Asset: P.S. 147 - QUEENS, 218-01 116 AVENUE, New York, 11411
Inspection Id Inspection Type Time In Last Edited
SA : Q147 Architectural - Senior 2018-10-25 7:47 AM 2019-06-05 5:36 PM
AA : Q147 Architectural - Associate 2018-10-25 8:52 AM 2018-10-25 3:51 PM
Asset Data
Question Answer
Was the building fully accessible for inspection No
Inspection Access Comment No keys were available for the 3rd Floor Locker Room Shower at thetime of inspection.
Principal(s) Information
Principal Name Afua Hill
Organization P.S. 147 - Queens
Did you meet with this Principal? No
Did this Principal provide feedback? Yes
Summary of Principal's Feedback A Principal questionnaire form was returned with the followingcomments: 1. The building main entrance lighting is not working dueto a power issue. This needs to be repaired since the front of thebuilding is very dark. 2. Exterior Doors need to be replaced. Due toweather changes they swell up and cannot be readily opened.
Custodian Charles Saccoccio
Fireman Scott Sather
Building Square Footage 80000
Comments on the Area None
Comments on the Stories (Floors) plus Basements 3 + B
Comments on the Number of Classrooms 41
Comments on the Year Built 1930
Student Population 601
Staff Population 64
Weather Fair
Facade Photo
116th Avenue - East view
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 1 of 50
Main Entrance Photo
Facade A - 116th Avenue
Roof Photo
Roof 3 - Southwest view
Have any Systems/Major Building Components been upgraded? Yes
Systems: New Ash Hoist Doors
Year: 2014
Systems: New Roof Drains, Areaway Doors/Structure, CafeteriaExit Doors, Basement Foundation Waterproofing.
Year: 2013
Systems: Partial Areaway Grating replacement, Areaway curbrepairs.
Year: 2011
Systems: New Science Lab
Year: 2009
Systems: Chimney, Bulkhead and Parapet repairs, Partial Facaderepointing
Year: 2007
Systems: New Windows, Exterior Guards refurbished.
Year: 2000
Systems: New Roofing and Flashing
Year: 1997
Have there been any New Building Additions? Yes
Comments on New Building Additions 1942 (+25,000 SF)
Tandem Schools? No
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 2 of 50
Leased Space? No
Priority Condition
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No Potential FallingDebris
Leaning Fenceis a potentialsafety hazard
SITE | FENCES 218th Street CharlesSaccoccio
Custodian
No ProtrudingElements
Protruding metalwith sharp edgeis a potentialsafety hazard.
INTERIOR |AUDITORIUM| Fixed Seating
Seats F/3,G/101, I/4, J/3
CharlesSaccoccio
Custodian
No ProtrudingElements
Severely Bentedsteel curb is apotential safetyhazard
SITE | PAVING| DOT Sidewalk| Concrete
116th Avenue CharlesSaccoccio
Custodian
Yes Tripping Hazard Severelydamaged Flooris a potentialtripping hazard
INTERIOR |CLASSROOMS/CORRIDORS/ADMINSPACES | FloorFinish
Room 324 CharlesSaccoccio
Custodian
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? No
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits No Saddle height > 1/2"
Exterior H/C Lifts No No
Exterior Ramps and Railings No Yes
Interior Routes
Corridor and Lobby H/C Lifts No Yes
Interior Corridor Doors and Hardware Yes Yes
Interior Corridors and Lobbies No Change in Elevation
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 3 of 50
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
Interior Routes
Interior Elevators No
Interior Lobby Doors and Hardware Yes
Interior Ramps No
Rooms & Spaces
Art Rooms No
Auditorium 1st Floor Yes No No Stage AccessNot on Accessible Route
Yes No
Cafeteria Basement Yes No Not on Accessible Route Yes No
Classrooms None on Accessible Route Yes No Not on Accessible Route
Computer Rooms No
Gymnasium 3rd Floor Yes No Not on Accessible Route Yes No
Library Room 222 Yes No Not on Accessible Route
Main Office Room 201 Yes No Not on Accessible Route
Multi-purpose Room 1st Floor Yes No Not on Accessible Route Yes No
Nurse's Room Room 263 Yes No Not on Accessible Route
Pool No
Science Lab Room 324 Yes No Not on Accessible Route
Toilet Rooms (Boys) None on Accessible Route Yes No Not on Accessible Route
Toilet Rooms (Girls) None on Accessible Route Yes No Not on Accessible Route
Toilet Rooms (Staff) None on Accessible Route Yes No Not on Accessible Route
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Inspected
InspectedInstance on AW1 - AW18
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 4 of 50
Question Response
EXTERIOR
AREAWAY
Instance Condition 4 - Between Fair and Poor
Instance Quantity 18
Instance Quantity Uom EACH
Deficiency AREAWAY STAIRS: DETERIORATEDTREADS/RISERS/NOSINGS
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
AW9
Violations No violations recorded.
Deficiency AREAWAY GRATINGS: MAJOR RUSTING AND / OR BROKENSUPPORTS
Roof Plan reference
Deficiency Quantity 40
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 5 of 50
Question Response
EXTERIOR
AREAWAY
Deficiency Photo1
AW12
Violations No violations recorded.
Deficiency AREAWAY WALLS: CRACKS AND SPALLING
Roof Plan reference
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
AW16
Violations No violations recorded.
AWNINGS AND CANOPIES Does not Exist
CHIMNEY Inspected
Material Type(s) Masonry
Condition 4 - Between Fair and Poor
Deficiency BRICK: OPEN JOINTS
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 6 of 50
Question Response
EXTERIOR
CHIMNEY
Roof Plan reference
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1
Violations No violations recorded.
COPING Inspected
Condition 3 - Fair
Deficiency CAST STONE: OPEN TRANSVERSE JOINTS WITH DAMAGEDCAULKING
Roof Plan reference
Deficiency Quantity 50
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 7 of 50
Question Response
EXTERIOR
COPING
Deficiency Photo1
Facade H
Violations No violations recorded.
Deficiency CAST STONE: CRACKED/BROKEN PIECES
Roof Plan reference
Deficiency Quantity 30
Quantity Uom L.F.
Potential Action REPLACE-IN-KIND
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
CORNICE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 5 - Poor
Deficiency METAL CLAD: DETERIORATED DOOR AND FRAME - MAJORDETERIORATION
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 8 of 50
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Roof Plan reference
Deficiency Quantity 8
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade C
Violations No violations recorded.
DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency STEEL: MAJOR RUSTING
Roof Plan reference
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 9 of 50
Question Response
EXTERIOR
DOORS
LINTELS
Deficiency Photo1
Facade E
Violations No violations recorded.
TRANSOM/SIDE LIGHT Does not Exist
EXTERIOR WALLS Inspected
Material Type(s) Masonry
Replacement Quantity 14,000
Replacement Uom S.F.
InspectedInstance on All Facades
Instance Condition 3 - Fair
Instance Quantity 14,000
Instance Quantity Uom S.F.
Deficiency STONE: CHIPPED/SPALLED/BROKEN PIECES
Roof Plan reference
Elevation
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 10 of 50
Question Response
EXTERIOR
EXTERIOR WALLS
Deficiency Photo1
Facade H
Violations No violations recorded.
Deficiency BRICK: WATER INFILTRATION IN INSTRUCTIONAL SPACE
Roof Plan reference
Elevation
Deficiency Quantity 150
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B - Room 127 shown, Facade D - Room 126, Cafeteriasimilar
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 11 of 50
Question Response
EXTERIOR
EXTERIOR WALLS
Deficiency BRICK: OPEN JOINTS
Roof Plan reference
Elevation
Deficiency Quantity 3,000
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade F
Violations No violations recorded.
EXTERIOR SOFFITS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOADING DOCK Does not Exist
LOUVER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
PARAPETS Inspected
Material Type(s) Masonry
Replacement Quantity 8,600
Replacement Uom C.F.
InspectedInstance on All Facades
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 12 of 50
Question Response
EXTERIOR
PARAPETS
Instance Condition 3 - Fair
Instance Quantity 8,600
Instance Quantity Uom C.F.
Deficiency BRICK: OPEN JOINTS
Roof Plan reference
Deficiency Quantity 500
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade F
Violations No violations recorded.
PLAZA DECK Does not Exist
ROOF Inspected
Roofing Inspected
Replacement Quantity 25,400
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Inspected
Condition 5 - Poor
Deficiency DETERIORATED
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 13 of 50
Question Response
EXTERIOR
ROOF
Roofing
ROOF HATCH/SMOKE HATCH
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1
Violations No violations recorded.
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF BARRIER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF CAGE Does not Exist
ROOF FENCE Does not Exist
ROOFING Inspected
InspectedInstance on Built-Up: All Roofs
Instance Condition 3 - Fair
Instance Quantity 25,400
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 1997
Source of Installation Documented
Deficiency BUILT-UP: FLASHING: BASE FLASHING DETERIORATED
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 14 of 50
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Potential Action REMOVE AND REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 3 - Facade G
Violations No violations recorded.
Deficiency BUILT-UP: ROOFING: BEYOND USEFUL LIFE
Deficiency Location/Instance Built-Up: All Roofs
Deficiency Quantity 25,400
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 1
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
ROOFING DRAINS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Specialties Inspected
BULKHEAD/PENTHOUSE Inspected
Condition 4 - Between Fair and Poor
Deficiency BULKHEAD/PENTHOUSE WINDOWS: DAMAGED,DETERIORATED WINDOWS
Roof Plan reference
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 15 of 50
Question Response
EXTERIOR
ROOF
Specialties
BULKHEAD/PENTHOUSE
Deficiency Photo1
BH2
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE WALLS/EXTERIOR: OPEN JOINTS
Roof Plan reference
Deficiency Quantity 300
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
BH2
Violations No violations recorded.
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Does not Exist
DUNNAGE STEEL Does not Exist
SKYLIGHT/ROOF VENT Inspected
Material Type(s) Other
Condition 2 - Between Good and Fair
Deficiency DAMAGED FLASHING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 16 of 50
Question Response
EXTERIOR
ROOF
Specialties
SKYLIGHT/ROOF VENT
Roof Plan reference
Deficiency Quantity 5
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1
Violations No violations recorded.
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
RAILINGS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
STAIRS/RAMPS Inspected
Condition 3 - Fair
Deficiency STONE: OPEN JOINTS
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 17 of 50
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Deficiency Quantity 50
Quantity Uom L.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
WINDOWS Inspected
Replacement Quantity 14,030
Replacement Uom S.F.
EXTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency STEEL: MAJOR RUSTING
Roof Plan reference
Elevation
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 18 of 50
Question Response
EXTERIOR
WINDOWS
LINTELS
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
Violations No violations recorded.
WINDOWS Inspected
Material Type(s) Aluminum, Solid Wood
InspectedInstance on Aluminum - Double Hung: All Facades
Instance Condition 3 - Fair
Instance Quantity 14,000
Instance Quantity Uom S.F.
Installation Year 2000
Source of Installation Documented
Deficiency No deficiencies recorded
InspectedInstance on Wood: Facade B - AW1
Instance Condition 5 - Poor
Instance Quantity 30
Instance Quantity Uom S.F.
Installation Year 1942
Source of Installation Documented
Deficiency WOOD: DETERIORATED
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 19 of 50
Question Response
EXTERIOR
WINDOWS
WINDOWS
Elevation
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE WINDOW
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 2 - Between Good and Fair
Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING
Deficiency Location/Instance Old Coal Bunker
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 20 of 50
Question Response
INTERIOR
STRUCTURAL
COLUMNS/BEAMS/BEARING WALLS Inspected
Old Coal Bunker
Violations No violations recorded.
FLOOR STRUCTURE Inspected
Condition 3 - Fair
Deficiency CINDER CONCRETE FLAT SLAB:CRACKED/SPALLED/REINFORCEMENT EXPOSED
Deficiency Location/Instance Old Coal Bunker
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Old Coal Bunker
Violations No violations recorded.
FOUNDATION WALLS Inspected
Material Type(s) Concrete
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
VAULTS-BUNKERS Inspected
Foundation Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Slab Structure Inspected
Condition 3 - Fair
Deficiency STEEL COLUMNS/BEAMS: MAJOR RUSTING
Deficiency Location/Instance Boiler Room
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 21 of 50
Question Response
INTERIOR
STRUCTURAL
VAULTS-BUNKERS
Slab Structure
Deficiency Photo1
Boiler Room
Violations No violations recorded.
Vault/Ash Hoist Doors and Framing Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
AUDITORIUM Inspected
InspectedInstance on 1st Floor - 532 Seats
Ceiling
InspectedInstance on 1st Floor - 532 Seats
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 1st Floor - 532 Seats
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed H/C Lift
Does not ExistInstance on 1st Floor - 532 Seats
Fixed Seating
InspectedInstance on 1st Floor - 532 Seats
Condition 5 - Poor
Deficiency DAMAGED/BROKEN/INOPERABLE
Deficiency Location/Instance Seats F/3, G/101, I/4, J/3
Deficiency Quantity 4
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Seat I/4
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 22 of 50
Question Response
INTERIOR
AUDITORIUM
Fixed Seating
Violations No violations recorded.
Deficiency DAMAGED/BROKEN/INOPERABLE
Deficiency Location/Instance Seats A/8, B/6, C/12, F/2,4 and others
Deficiency Quantity 111
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Seats F/2,4
Violations No violations recorded.
Floor Finish
InspectedInstance on 1st Floor - 532 Seats
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on 1st Floor - 532 Seats
Stage
InspectedInstance on 1st Floor - 532 Seats
Stage Inspected
InspectedInstance on 1st Floor - 532 Seats
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage Curtain Rigging Inspected
InspectedInstance on 1st Floor - 532 Seats
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage Curtains Inspected
InspectedInstance on 1st Floor - 532 Seats
Condition 3 - Fair
Deficiency WORN/DETERIORATED
Deficiency Location/Instance Left Side
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 23 of 50
Question Response
INTERIOR
AUDITORIUM
Stage
Stage Curtains
Deficiency Photo1
Left Side
Violations No violations recorded.
Walls
InspectedInstance on 1st Floor - 532 Seats
Condition 2 - Between Good and Fair
Deficiency STONE MOLDINGS: CRACKS/SPALLING
Deficiency Location/Instance Near Entrance
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Entrance
Violations No violations recorded.
Deficiency STONE: CRACKS/SPALLING
Deficiency Location/Instance Near Entrance, Right Side
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 24 of 50
Question Response
INTERIOR
AUDITORIUM
Walls
Deficiency Photo1
Near Entrance
Violations No violations recorded.
Window Curtains/Shades/Blinds
InspectedInstance on 1st Floor - 532 Seats
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CAFETERIA Inspected
InspectedInstance on Basement
Ceiling
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK
Deficiency Location/Instance Near Entrance
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Near Entrance
Violations No violations recorded.
Door(s)
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
Does not ExistInstance on Basement
Floor Finish
InspectedInstance on Basement
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 25 of 50
Question Response
INTERIOR
CAFETERIA
Floor Finish
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Near Servery, Right Side
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Servery
Violations No violations recorded.
Sliding-folding Partition
Does not ExistInstance on Basement
Stage
Does not ExistInstance on Basement
Walls
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on Basement
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK
Deficiency Location/Instance Rooms 127, 126
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 26 of 50
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Room 127
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Rooms 364, 124, 122, Corridor near Room 313, 301 and others
Deficiency Quantity 120
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 364
Violations No violations recorded.
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Rooms 327, 315, 122, 120, Main Entrance and others
Deficiency Quantity 11
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 327
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Rooms 217, 101, Corridor near Room 126
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 27 of 50
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 217
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Room 324
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Room 324
Violations No violations recorded.
Deficiency TERRAZZO: CRACKS
Deficiency Location/Instance Corridor near Cafeteria, Main Entrance Vestibule, Main Lobby
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 28 of 50
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish Inspected
Corridor near Cafeteria
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK
Deficiency Location/Instance Room 127
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Room 127
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Rooms 322, 305, 255, 124, Corridor near Room 319 and others
Deficiency Quantity 390
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 319
Violations No violations recorded.
Specialties Inspected
Classroom Locker(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Seating Does not Exist
GYMNASIUM Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 29 of 50
Question Response
INTERIOR
GYMNASIUM
InspectedInstance on 3rd Floor
Ceiling
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 3rd Floor
Condition 4 - Between Fair and Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Entrance, Storage Room
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Entrance
Violations No violations recorded.
Fixed Equipment
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Seating
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on 3rd Floor
Stage
Does not ExistInstance on 3rd Floor
Walls
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on 3rd Floor
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 30 of 50
Question Response
INTERIOR
INTERIOR DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
KITCHEN Inspected
InspectedInstance on Basement
Ceiling
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Basement
Condition 3 - Fair
Deficiency METAL: DETERIORATED DOOR
Deficiency Location/Instance Entrance
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Entrance
Violations No violations recorded.
Floor Finish
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance Center
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 31 of 50
Question Response
INTERIOR
KITCHEN
Floor Finish
Deficiency Photo1
Center
Violations No violations recorded.
Walls
InspectedInstance on Basement
Condition 3 - Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Near the windows, Storage Room
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near the windows
Violations No violations recorded.
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Near the windows, Storage Room
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 32 of 50
Question Response
INTERIOR
KITCHEN Inspected
Walls
Deficiency Photo1
Near the windows
Violations No violations recorded.
LIBRARY Inspected
InspectedInstance on Room 222
Built-in Furnishing
InspectedInstance on Room 222
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Ceiling
InspectedInstance on Room 222
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Room 222
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Room 222
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on Room 222
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOCKER ROOM Inspected
InaccessibleInstance on 3rd Floor
MULTI-PURPOSE ROOM Inspected
InspectedInstance on 1st Floor
Ceiling
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 1st Floor
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Exit 2 Vestibule, Main Entrance
Deficiency Quantity 3
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 33 of 50
Question Response
INTERIOR
MULTI-PURPOSE ROOM
Door(s)
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Exit 2 Vestibule
Violations No violations recorded.
Fixed Equipment
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on 1st Floor
Stage
Does not ExistInstance on 1st Floor
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency SALT GLAZED BRICK: CRACKS/SPALLING
Deficiency Location/Instance Near Drinking Fountain
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Drinking Fountain
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 34 of 50
Question Response
INTERIOR
MULTI-PURPOSE ROOM Inspected
Walls
Violations No violations recorded.
Window Curtains/Shades/Blinds
Does not ExistInstance on 1st Floor
SCIENCE DEMO ROOM Does not Exist
SCIENCE LAB Inspected
InspectedInstance on Room 324
Alternative use No
Fixed Equipment
InspectedInstance on Room 324
Condition 2 - Between Good and Fair
Deficiency CABINETRY: MISSING/DAMAGED
Deficiency Location/Instance Room 324
Deficiency Quantity 6
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 324
Violations No violations recorded.
SCIENCE PREP ROOM Does not Exist
SHOWER ROOM Inspected
InaccessibleInstance on 3rd Floor
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Yes
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency METAL CLAD WOOD: DETERIORATED DOOR
Deficiency Location/Instance Stair AB/1,3
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 35 of 50
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Door(s)
Deficiency Photo1
Stair AB/1
Violations No violations recorded.
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Stair AB/1, CD/1
Deficiency Quantity 6
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair AB/1
Violations No violations recorded.
Partition Inspected
Condition 2 - Between Good and Fair
Deficiency GLASS PANEL: DAMAGED/DETERIORATED
Deficiency Location/Instance Stair CD/Basement,2, F/3
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 36 of 50
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Partition Inspected
Stair F/3
Violations No violations recorded.
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs and Landings Inspected
Condition 5 - Poor
Deficiency STONE: WORN-OUT TREAD/NOSINGS
Deficiency Location/Instance Stair AB/1
Deficiency Quantity 130
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair AB/1
Violations No violations recorded.
Deficiency STONE: BROKEN/MISSING
Deficiency Location/Instance Near Gymnasium
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair E/1
Violations No violations recorded.
Deficiency ROLLED ASPHALT: CRACKS
Deficiency Location/Instance Stair CD/Basement, Bulkhead
Deficiency Quantity 300
Quantity Uom S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 37 of 50
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Stairs and Landings
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair CD/Bulkhead
Violations No violations recorded.
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Stair E/Bulkhead, F/3
Deficiency Quantity 250
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair E/Bulkhead
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Stair CD/Basement,1
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 38 of 50
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Walls
Deficiency Photo1
Stair CD/Basement
Violations No violations recorded.
Deficiency STONE: CRACKS/SPALLING
Deficiency Location/Instance Stair AB/1
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair AB/1
Violations No violations recorded.
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Inside Room 363
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 39 of 50
Question Response
INTERIOR
TOILET ROOMS - STAFF
Ceiling Inspected
Deficiency Photo1
Inside Room 363
Violations No violations recorded.
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Room 358
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 358
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance Room 358
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 40 of 50
Question Response
INTERIOR
TOILET ROOMS - STAFF
Floor Finish
Deficiency Photo1
Room 358
Violations No violations recorded.
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Inside Room 363Rooms
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Inside Room 363
Violations No violations recorded.
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Rooms 358, 1st Floor Women
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 41 of 50
Question Response
INTERIOR
TOILET ROOMS - STAFF
Walls
Deficiency Photo1
Room 358
Violations No violations recorded.
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Inside Room 207
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Inside Room 207
Violations No violations recorded.
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DAMAGED LOUVER
Deficiency Location/Instance Room C33
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 42 of 50
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Door(s)
Deficiency Photo1
Room C33
Violations No violations recorded.
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Rooms 360, 1st Floor Boys, Inside Room 207, 107, 105
Deficiency Quantity 6
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 360
Violations No violations recorded.
Floor Finish Inspected
Condition 3 - Fair
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance 3rd Floor Boys, 1st Floor Boys, 1st Floor Girls, Rooms 360, 217 andothers
Deficiency Quantity 90
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 43 of 50
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Floor Finish Inspected
Deficiency Photo1
Room C33
Violations No violations recorded.
Stalls Inspected
Condition 3 - Fair
Deficiency BROKEN/MISSING
Deficiency Location/Instance 3rd Floor Boys
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
3rd Floor Boys
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Rooms 233, 217, C29
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 44 of 50
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Walls
Deficiency Photo1
Room C29
Violations No violations recorded.
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance 3rd Floor Boys, Rooms 360, 217, 207, C29 and others
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room C29
Violations No violations recorded.
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Does not Exist
Drainage System for Asphalt Inspected
Catch Basins/Manhole - Surrounded by asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Asphalt Covering Does not Exist
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Concrete Covering Does not Exist
Drainage System for Soil Inspected
Catch Basins/Manhole - Surrounded by Soil Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 45 of 50
Question Response
SITE
Drainage System for Soil
Catch Basins/Manhole - Surrounded by Soil Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Soil Covering Inspected
Condition 3 - Fair
Deficiency DAMAGED
Deficiency Location/Instance 116th Avenue
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
116th Avenue
Violations No violations recorded.
DRINKING FOUNTAINS Does not Exist
FENCES Inspected
Condition 4 - Between Fair and Poor
Deficiency CHAIN LINK: DAMAGED POST/RAIL
Deficiency Location/Instance 218th Street
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
218th Street
Violations No violations recorded.
Deficiency WROUGHT IRON: DAMAGED/DETERIORATED
Deficiency Location/Instance 116th Avenue, 218th Street, 219th Street
Deficiency Quantity 1,000
Quantity Uom S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 46 of 50
Question Response
SITE
FENCES
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
116th Avenue
Violations No violations recorded.
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Inspected
Gravel Exists? No
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance 116th Avenue, 218th Street
Deficiency Quantity 275
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
116th Avenue
Violations No violations recorded.
Pavers Does not Exist
Student Use Inspected
Gravel Exists? Yes
Asphalt Inspected
Condition 4 - Between Fair and Poor
Deficiency CRACKS - MAJOR
Deficiency Location/Instance North of Building
Deficiency Quantity 700
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 47 of 50
Question Response
SITE
PAVING
Student Use
Asphalt
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
North of Building
Violations No violations recorded.
Concrete Does not Exist
Pavers Does not Exist
Site Sidewalks & Walkways Inspected
Asphalt Inspected
Condition 4 - Between Fair and Poor
Deficiency CRACKS - MAJOR
Deficiency Location/Instance 218th Street, 219th Street, around Minischool
Deficiency Quantity 1,200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
218th Street
Violations No violations recorded.
Concrete Inspected
Condition 4 - Between Fair and Poor
Deficiency CRACKS - MAJOR
Deficiency Location/Instance 116th Avenue
Deficiency Quantity 800
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 48 of 50
Question Response
SITE
PAVING
Site Sidewalks & Walkways
Concrete
Purpose of Action LEVEL 2
Deficiency Photo1
116th Avenue
Violations No violations recorded.
Pavers Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED CURBS
Deficiency Location/Instance 116th Avenue
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
116th Avenue
Violations No violations recorded.
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance 116th Avenue, 218th Street, 219th Street
Deficiency Quantity 150
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 49 of 50
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Deficiency Photo1
116th Avenue
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Does not Exist
PLAYING SURFACE Does not Exist
RETAINING WALLS Does not Exist
SEATING Does not Exist
SITE WALLS (NOT RETAINING WALLS) Does not Exist
STAIRS/RAMPS: EXTERIOR Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q147
PB/A&W Print Date: 6/21/2019Page 50 of 50