Eaton Power Distribution Rack PowerChain Management solutions
Features• Flexiblepowerdistributionwithupto168factory-installedbranch
breakersinahighlycompactfootprint
• Designedforhigh-densityracks,with400Apanelsandhigh powerinputs
• Aestheticallypleasingdesign,withanelegantrackenclosureintexturedblackfinish
• Free-standingunitwithtopandbottomcableentryforfast, flexibleinstallation
• Frontand/orrearaccess,columnpowerpanels,largeLCDfor easeofservicing
• Extensivemonitoringoptions,includingtheEaton®EnergyManagementSystem
• Optionalbranchcircuitmonitoringtomanageandmonitorpowerdowntoindividualcircuits
• Detailedeventandtrendinformationtosupportcapacityplanningandavoidunexpectedbreakertripping
• Factory-configuredandtestedtoensurehighestreliability
Flexible,high-densitypowerdistributionforrackenvironments
Product snapshot
Up to 168 circuits in a single enclosure
Four 400A (225A) circuit panels (two front and two rear)
EIA standard enclosure
Eaton Energy Management System (EMS)
Main lug or main breaker configuration
Areyoulookingforaspace-savingwaytodistributepowerthroughoutyourdatacenter?Aredual-andtriple-cordedloadsstressingyouravailablesupplyofpolepositions?Doyouwanttominimizerelianceonlicensedelectriciansasyoumakemoves,addsandchanges?Wouldyouliketoresolvetheseissueswithoutinstallingclunkypowerdistributionequipmentinyoursleek,modernrackline-up?
Iftheanswertotheseques-tionsisyes,Eatonhasthesolu-tionforyouwiththenewEaton Power Distribution Rack (PDR).ThePDRwasdesignedfortherealitiesofmoderndatacenters—floorspaceiscostly,changeisinevitable,anduptimeiscritical.
ThePDRwasalsodesignedforamoreintangiblereality:aesthetics.Theuniform,elegantlookofyourdatacentercon-veysanimpressionoforderandprofessionalism.Newequipmentacquisitionsshouldenhancethatappearance,notclutterordetractfromit.
Big power in a small footprint with a sleek lookThePDRoffersupto168cir-cuitsinanelegant,texturedblackenclosurethatharmonizeswiththerestofyourdatacenterline-up.
Forflexiblepowerdistribution,placethePDRinthemiddleofaroworattheendoftherow.Eitherway,youwillminimizecablerunsandusefloorspacewisely.Traditionalpowerpan-elswereacompromiseinthisregard.Notmatchingthedepthoftherestoftheenclosures,theyleftvaluablefloorspaceidle.
Nowyoucanaccommodateallthosenewserverswiththeirmultiplepowercords…allthoserackpowerdistributionunitsthatfeedgrowingloads…simplybyusingahigh-densityPDRthatstandsonminimalfloorspaceandenhancestheelegance,practicalityandreliabilityofyourdatacenter.
2 EATON CORPORATION Eaton Power Distribution Rack
Designed for the adaptable data centerMeet ever-increasing power demands.Someotherrackpowerpanelsonthemarketaredesignedwithmorecircuitsthanthemainbreakercanaccommodate:42polepositionsonapanelratedfor225A.Inthisconfiguration,someofthecircuitsareuseless—orifusedtocapacity,couldeasilytripthemainbreakerandjeopar-dizeyourcriticalload.
ThePDRusesoptionalhigher-capacity400Apanels,soyoucanmakefulluseofallcircuits.Theunitcanbeconfiguredwithonetofourofthesepowerpanels.Branchcircuitsarearrangedinacolumnforsuperiorwiringdesign.Spaciouswirewaysoffermoreroomtoworkforfastandeasyinstallationorchanges.Alargeairspacebeneaththepowerpanelspermitsimprovedaircirculationandmakesiteasyfortechnicianstomanagecabling.
Straightforward installation.ThestandalonePDRisfullyconfig-uredandtestedatthefactory,soinstallationissimple.Withyourchoiceoftoporbottomcableentry—aswellasfrontand/orrearpowerpanels—itiseasytoretrofitintoanyexistingdistribution system.
Flexible design.Mostotherrackpowerpanelshavetobeconfig-uredforeithertoporbottomcableentryatthefactory—andsomedon’toffertopcableentryatall.ThePDRcanbeconfiguredforeitheroption,makingitappropriateforraised-floorornon-raised-floorapplications.
Monitoring for premium availabilityContinuous insight into power conditions.PDRsareequippedwiththeEMS.Withthisstate-of-the-artmonitoringandalarm system,youcan:
• Monitorpowerconsumptionandensurepowerquality.
• Manageandplanpowerneedsindynamicenvironments.
• Reactquicklytopotentialproblemsdowntothebranchcircuitlevel.
OptionalbranchcircuitmonitoringwithintheEMScontinuouslymeasuresthecurrentonbranchcircuitsandwarnsofimpendingtrouble,soyoucantakeproactivesteps.Thesystemassessescir-cuitactivity7x24andprovidestime-stampedmetering,alarmandstatisticalinformationforeachbranchcircuit.
Armedwiththeseinsights,datacenterandfacilitiesmanagerscanmoreeffectivelymanageenergyconsumptiontopreventoverloadconditions,optimizepowerdistributionand,whereapplicable,accuratelybillinternalcustomersforpowerusage.
Monitoring and management from anywhere.WiththeoptionalPowerXpert®Gateway1000interfacecard,thePDRcansecurelytransmitreal-timestatustoremotemonitoringstations,admin-istratorPCsorwirelessdevicesanywherewithinthereachofanetworkconnection.Remotepersonnelcanconfigure,monitorandmanagethesystemfromanywhereoverthecompanynetworkorthe Internet.
Panelboard breakers can be the tradition-al 225A or 400A.
400A breakers enable you to make full use of all 42 pole positions on a panelboard.
Top and bottom cable entry opens up many choices for installation.
Monitor and manage the PDR over the network with the optional Power Xpert Gateway 1000 card.
Design for quality, security and convenience• Freestandingstructurewithtopandbottomcableentry
opensupmanychoicesforinstallation.
• Industry-standardfootprintmakeseffectiveuseofvaluabledatacenterspace.
• Attractive,texturedblackfinishmatchesyourequipmentandprovidesamodernlook.
• Spaciouswireways,hingeddoorsandremovablesidepan-elsenableeasyserviceaccess.
• Lockingdoorlatchesprotectthepowerdistributionsystemfromunauthorizedaccess.
• OptionalPlexiglascoverpanelsprovideeasyvisibilityto breakers.
• X-Slotbayssupportmanycommunicationoptionsforremotemonitoringandmanagement.
• Large,brightLCDwitheasy-to-usemenusupportslocalmoni-toringandconfiguration.
• Loadprofilelogshowspowerconsumptiontrendsforupto24months;historylogshowsupto128time-anddate-stampedevents.
3 www.eaton.com/powerquality 1.800.356.5794
Current and historical insights close at hand.Locally, technicianshaveanat-a-glanceviewofsystemstatusonalarge,8-linex40-characterLCD.Unitswithfrontandrearpanelshave twodisplays.
Amenuwithsoftkeysmakesiteasytonavigatethroughthefea-tures.Audio/visualindicatorsprovidealarmsandstatusupdates.Throughthislocaldisplay,youcanviewpowerconsumptiontrendsinahistorylogforupto24months—apowerfulaidincapacityplanning.Customalarmsettingscanbeprogrammedatthefactory,bytheuserorbyEaton’sserviceorganization.
Optional surge suppressionEvenwithintherelativesafetyofyourdatacenter,powersystems(andtheequipmentconnectedtothem)couldbeaffectedbylightningstrikesandothertransientaberrationsinvoltageandcur-rent.Forexample,atransienteventcouldtriggeraUPStoactivateitsstaticbypasspath,leavingcriticalloadsexposedtorawutilitypower.
IfthefacilitydoesnothaveTVSSdevicesattheutilitypointofentry,orifTierIVredundancyisrequired,consideraddingittoyourPDRforanimportantlayerofextraprotection.
Part of a complete data center solutionThePDRispartofafamilyofsolutionsthatareredefiningtheeco-nomicsofrunningthemoderndatacenter.Inadditiontofreestand-ing,wall-mountedandrack-mountedpowerdistributionsystems…
• Energy-efficientUPSsandPDUsdelivermorepowerinless rackspace.
• PatentedparallelingprovidesTierIVredundancy.
• AdvancedbatterytechnologieskeepITsystemsupwhenutilitypowerisdown.
• Rugged,attractiveenclosureshouse,protectandorganizeITandpowerqualitysystems.
• Powermonitoringoptionsgivefullvisibilityintothehealthofthesystem,fromindividualcircuitstotheentirefacility.
Eatondatacentersolutionsenableyoutocreateamoreresilientandadaptabledatacenter—onethatuseslessenergy,runsmoreefficiently,andprotectsyourinvestmentsinapplications,dataandhardware.Findoutmoreatwww.eaton.com/powerquality
A new level of confidenceEatonisagloballeaderinpowerqualityandmanagement solutions—namedbyFrost&Sullivanas“PowerQualityCompanyoftheYear”in2004,2005and2007(August2007).Ourruggedpowerdistributionunitsreflectmorethan40yearsofexpertiseinindustrial-strengthpowerqualitysolutions.Infact,wehavebeenmanufacturingPDUsforseveralothermajorbrandsforyears.
ThePDRdeliversconfidence—confidencethatthepower circuitsservingyourbladeserversandotheressentialequipment areappropriatelyloadedandcapableofsupportingthehigh availabilityyoudemand.Formoreinformation,visitourWebsiteat www.eaton.com/powerquality,orcontactusat1-800-356-5794.
X-Slot® bays support many communication options for remote monitoring and management.
A large, bright LCD with easy-to-use menu supports local monitoring and con-figuration.
The load profile log shows power consumption trends for up to 24 months.
The history log shows up to 128 time- and date-stamped events.
Technical specifications Electrical input
Nominalvoltage 208Y/120VacNominal 50/60Hz(45–65Hz) frequency(range)Inputconductor Three-wire+neutral+ground configuration Input connection options
Directconnectiontopanelboardmainbreakers(225A,400A)Connectionintosingleordualmainlugs(800A)Connectionintosingleordualmainbreakers(400A,600A)—sideaccessrequired Connectivity
OptionalPowerXpertGateway1000communicationscardBuilt-inWebandSMTPserverSupportforModbusTCP,SNMPandNTPprotocolsTwo(2)isolatedRJ-45Ethernetportsforredundancy Monitoring
Standardsystem-levelmonitoringNon-volatilereal-timeclock
Meters and load profiling points: Input1V12min/max Input1V23min/max Input1V31min/max Input1ACUVtotaltime Input1I1min/max(with optionalMainCTsinstalled) Input1I2min/max(with optionalMainCTsinstalled) Input1I3min/max(with optionalMainCTsinstalled) Input1V12THDmax Input1V23THDmax Input1V31THDmax Input1frequencymin/max Input1kVAmin/max(with optionalMainCTsinstalled) Input1powerfactormin/max(with optionalMainCTsinstalled) Input2V12min/max Input2V23min/max Input2V31min/max Input2ACUVtotaltime Input2I1min/max(with optionalMainCTsinstalled) Input2I2min/max(with optionalMainCTsinstalled) Input2I3min/max(with optionalMainCTsinstalled) Input2V12THDmax Input2V23THDmax Input2V31THDmax Input2frequencymin/max Input2kVAmin/max(with optionalMainCTsinstalled) Input2powerfactormin/max(with optionalMainCTsinstalled) GNDImin/max NEUImin/max
PowerXpertGateway1000Cardfirmwareisuser-upgradeable
Premium Eaton Branch Circuit Monitoring System (BCMS)
Individual panel monitoring
Configurable parameters: Panelnumber Panel name Nominalinputvoltage Nominalinputfrequency SystemkVA CTspresent L-LorL-Ninputsetting Main CT ratios Calibrationofinput,output, groundandneutralCTs Calibrationofvoltage Breakerrating Breakerwarninglevel Breakertype
Main panel board metering alarms Panelorsubfeedbreakeroverloadwarning Panelorsubfeedbreakeroverloadalarm Panelbreakeroverloadwarning Panelbreakeroverloadalarm Breakercurrentwarning Breakercurrentoverload
Branch circuit or subfeed breaker monitoring—up to 42 per panel (User can easily add panel breakers)
Configurable parameters —individual branch circuits Breakerrating Breakerwarninglevel Breakeroverloadlevel Breakertype
Individual branch circuit alarms (for each breaker): Breakercurrentwarning Breakercurrentoverload Distribution panelboards
42-circuitcolumn–ratedfor225A–maximumtwo(2)perside42-circuitcolumn–ratedfor400A–maximumtwo(2)perside Options
Transientvoltagesurgesuppression(TVSS)50kA/phor100kA/phIsolatedgroundBranchcircuitmonitoringPlexiglasormeshdoors Environmental and safety
Operating 0ºCto40ºC(32ºFto104ºF) temperatureRelativehumidity 5–95percentnon-condensingAudiblenoise <45dBAmeasured1.5m(5ft.)fromunitunder normaloperatingconditionsEMI FCC47,part15forClassAdevicesAgencymarking Domestic/Canadianmodels:UL/CSA60950-1 Physical characteristics
DimensionsHxWxD,in(mm)78.5x23.5x38(1994x597x965)ApproximateProductWeight,lb(kg) Oneside450(200) Twosides700(315)
Event logging: Input1ACovervoltage Input1ACundervoltage Input1underoroverfrequency Input2ACovervoltage Input2ACundervoltage Input2underoroverfrequency Buildingalarm1 Buildingalarm2 Buildingalarm3 Buildingalarm4 Input1overload(4levelsper phase,withoptionalMainCTs installed) Input2overload(4levelsper phase,withoptionalMainCTs installed) Input1phaserotationerror Input2phaserotationerror Configurationerror Alarm,highinput1THD (per-phasealarm),currentor voltage Alarm,highinput2THD (per-phasealarm),current orvoltage Alarm,neutraloverloadwarning (perpanel) Neutraloverload(perpanel) Groundcurrentwarning(perpanel) Groundcurrentoverload (perpanel)
Monitored parameters: RMS:V1,V2,V3,I1,I2,I3 Average:Vavg,kW,kVA,PF Load:MonthlykWh,yearlykWh, totalkWh Percentage:Input1,Input2, Input3,Inputtotal(percentload) Max:Vmax,Imax
Eaton, Flex, LanSafe, PowerChain Management and PowerTrust are trade names, trademarks, and/or service marks of Eaton Corporation or its subsidiaries and affiliates. All other trademarks are the property of their respective owners.
Monitored parameters Current:RMSandpercentage Average:kW,kVA,PF Load:MonthlykWh,yearlykWh, totalkWh Max:Amperage,kW Min:Powerfactor
UNITED STATES 8609 Six Forks Road Raleigh, NC 27615 U.S.A. Toll Free: 1.800.356.5794 www.eaton.com/powerquality
CANADAOntario: 416.798.0112 Toll free: 1.800.461.9166
LATIN AMERICASouth Cone: 54.11.4124.4000 Brazil: 55.11.3616.8500Andean & Caribbean: 1.949.452.9610Mexico & Central America: 52.55.9000.5252
EUROPE/MIDDLE EAST/AFRICADenmark: 45.3686.7910 Finland: 358.94.52.661 France: 33.1.6012.7400 Germany: 49.0.7841.604.0 Italy: 39.02.66.04.05.40 Norway: 47.23.03.65.50Portugal: 55.11.3616.8500 Sweden: 46.8.598.940.00 United Kingdom: 44.1753.608.700
ASIA PACIFICAustralia: 61.2.9693.9366New Zealand: 64.0.3.343.3314China: 86.21.6361.5599HK/Korea/Taiwan: 852.2745.6682India: 91.11.4223.2300Singapore/SEA: 65.6825.1668
©2010 Eaton CorporationAll Rights ReservedPrinted in USAPDRFXAJanuary 2010
Top Related