7/30/2017
1
PHASORS
August 22,2017
Bill Unbehaun Tacoma Power
Exchanging expertise since 1893
Objectives• What is a phasor?
• Why are phasors important in metering?
• Working with vectors or phasors
• Standard meter service phasor diagrams
• Troubleshooting
7/30/2017
2
Terms and Concepts
• Rotation – the direction around the center
Phasors rotate counter‐clockwise
• Sequence – the order of progressionPhase sequence can be ABC or ACB
Terms and Concepts
• Radians – a method of describing a circleCircumference = π x diameter or 2πr ; if radius = 1, then circumference = 2π (= 3600 )
Angle in degrees = angle in radians * 180 / Pi (or 57.30)
Used in equations for torque and frequency (ω = angular speed in radians/second )
P = τ ∙ ω; f = ω/ 2π
7/30/2017
3
A Phasor is a special type of Vector
A vector represents a quantity with magnitude and direction
Handbook for Electricity Metering
• A phasor is a quantity which has magnitude, direction and time relationship. Phasors are used to represent sinusoidal voltages and currents by plotting on rectangular coordinates. If the phasors were allowed to rotate about the origin, and a plot made of ordinates against rotation time, the instantaneous sinusoidal wave form would be represented by the phasor.
7/30/2017
4
Sine Wave
M7-7
Three phase sine wave and corresponding phasors –
ideal condition
7/30/2017
5
Three phase sine wave and corresponding phasors –unbalanced
load
Quantities
• For our purposes the main uses include:
– Voltage
– Current
– Impedance
7/30/2017
6
Lots of other uses
• Navigation: Seattle to Spokane 233 miles at 890
Why Study Phasors?
• A simple visual representation of electrical phenomena
– Visual of what’s happening in the service and in the meter
– Understand necessary concepts for testing and billing
• A tool for troubleshooting
7/30/2017
7
How do we work with phasors?
• Phasors are vectors in motion; treat them like vectors
• Vectors can be described in 2 ways: polar and rectangular (Cartesian)
• Vectors can be added, subtracted, multiplied and divided
Vector DescriptionRectangular Coordinates: (1,2)
2
1
(1,2)
M7-1
7/30/2017
8
Vector DescriptionPolar Coordinates: 2.24<63.40
1
2
1
63.40
M7-4,6
Vector Exercise 1
• Draw vectors 2<00 and 3<300 (thin)
• Draw vectors (1,0) and (1.73, 1) (thick)
7/30/2017
9
Vector Exercise 1
• Draw vectors 2<00 and 3<300 (thin)
1
1 200
900
Vector Exercise 1• Draw vectors 2<00 and 3<300 (thin)
• They remain the same vectors regardless of position in space
1
1 200
900
7/30/2017
10
Vector Exercise 1Reference changed – note position of 900
• Draw vectors 2<00 and 3<300 (thin)
1
1 200
900
Vector Exercise 1
• Draw vectors 2<00 and 3<300 (thin)
• Draw vectors (1,0) and (1.73, 1) (thick)
1
1 200
900
7/30/2017
11
Vector Exercise 1
• Draw vectors 2<00 and 3<300 thin
• Draw vectors (1,0) and (1.73, 1) thick
• Describe with both methods
1
1 200
900
Vector Exercise 1• Describe with both methods – the vectors on the X axis are straightforward (1,0) = 1< 00
• 3 < 300 : 3 x cos 300 = 2.6 ; 3 x sin 300 = 1.5
• 3 < 300 = (2.6, 1.5)
1
1 200
900
1 < 00 (2,0)
(2.6, 1.5)
7/30/2017
12
Vector Exercise 1• Describe with both methods
• (1.73, 1): 1.732 + 12 = 3.99; √ 3.99 = ~ 2
• 1 / 1.73 = 0.578; tan‐1 0.578 = 300
• (1.73, 1) = 2 < 300
1
1 200
900
1 < 00 (2,0)
2 < 300
(2.6, 1.5)
Adding (or subtracting) Vectors
• Vectors can be added or subtracted
• Easiest in rectangular coordinates
M7‐3
M7‐17
7/30/2017
13
Vector Exercise 1 extension• Add 1 < 00 + 2 < 00
• 1 < 00 = (1,0); 2 < 00 = (2,0)
• 1 + 2 = 3; 0 + 0 = 0
• 1 < 00 + 2 < 00 = (3,0) = 3 < 00
1
1 200
900
1 < 00 2 < 00
3
• Add 2 < 00 + 3 < 300
• 2 < 00 = (2,0) ; 3 < 300 = (2.6, 1.5)
• Xs: 2 + 2.6 = 4.6; Ys: 0 + 1.5 = 1.5
• (4.6, 1.5) ; 4.62 + 1.52 = 23.41; √ 23.41 = ~4.8
• 1.5 / 4.6 = 0.326; tan‐1 0.326 = 180
• 2 < 00 + 3 < 300 = 4.8 < 180
1
1 200
900
(2,0)
(2.6, 1.5)
4.8 < 180
7/30/2017
14
Vector Exercise 2
2 < 3100 + 10 < 350 = ?
270
0
Vector Exercise 22<310 = (1.29, ‐1.53) 10<35 = (8.19, 5.74)
Add X values Add Y values
1.29 + 8.19 = 9.48 ‐1.53 + 5.74 = 4.21
? = (9.48, 4.21)
4.21 / 9.48 = tan θ = 0.444
Θ = 23.95
Hyp = 9.48 / cos θ = 10.37
? = 10.37<23.95 = 10 < 24
7/30/2017
15
Vector Exercise 2
2<3100 + 10<350 =10<24
270
0
10<24
Proof of 1.73 relationship
• Side = 1; angle at bottom is 1200
• Perpendicular bisector of 120 also bisects red line
• Cos30 x 1 = half of red line = 0.866
• 0.866 x 2 = 1.73 = length of red line
3090
60
120
1
1.73
7/30/2017
16
Proof of 1.73 relationship
• ‐0.5 – 1 = 1.5
• 0.866 – 0 = 0.866
• SQRT(1.52 + 0.8662) = 1.73
• 0.866 / 1.5 = Tan‐1 30
1<0
1<120
(1,0)
(-0.5, 0.866)
Impedance
• To divide polar coordinates, divide magnitudes and subtract angles
V= 120 < 0; I = 10 < 30;
Z = V/I: 120/10 = 12; 0 – 30 = ‐30; Z = 12 < ‐30
7/30/2017
17
What’s the reference?
SCALE
What is the scale? Does the radius of the circle = 1v, 480v, 10a?Mfrs. handle this in different ways, showing the voltages relative to each other and the currents relative to each other, or scaling them to each other in some fashion.
7/30/2017
18
Names
• Vector (and phasors) must be named or labeled properly to be useful
• Voltages are labeled with a V or E and the phase relationship of the potential difference: Van, ECB, etc.
• Currents are labeled with an I and the phase: Ia, IB, etc.
Vector Review
• Magnitude and direction
• Rectangular coordinates
• Polar coordinates
• Add – head‐to‐toe
• Reference
• Scale
• Labels
7/30/2017
19
Phasor rotation is counterclockwise
0
45
270
90
180
Phasor rotation is counterclockwisePhase rotation or Phase sequencing
can be ABC or ACB
VA / VA
270
90
180
VB / VC
VC / VB
7/30/2017
20
3 phase ACB rotation
Phasor Review
• Phasors are vectors that rotate
• Represent cyclical phenomona
• In metering, rotation is counterclockwise
• In metering, degree notation is clockwise, with 0 at 3 o’clock
7/30/2017
21
Real Life AdventuresHow does this relate to my meter work?
Powermate Circuit Analyzer
7/30/2017
22
7/30/2017
23
7/30/2017
24
7/30/2017
25
LED Billboard
7/30/2017
26
7/30/2017
27
3 wire delta, 5S or 12S meter
Vab
Vcb
Ia
Ic
AB
C
W = E x I x √3 x cos θ
3 wire delta
Or…W = E x I x cos (α+θ) per element α is the angle at unity between E and IΘ is the pf angle caused by the load.
7/30/2017
28
Angles α and θW = E x I x cos (α + θ)
Vab
Ia theoretical
Ia actual—add α and θ for watts
Angle α is the unity phase relationship = 300 for VAB - Ia
Angle θ caused by customer load
Angles α and θW = E x I x cos (α + θ)
Vab
Angle α is the unity phase relationship 300 for IA in a 3W delta
If θ is leading the theoretical angle, consider it a negative angle when adding
If the theoretical angle is leading, consider angle αto be negative
7/30/2017
29
3 wire delta with 300 lag
Wa = E x I x cos (30+30) (0.5) Wc = E x I x cos (-30+30) (1.0)Wt = E x I x 1.5Wt = E x I x {√3 x cos 30} ({}=1.5)
3 Wire Delta
Several ways to approach this:
System PF = 0.816, so I lags V by 350
Or compare phases:- Ia lags Vab by 640, at unity this would be 300 so Ia lags by 340
- Ic lags Vcb by 50
but it should lead by 300 so Ic lags by 350
7/30/2017
30
Is this a delta?
2P-N service with CTs
7/30/2017
31
Next service type
Meter software example
7/30/2017
32
4W Wye
Ametek JemStar II
7/30/2017
33
4W Wye
Unbalanced 4W Wye
7/30/2017
34
4 Wire Wye Power Calculations per Phase
V x I = VA x PF = W
• PhA: 123.9 x 3.3 = 408.9 x 0.999 = 408.3
• PhB: 124.0 x 0.1 = 12.4 x 0.438 = 5.4
• PhC: 123.5 x 0.5 = 61.8 x 0.906 = 56.0
• Totals 483.1 469.7
• PF = W / V = .972 or 97.2%
• OR by average: Iave =1.3, <ave = 30.60
(123.8 x 1.3) x 3 = 482.8 x 0.860 = 415.2
Neutral Current
• Add current vectors
• Ia =3.31<2.83 = (3.31, ‐0.16)
• Ib = 0.11>304.40 = (0.06, 0.09)
• Ic = 0.51>145.36 = (‐0.49, ‐0.29)
• In = 2.88 > ‐180.04 = (2.88, ‐0.36)
• Angle of the neutral will be roughly opposite the largest current—current is flowing away from the meter in the neutral.
M-7 12
7/30/2017
35
Phasors with Neutral (green)
Example from phase angle lab tomorrow
7/30/2017
36
4W Wye
• Ia‐EAN____ Ia‐EBN_____ Ia‐ECN_____
• Ib‐EBN____ Ib‐ECN_____ Ib‐EAN_____
• Ic‐ECN____ Ic‐EAN_____ Ic‐EBN_____
What’s the reference?
7/30/2017
37
LUNCH
4 wire deltaPhasors
7/30/2017
38
4 W Delta Xfrmrs
B N A C
4 W Delta XfrmrsRearranged
N
AB
C
7/30/2017
39
4 W Delta Service Representation
A
C
B
4 W Delta Meter Phasors(3 phase balanced load)
C
AB
7/30/2017
40
4 wire deltaPhasors
4 wire deltaPhasors
7/30/2017
41
4 wire delta, 3 element solid state auto‐detecting meter phasors
4 wire delta, 3 element solid state auto‐detecting meter phasors
7/30/2017
42
4 Wire Delta at UnityPhase to phase V to describe
service
Van and Vbn are ½ V Φ –Φ
Vcn = Van x √ 3
Example: 240v delta
Van & Vbn = 120v
Vcn = 208v
Angle α for A phase = 300
Angle α for B phase = ‐300
Angle α for C phase = 00
Angle θ is the pf caused by the customer load.
Van
IaIb
Vbn
Vcn
Ic
αα
4 Wire Delta Power Calculations per Phase
• Wa = VAN * Ia * cos(α + θ) for A phase• Wb = VBN * Ib * cos(α + θ) for B phase• Wc = VCN * Ic * cos(α + θ) for C phase• Wt = Wa + Wb + Wc
• Angle α for A is 300, for B is ‐300, for C = 0• VAN and VBN = ½ Ø – Ø voltage, • VCN = VAN * √ 3• Like a wye, angle θ can be different for each phase
and results from the load connected to that phase
7/30/2017
43
The VA Question
• There are at least 2 methods commonly used to calculate VA, and others as well.
• 1. The traditional method of adding watts from each phase and VARs from each phase, then creating a hypotenuse, VA. This is basically what the old wh meter / VARh meter installations did, and is called the vectorial method.
The VA Question
• 2. With microprocessor meters, we can now calculate VA per phase, then add the 3 VA values. This is called the arithmetic method. The Handbook considers this to be more “accurate.” (See VA Metering)
• 3. One meter mfr. multiplies V x I x 0.93 on all three phases to arrive at VA.
7/30/2017
44
The VA Question
• Your utility has a method built into its rate structure. It is probably the vectorial method, based on a wh reading and a varh reading. Your meter may be calculating by another method. This will only matter if you use the meter’s power or PF calculations for billing.
4 Wire Wye Power Calculations per Phase
V x I = VA x PF = W var• PhA: 123.9 x 3.3 = 408.9 x 0.999 = 408.3 22.1• PhB: 124.0 x 0.1 = 12.4 x 0.438 = 5.4 11.6• PhC: 123.5 x 0.5 = 61.8 x 0.906 = 56.0 26.1• Arithmetic Totals 483.1 469.7 59.8• Vectoral: 408.3 + 5.4 + 56 = 469.7w
»22.1 + 11.2 + 26.1 = 59.4 var»469.72 + 59.42 = 473.42 va
• Is PF 97.2% or 99.2% ?
7/30/2017
45
Vectorial vs Arithmetic • How is your meter calculating power factor?
• 97.2% or 99.2%
• What if the difference is at the PF cutoff for var adjustment?
• Which is more accurate?
483.1 va469.7 w
473.4 va
469.7 w
59.9 var
59.9var
4 wire delta, 2 element meterphasor analysis
VAB,
IA-B
VC, IC
7/30/2017
46
4 wire delta, 2 element meter, phasor analysis
VAB,
IA-B
VC, IC
What if IB is not reversed?
VAB,
VC, IC
IA+B
Full torque on C0 torque on AB
7/30/2017
47
4 wire delta with roughly equal 1 phase and 3 phase loads
Phase C is a good indicator of 3p load
Bp 2.34-1.37=0.97Ap 2.95-1.37=1.58
Service has roughly 1.4a of 3p load and 1-1.5a single phase load
7/30/2017
48
Check
• P‐P voltage = 230 x 1.37 x 1.73 = 545w
• A = 115 x 2.95 = 339w
• B = 115 x 2.34 = 269w
• C = 199 x 1.37 = 273w
» Total 881w
»3p ‐545w
» 336w / 2 = 163 / 115=1.4
3 phase component1 phase component
7/30/2017
49
Varied Load
• This is just a way to understand what’s happening behind the phasors
• Don’t count on reverse analyzing load with any confidence
• There may be phase to phase load buried in there
• Understanding the relationship between the load and the phasors is important
Typical 4 Wire Delta
More load on A and B phases, but significant load on C phase indicating 3 phase loadNotice 3rd harmonic distortion on B phase
7/30/2017
50
4 Wire Delta
Small 3 phase load
Note mfr’s use of phasors to indicate angle but not magnitude
7/30/2017
51
4 Wire Delta
Notice lack of C phase current – A and B phase roughly balanced
4 Wire Delta
Notice lack of C phase current –most of load is on B phase
7/30/2017
52
4 Wire Delta Service
Note distortion of current waveform and smooth voltage waveform
Harmonic Analysis
Lots of 11th and 13th harmonic in current but relatively little voltage distortion
7/30/2017
53
Reactive MeteringElectromechanical
W =Van x Ia x cos θ
VAR = Van x Ia x sin θ or Vra x cos(90‐ θ)
Van
Ia
Vra
θ
Phase shift schematic from Handbook for Electricity Metering
7/30/2017
54
Shifting a Wye: Wiring and Phasors from HEM
Phasor analysis can help verify expected voltage angles and troubleshoot mis-wiring
Shifting a Delta: Wiring and Phasors from HEM
7/30/2017
55
Reactive Metering
VAR measurements are made by integrating the voltage waveform to obtain a 90°phase shift, then each voltage sample is multiplied by the coincident current sample and the product is accumulated to obtain a VARs.
From Landis + Gyr manual
Reactive MeteringElectromechanical
VAR = Van x Ia x sin θ = 0
or VAR = Vra x Ia x cos(90‐ θ) = 0
Ia
Vra
7/30/2017
56
Dk. Blue lags by 90 degrees
Power Factor = 0
Current (orange) lags voltage (blue) by 900 so positive and negative power (light green) cancel out – no real power, all reactive power
7/30/2017
57
Reactive MeteringElectromechanical
W =Van x Ia x cos 10
VAR = Van x Ia x sin 10 or Vra x Ia x cos(80)
Van
Ia
Vra
Θ = 10
100 lagging current, WH meter
7/30/2017
58
VARH meter sees 800 leading current
TROUBLESHOOTING
How Phasors Can Help Solve Your Problems
7/30/2017
59
Examples of troubleshooting:What’s wrong here?
4W Y with CTs
Van
Vbn
VcnIc
Ia
Ib
One polarity reversed
7/30/2017
60
What’s wrong here?
4W Y with CTs
Van
Vcn
VbnIc
IaIb
What’s wrong here?
4W Y with PTs and CTs
Van
Ic
Ib Ia
Vbn
Vcn
7/30/2017
61
Miswired 4 wire delta with 2 element EM 15S Self‐Contained Meter
What will the meter
register if C phase
(high leg) is in the
center at the
socket?
A C B
Miswired 4 wire delta 2 element EM
C
B A
B
AC
7/30/2017
62
Miswired 4 wire delta 2 element EM
• Expected ActualVcn
IcVab
Ia-IbVac
Vbn
Ib
Ia-Ic
Power calculations for 15S
• E x I x SQRT3 = 240v x 10a x 1.73 = 4157
• Correct meter
• “2S” element sees (240v x ½ Ia x 0.866) + (240v x ‐ ½ Ib x 0.866) = 2078va
• “1S” element sees 208v x 10a = 2080va
• 2078 + 2080 = 4158VAt
7/30/2017
63
Miswired 15S meter socket
• “2S” element sees the same as before, just A and C instead of A and B = 2078va
• “1S” element is now B phase with a 300
lag and 120v: 120v x 10a x 0.866 = 1039va
• 2078va + 1039va = 3117
• 3117 / 4157 = 75% registration on balanced 3 Φ load! Lighting load is ok.
What’s This?
7/30/2017
64
Solar System with 2 inverters to create a 3 phase feed
Here B phase is common – an inverter is connected A-B and another C-B. There is no A-C load / generation, but B current is combined from both sources.
Schematic
BA C
Inverter Inverter
PanelsPanels
7/30/2017
65
• 12S16S
Ib is unmetered in a 12S or 5S meter
Phase B is vector sum of –Ia and ‐Ic
7/30/2017
66
Use of Phasors or Vectors in Related Equipment
Transformer connections
Instrument transformer performance
Relay applications
Power Transformers
7/30/2017
67
Power Transformer Connections
Depending on the winding configuration, the phase angle relationship changes from high side to low. Normal shift in a delta—wye is +/‐ 300.
This is important for transformer relays.
Instrument Transformers
7/30/2017
68
Vector Analysis of a PT from the Handbook for Electricity Metering
Electromechanical relays
7/30/2017
69
Testing microprocessor relays
Sequence Phasors in Relaying
In relaying, phasors are used to analyze fault current into positive, negative and zero sequence currents; and there are many other situations where phasors make things clearer.
C B
C
A A
B
A
B C
7/30/2017
71
You can do the rectangular-polar conversion on some calculators. Look for the expressions R>P and P>R as second and/or third functions. There should also be an X<>Y key. To convert 1,2 to polar coordinates:1(X<>Y) 2(3rd) (R>P)Display should show 2.2360… which is the magnitude(X<>Y)Display should show 63.4349… which is the angle
Rectangular to Polar
7/30/2017
72
Rectangular to Polar
Rectangular to Polar
7/30/2017
73
Rectangular to Polar
Polar to Rectangular
• Reverse the process:
• Magnitude (2.236) X/Y angle (63.434)
• 2nd P>R
• Display = 1 X/Y 1.99999
7/30/2017
74
L+G terminology
• VAtd: Time delay (lagging) measurement of Volt‐Amperes. At unity power factor VAtd is equal to watts.
• VARtd: Time delay (lagging) measurement of Volt‐Amperes reactive.