Rotary Air-conditioning Compressors Specification
YZG-Q064Y4 Compressor Model
The Customer
Air-conditioner Model
QINGANQINGANQINGANQINGAN SIGNATURESIGNATURESIGNATURESIGNATURE CUSTOMECUSTOMECUSTOMECUSTOMERRRR’SSSS APPROVALAPPROVALAPPROVALAPPROVAL
。 This document will be effective with your authorized signature .please return one
copy of this document.
Compile:
Examine:
Approve:
Xi’an Qing’an Refrigeration Equipment Co., Ltd
共 11 页/11 page altogether
YZGYZGYZGYZG----Q06Q06Q06Q064444Y4/GSY4/GSY4/GSY4/GS----001B001B001B001B
2
1 Specification of Compressor
1.1 Application Scope
Air-conditioner Type 单冷 Cooling
Refrigerant
R134a
Range of Ambient temperature 15~43
Range of evaporating temperature -10~15
Range of Condensing temperature 35~56
Rated Voltage / Frequency / Phase
220-240V~/50Hz/1Φ
Approval Type CCC、TUV、CE
1.2 Basic Specification
Compressor Type Hermetic Rotary Compressor
Displacement
6.4cm3/rev
Cylinder Number
1
Suction Tube(I.D)
Φ6.5mm
Discharge Tube(I.D)
Φ5.7mm
Net Weight (Oil Included)
4.5kg
Oil & Oil Charge
RB68EP&150 mL
Painting Black Color Paint
1.3 Specification of Motor
Motor Type Single Phase Motor
Pole 2 极 2 Pole
Winding resistance (at 20) Main 17.2Ω±10% Sub 41.5Ω±10%
Rated Voltage / Frequency / Phase
220-240V~/50Hz/1Φ
Rated Revolution
2780 rev/min
Motor Starting Type Permanent Split Capacitor
3
YZGYZGYZGYZG----Q06Q06Q06Q064444Y4/GSY4/GSY4/GSY4/GS----001B001B001B001B
1.4 Electrical Component
Parts Name Specification
Running Capacitor (Self Provided)
6.5µF/450V·AC
Overload Protector (Outer)
BF225-JB
2. Performance Parameter
2.1 Test Condition & Performance
Parts Name Unit Numerical Value
Cooling Capacity
W︱Btu ≥690×95%︱2350×95%
(at 220V)
Input Power W
≤295×105%
(at 220V)
Current A
≤1.4×105%
(at 220V)
EER
W/W︱Btu/W ≥2.3×95%︱7.8×95%
(at 220V)
Noise dB(A)
≤53
Vibration
m/s2
≤15
Test Condition
w w
Rated Voltage / Frequency / Phase
Condensing temperature
220V~/50Hz/1Φ
:54.4
w Evaporating temperature :7.2 w w
Suction Gas temperature
Degree of Super-cooling
:35.0 :8.3
w Ambient temperature :35
2.2 Starting & Running
Parts Name Unit Numerical Value
Locked rotor amps
A 5
(at 220V)
Starting Voltage V
≥187
Running Voltage Range V 198~264
4
YZGYZGYZGYZG----Q06Q06Q06Q064444Y4/GSY4/GSY4/GSY4/GS----001B001B001B001B
2.3 Other Characteristics
Parts Name Unit Numerical Value
Leakage Testing Pressure
MPa
2.1
Shell Mechanical Strength Pressure
MPa
7.4
Insulation Class
B Class
Insulation Resistance
MΩ
≥30
Electric Strength 1500V 1min
or 1800V 1sec
Residual Moisture
mg
≤75
Residual Impurity
mg
≤20
Grounding Resistance
Ω
≤0.1
The Max. Filling Amount of Refrigerant
g
300
3. Operating Conditions of Compressor
3.1 When installed intothe refrigerating system,obey to accessories insrallation diagram.
3.2 3min。The period of turning down and restarting the compressor should be more than 3 minutes.
3.3 The compressor should not be left opened in the atmosphere for more than 5 minutes, otherwise the
moisture and impurity would enter into the compressor.
3.4 The degree of vacuum in the refrigerating system should be less than 20Pa room temperature just before charging refrigerant. The residual moisture should be less than 40ppm in the system.
3.5 Prevent moisture from entering into the enclosed unit system. When the moisture entered into the unit
with refrigerant R134a,the refrigerant oil and the organic compound material presented in the hermetic
motor will possibly decompose on the affecting of in the capillary depositing and the reducing of
insulation resistance.
3.6 To dehumidify the residual moisture mixed in the refrigerant in the cycling system, we suggest
install a dryer(molecular-sieve dryer) in the cycling system.
5
YZGYZGYZGYZG----Q06Q06Q06Q064444Y4/GSY4/GSY4/GSY4/GS----001B001B001B001B
3.7 Prevent the impurities from entering into the enclosed unit system. When the impurities entered into the
enclosed system,it will damage the moving mechanism partsand result in capillary depositing.
Keep the system clean when assembly system. Non-CL cleaning liquid should be applied. Residual
cleaning liquid should not over 0.03g/m3 and no metal powder allowed in
system.
No welding powder or dust should be prevented when welding the compressor to pipe. The CL element
content in welding powder should keep in a low level.If the welding powder need adding some water,please
use no-CL water. Prevent oxi surface when doing dry-welding.
3.8 Lay down of the compressor is forbidden.Do not put the compressor in open area. The compressor should
be stored in clean and dry rooms.
4. Parts and Drawing List
Parts Name Code QTY/Set Remarks
Compressor
YZG-Q064Y4
1 Shape
Electric container cap
YZG/AZ-00-16
1
Spring clip
YZG/AZ-00-17
1
Absorber Support
YZG/AZ-00-18
3
Rubber Pad
YZG/AZ-00-19
1
Outer compound protector
BF225-JB
1
Electric Wiring Diagram
Accessories Installation Diagram
5. The Period of Validity