connectors,
suspended from the ceiling with G.I. suspenders including
G.I. bolts & nuts, etc. as required.
3.1 150 mm width X 50 mm depth X 1.6 mm thickness Each 150.00
3.2 300 mm width X 50 mm depth X 1.6 mm thickness Each 110.00
Bill of Quantity
Name of Work: Construction of Research Park at IITG Campus.
Part-F(HVAC works)
CHAPTER 7-MV CABLE LAYING
CHAPTER 9-MV CABLE JOINTING & END TERMINATION
CHAPTER-4-CABLE TRAYS
4 Supplying and installing following size of perforated Hot
Dipped Galvanised Iron cable tray “bends” (galvanisation
not less than 50 microns) with perforation not more than
17.5%, in convenient sections, joined with connectors,
suspended from the ceiling with G.I. suspenders including
G.I. bolts & nuts, etc. as required.
4.1 150 mm width X 50 mm depth X 1.6 mm thickness Each 6.00
4.2 300 mm width X 50 mm depth X 1.6 mm thickness Each 6.00
5 Supplying and installing following size of perforated Hot
Dipped Galvanised Iron cable tray “Tee” (galvanisation
not less than 50 microns) with perforation not more than
17.5%, in convenient sections, joined with connectors,
suspended from the ceiling with G.I. suspenders including
G.I. bolts & nuts, etc. as required.
5.1 150 mm width X 50 mm depth X 1.6 mm thickness Each 6.00
5.2 300 mm width X 50 mm depth X 1.6 mm thickness Each 6.00
6.1 Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia
including accessories, and providing masonry enclosure
with cover plate having locking arrangement and
watering pipe etc. with charcoal/coke and salt as
required.
Each 4.00
6.2 Supplying and laying 25 mm X 5 mm G.I strip at 0.50
meter below ground as strip earth electrode, including
connection/terminating with G.I. nut, bolt, spring, washer
etc. as required.(Jointing shall be done by overlapping
and with 2 sets of G.I. nut bolt & spring washer spaced at
50 mm)
meter 40.00
6.3 Providing and fixing 25 mm X 5 mm G.I. strip on surface or
in recess for connections etc. as required.
meter 20.00
6.4 Providing and fixing 6 SWG dia G.I. wire on surface or in
recess for loop earthing as required.
meter 80.00
Sub Head-B
VRF Airconditioning system
VRF/ VRV -IVth generation Outdoor units
CHAPTER-5-EARTHING
1.0 Supply Installation Testing & commissioning of IVth
Generation air cooled Full Inverter VRF System with
Modular type outdoor units, all scroll DC Inverter
compressors for cooling & Heating applications along
with different types of indoors compitable with VRF
ODUs. All inverter capacity controlling compressors shall
be suitable for 3 Phase, 50 Hz.. The outdoor should be
with 'Ocean Black Fin' heat exchanger with a black
coating to shield it from Salt, Sand & other elements
brought in by the air. The manufacturer must be having
its own make compressor fitted in outdoor. All proposed
outdoor unit should have minimum COP of 4.0 & 6.1 at
100% & 50% load condition respectively for Cooling
.conditions ((Outside DBT-35 Deg C & Inside DBT 27 Deg C
&19 WBT) .COP should be based on nominal capacity as
mentioned in BOQ and power input at this condition i/c
first charge of refrigenet .Refrigerent shall be used 410a.
1.1 8 HP (22.4 KW) Top discharge Nos 4
1.2 10 HP (28 KW) Top discharge Nos 1
1.3 12 HP (33.6 KW) Top discharge Nos 4
1.4 20 HP (56 KW) Top discharge Nos 11
2.0 VRF/ VRV -Indoor units.
Supply, Instalaltion, testing and commissioning of(
histatcic ductable Type/Casseette Type/Hiwall Type)
Indoor units equipped with pre-filter, fan section with
suitable static fan, multispeed motor, coil section with
DX coil, outer cabinet, insulation, pipe connections etc.
of various capacities as per specifications and drawings.
The minimum TR/CFM has to be adhere while selecting
the equipment.Diversity beetwen ODU and IDU should
not exceed 108 %. Vendor has to select IDU or ODU of
nearby higher capacity to maintain the diversity as
specified.
2.1 Hi Static Type
2.1.1 8 TR/2650 CFM Nos 2
2.2 Cassette Type indoors
2.2.1 4 TR/1200 CFM Nos 2
2.2.2 2.5 TR/940 CFM Nos 22
2.2.3 3.5 TR /1164 CFM Nos 36
2.3 Hiwall Type
2.3.1 1.28 TR /470 CFM Nos 32
3.00 TFA
3.10 Supply , Installation , Testing & commissioining of Fresh
Air unit with low noise BLDC motor .It can supply the
fresh air in conditioned space and create positive presure
inside which can reduce contaminated air from outside.
3.1.1 6.3 TR/835 CFM Nos 4
4.00 SITC of Refnet joints for proper distribution of refrigernt
through the complete circuit for indoor and Outdoor
4.1 Refnet Nos 98
4.2 SITC ofCorded remote controller-For Cassette & Hi Static Nos 6
4.3 SITC of Cordless Remote Controller- For Hi wall Nos 92
5.00 Supply , Installation , Testing & commissioining of
interconnecting refrigerant piping along with closed cell
elastomeric insulation and supports, between indoor &
outdoor units duly insulated as per specifications. Make-
Rajco/Mandev5.1 41.3 mm O.D. ( insulation : 19 mm ) RM 160
5.2 34.9 mm O.D. ( insulation : 19 mm ) RM 210
5.3 28.6 mm O.D. ( insulation : 19 mm ) RM 340
5.4 25.4 mm O.D. ( insulation : 19 mm ) RM 180
5.5 22.2 mm O.D. ( insulation : 19 mm ) RM 240
5.6 19.1 mm O.D. ( insulation : 13 mm ) RM 350
5.7 15.9 mm O.D. ( insulation : 13 mm ) RM 650
5.8 12.7 mm O.D. ( insulation : 13 mm ) RM 220
5.9 9.5 mm O.D. ( insulation : 13 mm ) RM 590
5.10 6.4 mm O.D. ( insulation : 13 mm ) RM 180
6.00 SITC of 1.5 sq x 2c mm shielded cu cable for
communication
RM 2200
7.00 Supply, installation, testing and balancing of powder
coated Extruded Aluminium supply air Grilles with volume
control dampers in accordance with the approved shop
drawings and specifications.Make-Dynacraft/Sysytem Air
Sq Mt 12
8.00 Supply, installation, testing and balancing of Air Grilles
without volume control dampers in accordance with the
approved shop drawings and specifications.Make-
Dynacraft/Sysytem Air
Sq Mt 8
9.00 Supply, installation, testing and balancing of powder
coated Extruded Aluminium supply air Diffuse with
volume control dampers in accordance with the approved
shop drawings and specifications.Make-
Dynacraft/Sysytem Air/
Sq Mt 10
10.00 Supply, installation, testing and balancing of Air Diffuse
without volume control dampers in accordance with the
approved shop drawings and specifications.Make-
Dynacraft/Sysytem Air/
Sq Mt 10
11.00 Supply, installation and testing of Factory fabricated GI
sheet metal ducts as per approved shop drawings and as
required by the specifications with 6 mm nitrile insulation
. Make-Jindal/Tata11.1 22 G Sq Mt 150
11.2 24 G Sq Mt 350
12.00 Supply, fabrication, installation and testing the flexible
connections constructed of fire resistance flexible double
canvas sleeve as per the approved shop drawings.
Nos 2
13.00 DRAIN PIPING : Supply, Installation and Testing of UPVC
heavy class drain piping insulated out of 13 mm thick
Class O closed cell elastomeric nitrile rubber material of
approved make as per specification complete with
supports, consumables, fittings, pipe sleeves, U trap &
leak arresting of following sizes.
13.1 25 mm RMT 450
13.2 32 mm RMT 350
13.3 40 mm RMT 180
14.0 POWER PANEL:
Supply, installation, testing and commissioning of cubicle
type panels as specified and shown on drawing no.
WTE2291/STAGE 2/7.001 SHEET 1
i) Main Aluminium busbars with bar type feeder
connections & all internal wiring and connections.
ii) Earthing all components, frame etc. to a common
internal earth bar.
iii) Powder Coat painting of all sheet metal works.
iv) All accessories & supporting structure.
v) Brass glands and crimping lugs for sending and
receiving ends.
vi) All ammeters with C.T's and voltmeter and energy
meters with necessary fuses.
vii) Panel components as specified.
viii) MS base frame.
ix) All switch gear to have short circuit levels as specified.
14.1 LAB BLOCK MAIN AC PANEL NOS 1
i) 1 Nos.1000A, 4P, EDO, microprocessor based
ACB complete with Over current & S/C protection as
incomer
ii) 2 Nos. 200A TPN MCCB complete with Over
current & S/C protection as OUTGOING
iii) 6 Nos. 160A TPN MCCB complete with Over
current & S/C protection as OUTGOING
iv) 3 Nos. 63A TPN MCB complete with Over current
& S/C protection as OUTGOING
v) 96 mm² Voltmeter 0 - 600V with Voltmeter
selector switch - 3Nos
vi) 96 mm² Ampmeter 0-1000A with Ampmeter
selector switch - 3Nos.
vii) 3 Nos. CT's 1000/5A 10VA Class-I accuracy
viii) 3 Nos. indicating lamps (LED Type)
ix) TPN Aluminium busbar mounted on non-
hygroscopic insulator supports - 5x150x10 mm
electrical grade bar for phase 3x150x10 mm
electrical grade bar for neutral
x) Two Nos. 10 mm stud type earth terminals G.I.
earth bus bar arrangement
14.2 APPARTMENT BLOCK MAIN AC PANEL NOS 1
i) 1 No.250A 4P MCCB complete with Over current
& S/C protection as incomer
ii) 2Nos. 63A TPN MCB as outgoing
iii) 16Nos. 32A TPN MCB as outgoing
iv) 96 mm² Voltmeter 0 - 600V with Voltmeter
selector switch - 1 No
v) 96 mm² Ampmeter 0-250A with Ampmeter
selector switch - 1No
vi) 3 Nos. CT's 250/5A 10VA Class-I accuracy
vii) 3 Nos. indicating lamps (LED Type)
viii) TPN Aluminium busbar mounted on non-
hygroscopic insulator supports - 1x100x6 mm
electrical grade bar for phase 1x80x6 mm electrical
grade bar for neutral
ix) Two Nos. 10 mm stud type earth terminals G.I.
earth bus bar arrangement
14.3 LAB BLOCK FLOOR AC PANEL NOS 2
i) 1 No.160A 4P MCCB complete with Over current
& S/C protection as incomer
ii) 6Nos. 63A TPN MCB as outgoing
iii) 3Nos. 32A TPN MCB as outgoing
iv) 3Nos. 20A DP MCB as outgoing
v) 96 mm² Voltmeter 0 - 600V with Voltmeter
selector switch - 1 No
vI) 96 mm² Ampmeter 0-250A with Ampmeter
selector switch - 1No
vii) 3 Nos. CT's 250/5A 10VA Class-I accuracy
viii) 3 Nos. indicating lamps (LED Type)
ix) TPN Aluminium busbar mounted on non-
hygroscopic insulator supports - 1x100x6 mm
electrical grade bar for phase 1x80x6 mm electrical
grade bar for neutral
x) Two Nos. 10 mm stud type earth terminals G.I.
earth bus bar arrangement
15.00 MV CABLE
15.1 Supply of heavy duty 1100V grade LT XLPE insulated
sheathed & armoured cables with aluminium / copper
conductors as specified and required.
15.1.1 4C X 10sq.mm. Al. Ar. XLPE Cable RM 330
15.1.2 4C X 16sq.mm. Al. Ar. XLPE Cable RM 1164
15.1.3 3.5C X 35sq.mm. Al. Ar. XLPE Cable RM 72
15.1.4 3.5C X 185sq.mm. Al. Ar. XLPE Cable RM 120
15.1.5 3.5C X 300sq.mm. Al. Ar. XLPE Cable RM 160
16.0 Supply, installation, testing & commissioning of modular
type 240V, 50Hz, 25A stater with 20 A plug point
including base plate and necessary connection in
modular type MS box for 2TR, 1.5TR & 1TR split type AC
machine.
EACH 137
1 VENTILATION
1.1 Supply, erection, testing & commissioning of long casing
GSS Vane Axial (motor should complete accomodated in
side the fan casing) Flow Exhaust Fans (Fire Rated)of
capacity as below with TEFC single speed motor to suit
250 deg C for 2 hours.Fan should be complete with back
draft damper, outet wire guard, fan support frame work
in standard MS construction with painting. Fan should be
AMCA certified. Sound pressure level of the fan should
not exceed 73 dB(A) at 3 meter in room condition at given
CFM.
In case of vane axial, vanes outside of fan casing is not
acceptable.
1.1.1 EXHAUST FAN:AXIAL FLOW FAN: 3100 CFM @ 35 mm wg
static pressure for Kitchen, (SISW belt driven fan)
Nos 1
1.1.2 FRESH AIR SUPPLY FAN:AXIAL FLOW FAN: 3100 CFM @ 35
mm wg static pressure for Kitchen, (Vane Axial type direct
driven fan)
Nos 1
2 Supply, erection, testing & commissioning of rectangular
type direct driven inline fan. Fan should be AMCA
certified. Sound pressure level of the fan should not
exceed 55 dB(A) at 3 meter in room condition at given
CFM.2.1 750 CFM inline Fan for exhaust Nos 3
2.2 700 CFM inline Fan for exhaust Nos 3
3 DUCTING & ACCESSORIES
3.1 Supply and installation of sheet metal ducting complete
with GI threaded supports, vanes, splitters, gaskets for
joints, thermal isolation blocks, etc. as per specs. 120
GSM sheets GI Sheet Metal Ducting (Rectangular) Factory
Fabricated (made on lock forming machine RTV sealed)
3.1.1 24 Gauge Sqm 310
3.1.2 22 gauge Sqm 80
4 EXHAUST AIR DIFFUSERS
4.1 Supply, installation ,testing and balancing of rectangular
square type air Grilles / Diffusers with volume control
dampers. Each diffuser shall be equipped with fixed air
distribution grid, removable core for proper balancing of
air distribution system Powder coated extruded
aluminium diffusers of approved colour suitable for
installation in ceiling with sizes.
Sqm 20
5 SUPPLY AIR DIFFUSERS
5.1 Supply, installation ,testing and balancing of rectangular
square type air Grilles / Diffusers with volume control
dampers. Each diffuser shall be equipped with fixed air
distribution grid, removable core for proper balancing of
air distribution system Powder coated extruded
aluminium diffusers of approved colour suitable for
installation in ceiling with sizes.
Sqm 10
6 GRAVITY LOUVER WITH BIRD SCREEN
6.1 Gravity louvershall be designed to maintained 3.0 mm
over pressure inside the room. Frame and louver (self
acting type) thickness shall be 1.25 mm & 0.63 mm
respectively. Constructional feature of frame & louver
shall G.I. & aluminum respectively. Size : As per the
dimension of discharge section of fan
No. 8
7 DUCT DAMPER
8 Duct damper shall be fabricated from G.I. sheet with MS
Frame. Frame & louver thickness shall be 1.6 mm & 1.0
mm respectively. Damper shall have suitable operating
lever with bush / bearing and low leakage.
Sqm 10
9 Lifting and shifting charges Lot 1
10 Specialised structural works required for ventilation
system
Kg 100
Total of Part-F