Instruction Manual Ver 1.1
STYRAX INSTRUMENTS INDIA PVT LTD
INSTRUCTION MANUAL
INTERLOCKING SYSTEM (UPTO 12 DOOR) MODEL NO: ILS1058
VERSION: 1.1
Styrax Instruments India Pvt. Ltd. PLOT No.48-51,Dollapally,
Phase V Extn. I.D.A.,
Jeedimetla, Hyderabad – 014
Andhra Pradesh, INDIA
Ph: +91 40 2309 3314
Fax: +91 40 2309 3315
www.styraxinstruments.com
Email: [email protected]
Instrument SI. No :
Instruction Manual (Ver1.1)
STANDARD PACK
1) Instruction Manual --- 1 No
2) ILS-1058 Instrument --- 1 No
Checked By :
Date :
1. DESCRIPTION:
In clean room areas, any personnel passing through an unclassified area to a classified area is required to
pass through series of rooms. In each room certain steps need to be followed. This procedure ensures that the
person is not carrying any external contamination in to the process area and also the pressure in each room is
maintained before opening of door.
Door Inter Locking System achieves in prevention of process area contamination by
Preventing simultaneous access of doors/Rooms.
Ensures that when one door for a room is OPEN then all other doors in that particular room are closed.
Programmable delay between each door openings to maintain required pressure.
In Emergency an override key is available on a push button module for opening the door.
2. CONTROLLER FEATURES:
Advanced Micro controller based.
Supports Maximum of 12 doors & 24 Push buttons.
Supports Maximum of 12 Emergency Stations.
Sequence of door inter Locking is field configurable.
Delay between door openings is field configurable from 0 to 999 Sec.
Auto close time is field configurable from 0 to 999 Sec.
Facility available to read feed back from Magnetic Lock.
8x2 DOT MATRIX LCD for Programming.
Easy use Soft touch Tactile Membrane keypad & user-friendly programming options.
Non-Volatile Flash memory to store programming parameters.
Supports Access control module interface.
SPECIFICATIONS:
GENERAL
Push Button Inputs : 12 No.
Door Feedback Inputs : 12 No, 24V.
Door Control Outputs : 12 No, 24V / 25mA
Keypad : Soft touch Tactile Membrane Keys, 4.
Display : 8x2 Alphanumeric LCD.
Instruction Manual (Ver1.1)
Memory : Non-Volatile Flash.
Delay between each door : Programmable 0 to 999 Sec.
Door control sequencing : Programmable.
ENCLOSURE:
Enclosure type : MS (Siemens gray, Powder coated)..
Mounting : Flush / Panel / Wall mounting.
POWER:
Power source : 100 to 260 V, AC 50 Hz.
ENVIORMENTAL:
Temperature : 0 to 500C.
RH : 10 – 95%, Non-condensing.
MECHANICAL:
Weight : approx. 1Kg.
Dimensions : 495X295X50 mm
3. Push Button Station
Features: Elegant look Legrand Silver painted plastic Bezel/Face plate.
Indication facility for Door entry permitted / prohibited.
Support an entry switch for opening the door.
Long Life BAR LED for door open/close indication.
Elegant look Silver painted plastic Bezel with appropriate curvature to prevent resting of dust & powder.
Easy mounting arrangement for fixing on Doorframes or on Wall.
Specifications:
GENERAL:
Keypad : Soft touch Tactile Membrane Key
Status LED’s : WAIT Message for Door Open / Entry Prohibited.
GO Message for Door Close / Entry Permitted.
Digital Input (LED) : 24V DC
Life : 100, 000 Cycles Min.
ENCLOSURE:
Enclosure type : Legrand Silver painted plastic Bezel/Face plate.
Mounting : Flush mounting.
Dimension : 3”X3” Single Module.
POWER:
Instruction Manual (Ver1.1)
Supply Voltage : 24V/50mA DC
4. Emergency Station
Features: Elegant look Legrand Silver painted plastic Bezel/Face plate.
Support an push button switch for opening the all doors.
Elegant look Silver painted plastic Bezel with appropriate curvature to prevent resting of dust & powder.
Easy mounting arrangement for fixing on Doorframes or on Wall.
Specifications:
GENERAL:
Keypad : Soft touch Tactile Membrane Key
Digital Input (LED) : 24V DC
Life : 100, 000 Cycles Min.
ENCLOSURE:
Enclosure type : Legrand Silver painted plastic Bezel/Face plate.
Mounting : Flush mounting.
Dimension : 3”X3” Single Module.
POWER:
Supply Voltage : 24V/50mA DC
5. Electromagnetic locks:
A magnetic lock is a simple locking device that consists of an electromagnet
and armature plate. By attaching the electromagnet to the door frame and the
armature plate to the door, a current passing through the electromagnet
attracts the armature plate holding the door shut
The magnetic lock relies upon some of the basic concepts of
electromagnetism. Essentially it consists of an electromagnet attracting a
conductor with a force sufficiently large enough to prevent the door from
being opened.
Instruction Manual (Ver1.1)
6. OPERATION:
Key operation
▲: Increment key: To increment the parameter value.
►: Right shift key: To shift the cursor position to the right side.
OK: To enter a particular program parameter.
PRG: To enter into program mode and to exit the program mode.
PROGRAM MODES
S.NO MODE DESCRIPTION
1 Auto Lock To select time between the door release and re- energizing
the lock as required.
2 nC All doors to be in Normally Open/Normally Close
position
3 Emrgency Configure the doors for Emergency.
4 DI Configure the Door 1.
5 DII Configure the Door 2.
6 DIII Configure the Door 3.
7 DIV Configure the Door 4.
8 DV Configure the Door 5.
9 DVI Configure the Door 6.
10 DVII Configure the Door 7.
11 DVIII Configure the Door 8.
12 New Psd. To Enter new password.
Brief description of the program mode.
1) Auto Lock: This mode is to set the time between de-energizing of the electric strike or electro
magnetic lock and re-energizing the electric strike or electro magnetic lock.
2) nC: This mode is to enable the user to keep the doors either in the normally open (normally un locked)
or normally close (normally locked) position.
3) Emrgnency: This mode is to select the doors to be configured to emergency input i.e. which doors
should be interlocked to the emergency key press.
4) DI - DVIII: This mode is to select the doors to be configured to a particular door input i.e. which doors
should be interlocked to the that door’s key press.
5) New Psd.: This mode is to allow the user to enter a new password.
PROGRAMMING
NOTE: 1) The default value of the auto close timer is 4sec.
2) By default, all the doors will be in normally closed (normally locked) position.
3) By default, no door will be configured to any other door for interlocking.
4) By default, the delay timers of all doors are 000sec.
PROGRAM MODE:
i). Press “PRG” key to enter into the PROGRAM MODE.
ii). The following menu is displayed.
Instruction Manual (Ver1.1)
Use “►” key to move to the required location.
Use “▲” key to increment the location value (0 - 9).
Use “OK” key after entering the PASS WORD. (Default PASS WORD is 100)
The menu in the PROGRAM MODE is shown below.
Auto Lock Delay:
Using “▲”and “►” keys the programmer can set the auto close time delay i.e the time between the door release
and energising the lock as required.
Use “OK” key to go to next menu.
Normally Open/Normally Close, Lock:
Using “▲” key the programmer can configure the doors as normally open or normally close.
Y :-Normally Close.
N:- Normally Open.
Use “►” key to move to the next location (EM LOCK).
Y :- Electro magnetic lock.
Use “OK” key to go to next menu.
NOTE:
* Possible Mode of operations:
Instruction Manual (Ver1.1)
Emergency Configuration:
Emrgency
X X X X X X X X
Using “▲”and “►” keys the programmer can configure the doors (1-8) for emergency.
0 – Emergency inactive.
1 – Emergency active.
Use “OK” key to go to next menu.
GO, WAIT message toggle indicates that emergency or fire situation, in this situation both doors in un locked
condition up to 8 sec.
Door 1 Configuration:
SI. NO.
Mode of Operation
Program mode
1.
Normally Closed
Electro magnetic lock.
nC: Y
EM LOCK: Y
Normally Closed
Electric striker.
nC: Y
EM LOCK: N
Mode Description:
*Locking device is Electro magnetic lock or Electric striker. Normally locked:
In this mode, initially all doors in locked condition. Door access by using push button. Message
indication provided on the push button station indicates whether person can access the door or not.
Go = GO indicates that person can access the door.
Wait = WAIT indicates that person cannot access the door.
If emergency button pressed, all doors (emergency configured doors) will be unlocked up to 8 sec &
indication on push button will be toggle indicates emergency.
2.
Normally Open
Electro magnetic lock.
nC: N
EM LOCK: Y
Normally Open
Electric striker.
nC: N
EM LOCK: N
Mode Description:
*If locking device is Electromagnetic lock, separate reed Switch (magnetic sensor) is need be used.
Normally Un locked:
In this mode, initially all doors in un locked condition, here push buttons are used only for indication
purpose (no need to press the button). Message indication provided on the push button station indicates
whether person can access the door or not.
In this mode controller continuously monitors status of the door (open/close) through feed back from
magnetic lock. If any door is open then the system will lock the remaining doors as per configuration and
for duration required.
Go = GO indicates that person can access the door.
Wait = WAIT indicates that person cannot access the door.
If emergency button pressed, all doors (emergency configured doors) will be unlocked up to 8 sec &
indication on push button will be toggle indicates emergency.
Instruction Manual (Ver1.1)
DI XXX
d X X X X X X X
xxx -: door delay (secs). Time after which door will open after the closure of some door in its set.
Using “▲”and “►” keys the programmer can set the door delay time as required.
Using “▲”and “►” keys the programmer can configure the doors (1-8) for Door 1 set.
d – not applicable.
0 – Door not selected for inter locking with Door 1.
1 – Door selected for inter locking Door 1.
Use “OK” key to go to next menu.
Door 2 Configuration:
DII XXX
X d X X X X X X
xxx -: door delay (secs). Time after which door will open after the closure of some door in its set.
Using “▲”and “►” keys the programmer can set the door delay time as required.
Using “▲”and “►” keys the programmer can configure the doors (1-8) for Door 2 set.
d – not applicable.
0 – Door not selected for inter locking with Door 2.
1 – Door selected for inter locking with Door 2.
Use “OK” key to go to next menu.
Door 3 Configurations:
DIII XXX
X X d X X X X X
xxx -: door delay (secs). Time after which door will open after the closure of some door in its set.
Using “▲”and “►“ keys the programmer can set the door delay time as required.
Using “▲”and “►” keys the programmer can configure the doors (1-8) for Door 3 set.
d – not applicable.
0 – Door not selected for inter locking with Door 3.
1 – Door selected for inter locking with Door 3.
Use “OK” key to go to next menu.
Door 4 Configuration:
Instruction Manual (Ver1.1)
DIV XXX
X X X d X X X X
xxx -: door delay (secs). Time after which door will open after the closure of some door in its set.
Using “▲”and “►” keys the programmer can set the door delay time as required.
Using “▲”and “►” keys the programmer can configure the doors (1-8) for Door 4 set.
d – not applicable.
0 – Door not selected for inter locking with Door 4.
1 – Door selected for inter locking with Door 4.
Use “OK” key to go to next menu.
Door 5 Configuration:
DV XXX
X X X X d X X X
xxx -: door delay (secs). Time after which door will open after the closure of some door in its set.
Using “▲”and “►” keys the programmer can set the door delay time as required.
Using “▲”and “►” keys the programmer can configure the doors (1-8) for Door 5 set.
d – not applicable.
0 – Door not selected for inter locking with Door 5.
1 – Door selected for inter locking with Door 5.
Use “OK” key to go to next menu.
Door 6 Configurations:
DVI XXX
X X X X X d X X
xxx -: door delay (secs). Time after which door will open after the closure of some door in its set.
Using “▲”and “►” keys the programmer can set the door delay time as required.
Using “▲”and “►” keys the programmer can configure the doors (1-8) for Door 6 set.
d – not applicable.
0 – Door not selected for inter locking with Door 6.
1 – Door selected for inter locking with Door 6.
Use “OK” key to go to next menu.
Door 7 Configuration:
DVII XXX
X X X X X X d X
xxx -: door delay (secs). Time after which door will open after the closure of some door in its set.
Using “▲”and “►” keys the programmer can set the door delay time as required.
Using “▲”and “►” keys the programmer can configure the doors (1-8) for Door 7 set.
Instruction Manual (Ver1.1)
d – not applicable.
0 – Door not selected for inter locking with Door 7.
1 – Door selected for inter locking with Door 7.
Use “OK” key to go to next menu.
Door 8 Configuration:
DVIII XXX
X X X X X X X d
xxx-: door delay (secs). Time after which door will open after the closure of some door in its set.
Using “▲”and “►” keys the programmer can set the door delay time as required.
Using “▲”and “►” keys the programmer can configure the doors (1-8) for Door 8 set.
d – not applicable.
0 – Door not selected for inter locking with Door 8.
1 – Door selected for inter locking with Door 8.
Use “OK” key to go to next menu.
New Password:
New Psd
X X X
Use “►” key to move to the required location.
Use “▲” key to increment the location value(0 - 9).
Press “OK” key and then again press PRG To enter the new password and store all parameters.
7. Wiring Diagrams:
Instruction Manual (Ver1.1)
Instruction Manual (Ver1.1)
Instruction Manual (Ver1.1)
Instruction Manual (Ver1.1)
8. MECHANICAL DRAWINGS:
Figure for Installation of ILS-1058 Controller:
Front View Diagram of ILS-1058 Controller:
Instruction Manual (Ver1.1)
9. ORDERING INFORMATION: l). Door Interlocking System ( up to 8 Door):
Includes,
a) Door interlock controller (8Door):
b) Push Button Station:
Model No X Description
ILS-1054 X 4-Door interlocking System
ILS-1055 X 5-Door interlocking System
ILS-1056 X 6-Door interlocking System
ILS-1057 X 7-Door interlocking System
ILS-1058 X 8-Door interlocking System
Model No X Description
ILS-1054C X 4-Door interlocking Controller
ILS-1055C X 5-Door interlocking Controller
ILS-1056C X 6-Door interlocking Controller
ILS-1057C X 7-Door interlocking Controller
ILS-1058C X 8-Door interlocking Controller
Instruction Manual (Ver1.1)
c) Emergency Station:
d) IO MODULE:
e) Electromagnetic Lock:
e) Power Supply:
10. TROUBLE SHOOTING:
SL.NO Problem Cause Action
1. No Message indication. Power Failed Check the Power supply connections.
2. Indication on Push button
blinking.
Noise Switch OFF and switch ON again. If
problem is reported again then contact to the
factory.
3. Continuous WAIT
indication on push button
Other door is not
closed properly or
magnet armature not
fixed properly
Adjust armature until get GO
NOTES:
Model No X
ILS-105P 1. PLASTIC LEGRAND PUSH BUTTON
ILS-105P 2. SS FRAME PUSH BUTTON
Model No X
ILS-105E 1. PLASTIC LEGRAND PUSH BUTTON
ILS-105E 2. SS FRAME PUSH BUTTON
Model No X
ILS-IO X
Model No X
EML 1. Bar Electro magnetic lock
Model No X
ILS-PS X
Instruction Manual (Ver1.1)
For Further Information Contact:
Styrax Instruments India Pvt. Ltd. PLOT No.48-51, Dollapally road, Phase V Extn. I.D.A., Jeedimetla, Hyderabad – 014
Andhra Pradesh, INDIA
Ph: +91 40 2309 3314, +91 9640447474, Fax: +91 40 2309 3315
www.styraxinstruments.com
Email: [email protected]