Operating Instructions
TypeME24
I/O-Module
We reserve the right to make technical changes without notice.Technische Änderungen vorbehalten.Sous réserve de modifications techniques.
© Bürkert Werke GmbH & Co. KG, 2015 -2017
Operating Instructions 1710/02_EU-EN_00810473 / Original DE
3
Content
1 THEOPERATINGINSTRUCTIONS.............................................................................................................................................6
1.1 Symbols......................................................................................................................................................................................6
1.2 Definitionoftheterm“product”.....................................................................................................................................6
2 AUTHORIZEDUSE.............................................................................................................................................................................7
3 BASICSAFETYINSTRUCTIONS.................................................................................................................................................8
4 GENERALINFORMATION................................................................................................................................................................9
4.1 Contactaddress.....................................................................................................................................................................9
4.2 Warranty......................................................................................................................................................................................9
4.3 InformationontheInternet...............................................................................................................................................9
5 DESCRIPTIONOFTHEDEVICE...............................................................................................................................................10
5.1 Possiblecombinations.....................................................................................................................................................10
6 TECHNICALDATA.............................................................................................................................................................................11
6.1 Conformity..............................................................................................................................................................................11
6.2 Standards................................................................................................................................................................................11
6.3 Operatingconditions........................................................................................................................................................11
6.4 Mechanicaldata...................................................................................................................................................................12
6.5 Electricaldata.......................................................................................................................................................................13
6.5.1 Electricalpropertiesoftheinputsandoutputs...........................................................................13
7 INSTALLATION...................................................................................................................................................................................15
7.1 Safetyinstructions.............................................................................................................................................................15
7.2 MountTypeME24onbackplaneTypeBEF1........................................................................................................15
7.3 Connectexternalsensorsandactuators...............................................................................................................16
7.3.1 Plugconfigurationandwiring..........................................................................................................17
8 START-UP.............................................................................................................................................................................................23
8.1 Safetyinstructions.............................................................................................................................................................23
8.2 ConfigurationofTypeME24..........................................................................................................................................23
I/O module
TypeME24
English
4
TypeME24
9 CONFIGURATIONUSINGTHEDISPLAY.............................................................................................................................24
9.1 Briefdescriptionoftheuserinterface....................................................................................................................24
9.1.1 Descriptionofbuttons.......................................................................................................................25
9.2 Operatingstructure...........................................................................................................................................................26
9.3 Userlevel(accessrights)..............................................................................................................................................27
9.3.1 Changingtheuserlevel(accessrights).......................................................................................27
9.3.2 Loggingofftheuserlevel.................................................................................................................28
9.3.3 Changingpassword(PIN)................................................................................................................28
9.4 SwitchingtotheParameter,MaintenanceorDiagnosticsdetailedview.............................................29
9.5 SettingBürkertsystembus(büS).............................................................................................................................30
9.5.1 DetailedviewsinthebüSfunction.................................................................................................31
9.6 Settinginputmodule........................................................................................................................................................32
9.6.1 Settinganaloginput...........................................................................................................................32
9.6.2 Calibratinganaloginput....................................................................................................................35
9.6.3 Resetanaloginputtofactorysettings...........................................................................................37
9.6.4 Settingdigitalinput............................................................................................................................37
9.6.5 Resettotalizer,onlywhenFlowrateoperatingmodeactive....................................................40
9.6.6 Calibratedigitalinput,forFlowrateoperatingmodeonly........................................................41
9.6.7 Resettingdigitalinputtofactorysettings.....................................................................................42
9.6.8 Simulationofaprocessvalueontheinputmodule....................................................................43
9.7 Settingoutputmodule.....................................................................................................................................................44
9.7.1 Settinganalogoutput........................................................................................................................44
9.7.2 Calibratinganalogoutput.................................................................................................................47
9.7.3 Resettinganalogoutputtofactorysettings.................................................................................48
9.7.4 Settingdigitaloutput.........................................................................................................................48
9.7.5 Manuallyactuatingoutputmodule..................................................................................................62
10 DISPLAYELEMENTS......................................................................................................................................................................63
10.7.1 Displayofdevicestatus....................................................................................................................64
11 MAINTENANCE..................................................................................................................................................................................65
11.1 Safetyinstructions.............................................................................................................................................................65
11.2 Replacingdevices...............................................................................................................................................................65
11.3 Replacingthememorycard..........................................................................................................................................67
11.4 Troubleshooting...................................................................................................................................................................69
English
5
TypeME24
12 ACCESSORIES..................................................................................................................................................................................70
13 PACKAGINGANDTRANSPORT...............................................................................................................................................71
14 STORAGE..............................................................................................................................................................................................71
15 DISPOSAL............................................................................................................................................................................................71
English
6
Theoperatinginstructions
TypeME24
1 THEOPERATINGINSTRUCTIONSTheoperatinginstructionsdescribetheentirelifecycleofthedevice.Keeptheseinstructionsinalocationwhichiseasilyaccessibletoeveryuserandmaketheseinstructionsavailabletoeverynewownerofthedevice.
ImportantSafetyInformation.
Readtheoperatinginstructionscarefullyandthoroughly.Studyinparticularthechaptersentitled“2Authorizeduse”and“3Basicsafetyinstructions”.
Theoperatinginstructionsmustbereadandunderstood.
1.1 Symbols
DANGER!
Warnsofanimmediatedanger.
Failuretoobservethewarningwillresultinafatalorseriousinjury.
WARNING!
Warnsofapotentiallydangeroussituation.
Failuretoobservethewarningmayresultinseriousinjuriesordeath.
CAUTION!
Warnsofapossibledanger.
Failuretoobservethiswarningmayresultinamoderateorminorinjury.
NOTE!
Warnsofdamagetoproperty.
• Failuretoobservethewarningmayresultindamagetothedeviceortheequipment.
Indicatesimportantadditionalinformation,tipsandrecommendations.
Referstoinformationintheseoperatinginstructionsorinotherdocumentation.
Designatesinstructionsforriskprevention.
→ Designatesaprocedurewhichyoumustcarryout.
Indicatesaresult.
1.2 Definitionoftheterm“product”
Intheseinstructions,theterm„product“alwaysreferstotheI/Omodule,TypeME24.
English
7
Authorizeduse
TypeME24
2 AUTHORIZEDUSE
Non-authorizeduseoftheTypeME24maybedangeroustopeople,nearbyequipment,andtheenvironment.
TheI/OmoduleTypeME24collects,convertsandcomparesphysicalmeasurementdatafromexternalsensorsorreceivesswitchingcommandsfrombüSparticipantsviathebüSinterface.ThismeasurementdataortheseswitchingcommandsarerelayedtoexternalactuatorsortobüSparticipantsviathebüSinterface.
Useaccordingtotheauthorizeddata,operatingconditionsandconditionsofusespecifiedinthecontractdocumentsandoperatinginstructions.
Observethefollowingwhenusingtheproduct
Usethedeviceonlyinconjunctionwiththird-partydevicesandcomponentsrecommendedandauthorizedbyBürkert.
Useonlywheninperfectconditionandalwaysensureproperstorage,transportation,installationandoperation.
Useonlyasintended.
English
8
Basicsafetyinstructions
TypeME24
3 BASICSAFETYINSTRUCTIONSThesesafetyinstructionsdonotmakeallowanceforany
• contingenciesandeventswhichmayariseduringtheassembly,operation,andmaintenance.
• localsafetyregulations–theoperatorisresponsibleforobservingtheseregulations,alsoinrelationtotheinstal-lationpersonnel.
Generalhazardoussituations.
Topreventinjuries:
Donotmakeanyinternalorexternalchangesontheproductanddonotsubjectittomechanicalstress.
Securethesystemfromunintentionalactuation.
Onlytrainedtechniciansmayperforminstallationandmaintenancework.
Afteraninterruptioninthepowersupply,ensurethattheprocessisrestartedinacontrolledmanner.
Observethegeneralrulesoftechnology.
NOTE!
Electrostaticsensitivecomponentsormodules.
Theproductcontainselectroniccomponentswhichreactsensitivelytoelectrostaticdischarge(ESD).Contactwithelectrostaticallychargedpersonsorobjectsarehazardoustothesecomponents.Intheworstcasescenario,theywillbedestroyedimmediatelyorwillfailafterstart-up.
• ObservetherequirementsinaccordancewithEN61340-5-1tominimizeoravoidthepossibilityofdamagecausedbysuddenelectrostaticdischarge.
• Donottouchelectroniccomponentswhilethesupplyvoltageisswitchedon.
English
9
Generalinformation
TypeME24
4 GENERALINFORMATION
4.1 Contactaddress
Germany
BürkertFluidControlSystemsSalesCenterChristian-Bürkert-Str.13-17D-74653IngelfingenTel.+49(0)7940-1091111Fax+49(0)7940-1091448E-mail:[email protected]
International
Contactaddressescanbefoundonthefinalpagesoftheprintedoperatinginstructions.
AndalsoontheInternetat:
www.burkert.com
4.2 Warranty
ThewarrantyisonlyvalidiftheTypeME24isusedasintendedinaccordancewiththespecifiedapplicationconditions.
4.3 InformationontheInternet
TheoperatinginstructionsanddatasheetsforTypeME24canbefoundontheInternetat:
www.burkert.com
English
10
Descriptionofthedevice
TypeME24
5 DESCRIPTIONOFTHEDEVICETheoutputmoduleofTypeME24receivestheswitchingcommandsofbüSparticipantsviathebüSinterface,pro-cessesthemandrelaysthisinformationtoexternallyconnectedactuators.
TheinputmoduleofTypeME24receivesthephysicalmeasurementdatafromexternalsensors.TheinputmoduleconvertsandcomparesthismeasurementdataandcommunicatesthevaluesviathebüSinterfacetobüSparticipants.
TheHMIUmoduleTypeME25,inconjunctionwiththedisplayTypeME21,canbeusedtoconfigurethebasicfunc-tions.Alternatively,thiscanalsobecarriedoutviathe“BürkertCommunicator”.
5.1 Possiblecombinations
TheI/OmoduleTypeME24canonlybeoperatedwithinasystemincombinationwithadditionalmodules.Forsettingupasystemcomprisingseveralmodules,pleasecontactyourBürkertsalesoffice.
Exampleofasysteminminimumcombination:
Connectionvariant:Terminalsforcablegland
Connectionvariant:Circularplug-inconnectorM12
1 3
6 5 7
ME24
2 4
6 5 7
ME24
Figure 1: Example of a system: Minimum combination of Type ME24 with additional modules
Module Designation Types Orderno.
1 Inputmodule(connectionvariant:circularplug-inconnectorM12) ME29 00564825
2 Inputmodule(connectionvariant:terminals) ME29 00564826
3 Outputmodule(connectionvariant:socketM12) ME29 00564827
4 Outputmodule(connectionvariant:terminals) ME29 00564828
5 BackplaneforTypeME24 BEF1 00564841
6 Backplane,left BEF1 00564844
7 Backplane,right BEF1 00564846
Table 1: Modules of a possible combination with Type ME24
English
11
Technicaldata
TypeME24
6 TECHNICALDATA
6.1 Conformity
TheTypeME24I/OmoduleconformstotheEUdirectivesaccordingtotheEUDeclarationofConformity(ifapplicable).
6.2 Standards
Theappliedstandards,whichverifyconformitywiththeEUDirectives,canbefoundontheEU-TypeExaminationCertificateand/ortheEUDeclarationofConformity(ifapplicable).
6.3 Operatingconditions
WARNING!
Riskofinjury.
Avoidheatsourceswhichmaycausethepermissibletemperaturerangetobeexceeded.
Permittedtemperatures
Ambienttemperature: 0...+50°C
English
12
Technicaldata
TypeME24
6.4 Mechanicaldata
Dimensions:
94
22
3,1
111116
Figure 2: Dimensions
Housingmaterial: Polycarbonate
English
13
Technicaldata
TypeME24
6.5 Electricaldata
Supplyvoltage: 20...30VviathebackplaneBEF1 ULdevices: PowersupplyunitrestrictedtoClass2
Powerconsumption: <3WIftheoutputsaresuppliedviabüS,thetotalcurrentislimitedinternallyto2A:max.48W
Degreeofprotection: IP65accordingtoEN60529/IEC60529(onlyifcables,plugsandsocketshavebeenconnectedcorrectly)
6.5.1 Electricalpropertiesoftheinputsandoutputs
2AO,2DO
AnalogoutputAO • Currentoutput:4...20mA
• Galvanicisolation
• ProtectionagainstDCreversepolarity
• Resolution:6µA
• Maximumloopimpedance(atcurrentoutput22mA)1350Ωat35VDC850Ωat24VDC300Ωat12VDC
• Detectionofopenloop
DigitaloutputDO • Transistoroutput
• Galvanicisolation
• Max.2500Hz
• Max.0.7AperchannelMax.1Apermodule
• Operatingmode(signals):On-OffThresholdvaluePWMPFM
• Overloaddetection
Table 2: Electrical properties 2AO, 2DO
English
14
Technicaldata
TypeME24
4DOPWM20kHz
DigitaloutputDO • Transistoroutput:opendrainoutput
• Max.20,000Hz
• Max.0.7AperchannelMax.1.8Apermodule
• Operatingmode(signals):On-OffThresholdvaluePWMPFM
• Overloaddetection
Table 3: Electrical properties 4DO PWM 20 kHz
2AI,2DI
AnaloginputAI • Currentinputorvoltageinput: 4-20mA0-20mA0-10V0-5V0-2V
• Galvanicisolation
• ProtectionagainstDCreversepolarity
• Detectionofopenloop(atvoltageinput)
• Inputimpedanceforcurrentmeasurement:110Ω voltagemeasurement:120kΩ
DigitalinputDI • Voltageinput:0-35VDC
• Galvanicisolation
• ProtectionagainstDCreversepolarity
• Frequency:0.5...2500Hz
• Inputimpedanceapprox.3-5kΩatvoltageof5-35V
• Switchingthreshold:VON=5-35VVOFF<2VDC
Table 4: Electrical properties 2AI, 2DI
English
15
Installation
TypeME24
7 INSTALLATION
7.1 Safetyinstructions
WARNING!
Riskofinjuryfromimproperinstallation.
Installationmaybecarriedoutonlybytrainedtechniciansandwiththeappropriatetools.
Securesystemagainstunintentionalactivation.
Followinginstallation,ensureacontrolledrestart.
7.2 MountTypeME24onbackplaneTypeBEF1
A
A 1 : 1I/OmoduleTypeME24
Fasteningscrew(hexagonsocket2.5mm)
BackplaneTypeBEF1
Hinge
Figure 3: Mount I/O module Type ME24 on backplane Type BEF1
→ InserthingepartofTypeME24incounterpieceofbackplaneTypeBEF1.
→ PressTypeME24fullyonthebackplane.
→ Tightenfasteningscrew(hexagonsocket2.5mm).Max.torque1Nm.
TheTypeME24isnowconnectedtothesupplyvoltageonthebackplaneTypeBEF1.
NOTE!
Usepowersupplywithadequatepower.
English
16
Installation
TypeME24
7.3 Connectexternalsensorsandactuators
Fasteningscrew(hexagonsocket2.5mm)
Coveropened
Recessforsecuringthecables
Coverclosed
Openingforcable
Connectionterminals
Figure 4: Connect external sensors and actuators
→ UnscrewfasteningscrewatthecoverofTypeME24(hexagonsocket2.5mm).
→ Openandremovecover.
→ Pulloutconnectionterminals.
→ Insertcablesoftheexternalsensorsandactuatorsthroughtheopeningonthebackofthecover.
→ Connectwiresoftheexternalsensorsandactuatorstotheconnectionterminals(plugconfigurationseechapter“7.3.1Plugconfigurationandwiring”).
→ Reconnectconnectionterminal.
→ Closecoverandtightenfasteningscrew.Max.torque1Nm.
Fixingthecablesforexternalsensorsandactuators(strainrelief):
Torelievethestrain,fixthecablestotherecesswithacableclip.
English
17
Installation
TypeME24
7.3.1 Plugconfigurationandwiring
ME24models2AO,2DO,f(x)
1 2 3 4 5 6 7 8 9 10 11 12
2AO
/2D
O/f
(x)
Figure 5: Configuration 2AO, 2DO, f(x)
2AO,2DO,f(x)
Pin Plugconfiguration Externalcircuit
1 + 20-30V/2Amax.OUTPUTnogalvanicisolation2 –
3 AO1+ +(4-20mA)outputgalvanicallyisolated
4 AO1– –(4-20mA)outputgalvanicallyisolated
5 FE Shielding
6 AO2+ +(4-20mA)outputgalvanicallyisolated
7 AO2– –(4-20mA)outputgalvanicallyisolated
8 DO1+ +NPNgalvanicallyisolated
9 DO1– –NPNgalvanicallyisolated
10 FE Shielding
11 DO2+ +NPNgalvanicallyisolated
12 DO2– –NPNgalvanicallyisolated
Table 5: Configuration 2AO, 2DO, f(x)
English
18
Installation
TypeME24
20...30V
0V
20...30V
20...30V
0V
0V
20...30V
0V
+–
+–
+–
+–
1
Digitalinput(ontheexternalinstrument
orexternalload)
4-20mAinput(ontheexternal
instrument)
Digitalinput(ontheexternal
instrumentorexternalload)
4-20mAinput(ontheexternal
instrument)
+
–
AO1+
AO1–
FE
AO2+
AO2–
DO1+
DO1–
FE
DO2+
DO2–
2AO,2DO,f(x):2-wire
23
45
67
89
1011
12
Figure 6: External circuit 2AO, 2DO, f(x), 2-wire
0V
20...30V
20...30V
0V
20...30V
20...30V
0V
0V
+S–
+S–
+S–
+S–
1
Digitalinput(ontheexternal
instrument)
4-20mAinput(ontheexternal
instrument)
Digitalinput(ontheexternal
instrument)
4-20mAinput(ontheexternal
instrument)
+
–
AO1+
AO1–
FE
AO2+
AO2–
DO1+
DO1–
FE
DO2+
DO2–
2AO,2DO,f(x):3-wire
23
45
67
89
1011
12
Figure 7: External circuit 2AO, 2DO, f(x), 3-wire
English
19
Installation
TypeME24
ME24models4DOPWM20kHz
1 2 3 4 5 6 7 8 9
4DO
/f(x
)Figure 8: Configuration 4DO PWM 20 kHz
4DOPWM20kHz
Pin Plugconfiguration Externalcircuit
1 +20-30V/2Amax.totalcurrentnogalvanicisolation
2 DO1– Opendrain
3 +20-30V/2Amax.totalcurrentnogalvanicisolation
4 DO2– Opendrain
5 +20-30V/2Amax.totalcurrentnogalvanicisolation
6 DO3– Opendrain
7 +20-30V/2Amax.totalcurrentnogalvanicisolation
8 DO4– Opendrain
9 FE Shielding
Table 6: Configuration 4DO PWM 20 kHz
English
20
Installation
TypeME24
12
34
56
78
9
FE+–
+–
Digitalinput(ontheexternal
instrument)
Digitalinput(ontheexternal
instrument)
+
DO1–
+
DO2–
+
DO3–
+
DO4–
FE
4DO,f(x)
Externalload(e.g.valve)
Externalload(e.g.valve)
Figure 9: External circuit 4DO PWM 20 kHz
English
21
Installation
TypeME24
ME24models2AI,2DI
1 2 3 4 5 6 7 8 9 10 11 12
2AI/
2DI
Figure 10: Configuration 2AI, 2DI
2AI,2DI
Pin Plugconfiguration Externalcircuit
1 + 20-30V/2Amax.OUTPUTnogalvanicisolation2 –
3 AI1++(0/4-20mA,0-2/5/10V)Inputgalvanicallyisolated
4 AI1––(0/4-20mA,0-2/5/10V)Inputgalvanicallyisolated
5 FE Shielding
6 AI2++(0/4-20mA,0-2/5/10V)Inputgalvanicallyisolated
7 AI2––(0/4-20mA,0-2/5/10V)Inputgalvanicallyisolated
8 DI1++(ON:5-35V,OFF:<2V)Inputgalvanicallyisolated
9 DI1––(ON:5-35V,OFF:<2V)Inputgalvanicallyisolated
10 FE Shielding
11 DI2++(ON:5-35V,OFF:<2V)Inputgalvanicallyisolated
12 DI2––(ON:5-35V;OFF:<2V)Inputgalvanicallyisolated
Table 7: Configuration 2AI, 2DI
English
22
Installation
TypeME24
20...30V
0V
20...30V
20...30V
0V
0V
20...30V
0V
+–
+–
+–
1
Proximityswitch
Analogoutput(ontheexternal
instrument)
Digitaloutput(ontheexternal
instrument)
Analogoutput(ontheexternal
instrument)
+
–
AI1+
AI1–
FE
AI2+
AI2–
DI1+
DI1–
FE
DI2+
DI2–
2AI,2DI:2-wire
23
45
67
89
1011
12
Figure 11: External configuration 2AI, 2DI, 2-wire
0V
20...30V
20...30V
0V
20...30V
20...30V
0V
0V
+S–
+S–
+S–
+S–
1
Digitaloutput(ontheexternal
instrumentorproximityswitch)
Analogoutput(ontheexternal
instrument)
Digitaloutput(ontheexternal
instrumentorproximityswitch)
Analogoutput(ontheexternal
instrument)
+
–
A1+
AI1–
FE
AI2+
AI2–
DI1+
DI1–
FE
DI2+
DI2–
2AI,2DI:3-wire
23
45
67
89
1011
12
Figure 12: External configuration 2AI, 2DI, 3-wire
English
23
Start-up
TypeME24
8 START-UP
8.1 Safetyinstructions
WARNING!
Riskofinjuryfromimproperoperation.
Improperoperationmayresultininjuriesaswellasdamagetothedeviceandtheareaaroundit.
Beforestart-up,ensurethattheoperatingpersonnelarefamiliarwithandcompletelyunderstandthecontentsoftheoperatinginstructions.
Observethesafetyinstructionsandintendeduse.
Onlyadequatelytrainedpersonnelmaystartuptheequipment/thedevice.
8.2 ConfigurationofTypeME24
TheconfigurationcanbecarriedoutusingthedisplayoftheconnectedsystemoratthePCusingthe“BürkertCommunicator”software.
The“BürkertCommunicator”andtherelatedgeneraldescriptionareavailableontheBürkerthomepage.
ThebüSstick,whichisavailableasaccessory,isrequiredforconfigurationusingthe"BürkertCommuni-cator".SeeChapter“12Accessories”.
Forconfigurationusingthedisplayofthesystem,refertothechapterentitled“9Configurationusingthedisplay”.
English
24
Configurationusingthedisplay
TypeME24
9 CONFIGURATIONUSINGTHEDISPLAY
9.1 Briefdescriptionoftheuserinterface
2AI/2DI
4DO
Device2AI/2DI
AI1 Operatingmode 4-20mA Temp 30.25°C
AI2 Operatingmode 4-20mA Temp 9.75°C
DI1 Operatingmode Flowrate DI1 0.20l/s
AreaofApplication
Navigationarea
Designation
Deviceview
FunctionviewLocalizedeviceMessages
Changeuserlevel
ButtonMenu
ButtonChangetofunctionview
ButtonsChangetodesktopvieworuser-definedviews
11:19:06
Informationbar
Buttononscreenframe
Scrollbar
HMIU.0
2AO/2DO
In
Out
Out
HMIU
Figure 13: Device view of input module 2AI - 2DI (example)
Thebasicoperationofthedisplaycanbefoundintheoperatinginstructions“SoftwareforDisplay”ME21.
Symbol Description
HMIU
HMIUmoduleTypeME25
In
Inputmodule
Out
Outputmodule
Bürkertsystembus(büS)
Table 8: Symbols in the navigation area
English
25
Configurationusingthedisplay
TypeME24
Range Description
Informationbar Designationoftheshownview(andoftheselecteddevice)ordevicetypeanddevicename.
Buttons Configurationofthebuttonshasbeenadaptedtotheview,
e.g.Toggleviews,Menu,...
Designationandareaofapplication
Designationcorrespondingtotheview.
Displayofprocessvalues,graphsorinputoptionsinaccordancewiththeselectedview,deviceorfunction.
Navigationarea Selectionoftheconnecteddevicesorselectionoffunctionsaccordingtotheselectedview.
Isnotincludedinthedetailedviews.
Scrollbar Indicatesthepositiononthescreen.
Isonlyavailableifthecontentsofthenavigationareaorareaapplicationarelargerthantheuseinterface.
Button Exitwithoutsavingandchangetohomescreen(Desktop1).
Table 9: Description of the areas
9.1.1 Descriptionofbuttons
Button Commandordescription Button Commandordescription
Changeview.
Availableonlyindesktopviews,deviceviewanddetailedviews
Changetodetailedviewparameter
Availableonlyinfunctionview.
Changeview.
Availableonlyindesktopviews,deviceviewanddetailedviews
Back
Changetodeviceview.
Availableonlyindesktop1anduser-de-finedviews.
Cancelandexit.
Changetofunctionview.
Availableonlyindeviceview.
Savechanges(backup).
Inputscreen,optionfieldremainsactive.
Note:Ifyouexitaninputmaskusingcancel,savedchangesareretained.
Openmenu. Saveandexit.
Table 10: Description of buttons
English
26
Configurationusingthedisplay
TypeME24
9.2 Operatingstructure
Startpage(desktop1ofx)Deviceview
Functionview
FunctionviewLocalizedeviceMessages
Changeuserlevel
BackDetails
Back
Detailedview1Parameter
Detailedview2Maintenance
Detailedview3Diagnostics
EnableeditmodeLanguagesetting
Changeuserlevel
Changeuserlevel
Changeuserlevel
Figure 14: Operating structure
English
27
Configurationusingthedisplay
TypeME24
9.3 Userlevel(accessrights)
9.3.1 Changingtheuserlevel(accessrights)
Theusercanchangetheuserlevelintheviews.
Theusercanselectthefollowinguserlevelwithappropriaterights:
Symbol Userlevel Description
User NoPINrequired
• Canreadspecifiedvalues
• Restrictedrightstochangevalues
Advanceduser PINrequired(defaultPIN:5678)
• Canreadspecifiedvalues
• Restrictedrightstochangevalues
Installer PINrequired(defaultPIN:1946)
• Canreadallvalues
• Extendedrightstochangevalues
Bürkert PINrequired
• ForBürkertServiceonly
Table 11: User level
Changingtheuserlevel:
Changeuserlevel
Userlevel Loginas Advanceduser*
Selectuser
Userlevel Password 0
SetPIN
Theuserlevelissetandthesymbolappearsontheinformationbar.
* The next higher user level appears here.
Theselecteduserlevelisactiveuntil:
• Theuserlogsofftheuserlevel.
• Thescreensaverbecomesactive.
English
28
Configurationusingthedisplay
TypeME24
9.3.2 Loggingofftheuserlevel
Loggingofftheuserlevel:
Changeuserlevel
Userlevel Logout
Theuserlevelisthestandarduser.
9.3.3 Changingpassword(PIN)
Changingpassword:
Changeuserlevel
Userlevel Changepassword
Changepassword Enterpassword 0
SetPIN.
Changepassword Confirmpassword 0
SetPIN.
Thepasswordischanged.
English
29
Configurationusingthedisplay
TypeME24
9.4 SwitchingtotheParameter,MaintenanceorDiagnosticsdetailedview
TheusercanmakesettingsintheParameterandMaintenancedetailedviewsonly.
Pressbuttonorlistfield Commandordescription
→ Changetodeviceview.
→ Choosedeviceinthenavigationarea.
Processdataofthedeviceisdisplayedintheapplicationarea.
or
Functionviewxxxxxx
Changetofunctionview.
Thedisplayshowsthefunctionviewoftheselecteddevice.
→ Choosefunctioninthenavigationarea
Thedataoftheselectedfunctionisshownintheareaofapplication.
or
Detailsxx
Changetodetailedview.
ThedisplayshowsthedetailedviewParametersoftheselectedfunction.
ChangetoDiagnostics,ParametersorMaintenancedetailedviews.
→ Makesettings.
English
30
Configurationusingthedisplay
TypeME24
9.5 SettingBürkertsystembus(büS)
DataandsettingsfortheBürkertsystembusforeachI/Omodule.
e.g.designation,identification,versions
AI1
AI2
DI1
DI2
FunctionbüS
Uniquedevicename 5648160Location
Beschreibung 2AI/2DI
InputModule2AI/2DI 04.04.201412:21
büS
ChangetodetailedviewParameter
In
In
In
In
Figure 15: büS function view, input module (example)
Procedure:
→ Switchtodeviceview.
→ Selectdeviceinthenavigationarea.
→ Switchtofunctionview.
→ SelectbüSinthenavigationarea.
ThedisplayshowsthebüSfunctionviewoftheselecteddevice.
English
31
Configurationusingthedisplay
TypeME24
9.5.1 DetailedviewsinthebüSfunction
ParameterbüS
Basesettings Uniquedevicename 5648160
2AI/2DI
83
Location
Description
Address
InputModule2AI/2DI 04.04.201412:21
.
DetailedviewParameterbüS
Optionforsettinguser-specificdatafordeviceidentification.
• Designationanddescription
• Location
• Address
opensaninputscreen.
→ Makesettings.
DiagnosticsbüS
büSinformation Address 83
500kbit/s
büS-Modus
A.07.07.04
InputModule
53.43h
564816
Baudrate
Mode
büSversion
Devicename
Operatingduration
Ident.number
InputModule2AI/2DI 04.04.201412:21
Deviceinformation
DetailedviewDiagnosticsbüS
RepresentationofbüSinformationanddeviceinformation.
• Addressandbaudrate
• Devicenameanddeviceidentification
• Softwareinformationandhardwareinformation
• Devicedriverinformation
Nochangesbyuserarepossible.
MaintenancebüS
Device Resetdevice
InputModule2AI/2DI 12:21:16DetailedviewMaintenancebüS
Deviceisrestarted(softwarereset).
Table 12: Detailed views büS
English
32
Configurationusingthedisplay
TypeME24
9.6 Settinginputmodule
9.6.1 Settinganaloginput
Userlevel:Installer
→ SwitchtodetailedviewParameters.
→ 1 Selectinputsignal(operatingmode).
→ 2 Changenameifrequired.
→ 3 Selectphysicalsizeandunit.
→ 4 Assignthelowervalueofthephysicalsizetothelowervalueoftheinputsignal.
→ 5 Assigntheuppervalueofthephysicalsizetotheuppervalueoftheinputsignal.
→ 6 Setresponsetimeofthefilter.
→ 7 Setwarninglimitvaluesanderrorlimitvalues.
Re 1 :Selectinputsignal(operatingmode).
Configure Operatingmode Notconfigured*
Possibleselection:
Notconfigured
4-20mA
0-20mA
0-10V
0-5V
0-2V
Selectinputsignal
Theinputsignalisset.
*The value set previously appears here.
Re 2 :Changename.
Configure Name AI1* Setname
Thenameisset.
*The value set previously appears here.
English
33
Configurationusingthedisplay
TypeME24
Re 3 :Selectphysicalsizeandunit.
Configure Unit °C*
Valuetype Temperature*
Possibleselection:
Nounit
Concentration g/l,mg/l,µg/l,ppm,ppb
Conductivity mS/cm,µS/cm
Current mA,µA,nA,pA
Flowrate l/h,l/min,l/s,m³/h,m³/min,m³/s,USgal/h,USgal/min,USgal/s,Imp-gal/h,Impgal/min,Impgal/s
Frequency mHz,Hz,kHz,MHz
pHvalue pH
Pressure Pa,bar,at,atm,Torr,psi
Resistivity Ω⋅cm,KΩ⋅cm
Velocity m/s,mm/s
Temperature K,°C,°F
Turbidity FNU,NTU
Voltage V,mV,µV
Volume ml,l,m³,fl.oz.(Imp),USgal,Impgal
Unitspertime 1/s,1/min,1/h,1/d
Selectphysicalsize
Unit °C*
Possibleselection:
Theunitsappearaccordingtotheselectedphysicalsize.
Selectunit
Thephysicalsizeandtheunitareset.
*The value set previously appears here.
Re 4 :Assignthelowervalueofthephysicalsizetothelowervalueoftheinputsignal.
Configure Valueat4mA** 9.99°C*
Setvalue
Theassignmentisset.
*The value set previously appears here. **The lower value of the set input signal appears here.
English
34
Configurationusingthedisplay
TypeME24
Re 5 :Assigntheuppervalueofthephysicalsizetotheuppervalueoftheinputsignal.
Configure Valueat20mA** 30°C*
Setvalue
Theassignmentisset.
*The value set previously appears here. **The upper value of the set input signal appears here.
Re 6 :Setfilterresponsetime.
Theuserusesthisfunctiontospecifythedegreeofdampingforcurrentfluctuationsorvoltagefluctuationsoftheinputsignal.
Configure Filterresponsetime 3s*
Setvalue
Thefilterresponsetimeisset.
*The value set previously appears here.
Re 7 :Setwarninglimitvaluesanderrorlimitvalues.
Theuserusesthisfunctiontospecifythewarninglimitvaluesanderrorlimitvaluesfortheinputsignaland/orthephysicalsize.
Exampleofwarninglimitvalues:
Messagestriggers Warnings
Warningtriggers Activationsflag Emptylist
Possibleselection:
Lowlimit
Highlimit
Lowrawlimit
Highrawlimit
Openloop
Activateactivationflags
Settingthevaluesinthefollowingmenusaccordingtotheselectedactivationflags:
Warningtriggers Lowlimit -10°C*
Warningtriggers Highlimit -10°C*
Warningtriggers Lowrawlimit 0mA*
Warningtriggers Highrawlimit 0mA*
Thewarningtriggersandvaluesareset.
*The value set previously appears here
English
35
Configurationusingthedisplay
TypeME24
9.6.2 Calibratinganaloginput
Userlevel:Installer
→ SwitchtoMaintenancedetailedview.
Possiblecalibrationoftheanaloginputs:
• Calibrationoftheanaloginputwithregardtoameasuredvariable
• Calibrationoftheanaloginput(currentorvoltage)
• Calibrationoftheanaloginputtofactorysettings
Calibrationoftheanaloginputwithregardtoameasuredvariable
Thiscalibrationdoesnotreplacethecalibrationoftheconnecteddevice.
Calibration 2-pointcalibration
Theinputassistantstarts.
Inputvalueforpoint1 -10°C*
Setvalue
Waituntilthemeasuredvaluestabilizes
Inputvalueforpoint2 -10°C*
Inputvalue
Waituntilthemeasuredvaluestabilizes
Thecalculatedvaluesaredisplayed.
Accept orReject
Accept:
Thesettingsareaccepted.
Reject:
Theinputassistantstops.
*The value set previously appears here.
English
36
Configurationusingthedisplay
TypeME24
Calibrationoftheanaloginput(currentorvoltage)
Hardwarecalibration 2-pointcalibration
Theinputassistantstarts.
Inputvalueforpoint1 0mA*
Setvalue
Waituntilthemeasuredvaluestabilizes
Inputvalueforpoint2 0mA*
Setvalue
Waituntilthemeasuredvaluestabilizes
Thecalculatedvaluesaredisplayed.
Accept orreject
Accept:
Thesettingsareaccepted.
Reject:
Theinputassistantstops.
*The value set previously appears here.
Calibrationoftheanaloginputtofactorysettings
Hardwarecalibration Resettofactorycalibration
Theinputassistantstarts.
Thesettingsareaccepted.
English
37
Configurationusingthedisplay
TypeME24
9.6.3 Resetanaloginputtofactorysettings
Userlevel:Installer
→ SwitchtoMaintenancedetailedview.
Factorysettingforanaloginputs:Inputsignal0-10V
Resettofactorysettings
Thesettingsareaccepted.
9.6.4 Settingdigitalinput
Userlevel:Installer
→ SwitchtoParametersdetailedview.
→ 1 Selectoperatingmode.
→ 2 Changenameifrequired.
→ 3 Selectunit.Activeforflowrateoperatingmodeonly.
→ 4 Selecttotalizerunit.Activeforflowrateoperatingmodeonly.
→ 5 Setresponsetimeofthefilter.Activeforflowrateoperatingmodeonly.
→ 6 SetKfactor.Activeforflowrateoperatingmodeonly.
→ 7 Setwarninglimitvaluesanderrorlimitvalues.
Re 1 :Selectoperatingmode.
Configure Operatingmode Notconfigured*
Possibleselection:
Notconfigured
Binary
Flowrate
Selectoperatingmode
Theoperatingmodeisset.
*The value set previously appears here.
English
38
Configurationusingthedisplay
TypeME24
Re 2 :Changename.
Configure Name DI1*
Setname
Thenameisset.
*The value set previously appears here.
Re 3 :Selectunit.Activeforflowrateoperatingmodeonly.
Configure Unit l/s*
Unit l/s*
Possibleselection:
l/h
l/min
l/s
m³/h
m³/min
m³/s
USgal/h
USgal/min
USgal/s
Impgal/h
Impgal/min
Impgal/s
Selectunit
Theunitisset.
*The value set previously appears here.
English
39
Configurationusingthedisplay
TypeME24
Re 4 :Selecttotalizerunit.Activeforflowrateoperatingmodeonly.
Configure Totalizerunit l*
Possibleselection:
l
m³
USgal
Impgal
Selectunit
Theunitisset.
*The value set previously appears here.
Re 5 :Setfilterresponsetime.Activeforflowrateoperatingmodeonly.
Theuserusesthisfunctiontospecifythedegreeofdampingformeasuredvaluefluctuationsofthedigitalinput.
Configure Filterresponsetime 3s*
Setvalue
Thefilterresponsetimeisset.
*The value set previously appears here.
Re 6 :SetKfactor.Activeforflowrateoperatingmodeonly.
Configure Kfactor 1*
SetKfactor
TheKfactorisset.
*The value set previously appears here.
English
40
Configurationusingthedisplay
TypeME24
Re 7 :Setwarninglimitvaluesanderrorlimitvalues.
Theuserusesthisfunctiontospecifythewarninglimitvaluesanderrorlimitvaluesfortheinputsignaland/orthephysicalsize.
Exampleofwarninglimitvalues:
Messagestriggers Warnings
Theinputassistantstarts.
Warningtriggers Activationflag Emptylist
Possibleselection:Flowrateoperatingmode
Lowlimit
Highlimit
Possibleselection:Binaryoperatingmode
Inputnotactivated
Inputactivated
Activateactivationflags
Settingthevaluesinthefollowingmenusaccordingtotheselectedactivationflags:Activeforflowrateoperatingmodeonly.
Warningtriggers Lowlimit 0l/s*
Warningtriggers Highlimit 0l/s*
Thewarningtriggersandvaluesareset.
*The value set previously appears here.
9.6.5 Resettotalizer,onlywhenFlowrateoperatingmodeactive
Userlevel:Installer
→ SwitchtoMaintenancedetailedview.
Resettotalizer
Thetotalizerisreset.
English
41
Configurationusingthedisplay
TypeME24
9.6.6 Calibratedigitalinput,forFlowrateoperatingmodeonly
Userlevel:Installer
→ SwitchtoMaintenancedetailedview.
Possiblecalibrationofthedigitalinputs:
• SettingKfactor
• Calibratingtheflowratevolume
• Calibratingtheflowrate
CalibratingtheflowratevolumetodeterminetheKfactor.
Calibration Volumeteaching
Theinputassistantstarts.
Volumeunit ml*
Selectunit
Flowunit l/h*
Selectunit
Themeasurementstarts.
Waituntilthemeasurementhasended
Referencevolume 0ml*
Setvalue
ThecalculatedKfactorisdisplayed.
Accept orReject
Accept:
Thesettingsareaccepted.
Reject:
Theinputassistantstops.
*The value set previously appears here.
English
42
Configurationusingthedisplay
TypeME24
CalibratingtheflowratetodeterminetheKfactor.
Calibration Flowteaching
Theinputassistantstarts.
Flowunit l/h*
Selectunit
Themeasurementstarts.
Waituntilthemeasurementhasended.
Referenceflow 0l/h*
Setvalue
ThecalculatedKfactorisdisplayed.
Accept orReject
Accept:
Thesettingsareaccepted.
Reject:
Theinputassistantstops.
*The value set previously appears here.
9.6.7 Resettingdigitalinputtofactorysettings
Userlevel:Installer
→ SwitchtoMaintenancedetailedview.
Factorysettingfordigitalinputs:Binaryoperatingmode
Resettofactorysettings
Thesettingsareaccepted.
English
43
Configurationusingthedisplay
TypeME24
9.6.8 Simulationofaprocessvalueontheinputmodule
Theusercanusethisfunctiontosetanincomingprocessvalueontheinputmodule.
Userlevel:Installer
→ SwitchtoMaintenancedetailedview.
Simulation Status Off*
Select ON
Value 30.25°C*
Setvalue
Thesettingsareaccepted.
*The value set previously appears here.
English
44
Configurationusingthedisplay
TypeME24
9.7 Settingoutputmodule
Beforesettingtheoutputmodules,makethesettingsintheassigneddevicesorinputmodules.
9.7.1 Settinganalogoutput
Userlevel:Installer
→ SwitchtoParametersdetailedview.
Settinginput(assignment):
→ 1 Selectdeviceandvaluewhichisassignedtotheanalogoutput.
→ 2 Changenameifrequired.
Re 1 :Settinginput(assignment).
Mapping Configure
Theinputassistantstarts.
None Selectdevice*
AI1** Selectvalue***
Theselectedsettingsaredisplayed.
Thedeviceisrestartedandthesettingsareaccepted.
*Theconnecteddevicesappear.**The1stvalueonthelistappears.***Thepossiblevaluesoftheselecteddeviceappear.
Re 2 :Changename.
Mapping Name AI1*
Setname
Thenameisset.
*The value set previously appears here.
English
45
Configurationusingthedisplay
TypeME24
Settingoutput:
→ 1 Setthevalueoftheprocessinputwhichisassignedtothecurrentof4mA.
→ 2 Setthevalueoftheprocessinputwhichisassignedtothecurrentof20mA.
→ 3 Setresponsetimeofthefilter.
→ 4 Changenameifrequired.
→ 5 Selectinitialvalueforerrorhandling(onlyifassigneddeviceismissing).
→ 6 Activatingdiagnostics:Todetectanopencurrentloop.
Re 1 , 2 :Setvalueoftheprocessinputfor4mAand20mA.
Output Valueat4mA -10°C*
Output Valueat20mA 30°C*
Setvalue
Thevalueisset.
*The value set previously appears here.
mA
0
20
4
P1 P2
Figure 16: Current 4 - 20 mA depending on the process value
Re 3 :Setfilterresponsetime.
Theuserusesthisfunctiontospecifythedegreeofdampingformeasuredvaluefluctuationsoftheanalogoutput.
Output Filterresponsetime 3s*
Setvalue
Thefilterresponsetimeisset.
*The value set previously appears here.
English
46
Configurationusingthedisplay
TypeME24
Re 4 :Changename.
Output Name AO2*
Setname
Thenameisset.
*The value set previously appears here.
Re 5 :Selectinitialvalueforerrorhandling(onlyifassigneddeviceismissing).
Theuserusesthisfunctiontoselectthevaluewhichisoutputforanerrormessage.
Errorhandling Outputvalue 22.0mA*
Possibleselection:
Lastvalidvalue
22.0mA
20.5mA
3.5mA
Selectvalue
Theinitialvalueforerrorhandlingisset.
*The value set previously appears here.
Re 6 :Activateactivationflagfordiagnostics.
Todetectanopencurrentloop(e.g.brokenwire),thediagnosticsmustbeactivated.
Diagnostics Activationflag None*
Setflag
Theactivationflagisset.
*The value set previously appears here.
English
47
Configurationusingthedisplay
TypeME24
9.7.2 Calibratinganalogoutput
Userlevel:Installer
→ SwitchtoMaintenancedetailedview.
Calibratinganalogoutputwithinputassistants:
→ Connectameasuringdevicetotheanalogoutput(e.g.amultimeter).
Hardwarecalibration Wizard Start
Theinputassistantstarts.
Measuredvalue 4.24mA*
Setmeasuredvalueofthemeasuringdevice
Measuredvalue 19.91mA*
Setmeasuredvalueofthemeasuringdevice
Theselectedsettingsaredisplayed.
Thesettingsareaccepted.
*The value set previously appears here.
Manuallysettingvaluesforanalogoutput:
Theusercanmanuallysetthevaluesfor4mAand20mAinthemenus.
Hardwarecalibration Valuefor4mA 4.24mA*
Hardwarecalibration Valuefor20mA 19.94mA*
Setvalue
Thevalueisset.
*The value set previously appears here.
Calibratinganalogoutputtofactorysettings
Hardwarecalibration Resettofactorysettings
Theinputassistantstarts.
Thesettingsareaccepted.
English
48
Configurationusingthedisplay
TypeME24
9.7.3 Resettinganalogoutputtofactorysettings
Userlevel:Installer
→ SwitchtoMaintenancedetailedview.
Resettofactorysettings
Thesettingsareaccepted.
9.7.4 Settingdigitaloutput
Userlevel:Installer
→ SwitchtoParametersdetailedview.
Settinginput(assignment):
→ 1 Selectdeviceandvaluewhichisassignedtothedigitaloutput.
→ 2 Changenameifrequired.
Re 1 :Selectdeviceandvaluewhichisassignedtothedigitaloutput.
Mapping Configure
None Selectdevice
AI1 Selectvalue
Theselectedsettingsaredisplayed.
Thedeviceisrestartedandthesettingsareaccepted.
Re 2 :Changename.
Mapping Name AI1*
Setname
Thenameisset.
*The value set previously appears here.
English
49
Configurationusingthedisplay
TypeME24
Settingoutput:
→ 1 Selectoperatingmode.
→ 2 Makesettingsaccordingtotheselectedoperatingmode.
Re 1 :Selectoperatingmode:
Output Operatingmode Nonconfigured*
Possibleselection:
Nonconfigured
On-Off Forthecontrolofactuatorswith2states.
Threshold Theoutputstatechangesassoonasathresholdisreached.
PWM Fast:Forthecontrolofaproportionalsolenoidvalve
Slow:ForthecontrolofanOn-Offactuator
PFM E.g.forthecontrolofapump
Selectoperatingmode
Theoperatingmodeisset.Therequiredmenusappearaccordingtothesetoperatingmode.
*The value set previously appears here.
Re 2 :On-Off
SettingsintheOn-Offoperatingmode:
→ On-Off 1 Setthedelaydurationbeforeswitchingovertheoutput.
→ On-Off 2 Selectinvertoutputordonotinvertoutput.
→ On-Off 3 Changenameifrequired.
→ On-Off 4 Selectinitialvalueforerrorhandling(onlyifassigneddeviceismissing).
→ On-Off 5 Setpowerreduction(for4DOPWM20kHzonly).
ReOn-Off 1 :Setdelaydurationbeforeswitchingovertheoutput.
Output Delay 0s*
Settime
Thedelaydurationisset.
*The value set previously appears here.
English
50
Configurationusingthedisplay
TypeME24
ReOn-Off 2 :Invertoutput.
Output Inversion Off*
Select ON
Theoutputisinverted.
*The value set previously appears here.
ReOn-Off 3 :Changename.
Output Name DO1OnOff*
Setname
Thenameisset.
*The value set previously appears here.
ReOn-Off 4 :Selectinitialvalueforerrorhandling(onlyifassigneddeviceismissing).
Theuserusesthisfunctiontoselectthevaluewhichisoutputforanerrormessage.
Errorhandling Outputvalue Off*
Possibleselection:
Lastvalidvalue
Off
On
Selectvalue
Theinitialvalueforerrorhandlingisset.
*The value set previously appears here.
English
51
Configurationusingthedisplay
TypeME24
ReOn-Off 5 :Setpowerreduction(for4DOPWM20kHzonly).
→ Activatepowerreduction.
→ Settimeafterwhichthepowerreductionbecomesactive(max.10s).
→ Setdutycycle(PWM20kHz).
Voltage
tT1 T2
T1:TimeuntilpowerreductionbecomesactiveT2:Dutycycle(PWM20kHz)
Figure 17: Power reduction
Settingpowerreduction:
Powerreduction Status Off*
Select ON
Powerreduction Powerreductionafter 300ms*
Setvalue
Powerreduction Dutycycle** 30%*
Setvalue
Thepowerreductionisactivatedandthevaluesareset.
*The value set previously appears here. ** Ratio between duty cycle and period duration.
English
52
Configurationusingthedisplay
TypeME24
Re 2 :Thresholdvalue
Settingsinthethresholdvalueoperatingmode:
→ Thresholdvalue 1 Selectingtypeofthreshold:Hysteresisorwindow.
→ Thresholdvalue 2 Setlowerthresholdvalue.
→ Thresholdvalue 3 Setupperthresholdvalue.
→ Thresholdvalue 4 Setthedelaydurationbeforeswitchingovertheoutput.
→ Thresholdvalue 5 Selectinvertoutputordonotinvertoutput.
→ Thresholdvalue 6 Changenameifrequired.
→ Thresholdvalue 7 Selectinitialvalueforerrorhandling(onlyifassigneddeviceismissing).
→ Thresholdvalue 8 Setpowerreduction(for4DOPWM20kHzonly).
Contact
ON
OFF Processvaluelower upperThresholdvalue
notinvertedContact
ON
OFF Processvaluelower upperThresholdvalue
inverted
Contact
ON
OFF Processvaluelower upperThresholdvalue
notinvertedContact
ON
OFF Processvaluelower upperThresholdvalue
inverted
Hysteresisthresholdtype:
Windowthresholdtype:
Figure 18: Threshold value operating mode
Rethresholdvalue 1 :Selectthresholdvalue.
Output Thresholdmode Hysteresis*
Possibleselection:
Hysteresis
Window
Selectthresholdvalue
Thethresholdvalueisset.
*The value set previously appears here.
English
53
Configurationusingthedisplay
TypeME24
Rethresholdvalue 2 :Setlowerthresholdvalue.
Output Lowerthreshold 0l/s*
Setvalue
Thelowerthresholdvalueisset.
*The value set previously appears here.
Rethresholdvalue 3 :Setupperthresholdvalue.
Output Upperthreshold 1.7l/s*
Setvalue
Theupperthresholdvalueisset.
*The value set previously appears here.
Rethresholdvalue 4 :Setlowerdelayduration.
Output Delay 0s*
Setvalue
Thedelaydurationisset.
*The value set previously appears here.
Rethresholdvalue 5 :Invertoutput.
Output Inversion Off*
Select ON
Theoutputisinverted.
*The value set previously appears here.
Rethresholdvalue 6 :Changename.
Output Name DO1OnOff*
Setname
Thenameisset.
*The value set previously appears here.
English
54
Configurationusingthedisplay
TypeME24
Rethresholdvalue 7 :Initialvalueforerrorhandling(onlyifassigneddeviceismissing).
Theuserusesthisfunctiontoselectthevaluewhichisoutputforanerrormessage.
Errorhandling Outputvalue Off*
Possibleselection:
Lastvalidvalue
Off
On
Selectvalue
Theinitialvalueforerrorhandlingisset.
*The value set previously appears here.
Rethresholdvalue 8 :Setpowerreduction(for4DOPWM20kHzonly).
→ Activatepowerreduction.
→ Settimeafterwhichthepowerreductionbecomesactive(max.10s).
→ Setdutycycle(PWM20kHz).
Voltage
tT1 T2
T1:TimeuntilpowerreductionbecomesactiveT2:Dutycycle(PWM20kHz)
Figure 19: Power reduction
Settingpowerreduction:
Powerreduction Status Off*
Select ON
Powerreduction Powerreductionafter 300ms*
Setvalue
Powerreduction Dutycycle** 30%*
Setvalue
Thepowerreductionisactivatedandthevaluesareset.
*The value set previously appears here. ** Ratio between duty cycle and period duration.
English
55
Configurationusingthedisplay
TypeME24
Re 2 :PWM
SettingsinthePWMoperatingmode:
→ PWM 1 SelecttypeofPWM:fastorslow.
RePWM 1 :SelectthetypeofPWM.
Output Mode FastPWM*
Possibleselection:
FastPWM
SlowPWM
Selecttype
ThetypeofPWMisset.
*The value set previously appears here.
SettingsforfastPWMselection:
→ FastPWM 1 Setvalueoftheoutputfrequency.
→ FastPWM 2 SetvalueoftheprocessinputwhichcorrespondstoaPWMof0%.
→ FastPWM 3 SetvalueoftheprocessinputwhichcorrespondstoaPWMof100%.
→ FastPWM 4 Selectinvertoutputordonotinvertoutput.
→ FastPWM 5 Changenameifrequired.
→ FastPWM 6 Selectinitialvalueforerrorhandling(onlyifassigneddeviceismissing).
Output
100%
0% t
notinverted
T2
T1 T1T1T1
T2 T2
Output
100%
0% t
inverted
T2
T1 T1T1
T2 T2
T1variesT2=period,constant=1/frequency
FastPWM:
Figure 20: Fast PWM operating mode
English
56
Configurationusingthedisplay
TypeME24
RefastPWM 1 :Setoutputfrequency.
Output Frequency 2000Hz*
Setvalue
Theoutputfrequencyisset.
*The value set previously appears here.
RefastPWM 2 :SetvalueoftheprocessinputforaPWMof0%.
Output Valueat0% 0l/s*
Setvalue
Thevalueisset.
*The value set previously appears here.
RefastPWM 3 :SetvalueoftheprocessinputforaPWMof100%.
Output Valueat100% 0l/s*
Setvalue
Thevalueisset.
*The value set previously appears here.
RefastPWM 4 :Invertoutput.
Output Inversion Off*
Select ON
Theoutputisinverted.
*The value set previously appears here.
RefastPWM 5 :Changename.
Output Name DO1Percent*
Setname
Thenameisset.
*The value set previously appears here.
English
57
Configurationusingthedisplay
TypeME24
RefastPWM 6 :Initialvalueforerrorhandling(onlyifassigneddeviceismissing).
Errorhandling Outputvalue Errorvalue*
Possibleselection:
Lastvalidvalue
Errorvalue
Selectvalue
Errorhandling Errorvalue 0%*
Setvalue
Theerrorhandlingisset.
*The value set previously appears here.
English
58
Configurationusingthedisplay
TypeME24
SettingsforslowPWMselection:
→ SlowPWM 1 SetvalueofperiodT2.
→ SlowPWM 2 Setminimumswitch-ontimeT1.
→ SlowPWM 3 SetvalueoftheprocessinputwhichcorrespondstoaPWMof0%.
→ SlowPWM 4 SetvalueoftheprocessinputwhichcorrespondstoaPWMof100%.
→ SlowPWM 5 Selectinvertoutputordonotinvertoutput.
→ SlowPWM 6 Changenameifrequired.
→ SlowPWM 7 Selectinitialvalueforerrorhandling(onlyifassigneddeviceismissing).
Output
100%
0% t
notinverted
T2
T1 T1T1T1
T2 T2
Output
100%
0% t
inverted
T2
T1 T1T1
T2 T2
T1variesT2=period,constant
SlowPWM:
Figure 21: Slow PWM operating mode
ReslowPWM 1 :SetvalueofperiodT2.
Output Period 60s*
Setvalue
Thevalueisset.
*The value set previously appears here.
ReslowPWM 2 :Setminimumswitch-ontimeT1.
Output MinimumONtime 0.125s*
Setvalue
Thevalueisset.
*The value set previously appears here.
English
59
Configurationusingthedisplay
TypeME24
ReslowPWM 3 :SetvalueoftheprocessinputforaPWMof0%.
Output Valueat0% 0*
Setvalue
Thevalueisset.
*The value set previously appears here.
ReslowPWM 4 :SetvalueoftheprocessinputforaPWMof100%.
Output Valueat100% 100*
Setvalue
Thevalueisset.
*The value set previously appears here.
ReslowPWM 5 :Invertoutput.
Output Inversion Off*
Select ON
Theoutputisinverted.
*The value set previously appears here.
ReslowPWM 6 :Changename.
Output Name DO1Percent*
Setname
Thenameisset.
*The value set previously appears here.
ReslowPWM 7 :Initialvalueforerrorhandling(onlyifassigneddeviceismissing).
Errorhandling Outputvalue Errorvalue*
Possibleselection:
Lastvalidvalue
Errorvalue
Selectvalue
Errorhandling Errorvalue 0%*
Setvalue
Thenameisset.
*The value set previously appears here.
English
60
Configurationusingthedisplay
TypeME24
Re 2 :PFM
SettingsinPFMoperatingmode:
→ PFM 1 Selectmaximumfrequency(1/T2)ofthepulses.
→ PFM 2 Selectpulsewidth(T1).
→ PFM 3 Setvalueoftheprocessinputwhichcorrespondstotheminimumfrequencyat0%.
→ PFM 4 Setvalueoftheprocessinputwhichcorrespondstothemaximumfrequencyat100%.
→ PFM 5 Selectinvertoutputordonotinvertoutput.
→ PFM 6 Changenameifrequired.
→ PFM 7 Selectinitialvalueforerrorhandling(onlyifassigneddeviceismissing).
Output
100%
0% t
notinverted
T2
T1
T2 T2 T2
Output
100%
0% t
inverted
T2
T1
T2 T2 T2
T1=period,constantT2varies
PFM:
Figure 22: PFM operating mode
RePFM 1 :Setmaximumfrequency(1/T2).
Output Maximumfrequency 1801/min*
Setvalue
Thevalueisset.
*The value set previously appears here.
RePFM 2 :Setpulsewidth(T1).
Output Pulsewidth 0.2s*
Setvalue
Thevalueisset.
*The value set previously appears here.
English
61
Configurationusingthedisplay
TypeME24
RePFM 3 :Setvalueoftheprocessinputattheminimumfrequencyof0%.
Output Valueat0% 0*
Setvalue
Thevalueisset.
*The value set previously appears here.
RePFM 4 :Setvalueoftheprocessinputattheminimumfrequencyof100%.
Output Valueat100% 100*
Setvalue
Thevalueisset.
*The value set previously appears here.
RePFM 5 :Invertoutput.
Output Inversion Off*
Select ON
Theoutputisinverted.
*The value set previously appears here.
RePFM 6 :Changename.
Output Name DO1Percent*
Setname
Thenameisset.
*The value set previously appears here.
RePFM 7 :Initialvalueforerrorhandling(onlyifassigneddeviceismissing).
Errorhandling Outputvalue Errorvalue*
Possibleselection:
Lastvalidvalue
Errorvalue
Selectvalue
Errorhandling Errorvalue 0%*
Setvalue
Thenameisset.
*The value set previously appears here.
English
62
Configurationusingthedisplay
TypeME24
9.7.5 Manuallyactuatingoutputmodule
Theusercanusethisfunctiontosetavalueontheoutputmodule.
Userlevel:Installer
→ SwitchtoMaintenancedetailedview.
MANUALoperatingstate Status Off*
Select ON
Value 10mA*
Setvalue
Thesettingsareaccepted.
*The value set previously appears here.
English
63
Displayelements
TypeME24
10 DISPLAYELEMENTSTheLEDdisplayelementsprovideinformationaboutthedevicestatus.
DisplayelementontheI/OmoduleTypeME24
LEDfordevicestatus(colorsinaccordancewithNAMURNE107)
Fordescriptionseechapter“10.7.1”
Figure 23: Display element, I/O module Type ME24
Displayelementonthedisplay,ifavailable
XXXX
PMU
Gerät XXXX
Standort Status N/A
Sprache Deutsch Benutzerebene
IP-Adresse
Geräteansicht 24.04.2014 10:25
HMIU
PMU
NAMURlightelement
Figure 24: Display element, display
English
64
Displayelements
TypeME24
10.7.1 Displayofdevicestatus
TheLEDfordevicestatusandtheNAMURlightelementchangescolorinaccordancewithNAMURNE107.
Ifseveraldevicestatusesexistsimultaneously,thedevicestatuswiththehighestpriorityisdisplayed.Thepriorityisdeterminedbytheseverityofthedeviationfromcontrolledoperation(redLED=failure=highestpriority).
StatusdisplayinaccordancewithNE107,edition2006-06-12
Color ColorCode Description Meaning
Red 5 Failure,errororfault Duetoamalfunctioninthedeviceoronitsperiphery,controlledoperationisnotpossible.
Orange 4 Functioncheck Thedeviceisbeingworkedon;controlledoper-ationisthereforetemporarilynotpossible.
e.g.OperatingmodeHANDorsimulation.
Yellow 3 Outsidethespecification Theambientconditionsorprocessconditionsforthedeviceareoutsidethespecifiedarea.
Blue 2 Maintenancerequirement Thedeviceisincontrolledoperation,howeverfunctionisbrieflyrestricted.
→ Maintaindevice.
Green 1 Diagnosticsactive Deviceisoperatingfaultlessly.Statuschangesareshownincolor.
Messagesaretransmittedviaanyconnectedfieldbus.
White 0 Diagnosticsinactive Deviceisswitchedon.
Statuschangesarenotshown.
Messagesarenottransmittedviaanyconnectedfieldbus.
Table 13: Description of the colors
LightingstateoftheLEDfordevicestatus:
Display Description Meaning
Lightingstate
Off Nopowerissuppliedtothedevice.
Islitgreen Normal Deviceisincontrolledoperation.
Flashingrapidly Identification IsusedforidentificationofadeviceinthebüSnetwork.
Thedeviceisselectedusingthe“Bürk-ert-Communicator”softwareoronadisplay.
Table 14: Description of the lighting state for device status
English
65
Maintenance
TypeME24
11 MAINTENANCE
11.1 Safetyinstructions
WARNING!
Riskofinjuryfromimpropermaintenance.
Maintenancemaybecarriedoutonlybytrainedtechniciansandwiththeappropriatetools.
Securesystemagainstunintentionalactivation.
Followingmaintenance,ensureacontrolledrestart.
11.2 Replacingdevices
1.Takesafetymeasures:
→ Switchoffsupplyvoltage!
2.Removecablesfromsensorsandactuators.
→ Ifthecablehasbeensecuredtothehousingforstrainrelief,removecablefromsecuringdevice.
→ UnscrewfasteningscrewatthecoverofTypeME24.
→ Openandremovecover.
→ Removeconnectionterminal.
→ Presspush-incontactsontotheconnectionterminalandpulloutwires.
I/OmoduleTypeME24
Coveropened
BackplaneTypeBEF1
Fasteningscrewforbackplane
Fasteningscrewforcover
Figure 25: Replacing devices, I/O module Type ME24
English
66
Maintenance
TypeME24
3.RemoveI/OmoduleTypeME24fromthebackplaneTypeBEF1.
→ UnscrewfasteningscrewontherearofthehousingandremoveTypeME24.
4.Changethememorycardifrequired
Thememorycardisontheundersideofthedevice.
MicroSDcard
MicroSIMcard
Figure 26: Replacing the memory card, I/O module ME24
Removingthememorycard:
→ MicroSDcard:PressontheedgeoftheengagedmicroSDcardtounlockit.
→ Pulloutmemorycard.
Insertingmemorycardintothereplacementdevice:
Insertmemorycardintherightdirection.
→ Pushmemorycardintothecardholderofthereplacementdevice.MicroSDcard:EnsurethatthemicroSDcardclicksintoplace.
5.Installreplacementdevice.
→ InserthingepartofTypeME24intothecounterpieceofbackplaneTypeBEF1.
→ PressTypeME24fullyontothebackplane.
→ Tightenfasteningscrewforbackplane.Maximumtorque1Nm.
→ UnscrewfasteningscrewonthecoveroftheTypeME24(hexagonsocket2.5mm).
→ Openandremovecover.
→ Pulloutconnectionterminals.
→ Insertcablesoftheexternalsensorsandactuatorsthroughtheopeningonthebackofthecover.
→ Connectwiresoftheexternalsensorsandactuatorstotheconnectionterminals(plugconfigurationseechapter“7.3.1Plugconfigurationandwiring”).
→ Reconnectconnectionterminal.
English
67
Maintenance
TypeME24
→ Closecoverandtightenfasteningscrew.Maximumtorque1Nm.
TypeME24isconnectedtothepowersupplyofthebackplaneTypeBEF1.
Securingthecables(strainrelief):Torelievethestrain,fixthecablestotherecesswithacableclip.
Recessforsecuringthecables
Figure 27: Strain relief for cables, I/O module Type ME24
11.3 Replacingthememorycard
TheI/OmoduleME24hasaremovabledatastorageintheformofamemorycardonwhichthedevice-specificdataisstored.
Onmodules2AO,2DOand4DOthismemorycardisamicroSDcard.Onmodule2AI,2DIaMicroSIMcard.
Thedeviceisdeliveredwiththememorycardinserted.
Thememorycardcanbeusedtoreplacespecificdataondeviceswhichhavethesameidentificationnumber.Forexample,fortransferringthedatafromadefectivedevicetoanewdevice.
Thememorycardstorese.g.thebaudrate,theaddressand/ortheconfigurationofthedeviceprocessvalues.
Ifthereisdevice-specificdataontheinsertedmemorycardduringtherestart,thedevicewilltakeoverthisdata.
Ifthereisnodevice-specificdataonthememorycard,thedevicewillstoreitsowndataonit.
NOTE!
Donotuseastandardmemorycardforthedevice.PurchasethememorycardforTypeME24fromyourBürkertsalesdepartment.Seechapter“12Accessories”.
ThemicroSDcardmustbeformattedwiththeFAT12/16/32filesystem.Ifthisisnotthecase,thecardwillnotbedetectedwhenitisinserted.
Replacingthememorycard:
Thememorycardisontheundersideofthedevice.
1.Takesafetymeasures:
→ Switchoffsupplyvoltage!
2.RemoveI/OmoduleTypeME24fromthebackplaneTypeBEF1.
→ UnscrewfasteningscrewontherearofthehousingandremoveTypeME24.
English
68
Maintenance
TypeME24
I/OmoduleTypeME24
BackplaneTypeBEF1
Fasteningscrewforbackplane
Figure 28: Replacing devices, I/O module Type ME24
3.Removingthememorycard:
→ MicroSDcard:Pressontheedgeoftheengagedmemorycardtoreleaseit.
→ Pulloutmemorycard.
MicroSDcard
MicroSIMcard
Figure 29: Replacing the memory card, I/O module ME24
4.Insertingmemorycardintothedevice:
Insertmemorycardintherightdirection.
→ Pushmemorycardintothecardholderofthedevice.Ensurethatthememorycardclicksinplace.
5.InstallingI/Omodule:
→ InserthingepartofTypeME24intothecounterpieceofbackplaneTypeBEF1.
→ PressTypeME24fullyontothebackplane.
→ Tightenfasteningscrewforbackplane.Maximumtorque1Nm.
ThememorycardisreplacedandTypeME24connectedtothebackplaneTypeBEF1.
English
69
Maintenance
TypeME24
11.4 Troubleshooting
Problem Possiblecause Procedure
LEDisnotlit. Nopowerissuppliedtothedevice. Connectdevicetopowersupply.
LEDgoesoutperiodically. Thesupplyvoltagefailsperiodically:Thedeviceperformsareset.
Usepowersupplywithadequatepower.
Thevoltagedropintheconnectioncableistoogreat.
Increasesupplyvoltage(Attention:donotexceedmaximumpermittedvoltage).Increasecablecross-section.Reducecablelength.
LEDislitred. Assigneddeviceismissing(for2AO,2DOand4DOPWM20kHzonly).
Checkassigneddevice,e.g.defectivedevice,faultybüSconnection,nosupplyvoltage,etc.
büSconnectionnotavailable CheckbüSnetwork.Opencurrentloop(e.g.Brokenwire)detected(onlyontheanalogoutputofmodule2AO,2DO).
Checksignallinesoftheanalogoutputs.
Replacementdevicedoesnottakeovervaluesfromthememorycardtakenoutofthedefectivedevice.
Thedeviceidentificationnumbersofthereplacementdeviceandthedefectivedevicediffer.
Onlyvalueshavingthesameidentitynumbercanbetransferredbetweendevices.
Thememorycardisdefective.Thedevicecannotwriteanyvaluestothememorycard.
Replacethememorycardandretrytransferringtheparametersfromthedefectivedevicetothememorycard.(Seechapter“11.3Replacingthememorycard”).
Replacementdevicedoesnottakeoverallvaluesfromthememorycardtakenoutofthedefectivedevice.
TheEDSdevicedescriptionbetweenthereplacementdeviceandthedefectivedevicediffers.
Onlyexistingvaluesofthedefectivedevicecanbetransferredtothereplacementdevice.Setnewvaluesofthereplacementdeviceusingthe“Bürkert-Communi-cator”software.
Table 15: Troubleshooting
English
70
Maintenance
TypeME24
12 ACCESSORIES
CAUTION!
Riskofinjuryand/ordamagebytheuseofincorrectparts.
Incorrectaccessoriesandunsuitablesparepartsmaycauseinjuriesanddamagethedeviceandthesur-roundingarea.
UseoriginalaccessoriesandoriginalsparepartsfromBürkertonly.
Accessories Orderno.
büSstickwithcable(socketM12) 00772551
büSstickset(includingpowersupplyunit)and"BürkertCommunicator"software 00772426
MicroSDcard 00919877
MicroSIMcard 00919902
English
71
PackagingandTransport
TypeME24
13 PACKAGINGANDTRANSPORT
NOTE!
Transportdamage.
Inadequatelyprotecteddevicesmaybedamagedduringtransportation.
• Protectthedeviceagainstmoistureanddirtinshock-resistantpackagingduringtransportation.
• Preventthetemperaturefromexceedingordroppingbelowthepermittedstoragetemperature.
14 STORAGE
NOTE!
Incorrectstoragemaydamagethedevice.
• Storethedeviceinadryanddust-freelocation.
• Storagetemperature:–40°C–+60°C.
15 DISPOSAL
NOTE!
Damagetotheenvironmentcausedbypartscontaminatedwithmedia.
• Disposeofthedeviceandpackaginginanenvironmentallyfriendlymanner.
• Observeapplicabledisposalandenvironmentalregulations.
Observethenationalwastedisposalregulations.