8400 Series Thermostats
READ AND SAVE THESE INSTRUCTIONS
Safety & Installation Instructions
61000652C 8400 Tstat Install.indd 1 10/13/09 11:08:56 AM
2
Installation location recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3Outdoor temperature sensor (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4Thermostat mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5Power & reset options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5Wiring terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
TAblE Of CONTENTS
INSTAllATION
SETUp & TESTINg
REfERENCES
System setup instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11System test mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Quick reference to controls & display •Non-programmablemodels(8444,8446,8448) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22 •Programmablemodels(8463,8465,8466) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23Thermostat features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
61000652C 8400 Tstat Install.indd 2 10/13/09 11:08:56 AM
3
INSTAllATION
INSTAllATION lOCATION RECOmmENDATIONS
Thermostat should be mounted:
•Onaninteriorwall,inafrequentlyoccupiedspace.
•Approximately5‘abovefloor.
•Atleast18”fromoutsidewall.
•Thermostatcanbemountedtoaverticaljunctionbox.
Do not mount thermostat:
•Behinddoors,incorners,orotherdeadairspaces.
•Indirectsunlight,nearlightingfixtures,orotherappliancesthatgiveoffheat.
•Onanoutsideorunconditionedareawall.
•Intheflowofasupplyregister,instairwells,ornearoutside doors .
•Onawallwithconcealedpipesorductwork.
61000652C 8400 Tstat Install.indd 3 10/13/09 11:08:57 AM
4
OUTDOOR TEmpERATURE SENSOR (OpTIONAl)
Outdoortemperaturecanbemeasuredbyattachingan8052sensortotheS1andS2terminals.Systemsetting#05(Remotesensor)isusedtoenablesensor.
Heat pump models can use the outdoor temperature to effectivelyutilizetheheatpump:
•WhentheoutdoortemperatureislessthantheLowBalancePoint,theheatpumpwillbelockedoutandonlyauxiliaryheatingwillbeused.
•WhentheoutdoortemperatureishigherthantheHighBalancePoint,theauxiliaryheatingwillbelockedoutandonlytheheatpumpwillbeusedtoprovideheating.
INSTAllATION
CGYWR LS1 S2 O/B W2 Y2RC
•Installonsideofbuildingoutofdirectsunlight (north side recommended) .
•Mountabovesnowline.
•Mountatleast3’awayfromexhaustventsandcondensing lines .
•Maximumwirelengthis300’.
•Donotroutewiresalong120VAClines.
61000652C 8400 Tstat Install.indd 4 10/13/09 11:08:57 AM
5
THERmOSTAT mOUNTINg
1.Removethebackofthethermostat,bypressingthe tabonthebottomoftheunit.
2.Pullwiresthroughtheopeningonthebackofthethermostat .
3.Positionandlevelthebackofthethermostatonwalland mark the hole locations with a pencil .
4.Drill1/4”holes&insertsuppliedanchors(drywallonly).
5.Placebackoveranchors,insertandtightenscrews.
6.Sealwireentryholestopreventdraftsaffectingtemperature readings .
INSTAllATION
pOwER & RESET OpTIONS
Thethermostatisdualpower.ItcaneitherbeACorbatterypowered,orboth(toprovidebackuppowerfortheclock).BatteriesareoptionalifthethermostatwasconnectedtoACpowerwheninstalled.
Forheatpumpmodels(8446,8448HP,8465,8466HP) 24VACmustbeconnectedinorderforthesystemfaultand emergency heat indicators to operate .
Thethermostathasamemorybackupthatsavesthethermostat’ssettingsincaseofapowerinterruption.
Theresetbuttonlocatedunderthebatterycovercanbeusedtoresetthethermostatbacktofactorydefaults.Thesystemsettingswillalsoberesetbacktodefaults.
61000652C 8400 Tstat Install.indd 5 10/13/09 11:08:58 AM
6
wIRINg TERmINAl
wire specifications
18-24gaugethermostatwire
Installation notes
•EnsurepowerattheHVACequipmentisoff.
•Loosenscrewterminals,insertstrippedwireandre-tighten.
•Pushtheexcesswirebackintotheopeningandplugthewallopeningtopreventdrafts.
INSTAllATION
RC–24VACsupplycooling*R–24VACsupplyheating*w–1ststageheat/auxiliaryY–1ststagecooling/compressorg – FanC–Common(optionalwhenpoweredbybatteries)S1 & S2 – outdoor temperature sensor (optional)O/b–Reversingvalvel – System fault indicatorw2–2ndstageheat/auxiliaryY2–2ndstagecooling/compressor* Jumper between RC & R is used in single transformer systems
(see wiring diagrams).
CGYWR LS1 S2 O/B W2 Y2RC
61000652C 8400 Tstat Install.indd 6 10/13/09 11:08:58 AM
7
wIRINg – mODEl 8463 & 8444 SINglE TRANSfORmER (USE jUmpER wIRE)
INSTAllATION
CGYWR S1 S2RC
HEA
TIN
G
COO
LIN
G
FAN
OU
TDO
OR
TEM
P SE
NSO
R
JUM
PER
TRA
NSF
ORM
ERwIRINg – mODEl 8463 & 8444 TwO TRANSfORmERS (REmOVE jUmpER wIRE)
CGYWR S1 S2RC
HEA
TIN
G
COO
LIN
G
FAN
OU
TDO
OR
TEM
P SE
NSO
R
HEA
TIN
GTR
AN
SFO
RMER
COO
LIN
GTR
AN
SFO
RMER
61000652C 8400 Tstat Install.indd 7 10/13/09 11:08:58 AM
8
wIRINg – mODEl 8465 & 8446 SINglE TRANSfORmER (USE jUmpER wIRE)
INSTAllATION
AU
X H
EATI
NG
COM
PRES
SOR
FAN
REVE
RSE
VALV
E
FAU
LT D
ETEC
T
OU
TDO
OR
TEM
P SE
NSO
R
JUM
PER
TRA
NSF
ORM
ER
CGYWR LS1 S2 O/BRC
wIRINg – mODEl 8465 & 8446 TwO TRANSfORmERS (REmOVE jUmpER wIRE)
AU
X H
EATI
NG
COM
PRES
SOR
FAN
REVE
RSE
VALV
E
FAU
LT D
ETEC
T
OU
TDO
OR
TEM
P SE
NSO
R
AU
X H
EATI
NG
TRA
NSF
ORM
ER
HEA
T PU
MP
TRA
NSF
ORM
ER
CGYWR LS1 S2 O/BRC
61000652C 8400 Tstat Install.indd 8 10/13/09 11:08:58 AM
9
wIRINg – mODEl 8466 & 8448 SINglE TRANSfORmER (USE jUmpER wIRE) fOR HEAT/COOl SYSTEm
INSTAllATION
1st H
EATI
NG
1st C
OO
LIN
G
FAN
2nd
HEA
TIN
G
2nd
COO
LIN
G
OU
TDO
OR
TEM
P SE
NSO
R
NO
T U
SED
NO
T U
SED
JUM
PERTR
AN
SFO
RMER
CGYWR LS1 S2 O/B W2 Y2RC
wIRINg – mODEl 8466 & 8448 TwO TRANSfORmERS (REmOVE jUmpER wIRE) fOR HEAT/COOl SYSTEm
1st H
EATI
NG
1st C
OO
LIN
G
FAN
2nd
HEA
TIN
G
2nd
COO
LIN
G
OU
TDO
OR
TEM
P SE
NSO
R
NO
T U
SED
NO
T U
SED
HEA
TIN
GTR
AN
SFO
RMER
COO
LIN
GTR
AN
SFO
RMER
CGYWR LS1 S2 O/B W2 Y2RC
61000652C 8400 Tstat Install.indd 9 10/13/09 11:08:58 AM
10
INSTAllATION
wIRINg – mODEl 8466 & 8448 SINglE TRANSfORmER (USE jUmpER wIRE) fOR HEAT pUmp SYSTEm
1st A
UX
HEA
TIN
G
1st C
OM
PRES
SOR
FAN
REVE
RSE
VALV
E
FAU
LT D
ETEC
T
2nd
AU
X H
EATI
NG
2nd
COM
PRES
SOR
OU
TDO
OR
TEM
P SE
NSO
R
HEA
T PU
MP
TRA
NSF
ORM
ER
CGYWR LS1 S2 O/B W2 Y2RC
JUM
PER
1st A
UX
HEA
TIN
G
1st C
OM
PRES
SOR
FAN
REVE
RSE
VALV
E
FAU
LT D
ETEC
T
2nd
AU
X H
EATI
NG
2nd
COM
PRES
SOR
OU
TDO
OR
TEM
P SE
NSO
R
HEA
TIN
GTR
AN
SFO
RMER
HEA
T PU
MP
TRA
NSF
ORM
ER
CGYWR LS1 S2 O/B W2 Y2RC
wIRINg – mODEl 8466 & 8448 TwO TRANSfORmERS (REmOVE jUmpER wIRE) fOR HEAT pUmp SYSTEm
61000652C 8400 Tstat Install.indd 10 10/13/09 11:08:59 AM
11
SYSTEm SETUp INSTRUCTIONS
How to enter the system setup menu to change system settings
press repeatedly until system is set to OFF .
press and hold and for three seconds .
Thescreenofthefirstsettingwillbedisplayed.
SETUp & TESTINg
press or to change the setting .
press tochangetothenextoption.
press afterthelastsetting.“DONE”willbedisplayed .
ThethermostatwillreturntoNormalmodeifnokeyispressed in 3 seconds .
Toresetallsystemsettingsbacktodefault,presstheRESETbuttonlocatedunderthebatterydoor.
Thefollowinginstructionsshowhowtoenterthesystemsetupmenuandchangesettings.Thetableonthefollowingpagesliststhesettingsandtheirdetails.Defaultsettingsareshowninbold . Some settings are only availabletocertainmodels,andsomearespecifictothermostatssettoheatpumpmode.
SYSTEMSETTINGNUMBER
SETTINGVALUE
61000652C 8400 Tstat Install.indd 11 10/13/09 11:08:59 AM
12
SETUp & TESTINg
SYSTEm SETUp INSTRUCTIONS (CONTINUED)
Thermostatmodels8448&8466havetheoptionofbeingusedinheatpumporheat/coolsystems.SwitchSW1locatedonthebackofthethermostat’sfaceisusedtoselectthis.Systemsettingnumber00willonlybeshownonthese models to display the position of SW1 .
Sw1HEATPUMPHEAT/COOL
61000652C 8400 Tstat Install.indd 12 10/13/09 11:08:59 AM
13
SETUp & TESTINg
System setting Setting range, default in bold
00Equipmenttype(8466,8448)(Set by Sw1) 0:heat/cool1:heatpump
01 Temperature scale0 : fahrenheit1:Celsius
02 Fan control in heating0 : gas or oil furnace (Equipment controls fan)1:Electric(Thermostatcontrolsfan)
03 Offset temperature for internal sensor0° : No offset applied–4°Fto+4°F(–2°Cto+2°C)
04Automode 0 : Auto mode is disabled1:Automodeisenabled
05 Outdoor temperature sensor0 : No outdoor temperature sensor attached1:Outdoortemperaturesensorattached
06Compressorminimumofftime 5 minutes1 to 5 minutes in 1 minute steps
07 Heating minimum off time2 minutes1 to 5 minutes
08Equipmentminimumontime 2 minutes1 to 5 minutes
SYSTEm SETUp INSTRUCTIONS (CONTINUED)
61000652C 8400 Tstat Install.indd 13 10/13/09 11:08:59 AM
14
SETUp & TESTINg
System setting Setting range, default in bold
09 1st stage differential1°f (0.5°C)1°Fto4°F(0.5°Cto2°C)
102ndstagedifferential(8448,8466) 1°f (0.5°C)1°Fto4°F(0.5°Cto2°C)
113rdstagedifferential(8448HP,8466HP) 1°f (0.5°C)1°Fto4°F(0.5°Cto2°C)
12Reversevalve(8446,8466HP,8465,8466HP) 0 – O/b energized in cooling (O)1–O/Benergizedinheating(B)
13Integralfactorperiod(P+Icontrol)* Set to OFF for proportional control only
4 minutes1to5minutesor“OFF”todisable
14Deadband(automode) 3°f (2°C)2°Fto5°F(1°Cto3°C)
15Progressiverecovery(8463,8465,8466) 0:Progressiverecoveryisdisabled1 : progressive recovery is enabled
*Theintegralfactorisusedintheequipmentcontrolalgorithmtomaintainthespacetemperatureatsetpoint. Ashortintegralfactorperiodwillincreasethenumberofcyclesperhour.(Ashortintegralfactorperiodwillbemorecomfortable.)Alongintegralfactorperiodwilllowerthenumberofcyclesperhour.(Alongintegralfactorperiodwillbemoreeconomical.)
SYSTEm SETUp INSTRUCTIONS (CONTINUED)
61000652C 8400 Tstat Install.indd 14 10/13/09 11:09:00 AM
15
SETUp & TESTINg
System setting Setting range, default in bold
16LowBalancePt.(8446,8448HP,8465,8466HP) Systemsetting05mustbeenabled
20°f (–7°C) 1°Fto35°F(–17°Cto1°C)or“OFF”todisable
17HighBalancePt.(8446,8448HP,8465,8466HP) Systemsetting05mustbeenabled
60°f (16°C)40°Fto80°F(4°Cto27°C)or“OFF“todisable
19Programformat(8463,8465,8466) 0 – 5/2 program (weekdays and weekends)1–5/1/1program(Weekdays,Sat.andSun.)
20Changeairfilter Off1,3,6,12monthsor“OFF”todisable
21Changewaterpanel** Setnumberofmonthsuntilreminderisrequired
Off1to12monthsor“OFF”todisable
22Humidifiertype** 0 : flow through type humidifier (1 reminder per season)1:Drain-lesstypehumidifier(2 reminders per season)
23Servicedehumidifier Off1to12monthsor“OFF”todisable
24ServiceHVAC Off1to12monthsor“OFF”todisable
**IfhumidifiertypeissettoDrain-less,thenthefirstreminderisbasedonthesystemsetting21,secondreminderwillactivate3monthslater.IfhumidifiertypeissettoFlowthrough,thenthefirstreminderisbasedonsystemsetting21,secondreminderwillactivate12monthslater.
SYSTEm SETUp INSTRUCTIONS (CONTINUED)
61000652C 8400 Tstat Install.indd 15 10/13/09 11:09:00 AM
16
SYSTEm TEST mODE
Thesystemtestmodeisusedtotestasystemafterinstallation.Theoutputsofthethermostatcanbemanuallyactivatedoneatatimetotesttheirfunction.Thefollowinginstructionsshowhowtoenterthetestmodeandturnoutputs on and off . The charts on the following pages show all of the options for each model .
The test steps are:
SETUp & TESTINg
Test Number
Heat/Cool models8444, 8463, 8448HC, 8466HC
Heat pump models8446, 8465, 8448Hp, 8466Hp
50 Heating (W) (W2) AuxHeating(W)(W2)
51 Cooling(Y)(Y2) CompressorCooling(Y)(Y2)
52 Fan(G) CompressorHeating(Y)(Y2)
53 Fan(G)
61000652C 8400 Tstat Install.indd 16 10/13/09 11:09:00 AM
17
How to enter the system test menu
press repeatedly until system is set to OFF .
press and hold and for three seconds .
Thescreenofthefirstteststep#50isdisplayed:
SYSTEm TEST mODE (CONTINUED)
SETUp & TESTINg
press toturnontheoutput(01).Formultistageoutput,press againtoturnonthe2ndstage(02).
press toturnofftheoutput(00).
press tochangetothenextteststep.
press afterthelastteststep.“DONE”willbedisplayed .
ThethermostatwillreturntoNormalmodeifnokeyispressed in 3 seconds .
SYSTEMTESTNUMBER
OUTPUTSTATUS
FLASHESIF24VACISNOTPRESENT
MODE(SW1SETTING8448&8466ONLY)
61000652C 8400 Tstat Install.indd 17 10/13/09 11:09:00 AM
18
SETUp & TESTINg
Test steps for 8444 & 8463
Step Key Input
System Setting Display (Output)
#2 01
HEATINg ON (w)
01
COOlINg ON (Y)
01
fAN ON (g)
#50Heat[UP]
0:Gas ON
1:Elec ON ON [DOWN]
#51Cool[UP] ON ON
[DOWN]
#52 Fan[UP] ON
[DOWN]
61000652C 8400 Tstat Install.indd 18 10/13/09 11:09:01 AM
19
SETUp & TESTINg
Test steps for 8448HC & 8466HC
Step Key Input
System Setting Display (Output)
#2 01
HEATINg ON (w)
02 HEATINg ON (w2)
01 COOlINg
ON (Y)
02 COOlINg ON (Y2)
01 fAN ON
(g)
#50Heat
1st[UP]0:Gas ON 1:Elec ON ON
2nd[UP]0:Gas ON ON 1:Elec ON ON ON
[DOWN]
#51Cool1st[UP]
ON ON
2nd[UP] ON ON ON [DOWN]
#52 Fan[UP] ON
[DOWN]
61000652C 8400 Tstat Install.indd 19 10/13/09 11:09:01 AM
20
Test steps for 8446 & 8465
Step Key Input
System Setting Display (Output)
#2 #1201 AUX
HEATINg ON (w)
01
COOl/HEAT ON (Y)
01
fAN ON (g)
O/b
#50Aux[UP]
0:Gas
ON 1:Elec ON ON
[DOWN]
#51Cool[UP]
0:O ON ON ON1:B ON ON
[DOWN] 0:O ON1:B
#52 Heat[UP]
0:O ON ON 1:B ON ON ON
[DOWN] 0:O 1:B ON
#53 Fan[UP] ON
[DOWN]
SETUp & TESTINg
61000652C 8400 Tstat Install.indd 20 10/13/09 11:09:01 AM
21
Test steps for 8448Hp & 8466Hp
Step Key Input
System Setting Display (Output)
#2 #1201 AUX
HEATINg ON (w)
02 AUX HEATINg ON (w2)
01 COOl/HEAT
ON (Y)
02 COOl/HEAT
ON (Y2)
01 fAN ON
(g)O/b
#50Aux
1st[UP]0:Gas
ON
1:Elec ON ON
2nd[UP]0:Gas
ON ON
1:Elec ON ON ON [DOWN]
#51Cool
1st[UP] 0:O ON ON ON1:B ON ON
2nd[UP] 0:O ON ON ON ON1:B ON ON ON
[DOWN] 0:O ON1:B
#52 Heat
1st[UP] 0:O ON ON 1:B ON ON ON
2nd[UP] 0:O ON ON ON 1:B ON ON ON ON
[DOWN] 0:O 1:B ON
#53 Fan[UP] ON
[DOWN]
SETUp & TESTINg
61000652C 8400 Tstat Install.indd 21 10/13/09 11:09:02 AM
22
QUICK REfERENCE TO CONTROlS & DISplAY
NON-pROgRAmmAblE mODElS (8444, 8446, 8448)
NOTE:BACKLIGHTISACTIVATEDWITHFIRSTBUTTONPRESSANDAUTOMATICALLYTURNSOFF.
CURRENTINDOORTEMPERATURE
SYSTEMMODESETTING
FANSETTING
SYSTEMMODE
FANSETTING
BATTERYDOOR
MESSAGECENTER LOWBATTERYWARNING
QUICKREFERENCECARD
OUTDOORTEMPERATURE(OPTIONAL)
TEMPERATURESETTING
EQUIPMENTSTATUS
EMERGENCYHEAT(RED)
SYSTEMFAULT(YELLOW)
INDICATORSHOWSTHROUGHHOUSING
HEAT pUmp mODElS ONlY
UP
DOWN
61000652C 8400 Tstat Install.indd 22 10/13/09 11:09:02 AM
23
QUICK REfERENCE TO CONTROlS & DISplAY
pROgRAmmAblE mODElS (8463, 8465, 8466)
NOTE:BACKLIGHTISACTIVATEDWITHFIRSTBUTTONPRESSANDAUTOMATICALLYTURNSOFF.
CURRENTINDOORTEMPERATURE
SYSTEMMODESETTING
FANSETTING
SYSTEMMODE
FANSETTING
BATTERYDOOR
MESSAGECENTER LOWBATTERYWARNING
QUICKREFERENCECARD
OUTDOORTEMPERATURE(OPTIONAL)
TEMPERATURESETTING
EQUIPMENTSTATUS
EMERGENCYHEAT(RED)
SYSTEMFAULT(YELLOW)
INDICATORSHOWSTHROUGHHOUSING
HEAT pUmp mODElS ONlY
UP
DOWN
PROGRAM
CURRENTSCHEDULEPERIOD
HOLD
CURRENTTIME
61000652C 8400 Tstat Install.indd 23 10/13/09 11:09:02 AM
24
THERmOSTAT fEATURES
All 8400 SERIES THERmOSTATS
•Large,clear,backlitdisplayiseasytoread–evenin the dark .
•Displaysroomtemperature,temperaturesetting,andoptional outdoor temperature .
•Dualpoweroption(Batteryor24VAC).
•Frontbatterydooraccessforfast,easyreplacement.
•Builtincompressorprotection.
•Circulationfanmodeforaircleaning.
•Waterpanel,dehumidifier,airfilter,andHVACserviceindicators.
•Systemtestmode.
pROgRAmmAblE mODElS ONlY (8463, 8465, 8466)
•Separatelyprogrammableweekday/weekendschedules .
•Easytousetemperaturecontrolcanoverrideprogram schedule at any time .
•Progressiverecovery.ProgressiveRecoveryfeatureallowsthethermostattoactivatetheheatingandcoolingequipmentpriortoaneventinordertoreachthedesiredtemperatureatthestartofthenextscheduledevent.
61000652C 8400 Tstat Install.indd 24 10/13/09 11:09:02 AM
25
TROUblESHOOTINg
DISplAY IS blANK
•Checkcircuitbreakerandresetifnecessary.
•Makesurepowerswitchatheating&coolingsystem is on .
•Makesurefurnacedoorisclosedsecurely.
•Ifthermostatisbatterypowered,makesurefreshAAalkalinebatteriesarecorrectlyinstalled.
TEmpERATURE SETTINgS DO NOT CHANgE
Makesureheatingandcoolingtemperaturesaresettoacceptableranges:
• Heat:45°to90°F(7°to32°C).
• Cool:50°to99°F(10°to37°C).
HEATINg SYSTEm DOES NOT RESpOND (“HEATINg” AppEARS ON SCREEN)
•Checkfor24VACattheequipmentonthesecondarysideofthetransformerbetweenpowerandcommon.Ifvoltageisnotpresent,checktheheatingequipmenttofindthecauseoftheproblem.
•Checkfor24VACbetweentheheatterminal(W)andthetransformercommon.If24VACispresent,thethermostatisfunctional.Checktheheatingequipmenttofindthecauseoftheproblem.
•Checkforlooseorbrokenwiresbetweenthethermostatandtheheatingequipment.
61000652C 8400 Tstat Install.indd 25 10/13/09 11:09:03 AM
26
TROUblESHOOTINg
COOlINg SYSTEm DOES NOT RESpOND (“COOlINg” AppEARS ON SCREEN)
•Checkfor24VACattheequipmentonthesecondarysideofthetransformerbetweenpowerandcommon.Ifvoltageisnotpresent,checkthecoolingequipmenttofindthecauseoftheproblem.
•Checkfor24VACbetweenthecoolingterminal(Y)andthetransformercommon.If24VACispresent,thethermostatisfunctional.Checkthecoolingsystemtofindthecauseoftheproblem.
•Checkforlooseorbrokenwiresbetweenthethermostatandthecoolingequipment.
fAN DOES NOT TURN ON IN A CAll fOR HEAT
•CheckSystemSetting#02(FanControl),tomakesure the fan control is properly set to match the type of system (see page 11) .
HEAT pUmp ISSUES COOl AIR IN HEAT mODE, OR wARm AIR IN COOl mODE
•CheckSystemSetting#12(ReversingValve),tomakesure it is properly configured for your system (see page 11) .
HEAT/COOl bOTH ON AT SAmE TImE
•CheckSW1(EquipmentType),tomakesureitissettomatchtheinstalledheating/coolingequipment(see page 12) .
•Checktomakesureheatingandcoolingwiresarenot shorted together .
HEATINg EQUIpmENT IS RUNNINg IN COOl mODE
•CheckSW1(EquipmentType),tomakesureitissettomatchtheinstalledheating/coolingequipment(see page 12) .
“HEATINg” IS NOT DISplAYED
•ChangetheSystemModetoHeat,andsetthetemperaturelevelabovethecurrentroomtemperature .
“COOlINg” IS NOT DISplAYED
•ChangetheSystemModetoCool,andsetthetemperaturelevelbelowthecurrentroomtemperature .
61000652C 8400 Tstat Install.indd 26 10/13/09 11:09:03 AM
27
SpECIfICATIONS
Electrical
Operatingvoltage 24VAC(18–30VAC)
CurrentMaximum:2.5A(total),1.0A(singleoutput)
Maximumsurgecurrent:5A
Power supplyDualpower.Canbebatteryor24VACpowered.
Whenboththesourcesareavailable,batterywillbeusedasbackuppower.
BatterypowerBatterypower:AAsizealkalinebatteryx2
Batterylife:Approximately1year
Environment
TemperatureOperating:32°to120°F(0°to48.9°C)
Shipping:-30°to140°F(-34.4°to60°C)
Relativehumidity Operating:5%to90%R.H.(non-condensing)
61000652C 8400 Tstat Install.indd 27 10/13/09 11:09:03 AM
28
SpECIfICATIONS
Thermal
Outdoor temperature sensor Maximumdistance:300feet
Roomtemperaturemeasurement Displayrange:32°to99°F(0°to40°C)
Outdoor temperature measurement Displayrange:-20°to130°F(-30°to55°C)
Temperature setting rangeHeat:45°to90°F(7°to32°C)
Cool:50°to99°F(10°to37°C)