How To
ITER catalogue for I&C products - Slow controllers PLCThis document contains the list of Siemens S7 components to be used within Plant Systems for slow controls and SIL-2 and 3 purposes.
Approval Process Name Action AffiliationAuthor Simelio A. 11 Aug 2017:signed IO/DG/COO/SCOD/CSD/PCICo-Authors Bhamare A.
Evrard B. Wagner R.
11 Aug 2017:signed11 Aug 2017:signed11 Aug 2017:signed
TATA Consultancy Services France SA (EU)IO/DG/COO/SCOD/CSD/PCIIO/DG/COO/SCOD/CSD/PCI
Reviewers Fernandez Robles C. Patel J. Soni J. Wallander A.
11 Aug 2017:recommended11 Aug 2017:recommended11 Aug 2017:recommended11 Aug 2017:recommended
IO/DG/COO/SCOD/CSD/PCIIO/DG/COO/SCOD/CSD/CDCIO/DG/COO/SCOD/CSD/PCIIO/DG/COO/SCOD/CSD
Approver Petitpas P. 11 Aug 2017:approved IO/DG/COO/SCOD/CSD/PCIDocument Security: Internal Use
RO: Simelio AntoniRead Access LG: PLC group, LG: CODAC team, AD: ITER, AD: External Collaborators, AD: IO_Director-General, AD:
EMAB, AD: OBS - Plant Control and Instrumentation Section (PCI), AD: Auditors, AD: ITER Management Assessor, project administrator, RO, AD: OBS - Control System Division (CSD) - EXT, AD: OBS - CODAC Sec...
IDM UID
333J63VERSION CREATED ON / VERSION / STATUS
11 Aug 2017 / 4.1 / Approved
EXTERNAL REFERENCE / VERSION
PDF generated on 11 Aug 2017DISCLAIMER : UNCONTROLLED WHEN PRINTED – PLEASE CHECK THE STATUS OF THE DOCUMENT IN IDM
Change Log
ITER catalogue for I&C products - Slow controllers PLC (333J63)
Version Latest Status Issue Date Description of Change
v1.0 Signed 10 Dec 2009
v1.1 Approved 01 Feb 2010 Updated for version %5.1 of PCDHv1.2 Signed 31 Aug 2010 Update of documentation links, minor syntax changes, change of module
references:Replace 6ES7 317-2EK13-0AB0 by 6ES7 317-2EK14-0AB0 within section 3.1.3Replace 353-1AH01-0AE0 by 6ES7353-1AH01-0AE0 within section 3.2.6Replace 6ES7 75710-8MA11 by 6ES5710-8MA11 within section 3.3.1Replace 6ES7 8GL11-0AA0 by 6ES7 8LG11-0AA0 within section 3.3.3Replace 6ES7 416-3 PN 3ER05-0AB0 by 6ES7 416-3ER05-0AB0 within section 3.4.3Replace 6GK7 443-1EX20-0EX0 by 6GK7 443-1EX20-0XE0 within section 3.4.4Replace 6ES7 414-FH by 6ES7414HM14-0AB0 within section 3.5.3Replace 6ES7 960-1AA04-5BK0 by 6ES7 960-1AA04-0XA0 within section 3.5.5Replace 6ES7153-1BK00-0AB0 by 6ES7153-1BK00-0XB0 within section 3.5.5Replace 6ES7326-1BK01-0AB0 by 6ES7326-1BK02-0AB0 within section 3.6.4Replace 6ES7326-2BF01-0AB0 by 6ES7326-2BF10-0AB0 within section 3.6.4Replace 6ES7650-1KA11-7XX0 by 6ES7650-1AK11-7XX0 within section 3.6.5Replace 6ES7 138-4CF02-0AA0 by 6ES7138-4CF03-0AB0 within section 3.7.2Replace 6ES7 953-8GL11-0AA0 by 6ES7953-8LG11-0AA0 within section 3.7.3
v1.3 Signed 22 Oct 2010 Replace 6ES7390-1BC00-0AA0 by 6ES7390-1AJ30-0AA0 within section 3.1.1Replace 6ES7341-1CH02 by 6ES7341-1CH02-0AE0 within section 3.1.5Replace 6ES7193-4CC20-0AA0 by 6ES7193-4CC30-0AA0 within section 3.3.2
v1.4 Signed 28 Oct 2010 Replace 6ES7307-1EA00-0AA0 by 6ES7307-1EA01-0AA0 within section 3.1.2Add reference S7 PLC ordering process (https://user.iter.org/?uid=3Q6UQ3)
v1.5 Signed 17 Nov 2010 Add 6ES7971-0BA00 within section 3.4.2Add 6ES7952-1AM00-0AA0 within section 3.5.3Add 6ES7960-1AA04-0XA0 within section 3.5.3Add section 3.5.7Add 6ES7922-3BD00-0AS0 within section 3.6.5Add 6ES7922-3BD00-0AN0 within section 3.6.5
v1.6 Signed 06 Jan 2011 New RO: B Evrardv1.7 Approved 09 Feb 2011 Version updated after PCDH review.v2.0 In Work 22 Oct 2012 Catalog organization completely Re-shuffled.
TAble of Content is different.v3.0 Signed 03 Dec 2012 Complete Re-shuffling.
References moved to another living documentAddition of gudielines for architectures
v3.1 Approved 13 Dec 2012 - Update of Satelite Documents picture.- Update Reviewers and Approver
PDF generated on 11 Aug 2017DISCLAIMER : UNCONTROLLED WHEN PRINTED – PLEASE CHECK THE STATUS OF THE DOCUMENT IN IDM
- Addition of Exploded view for s7-400 Rackv3.2 Revision
Required31 Jul 2013 Modification of Chapter 7: Software Packages
v3.3 Approved 04 Jul 2014 Solve problem with cover pagev3.4 In Work 02 Feb 2016 Addition of Network Section
Addition of exploded views.v4.0 Signed 10 Aug 2017 Major modification of the Document:
Reference System :o SIEMENS Reference List is the main document referenced
Systems Selection :o Main reshape of the chapter adapted to the current philosophyo 1500 CPUs addedo Controller, CPU Range subchapters reformulated, CPU and communication performance is taking in accounto Remote IO Selection sub reformulatedo Network selection subchapter reshaped, detailed and enlarged taking in account new needs of the Plant Systemso Cubicle Monitoring system selection addedo Accessing point selection added
System Composition :o Main reshape of the chapter adapted to the current philosophyo Inclusion of 1500 Family devices
Network Composition :o Main reshape of the chapter adapted to the current philosophyo Added devices taking in account the new needs of the Plant Systems
Software :o Reshape of the chaptero TIA Portal Added
v4.1 Approved 11 Aug 2017 Typo mistakes corrected.
Major modification of the document regarding version 3.X:
-Reference System:- SIEMENS Reference List settled as the main reference of the catalogue.
-Systems Selection:- Main reshape of the chapter, adapted to the current philosophy.- 1500 CPUs added.- Controllers and CPU Range subchapters reformulated, CPU and communication performance is taken in account.- Remote IO Selection subchapter reformulated.- Network selection subchapter reshaped, detailed and enlarged taking in account new needs of the Plant Systems.- Cubicle monitoring system selection added.- Accessing point selection added.
-System Composition:- Main reshape of the chapter, adapted to the current philosophy.- Inclusion of 1500 Family devices.- Network Composition :- Main reshape of the chapter, adapted to the current philosophy.
PDF generated on 11 Aug 2017DISCLAIMER : UNCONTROLLED WHEN PRINTED – PLEASE CHECK THE STATUS OF THE DOCUMENT IN IDM
- Added devices taking in account the new needs of the Plant Systems.
-Software:- Reshape of the chapter.- TIA Portal Added.
ITER_D_333J63 v4.1
Page 1 of 83
Table of Contents
1 PURPOSE ............................................................................................................................4
2 SCOPE .................................................................................................................................5
2.1 PCDH context ..............................................................................................................5
3 DEFINITIONS ....................................................................................................................6
3.1 Acronyms .....................................................................................................................6
3.2 Definitions ....................................................................................................................6
3.3 Reference Documents .................................................................................................7
4 REFERENCE SYSTEM ....................................................................................................8
5 SYSTEM SELECTION ......................................................................................................9
5.1 Controller type selection.............................................................................................9
5.2 CPU Rack Selection ....................................................................................................9 A. Standard System(no designation) ...............................................................................10 B. High Availability System(“H”)...................................................................................10 C. Fail-Safe System(“F”):................................................................................................10
5.3 CPU Range Selection ................................................................................................11 A. Processor Performance and Memory Size ..................................................................11 B. Communication Performance Expected .....................................................................14 C. Sample System (example)...........................................................................................14
5.4 Remote IO Devices Selection....................................................................................15
5.5 Network Selection .....................................................................................................19 A. Technology Selection..................................................................................................20 B. Field Network Architectures .......................................................................................21
5.5.B.1 FieldBus (Profibus) .........................................................................................22 5.5.B.2 Field Net (Profinet) using Central I&C Systems Physical Infrastructure. ......24
5.5.B.3 FieldNet (Profinet) using independent physical infrastructure. ......................26 5.5.B.4 Modbus ...........................................................................................................28
C. Plant System Local (Private) Network Architecture. .................................................29
5.5.C.1 Inter-Controllers communications using the Central I&C Networks. ............29 5.5.C.2 Inter-Controllers communications using independent physical architecture ..31
5.6 Central I&C Network accessing point Selection ....................................................33 A. Analysis of the Arguments..........................................................................................33 B. Outcome of the analysis .............................................................................................35
5.7 Cubicle Monitoring System Selection .....................................................................36 A. Complete Solution for 1 cubicle .................................................................................36 B. Partial Solution for ‘2 to 11’ cubicles .........................................................................37
6 SYSTEMS COMPOSITION ...........................................................................................40
6.1 Slow Controllers Range ............................................................................................40 A. Low (distributed) Range of Slow Controllers .............................................................40
6.1.A.1 Low (Distributed) Range PLCs: [S7-1500] CPU + IO Rack ..........................40 B. Medium Range of Slow Controllers ...........................................................................42
6.1.B.1 Mid-range PLCs: [S7-300 or S7-1500] CPU Rack........................................42 6.1.B.1.1 S7-300: CPU Rack....................................................................................42
ITER_D_333J63 v4.1
Page 2 of 83
6.1.B.1.2 S7-1500: CPU Rack..................................................................................45
6.1.B.2 Mid-range PLC with local IO: [S7-300 or S7-1500] CPU+IO Rack.............48
6.1.B.2.1 S7-300: CPU+IO Rack .............................................................................48
6.1.B.2.2 S7-1500: CPU+IO Rack ...........................................................................50 6.1.B.3 Mid-range Fail Safe PLCs: [S7-300 or S7-1500] CPU rack...........................52
6.1.B.3.1 S7-300 “F” CPU rack ...............................................................................52 6.1.B.3.2 S7-1500 “F” CPU rack .............................................................................53
C. High Range of Slow Controllers .................................................................................54
6.1.C.1 High range PLCs: S7-400 ...............................................................................54 6.1.C.2 High range Fail Safe PLCs: S7-400 “F” CPU rack ........................................57 6.1.C.3 High Range, High Availability PLCs: S7-400 “H” CPU Rack ......................59
6.2 Remote I/O Modules Range .....................................................................................63 A. Small I/O modules [S7-300 or S7-1500] ...................................................................63
6.2.A.1 S7-300 Family: ET200S .................................................................................63
6.2.A.2 S7-1500 Family: ET200SP .............................................................................65
B. Medium I/O modules [S7-300 or S7-1500] ...............................................................67 6.2.B.1 S7-300 Family: ET200M ................................................................................67 6.2.B.2 S7-1500 Family: ET200MP ............................................................................69
C. Medium I/O Fail-Safe modules [S7-300 or S7-1500] ................................................71
6.2.C.1 S7-300 Family: ET200M –“F” .......................................................................71 6.2.C.2 S7-1500 Family: ET200MP –“F” ...................................................................73
6.3 Accessories .................................................................................................................75
7 NETWORK COMPOSITION .........................................................................................76
7.1 Field Network Architecture equipment ..................................................................76 A. Field Bus (Profibus) components................................................................................76 B. Field Net (Profinet) components .................................................................................77
7.2 Plant System Local (Private) Network Architecture equipment ..........................78
8 SOFTWARE : STEP7 & TIA Portal ..............................................................................79
8.1 STEP7.........................................................................................................................79 A. Dependencies ..............................................................................................................79 B. Versions compatibility ................................................................................................80
8.2 TIA Portal ..................................................................................................................81 A. Dependencies ..............................................................................................................81
B. Versions compatibility ................................................................................................82
8.3 What version to install ? ...........................................................................................83
8.4 Applications portability between versions ..............................................................83
ITER_D_333J63 v4.1
Page 3 of 83
Table of Figures
Figure 1: PCDH documents ___________________________________________________5 Figure 2: Hardware selection flowchart __________________________________________9 Figure 3: SIMATIC S7-300 CPU 317-2 PN/DP___________________________________11
Figure 4: SIMATIC S7-400, CPU 416-3 PN/DP __________________________________12 Figure 5: SIMATIC S7-1500, CPU 1516-3 PN/DP ________________________________13 Figure 6: ET200M__________________________________________________________15 Figure 7: ET200MP ________________________________________________________15 Figure 8: ET200S __________________________________________________________16
Figure 9: ET200SP _________________________________________________________16 Figure 4: Network Functional Segregation _______________________________________19 Figure 5: FieldBus (Profibus) Network using independent infrastructure _______________23 Figure 6: FieldNet Network (Profinet) using ‘Central I&C Network’ infrastructure _______25
Figure 7: FieldNet Network (Profinet) using independent infrastructure ________________27 Figure 10 : Modbus RTU Network Layout_______________________________________28 Figure 8 : Inter-Controllers (S7 communication) using the ‘Central I&C Network’ _______30
Figure 9: Inter-Controllers (S7 Communication) using independent infrastructure ________32 Figure 30 : Target of the solution for the monitoring of one single cubicle ______________36 Figure 31 : SIEMENS Hardware for CUB MON SYS 1 Single Cubicle _____________37 Figure 32 : Target of the solution for the monitoring of ‘2 to 11’ Cubicles ______________37
Figure 33 : SIEMENS Hardware for CUB MON SYS From ‘2 to 11’ cubicles ________38 Figure 11 : Distributed Rack [S7-1500 + IO] exploded view _________________________41 Figure 12: Rack s7-300 exploded view. _________________________________________43
Figure 13: Rack S7-1500 exploded view ________________________________________46 Figure 14: Rack S7-300 + IO exploded view _____________________________________48
Figure 15 : Rack S7-1500 + IO exploded view ___________________________________50
Figure 16: Fail Safe, High range PLCs S7300F ___________________________________52
Figure 17 : Fail Safe, High range PLCs S71500F _________________________________53 Figure 18: Rack S7-400 exploded view. _________________________________________55
Figure 19: Fail Safe, High range PLCs S7400F ___________________________________57 Figure 20: High availability PLCs architecture ___________________________________59 Figure 21: High availability PLCs S7-400H ______________________________________60
Figure 22: ET200S Modules exploded view _____________________________________63 Figure 23: ET200SP Modules exploded view ____________________________________65 Figure 24: ET200M Modules _________________________________________________67 Figure 25: ET200M Modules to use with s7-400”H” _______________________________68 Figure 26: ET200MP Modules ________________________________________________69 Figure 27: ET200M “F” Modules ______________________________________________71 Figure 28: ET200M “F” Modules for S7-400FH __________________________________72
Figure 29: ET200MP “F” Modules_____________________________________________73 Figure 34: Software and Applications Dependency Tree for STEP7 ___________________79
Figure 35: Software and Applications Dependency Tree for TIA Portal ________________81
ITER_D_333J63 v4.1
Page 4 of 83
1 PURPOSE
This catalogue has been created and is constantly maintained to help the Plant System
manufacturers and system integrators in their work. The primary objective is to promote the
usage of identical equipment in all Plant Systems so that the integration and interoperability
with the ITER Instrumentation and Control system would be seamless. The secondary
objective is to coordinate site-wide maintenance of the equipment. The third objective is to
provide tools for the obsolescence management.
The objectives will be met by a careful selection of industrial COTS products which will
comply with existing standards, defined by the Plant Control Design Handbook (PCDH,
[RD1]).
ITER_D_333J63 v4.1
Page 5 of 83
2 SCOPE
This document addresses the needs for Plant Control Systems developed using COTS system
devices, named Slow Controllers in the Plant Control Design Handbook.
This document is applicable to Conventional, Interlock and Occupational Safety I&C systems
based on slow controllers.
Slow controllers used for the nuclear safety I&C systems are out of scope of this document and
are described in [RD9].
‘ITER Catalogue of I&C Products - Slow Controllers PLC’ gives a list of COTS products
recommended by ITER Organization for Slow I/O systems.
‘ITER Catalogue of I&C Products - Slow Controllers PLC’ is a living document, which is
released at regular intervals throughout the lifetime of ITER. Versions of standards and
products are subject to updates and extensions as the ITER project progresses.
2.1 PCDH context
The ‘Plant Control Design Handbook (PCDH)’ [RD1] defines methodology, standards,
specifications and interfaces applicable to ITER Plant Systems Instrumentation & Control
(I&C) system life cycle. I&C standards are essential for ITER in order to:
• Integrate all plant systems into one integrated control system.
• Maintain all plant systems after delivery acceptance.
• Contain cost by economy of scale.
PCDH comprises a core document which presents the plant system I&C life cycle and recaps
the main rules to be applied to the plant system I&Cs for conventional controls, interlocks and
safety controls. Some I&C topics will be explained in greater detail in dedicated documents
associated with PCDH as presented in the picture below. This document is one of them.
Figure 1: PCDH documents
Core PCDH (27LH2V)
Plant system control philosophy
Plant system control Life Cycle
Plant system control specifications
CODAC interface specifications
Interlock I&C specification
Safety I&C specification
PCDH core and satellite documents: v7PS CONTROL DESIGN
Plant system I&C architecture (32GEBH)
Methodology for PS I&C specifications (353AZY)
CODAC Core System Overview (34SDZ5) INTERLOCK CONTROLS
Guidelines for PIS design (3PZ2D2)
Guidelines for PIS integration & config. (7LELG4)
Management of local interlock functions (75ZVTY)
PIS Operation and Maintenance (7L9QXR)
I&C CONVENTIONS
I&C Signal and variable naming (2UT8SH)
ITER CODAC Glossary (34QECT)
ITER CODAC Acronym list (2LT73V)
PS SELF DESCRIPTION DATA
Self description schema documentation (34QXCP)
CATALOGUES for PS CONTROL
Slow controllers products (333J63)
Fast controller products (345X28)
Cubicle products (35LXVZ)
Integration kit for PS I&C (C8X9AE)
PS CONTROL INTEGRATION
The CODAC -PS Interface (34V362)
PS I&C integration plan (3VVU9W)
ITER alarm system management (3WCD7T)
ITER operator user interface (3XLESZ)
Guidelines for PON archiving (B7N2B7)
PS Operating State management (AC2P4J)
Guidelines for Diagnostic data structure (354SJ3)
PS CONTROL DEVELOPMENT
I&C signal interface (3299VT)
PLC software engineering handbook (3QPL4H)
Guidelines for fast controllers (333K4C)
Software engineering and QA for CODAC (2NRS2K)
Guidelines for I&C cubicle configurations (4H5DW6)
CWS case study specifications (35W299)
NUCLEAR PCDH (2YNEFU)
OCCUPATIONAL SAFETY CONTROLS
Guidelines for PSS design (C99J7G)
Available and approved
Legend
This document
(XXXXXX) IDM ref.
Slow controllers products (333J63)
ITER_D_333J63 v4.1
Page 6 of 83
3 DEFINITIONS
3.1 Acronyms
AI Analogue Input
AO Analogue Output
CIN Central Interlock Network
CIS Central Interlock System
CODAC COntrol Data Access and Communications
COTS Commercial Off the Shelf
CNP CODAC Network Panel
DA Domestic Agency
DC Direct Current
DI Digital Input
DO Digital Output
I&C Instrumentation & Control
I/O Input / Output
IO ITER Organization
IEC International Electro technical Commission
IM Interface Module (Profibus or Profinet)
IP Internet Protocol
LED Light Emitting Diode
NTP Network Time Protocol
PCDH Plant Control Design Handbook
PLC Programmable Logic Controller
PLN Plant System Local Network
PS Plant System
PSH Plant System Host
SIL Safety Integrity Level
TBC To Be Confirmed
TBD To Be Defined
TS Transceiver
UPS Uninterruptible Power Supply
WMC Wall Mounted Cubicle
1oo2 One out Of Two
2oo3 Two out Of Three
3.2 Definitions
Central I&C Systems
Central Control System including the CODAC
(Conventional Control), the CIS (Interlock) and the
CSS (Safety)
Dark Fiber Network-device-free optical fiber link between two
locations
CNP
CODAC Network Panel
Wall mounted cubicle that perform passive patch
cabling between optical fiber patch panels.
ITER_D_333J63 v4.1
Page 7 of 83
3.3 Reference Documents
IDM Number Title
[RD1] ITER_D_27LH2V Plant Control Design Handbook
[RD2] ITER_D_6M58M9 CODAC DDD [Network Infrastructure Chapter]
[RD2] ITER_D_C8X9AE Integration Kit for PS I&C
[RD3] ITER_D_3QPL4H PLC Software Engineering Handbook
[RD4] ITER_D_AWYQ5G SIEMENS Reference List
[RD6] ITER_D_32GEBH Plant System I&C Architecture
[RD7] ITER_D_4H5DW6 I&C Cubicle Internal Configuration
[RD8] ITER_D_UBZTCW Guide for Development of the Modbus protocol programming
[RD9] ITER_D_JHQLDP ITER catalogue for Nuclear Safety I&C products
[RD10] ITER_D_UVYE98 Benchmark information about the communication
performance between CODAC and the PLCs
[RD11] ITER_D_DZJ4ZT Occupational Safety Cubicle Monitoring System based
on S7-1200
ITER_D_333J63 v4.1
Page 8 of 83
4 REFERENCE SYSTEM
In the document, no Manufacture Reference will be mentioned. Every product will be
associated to a Short Designation. All Manufacture references are specified in another
document: [RD4]. The reason is that references may change frequently and would make this
document obsolete almost every 3 months. So the products are designed by a Short
Designation, itself pointing to a Manufacturer reference in the other document.
Example:
Short Designation Description Product Reference Status
CPU317-2 CPU 317-2 PN/DP (2x Eth) 6ES7317-2EK14-0AB0 Active
ITER_D_333J63 v4.1
Page 9 of 83
5 SYSTEM SELECTION
This chapter provides guidance to aid in the selection of slow controller hardware. CPU, CP,
power supplies, I/O modules and Field Network technology should all be selected in parallel
for homogenous system design.
START
Controller Type Selection (Standard, “H”, “F”)
PLC Range Selection (S7-300, 400, 1500)
I/O Selections
END
Network SelectionPower SupplyCommunication Processor (CP)
Central Processing Unit (CPU)
Figure 2: Hardware selection flowchart
5.1 Controller type selection
Selection between fast and slow control is out of scope of this document. Refer to the PCDH
[RD1] for guidance related to fast or slow control selection and network performance criteria.
This catalogue has been developed to provide guidance in selecting you PLC system hardware.
5.2 CPU Rack Selection
The following information provides guidance for the selection of a conventional CPU. It is
recommended that you consult your ITER Control System Division representative if you
require more information than the given below.
These factors should be considered when selecting a CPU rack:
o Standard System
o High Availability System (“H”)
o Fail-safe System (“F”)
The first step in selecting your CPU is to determine your rack requirements. Select the type of
system in development; Standard, High Availability, Fail-safe, or High Availability Fail-safe.
ITER_D_333J63 v4.1
Page 10 of 83
A. Standard System(no designation) The following standard CPUs are found in the Siemens Reference List [RD4].
CPU 317-2 PN/DP
CPU 416-3 PN
CPU 1512SP-1 PN for Rail DIN
CPU 1516-3 PN/DP
Standard CPUs will be used in an estimated 90% of all ITER conventional control systems.
Notes:
(1) The CPU 1214C is included in the Siemens Reference List [RD4]. The CPU 1214C must
be used, only, in the cubicle monitoring system and forbidden for use in conventional control
systems.
(2) The ITER Control System Division recommends using the S7-400 for master control
functions.
B. High Availability System(“H”)
The S7-400H is suitable as a controller for high-availability processes, with two H CPUs of the
same type; in the event of a fault, changeover takes place from the master system to the
standby station.
For more information regarding “H” CPUs, see: SIMATIC S7-400H High-availability CPUs
The following “H” high availability CPUs are found in the Siemens Reference List:
CPU 414-5H PN/DP
CPU 416-5H PN/DP
CPU 417-5H PN/DP
In Siemens CPU references, an “H” is integrated in the short description and in the Siemens
reference number: i.e. “CPU414-5H,” and “6ES7414-5HM06-0AB0.”
Notes: (1) An “H” CPU also qualifies as High Availability FailSafe, or “FH”.
(2) The ITER Control System Division recommends using the S7-400H for master control
functions.
C. Fail-Safe System(“F”):
The following “F” Fail-safe CPUs are found in the Siemens Reference List:
CPU 315F-2 PN/DP Fail Safe CPU
CPU 1516F-3 PN/DP Fail Safe CPU
In Siemens CPU references, an “F” is integrated in the short description and in the Siemens
reference number: i.e. “CPU315F-2,” and “6ES7315-2FJ14-0AB0”
Note: (1)“F” CPUs are used in interlock and safety systems only and are not required for use in
conventional control systems. The fail-safe controllers are used to guarantee the functional
safety of machines. For more information regarding “F” CPUs, see: Fail-safe SIMATIC CPUs
See the Siemens Reference List [RD4] for the latest information regarding ITER approved
CPUs.
ITER_D_333J63 v4.1
Page 11 of 83
5.3 CPU Range Selection
A. Processor Performance and Memory Size
The second step in selecting your CPU is to determine your performance and memory
requirements for the system. The following tables provided for the S7-300, S7-400 and
S7-1500 ranges were extracted from Siemens Online resources.
SIMATIC S7-300 CPU 317-2 PN/DP
CPU Processing Time
for bit operations, typ. 0.025 µs
for word operations, typ. 0.03 µs
for fixed point arithmetic, typ. 0.04 µs
for floating point arithmetic, typ. 0.16 µs
CPU - blocks
Number of blocks (total) 2048 (DBs, FCs, FBs)
Size, max. 64 kbyte
Digital channels
Inputs 65536
Outputs 65536
Inputs, of which central 1024
Outputs, of which central 1024
Analog channels
Inputs 4096
Outputs 4096
Inputs, of which central 256
Outputs, of which central 256
Hardware Configuration
Racks, max. 4
Modules per rack, max. 8
Expansion devices, max. 3
Interfaces
Number of other interfaces 1; Ethernet, 2-port switch, 2*RJ45
PROFINET IO Controller
Transmission rate, max. 100 Mbit/s
number of connectable IO devices, max. 128
PROFIBUS proxy functionality
number of linked PROFIBUS devices 16
Data length per connection, max. 240 byte; slave-dependent
Work memory
integrated 1024 kbyte
expandable No
size of retentive memory for DBs 256 kbyte
Load memory
Pluggable (MMC), max. 8 Mbyte
Software TIA Portal and STEP 7
Figure 3: SIMATIC S7-300 CPU 317-2 PN/DP
ITER_D_333J63 v4.1
Page 12 of 83
SIMATIC S7-400, CPU 416-3 PN/DP
CPU Processing Time
for bit operations, typ. 0.0125 µs
for word operations, typ. 0.0125 µs
for fixed point arithmetic, typ. 0.0125 µs
for floating point arithmetic, typ. 0.025 µs
CPU - blocks
DB number, max. 10,000
FB number, max. 5,000
FC number, max. 5,000
Size, max. 64 kbyte
Digital channels
Inputs 131,072
Outputs 131,072
Inputs, of which central 131,072
Outputs, of which central 131,072
Analog channels
Inputs 8,192
Outputs 8,192
Inputs, of which central 8,192
Outputs, of which central 8,192
Hardware Configuration
Racks, max. 21
connectable Ops 95
multi-computing Yes, 4 CPUs max. (with UR1 and UR2)
Interfaces
Interfaces/bus type 1xMPI/PROFIBUS DP, 1xPROFINET (2 ports), 1xPROFIBUS DP number of RS 485 interfaces 1; combined MPI / PROFIBUS DP
number of other interfaces 1; PROFIBUS DP with IF 964-DP
PROFINET IO Controller
Transmission rate, max. 100 Mbit/s
number of connectable IO devices, max. 256
PROFIBUS DP Master
Transmission rate, max. 12 Mbit/s
number of linked PROFIBUS devices 32
Work memory
integrated 16 Mbyte
expandable No
Load memory
expandable FEPROM, max. 64 Mbyte
integrated RAM, max. 1 Mbyte
Software TIA Portal & STEP 7
Figure 4: SIMATIC S7-400, CPU 416-3 PN/DP
ITER_D_333J63 v4.1
Page 13 of 83
SIMATIC S7-1500, CPU 1516-3 PN/DP
CPU Processing Time
for bit operations, typ. 0.010 µs
for word operations, typ. 0.012 µs
for fixed point arithmetic, typ. 0.016 µs
for floating point arithmetic, typ. 0.064 µs
CPU - blocks
Number of elements (total) 6,000
Size, max. 5 MB
Address area
number of IO modules 8,192; max. number of modules
Inputs 32 kbyte; All in the process image
Outputs 32 kbyte; All in the process image
Number of distributed IO systems 64
Hardware Configuration
modules per rack, max 32; CPU + 31 modules
number of lines max 1
PtP CM limited only by the number of
available slots
Interfaces
number of PROFINET interfaces 2
number of PROFIBUS interfaces 1
number of other interfaces 1; PROFIBUS DP with IF 964-DP
1st PROFINET IO Controller
Number of connectable IO devices, max.
256; in total, up to 1,000 distributed I/O devices can be connected via AS-I
PROFIBUS or PROFINET
2nd PROFINET IO Controller
Number of connectable IO devices, max.
32; in total, up to 1,000 distributed I/O devices can be connected via AS-I
PROFIBUS or PROFINET
PROFIBUS; RJ 45 (Ethernet), RS 485
Transmission rate, max. 12 Mbit/s
number of linked PROFIBUS devices 256, via integrated interfaces of the
CPU and connected CPs / CMs
Work memory
integrated (for program) 1 Mbyte
integrated (for data) 5 Mbyte
Load memory
Plug-in (SIMATIC Memory Card), max 32 Gbyte
Software TIA Portal
Figure 5: SIMATIC S7-1500, CPU 1516-3 PN/DP
ITER_D_333J63 v4.1
Page 14 of 83
B. Communication Performance Expected
Another important point in order to determine the CPU is the ‘Communication Performance’
expected. This performance is in straight relation with the quantity of data your application is
going to manage (send/receive). Logically bigger quantity of data needs more powerful CPUs
to achieve an acceptable communication rate.
Moreover, ITER standards advice to use the CP as a device connecting to the High Network
and this has also an impact in the ‘communication performance’ towards the ‘Central I&C
System’
Please refer to the document [RD10] to have detailed information about the ‘communication
performances’ of the ‘ITER PLC Configurations’ in relation with the quantity of data ‘sent’
towards the ‘Central I&C System’.
C. Sample System (example)
With the information provided above, a determination can be made for the conventional system
CPU based on rack requirements and performance and memory requirements.
For example, a system has the following requirement:
[CSD1] The PLC shall perform standard process control and monitoring
This requires a standard rack leaving us with the following CPUs to select from:
CPU 317-2 PN/DP CPU 416-3 PN CPU 1512SP-1 PN
for Rail DIN
CPU 1516-3 PN/DP
Next, the system has the following performance requirement:
[CSD2] The PLC shall perform bit operations in less than 0.02 µs.
From the notes above, the CPU 1214C must only be used in the cubicle monitoring system.
The CPU 1512SP-1 PN for ‘Rail DIN’ is a distributed controller. From the tables above the
minimum bit operation time for the CPU 317-2 PN/DP is 0.025 µs. This excludes the CPU
317-2 PN/DP from consideration; it does not meet the [CSD2] performance requirement.
Two CPUs meet the above requirements, the CPU 416-3 PN or the CPU 1516-3 PN/DP.
Selection of CPU can be based on other considerations.
The CPU 416-3 PN is programmed in STEP 7 or TIA Portal while the CPU 1516-3 PN/DP can
be programmed only in TIA Portal. These programming platforms are described in the chapter:
[Software]. Other system requirements can be used to make a final CPU selection. It is
recommended that you consult your ITER Control System Division representative should you
require assistance in selecting your CPU range.
Refer to chapter [Systems Composition] of this document for more information regarding each
of the CPU ranges.
[CSD3] The Application needs to send ‘16K’ of ‘process variables’ with a
‘communication rate’ of ‘150ms’ towards the ‘Central I&C System.
Last point is to confirm that the ‘communication performance’ provided for the selected ‘PLC
Configuration’ matches with what is needed for the application. Refer to the document [RD10]
to verify the ‘PLC Configuration’ chosen (by CSD1 and CSD2) is able to accomplish the
‘communication rate’ desired.
ITER_D_333J63 v4.1
Page 15 of 83
5.4 Remote IO Devices Selection
When selecting an IO rack you are confronted to the following choices:
o Medium : ET200M or ET200MP
o Small : ET200S or ET200SP
o Standard or Fail-Safe
SIMATIC ET200M – Medium Range Remote IO
The SIMATIC ET200M belongs to the S7-300 family.
The SIMATIC ET200M is a modular I/O station for the control cabinet with high density-
channel applications. Connection to PROFIBUS and PROFINET is achieved using interface
modules.
The ET200M can be used for standard as well as fail-safe applications. Up to 12 multi-channel
signal modules (e.g. 64 digital outputs) and a high range of different modules to use as
interface to process.
ET200M supports modules with expanded user data, e.g. HART modules with HART minor
variables. In addition to proven connection techniques the ET200M offers the insulation
displacement method FAST CONNECT for easy wiring.
Figure 6: ET200M
For more information see Section [Systems Composition] below and: SIMATIC ET200M
SIMATIC ET200MP – Medium Range Remote IO
The ET200MP belongs to the S7-1500 family.
The simple use of SIMATIC ET200MP is exemplified by a modular and scalable station with
the SIMATIC S7-1500 I/O modules in a distributed configuration. The modules have high
channel density and low parts variance. As a result, ordering, logistics and spare-parts
inventory are considerably simplified.
The ET200MP IO system with IP20 degree of protection is scalable and is used not only as a
central IO system for S7-1500, but also in a distributed configuration connected to PROFINET
or PROFIBUS. As many as 30 IO modules can be inserted into each station. The modules use a
limited variety of parts and the front connector is standardized for all 35mm wide modules.
Figure 7: ET200MP
For more information see Section [Systems Composition] below and: SIMATIC ET200MP
ITER_D_333J63 v4.1
Page 16 of 83
SIMATIC ET200S – Small Range Remote IO
The ET200S belongs to the S7-300 family.
The ET200S distributed I/O system is a discretely modular, highly flexible DP slave for
connection to process signals on a central controller or a field bus. ET200S supports field bus
types PROFIBUS DP and PROFINET IO. ET200S has a protection class IP20.
The ET200S is installed on a mounting rail.
Depending on the interface module, each ET200S can consist of up to 63 modules – for
example, power modules, I/O modules and motor starters.
For the solution of technological tasks, high-performance function modules are available that
perform these tasks largely autonomously and relieve the CPU significantly. Used directly
onsite; e.g. for counting, measuring and positioning tasks.
Figure 8: ET200S
For more information see Section [Systems Composition] below and SIMATIC ET200S
SIMATIC ET200SP – Small Range Remote IO
The ET200SP belongs to the S7-1500 family.
The I/O system ET200SP provides maximum usability, compact design, and high performance.
The ET200SP distributed I/O system is used for connecting process signals to a central
controller via PROFINET or PROFIBUS.
The ET200SP is installed on a mounting rail and generally comprises:
o An interface module, which communicates with all of the controllers that behave
according to the PROFINET standard IEC 61158
o Up to 64 I/O modules, which are plugged into passive base units in any combination
o A server module, which completes the structure of the SIMATIC ET200SP
The distributed I/O system is particularly easy to operate, and with its compact design it
achieves maximum economy in the control cabinet.
Figure 9: ET200SP
For more information see Section [Systems Composition] below and: ET200SP
ITER_D_333J63 v4.1
Page 17 of 83
ET200M(P) and ET200S(P) essential differences:
o Number of channels available. ET200M is highly integrated. One big module can
integrate up to 64 signals. (this catalogue restricts to 32 signals module)
o ET200S can be expended with compatible Siemens Frequency Converters.
o ET200S has faster analogue modules. So faster Control Loops can be achieved.
o ET200M is adapted to “Fast Connect” wiring solutions. ET200S have to be wired
directly on the module.
o An ET200S module is smaller than an ET200M and can be mounted on a simple DIN
Rail.
Extract of Siemens Catalogue ST70
ET200S ET200M
o Ex approval to Cat. 3 for Zone 2 acc.
to ATEX100 a
o Transmission rates up to 12 Mbit/s
o Ex approval to Cat. 3 for Zone 2 acc.
to ATEX100 a
o Transmission rates up to 12 Mbit/s
o Distributed I/O system to degree of
protection IP20 with minimal wiring
outlay, also for extremely time-critical
tasks such as high-speed closed-loop
controls
o Discretely-modular design for exact
adaptation to the automation task in
hand.
o Interface modules available with
PROFIBUS DP or PROFINET
interfaces
o Can be combined from digital and
analog in/output modules, technology
modules, motor starters and frequency
converters for the control of drives up
to 7.5 or 4 kW.
o Exchange of modules during operation
(hot swapping), permanent wiring with
multi-conductor connection
o Channel-specific diagnostics for high
availability
o Can be supplied with integrated fiber
optic interface if required
o FastConnect using unstripped quick
connection technology, screw or
o Modular I/O system with degree of
protection IP20, particularly suitable
for user-specific and complex
automation tasks
o Can be expanded with S7-300
automation system signal,
communication and function modules.
o Applicable Ex analogue input or
output modules with HART optimize
the ET 200M for use in process
engineering
o Can be used in redundant systems (S7-
400H, S7-400F/FH)
o Consists of a PROFIBUS DP IM 153
connection, up to eight or twelve I/O
modules of the S7-300 automation
system (assembly with bus
connections or active bus modules)
and if required a power supply
o Modules can be replaced during
operation (hot swapping) with the bus
modules active
o Can be supplied with integrated fiber
optic interface if required
o Fail-safe digital in/outputs as well as
ITER_D_333J63 v4.1
Page 18 of 83
spring-loaded terminals
o Slot reservation with spare modules
o Fail-safe DI modules with safety-
related signal processing according to
PROFIsafe
Option handling – for simples
management of machine options
analogue inputs for safety oriented
signal processing in accordance with
PROFIsafe
o Support of modules with expanded
user data, e.g. HART modules with
HART minor variables
The choice of Fail-Safe products is driven by the outcome of a specific analysis, according to
IEC61508 standard. In some cases you may need Hardware suitable for loops with SIL>=2.
ITER_D_333J63 v4.1
Page 19 of 83
5.5 Network Selection
First of all, let’s specify what type of communication networks the ITER Project will contain.
Central I&C System
Plant
System
Host
Slow
Controller
Slow
Controller
Slow
Controller
IO Module IO Module IO Module
IO Module IO Module IO Module
IO Module IO Module IO Module
1
2
3
2
Figure 10: Network Functional Segregation
In Figure 10, the network organization described in [RD6] is specified. The networks are
broken down in 3 communication groups:
- Group(1): The Communication between the Controller and the Central I&C Systems.
- Group(2): The Communication between Slow Controllers and their Field
Inputs/Outputs.
- Group(3): The Communication between the Controllers.
Group (1): is entirely covered by the Central I&C Networks.
Group (2): can be:
1. Field Network, based on Field bus: A Profibus network.
2. Field Network, Ethernet based network: Profinet.
In this cased it can be:
o Covered by the Physical Infrastructure of the Central I&C Networks
The Central Infrastructure is implemented exclusively using single-mode
Fibers.
o Covered by a physically independent network.
Group (3): is based on Ethernet, is using Siemens S7 Specific Protocols and it can be:
- Covered by the Central I&C Networks
- Covered by a physically independent network based on Ethernet called “Plant System
Local (Private) Network”.
ITER_D_333J63 v4.1
Page 20 of 83
A. Technology Selection
Group (2): To choose between Profibus or Profinet?
The choice between Profibus and Profinet is straightforward. By default the selected protocol
must be Profinet, but if the slaves support only Profibus and/or the requirements or
characteristics of your system make it necessary (i.e: OS safety), then Profibus must be
selected. Avoid heterogeneous architectures mixing Profinet and Profibus with bridges. If you
application has Profibus and Profinet slaves, then deploy both networks with the CPU as a
master.
Group (2) (Profinet case) and Group (3):
To choose between using the ‘Physical Infrastructure’ of the ‘Central I&C Networks’ or
a completely independent network?
It is difficult to give a strict decision tree. The table below just list advantages and
disadvantages of both solutions.
Central I&C Networks Infra Plant System Local (Private) Network
Advantages Nothing to do for the design.
Only give the number of
connections required to ‘Central
I&C Systems’.
No network Management. No
technical responsibility.
In case of failure of the network, the
recovery is instantaneous.
Administration at commissioning,
then nothing to do any more.
Disadvantages In case of failure in the higher
layers of the network, recovery
time might take seconds (4-6).
There is physical common mode
with the other networks.
Modification on other logical
networks might impact the
network.
Impact on the Design, interface with
cable trays, …
Magnetic Field and radiation
impacts to be assessed.
ITER_D_333J63 v4.1
Page 21 of 83
B. Field Network Architectures
For the FieldBus the protocol to use is PROFIBUS.
PROFIBUS (Process Field Bus) is a standard for fieldbus communication in automation
technology and was first promoted in 1989 by BMBF (German department of education and
research) and then used by Siemens.
For the FieldNet the protocol to use is PROFINET.
PROFINET (pitch acronym for Process Field Net) is an industry technical standard for data
communication over Industrial Ethernet, designed for collecting data from, and controlling,
equipment in industrial systems, with a particular strength in delivering data under tight time
constraints (on the order of 1ms or less).
CSD is advising, through this document, the use of only these two protocols: PROFINET
and PROFIBUS, as the standards to apply for any ‘Field Network Architecture’ of the
ITER project.
ITER_D_333J63 v4.1
Page 22 of 83
5.5.B.1 FieldBus (Profibus)
The picture below is showing an example of a Plant Control System with 4 Panels (Cubicles or
WMC) with Profibus network between the CPU and the IO modules. It is a Ring Physical
Topology. This is only possible with the usage of Fiber Optic Transceiver Modules. From the
application Layer, the Profibus is still seen as a BUS Topology.
The layout represents almost all the possible scenarios:
In ‘CU-0001’, you have the CPU of the PLC. It is connected by Profibus Copper cable to
the inputs/outputs module located in this same cubicle. Then, as a part of the Integration
KIT, you also have the switch and the PSH.
The Profibus network is extended outside the cubicle using Fiber Optics. The transceivers
modules (TS) are performing the conversion between copper Physical Layer and Optical
fiber physical layer. These modules performs several functions:
o Physical Layer Conversion.
o Repeater: One copper segment supports only 32 stations, while Profibus afford 128
stations. So each module support 32 stations, and the connection between them
allows using the full addressing range.
o Ring Management: Most of the providers of these modules allow a ring connection.
It means that a break in the ring will be managed instantaneously, and is
transparent to the application
In ‘CU-002’, the connection to the next cubicle is made of fiber optic pairs, routed in the
cable trays of the building. The concerned Plant System is fully in charge of the
management of this routing. (Interface with PBS44, etc…).
The copper segment bus can be extended to field devices
In ‘CU-003’, connexion to cubicles in another building could be made using the Central
I&C Systems dark fibers. The concerned Plant System must communicate it previously it
to CSD.
This has to be absolutely managed in the interface documents with PBS 45 (CODAC).
Topology :
The 2 network legs of the ring should preferably use 2 different routes (cable trays)
If field devices are located too far away from the cubicles, the bus can be extended with FO
to a WMC (wall mounted cubicle) embedding a Media Converter ( OLM)
The picture below is showing an example based in ‘Conventional Control’ architecture and it is
not necessarily shared for Interlock and Safety.
Reference PCDH satellite documents for more information regarding interlock or safety
networks.
ITER_D_333J63 v4.1
Page 23 of 83
Figure 11: FieldBus (Profibus) Network using independent infrastructure
ITER_D_333J63 v4.1
Page 24 of 83
5.5.B.2 Field Net (Profinet) using Central I&C Systems Physical Infrastructure.
Picture below is showing an example of a Plant Control System with 4 Panels (Cubicles or
Wall Mounted Cubicle) with Profinet Network between the CPU and the IO modules. The
Central I&C Networks are used as a Physical Layer (the Fiber Optic used in the Central I&C
Networks is a single-mode fiber).
The layout represents almost all the possible scenarios:
Cubicle “CU-0001” is embedding a PLC CPU, One Input/Output Rack, the PSH and the
Network Switch of the Integration Kit see [RD2]. The PLC and the Input/Output modules
are connected to the Network Switch using conventional copper Ethernet cables (CAT5).
The Switch is connected to the Central I&C Systems networks via the CNPs. It is
connected through 2 pairs (RX/TX) of Fiber Optics. This double connection assumes
redundancy in the Central I&C Systems network. See [RD2] for more details.
Panel “CU-0002” is an example of a Panel close to the “CU-0001”. The Remote I/O
modules can be connected to the network switch of “CU-0001”with regular Ethernet
copper cables (CAT5(E))
Panel “CU-0003” is an example of a Panel far away from “CU-0001”. An intermediary
network switch has to be installed. This switch must be chosen, in this same document, in
the chapter [Networks Composition]. The Remote I/O modules have to be connected to
this intermediary network switch. The connection to “CU-0001” is done through the
‘Central I&C Systems’ Networks via the CNP and also 2 pairs of Fiber Optics.
This has to be absolutely managed in the interface documents with PBS 45 (CODAC).
Cubicle “CU-0004” located in another building is exactly in the same conditions as “CU-
0003”. ‘Central I&C Systems’ is managing building interconnection; this is the big
advantage of this configuration.
This has to be absolutely managed in the interface documents with PBS 45 (CODAC).
The picture below is showing an example based in ‘Conventional Control’ architecture and it is
not necessarily shared for Interlock and Safety.
Reference PCDH satellite documents for more information regarding interlock or safety
networks.
ITER_D_333J63 v4.1
Page 25 of 83
Figure 12: FieldNet Network (Profinet) using ‘Central I&C Network’ infrastructure
ITER_D_333J63 v4.1
Page 26 of 83
5.5.B.3 FieldNet (Profinet) using independent physical infrastructure.
Figure below is showing an example of a Plant Control System with 4 Panels (Cubicles or
WMC) with Profinet network between the CPU and the IO modules. An independent network
is used as a Physical Layer. It is a Ring Physical Topology. The picture is representing almost
all the possible scenarios:
In “CU-0001”, the Ethernet Interface of the PLC CPU is connected to a DIN Rail
Manageable Switch. The Input /Outputs module is connected to this switch as well.
“CU-0002” is close to “CU-0001”, so the inputs/outputs modules are connected to the
switch of “CU-0001”with a copper cable. The copper cable is routed in the cable trays.
“CU-0003” is located somewhere else in the same building. So there is another
manageable Switch in the cubicle to connect the Inputs/Outputs modules. This switch is
connected to “CU-0003”with fiber optic pairs routed in the cable trays. The concerned
Plant System is fully in charge of the management of this routing. (Interface with
PBS44, etc…)
Profinet Slave devices can be also connected to this DIN Rail Manageable Switch.
“CU-004” is an extreme case, the cubicle is located in another building , so, it is
recommended to perform the connexion to panels in another building through the ‘Central
I&C Systems’ dark fibers (however every Plant System could select another way if the
suitability is improved). So the FO has to be connected to the ‘Central I&C Systems’
CNPs.
This has to be absolutely managed in the interface documents with PBS 45 (CODAC).
Topology :
All the DIN rail switches are connected in a ring configuration. The 2 network legs of the
ring should preferably use 2 different CNPs in order to avoid a common mode in the ring
routing.
The picture below is showing an example based in ‘Conventional Control’ architecture and it is
not necessarily shared for Interlock and Safety.
Reference PCDH satellite documents for more information regarding interlock or safety
networks.
ITER_D_333J63 v4.1
Page 27 of 83
Figure 13: FieldNet Network (Profinet) using independent infrastructure
ITER_D_333J63 v4.1
Page 28 of 83
5.5.B.4 Modbus
Modbus RTU and MODBUS TCP
Modbus RTU is an open, serial (RS-232 or RS-485) protocol derived from the Master/Slave
architecture. It is a widely accepted protocol due to its ease of use and reliability. Modbus RTU
is widely used within Building Management Systems (BMS) and Industrial Automation
Systems (IAS).
Modbus TCP/IP (also Modbus-TCP) is simply the Modbus RTU protocol with a TCP
interface that runs on Ethernet. The Modbus messaging structure is the application protocol
that defines the rules for organizing and interpreting the data independent of the data
transmission medium.
CSD, through this document, is advising against the use of MOBUS (as said only
PROFINET and PROFIBUS must be used in ITER Project).
However, exceptionally, if the circumstances of the particular Plant System make the use
of MODBUS absolutely necessary and unavoidable , its use could be allowed after
presenting the necessary justification and under the approval of the engineers in charge.
Two mandatory conditions to follow for the software and for the hardware.
Software:
For the programming of the ‘Modbus Communication’ it is mandatory to follow the document
[RD8].
Hardware:
CSD is providing the necessary HARDWARE to allow this communication. The selection of
other hardware is not allowed. Refer to [RD4].
In the figure below, suitable MODBUS RTU boards are exposed.
Figure 14 : Modbus RTU Network Layout
ITER_D_333J63 v4.1
Page 29 of 83
C. Plant System Local (Private) Network Architecture.
Two types of ‘inter communication’ between controllers are allowed in the ITER Standards:
- S7 Communication is a Siemens proprietary protocol that runs between programmable
logic controllers (PLCs) of the Siemens standard families.
- TCP Connection is taking advantage of the existing TCP/IP protocol to stablish the
communication link between the PLC devices.
In the ‘S7 Communication’, as well as, in ‘TCP Connection’ the communication has to be
programmed using dedicate blocks in every PLC involved.
5.5.C.1 Inter-Controllers communications using the Central I&C Networks.
In this case you are just using the Central I&C Networks as described in all the PCDH
documents to interconnect your controllers. Figure below is showing how practically to extend
your network.
The layout is showing an example of a Plant Control System with 4 Panels (Cubicles or WMC)
with S7 communications between a “Main” (Master, Server, …) PLC and “subordinated”
(Slaves, Clients,…) PLCs. The Central I&C Networks are supporting the ‘Inter-Controllers
communications’ and, in addition, ‘Central I&C Systems’ communications. . The figure is
representing almost all the possible scenarios:
Panel “CU-0001” is embedding a PLC CPU, the PSH and the Network Switch of the
Integration Kit, [RD2]. The PLC is connected to the Network Switch using conventional
copper Ethernet cables (CAT5 (E)).
The Switch is connected to the ‘Central I&C Systems’ networks via the CNPs. It is
connected through 2 pairs (RX/TX) of Fiber Optics. This double connection assumes
redundancy in the ‘Central I&C Systems’ network. See [RD2] for more details.
Panel “CU-0002” is an example of a Panel close to the “CU-0001”. The subordinated
PLC can be connected to the network switch of “CU-0001”with regular Ethernet copper
cables (CAT5(E))
Panel “CU-0003” is an example of a Panel far away from “CU-0001”. An intermediary
network switch has to be installed. This switch must be chosen in [Networks
Composition]. The subordinated PLCs have to be connected to this intermediary network
switch. The connection to “CU-0001” is done through the ‘Central I&C Systems’
Networks via the CNP and also 2 pairs of Fiber Optics.
This has to be absolutely managed in the interface documents with PBS 45 (CODAC).
Panel “CU-004”, located in another building, is exactly in the same conditions as “CU-003.
‘Central I&C Systems’ are managing building interconnections; this is the big advantage of
this configuration.
The picture below is showing an example based in ‘Conventional Control’ architecture and it is
not necessarily shared for Interlock and Safety.
Reference PCDH satellite documents for more information regarding interlock or safety
networks.
ITER_D_333J63 v4.1
Page 30 of 83
i
Figure 15 : Inter-Controllers (S7 communication) using the ‘Central I&C Network’
ITER_D_333J63 v4.1
Page 31 of 83
5.5.C.2 Inter-Controllers communications using independent physical architecture
Figure below is showing an example of a Plant Control System with 4 Panels (Cubicles or
WMC) with S7 Communications between a “Main” (Master, Server, …) Controller and
“subordinated” (Slaves, Clients,…) PLCs. An independent network is used as a Physical
Layer, generally referred at ITER as, Plant System Local Network. It is a Ring Physical
Topology.
The layout represents almost all the possible scenarios:
In “CU-0001”, the Ethernet Interface of the Communication Processor (“CP”) of the Main
“400-PLC” is connected to a DIN Rail Manageable Switch.
Important note: the CP requires 2 Ethernet connexions, as the first one is already
used by the connection to Central I&C Networks (CP440-1-Adv to be used).
“CU-0002” is close to “CU-0001”, the Ethernet Interface of a Communication Processor
(CP) of the “Subordinated” PLC is connected to the switch of “CU-0001” with a copper
cable. The copper cable is routed in the cable trays.
Important note: As in the figure below, if the PLC is a S7-300, then it will require a
second Communication Processor, as the first one is dedicated to connection to
Central I&C Networks.
“CU-0003” is located somewhere else in the same building. So there is another
manageable Switch in the cubicle to connect the Inputs/Outputs modules. This switch is
connected to “CU-0003” with fiber optic pairs routed in the cable trays. The concerned
Plant System is fully in charge of the management of this routing. (Interface with
PBS44, etc…)
In “CU-0004” it is recommended to perform the connexion to panels in another building
through the ‘Central I&C Systems’ dark fibers (however every Plant System could select
another way if the suitability is improved). So the FO has to be connected to the ‘Central
I&C Systems’ CNPs. This has to be absolutely managed in the interface documents
with PBS 45 (CODAC).
Topology :
All the ‘DIN Rail’ switches are connected in a ring configuration. The 2 network legs of
the ring should preferably use 2 different CNPs in order to avoid a common mode in the
ring routing.
It is recommended to connect all the ‘Slow Controllers’ to the ‘Central I&C Networks’,
however if this is not possible for the requirements or constraints of a particular system, so it is
the case in a ‘Plant System Local Network’, anyway the PLCs in this ‘private network’ must be
‘Time Synchronized’ with the ‘Central System Time Server’. It is strongly advised in this case
to use a ‘Time and Frequency Synchronization Platform’ to work in between two networks, to
get the ‘Time Synchronization’ information from a ‘Central Network’ and deliver it to the
‘‘Plant System Local Network’ in order to synchronize all the devices in there. Refer to
CODAC Department to get the specific data of the device.
The picture below is showing an example based in ‘Conventional Control’ architecture and it is
not necessarily shared for Interlock and Safety.
Reference PCDH satellite documents for more information regarding interlock or safety
networks.
ITER_D_333J63 v4.1
Page 32 of 83
Figure 16: Inter-Controllers (S7 Communication) using independent infrastructure
ITER_D_333J63 v4.1
Page 33 of 83
5.6 Central I&C Network accessing point Selection
A. Analysis of the Arguments
In order to get connected to the ‘central I&C Networks’ (in case of the ‘central I&C Systems’
infrastructure) the developer will be confronted to the choice: CP or CPU.
At the same time, in order to get connected to the ‘PROFINET Network’, the developer will be
confronted to the same choice: CP or CPU.
The present chapter summarizes the arguments to take in account in order to the select the
proper device to do such a task: the best point of connection (device/slot) to the ‘central
I&C Network’. This set of criteria is summarized below:
- For the ‘Central I&C Networks’ Communication
o Network Security
o Communication Performance to the ‘Central I&C Network’
o Reset of the communication with the ‘Central I&C Network’.
- For the Profinet Communication
o Number of slaves connected to Profinet Network
o Necessary Functions to implement Profinet Communication
o System Health Monitoring
These criteria are analysed against the three hardware families proposed in this catalogue: 300,
400 and 1500.
Below, the summary table with the capital arguments for every family of devices:
Device to
connect Subject
‘Central I&C Networks’ Communication Network security CP343-1-ADV The CP has the security functions : VPN, Firewall,
CPU317-2 The Ethernet interface of the CPU does not have the security functions.
CP443-1-ADV The CP has the security functions : VPN, Firewall
CPU416-3 The Ethernet interface of the CPU does not have the security functions.
CP1543-1 The CP has the security functions : VPN, Firewall
CPU1516-3 X2 Port X2 of CPU does not have security functions
CPU1516-3 X1 Port X1 of CPU does not have security functions
Communication Performance to the ‘Central I&C Network’
TCP/IP maximum data volume to send in a single command
CP343-1-ADV 32KB Data with Block AG-SEND with a CPU Bit Operation Performance of 25ns
But diminished for the [CP CPU] backplane serial bus of 1MB communication
CPU317-2 32KB Data with Block T-SEND with a CPU Bit Operation Performance of 25ns
CP443-1-ADV 32KB Data with Block AG-SEND with a CPU Bit Operation Performance of 12.5ns
But diminished for the [CP CPU] backplane parallel bus communication
CPU416-3 32KB Data with Block T-SEND with a CPU Bit Operation Performance of 12.5ns
CP1543-1 64KB Data with Block T-SEND with a CPU Bit Operation Performance of 10ns
ITER_D_333J63 v4.1
Page 34 of 83
Device to
connect Subject
But diminished for the [CP CPU] backplane serial bus communication
CPU1516-3 X2 64KB Data with Block T-SEND with a CPU Bit Operation Performance of 10ns
Reset of the Communication with Central I&C Networks CP343-1-ADV Reset of CP could be done using ‘SIEMENS Console’ connected through CPU
(without restarting CPU, so, not affecting buses attached to CPU interfaces)
CPU317-2
CP443-1-ADV Reset of CP could be done using ‘SIEMENS Console’ connected through CPU
(without restarting CPU, so, not affecting buses attached to CPU interfaces)
CPU416-3
CP1543-1 Reset of CP could be done using ‘Special Functions’: T-Reset
CPU1516-3 X2
Profinet Communication Number of slaves connected to Profinet Network CP343-1-ADV The CP can manage 32 devices
CPU317-2 The CPU (315 or 317) can manage 128 devices
CP443-1-ADV The CP can manage 128 devices
CPU416-3 The CPU (416-3 PN/DP) can manage 256 devices.
CP1543-1 The CP does not have Profinet capabilities
CPU1516-3 X1 CPU X1 can manage 256 devices
Necessary Functions to implement Profinet Communication CP343-1-ADV To communicate with the devices it is needed to add to the program the software
blocks ‘PNIO_SEND’ and ‘PNIO_RECV’
CPU317-2 To communicate with the devices no need to add software blocks
CP443-1-ADV To communicate with the devices no need to add software blocks
CPU416-3 To communicate with the devices no need to add software blocks
CP1543-1 The CP does not have Profinet capabilities
CPU1516-3 To communicate with the devices no need to add software blocks
System Health Monitoring CP343-1-ADV CP failed to do this job with the standard program used by ITER. Other methods may
succeed.
CPU317-2 CPU can extract System Health data
CP443-1-ADV CP can extract System Health data
CPU416-3 CPU can extract System Health data
CP1543-1 CP cannot extract System Health data ( no PROFINET)
CPU1516-3 CPU can extract System Health data
Every argument stated is corroborated with SIEMENS.
ITER_D_333J63 v4.1
Page 35 of 83
B. Outcome of the analysis
For the 300 Family:
- It is advised to use a CP to perform the connection to the ‘Central I&C Networks’.
- It is advised to use a CP to perform the connection to the ‘Plant System Local (private)
Network’.
- It is advised to use the CPU to perform the connection to the Field Devices Network.
For the 400 Family:
- It is advised to use a CP to perform the connection to the ‘Central I&C Networks’.
- It is advised to use a CP to perform the connection to the ‘Plant System Local (private)
Network’.
- It is advised to use the CPU to perform the connection to the Field Devices Network.
For the 1500 Family:
- It is advised to use a CP to perform the connection to the ‘Central I&C Networks’.
Note: The use of the ‘CPU [Port X2]’ to perform this connection, instead of a CP, could
be accepted if the security and performance of the controller’s configuration is not
endangered.
- It is advised to use CPU Port X1 to perform the connection to the Field Devices
Network
- It is advised to use CP to perform the connection to a Plant System Local (Private)
Network.
Communication Performance Tests between CODAC and the most representative PLC
Configurations are being run at the time this document is released.
This information will be summarized in [RD10].
ITER_D_333J63 v4.1
Page 36 of 83
5.7 Cubicle Monitoring System Selection
Cubicle Monitoring System is a mandatory requirement stated in the [R157] of the Plant
Control Design Handbook [RD1]:
- The I&C cubicles shall be equipped with a monitoring system for doors, temperature
and cooling monitoring and the monitoring system shall be interfaced to the plant
system I&C.
The detailed specification of the ‘Cubicle Monitoring System’ could be found in the ‘Chapter
7’ of the key document ‘I&C Cubicle Internal Configuration’ [RD7].
The solutions given are targeting the Conventional Control.
*In case the cubicle belongs to a Safety System please refer to the document [RD11].
A. Complete Solution for 1 cubicle
ITER is providing a standard complete solution for the monitoring of 1 single Cubicle.
This solution is already being widely used in the ‘Integration Kit [RD2]’ provided by CODAC
Section.
Target of the Solution:
So, this solution is targeting the monitoring of only 1 Cubicle
Figure 17 : Target of the solution for the monitoring of one single cubicle
Implementation of the solution:
Subject Reference Document
Electrical Diagrams I&C Integration Kit Cubicle Monitoring System(HMU)
Electrical Diagrams
Guide for the configuration
and start-up Guide for the configuration and start-up of the ITER
Standard Cubicle Monitoring System
Software SVN Link referenced in the ‘Guide for the Configuration and
start-up’
ITER_D_333J63 v4.1
Page 37 of 83
SIEMENS equipment involved in the solution:
TS90Ethernet Interface
RA
IL D
IN
CPU1214C
PON
Figure 18 : SIEMENS Hardware for CUB MON SYS 1 Single Cubicle
Short Designation QTY Description and Characteristics
CPU1214C 1
RAIL DIN
CPU 1214C 14DI, 10DO, 2AI
Power Supply 230V
*For the exact reference of every component please refer to [RD4].
*For the datasheet of the every product, use the reference and refer to SIEMENS Website.
B. Partial Solution for ‘2 to 11’ cubicles
ITER is providing a partial solution to monitor ‘from 2 to 11’ cubicles.
So, this solution is targeting the monitoring of a sets of cubicle, up to 11, placed in a row,
close, one after the other, or separated by small distances, less than 15 m.
Figure 19 : Target of the solution for the monitoring of ‘2 to 11’ Cubicles
ITER_D_333J63 v4.1
Page 38 of 83
Implementation of the solution:
Subject Reference Document
Electrical Diagrams
Current IDM Electrical Diagrams are not applicable
The Electrical Diagrams must be developed for the supplier.
The Electrical Diagrams presented in the ‘Complete solution
for 1 single cubicle’ could be used as a template for the
dedicated electric diagrams to every particular case.
Guide for the configuration
and start-up
Current IDM Guide is applicable.
Guide for the configuration and start-up of the ITER
Standard Cubicle Monitoring System
Software
Software is applicable
( SVN Link referenced in the ‘Guide for the Configuration and
start-up’)
- Hardware Configuration of the Project will need to be
modified. Adding the new IO Boards.
- PLC-Code is applicable ( No modification is necessary)
SIEMENS equipment involved in the solution:
TS90Ethernet Interface
RA
IL D
IN
CPU
1214
C
CPU1214C
PON
SM12
21-1
6DI
SM12
21-1
6DI
SM12
22-8
DO
SM12
31-8
AI
SM12
31-8
AI
SM1221-16DI SM1222-8DO SM1231-8AI
Figure 20 : SIEMENS Hardware for CUB MON SYS From ‘2 to 11’ cubicles
ITER_D_333J63 v4.1
Page 39 of 83
Short Designation QTY Description and Characteristics
CPU1214C 1
RAIL DIN
CPU 1214C 14DI, 10DO, 2AI
Power Supply 230V
SM1221-16DI 2 ● 16 Digital Input for S7-1200
SM1222-8DO 1 ● 8 Digital Output for S7-1200
SM1231-8AI 2 ● 8 Analogue Input for S7-1200
SM1231-8AI 2 ● 8 Digital Output for S7-1200
*For the exact reference of every component please refer to [RD4].
*For the datasheet of the every product, use the reference and refer to SIEMENS Website.
ITER_D_333J63 v4.1
Page 40 of 83
6 SYSTEMS COMPOSITION
6.1 Slow Controllers Range
A. Low (distributed) Range of Slow Controllers
Low range controllers are the intelligent choice for applications in the low to mid-performance
range. They are modular, small, compact and cost-effective. The objective is to achieve flexible
solutions for simple networking with integrated and optional communications connections.
The decentralization of intelligence helps hugely in making machines and plants more flexible
and is thus becoming a decisive competitive factor. Increasing networking makes possible to
integrate autonomous, intelligent units at the field level into the system-wide communication
system. The remote I/O systems capabilities can be expanded using integral, intelligent
controllers. This gives rise to distributed controllers.
6.1.A.1 Low (Distributed) Range PLCs: [S7-1500] CPU + IO Rack
Exceptionally, if the needs of the process are extremely limited and the segregation of the
functionalities in different controllers a main objective for the particular Control System the
use of the Distributed [CPU + IOs] could be suitable.
However, even in the case stated above the use of the ‘Distributed Remote I/O Modules’ in
their small version is highly recommended.
- The fact of using a PLC, uniquely, as a ‘Data Transmitter’ to a higher control instance
is not wise from a ‘Control System’ point of view. This is precisely the job of a
Distributed I/O Module.
- The fact of placing several controllers dedicated to control different functions of the
same Plant system in the same cubicle or contiguous cubicles is not wise from a
Cubicle configuration point of view.
The ‘Distributed CPU’ is using as a background support the Standard RAIL DIN.
The ‘I/O Modules’ to be attached to the CPU correspond to the ‘S7-1500 Small Range’
subfamily (ET200SP) and their background support is, as well, the standard RAIL DIN.
It is recommended to place the modules in the following order:
- Digital Inputs
- Digital outputs
- Analog Inputs
- Analog outputs.
The concern is not technical. The idea is to have same I/O structures on all racks.
ITER_D_333J63 v4.1
Page 41 of 83
Figure 21 : Distributed Rack [S7-1500 + IO] exploded view
Short Designation QTY Description and Characteristics
CPU1512SP-1 1 CPU1512SP-1 characteristics detailed in the datasheet.
TM-P-SP 1 Terminal Module for Power Supply
TM-E-SP (1..n)-1 Terminal Module for Power Supply Bridge
Monitors the supply voltage
Diagnostics support
Rated voltage 24VDC
SM131SP-16DI 1..n 16 DI Module, Module Diagnostic
SM132SP-16DO 1..n 16 DO Module, Module Diagnostic
SM134SP-4AI 1..n 4AI U/I Input Module, Module Diagnostic
SM134SP-4RTD/TC 1..n 4 RTD/TC input Module High Feature. Diagnosis
SM134SP-8AI-U 1..n 8 AI "U" Input Module, Diagnosis
SM134SP-8AI-I 1..n 8 AI "I" 2-/4-WIRE Input Module, Diagnosis
SM135SP-4AO 1..n 4 U/I Output Module, Diagnosis
*For the exact reference of every component please refer to [RD4].
*For the datasheet of the every product, use the reference and refer to SIEMENS Website.
ITER_D_333J63 v4.1
Page 42 of 83
B. Medium Range of Slow Controllers
The perfect alternative for the mid-range applications; medium controllers offer the features
and flexibility needed without the overhead of larger systems, but suitable for medium and
complex applications. Medium controllers with modular expansion capability are long-term
compatible, maintenance-free, scalable and include safety certified. They are the ideal solution
for any automation task.
6.1.B.1 Mid-range PLCs: [S7-300 or S7-1500] CPU Rack
6.1.B.1.1 S7-300: CPU Rack
The S7-300 is the modular PLC system for the low and mid-performance ranges. In ITER, a
small plant system which requires medium range of performances could perfectly work using
these mid-range PLCs.
The backplane is the regular one, without Hot Swapping capability.
In the figure below, two possible configurations for the Ethernet Communication Processor
(CP343) are presented:
First configuration ( Standard one ) :
o A connection to a Profinet Network
o A connection to the Central I&C Networks
The connection to Profinet is made through the CPU Ethernet Port. The connection to
the Central I&C Networks through the CP343-1 Ethernet Port (the CP has 2 Ethernet
slots, but it is the same Ethernet connection)
Second configuration ( In case of Plant System Local (private) Network ) :
o A connection to a Profinet Network,
o A connection to a Plant System Local (Private) Network.
o A connection to the Central I&C Networks
The connection to Profinet is made through the CPU Ethernet Port. The connection to
the Plant System Local (Private) Net through the “X1” Interface of the CP343-1-Adv
and the connection to the Central I&C Networks through the “X2” Interface. Another
possibility is to add a new CP343-1 for the Plant System Local (private) Network.
ITER_D_333J63 v4.1
Page 43 of 83
Figure 22: Rack s7-300 exploded view.
ITER_D_333J63 v4.1
PLC Software Engineering Handbook Page 44 of 83
Short Designation QTY Description and Characteristics
RAIL-19IN 1 Rail 19"
PS300-5A 1 PS 300 5A (1 Slot)
MMC-2M-EEPROM 1 Micro Memory Card 2MB (Upto 8 MB Max)
CPU317-2 1 CPU 317-2 PN/DP (2x Eth) Central Unit.
Detailed information in [System Selection].
Detailed characteristics in datasheet.
CP343-1 1 Communication Processor Ethernet
16 Connections maximum
Profinet
1 x Ethernet Port
SEND/RECEIVE:
ISO-on-TCP: 8Kb
TCP/IP: 8Kb
UDP : 2Kb
S7 communications
Web based diagnostic
DHCP Client
NTP Client
SNMP v1
CP343-1-Adv 1 Communication Processor Ethernet
16 Connections maximum
Profinet
2 x Ethernet Port
SEND/RECEIVE:
ISO-on-TCP: 8Kb
TCP/IP: 8Kb
UDP : 2Kb
S7 communications
Web based diagnostic
DHCP Client
NTP Client
SNMP v1
*For the exact reference of every component please refer to [RD4].
*For the datasheet of the every product, use the reference and refer to SIEMENS Website.
ITER_D_333J63 v4.1
Page 45 of 83
6.1.B.1.2 S7-1500: CPU Rack
The S7-1500 is the modular PLC system for the mid-performance ranges. In ITER a small or
medium plant system which requires medium range of performances could perfectly work with
these Mid-range PLCs.
The backplane is the regular one for the 1500 family, without hot Swapping capability.
In the below, it is presented the basic configuration proposed for the ‘1500 family’.
Connection to Central I&C Networks
The connection to Central I&C Networks will be made through the Ethernet Port of the
CP 1543-1, installed in the second slot.
Connection to the FIELD (Remote IO) : FieldBus or FieldNet
The connection to Profinet will be made through the CPU Ethernet Port X1.
The connection to Profibus will be made through the CPU Profibus Port.
In case of Plant System Local (Private) Net
Connection to Plant System Local (Private) Network (S7 Comm. between PLCs).
Another CP will be installed (CP1543-1) in the third slot.
The connection to the ‘Plant System Local Network’ will be made through the Ethernet
Port of CP1543.
ITER_D_333J63 v4.1
Page 46 of 83
Figure 23: Rack S7-1500 exploded view
ITER_D_333J63 v4.1
Page 47 of 83
Short Designation QTY Description and Characteristics
RAIL-1500-19IN 1 1500 MOUNTING RAIL 482 MM
PS1500-3A 1 PS 1507 24 V/3 A STABILIZED POWER SUPPLY
MMC-24M-EEPROM 1 SIMATIC S7, MEMORY CARD FOR S7-1X00
CPU/SINAMICS, 3,3 V FLASH, 24 MBYTE
CPU1516-3 1 CPU 1516-3 PN/DP Central Unit.
Detailed information in [System Selection].
Detailed characteristics in the datasheet.
CP1543-1 1 Communication Processor Ethernet CP1543-1. Detailed
characteristics in datasheets.
Interfaces 1 Ethernet Interface
Performance
Data
118 Connections maximum (S7 and
Open Communication)
ISO-on-TCP by means of T Blocks:
64Kb
Protocols
Supported
S7/Open Communication
DCP
NTP
SNMP v1
Product
Function
Web Based Diagnostic
*For the exact reference of every component please refer to [RD4].
*For the datasheet of the every product, use the reference and refer to SIEMENS Website.
ITER_D_333J63 v4.1
Page 48 of 83
6.1.B.2 Mid-range PLC with local IO: [S7-300 or S7-1500] CPU+IO Rack
6.1.B.2.1 S7-300: CPU+IO Rack
If the needs are very limited, a single rack with CPU+IOs may be sufficient. The first part is
identical to the CPU rack described in chapter [S7-300 CPU Rack]. The following boards are
Inputs/Outputs modules, of all the kind, detailed in the table below. Up to 7 modules can be
added after the Communication Processor CP343-1. If no communication modules appear in
the configuration, then, up to 8 modules can be added.
It is recommended to place the modules in the following order:
Special modules (RS232/RS485,…)
Digital Inputs
Digital outputs
Analog Inputs
Analog outputs.
The concern is not technical. The idea is to have same I/O structures on all racks.
Figure 24: Rack S7-300 + IO exploded view
ITER_D_333J63 v4.1
Page 49 of 83
Short Designation QTY Description and Characteristics
CP341-1 1 Communication Processor RS232,RS422,RS485
SM321-32DI n Digital Input Module, 32 DI, 24V, 500 V DC isolated
SM321-16DI n Digital Input Module, 16 DI Module with Channel
Diagnostics
SM322-32DO n Digital Input Module, 32 DO, 24V, 500 V DC isolated
SM322-8DO n Digital Input Module, 8 DO, 24V, 500 V DC isolated with
Channel Diagnostics
SM331-8AI n Analog Input Module, 8 AI, 500 V DC isolated, 15 bits,
Diagnostic Status
SM332-8AO n Analog Input Module, 8 AO, 500 V DC isolated, 12 bits,
Diagnostic Status
*For the exact reference of every component please refer to [RD4].
*For the datasheet of the every product, use the reference and refer to SIEMENS Website.
ITER_D_333J63 v4.1
Page 50 of 83
6.1.B.2.2 S7-1500: CPU+IO Rack
If the needs are very limited, a single rack with CPU+IOs may be sufficient. The first part is
identical to the CPU rack described in the chapter [S7-1500: CPU Rack]. The following
boards are Inputs/Outputs modules, of all the kind, described in the following table. Up to 31
modules can be added after the CPU1516.
So, the Communication Processor will take the place right after the CPU1516, then 30 modules
more could be added.
It is recommended to place the modules in the following order:
Special modules (CM-PTP,…)
Digital Inputs
Digital outputs
Analog Inputs
Analog outputs.
The concern is not technical. The idea is to have same I/O structures on all racks.
Figure 25 : Rack S7-1500 + IO exploded view
ITER_D_333J63 v4.1
Page 51 of 83
Short Designation QTY Description and Characteristics
CM-PTP 1 Communication Module CM 1541-1 for Serial RS422,
RS485
SM521-32DI n 32 DI module with Diagnostics
SM522-32DO n 32 DO Module with Diagnostics
SM531-8AI n 8 Analog Inputs Module U/I/RTD/TC with Diagnosis
SM532-8AO n 8 Analog Outputs Module U/I with Diagnosis
*For the exact reference of every component please refer to [RD4].
*For the datasheet of the every product, use the reference and refer to SIEMENS Website.
ITER_D_333J63 v4.1
Page 52 of 83
6.1.B.3 Mid-range Fail Safe PLCs: [S7-300 or S7-1500] CPU rack
Safety Configurations are used to control processes and adopt or remain in a safe state as soon
as an error occurs. They provide a consistent and efficient safety concept in plants with
increased safety requirements.
Safety Configurations will be used by Safety an Interlock systems. Specific information about
systems composition and network connectivity could be found, for these two ‘Control System’
vertical tiers, in their dedicated documentation; refer to [RD1].
However, an important detail to remember is that S7-300F for the OS can only be used for
local functions; central functions require a S7-400.
6.1.B.3.1 S7-300 “F” CPU rack
S7-300 “F” systems are medium range Fail safe systems provided by Siemens.
PS300-5A
CP343-1
RAIL-19IN
CPU Profibus DP Interface
CPU Ethernet Interface
CP343-1 Ethernet Interface
MMC-2MB-EEPROM
CPU 315F-2 PN/DP
Figure 26: Fail Safe, High range PLCs S7300F
Short Designation QTY Description and Characteristics
RAIL-19IN 1 Rail 19"
PS300-5A 1 PS 300 5A (1 Slot)
CPU315F 1
CPU 315F-2 PN/DP (detailed information in datasheet).
Software STEP 7 V 5.5 or higher,
Distributed Safety V 5.4 SP4
MMC-2M-EEPROM 1 Micro Memory Card 2MB
CP343-1 1 Communication Processor Ethernet
*For the exact reference of every component please refer to [RD4].
*For the datasheet of the every product, use the reference and refer to SIEMENS Website.
ITER_D_333J63 v4.1
Page 53 of 83
6.1.B.3.2 S7-1500 “F” CPU rack
S7-1500 “F” systems are medium range Fail safe systems provided by Siemens.
It is important to remember that at the time of the release of this document the ‘CSD-PCI-
Safety’ department guidelines do not cover yet this PLC. Please refer to the ‘CSD-PCI-Safety’
department to get the last update if you are willing to use this PLC for a Safety application.
Figure 27 : Fail Safe, High range PLCs S71500F
Short Designation QTY Description and Characteristics
RAIL-1500-19IN 1 1500 MOUNTING RAIL 482 MM
PS1500-3A 1 PS 1507 24 V/3 A STABILIZED POWER SUPPLY
CPU1516F-3 1
CPU 1516-3 PN/DP Fail Safe CPU (detailed info in datasheet)
Software TIA Portal V14 SP1 or higher
Safety Advanced v14
CP1543-1
1
Communication Processor Ethernet CP1543-1.
*For the exact reference of every component please refer to [RD4].
*For the datasheet of the every product, use the reference and refer to SIEMENS Website.
ITER_D_333J63 v4.1
Page 54 of 83
C. High Range of Slow Controllers
High Range Slow Controllers are suitable for the most demanding application needs. They
offer modular architectures and a wide spectrum of I/O and network options. These powerful
control solutions deliver world-class capabilities from process to safety to motion. Designed
for distributed or supervisory control applications, high range programmable automation
controllers provide multi-computing skills, modularity, exceptional reliability, performance
and diagnostic abilities.
6.1.C.1 High range PLCs: S7-400
The Figure 28 represents two kinds of configurations for the Ethernet Communication
Processor (CP443-1).
First configuration (standard configuration):
o A connection to a Profinet Network,
o A connection to the Central I&C Networks.
The connection to Profinet is made through the CPU Ethernet Port.
The connection to the ‘Central I&C Networks’ is made through the CP 443-1 Ethernet
Port. The CP has 2 Ethernet ports, but it is the same Ethernet connection.
Second configuration (in case of Plant System Local (Private) Net):
o A connection to a Profinet Network,
o A connection to a Plant System Local (Private) Network
o A connection to the Central I&C Networks.
The connection to Profinet is made through the CPU Ethernet Port.
The connection to the Plant System Local (Private) Network is made through the “X1”
Interface of the CP 443-1-Adv and the connection to the Central I&C Networks through
the “X2” Interface of the CP 443-1-Adv.
ITER_D_333J63 v4.1
Page 55 of 83
Figure 28: Rack S7-400 exploded view.
ITER_D_333J63 v4.1
Page 56 of 83
Short Designation QTY Description and Characteristics
UR2 1 Chassis 400 UR2 9 Slots
PS400-10A 1 PS 400 10A
BAT-400 2 Back Up Battery 400
PCCARD-4MB-RAM 1 Memory PC Card 4MB RAM
PCCARD-8MB-RAM 1 Memory PC Card 8MB RAM
PCCARD-16MB-RAM 1 Memory PC Card 16MB RAM
CPU416-3 1 CPU 416-3 PN/DP Central Unit.
Detailed information in [System Selection].
Detailed characteristics listed in datasheet.
CP443-1 1 Communication Processor Ethernet
96 Connections maximum
Profinet
SEND/RECEIVE:
ISO-on-TCP: 8Kb
TCP/IP: 8Kb
UDP : 2Kb
Open IE (“T” Blocks)
ISO-on-TCP: 1452 Bytes
S7 communications
http server
DHCP Client
NTP Client
SNMP v1
CP443-1-ADV 1 Communication Processor Ethernet “Advanced”.
This CP has 2 interfaces, and supports some more protocols.
For each Interface:
96 Connections maximum
Profinet
IRT
SEND/RECEIVE:
ISO-on-TCP: 8Kb
TCP/IP: 8Kb
UDP : 2Kb
Open IE (“T” Blocks)
ISO-on-TCP: 1452 Bytes
S7 communications
http server
DHCP Client
NTP Client
SNMP v1
FTP
*For the exact reference of every component please refer to [RD4].
*For the datasheet of the every product, use the reference and refer to SIEMENS Website.
ITER_D_333J63 v4.1
Page 57 of 83
6.1.C.2 High range Fail Safe PLCs: S7-400 “F” CPU rack
Safety systems are used to control processes and adopt or remain in a safe state as soon as an
error occurs. They provide a consistent, efficient safety concept in plants with increased safety
requirements. S7-400 “F” systems are high range Fail safe systems provided by Siemens.
The hardware is exactly the same at what is shown in the redundant configuration, but in a
Single Configuration (either CP443-1 or CP443-1-ADV can be used depending of the needs of
the system)
These systems will be used by Safety an Interlock systems. More information regarding
network connectivity can be found in the documentation of these systems.
Figure 29: Fail Safe, High range PLCs S7400F
Short Designation QTY Description and Characteristics
UR2 1 Chassis 400 UR2 9 Slots
PS400-10A 1 PS 400 10A
BAT-400 2 Back Up Battery 400
ITER_D_333J63 v4.1
Page 58 of 83
PCCARD-4MB-RAM
(or FLASH)
1 Memory PC Card 4MB RAM
CPU414-H 1 CPU 414-5H PN/DP. Detailed characteristics listed in
datasheets.
Memory Work memory
Integrated 4 Mbyte
Integrated (for program) 2 Mbyte
Integrated (for data) 2 Mbyte
Load memory
Expandable FEPROM, max. 64
Mbyte
Integrated RAM, max. 512 Kbyte
Expandable RAM, max. 64
Mbyte
Address Area I/O address area
Inputs 8 Kbytes
Outputs 8 Kbytes
Process Images
Inputs 8 Kbytes
Outputs 8 Kbytes
Profibus DP
Interface First Interface:
RS 485 / PROFIBUS + MPI ,
MPI + DP Master,
32 Max DP Slaves
Second Interface:
RS 485 / PROFIBUS,
DP Master,
96 Max DP Slaves
Ethernet
Interface 64 connections maximum
Profinet
open ie,
o TCP : 32Kb
o ISO-on-TCP : 32Kb
o UDP : 1452 Bytes
S7 communications
Integrated Switch
Software STEP 7 v5.5 SP2 with HF1
(or CPU416-H)
(or CPU417-H)
CP443-1 1 Communication Processor Ethernet
CP443-1-ADV 1 Communication Processor Ethernet Advanced
*For the exact reference of every component please refer to [RD4].
*For the datasheet of the every product, use the reference and refer to SIEMENS Website
ITER_D_333J63 v4.1
Page 59 of 83
6.1.C.3 High Range, High Availability PLCs: S7-400 “H” CPU Rack
In addition to the Failsafe feature, this PLC configuration presents High Availability: it is
redundant.
These devices will be used for Safety an Interlock control systems. More information
regarding network connectivity can be found in the documentation of these systems.
A highly availability controller minimizes the probability of production failures and thus
decisively contributes to maximum productivity and safety.
Picture below represents the complete architecture of a S7-400FH. Three noticeable facts:
Connection to ‘Remote I/Os’ is made through Profibus or Profinet, using the interfaces that
the CPU provides. And preferably stablishing rings ‘Profinet Redundant Ring’ or ‘Profibus
Redundant Ring’ in order to make the ‘IO Network’ more reliable.
The connection to the Central I&C Networks is still established through a CP while there is
an Ethernet connection on the CPU.
o Previously the CPU414-4H itself didn’t have an Ethernet connexion, so the CP was
required. Now the systems CPU416-H and CPU417-H already have Ethernet Port
included in the CPU, but the recommendation remains the same : use CP.
Configuration of the two redundant backplane shall be exactly the same. They are twins.
Figure 30: High availability PLCs architecture
*At the moment of the release of this document, the connexion to the Central I&C Networks
for Conventional Control, through on-board Ethernet Connexion of a Redundant PLC is being
tested. Please refer to ‘Control System Division’ to know the last update of the tests if you are
willing to use it.
ITER_D_333J63 v4.1
Page 60 of 83
Here below the advantages of using high availability PLC Configuration:
Highest system availability with early fault detection and integrated diagnostic
capabilities
Efficient solutions with scalable performance and redundancy
Simple programming and configuration
Performance-oriented solution for time-critical processes
Synchronized hardware solution without information loss
Highly available communication via Industrial Ethernet
Integrated diagnostic functions
Exchange of all components during operation ( hot swapping)
The figure below shows a S7-400H Configuration in detail:
UR2-2x9
CPU4146-H
PS400-1
0A-KR
PS400-1
0A-KR
CP443-1
PS400-10A-KR
CP443-1
SYNC-10KM-5H
PCCARD-4MB-FLASH
PCCARD-4MB-RAM
SYNC-10M-5H
2 x UR2
CPU414-H
PS400-1
0A-KR
PS400-1
0A-KR
CP443-1EX20
RACK “A” RACK “B”
Sync
Sync
F0-10M
F0-2M
PON
CPU416-H
4xBAT400
CP443-1-ADV Ethernet Interface
“X1”
CP443-1-ADV Ethernet Interface
“X2”
PON
Private Net(S7)
CP443-1-ADV
Replace CP443-1 of every
RACK for
In case of PS Local (private) Network
PON
Figure 31: High availability PLCs S7-400H
ITER_D_333J63 v4.1
Page 61 of 83
Both stations are connected to each other with Synchro modules and fiber cables.
o Be careful with references, the older references for previous CPU414H are still
available for spare parts, they are not compatible with the new generation “5H”.
There are 2 types of Synchro Modules:
o For a distance of up to 10 m,
o For a distance up to 10Km.
Siemens provides 10m and 2m cables. For longer distances, cables shall be bought to
specific providers.
2 different backplanes of 9 slots must be used if each S7-400 CPU is installed in different
cubicles. Otherwise, in the same cubicle, a 2x9 backplane has to be used. Be careful it is
not a regular 18 slots backplane!
Plant System Local (private) Net is optional, depending of the needs of the Plant System. In
case this is necessary, a supplementary CP443-1 must be installed or the current CP443-1
(appearing in the drawing above) must be replaced for a CP443-1-Adv.
Short Designation QTY Description and Characteristics
UR2-2x9 1 Chassis 400 UR2H 18 Slots (2x9)
UR2 2 Chassis 400 UR2 9 Slots
PS400-10A-KR 4 PS 400 10A For Redundant Rack
BAT-400 8 Back Up Battery 400
PCCARD-4MB-RAM
(or FLASH)
2 Memory PC Card 4MB RAM
CPU416-H
(or CPU414-H)
(or CPU416-H)
2 CPU 416-5H PN/DP Central Unit. Detailed characteristics
listed in datasheets.
Memory Work memory
Integrated 16 Mbyte
Integrated (for program) 6 Mbyte
Integrated (for data) 10 Mbyte
Load memory
Expandable FEPROM, max. 64
Mbyte
Integrated RAM, max. 1Mbyte
Expandable RAM, max. 64
Mbyte
Address Area I/O address area
Inputs 16 Kbytes
Outputs 16 Kbytes
Process Images
Inputs 16 Kbytes
ITER_D_333J63 v4.1
Page 62 of 83
Outputs 16 Kbytes
Profibus DP
Interface First Interface:
RS 485 / PROFIBUS + MPI ,
MPI + DP Master,
32 Max DP Slaves
Second Interface:
RS 485 / PROFIBUS,
DP Master,
125 Max DP Slaves
Ethernet
Interface 96 connections maximum
Profinet
open ie,
o TCP : 32Kb
o ISO-on-TCP : 32Kb
o UDP : 1452 Bytes
S7 communications
Integrated Switch
Software STEP 7 v5.5 SP2 with HF1
FO-2M 2 Synchro Cable FO 2m
FO-10M 2 Synchro Cable FO 10m
SYNC-10M-5H 2 Synchro Module FO 10m compliant 414-5H
SYNC-10KM-5H 2 Synchro Module FO 10km compliant 414-5H
CP443-1 2 Communication Processor Ethernet
*For the exact reference of every component please refer to [RD4].
*For the datasheet of the every product, use the reference and refer to SIEMENS Website
ITER_D_333J63 v4.1
Page 63 of 83
6.2 Remote I/O Modules Range
A. Small I/O modules [S7-300 or S7-1500]
Distributed I/O systems are particularly easy to operate, and with its compact design it achieves
maximum economy in the control cabinet. Their high speed and transmission rate ensure
significantly greater performance than conventional systems. Several modules have been
identified in ITER.
The CPUs 300/400/1500 work with these modules remotely.
Two types of ‘Distributed I/O’ are presented in the catalogue:
- ET200S for the S7-300 Family
- ET200SP for the S7-1500 Family
6.2.A.1 S7-300 Family: ET200S
Figure 32 is showing how to build the system.
The configuration can have up to 63 signal modules in an ET200S. A Power Module (PM-E)
is placed in front of a bank of signals modules. The maximum number of signal modules for a
bank depends on the current consumption. A Terminal Module (TM-E) can drive up to 8A.
ET200S modules have hot swapping capability.
PM-E module requires a TM-P base. SMs modules require TM-E bases.
Figure 32: ET200S Modules exploded view
ITER_D_333J63 v4.1
Page 64 of 83
Short Designation QTY Description and Characteristics
IM151-1 HF 1 Interface Module for linking ET200S to Profibus DP.
Supports DP V0 and DP V1
Connection type RS485
IM151-3 1 IM151-3 PN Interface module for ET200S IO modules
Interface module for linking the ET 200S to PROFINET
Integrated 2-port switch
MMC-128K-EEPROM Micro Memory Card 128 KB
TM-P 1 TM-P Terminal Module for Power Supply
PM-E 1 Power Module for PM-E electronic Module
TM-E (1..n) -1 Terminal Module for Power Supply Bridge
Monitors the supply voltage
Diagnostics support
Rated voltage 24VDC
Electrical isolation
SM131-8DI 1..n Digital Input Module, 8 DI, 24V, 500 V DC isolated
SM131-8DO 1..n Digital output Module, 8 DO, 24V, 500 V DC isolated
SM134-2AI 1..n Analog Input Module, 2 AI, 500 V DC isolated, 14 bits,
Diagnostic Status
SM134-2TC 1..n Thermocouple Module, 2 AI, 500 V DC isolated, 16 bits,
Diagnostic Status
SM134-2AO 1..n Analog Output Module, 2 AO, 13 bits, 500 V DC isolated,
Diagnostic Status
SM134-2RTD 1..n RTD Module, 2 AI, 16 bits, 500 V DC isolated, Diagnostic
Status
*For the exact reference of every component please refer to [RD4].
*For the datasheet of the every product, use the reference and refer to SIEMENS Website
ITER_D_333J63 v4.1
Page 65 of 83
6.2.A.2 S7-1500 Family: ET200SP
Figure below is showing how to build the system.
The configuration can have up to 32 signal modules. The first ‘I/O board’ will need a Terminal
Power Module (TM-P-SP), so, this is placed in the first position, top left (this is necessary to
feed the whole process downstream of the ET200SP). Right after, every ‘I/O board’ will need
one Terminal Follower Module (TM-E-SP).
The maximum number of signals for a bank depends on the current consumption. A TM-P-SP
can drive up to 10A.
ET200SP modules have hot swapping capability.
Figure 33: ET200SP Modules exploded view
ITER_D_333J63 v4.1
Page 66 of 83
Short Designation QTY Description and Characteristics
IM155DP-6DP-HF 1 Interface Module to link ET200SP to Profibus DP.
Supports DP V0 and DP V1
Connection type RS485
IM155PN-6DP-ST 1 Interface Module to Link ET200SP to PROFINET
Integrated 2 port Switch
TM-P-SP 1 Terminal Module for Power Supply
TM-E-SP (1..n)-1 Terminal Module for Power Supply Bridge
Monitors the supply voltage
Diagnostics support
Rated voltage 24VDC
SM131SP-16DI 1..n 16 DI Module, Module Diagnostic
SM132SP-16DO 1..n 16 DO Module, Module Diagnostic
SM134SP-4AI 1..n 4AI U/I Input Module, Module Diagnostic
SM134SP-4RTD/TC 1..n 4 RTD/TC input Module High Feature. Diagnosis
SM134SP-8AI-U 1..n 8 AI "U" Input Module, Diagnosis
SM134SP-8AI-I 1..n 8 AI "I" 2-/4-WIRE Input Module, Diagnosis
SM135SP-4AO 1..n 4 U/I Output Module, Diagnosis
*For the exact reference of every component please refer to [RD4].
*For the datasheet of the every product, use the reference and refer to SIEMENS Website
ITER_D_333J63 v4.1
Page 67 of 83
B. Medium I/O modules [S7-300 or S7-1500]
6.2.B.1 S7-300 Family: ET200M
ET200M is a modular I/O system used for user-specific and complex automation tasks:
o Used with S7 SIEMENS automation system to expand signals , communication and
function modules :
o In CPUs S7-300 in both local and Remote
o In CPUs S7-400 & S7-400H in Remote
o In CPUs S7-1500 in remote
o Supports PROFIBUS DP and PROFINET interface module
o Modules can be replaced during operation (hot swapping) with the bus modules active.
Attention must be paid to the type of base module:
o PS300-5A and IM must be place on a “BM-PS-IM153” base module.
o SM modules must be placed on “BM-sx40 base” modules.
o If the architecture is redundant, the IM153-2 modules must by placed on “BM-IM153-
IM153” base modules
If the configuration uses Profibus, you can set up to 8 SM modules.
If the configuration uses Profinet, you can set up to 12 SM modules.
RAIL-19IN-HS
PS300-5
A
SM321-3
2DI
IM153-4
SM322-3
2DO
SM332-8
AI
SM331-8
TC
PS300-5A
IM153-4 IM153-2OR
IM Profibus DP Interface
IM ProfiNet Interface
RAIL-19IN-HS
BM-PS-IM153
BM-2x40 BM-2x40 BM-2x40
MMC-128K-EEPROM
Figure 34: ET200M Modules
See Table below
ITER_D_333J63 v4.1
Page 68 of 83
Figure 35: ET200M Modules to use with s7-400”H”
Short Designation QTY Description and Characteristics
RAIL-19IN-HS 1 Mounting Rail Hot SWAP length: 19 Inches, up to 5 bus
modules
PS300-5A 1 PS 300 5A (1 Slot)
IM153-4 1 IM153-4 High Feature (ProfiSafe Compliant)
Integrated 2-port switch
PN IO Transmission protocol
IM153-2 1 IM153-2 Standard Feature
Profibus Transmission Protocol
MMC-128K-EEPROM 1 Micro Memory Card 128 KB
BM-PS-IM153 1 Backplane Module PS/IM153. Hot swap capability
SM321-32DI 1 Digital Input Module, 32 DI, 24V, 500 V DC isolated
SM322-32DO 1 Digital Input Module, 32 DO, 24V, 500 V DC isolated
SM331-8AI 1 Analog Input Module, 8 AI, 500 V DC isolated, 15 bits,
Diagnostic Status
SM332-8AO 1 Analog Input Module, 8 AO, 500 V DC isolated, 12 bits,
Diagnostic Status
BM-2x40 n/2 Backplane Module 2x40. Hot swap capability
*For the exact reference of every component please refer to [RD4].
*For the datasheet of the every product, use the reference and refer to SIEMENS Website
ITER_D_333J63 v4.1
Page 69 of 83
6.2.B.2 S7-1500 Family: ET200MP
ET200MP is a module I/O system used for user-specific and complex automation tasks:
o Used with S7 SIEMENS automation system to expand signals , communication and
function modules :
o In CPUs S7-1500 in both local and Remote
o In CPUs S7-400 in Remote
o In CPUs S7-300 in Remote
o Supports PROFIBUS DP or PROFINET interface module
o Modules cannot be replaced during operation with the bus module active. Without hot
swapping capability.
If the configuration uses Profibus, you can set up to 12 SM modules.
If the configuration uses Profinet, you can set up to 12 SM modules.
Figure 36: ET200MP Modules
See Table below
ITER_D_333J63 v4.1
Page 70 of 83
Short Designation QTY Description and Characteristics
RAIL-1500-19IN-HS 1 1500 Mounting Rail 482 MM. Including grounding
element
PS1500-8A 1 PS 1507 24V/8A Stabilized Power Supply
IM155-5PN-HF 1 IM153-5PN High Feature
Integrated 2-port switch
PN IO Transmission protocol
Profisafe Compliant
IM155-5DP-ST 1 IM155-5DP Standard Feature
Profibus Transmission protocol
Profisafe Compliant
U-TYPE-CONNECTOR N Spare Part, U-Type-Connector for Connection IO Module
SM521-32DI 1 32 DI module with Diagnosis
SM522-32DO 1 32 DO Module with Diagnosis
SM531-8AI 1 8 Analog Inputs Module U/I/RTD/TC with Diagnosis
SM532-8AO 1 8 Analog Outputs Module U/I with Diagnosis
*For the exact reference of every component please refer to [RD4].
*For the datasheet of the every product, use the reference and refer to SIEMENS Website
ITER_D_333J63 v4.1
Page 71 of 83
C. Medium I/O Fail-Safe modules [S7-300 or S7-1500]
6.2.C.1 S7-300 Family: ET200M –“F”
ET200M-F is a modular I/O system used for Fail-Safe automation tasks:
o Used in S7 SIEMENS automation system to expand signals, communication and function
modules :
o In CPUs S7-300F in both local and Remote
o In CPUs S7-400F and S7-400FH in Remote
o In CPUs S7-1500F in remote
o Supports PROFISAFE over Profibus DP
o Modules can be replaced during operation (hot swapping) with the bus modules active.
Attention must be paid to the type of base module:
o PS300-5A and IM must be place on a “BM-PS-IM153” base module.
o SM modules of 1 slot width must be placed on “BM-2x40” base modules.
o SM modules of 2 slots width must be placed on “BM-80” base modules
o If the architecture is redundant, the IM153-2 modules must by placed on “BM-IM153-
IM153” base modules
You can set up to 8 SM modules on the same rack.
Figure 37: ET200M “F” Modules
ITER_D_333J63 v4.1
Page 72 of 83
Figure 38: ET200M “F” Modules for S7-400FH
Short Designation QTY Description and Characteristics
RAIL-19IN-HS 1 Mounting Rail Hot SWAP length: 19 Inches
PS300-5A 1 PS 300 5A (1 Slot)
IM153-2 1-2 IM 153-2 Profibus Coupler
BM-PS-IM153 0..n Backplane Module PS + IM153
BM-IM153-IM153 0..n Backplane Module IM153+ IM153
BM-80 0..n Backplane Module for 80mm modules
BM-2x40 0..n Backplane Module for 2x 40mm modules.
SM326-24DI 0..n 24 F-DI Module
SM326-10DO 0..n 10 F-DO Module
SM336-6AI 0..n 6 F-AI Module
*For the exact reference of every component please refer to [RD4].
*For the datasheet of the every product, use the reference and refer to SIEMENS Website
ITER_D_333J63 v4.1
Page 73 of 83
6.2.C.2 S7-1500 Family: ET200MP –“F”
ET200MP-F is a modular I/O system used for Fail-Safe automation tasks:
o Used in S7 SIEMENS automation system to expand signals, communication and function
modules :
o In CPUs S7-1500F in both local and Remote
o In CPUs S7-400F in Remote
o In CPUs S7-300F in remote
o Supports PROFISAFE over Profibus DP and PROFINET
o Modules cannot be replaced during operation with the bus modules active.
You can set up to 12 SM modules on the same rack using the PROFIBUS header
You can set up to 30 SM modules on the same rack using the PROFINET header.
OR
IM Profibus DP Interface
IM ProfiNet Interface
PS1500-8A IM155-5DP-STIM155-5PN-HF
RAIL-1500-19IN
SM526-16DI SM526-8DO
SM526-1
6DI
SM526-8
DO
Figure 39: ET200MP “F” Modules
ITER_D_333J63 v4.1
Page 74 of 83
Short Designation QTY Description and Characteristics
RAIL-1500-19IN-HS 1 1500 Mounting Rail 482 MM. Including grounding
element
PS1500-8A 1 PS 1507 24V/8A Stabilized Power Supply
IM155-5PN-HF 1 IM153-5PN High Feature
Integrated 2-port switch
PN IO Transmission protocol
Profisafe Compliant
IM155-5DP-ST 1 IM155-5DP Standard Feature
Profibus Transmission protocol
Profisafe Compliant
U-TYPE-CONNECTOR n Spare Part, U-Type-Connector for Connection IO Module
SM326-16DI 1 16 F-DI Module
SM326-8DO 1 8 F-DO Module
*For the exact reference of every component please refer to [RD4].
*For the datasheet of the every product, use the reference and refer to SIEMENS Website
ITER_D_333J63 v4.1
Page 75 of 83
6.3 Accessories
Short Designation QTY Description and Characteristics
SITOP-10A 1 PS SITOP 10A
SITOP-20A 1 SITOP power supply Modular 230Vac/24Vdc 20A
SITOP-DIODES 1 SITOP redundancy module 24Vdc/40A
PC-USB 1 PC Adapter (USB)
*For the exact reference of every component please refer to [RD4].
*For the datasheet of the every product, use the reference and refer to SIEMENS Website
ITER_D_333J63 v4.1
Page 76 of 83
7 NETWORK COMPOSITION
The network is an integral part of the Control System infrastructure based on slow controllers.
In this chapter, a set of equipment is presented to ease and drive the job of development of such
infrastructure.
- Field Network Architecture equipment
To implement the immediate layer below the ‘Slow Controllers’; to connect them to
their slaves, using either Profinet or Profibus.
- Plant System Local (Private) Network Architecture equipment
To implement the immediate layer above the ‘Slow Controllers’, to interconnect them,
using Ethernet.
7.1 Field Network Architecture equipment
A. Field Bus (Profibus) components
The ‘FieldBus (Profibus) components’ are the ‘Media Converters and Connectivity devices’.
This equipment will be used to deploy the ‘Profibus Network Architecture’.
A Key device is the OLM (Optical Link Module or Profibus transceiver module (TS)),
normally called Media Converter, represented several times in the chapter: [Network
Selection].
Short Designation QTY Description and Characteristics
PB-CABLE
- Profibus Cable (20m)
PB-CON
- Profibus Connector
OLM
-
Profibus Optical Link Module
1 RS485 and 1 Glass-Focinterface (2 Bfoc-Sockets)
Single mode fiber. Support Ring Redundancy
ITER_D_333J63 v4.1
Page 77 of 83
B. Field Net (Profinet) components
The ‘FieldNet (Profinet) components are the ‘Field Switches’.
This equipment will be used to deploy an ‘independent Profinet Network Architecture’ stated
in the chapter: [Network Selection].
Two references are stated, both of them suitable to implement properly this task.
Short Designation QTY Description and Characteristics
RS20-08 (Hirschman)
0..n
DIN Mounting
8 ports: 6 RJ45/2 FO
10/100Mbits
FO: Monomode, SC connectors
24VDC Power Supply
Manageable
Redundancy Management: Hyper-Ring
X308-2LD (Siemens)
0..n
DIN Mounting
10 ports : 7 RJ45/2FO
10/100/1000Mbits
FO: Monomode, SC connectors
24VDC Power Supply
Manageable
Redundancy Management
*For the exact reference of every component please refer to [RD4].
*For the datasheet of the every product, use the reference and refer to SIEMENS Website
ITER_D_333J63 v4.1
Page 78 of 83
7.2 Plant System Local (Private) Network Architecture equipment
The ‘Plant System Local Network components’ are the ‘Network Switches’.
This equipment will be used to deploy an ‘independent Plant System Local (Private) Network’
stated in the chapter: [Network Selection].
Two references are stated, both of them suitable to implement properly this task.
Short Designation QTY Description and Characteristics
MACH102 (Hirschman)
0..n
19” RACK Mounting
24 Ports Fast Ethernet
2 Ports Combo Ethernet Gigabit
10/100/1000Mbits
230 VAC Power Supply
Manageable
Redundancy Management: Hyper-Ring
XR324-12M (Siemens)
0..n
19” RACK Mounting
24 ports (ST, SC, LC)
100/1000Mbits
230 VAC Power Supply
Manageable
Redundancy Management
*This is the network equipment to be used, also, when the PLC must be connected to the
‘Central I&C Networks’. This equipment should be provided, by default, with the Interface Kit
[RD3].
*For the exact reference of every component please refer to [RD4].
*For the datasheet of the every product, use the reference and refer to SIEMENS Website
ITER_D_333J63 v4.1
Page 79 of 83
8 SOFTWARE : STEP7 & TIA Portal
8.1 STEP7 STEP7 is an engineering software for the configuration and programming of SIMATIC-S7
PLCs of SIEMENS. Targeting the families: S7-300 and S7-400.
A. Dependencies
The graph below shows the software packages required, depending on the type of applications.
The blue coloured rectangles boxes represents installable packages,
The container rectangles represent inseparable packages, for commercial and/or technical
reasons.
The ellipses represent in which domain of activity the software package is used in ITER (in
the current state of development), linked to the device able to develop such task :
o S7-300,S7-400,S7-300F, S7-400FH
The arrows represent the dependencies. Between applications and software packages, and
between software packages.
Distributed Safety
Step 7 Professional Bundle
F Systems
STEP7(LAD,FBD,LST)
SCL CFCPLCSIM S7-Graph
Distributed Safety
(Programming)
S7 F Configuration Pack (Library)
F Systems (Programming)
F Systems (Library)
ConventionalControl Applications
S7-300,S7-400
Safety ApplicationsS7-300F
Interlock & Safety Applications
S7-400FH
Opt
iona
l
Figure 40: Software and Applications Dependency Tree for STEP7
For safety applications, there are 2 ways. The reason is that ‘Distributed Safety (F)’ and F-
Systems (FH) are two different product lines in Siemens. Their life cycles are completely
dissociated. F-Systems can be user for any application whereas distributed safety is only
allowed for systems implementing local functions.
ITER_D_333J63 v4.1
Page 80 of 83
Important: if you deploy a S7-400FH without the redundancy feature, you will finally
have something more or less functionally equivalent to a S7-400 F. But it will not be a
genuine S7-400F, at least from the Siemens perspective.
The “Distributed Safety” Package is in 2 parts:
“Distributed Safety: ” programming part
“S7 F Configuration Pack”: Library part
Both packages are provided together and require to be installed.
The “F Systems” Package is in 2 parts:
“F Systems ” programming part
“F Systems Library”: Library part
Both packages are provided together and require to be installed.
B. Versions compatibility
The versions compatibility is a complex topic. Siemens is regularly issuing new major or
minor versions, service packs and updates. They also are keeping up with their supporting OS
Microsoft Windows roadmap. A versions compatibility matrix is maintained at the following
location:
http://support.automation.siemens.com/WW/llisapi.dll?func=cslib.csinfo&lang=en&objid=187
34363&caller=view
In the table underneath, there is an example of a “coherent” suite that can be installed under
Windows 7 64 Bits + SP1 Ultimate, Enterprise or Pro.
It is including the latest packages at the time of writing this document.
Short Designation Description
Bundle Package
Step 7 Professional
Bundle
Step 7 Basic LAD,FDB,LST editors
PLCSIM Hardware Simulator
SCL Structured Text Editor
S7-Graph Graphset Editor
CFC CFC Continuous Flow Chart editor.
Distributed Safety Distributed Safety “Programming” Part
S7-F Configuration Pack “Library” Part
“F” Systems “F” Systems “Programming” Part
“F” Systems Library “Library” Part
ITER_D_333J63 v4.1
Page 81 of 83
8.2 TIA Portal
TIA PORTAL is an engineering software for the configuration and programming of SIMATIC-
S7 PLCs of SIEMENS. Targeting the families: S7-1200, S7-1500, S7-300 and S7-400.
A. Dependencies
The figure below shows the software packages required, depending on the type of applications.
The blue coloured rectangles boxes represents installable packages,
The container rectangles represent inseparable packages, for commercial and/or technical
reasons.
Safety Advanced
Step 7 Professional Bundle
PLCSIM
TIA Portal(LAD,FBD,STL,S7-Graph)
SCL PLCSIM S7-Graph
Safety Advanced
(Programming)
Safety Advanced (Library)
ConventionalControl Applications
S7-1200,S7-1500S7-300,S7-400
Interlock ApplicationsS7-1500F
PLCSIMAdvanced
Figure 41: Software and Applications Dependency Tree for TIA Portal
About the Software Packages:
Safety Advanced V14 SP1:
STEP 7 Safety Advanced is the add-on package for all fail-safe TIA SIMATIC controller
classes (S7-1500, S7-1200, S7-1500 Software Controller, S7-300, S7-400, WinAC).
This add-on package combines updated engineering features and supports the extended
portfolio of S7-1500F and S7-1200F.
ITER_D_333J63 v4.1
Page 82 of 83
With ‘Safety Advanced’ package, configuration control (option handling) for SIMATIC F-I/O
is supported in the following configurations:
o Distributed on a F-CPU S7-300/400/1200/1500
o Central on a F-CPU S7-1500 (including fail-safe ET200SP CPUs)
Simatic PLCSIM Advanced
SIMATIC PLCSIM Advanced enables you to create virtual controllers for simulating S7-1500
and ET 200SP controllers and provides extensive simulation of functions. Compared to the
standard S7-PLCSIM, PLCSIM Advanced offers the following additional functions:
o API for connection to co-simulations
o Multiple, distributed instances possible
o Web server and OPC UA access.
B. Versions compatibility
To be able to install TIA Portal, you need one of the following operating system versions:
• Windows 7 Professional/Enterprise/Ultimate in 32/64Bit
• Windows 8 Professional/Enterprise
• Windows Server 2008 R2 Standard SP1
• Windows Server 2012
Siemens is regularly issuing new major or minor versions, service packs and updates for TIA
portal. Below table provide the list of packages
Short Designation Description
Bundle Package
Step 7 Professional
bundle
TIA Portal LAD,FDB,STL,SCL and
S7-GRAPH editors
PLCSIM Hardware Simulator
Safety Advanced Safety Advanced “Programming” Part
Safety Advanced “Library” Part
ITER_D_333J63 v4.1
Page 83 of 83
8.3 What version to install ?
In fact one doesn’t really have the choice. Siemens is selling only the latest Software release.
SIEMENS will also give support on the compatibility between the installed packages, and the
new ones. If some packages, already installed, are incompatible with the new one installed, the
only solution is to upgrade the obsolete ones, and eventually pay for the upgrade.
If the software packages installed in the ‘Siemens Console’ are not updated to the latest
version, there is no need to upgrade unless:
The application is facing a technical issue, solved in a newer version.
The application need to configure a new hardware, not supported by the current
version.
Siemens will assume support on any “coherent” package, according to their compatibility table,
no matter how old it is.
The version of the software to use is stated in [RD4].
8.4 Applications portability between versions
The ascendant compatibility is complete, and assumed by Siemens. In other words any
application created in version “n” is compatible with the “n+i” version. There are just a few
possible problems, because sometimes some freedom possible in version “n” is restricted in
version “n+i”. But Siemens always supports these cases and provides the solution.
The reverse way is not advised but remains possible, in some conditions:
If the application didn’t add a hardware not supported in “n-i” version
If the application didn’t add a feature (ie a System Block) not available in “n-i” version.
For minor code modification, they should remain compatible.
This information is critical and must be taken into account for the transfer of responsibility
between the supplier and ITER.
Top Related