Installing Intrinsic SafetyTermination Panels andBarriers
Installation Manual
PH2.1:CL6340
Revision D July 2003This manual supercedes the issue dated November 1995.
D3P
01241402
ABC Batch, ConfiguWrite, DeltaV, DOCVUE, ENVOX, FIELDVUE, Fisher-Rosemount, InstrumentInformation System, Managing The Process Better, microPROVOX, MOMENTUM, PROFLEX,ProjectDelta, PROVOX, PROVUE, RNI, RS3, and ValveLInk are marks of one of the Fisher-Rosemountgroup of companies.
All other marks are the property of their respective owners.
See CE Statement in Section 1
2000, 2003 Fisher-Rosemount Systems, Inc. All rights reserved.Printed in USA
The contents of this publication are presented for informational purposes only, and while every efforthas been made to ensure their accuracy, they are not to be construed as warranties or guarantees,express or implied, regarding the products or services described herein or their use or applicability. Wereserve the right to modify or improve the designs or specifications of such products at any time withoutnotice.
iiiInstalling Intrinsic Safety Termination Panels and Barriers(Revision D July 2003)
Your Evaluation Please ...
Name: Title and Department:
Company: Years of Experience: ___ Instrumentation ___ Distributed Control
Telephone: ( ) Education: ____High School ____Years College ____Degree
Job Responsibility:
Please indicate your evaluation of this manual. Attach extra sheets if needed.
1. How and when do you use this manual? Read entire manual before attempting task
Read selected sections before attempting task
Read while attempting task
Attempt task first
Read as last resort
2. How well is the manuals contentorganized? Please explain.
Excellent parallels products operation,very usable
Good representative of the productsoperation, usable
Average usable but can be improved
Fair not very usable, should be improved
Poor not usable, must be improved
No Opinion
Understandable Applicable
3. Is the manuals content understandableand applicable to the products operation?Please explain.
Excellent very easy to understand,very applicable
Good easy to understand, applicable
Average applicable but some sectionsnot easy to understand
Fair not very understandable/applicable,should be improved
Poor not understandable/applicable,must be improved
No Opinion
4. How well do the manuals illustrationsconvey product information?Please explain.
Excellent very easy to understand, extremelyusable
Good easy to understand, very usable
Average fairly easy to understand, usable
Fair not easy to understand, should beimproved, not very usable
Poor cannot understand, must be improved,totally unusable
No Opinion
iv Installing Intrinsic Safety Termination Panels and Barriers(Revision D July 2003)
Your Evaluation Please ...
5. Describe the amount of usable informationin this manual including tables. Please explain.
Too much information not all required toperform task
Proper amount provided not too much nortoo little
Too little information needed additionalinformation to perform task
No Opinion
Sections Index
6. How well is information cross-referenced inthe manuals individual sections and index?Please explain.
Excellent very easy to locateinformation, extremely usable
Good easy to locate information,very usable
Average fairly easy to locate information,usable
Fair not easy to locate information,should be improved, not very usable
Poor cannot locate information, must beimproved, totally unusable
Did Not Use
No Opinion
7. How useful is the Glossary? Useful
Useful but not complete/accurate
Not Useful
Did Not Use
No Opinion
8. What is your overall impression of thismanual? Please explain.
Excellent met all needs, extremely usable
Good met most of my needs, very usable
Average usable
Fair should be revised, not very usable
Poor must be revised, totally unusable
No Opinion
Please FAX or MAIL this form to: Emerson Process ManagementTechnical Documentation Editor
FAX Number: (512) 4187503 8627 Mopac Expressway NorthAttention: Technical Documentation Editor Austin, TX 78759
vInstalling Intrinsic Safety Termination Panels and Barriers(Revision D July 2003)
Contents
Contents
1 Introduction 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 Intended Audience 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.2 CE Statement 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.3 Structure of this Manual 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.4 Manual Conventions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.5 Warnings, Cautions, and Notes 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.6 Related IS Product Documentation 4. . . . . . . . . . . . . . . . . . . . . . . . 1.7 Related PROVOX Documentation 4. . . . . . . . . . . . . . . . . . . . . . . . . 1.8 Where to Find Answers for Product and Document Questions 4.
2 Product Overview 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.1 Available Termination Panels 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.2 Available Intrinsic Safety Barriers 6. . . . . . . . . . . . . . . . . . . . . . . . . . 2.3 Determining the Quantity of Barriers and Termination Panels for
Your Application 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.4 Physical and Electrical Pre-Installation 8. . . . . . . . . . . . . . . . . . . . .
3 Installation 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.1 Special Considerations 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2 Planning the Physical Installation 9. . . . . . . . . . . . . . . . . . . . . . . . . . 3.2.1 I/O Cards and Card File 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2.2 Termination Panel Installation 10. . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2.3 Barrier Dimensions 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2.4 Termination Cables 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2.4.1 Cabling for Simplex I/O Cards 12. . . . . . . . . . . . . . . . . . . . . . . . . 3.2.4.2 Cabling for 1 for 1 Redundant I/O Cards 16. . . . . . . . . . . . . . . . 3.2.4.3 Cabling 1 for N Configurations 21. . . . . . . . . . . . . . . . . . . . . . . . 3.2.5 Termination Cable Connectors 26. . . . . . . . . . . . . . . . . . . . . . . . . . 3.3 Planning the Electrical Installation 28. . . . . . . . . . . . . . . . . . . . . . . . . 3.3.1 Termination Panel Power 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.3.2 Shield Grounding 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.3.3 DC Grounding 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.3.4 Connecting Field Wiring to Barriers 29. . . . . . . . . . . . . . . . . . . . . .
A Barrier Specifications 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A.1 Type CL6351 IS High-Level Analog Input Isolating Barrier (HART
compatible) 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A.2 Type CL6352 IS Millivolt Input, Type CL6353 IS RTD Input, and
Type CL6354 IS Thermocouple Input Isolating Barriers 34. . . . . . A.3 Type CL6355 IS Analog Output Isolating Barrier 37. . . . . . . . . . . . . A.3.1 Conventional Analog Output Application 37. . . . . . . . . . . . . . . . . . A.3.2 Smart Device Output Application 39. . . . . . . . . . . . . . . . . . . . . . . .
vi Installing Intrinsic Safety Termination Panels and Barriers(Revision D July 2003)
Contents
A.4 Type CL6356 IS Discrete Input Isolating Barrier (With and Without Debounce) 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.5 Type CL6357 IS Discrete Output Isolating Barrier 43. . . . . . . . . . . . A.5.1 Solid State 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A.5.2 Relay Output 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A.6 Type CL6358 IS Pulse Count Input Isolating Barrier 47. . . . . . . . . . A.7 Cross-Reference Between CL6350-Series Type Numbers
and MTL Model Numbers 49. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B Panel and Cable Specifications 51. . . . . . . . . . . . . . . . . . . . . . B.1 Termination Panel Specifications 51. . . . . . . . . . . . . . . . . . . . . . . . . . B.2 Termination Panel Current Requirements 52. . . . . . . . . . . . . . . . . . . B.3 Cable Lengths 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B.4 Field Wiring Specifications 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B.5 MTL Installation Tools 56. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Glossary 57. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Index 61. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
viiInstalling Intrinsic Safety Termination Panels and Barriers(Revision D July 2003)
Contents
Figures
Figure 2-1. Typical CL6340-Series Termination Panel Connections with CL6350-Series Intrinsic Safety Barriers 5. . . . . . . . . . .
Figure 3-1. Type CP6701 Card File Arrangement 10. . . . . . . . . . . . . . . . . Figure 3-2. CL6340-Series Termination Panel Dimensions 11. . . . . . . . . Figure 3-3. CL6350-Series Barrier Dimensions 11. . . . . . . . . . . . . . . . . . . Figure 3-4. Cabling for Two Simplex Analog Output Cards 13. . . . . . . . . Figure 3-5. Cabling for One Simplex Analog Input Cards and for a
Smart Input Termination Panel with a Smart Input Card 14. Figure 3-6. Cabling for Two Simplex Discrete Input Cards 14. . . . . . . . . . Figure 3-7. Cabling for Simplex Discrete Output Cards 15. . . . . . . . . . . . Figure 3-8. Cabling for Simplex Pulse Count Inputs 15. . . . . . . . . . . . . . . Figure 3-9. Cabling for 1 for 1 Redundant Analog Input Cards and for
Smart Input Termination Panel with Smart Input Cards 16. Figure 3-10. Cabling for 1 to 1 Redundant Analog Output Cards 17. . . . . Figure 3-11. Cabling for 1 to 1 Redundant Discrete Input Cards 18. . . . . Figure 3-12. Cabling for 1 to 1 Redundant Discrete Output Cards 19. . . . Figure 3-13. Cabling for 1 to 1 Redundant Pulse Count Inputs 20. . . . . . . Figure 3-14. Cabling for 1 for 4 Redundant Analog Input Cards and
Smart Input Termination Panel with Smart Input Card 22. . Figure 3-15. Cabling for 1 for 2 Redundant Analog Output Cards 23. . . . Figure 3-16. Cabling for 1 to 2 Redundant Discrete Input Cards 24. . . . . Figure 3-17. Cabling for 1 for 3 Redundant Discrete Output Cards 25. . . Figure 3-18. Cabling for 1 to 2 Redundant Pulse Count Inputs 26. . . . . . . Figure 3-19. Barrier and Terminal Connections 30. . . . . . . . . . . . . . . . . . . . Figure A-1. Typical Connections for Type CL6351 32. . . . . . . . . . . . . . . . . Figure A-2. Typical Connections for Type CL6352, Type CL6353, and
Type CL6354 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure A-3. Typical Connections for Type CL6355 37. . . . . . . . . . . . . . . . . Figure A-4. Typical Connections for Type CL6355 (Smart Application) 39Figure A-5. Typical Connection for Type CL6356 41. . . . . . . . . . . . . . . . . . Figure A-6. Typical Connections for Type CL6357 (Solid State) 43. . . . . Figure A-7. Typical Connections for Type CL6357 45. . . . . . . . . . . . . . . . . Figure A-8. Typical Connections for Type CL6358 47. . . . . . . . . . . . . . . . .
viii Installing Intrinsic Safety Termination Panels and Barriers(Revision D July 2003)
Contents
Tables
Table 2-1. Maximum Number of Channels Supported by I/O Cards 8. . Table 2-2. System Planning Documents 8. . . . . . . . . . . . . . . . . . . . . . . . . . Table 3-1. D-Shell Connector Pin Assignments 27. . . . . . . . . . . . . . . . . . . Table A-1. Type CL6353 Range Specifications 35. . . . . . . . . . . . . . . . . . . . Table A-2. Type CL6354 Range Specifications 35. . . . . . . . . . . . . . . . . . . . Table A-3. Cross-Reference Between CL6350-Series Type Numbers
and MTL Model Numbers 49. . . . . . . . . . . . . . . . . . . . . . . . . . . Table B-1. Current Requirements for Termination Panels 52. . . . . . . . . . . Table B-2. Maximum Cable Parameters (FM) Low-Level Signal 53. . . . . Table B-3. Maximum Cable Parameters (FM) Other Signal 53. . . . . . . . Table B-4. Maximum Cable Parameters EECS (ATEX 100) 54. . . . . . . . Table B-5. Installation Tools Ordering Information 56. . . . . . . . . . . . . . . . . .
1Introduction Section 1
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Figure 1-Table 1
1 Introduction
This installation planning manual describes the installation ofCL6340-Series termination panels and CL6350-Series Intrinsic Safetybarriers. This manual also describes physical characteristics, electricalcharacteristics, and wiring required for the termination panels andbarriers. Before developing and installing an intrinsically safe system,consult the guidelines set forth by the country of installation.
1.1 Intended Audience
The information in this manual is written for the installation andmaintenance technician who is familiar with process control systems,intrinsic safety systems, and the attendant field wiring.
1.2 CE Statement
If you intend to have your PROVOX system certified for compliance toappropriate European Union directives, the following statement isextremely important to your ability to achieve that compliance.
This manual describes installation and maintenance procedures forproducts which have been tested to be in compliance with appropriateCE directives. To maintain compliance, these products must beinstalled and maintained according to the procedures described inthis document. Failure to follow the procedures may compromisecompliance.
11
Section 1 Introduction 2
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
1.3 Structure of this Manual
This manual contains the following sections and appendixes:
Section 1 Introduction: includes an overview of this manual, theintended audience, the stylistic and typographical conventions used, andlists additional related documents.
Section 2 Product Overview: provides an overview of the installationprocess, and describes the criteria for determining the intrinsic safetysystem design.
Section 3 Installation: describes the physical and electrical installationof CL6340-series Termination Panels and the CL6350-Series IntrinsicSafety Barriers.
Appendix A Barrier Specifications: provides barrier specifications andfield wiring diagrams.
Appendix B Panel and Cable Specifications: provides terminal panelspecifications, cable specifications, and lists helpful cable installationtools available from MTL Incorporated.
1.4 Manual Conventions
This document uses the following conventions.
Abbreviations Standard abbreviations and symbols are used inthis document. Instances where non-standard abbreviations oracronyms are used, will be explained at the first usage.
Revision Control The title page of each document lists therevision level and the printing date. When the manual is revised, therevision level and the printing date are changed.
Cross Referencing References to other documentation foradditional information list the document name and number.
1
3Introduction Section 1
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
1.5 Warnings, Cautions, and Notes
Warnings, Cautions, and Notes attract attention to essential or criticalinformation in this manual. The types of information included in each areexplained in the following:
All warnings have this form and symbol. Do not disregardwarnings. They are installation, operation, or maintenanceprocedures, practices, conditions, statements, and so forth,which if not strictly observed, may result in personal injury orloss of life.
Warning ...
All cautions have this form and symbol. Do not disregardcautions. They are installation, operation, or maintenanceprocedures, practices, conditions, statements, and so forth,which if not strictly observed, may result in damage to, ordestruction of, equipment or may cause a long term healthhazard.
Caution ...
Notes have this form and symbol. Notes contain installation,operation, or maintenance procedures, practices, conditions,statements, and so forth, that alert you to important informationwhich may make your task easier or increase yourunderstanding.
Note ...
1
Section 1 Introduction 4
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
1.6 Related IS Product Documentation
Reading and understanding the vendors manual for installingintrinsic safety barriers is very important, especially sections 3,5, and 9 which describe various precautions and warnings toheed prior to and during installation. Be sure that you have thelatest version of the instruction manual, MTL4000 SeriesIsolating IS interface units, INM4000.
Note ...
1.7 Related PROVOX Documentation
For detailed information for planning a system installation, includingrequirements for ac power, system grounding, and adequate systemenvironment, consult the documents listed below. Use these relateddocuments to complete the overall system installation planning beforebeginning the planning for subsystem installation.
Planning the Installation, PN1:002
AC and DC Power and Ground Wiring, PN1:003
Signal Wiring and Highway Signal Guidelines, PN1:004
Environmental Conditions for Instrumentation Systems, PN1:006
Lightning Protection Guidelines for Instrumentation Systems,PN1:007
Installing Type CP7043 Series Cabinets, PN4.4:CP7043
Product Bulletin, CL6340-Series Termination Panels andCL6350-Series Intrinsic Safety Barriers, BU4.2:CL6340
1.8 Where to Find Answers for Product and DocumentQuestions
If you believe that this product is not performing as expected, or if youhave comments about this manual, please contact your EmersonProcess Management representative or sales office. You may alsocomplete and send in the Reader Evaluation Form located in the front ofthis manual.
We also appreciate your suggestions on ways to improve any page ofthe manual. Please mark your suggestions on a copy of the page andinclude it with the evaluation form. Thank you for providing thisinformation.
1
5Product Overview Section 2
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Figure 2-Table 2
2 Product Overview
CL6340-Series termination panels can hold as many as sixteenCL6350-Series IS barriers. Figure 2-1 shows a typical IS terminationpanel configuration with barriers.
24V DC PRI24V DC SEC
SHLD
To Control I/OCards in SafeArea
Cable Tray/ControlRoom Safe Side(WHITE) SignalWiring
CL6340-SeriesTermination Panel
PowerConnection FromPower Bus Barin CP7043Cabinet
Blue Cable Trayon TerminationPanel
SideView
Notes:
1
2
INCH(mm)
FrontView
2.0(50.8)
CL6350-SeriesIS Barriers
CableTray/ControlRoom HazardousSide (BLUE)Signal Wiring
TerminationPanel
Barrier
For important precautions and warnings, see the vendorsinstruction manual, MTL4000 Series Isolating IS interface units,INM4000.
Field wiring must not be routed from the end of the blue cable tray.See field wiring instructions in section 3.
A blue horizontal cable tray is provided with each CL6340-Seriestermination panels.
1
2
3
Shield GroundBar (optional)
PSC
1
Figure 2-1. Typical CL6340-Series Termination Panel Connections with CL6350-SeriesIntrinsic Safety Barriers
2 2
Section 2 Product Overview 6
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
2.1 Available Termination Panels
Available CL6340-Series termination panels are:
Type CL6341 Analog Input Termination Panel
Type CL6342 Analog/Smart Device Output Termination Panel (HARTCompatible)
Type CL6343 Discrete Input/Output Termination Panel
Type CL6344 Pulse Count Termination Panel
Type CL6345 Smart Device Input Termination Panel (HARTCompatible)
System designers must follow certain requirements whendesigning an intrinsic safety system using CL6340-Seriestermination panels. Refer to the vendors instruction manual,MTL4000 Series Isolating IS interface units, INM4000 andSection 3 of this manual for an overview of these requirements.Table A-3 in this manual provides a cross reference betweenthe PROVOX type number and the MTL model number.
Note ...
2.2 Available Intrinsic Safety Barriers
CL6350-Series Intrinsic Safety (IS) Barriers plug into CL6340-Seriestermination panels and provide field voltage and current limitationsrequired by an intrinsically safe I/O system. Available barriers are:
Type CL6351 IS High-Level Analog Input Isolating Barrier (HARTcompatible) [4-20 mA]
Type CL6352 IS Millivolt Input Isolating Barrier
Type CL6353 IS RTD Input Isolating Barrier
Type CL6354 IS Thermocouple Input Isolating Barrier
Type CL6355 IS Analog Output Isolating Barrier
This barrier is available in a 4 to 20 mA version for analog outputsignals and a HART-compatible version for smart device outputsignals.
Type CL6356 IS Discrete Input Isolating Barrier
Type CL6357 IS Discrete Output Isolating Barrier
2
7Product Overview Section 2
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Type CL6358 IS Discrete Pulse Count Input Isolating Barrier
Refer to the vendors instruction manual, MTL4000 Series Isolating ISinterface units, INM4000 and Appendix A of this manual for descriptionsand specifications of CL6350-Series barriers.
2.3 Determining the Quantity of Barriers and TerminationPanels for Your Application
The quantity and type of barriers, and termination panels, used for anapplication depend on the field signals and backup strategy.
CL6350-Series barriers for the following signals are available:
Analog Input (AI)
Analog Output (AO)
Smart Device Input (HART compatible)
Smart Device Output (HART compatible)
Discrete Input (DI)
Discrete Output (DO)
Pulse Count Input (PCI)
Types of backup strategies you may choose are:
Simplex (No backup)
1 for 1 Redundancy
1 for N Redundancy
First, determine the number of barriers your system requires. Each signalthat you want to connect to the PROVOX system from the hazardousarea must connect to a barrier.
All CL6350-Series barriers, except Type CL6356, accept one signal froma hazardous area. The Type CL6356 IS discrete input isolating barrieraccepts two input signals. Therefore, you need a barrier for each type ofsignal except a discrete input signal, for which you need one barrier forevery two signals.
Secondly, determine the number of termination panels required. Eachtermination panel can accept as many as 16 barriers carrying the samekind of signals, except for the Discrete Input termination panel, whichcan accept 32 signals (16 barriers with two inputs each.)
You cannot mix major barrier types (AI, AO, DI, DO, PCI, Smart Input,and Smart Output) on a termination panel. For example, you cannot put
2
Section 2 Product Overview 8
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
analog input barriers on the same panel as analog output barriers. Also,you cannot mix analog barriers and smart device barriers on the samepanel. However, you can put the Type CL6353 RTD and Type CL6354Thermocouple IS Input Isolating Barriers on the same panel becausethey are both analog input barriers, using the same analog I/O card.
Next, determine the number of I/O cards needed. To relate the numberof termination panels and barriers to the number of I/O cards, considerthe number and type of channels an I/O card can have. For example, anAnalog I/O card can have as many as 16 analog input channels or asmany as 8 analog output channels; a Discrete I/O card can have asmany as 16 discrete inputs, 16 discrete outputs, or 8 pulse count inputchannels. Do not mix input and output signals on the same card. Thesignals must be all input, or all output, or all pulse count input.
Table 2-1 shows the maximum number of input or output channelssupported by I/O cards. Knowing the number of channels you wish touse, up to the maximum, you can calculate the number and type of I/Ocards you need.
Table 2-1. Maximum Number of Channels Supported by I/O Cards
I/O Card Type MaximumNumber ofInputChannels
MaximumNumber ofOutputChannels
MaximumNumber ofPulse CountInput Channels
Type CL6721 Discrete I/O 16 (1) 16 8
Type CL6821 Analog I/O 16 8
Type CL6824 Analog Input 16
Type CL6825 Smart Input 16
Type CL6826 Smart Output 8
1. 16 input channels permits 32 input signals, two input signals per input barrier.
2.4 Physical and Electrical Pre-Installation
For detailed system planning information before installing the intrinsicsafety system, consult the documents listed in Table 2-2.
Table 2-2. System Planning DocumentsINM4000 MTL4000 Series Isolating IS interface units (vendors manual)
PN1:002 Planning the Installation
PN1:003 AC and DC Power and Ground Wiring
PN1:004 Signal Wiring and Data Highway Guidelines
PN1:006 Environmental Conditions for Instrumentation Systems
PN1:007 Lightning Protection Guidelines for Instrumentation Systems
PN4.4:CP7043 Installing Type CP7043 System Cabinets
2
9Installation Section 3
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Figure 3-Table 3
3 Installation
Before a system is installed, both physical planning and electricalplanning is required. This section provides information for both. Themanuals listed in Table 2-2 describe other pre-installation physical andelectrical planning.
3.1 Special Considerations
Appropriate precautions must be taken when using controlinstrumentation in areas where explosive gases or vapors are present.Precautions include special handling and special wiring.
Simply installing CL6340-Series termination panels and CL6350-Seriesbarriers does not necessarily provide a certifiable intrinsically safesystem. A certifiable system is a matter of design. To be certifiable, asystem must be designed and installed according to guidelines relevantto the country of installation and provided by the locally approvedcertifying authority.
Regulations governing intrinsic safety applications may preclude, ormake difficult, the mounting of CL6340-Series and CL6350-Seriesproducts in cabinets which contain other equipment, such as Control I/Otermination panels and MUX I/O files. Consult your certification authorityif combined mounting is essential.
Also see the vendors instruction manual, MTL4000 Series Isolating ISinterface units, INM4000, especially sections 3, 5, and 9 which describevarious precautions and warnings to heed prior to and during installation.
3.2 Planning the Physical Installation
The following subsections describe how to install the physical elementsof an intrinsically safe system.
3.2.1 I/O Cards and Card File
The I/O cards can be installed in any one of the 14 l/O card slots in theType CP6701 Control I/O Card File (Figure 3-1). An l/O card can beconfigured either as simplex, or for a redundant configuration, as the
33
Section 3 Installation 10
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
primary card or backup card. One backup can provide redundancy for amaximum of eight primary cards (1 for 8).
X00751APower Connection Card
Primary Power/Communication Card
Space for 14 I/O Cards
Secondary Power/Communication Card Backplane
Figure 3-1. Type CP6701 Card File Arrangement
The three left card slots of the l/O card file are reserved for the powerconnection card, the primary power/communication card, and thesecondary power/communication card. Refer to installation manual,Installing the Control I/O Subsystem, PN4.4:CP6701, for detailedinformation regarding the installation of an l/O card file.
See installation manual, Installing Type CP7043 SystemCabinets, PN4.4:CP7043, for termination panel locationguidelines in relation to the I/O card file, SR90 controller,door-mounted fans, and other PROVOX equipment.
Note ...
3.2.2 Termination Panel Installation
Termination panels mount on standard 19-inch EIA rails. The panelsrequire no operator access and should be mounted in cabinets orequipment rooms with access for maintenance personnel only. The TypeCP7043 System Cabinet is designed specifically to house theseproducts. For more information about the cabinet, refer to productbulletin, BU4.4:CP7043.
Figure 3-2 shows the dimensions of a CL6340-Series termination panelwith barriers installed.
3
11Installation Section 3
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
19.0(482.6)
INCH(mm)
7.0(177)
4.96(126)
Note: 1 Fits standard 19 rack.
1
BarrierTermination Panel
Figure 3-2. CL6340-Series Termination Panel Dimensions
3.2.3 Barrier Dimensions
Figure 3-3 shows the overall dimensions for CL6350-Series barriers.
0.64(16.2)
INCH(mm)
3.53(89.6)
4.11(104.5)
Hazardous AreaConnector Location
1.4(18)
Hazardous AreaConnector Top View
Figure 3-3. CL6350-Series Barrier Dimensions
3
Section 3 Installation 12
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
3.2.4 Termination Cables
Termination cables connect the I/O cards to CL6340-Series terminationpanels. The cables can be a maximum of 200 feet (60 m) long. Fordetails on available cables and approved lengths, and a table which listshelpful cable installation tools, refer to Appendix B of this manual.
Compliance with electromagnetic compatibility legislation maybe compromised through the use of cables other than thosesupplied with the product.
Note ...
You must make sure that cable ducting does not become too full. With amaximum of ten panels possible on one side of a Type CP7043 cabinet,and a maximum of four cables for each term panel, there can bepotentially 40 cables in the ducting; however, the number of cablesshould not exceed 30.
The number of cables in the ducting of the Type CP7043System Cabinet should not exceed 30. Also, for a TypeCL6741, Type CL6841, or Type CL6842 cable interface panel,at least one rack-unit of space between the top of the panel andthe next panel above it must be left open. Cables are routed outof the top of the interface panels and require the space to makea proper radius bend.
Note ...
3.2.4.1 Cabling for Simplex I/O Cards
The number of cables and connections you require depends on the typeof I/O card and the type of redundancy strategy you are using. Forexample, assume you have a termination panel that contains 16Type CL6355 IS Analog Output Isolating Barriers which you areconnecting to two Analog cards (with 8 channels each).
To implement this example in a simplex system, you need two cables:one to connect each analog I/O card to the termination panel. (Thecables for connecting the analog cards to the termination panel aresupplied with the termination panel).
3
13Installation Section 3
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Figure 3-4 shows the connections between the two analog output cardsand the termination panel in a simplex system.
I/O Card to Termination Panel Cables
I/O Card File
AnalogI/O Cards
CL6342 Termination Panel
Card #2Channels 1-8(Barriers 9-16)
Card #1Channels 1-8(Barriers 1-8)
Notes:
1
2
1 Wiring from field instruments connect toterminals located on the barriers. SeeAppendix A for details of these connections.
2 Power connections. See Section 3.3.1.
J1
J2
Figure 3-4. Cabling for Two Simplex Analog Output Cards
Figure 3-5 shows the cable connections for a single analog input card ina simplex system and for a smart termination panel with a smart inputcard. This combination of one card and one termination panel cancontain as many as 16 analog inputs.
3
Section 3 Installation 14
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
I/O Card to Termination Panel Cable
I/O Card File
AnalogI/O Card
CL6341 Termination Panel
Channels 1-16
Notes:1 Wiring from field instruments connect to
terminals located on the barriers. SeeAppendix A for details of these connections.
2 Power connections. See Section 3.3.1.
1
2
J1
Figure 3-5. Cabling for One Simplex Analog Input Cards and for aSmart Input Termination Panel with a Smart Input Card
Figure 3-6 shows the cable connections for two discrete Input cards in asimplex system. This combination of cards and termination panels cancontain as many as 32 discrete inputs. (The termination panel cancontain as many as 16 barriers which can accept two discrete inputseach.)
I/O Card to Termination Panel Cables
I/O Card File
DiscreteI/O Cards
CL6343 Termination Panel
Card #2Channels 1-16(Barriers 9-16)
Card #1Channels 1-16(Barriers 1-8)
Notes:1 Wiring from field instruments connect to
terminals located on the barriers. SeeAppendix A for details of these connections.
2 Power connections. See Section 3.3.1.
1
2
J2
J1
Figure 3-6. Cabling for Two Simplex Discrete Input Cards
3
15Installation Section 3
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Figure 3-7 shows the cable connections for discrete output cards in asimplex system. This combination of one card and one termination panelcan contain as many as 16 discrete outputs.
I/O Card to Termination Panel Cable
I/O Card File
DiscreteI/O Card
CL6343 Termination Panel
Channels 1-16
Notes:1 Wiring from field instruments connect to
terminals located on the barriers. SeeAppendix A for details of these connections.
2 Power connections. See Section 3.3.1.
1
2
J1
Figure 3-7. Cabling for Simplex Discrete Output Cards
Figure 3-8 shows the cable connections for discrete input cards used forPulse Count Input Signals in a simplex system.
I/O Card to Termination Panel Cables
I/O Card File
DiscreteI/O Cards
Card #2Channels 1-8Barriers 9-16
Card #1Channels 1-8Barriers 1-8
Notes:1 Wiring from field instruments connect to
terminals located on the barriers. SeeAppendix A for details of these connections.
2 Power connections. See Section 3.3.1.
1
2
CL6344 Termination Panel
J1
J2
Figure 3-8. Cabling for Simplex Pulse Count Inputs
3
Section 3 Installation 16
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
3.2.4.2 Cabling for 1 for 1 Redundant I/O Cards
When your system has 1 for 1 redundancy, every primary I/O card hasan associated backup I/O card. The following figures show examples ofeach type of I/O card and termination panel combination for 1 for 1redundancy. Although the following figures show the primary and backupI/O cards installed in the same card file, you can install them in separatefiles. The termination cables must not exceed 200 feet (60m).
Figure 3-9 shows cable connections for an analog input card with 16inputs in a 1 for 1 redundant system. This combination of cards andtermination panels can accept as many as 16 analog inputs.
I/O Card to Termination Panel Cables
I/O Card File
PrimaryAnalogI/O Card
CL6341 Termination Panel
Channels 1-16
Backup I/O Card
Notes:1 Wiring from field instruments connect to
terminals located on the barriers. SeeAppendix A for details of these connections.
2 Power connections. See Section 3.3.1.
1
2
J1
J2
Figure 3-9. Cabling for 1 for 1 Redundant Analog Input Cards andfor Smart Input Termination Panel with Smart InputCards
3
17Installation Section 3
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Figure 3-10 shows cable connections for two analog output cards with 8outputs each in a 1 for 1 redundant system. This combination of cardsand termination panels can contain as many as 16 analog outputs.
I/O Card to Termination Panel Cables
I/O Card File
CL6342 Termination Panel
BackupCard #1
PrimaryAIO Card #1
PrimaryAIO Card #2
BackupCard #2
Card #2Channels 1-8(Barriers 9-16)
Card #1Channels 1-8(Barriers 1-8)
Notes:1 Wiring from field instruments connect to
terminals located on the barriers. SeeAppendix A for details of these connections.
2 Power connections. See Section 3.3.1.
1
2
J1J2J3
J4
Figure 3-10. Cabling for 1 to 1 Redundant Analog Output Cards
3
Section 3 Installation 18
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Figure 3-11 shows cable connections for two discrete Input cards in a 1for 1 redundant system. This combination of cards and terminationpanels can accept as many as 32 discrete inputs. (The termination panelcan contain as many as 16 barriers which can accept two discrete inputseach.)
I/O Card File
CL6343 Termination Panel
I/O Card to Termination Panel Cables
BackupCard #1
PrimaryDIO Card #1
PrimaryDIO Card #2
BackupCard #2
Card #2Channels 1-16(Barriers 9-16)
Card #1Channels 1-16(Barriers 1-8)
Notes:1 Wiring from field instruments connect to
terminals located on the barriers. SeeAppendix A for details of these connections.
2 Power connections. See Section 3.3.1.
1
2
J1
J2J3
J4
Figure 3-11. Cabling for 1 to 1 Redundant Discrete Input Cards
3
19Installation Section 3
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Figure 3-12 shows cable connections for discrete output cards in a 1 for1 redundant system. This combination of cards and termination panelscan contain as many as 16 discrete outputs.
I/O Card to Termination Panel Cable
I/O Card File
PrimaryDiscreteI/O Card
CL6343 Termination Panel
Channels 1-16
Backup I/O Card
Notes:1 Wiring from field instruments connect to
terminals located on the barriers. SeeAppendix A for details of these connections.
2 Power connections. See Section 3.3.1.
1
2
J1
J3
Figure 3-12. Cabling for 1 to 1 Redundant Discrete Output Cards
3
Section 3 Installation 20
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Figure 3-13 shows cable connections for discrete input cards used forPulse Count Input Signals in a 1 for 1 Redundant system.
I/O Card File
CL6344 Termination Panel
I/O Card to Termination Panel Cables
BackupCard #1
PrimaryDIO Card #1
PrimaryDIO Card #2
BackupCard #2
Card #2Channels 1-8(Barriers 9-16)
Card #1Channels 1-8(Barriers 1-8)
Notes:1 Wiring from field instruments connect to
terminals located on the barriers. SeeAppendix A for details of these connections
2 Power connections. See Section 3.3.1.
1
2
J1J3J2J4
Figure 3-13. Cabling for 1 to 1 Redundant Pulse Count Inputs
3
21Installation Section 3
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
3.2.4.3 Cabling 1 for N Configurations
Cabling for 1 for N redundancy (where N = 2 to 8 primary I/O cards)requires a Cable Interface Panel. The panel allows 1 backup I/O card toprovide redundancy for two to eight primary I/O cards. The CableInterface Panel is not required 1 for 1 redundancy.
The cable length between the primary I/O card and the termination panelmust not exceed 200 feet (60m). Also, the overall length of the cablesconnecting the I/O card, the Cable Interface Panel, and the terminationpanel must not exceed 200 feet (60m).
All termination panels and cable interface panels have either two or threeterminals labeled SHLD. One SHLD terminal on each panel must beconnected to the cabinet ground.
Cabinet mounting rails are grounded so that a short groundingstrap attached to the rail and a mounting bolt or grounding studon the back plate will provide adequate grounding.
Note ...
The following examples show some multiple card and termination panelcombinations. Not every possible redundancy combination is shown. Usethese examples to help you determine the correct wiring for yourredundancy strategy and card application.
3
Section 3 Installation 22
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Figure 3-14 shows cable connections for an analog input card with 16analog inputs in a 1 for N redundant system. In this example, N is 4. Thatis, 1 card backs up 4 primary cards.
I/O Card File
PrimaryCard #1
CL6341 Termination Panel
Channels 1-16
BackupI/O Card
SHLD
Analog In Cable Interface Panel
Channels 1-16
Channels 1-16
Channels 1-16
PrimaryCard #2
PrimaryCard #3
PrimaryCard #4
Notes:1 Wiring from field instruments connect to
terminals located on the barriers. SeeAppendix A for details of these connections.
2 Power connections. See Section 3.3.1.
1
2
1
2
1
2
1
2
CL6341 Termination Panel
CL6341 Termination Panel
CL6341 Termination Panel
J1J2
J1J2
J1J2
J1J2
Figure 3-14. Cabling for 1 for 4 Redundant Analog Input Cards andSmart Input Termination Panel with Smart Input Card
3
23Installation Section 3
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Figure 3-15 shows cable connections for two analog output cards with 8outputs each in a 1 for 2 redundant system. This combination of cardsand termination panels can contain as many as 16 analog outputs.
I/O Card File
CL6342 Termination Panel
BackupI/O Card
PrimaryAIO Card #1
PrimaryAIO Card #2
SHLD
Analog OutCable Interface Panel
Card #2Channels 1-8(Barriers 9-16)
Card #1Channels 1-8(Barriers 1-8)
Notes:1 Wiring from field instruments connect to
terminals located on the barriers. SeeAppendix A for details of these connections
2 Power connections. See Section 3.3.1.
1
2
J1J2J3J4
Figure 3-15. Cabling for 1 for 2 Redundant Analog Output Cards
3
Section 3 Installation 24
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Figure 3-16 shows cable connections for two discrete Input cards in a 1for 2 redundant system. This combination of cards and terminationpanels can accept as many as 32 discrete inputs. (The termination panelcan contain as many as 16 barriers which can accept two discrete inputseach.)
I/O Card File
CL6343 Termination Panel
BackupI/O Card
PrimaryDIO Card #1
PrimaryDIO Card #2
SHLD
Discrete I/OCable Interface Panel
Card #2Channels 1-16(Barriers 9-16)
Card #1Channels 1-16(Barriers 1-8)
Notes:1 Wiring from field instruments connect to
terminals located on the barriers. SeeAppendix A for details of these connections.
2 Power connections. See Section 3.3.1.
1
2
J1J2J3J4
Figure 3-16. Cabling for 1 to 2 Redundant Discrete Input Cards
3
25Installation Section 3
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Figure 3-17 shows cable connections for discrete output cards in a 1 for3 redundant system. This combination of cards and termination panelscan contain as many as 16 discrete outputs.
I/O Card File
PrimaryDIO Card #1
CL6343 Termination Panel
Channels 1-16
BackupI/O Card
PrimaryDIO Card #2
PrimaryDIO Card #3
Channels 1-16
Channels 1-16
SHLD
Discrete I/OCable Interface Panel
Notes:1 Wiring from field instruments connect to
terminals located on the barriers. SeeAppendix A for details of these connection
2 Power connections. See Section 3.3.1.
1
2
1
2
1
2
J1J3
J1J3
CL6343 Termination Panel
CL6343 Termination Panel
J1J3
Figure 3-17. Cabling for 1 for 3 Redundant Discrete Output Cards
3
Section 3 Installation 26
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Figure 3-18 shows cable connections for discrete input cards used forPulse Count Input Signals in a 1 for 2 redundant system.
I/O Card File
CL6344 Termination Panel
PrimaryDIO Card #1
PrimaryDIO Card #2
BackupI/O Card
SHLD
Discrete I/OCable Interface Panel
Card #2Channels 1-8(Barriers 9-16)
Card #1Channels 1-8(Barriers 1-8)
Notes:1 Wiring from field instruments connect to
terminals located on the barriers. SeeAppendix A for details of these connections.
2 Power connections. See Section 3.3.1.
1
2
J1J3
J2J4
Figure 3-18. Cabling for 1 to 2 Redundant Pulse Count Inputs
3.2.5 Termination Cable Connectors
Termination cables longer than 20 feet (6m) are supplied with a spareD-shell connector. If the connector is too large to fit through a conduit orother limited access area, you can cut the cable and remove theconnector and then attach the spare connector after routing the cable.You should attach the spare connector to the end of the terminationcable according to the instructions provided with the connector. Refer toTable 3-1 for D-shell connector pin assignments (37-pin and 25-pin).
If you find it necessary to route the cable through a small area,cut the cable near the connector that you will attach to thetermination panel. An extra connector is provided with cables of50, 100, or 200 feet (15, 30, or 60m) for this purpose.
Note ...
3
27Installation Section 3
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Table 3-1. D-Shell Connector Pin Assignments
37-pin D-shell Connector 25-pin D-shell ConnectorPin Color Pin Color
1 Red 1 Red
2 White 2 White
3 Green 3 Green
4 Blue 4 Blue
5 Yellow 5 Yellow
6 Brown 6 Brown
7 Orange 7 Orange
8 White 8 White
9 Green 9 Green
10 Blue 10 Blue
11 Yellow 11 Yellow
12 Brown 12 Brown
13 Orange 13 Orange
14 White 14 through 20 Black
15 Blue 21 through 25 Red
15 Blue Shell Silver(Shield)
16 Yellow
17 Brown
18 Orange
19 Blue
Shell Silver(Shield)
20 through 26 Black
27 through 32 Red
33 through 36 Green
N/C Green
N/C White
37 No wire
3
Section 3 Installation 28
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
3.3 Planning the Electrical Installation
Each element in the installation has specific electrical requirements thatmust be considered. The following subsections provide planninginformation and electrical requirements for the elements.
The supplied wiring kit includes pre-terminated wires of the correctgauge and length to make the required connections when the panels aremounted in a Type CP7043 System Cabinet.
3.3.1 Termination Panel Power
Termination panels are supplied with nominal 24 Vdc power. Each panelis protected by a fuse. Screw terminals on the panels can accommodatetwo 14 AWG wires or a single 22 AWG wire.
Four screw terminals provide connections for primary and secondary +24Vdc and Power Supply Common.
The primary and secondary power terminals are labeled PRI +24 Vand SEC +24 Vdc, respectively.
Two redundant Power Supply Common terminals are labeled PSC.
Refer to Figure 2-1 to see the location of the power connector on thetermination panel. To connect power to the termination panels:
Step 1: Connect the positive wire from your 24Vdc supply to theterminal labeled PRI +24 V.
Step 2: If you have a secondary power supply, connect the positiveline to the terminal labeled SEC +24 Vdc.
If redundant power supplies are not used, place a jumperbetween the terminals labeled PRI +24V and SEC +24V.
Note ...
Step 3: Connect the screw terminal labeled PSC to the return, ornegative, line of the 24Vdc power supply.
Both simplex and redundant termination panels have two screws labeledSHLD that provide shield grounding for the termination cables. Use theshort black wire in the wiring kit to connect one of these terminals to thestud on the metal chassis. For more information about grounding, referto subsection 3.3.2.
3
29Installation Section 3
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
3.3.2 Shield Grounding
A ground bar kit containing grounding terminals is optional and availablewhere field cable shield grounding is required at the termination panel.For detailed information on grounding, refer to the followingdocumentation:
AC and DC Power and Ground Wiring, PN1:003
Signal Wiring and Highway System Guidelines, PN1:004
Installing Type CP7010 Cabinets, PN4.4:CP7010
Installing Type CP7043 Cabinets, PN4.4:CP7043
If your system uses shield grounding, ground shields at one endonly. The other ends must be carefully insulated to preventpossible sparks or possible current flow between differentpotential ground points.
Warning ...
3.3.3 DC Grounding
The Power Supply Common (PSC) circuitry must be grounded through alocal ground bus (LGB) or a master ground bus (MGB) to the designatedsystem earth ground. For specific DC grounding information, refer to thedocumentation listed in subsection 3.3.2.
3.3.4 Connecting Field Wiring to Barriers
Hazardous area field wiring is connected to the BLUE terminal blocksthat plug into the front of the barrier. Either connect the wires using thescrews on the terminal block (maximum gauge 12 AWG) or by using anoptional push-in and crimp type block. Figure 3-19 shows the barrier andterminal connections. For detailed information about barrier field wiringconnections, refer to the specifications for the individual barriers inAppendix A and the vendors instruction manual, MTL4000 SeriesIsolating IS interface units. INM4000.
3
Section 3 Installation 30
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Field Wiring Connections
1 2 3 4 5 6
Top View of plug-in terminal block
Side ViewThis end of the barrierconnects to the terminationpanel
Figure 3-19. Barrier and Terminal Connections
3
31Barrier Specifications Appendix A
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Figure A-Table A
Appendix AA Barrier Specifications
The vendors instruction manual, MTL4000 Series Isolating IS interfaceunits, INM4000, and this appendix contain specifications forCL6350-Series barriers. Table A-3 in this manual provides a crossreference between the PROVOX type number and the MTL modelnumber.
CL6340-Series termination panels provide the power and signalrequirements specified for the termination-panel side of the barriers.
General Specifications for CL6350-Series Intrinsic Safety BarriersLocation ofUnits
Long TermDrift
MaximumSafe-AreaVoltage
Hazardous-AreaConnectors
Safe Area
No recalibration necessary
UM = 250V rms or dc
Screw-clamp connectoraccommodates conductors of 14 AWG(2.5mm2) maximum. Crimp-contactheader accommodates wire crimps forconductors of 1420 AWG, or wirecrimps for conductors of 1824 AWG.
Electro-magneticCompatibility
Approvals
Humidity
AmbientTemperatureLimits
Mounting
Indicators
Weight
Complies with European StandardsEN61326-1 and EN50014:1977plus amds 1 and 2.
ATEX, CSA, and FM
5% to 95% RH
20C to +60C continuousworking40C to +80C storage
Barriers mount on CL6340-Seriestermination panels which can besurface or EIA-rail mounted
Green power indicator on eachbarrier
100 g approximately
A
Appendix A Barrier Specifications 32
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
A.1 Type CL6351 IS High-Level Analog Input IsolatingBarrier (HART compatible)
The Type CL6351 IS High-Level Analog Input Isolating Barrier provides afully floating dc supply for energizing a 2- or 3-wire, 4 to 20 mAconventional analog transmitter or smart transmitter located in ahazardous area, and repeats the current in another floating circuit todrive a safe-area load. Figure A-1 contains the connections for theCL6351 Barrier.
Safe Area
Hazardous Area
IS007M
7 8 9 10 11 12 13 14
1 2 3 4 5 6
2035VdcVs
Vs +
4/20mA
4/20mA
Load
HART Hand-heldCommunicator
4/20mA
I
I
Termination Panel
Barrier
Notes:1 The type of communicator must be such that it
does not send a signal out to the field that willinfringe on safety regulations.
1
Figure A-1. Typical Connections for Type CL6351
A
33Barrier Specifications Appendix A
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
For smart transmitters, the unit allows bi-directional transmission ofdigital communication signals superimposed on the 4 to 20 mA signal sothat the transmitter can be interrogated either from the operator stationor by a hand-held communicator (HHC). The barrier can also be usedwith hazardous-area current sources.
There are two versions of this barrier. The following table containsspecifications for both versions.
Type CL6351 Barrier Specifications (Standard and High Power)Number ofChannels
Location ofTransmitter
VoltageAvailable forTransmitter andLines
Input andOutput SignalRange
Digital SignalBandwidth
Safe-Area
Response Time
TransferAccuracy at20C
TemperatureDrift
LED Indicator
One
Zone 0, IIC, T4-T6 if suitablycertifiedDiv. 1, Group A, hazardouslocation
Standard: 15 V minimum at 20 mAHigh Power: 16.3 minimum at 20mANote: Maximum open-circuitvoltage is 28 V
4 to 20 mA
10 Hz to 8 kHz
Circuit Load Resistance:Conventional transmitters: 0 to650 . Smart transmitters: 250 10%Circuit Output Resistance:>1 MCircuit Ripple:
Appendix A Barrier Specifications 34
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
A.2 Type CL6352 IS Millivolt Input, Type CL6353 IS RTDInput, and Type CL6354 IS Thermocouple Input
Isolating Barriers
The Type CL6352, Type CL6353, and Type CL6354 IS barriers convert alow-level dc signal from a temperature sensor mounted in a hazardousarea into a 4 to 20 mA current for driving a safe-area load.
These barriers are based on a barrier which is available in severalstandard thermocouple and RTD temperature ranges. Thesetemperature ranges can be customer modified with a pocket dataterminal available from Measurement Instruments Limited (MTL).Figure A-2 shows the connections for the Type CL6352, Type CL6353,and Type CL6354.
7 8 9 10 11 12 13 14
1 2 3 4 5 6
2035VdcVs
Vs +
Socket forConfiguration
Load
mV
I
4/20mA
Safe Area
Hazardous Area
2-Wire
3-Wire
4-Wire
Termination Panel
Barrier
Figure A-2. Typical Connections for Type CL6352, Type CL6353,and Type CL6354
The following table specifies the resistance temperature detector rangeswhich can be used with the barriers.
A
35Barrier Specifications Appendix A
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Table A-1. Type CL6353 Range Specifications
Temp C Range Ohms Span Ohms Accuracy % ofSpan @20C
Drift % of Spanper C
168 to 60 32.165 to 123.239 91.074 0.157% 0.011%
100 to 100 60.254 to 138.5 78.246 0.171% 0.013%
73 to 315 71.134 to 217.345 146.211 0.123% 0.009%
0 to 200 100 to 175.839 75.839 0.174% 0.013%
0 to 600 100 to 313.593 213.593 0.106% 0.007%
38 to 260 114.767 to 197.686 82.919 0.165% 0.012%Note: RTD is 100 Ohm Platinum, =0.00385.
The following table specifies the thermocouple ranges which can beused with the barriers.
Table A-2. Type CL6354 Range Specifications
TC Type Temp C Milli-Volts Spanmilli-Volts
Accuracy% of Span@20C
Drift % ofSpan perC
J-Type 100 to 760 4.632 to 42.922 47.554 0.100% 0.006
J-Type 51 to 338 2.478 to 18.426 20.904 0.141% 0.006
K-Type 100 to 1350 3.553 to 54.125 57.678 0.095% 0.007
K-Type 18 to 538 0.701 to 22.26 22.961 0.134% 0.007
R-Type 0 to 1750 0 to 20.878 20.878 0.141% 0.007
T-Type 184 to 315 5.333 to 15.151 20.484 0.142% 0.006
E-Type 73 to 871 8.391 to 66.551 74.942 0.089% 0.006
B-Type 0 to 1800 0 to 13.585 13.585 0.179% 0.007
S-Type 0 to 1750 0 to 18.504 18.504 0.150% 0.007
K-Type 0 to 250 0 to 10.151 10.151 0.217% 0.007
Note: Cold junction compensation is provided in the hazardous area connector supplied with Type CL6353 Barriers.
A
Appendix A Barrier Specifications 36
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
The following table contains specifications for these barriers.
Type CL6352, CL6353, and CL6354 Barrier SpecificationsNumber ofChannels
Signal Sourceand Range
Location ofSignal Source
RTD ExcitationCurrent
Cold Junction
Rejection
CalibrationAccuracy(at 20C)
TemperatureDrift (typical)
Example ofCalibrationAccuracy &TemperatureDrift for anRTD
One
Millivolt (Type CL6352): 10 to 70mVRTD: See table, Type CL6353Range SpecificationsThermocouple: See table, TypeCL6354 Range Specifications
Zone 0, IIC, T4 hazardous area Div. 1, Group A, hazardous location
200 A nominal
Compensation: AutomaticCompensation Error: 1.0C
Common Mode: 120 dB for 240 Vat50 Hz or 60 HzSeries Mode: 40dB for 50Hz or 60Hz
Includes hysteresis, nonlinearityand repeatabilitymV/TC: 15V or 0.05% of inputvalue(whichever is greater)RTD: 80mOutput: 11A
mV/THC: 0.003% of inputvalue/CRTD: 7m/COutput: 0.6A/C
Span: 0 to 250Accuracy: (0.08/250 +11/16000) 100%= 0.1% of spanTemp.Drift:(0.007/25016000 + 0.6) A/C = 1A/C
Upscale, Downscale, or Off
A pocket data terminal fitted with abarrier interface.
4 to 20 mA nominal (direct orreverse)
600
Green: One provided for powerand status indication
57 mA at 24V55 mA at 20 V60 mA at 35 Vdc with 20 mAsignal
1.2 W at 24 V with 20 mA signal2 W at 35 V
250 Vac between safe andhazardous-area circuits
Terminals 5 and 6 (Con 1):Non-energy storing apparatus1.2 V, 0.1 A, 20 J,25 mW. Can be connectedwithout further certification intoany IS loop with open-circuitvoltage not more that 10 V.Terminals 1 and 2 (Con 1): 7.2 V,950 , 8 mA.Configuration socket (Con 2):Umax: in = 11.2 VImax: in = 12 mAWmax: in = 280 mWUmax: out = 7.2 VImax: out = 8 mAWmax: out = 15 mW
Safety Driveon SensorBurnout
Configurator
Output Range
MaximumLoadResistance
LED Indicator
PowerRequirements(Vs)
PowerDissipationWithin Unit
Isolation
SafetyDescription
A
37Barrier Specifications Appendix A
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
A.3 Type CL6355 IS Analog Output Isolating Barrier
There are two types of Analog Output Isolating Barriers:
Conventional Analog Output
Smart Device Output
Use the conventional analog output barrier for applications which do nothave smart device capability. Use the smart device output barrier forapplications with smart digital valve controllers and digital transducers.
A.3.1 Conventional Analog Output Application
In an analog application, the Type CL6355 IS Analog Output IsolatingBarrier accepts a 4 to 20 mA signal from a safe-area controller to drive acurrent/pressure (I/P) converter or any other load up to 800 in ahazardous area. The output capability is 16 V at 20 mA, and the dropaccess across the input terminals is low (4 V). The input and outputcircuits float independently.
IS009M
7 8 9 10 11 12 13 14
1 2 3 4 5 6
2035VdcVs
Vs +
4/20mA
I/P
Safe Area
Hazardous Area
I
I
Termination Panel
Barrier
Figure A-3. Typical Connections for Type CL6355
A
Appendix A Barrier Specifications 38
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Process controllers with a read-back facility can detect open or shortcircuits in the field wiring. If such faults occur, the resistance across theinput terminals changes to a preset high value to simulate an open circuitin the safe-area wiring. Figure A-3 shows the connections for the TypeCL6355 barrier.
The following table contains specifications for the barrier.
Type CL6355 Barrier Specifications (Analog Application)Number ofChannels
Location of I/PConverter
DriveCapability
MaximumLoad DrivingCapability
MinimumLoadResistance
OutputResistance
Input/Output
TransferAccuracy at20 C
InputResistance
One
Zone 0, IIC, T4T6 hazardous areaif suitably certifiedDiv. 1, Group A, hazardous location
4 to 20 mA
16 V (800 at 20 mA)
90 (Short circuit detection at 1 M
Signal Range: 1.0 to 21.4 mACircuit Ripple: 47 k with the field wiring opencircuit< 0.75 mA with the field wiring shortcircuit
Settle within 200 A of final valuewithin 100 ms
< 1.0 A/C
Green: One provided for powerindication
50 mA at 24 Vdc with 20 mA signal55 mA at 20 Vdc40 mA at 35 Vdc
1.0 W maximum at 24 V with 20 mAsignal1.2 W at 35 V
250 Vac between safe andhazardous-area circuitsWith Line-Fault Detection: Inputcircuit is floating, clamped to lessthan 10 V above supply vepermitting the use of a 250 currentsense resistor in the return path
28 V, 300 , 93 mA,Um = 250 V rms or dc
Voc = 28 VdcIsc = 93 mACa = 0.12 FLa = 4.2 mH
ResponseTime
TemperatureDrift
LED Indicator
PowerRequirements(Vs)
PowerDissipationWithin Unit
Isolation
SafetyDescription
FM EntityParameters
A
39Barrier Specifications Appendix A
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
A.3.2 Smart Device Output Application
In a smart device application, the Type CL6355 IS Analog OutputIsolating Barrier accepts a 4 to 20 mA floating signal from a safe-areacontroller to drive a current/pressure (I/P) converter or any other floatingload up to 870 in a hazardous area. For HART compatible valvepositioners, the barrier also permits bi-directional transmission of digitalcommunication signals so that the smart device can be interrogatedeither from the controller or by a hand-held communicator (HHC).
Process controllers with a read-back facility can detect open or shortcircuits in the field wiring. If this occurs, the current taken into theterminals drops to a preset low value.
7 8 9 10 11 12 13 14
1 2 3 4 5 6
20-35VdcVs
Vs +
4/20mA
I/P
Safe Area
Hazardous Area
I
I
Figure A-4. Typical Connections for Type CL6355 (Smart Application)
HHC
Notes:1 The type of communicator must be such that it
does not send a signal out to the field that willinfringe on safety regulations.
1
A
Appendix A Barrier Specifications 40
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
The following table contains specifications for the barrier.
Type CL6355 Barrier Specifications (Smart Device Application)Number ofChannels
Location of I/PConverter
DriveCapability
Digital SignalBandwidth
MaximumLoadResistance
OutputResistance
Input/Output
TransferAccuracy at20 C
InputCharacteristic
One
Zone 0, IIC, T4T6 hazardousarea if suitably certifiedDiv. 1, Group A, hazardouslocation
4 to 20 mA
500 Hz to 10k Hz
870 (17.4 V at 20 mA)
> 1 M
Signal Range: 1.0 to 26.0 mACircuit Ripple:
41Barrier Specifications Appendix A
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
A.4 Type CL6356 IS Discrete Input Isolating Barrier (Withand Without Debounce)
The Type CL6356 IS Discrete Input Isolating Barrier is a two-channel unitenabling safe-area loads to be controlled by switches or proximitydetectors located in hazardous areas through logic compatiblesolid-state outputs. Only the Without-Debounce version of this barriershould be used with positive displacement (PD) flowmeters or turbinemeters.
Optional earth fault detection is available using an earth leakagedetector. Power and switch status is indicated by LEDs located on thefront of the barrier. Figure A-5 shows the connections for the TypeCL6356 barrier.
IS002B
7 8 9 10 11 12 13 14
1 2 3 4 5 6
2035Vdc
To MTL4220/MTL2220Earth Leakage Detector(Optional)
1 2
Vs
Vs +
Safe Area
Hazardous Area
Figure A-5. Typical Connection for Type CL6356
A
Appendix A Barrier Specifications 42
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
There are two types of this barrier: With and Without Debounce. Thefollowing table contains specifications for both barriers.
Type CL6356 Barrier Specifications (With and Without Debounce)Number ofChannels
Location ofSwitches
Location ofProximityDetector
Voltage Appliedto Sensor
Input/OutputCharacteristics
No-fail EarthFault Protection
Two
Zone 0, IIC, T6 hazardous areaDiv. 1, Group A, hazardouslocation
Zone 0, IIC, T4-T6 if suitablycertifiedDiv.1, Group A, hazardouslocation
7.0 V - 9.0 Vdc from 1 k
Output on if > 2.1 mA* (< 2 k) insensor circuitOutput off if < 1.2 mA* (> 10 k) insensor circuitHysteresis: 200 A (650 )normal. *NAMUR and DIN 19234standards for proximity detectorsTime Constant: 1.0 msec typical
Enabled by connecting terminals3 and 6 to an earth leakagedetector.Fault on Either Line Detected:unit continues workingNote: If maintaining isolationbetween the two channels isrequired, two separate earthleakage detectors are required.
Operating Frequency:Without Debounce: dc to 5 kHzWith Debounce: time constant of1.0 msec, typicalMaximum Off-State Voltage:35 VMaximum Off-State LeakageCurrent: 10 AMaximum Off-State VoltageDrop:1 + (0.1 current in mA) VMaximum On-State Current:50 mANote: Each output is Zener-diodeprotected against inductive loads.
Amber: One provided for eachchannel, lighted when outputcircuit is closedGreen: One provided for powerindication
45 mA at 20 Vdc47.5 mA at 24 Vdc50 mA at 35 Vdc
1.15 W at 24 V1.75 W at 35 V
250 Vac between safe andhazardous-area circuits
10.5 V, 800 , 14 mA
Voc = 10.5 VdcIsc = 14 mACa = 2.4 FLa = 165 mH
OutputCharacteristics
LED Indicators
PowerRequirement(Vs)
PowerDissipationWithin Unit
Isolation
SafetyDescription forEach Channel
FM EntityParameters
NOTE: All values are applicable to both With and Without Debounce unless otherwise indicated.
A
43Barrier Specifications Appendix A
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
A.5 Type CL6357 IS Discrete Output Isolating Barrier
There are two types of Discrete Output Isolating Barriers:
Solid State
Relay Output
Use the solid-state barrier for low-power discrete output applications.Use the relay output barrier for applications that need relay contacts foran ON/OFF switch.
A.5.1 Solid State
The Type CL6357 IS Discrete Output Isolating Barrier (Solid-State)enables an ON/OFF device in a hazardous area to be controlled by avolt-free contact or logic signal in a safe area. It can drive loads such assolenoids, alarms, LEDs, and other low power devices that are certifiedas intrinsically safe or are classified as non-energy storing simpledevices. Figure A-6 shows the connections for the Type CL6357 SolidState barrier.
7 8 9 10 11 12 13 14
1 2 3 4 5 6
2035VdcVs
Vs +
Solenoid, Alarm, orOther IS Device
IS003M
Safe Area
Hazardous Area
Termination Panel
Barrier
Figure A-6. Typical Connections for Type CL6357 (Solid State)
A
Appendix A Barrier Specifications 44
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
By connecting a second safe-area switch or logic signal, the output canbe disabled, which, for example, can enable a safety system to overridea control signal.
The following table contains specifications for the solid-state barrier.
Type CL6357 Barrier Specifications (Solid-State)Number ofChannels
Location ofLoad
MinimumOutput Voltage
MaximumOutput Voltage
Output Ripple
Control Input
Override Input
One
Zone 0, IIC, T4-T6 hazardous areaif suitably certified Div. 1, Group A,hazardous location
Depends on the current; Rangesfrom 20 V at 1 mA to 10 V at 50 mAoutput current
25.5 V from 232
< 0.5% of maximum output,peak-to-peak
Suitable for switch contacts, anopen collector transistor or logicdrive.The output turns on if < 1.4 Vis applied across terminals 10 and11 and turns off if > 4.5 V is appliedacross these terminals.
An open collector transistor or aswitch connected across terminals8 and 9 can be used to turn theoutput off whatever the state of thecontrol input.
Output within 10% of the finalvalue after 100 ms
Amber: One provided for status,ON when output circuit is activeGreen: One provided for powerindication
120 mA at 20 Vdc100 mA at 24 Vdc75 mA at 35 Vdc
1.3 W with typical solenoidvalue, output on1.9 W worst case
250 Vac between safe andhazardous-area circuits
25.5 V, 232 , 110 mA
Voc = 25.5 VdcIsc = 110 mACa = 0.17 FLa = 3 mH
ResponseTime
LED Indicators
PowerRequirement(Vs)
PowerDissipationWithin Unit
Isolation
SafetyDescription
FM EntityParameters
A
45Barrier Specifications Appendix A
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
A.5.2 Relay Output
The Type CL6357 IS Discrete Output Isolating Barrier (Relay Output)enables either one or two separate IS circuits in a hazardous area to berelay-contact controlled by a single ON/OFF switch or logic signal in asafe area.
Applications include: the calibration of strain-gauge bridges, changingthe polarity (and thereby the tone) of a Linden IS Sounder, the testing ofIS fire alarms, and the transfer of safe-area signals into an annunciatorwith IS input terminals that are not segregated from each other.
The output-relay contacts are certified as a non-energy storing deviceand can be connected to any IS-circuit without further certification,provided that separate IS circuits are such that they would still remainsafe if connected together. Figure A-7 shows the connections for theType CL6357 Relay Output barrier.
IS008B
7 8 9 10 11 12 13 14
1 2 3 4 5 6
Vs
Vs +
Safe Area
Hazardous Area
ISRelay
A B
20-35Vdc
Non-ISSwitch
Figure A-7. Typical Connections for Type CL6357
ISRelay
A
Appendix A Barrier Specifications 46
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
The following table contains specifications for the relay output barrier.
Type CL6357 Barrier Specifications (Relay Output)Number ofChannels
Location ofControl Circuit
Input/OutputCharacteristics
Power SupplyFailure Protec-tion
Response Time
Contacts (suit-able for connec-tion to IS cir-cuits)
Contact
One, fully floating
Safe area
Relay Energized if:< 27 k or < 1 V appliedRelay De-energized if:> 54 k or > 2 V applied(50 V maximum)Hysteresis, Nominal: 15 k or0.5 V
Relay de-energized if supply fails
25 ms, nominal
2-pole changeover
Rating: 100 Vdc (limited to 30 Vdcfor I.S. applications), 250 mA 5 VA(reactive loads must besuppressed)< 150 m contact resistanceLife Expectancy: 2 105operations at maximum load
Amber: One provided for relaystatus, ON when relay energizedGreen: One provided for powerindication
20 mA at 20 Vdc25 mA at 24 Vdc40 mA at 35 Vdc
0.6 W maximum at 24 Vdc1.4 W maximum at 35 Vdc
Non-energy Storing Apparatus:relay contacts may be connectedto any certified IS circuit withoutfurther certificationNote: The 2-pole changeovercontacts may be connected to anycertified IS circuit only if theseremain intrinsically safe wheninterconnected, since the two setsof relay contacts are notsegregated from each other.
LED Indicators
Power Re-quirements(Vs)
Power Dissipa-tion WithinUnit
Safety Descrip-tion (eachchannel)
A
47Barrier Specifications Appendix A
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
A.6 Type CL6358 IS Pulse Count Input Isolating Barrier
The Type CL6358 IS Pulse Count Input Isolating Barrier isolates pulsesfrom a switch, proximity detector, current pulse transmitter or voltagepulse transmitter located in a hazardous area. This barrier is ideal forapplications involving high pulse rates and fast response times.Figure A-8 shows the connections for the TYpe CL6358 Barrier.
4/20mA
IS002M
7 8 9 10 11 12 13 14
1 2 3 4 5 6
2035VdcVs
Vs +
Safe Area
Hazardous Area
ProximityDetector
Switch
3-wireCurrentPulse
3-wireVoltagePulse
2-wireCurrentPulse
V
ExternallySourcedCurrentPulse
Externally SourcedVoltage Pulse
4/20mA
Termination Panel
Barrier
Figure A-8. Typical Connections for Type CL6358
A
Appendix A Barrier Specifications 48
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
The following table contains specifications for the barrier.
Type CL6358 Barrier SpecificationsNumber ofChannels
Sensor Type
Location ofSwitch
Location ofProximityDetector orTransmitter
Input
One, fully floating
Switch or proximity detector (NAMUR/DIN19234)2- or 3-wire voltage or pulse transmitter
Zone 0, IIC, T6 hazardous areaDiv. 1, Group A, hazardous location
Zone 0, IIC, T4-T6 if suitably certifiedDiv. 1, Group A, hazardous location
Switch Input:Output ON if switch is closedOutput OFF is switch is openProximity Detector Input: Excitation: 7.0to 9.0 Vdc from 1 k nominalOutput ON if input > 2.1 mA* (< 2 k)Output OFF if input < 1.2 mA* (> 10 k)* NAMUR and DIN19234 standards forproximity detectorsSwitching hysteresis: 0.2 mA (650 )nominalCurrent Pulse Input:Transmitter supply: 16.5 Vdc at 20 mAShort circuit current: 24 mAOutput ON if input > 9.0 mAOutput OFF if input < 7.0 mASwitching hysteresis: 0.5 mAVoltage Pulse Input:Input impedance: > 10 kSwitching point voltage (Vsp):3, 6, or 12 V (selectable by switch on top of unit)Output ON if input > VspOutput OFF if input < VspSwitching hysteresis:100 mV + (0.1 Vsp) typical
High: 10 s minLow: 10 s min
0-50 kHz
Maximum off-state voltage: 35 VMaximum off-state leakage current:10 AMaximum on-state voltage drop:1 + (0.1 current in mA) VMaximum on-state current: 50 mAOutput OFF is supply failsNote: The output is Zener-diodeprotected against inductive loads
Amber: One provided for for input, ONwhen output circuit is ONGreen: One provided for power indication
65 Ma at 24 V dc70 mA at 20 Vdc55 mA at 35 Vdc
1.35 W maximum at 24 V1.75 W maximum at 35 V
250 Vac between safe and hazardousarea circuits
Terminals 2 to 1: 10.5 V, 800 , 14 mATerminals 4 to 3 and 1:28 V, 300 , 93 mATerminals 3 to 1: Non-energy storingapparatus 1.2 V, 0.1 A, 20 J, and 25 mW; can be connected withoutfurther certification into any IS loop withopen-circuit voltage not more than 28 VTerminals 5 to 4 and 1:Vmax 28 V, Imax 94 mAPmax 0.66 W
Pulse Width
FrequencyRange
OutputCharacteristics
LED Indicators
PowerRequirements
PowerDissipationWithin Unit
Isolation
SafetyDescription
A
49Barrier Specifications Appendix A
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
A.7 Cross-Reference Between CL6350-Series TypeNumbers and MTL Model Numbers
Table A-3 cross references the type numbers of CL6350-Series IntrinsicSafety Barriers and the MTL model numbers.
Table A-3. Cross-Reference Between CL6350-Series Type Numbersand MTL Model Numbers
TypeNumber
MTL ModelNumber Functional Description
CL6351 MTL4041B IS High-Level Analog Input Isolating Barrier(standard power version) [4 to 20 mA]
MTL4041P IS High-Level Analog Input Isolating Barrier (highpower version) [4 to 20 mA]
CL6352 MTL4073 IS Millivolt Input Isolating Barrier
CL6353 IS RTD Input Isolating Barrier (Six temperatureranges see the specification table
CL6354 IS Thermocouple Input Isolating Barrier (Ninetemperature ranges see the specification table)
CL6355 MTL4045B IS Analog Output Isolating Barrier [4 to 20 mA]
MTL4046P IS Smart Device Output Isolating Barrier[4 to 20 mA]
CL6356 MTL4013 IS Discrete Input Isolating Barrier (With Debounce)
MTL4013F IS Discrete Input Isolating Barrier (WithoutDebounce)
CL6357 MTL4021 IS Discrete (Solid State) Output Isolating Barrier
MTL4215 IS Discrete (Relay) Output Isolating Barrier
CL6358 MTL4032 IS Pulse Count Input Isolating Barrier
A
Appendix A Barrier Specifications 50
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Blank page.
A
51Panel and Cable Specifications Appendix B
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Figure B-Table B
Appendix BB Panel and Cable Specifications
This appendix contains the specifications for CL6340-series terminationpanels and for the cables used with the panels. Also included is a list oftools available from MTL which may be of help in cable installation.
B.1 Termination Panel Specifications
The following table lists specifications for the CL6340-Series TerminationPanels:
Primary and secondary +24Vdc powersupplied from the system cabinet powerbus bar. Connections provided byfront-accessible screw-clamp connectors
Termination panels include a horizontalbracket which mounts to standard 19 inch(483 mm) EIA rails, and occupy fourrack-units
Fisher-Rosemount Systems EngineeringStandard 137 (ES137) Category B,normal operating conditions temperaturerange extends to 122F (50C)
ISA S71.04-1985, severity level G2(Environmental Conditions for ProcessMeasurement and Control Systems:Airborne Contaminants)
Refer to section 3 for compatibilityinformation and different configurations ofchannels, termination panels, andPROVOX equipment.
Two green LEDs indicate the status of the+24 Vdc power. One LED is labeled PRIfor primary power and the other is labeledSEC for secondary power. LEDs are ONwhen 24 Vdc is applied and the fuse isgood.
Refer to Nonhazardous AreaClassification Bulletin BU4.7:001
Specifications for CL6340-Series Termination PanelsPower
Mounting
EnvironmentalConditions
ChannelOptions
Indicators
ElectricalClassification
Operating Conditions
ConditionsReferenceLimits (1)
NormalLimits (1)
OperativeLimits (1)
Transport &StorageLimits (1)
AmbientTempera-ture
MaximumTempera-tureVariation
AmbientRelativeHumidity(withoutcondensa-tion)
73 & 81F(23 & 27C)
3.5F/h(2C/h)
35 & 45%
41 & 122F(5 & 50C)
36F/h20C/h
10 & 90%
32 & 131F(0 & 55C)
9F/min5C/min
5 & 95%
40 & 158F(40 & 70C)
18F/min10C/min
5 & 95%
1. These terms are defined in ISA Standard ISA-S5114-1979.
Electro-magneticCompatibility
Dimensionsand Weight
Cabling
Complies with European StandardsEN61326-1 and EN50014:1977 Amds 1and 2
Termination Panel: 7 inches (178 mm)by 19 inches (483 mm). Approximately5.3 pounds (2.4 kg) without modules
The maximum length of the cablesbetween I/O cards and the terminationpanel is 200 feet (61 m).
B
Appendix B Panel and Cable Specifications 52
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
B.2 Termination Panel Current Requirements
Table B-1 lists termination panel electrical current requirements at24 Vdc.
Table B-1. Current Requirements for Termination Panels
Termination Panel Current at 24Vdc withoutbarriers
Type CL6341 Analog Input 50mA
Type CL6342 Analog Output 50mA
Type CL6343 Discrete Input/Output 150mA
Type CL6344 Pulse Count Input 50mA
Type CL6345 Smart Device Input 150mA
Note: Each barrier installed on a termination panel also requires power. Refer to the appropriatespecifications in Appendix A for the power consumption of the barriers. Then add the powerrequired for each barrier that will be mounted on the termination panel to get the total powerrequired.
B.3 Cable Lengths
The following cable lengths are supplied by the factory and used for theconnecting termination panels to I/O cards. Make note that redundanttermination panels can require as many as four cables, depending uponthe type of termination panel you install. See subsection 3.2.4 for severalcombinations of redundancy.
10 feet
20 feet
50 feet
100 feet of cable with molded connector ends and an extraunattached connector
200 feet of cable with molded connector ends and anextra,unattached cable connector (for custom cutting to length)
Length specified by Fisher-Rosemount Systems during PROVOXsystem staging
You are REQUIRED to locate safe area cabling (For example,power termination panel cables) and hazardous area cabling(field wiring) in SEPARATE cable trays. The trays for hazardouscables are colored BLUE.
Warning ...
B
53Panel and Cable Specifications Appendix B
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
B.4 Field Wiring Specifications
Table B-2 lists field wire specifications required to comply with FMcertification for Types CL6352, CL6353, and CL6354 barriers.
Table B-2. Maximum Cable Parameters (FM) Low-Level Signal
Barrier Group Con 1 (1)Terms 1 & 2
Con 1 (1)Terms 5 & 6
Con 2 (1)
F mH F mH F mH
Type CL6352T CL6353
A+B 11.0 500 1000 3.6 0.6 47ypType CL6353Type CL6354
C 33.0 1500 1000 10.8 1.8 141Type CL6354
D 88.0 4000 1000 27.8 4.8 376
1. See the Safety Description specifications in the Type CL6352, CL6353, and CL6354 BarrierSpecifications table for descriptions of Con 1 and Con 2.
Table B-3 lists field wire specifications required to comply with FMcertification for Types CL6351, CL6355, CL6356, CL6257, and CL6358barriers.
Table B-3. Maximum Cable Parameters (FM) Other Signal
Barrier Group F mH
Type CL6351 (Standard Poweri )
A+B 0.13 4.2yp (version) C 0.39 12.6
D 1.04 33.6
Type CL6351(Hi h P i )
Terminals 2, 3, 4, 5, and 6yp(High Power version) A+B 0.4 1.41
C 0.43 5.75
D 1.14 10.8
Type CL6355 (Conventionall li ti )
A+B 0.13 4.2yp (analog application) C 0.39 12.6
D 1.04 33.6
Type CL6355(S t d i li ti )
A+B N/A N/Ayp(Smart device application) C N/A N/A
D N/A N/A
Type CL6356 (With and WithoutD b )
A+B 2.4 165yp (Debounce) C 7.2 495
D 19.2 1320
Type CL6357 (Solid StateO t t)
A+B 0.17 3yp (Output) C 0.51 9
D 1.36 24
B
Appendix B Panel and Cable Specifications 54
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Table B-3. Maximum Cable Parameters (FM) Other Signal(Continued)
Barrier mHFGroup
Type CL6357 (Relay Output) Cable parameters are defined by the circuit beingswitched.
Type CL6358 Terminal 2 to 1yp
A+B 2.4 165
C 7.2 495
D 19.2 1320
Terminal 4 to 3 to 1
A+B 0.13 4.2
C 0.39 12.6
D 1.04 33.6
Table B-4 lists field wire specifications required to comply with EECS(ATEX 100) certification for Types CL6351 through CL6358 barriers.
Table B-4. Maximum Cable Parameters EECS (ATEX 100)
Barrier Group F mH H/Type CL6351 StandardPower Version (MTL4041B)
Connector CON1, pins 2/3 wrt 4/5Power Version (MTL4041B)
IIC 0.083 3.05 (4.20) 56
IIB 0.650 9.15 (12.6) 210
IIA 2.150 24.4 (33.6) 444
Connector CON1, pins 6 wrt 4/5
IIC 100 13.06 2436
IIB 1000 49.77 8931
IIA 1000 105.05 18140
Connector CON1 Pins 2/3 wrt 6
lIC 0.083 3.05 (4.20) 60
IIB 0.650 9.15 (12.6) 222
IIA 2.150 24.4 (33.6) 469
1. N/A Not Applicable
B
55Panel and Cable Specifications Appendix B
Installing Intrinsic Safety Termination Panels and Barriers (Revision D July 2003)
Table B-4. Maximum Cable Parameters EECS (ATEX 100)(Continued)
Barrier H/mHFGroupType CL6351 High PowerVersion (MTL4041P)
Connector CO 1, pins 2/3 wrt 4/5Version (MTL4041P)
IIC 0.083 1.82 (2.5
Top Related