Download - Power Supply Board Information & Wiring Diagram · Extension Board or I/O Controller C+ C-Extension Board or I/O Controller C+ C- ... Board Information & Wiring Diagram Door Relay

Transcript
Page 1: Power Supply Board Information & Wiring Diagram · Extension Board or I/O Controller C+ C-Extension Board or I/O Controller C+ C- ... Board Information & Wiring Diagram Door Relay

MUD-SNet-UM-PC-003REG No. 749921389

LED Diagnostic

CASE

Before ApplicationExecute

HardwareInitialization

Memory ErrorDetected

Firmware Checking /Status Update

Erase Firmware

Erase Error Detected

Update Firmware

Update ErrorDetected

Verify Firmware

Verify Error Detected

Loading Application

No ApplicationDetected

Normal Operation

Normal Operation(Busy)

Remote Firmware Update

LEDRED GREEN YELLOW BLUEOff

Off

On

Off

Off

On

Off

On

Off

On

Off

Off

Off

On

Off

Continuesblinking

Off

Off

Continuesblinking

Off

Continuesblinking

Off

Continuesblinking

On

Continuesblinking

Continuesblinking(slowly)

On

Off

Continuesblinking

On

On

Blink x 1(3 sec. interval)

Continuesblinking

Blink x 2(3 sec. interval)

Off

Blink x 3(3 sec. interval)

Off

-

-

On

Off

-

Off

On

-

Off

-

Continuesblinking

-

On

Continuesblinking

(1 sec. interval)

Continuesblinking

(1 sec. interval)

Blue, Yellow, Green, and Red blink sequentially

CASE

Memory ErrorDetected

Erase ErrorDetected

Update ErrorDetected

Verify ErrorDetected

No ApplicationDetected

No ServerConnection

Fire Alarm Trigger

Setup Mode

Web Diagnostic On

Door Forced Open,Door Left Open,Tamper Triggered,Main Power Fail

On

On

On

On

Off

Continuesblinking

Error

LEDRED GREEN YELLOW BLUE

Continuesblinking

Continuesblinking

Continuesblinking

Continuesblinking

Off

Continuesblinking

Continuesblinking

Blink x 1(3 sec. interval)

Blink x 2(3 sec. interval)

Blink x 3(3 sec. interval)

Off

-

-

-

-

-

Continuesblinking

(1 sec. interval)

Continuesblinking

(1 sec. interval)

Blue, Yellow, Green, and Red blink sequentially

Please refer to UPLINK STAT LED

Buzzer beeps every 10 secs.

Buzzer beeps once

Controller Web Diagnostic

Connect network cable to RJ45 socket.Note: SNet controller supports both directand crossover cables.

Pre-Configuration

SNet’s default setting after ColdStart:Host IP = 192.168.1.200Ethernet IP = 192.168.1.210

ColdStart2

Open Internet Explorer browser > Typehttp://192.168.1.210 in the address box >Key in 'admin' for username > Key in'password10' for password.

Login to Controller WebDiagnostic3

Click System Info > Monitor system status(Server Status, Main Power Status,Tamper Status, Fire Alarm Status,Controller ID, DIPS Setting (HEX), RS485Reader Status)

Monitoring System Status4

Click Device Info > Confirm Date Time,Device Version, Description, Internal ID,Date Time Released, Date Time Loaded,Boot Loader Version & Board Serial No.

Checking Device Info6

Click Configuration > Enter new username> Enter new password > Retype newpassword > Click Confirm Change Password .

Changing Login Details7

Click Configuration > Click Confirm Reset .

Resetting Controller8

Click Log Out > Log Out message will be displayed.

Log Out from Web Diagnostic9

*Note:After changing Ethernet IP, the Web Diagnostic of the controller will only accessible through the newcustomised Ethernet IP.

Click Network Setting > Refer to the table below for detailed descriptions > Perform neccessary changes> Click Save Setting .

Configuring Network Setting5

FIELD DESCRIPTION

Host IP

Ethernet IP

Ethernet Subnet

Ethernet Gateway

Ethernet Pri DNS

Ethernet Sec DNS

MAC Address

Enhanced NetworkEncryption (AES 128)

IP address of server PC Default: 192.168.1.200

IP address of controller Default: 192.168.1.210

Subnet mask of the controller network setting Default: 255.255.255.0

Gateway of the controller network setting Default: 192.168.1.1

Primary DNS setting

Secondary DNS setting

MAC address of controller

Network encryption setting of controller Note: In order to use AES 128, please ensure that this is available in the application.

Reader (RS485)OR Reader

Interface Unit

RS485 Uplink

C+

C-

C+

C-

Multi-PurposeRelay Outputs

CO

N37

D3+

D3-

+12V (O

UTP

UT O

NLY

)

LAN

CO

N21

Buzzer

C+

C-Extension Boardor I/O Controller

C+

C-Extension Boardor I/O Controller

C+

C-Extension Boardor I/O Controller

DC Input Terminal

RS485 COM PortInterfaces

External WatchdogTimer Jumper(Always shorted)

Bootloader Jumper(Always opened)

JTAG Interface Control Signal Jumper(Always opened)

Output Power Terminal for ExternalBoard (e.g.: Extension Board, I/OController, RS485 Uplink, ReaderInterface Unit, RS485 Reader)

Note:3A Fuse Protection for CON53 &CON54

Battery:To supply power toSRAM and RTC

CPU boardpower status LED

RJ45 Socket:10 Base-T / 100 Base-TXEthernet Network Interface

Fire Alarm Input(Normally closed)

Tamper Input(Normally closed)

- +

CO

N18

ADDRESS SETTINGS

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

00 01 02 03 04 05 06 07

08 09 10 11 12 13 14 15

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

CONTROLLER SETTINGS

SETTINGController Type

Internal Door I/OMonitoring Function

Internal I/O Configuration

RS485 Uplink Baud Rate

ONLift Controller

(Max. 128 relay output points)

Enable

Configurable I/O(via xPortal)

19200 bps(Please confirm that the RS485

Uplink used supports this baud rate)

OFFDoor Controller

(Max. 10 alarm boards)

Disable(All internal I/O usedfor alarm function)

Fixed Door I/O

9600 bps

1

2

3

4

ReaderConnector 1-5ABA / Wiegand

Reader12V0V

CLK / Data 0Data / Data 1

LED 1LED 2Buzzer

RS232 / RS485 SELECTORJUMPER SETTING

Short 1 & 2RS232 port

Short 2 & 3RS485 port

RS485J26/J28J25/J27

RS232J27 J28

321

321

SNET

Board Information & Wiring Diagram

Door RelayOutput 1-5

(If set to FixedDoor I/O)

Multi-PurposeInputs

CO

N51

+-

CO

N52

+-

CO

N53

+-

CO

N54

+-

+12V (M

AX

3A)

DOWNLINK

CO

N36

D3+

D3-

CO

N35

D3+

D3-

CO

N34

D2+

D2-

CO

N33

D1+

D1-

CO

N32

D0+

D0-

UP

LINK

PC

+P

C-

COLDSTARTRUN STAT CPU

M1 M2 M3

ERR

M0SW1

RELAY / DRY CONTACT OUTPUT SELECTION

J1

123

J2

123

RE

LAY 1

LEFT JUMPERS: J1, J3, J5, J7, J9, J11, J13, J15

Short 1 & 2: Short 2 & 3:Use as dry contact Use as relay output

RIGHT JUMPERS: J2, J4, J6, J8, J10, J12, J14, J16

Short 1 & 2: Short 2 & 3:Use as NO (Normally Opened) Use as NC (Normally Closed)

RS485 INTERFACES CAPACITY

Extension Board & I/O Controllera) Door (5 Doors)SNet-E5D

b) Lift (Max. 128 Outputs)SNet-E32Rc) Alarm (Max. 10 Boards)SNet-E32R, SNet-E32S, SNet-E248SMiO-L32, MiO-S168, MiO-R16

Reader Interface UnitMK800 / MK801

Reader (RS485)MicroEngine Readers

Note: SNet supports total of 10 units of readerinterfaces together with RS485 readers.

RELAY OUTPUT CONNECTOR INFO

12VDC

GND

12V+G

ND

NO

/NC

CO

M

NO / NC

COM

12V+G

ND

NO

/NC

CO

M

WET OUTPUT DRY CONTACT OUTPUT

TYPICAL DOOR I/O

DoorSensor

PushButton

S1+ S1-DS1

S2+PB1

0V

EM Lock

EBG

COMNO NC

12V

12V+

GNDNO/NCCOM S2-

Power Supply

ON

1 2 3 4

ADDRESS

ON

1 2 3 4

SETTING

J16J15

Relay 1(Door 1)

Relay 2(Door 2)

Relay 3(Door 3)

Relay 4(Door 4)

Relay 5(Door 5)

Relay 6

Relay 7

Relay 8

CON31

C+

C-Reader (RS485)RS485

RS232

J27

J28

CO

M1

RS485

RS232

J25

J26

CO

M0

COM SEL

CO

N38

TXRX

GNDCOM0

RS232

RS232COM PortInterfaces

RS232 /RS485

SelectorJumper

J30

J31

J32

J33

PROG

WDT

DIAG

TEST

UPLINK STAT

UPLINK STATUSServer PC not foundServer PC foundConnected to xPortal

OffBlinkOn

Test ModeJumper

WDT Disabled(Always opened)

*BLOAD(Always opened)

RESET

SW4

RESET:Press the button toreset the controller

12V G

ND

+ NO

/NC

CO

M12V

GN

D + N

O/N

C C

OM

12V G

ND

+ NO

/NC

CO

M12V

GN

D + N

O/N

C C

OM

12V G

ND

+ NO

/NC

CO

M12V

GN

D + N

O/N

C C

OM

12V G

ND

+ NO

/NC

CO

M12V

GN

D + N

O/N

C C

OM

CO

N22

CO

N23

CO

N24

CO

N25

CO

N26

CO

N27

CO

N28

J14J13

J12J11

J10J9

J8J7

J6J5

J4J3

J2J1

RE

LAY8

RE

LAY1

RE

LAY2

RE

LAY3

RE

LAY4

RE

LAY5

RE

LAY6

RE

LAY7

COLDSTART1. Press & hold COLDSTART button2. Press & release RESET button3. Wait for STAT & CPU LED light up together4. Release COLDSTART button

DIAGNOSTIC MODE1. Short Diagnostic jumper (J32) Network setting temporary reset to default2. Remove Diagnostic Jumper (J32) when finish network setup

CO

N50

12V

GN

D

MA

IN

POWER BATTSTAT

Power status LED

Battery status LED

LEFT RIGHT

WEB DIAGNOSTIC JUMPER SETTINGWeb Diagnostic On : All IP setup and web login willtemporarily reset to default

Short

Web Diagnostic Off: Return to normal operationOpen

Buzzer will be beepingevery 10 secs.

RESET

SW

1

RESET:Press the button toreset the controller

BLO

AD

J1E-W

DT

J2

RTC

KJ4

PW

RC

PU

VPPGND

D0D1L1L2

BUZ

READER 1

VPPGND

D0D1L1L2

BUZ

READER 2

VPPGND

D0D1L1L2

BUZ

READER 3

VPPGND

D0D1L1L2

BUZ

READER 4

VPPGND

D0D1L1L2

BUZ

READER 5

Door Sensor &Push Button 1-5(If set to FixedDoor I/O)

Input 1DoorSensor 1

CON1S1- S

1+

Input 2PushButton 1

CON2S2- S

2+

Input 3DoorSensor 2

CON3S3- S

3+

Input 4PushButton 2

CON4S4- S

4+

Input 5DoorSensor 3

CON5S5- S

5+

Input 6PushButton 3

CON6S6- S

6+

Input 7DoorSensor 4

CON7S7- S

7+

Input 8PushButton 4

CON8S8- S

8+

Input 9DoorSensor 5

CON9S9- S

9+

Input 10PushButton 5

CON10S10- S

10+

Input 11CON11S

11- S11+

Input 12CON12S

12- S12+

Input 13CON13S

13- S13+

Input 14CON14S

14- S14+

Input 15CON15S

15- S15+

Input 16CON16S

16- S16+

CON17

-FIRE

+

FIRE ALARM

TAMPER

CONFIGURATION OF CONNECTION TO READER

CON32 Plato / Plato KL (Door 0 to 4, Entry & Exit)Plato / Plato KL (Door 5 to 9, Entry & Exit)ORMK800 / MK801 (Door 0 to 9)

Plato / Plato KL (Lift 0 to 9, Entry)Plato / Plato KL (Lift 0 to 9, Exit)ORMK800 / MK801 (Lift 0 to 9)

CON33

DOOR CONTROLLER LIFT CONTROLLER

L N COM BAT COM V V(ADJ)(AC)

AC Input BackupBattery

DC OutputMain FailSignal

+ +- -