Hitachi Air ConditioningEngineered for tomorrow.
KPI Active + DX Coil KPI-X3EHitachi’s heat recovery ventilation system adjusts the temperature and humidity of incoming fresh air to match the indoor environment.
3 models available: 500 m3 - Cooling capacity 5.3kW (1.5HP)
800 m3 - Cooling capacity 8.0kW (2HP)
1000 m3 - Cooling capacity 10.8kW (2.5HP)
Features and Benefits
Capacities from 5.3kW to 12.9kW
Linear flow between intake and air extraction ducts
Reduced noise level: 26 dB (A) on KPI 502X3E
Compatible with System Free indoor units, H-LINK II and CS Net Web
R410A DX Coil allows connection to Utopia IVX split systems and Set Free VRF systems.
www.hitachiaircon.com | www.hitachiheating.com
KPI Active + DX CoilKPI 502 ~ 1002X3E
Air Flow Rate ( m³/h) 500 ~ 1000Capacity HP 1.5 ~ 2.5Nominal Cooling Capacity (Utopia System)(1) 7.4 ~ 9.7Nominal Heating Capacity (Utopia System)(1) 9.1 ~ 11.4Nominal Cooling Capacity (Set Free System)(1) 5.3 ~ 10.8 Nominal Heating Capacity (Set Free System)(1) 6.9 ~ 12.9Total Enthalpy Heat exchange
Free Cooling
EC Fans - EuP Lot 11 2nd Tier Compliant
Hi Efficiency Filter (F7 based on EN779) OptionAutomatic Ventilation via CO2 Sensor input
Operating Range -20°C ~ 46°CRemote Controller Type (not included) Infra Red or Wired
Remote Controller Type Infra Red or Wired(1) The nominal cooling and heating capacity is the combined capacity of outdoor
and indoor unit of the system and is based on Standard EN14511.
Optional Remote Controllers PC-ART Standard wired remote controller (inc. 7-day time clock)
PC-ARF Advanced wired LED controller (inc. 7-day time clock)
PC-ARF
PC-ART
Compatible with Hitachi’s full range of commercial outdoor units.
KPI Active
Active Energy RecoveryKPI 502X3E KPI 802X3E KPI 1002X3E
HP 1.5 2.0 2.5Nominal Cooling Capacity (Utopia System)(1) kW - 7.4 (2.9) 9.7 (3.7)
Nominal Heating Capacity (Utopia System)(1) kW - 9.1 (3.5) 11.4 (4.4)
Nominal Cooling Capacity (Set Free System)(1) kW 5.3 (1.8) 8.0 (2.9) 10.8 (3.7)
Nominal Heating Capacity (Set Free System)(1) kW 6.9 (2.1) 9.8 (3.5) 12.9 (4.4)
Air Flow Rate (H/M/L) m³/h 500 / 430 / 380 800 / 700 / 590 1000 / 820 / 740External Static Pressure(2) (H/M/L) Pa 150 / 120 / 100 125 / 95 / 70 120 / 85 / 70Boost External Static Pressure Pa 235 (500m³/h) 125 (800m³/h) 125 (1000m³/h)Sound Pressure Level(3) (H/M/L) dB(A) 29 / 27 / 26 31 / 30 / 29 34 / 33 / 31Exchanger Material Air to Air cross flow Celluloid material (Total Energy Exchange)Temp Efficiency % 75 75 78Enthalpy Efficiency Heating % 65 65 68Cooling % 61 62 62Dimensions (H x W x D) mm 330x1630x920 385x1710x1015 385x2100x1295Weight Kg 62 69 100
Piping diameter (Liquid / Gas)Inch 1/4 / 1/2 1/4 / 5/8 3/8 / 5/8mm 6.35 / 12.70 6.35 - 15.88 9.53 - 15.88
Duct Sizes (dia) mm 200 250 300Supplied Air Filter Class (EN779)(5) G3 G3 G3Nominal Power Input (H/M/L) W 159 / 99 / 72 272 / 190 / 122 335 / 195 / 150
Specific Fan Power (H/M/L) W/(m3/s) 1145 / 829 / 682 1224 / 977 / 744 1206 / 856 / 730
Drain Diameter (ext) mm φ32 φ32 φ32Working Range(4) -20°C ~ 46°CPower Supply 230V / 1Ph / 50HzRunning Current A 1.2 1.9 2.2Recommended Fuse Size A 5 5 5
For details of interlocks with Utopia & Set Free systems contact your local sales office.
(1) The nominal cooling and heating capacity is the combined capacity of outdoor and indoor unit of the system and is based on Standard EN14511.(2) Default fan pressure setting. (3) Sound pressure level has been measured in an anechoic chamber, with the measuring point 1.5m below the centre of the unit, with no ceiling
under the unit and using a sound insulated duct. Reflected sound must be considered when installing the unit in the field.(4) The installation of an electric heater is necessary when temperature becomes lower than -5ºC(DB). (5) Hi Efficiency filter class F7 (EN779) is available as accessory.
KPI-X3E