1
HINDUSTAN PETROLEUM CORP. LTD
(A GOVERNMENT OF INDIA ENTERPRISE)
TENDER DOCUMENT
FOR
SUPPLY OF FIRE FIGHTING EQUIPMENT
FOR
BIHTA DEPOT AND TIKRIKALAN TERMINAL
2
INTRODUCTION
Hindustan petroleum corporation Limited is in the process of setting up green field POL Installation at
Bihta, near Patna and at Tikrikalan in New Delhi. This tender has been initiated for the supply of
additional Fire fighting equipment for the both the locations as per the requirements of OISD-117
(Latest revision)
The Detailed Scope of Supply is mentioned under each technical portion of tender document,
Standard Specification and Drawings. The Scope of Supply, in brief, as given here below, shall be
read in conjunction with the Scope of Supply under various sections of the tender document.
Scope of supply of the items as specified under this tender is applicable for both the locations.
However, HPCL reserves the right to place order on part of the work from total scope of work.
All necessary tests shall be conducted by the bidder to determine whether the equipment with
auxiliaries offered conform to the relevant standards and specifications as listed in this tender. Such
tests shall be conducted after arranging the equipment in a manner representative of actual service
conditions at the site and the external component and fittings in places which are likely to affect the
performance.
Compliance with this specification will not relieve the bidder of his responsibility for supplying the
equipment / item of proper design, material and workmanship to meet the specified operating
requirements and also proper workmanship and performance of the facilities under the contract.
Applicable Codes and Standards
The design, fabrication, assembly, inspection, testing, painting, and supply and shipment of Fire
Fighting Items/ Equipment shall be in accordance with the latest edition of codes, specifications and
standards (including standards / specification mentioned therein) listed in this tender.
The successful bidder shall execute the order based on the detailed Technical Specification and Data
Sheets for each of the items specified elsewhere in the tender document.
Inspection and testing
All the equipment/item under Bidder Scope of supply shall be shop tested according to the
relevant standards. All the certificates shall be accompanied with the materials being
despatched to respective sites.
The items under the scope of supply of this tender shall be inspected by TPI (to be appointed
by the bidder from approved TPI list). The bidder shall furnish in his offer the detailed
QAP/ITP. Bidder shall arrange all facilities required during inspection and testing at his cost.
The vendor shall refer the scope of TPI/QAP provided along with the specification for each
item.
All ISI approved items shall carry ISI stamping. The qualified bidder shall submit the copy of
valid ISI License where ever applicable.
The vendor shall provide the necessary drawings, valid certificates like UL listing/FM/VDS
approvals and marking of offered Fire fighting equipment.
3
Schedule of Quantities
S.No Description Unit Qty
Tikrikalan Terminal
1 Emergency Kit Each 1
2 Fixed MEFG Each 4
3 Spare Co2 cartridge 10kg DCP Each 6
4 9 litre Sand bucket Each 2
5 Alcohol resistant Foam Litres 1000
6 Portable MEFG – Trolley mounted Each 2
7 10 Kg DCP Fire Extinguisher Each 2
8 Spare Co2 cartridge 25kg DCP Each 3
9 DCP Powder Kg 25
10 AFFF foam Concentrate Litres 8000
Bihta POL Depot
11 Emergency Kit Each 1
12 Fixed MEFG Each 2
13 Spare Co2 cartridge 10kg DCP Each 12
14 Fog Nozzle Each 2
15 Inline foam inductor Each 1
16 Water Curtain Nozzle Each 2
17 9 Litre Sand bucket Each 2
18 10 Kg DCP Fire Extinguisher Each 10
19 75 Kg DCP Fire Extinguisher Each 1
20 Alcohol resistant Foam Litres 1000
21 Portable MEFG – Trolley mounted Each 2
22 Spare Co2 cartridge 25kg DCP Each 5
23 DCP Powder Kg 50
24 AFFF foam Concentrate Litres 8000
4
SCHEDULE OF QUANTITIES – LOCATION WISE BREAKUP
S.N Item Description Unit Quantity for Total
Quantity Bihta Tikrikalan
1 Emergency Kit
The Emergency kit shall contain the list of items
mentioned below from S. No. A to L as per the
quantities indicated per set of emergency Kit..
The items shall be mounted on a compact light
weight trolley. The vendor shall quote a lump
sum price inclusive of the trolley.
Set 1 1 2
A Chemical/Oil Splash Proof Goggles – Confirming to EN 166 - 4 Nos
B PVC suit – Conforming to EN Standards - 2 Set
C Leak control kit – 1Set
D Mega Phone Ex-Proof –PA System – 1 Set
E Petroleum Clean up Boom
a) Boom 5” diameter and 3m long - 6 Nos.
b) Boom 3” diameter and 3m long – 6 Nos.
c) Granular particles to absorb oil - 20 Kg
F Oil Spill Dispersant – Shall be of water soluble type with spray gun and 20 litre back pack- 20
Kg
G Fireman Axe – Confirming to specification with, rubber handle resisting voltage up to 20,000
V- 1 No
H Emergency escape sets – 15 min duration - 2 Nos
I Flame proof search light/torch, - as per the technical specification - 2 Nos
J Non Sparking tool Kit – as per technical specification- 1 Set
K Electrical Tester – 1 No
L Breathing apparatus – Confirming to EN-137-1988 /NIOSH-MSHA- 1 No
M Cold/Low Temperature hand gloves – 4 Pairs
N Mechanical Tool Kit – 1 No.
2 Fixed Medium Expansion Foam Generator-
Mobile System with inlet flange, Inline foam
inductor with inlet and outlet flange, Foam Pick
up tube, strainer and foam valve etc.
Set 2 4 6
3 Spare CO2 cartridge for 10 Kg DCP Each 12 6 18
4 Fog Nozzle conforming to IS-952 Each 2 0 2
5 150mm NB Inline Foam Inductor suitable for
1900 lpm foam solution rate @ 7-7.5 kg/cm2
pressure
Each 1 0 1
6 Water curtain nozzle confirming to IS 903 Each 2 0 2
7 9 litre Sand bucket with stand – Confirming
to IS 2546
Each 2 2 4
8 10 kg DCP Fire extinguisher , ISI Marked Each 10 2 12
9 75 kg DCP Fire extinguisher , ISI Marked Each 1 0 1
10 Alcohol Resistant Foam Litres 1000 1000 2000
11 Portable MEFG Set 2 2 4
12 Spare CO2 cartridge for 25 Kg DCP Each 5 3 8
13 DCP Powder Kg 50 25 75
14 AFFF Foam Concentrate Litres 8000 8000 16000
5
SPECIAL TERMS AND CONDITIONS
1. SCOPE :Design, engineering, shop assembly, factory testing, Third Party Inspection,
transportation, transit insurance, delivery of Fire Fighting Equipment as per Schedule of
Quantities, specification, terms and conditions at Bihta near Patna and Tikrikalan, in New
Delhi.
2. QUANTITIES: As per technical Specification & Schedule of Quantities
3. EXCLUSION: Unloading at site
4. PAYMENT TERMS: Payment against invoices shall be made on receipt of material at site
against submission of following documents along with Bill/Invoice.
Delivery Challan / Lorry receipt duly acknowledged by our site
Manufacturer’s Test Certificate and copy of certificates from Statutory authorities
Third Party Inspection/ Clearance report
Manufacturer’s Guarantee Certificate & PBG
Operation Manual, drawings and other related documentation
5. Payment shall be made within 15 days of receipt of bill at our Disbursement Section at
Gresham Assurance House, 2nd Floor, Sir P.M. Road, Fort, Mumbai- 400 001.
6. TRANSIT INSURANCE: To be arranged by vendor
7. PERFORMANCE GUARANTEE: Supplies shall be fully guaranteed against any
manufacturing defects/poor workmanship/inferior design or quality etc., for a period of 12
months from the date of delivery or 18 months from the date of supply, whichever is earlier
During this period seller will arrange to repair/replace any defective part at free of cost or
replace complete set if required.
8. EVALUATION OF BIDS: Techno – Commercial evaluation of bids:
To assist in the examination, evaluation and comparison of bids, the owner may at its
discretion, ask the bidder clarifications on the bid. The request for such clarifications
and responses shall be thru e-mail, fax, query in e-proc system.
Prior to evaluation and comparison of bids pursuant to relevant clause in this chapter,
owner will determine the substantial responsiveness of each bid to the bid document.
A substantially responsive bid is one which confirms to all the terms and conditions
of the bid document without material deviation or reservations. The owner’s
determination of bids responsiveness shall be based on the contents of the bid itself.
Conditional bids are liable to be rejected.
Bidders are requested to accept all terms and conditions of the bid document. Bidders
are requested to note that exception if taken by them to or suggested modifications to
the following clauses may result in rejection of their bid.
a. Firm Prices.
b. Guarantee/Warranty.
c. Force Majeure.
d. Price Reduction.
e. Arbitration.
6
9. DELIVERY PERIOD: WITHIN 3 MONTHS FROM THE DATE OF LOI. Preparation
of drawings/ Data Sheet & QAP, review and approval by Owner is included within the
completion period. Owner shall take a min. of one week’s time for review and approval of
Data sheet/drawing/QAP from the date of receipt of documents. (Commissioning shall be
outside the purview of the delivery period & Liquidated Damage)
10. Approved Third Party Inspection Agency: CEIL/DNV/BV/ IRS/ LLYODS
11. DELIVERY LOCATION ADDRESS
Bihta Depot
Hindustan Petroleum Corporation Limited
Bihta Depot Project, Bihta
On Bihta Lai Road, Near Bihta Railway Station
Block: Bihta, Dist: Patna, BIHAR, 801103
Contact Person: Shri Ajoy.Singh, Sr.Manager / Shri Amrendra K.Dubey
Tikrikalan Terminal
HPCL Tikrikalan Terminal Project Site
Village: Tikrikalan, On NH-10, Rohtak Highway
Near Tikrikalan Village Bus stop, New Delhi – 110004
Contact Person: Mr. A.K.Behra
12. The materials are required to be supplied on “Door Delivery Basis” to the respective
locations.
13. The vendor (quoting for extinguishers) must have experience in fabricating extinguishers as
per IS: 2825 (pressure vessel code) and also to submit copies of purchase orders and
inspection certificates issues by Hydrocarbon Industries (PSU) for the above product.
14. Where ever ISI marking has been mentioned, the bidder shall provide valid copy of the BIS
license. The same shall be applicable for FM/UL/CE or other approvals.
15. Vendor quoting for foam generator and matching inline foam inductor shall have it approved
by any of the state/central government test house and the copy of the valid approval should be
submitted along with the offer.
16. In cases where TPI certificates are not applicable, the party has to submit the manufacturer’s
test certificate and guarantee certificate and other standard approvals, as applicable.
17. The successful bidder shall submit all drawings/ data sheet and QAP for owner’s approval
within 15 days of LOI.
Note: Successful vendor shall supply the materials along with manufacturing test certificate and
guarantee / warranty certificate.
7
Technical Specifications
1.0 Emergency Kit
Emergency Kit shall be compact and capable to accommodate minimum of the following rescue
equipment required during an emergency in the oil installation. Emergency Kit shall be consisting of a
compact trolley which can take the load of entire unit with equipment. A suitable towing eye at the
front of the trolley of sufficient strength shall be provided for ease in towing. Braking arrangement
shall be provided. Supporting legs and foldable handle for facilitating manual towing shall be
provided. Trolley shall be equipped with reflectors both in front and rear.
The emergency kit contains the following list of items
A. Chemical / Splash proof goggles
Product Specification-
Features:
The goggle should be ergonomically designed lens ensures unrestricted all round vision
The goggle lens should be easily replaceable.
The Head band should be made from Synthetic material, high quality, individually adjustable and
easy replaceable.
The goggle should offer exceptional wearer comfort.
The goggle should offer 100% UV protection.
The goggle should be such that it could be worn comfortably over most prescription spectacles.
The goggles should be provided with outstanding ventilation ensures a pleasant interior
environment, whilst protecting against splash and dust.
The goggle should have Optical Class 1 polycarbonate lens.
The goggle should be CE approved to EN 166B 3-4-9 – liquid splash, large dust particles, molten
metals and solids.
Colour : Orange / grey
Lens : PC clear / UV
Weight: Only 80 grams.
Technical Specification:
Goggle Frame:
Material : 2 components, PP & TPE
Colour : Orange / Grey
Impact Resistance: Designed to withstand energy impact of 120 m/s with the marking B on the
frame which will confirm to EN Standards.
Symbol of conformity CE, DIN tested sign and certified body number will be marked on the
frame.
Standards : EN 166 – with Frame marking of 3 – for Liquids, 4 – for large dust particles, 9 –
molten metals and hot solids
Goggle Lens:
Material : PC
Colour – Clear
8
Thickness – 1.9mm
Filter – 2-1.2 UV according to DIN EN 170
Optical Class 1 with marking of 1 on the lens.
Impact Resistance: Designed to withstand energy impact of 120 m/s with B marking on the
lens to confirm EN standards.
The lens should be Anti fog from inside according to DIN EN 166 marked with N on the lens
which confirms to EN Standards outside Anti scratch resistance from outside to EN 166
marked with K on the lens which confirms to EN Standards.
Approvals:
Lens: Tested and approved to EN 166 and EN 170 with the marking on the lens such as – Impact
resistance (B), Optical Class (1), Anti fogging (N), Anti Scratch Resistance (K), Filter (2-1.2),
Manufacturer’s name, CE and DIN markings.
Frame: Tested and approved to EN 166 with the marking on the frame such as – Impact
resistance(B), Protection from Liquids(3), large dust particles(4), molten metals and hot solids(9),
certification body number, Manufacturer’s name, CE markings.
B. PVC Suit
The PVC suit shall serve as chemical protective coverall in case of Emergency.
The coverall shall be certified to Type 3 Certified to EN standards. The coverall should combine an
exceptionally lightweight fabric with a high barrier to a wide range of hazardous chemicals. In
addition to the unique design features should have been developed for protecting emergency services
responding team against life threatening liquid chemicals.
The suit intended to be supplied shall have the following features.
The suit should be extremely soft, lightweight coverall designed with attached hood for
protection against highly hazardous chemical splash.
The suit should be certified for Type 3, Type 4, Type 5 & Type 6 protection to EN 14605,
EN 13982-1 & 2 & EN13034 respectively.
The suit should also be certified to be used in Ex-Zone (Explosive Environment) making it
absolutely safe for use in Refineries and other industries where static charges is concern and
explosive environment exists.
The suit should be made from multi-layered fabric having good mechanical strength and
higher chemical resistance.
The suit should be liquid tight.
The suit should be designed with rare entry double seal arrangement for complete chemical
protection.
The sleeves provided should be of double cuff design to enable a liquid tight protection with
attached chemical resistance barrier gloves.
The sleeves should be provided with special knitted elastic cuff for better grip.
The suit should be provided with fully elasticized hood with Neoprene rubber face seal for
better seal when used with full face mask.
The suit should be provided with attached sock with boot cover and overlapping flap.
The suit should be ultrasonically welded for offering complete protection as well as better
mechanical strength at joints. It should be additionally also taped seamed for improved
mechanical performance.
9
The suit should offer wide ranges of Hazardous range of chemical resistance.
The suit should be Green (OR) Yellow (OR) Orange in colour.
The suit should be available in S, M, L & XL size.
Approvals:
The suit should be CE certified to EN 14605 (Type 3 & Type 4), EN 13982 -1&2, EN 13034 & EN
1149-1, EN 14126, EN 1073-2.
C. Leak Arresting Control Kit
One Complete Set consisting of 1 no. each of leak arresting pad, leakage control of external pipes,
internal pipes, large external pipes up to 8 inch, drums/containers leakages, general purpose leakages,
large hole leakages in storage tanks.
The kit shall additionally consist of the following.
1.5 bar leak sealing bandage for sealing external leaks on the pipes having following dimensions
Sealing Size – 200 to 450mm
Size of bandage – 450 X 1700 mm
Weight – 11 kg.
For Drum/Container leakage we have leak sealing lances in different shape like wedge & cone type
Wedge 1.5 bar – Size 23 x 6 x 5 cm , Sealing Size / Wide – 15-45/60-80
Wedge 1.5 bar – Size 23 x 8 x 5.5 cm , Sealing Size / Wide – 15-45/80-110
Wedge 1.5 bar – Size 23 x 11 x 7 cm , Sealing Size / Wide – 30-60/110-170
Cone 1.5 bar - Size 23 x Dia 7 cm, Sealing Size – 30-60
Accessories required for both the above:-
1- Pressure Reducer – 200/300 bar with connection hose 2mtr.
2- Connection Hose 5 mtr Yellow
3 –Foot Pump 1.5 bar with 2 mtr connection hose.
4- Single controller 1.5 bar
5 –Inflation Hose 5 Mtr blue.
D. Megaphone Explosive proof PA System
Portable battery operated PA system with 1 loud speaker with a range of 1 KM in still air and 500 M
in noisy areas.
A powerful and durable megaphone suitable for all outdoor occasions. It should have a built-in
powerful 25W amplifier and a high quality anti-feedback microphone which can project a clear sound
up to a distance of 1 km depending upon conditions. The microphone should also feature a handy
push to talk switch and rotary volume control and should be made from strong ABS and with a rubber
edge protector.
The system intended to be provided shall have the following features as mentioned below.
Shoulder strap for comfortably hanging it on the shoulder.
Built-in switchable siren function
10
Pistol grip handled with trigger switch
Supplied with 5m power lead, cigarette lighter plug to DC plug for external 12V DC
operation.
Specification
Power max 25W
Battery 12V (8 x C)
Range 0.5 – 1 km
Dimensions 335 x 230 mm
Weight – 1.65 kg
E. Petroleum product clean up Chemical
The petroleum product clean up chemical kit shall contain the following.
a. Oil absorbing boom – 5” diameter, 10 feet long.
b. Oil absorbing boom – 3” diameter, 10 feet long.
c. Granular Particles to absorb oil – 20kg pack.
Specification for Oil absorbing boom
Oil Absorbent Booms made of pure melt blown polypropylene fibers are the most cost-effective
adsorption technology today. Fast wicking fibres absorb up to 25 times their weight in
hydrocarbon.
Excellent for emergencies. Quick, powerful containment and absorption of spilled oil.
Provides containment & maximum adsorption while repelling water
Absorbs oil on land or water even when raining
Ideal uses include wastewater troughs, loading docks, ponds, rivers, and oceans to absorb oily
spills
F: Oil spill dispersant with back pack and spray gun
The oil spill dispersant (OSD) shall have the following specification as mentioned below.
Dispersant – The dispersant shall be of water soluble type and shall be listed in NCP of USA & NIO,
Goa.
Backpack Sprayer 20 Ltr
The 20 litre Lamor Backpack sprayer LDK 20 features a leak proof tank design with piston pump for
easy cleaning and maintenance. It is carried by shoulder harness. Once on the operator's back, it is
easily and quickly adjusted. A basket filter along with trigger valve and nozzle filters greatly reduce
blockages during application. Large 14 cm filling point allows for quicker filling.
Spraying should be controlled from the trigger valve through a lightweight trigger incorporating a
spring loaded quick acting valve and in-line filter. A lock "ON" function eases continual operation
and a lockable "OFF" function prevents accidental operation.
The unit should employ a large capacity wear resistant piston pump ideal for use in harsh conditions.
All working parts should be internal to prevent accidental damage to sprayer pump mechanism.
Rapid-fit shoulder straps with rubber shoulder pads for added comfort. Shoulder harness is fully
extended when putting the sprayer on or taking it off. Once on the operator's back, it is easily and
quickly adjusted.
11
With pressure up to 3 bar, it is ideal for manual dispersant spraying. Spraying is controlled from the
trigger valve.
Additional Design details:-
Lightweight 50 cm lance with holder
Spring-loaded, ON/OFF valve
Reusable hose clips
Reinforced, 124 cm synthetic hose
Quick filling with large 14 cm opening
Side opening for emptying of the tank
Ergonomically designed transparent, polypropylene tank
Left or right-handed operation
Storage compartment for nozzles etc
Basket filter along with trigger valve and nozzle filters can greatly reduce annoying stops in the
job.
A 1 or 3 bar pre-set (Low or High) is set according to the nozzle type used.
Spraying is controlled from the trigger valve.
Lightweight trigger has spring-loaded quick acting valve and line filter.
Best for harsh conditions.
Well protected under sprayer.
Easy to service
Physical Dimension:-
Length 410 mm
Width 190 mm
Height 630 mm
Weight 5,5 kg
Capacity 20 litre
Pressure 1 to 3 bar
G: Fireman Axe
Axe mate Tool Kit:
Application: Emergency workers, fire fighters & in disasters
Specification: Axe with fibre glass reinforced, thermoplastic handle, forged tested for 20,000 V with
different attachments, i.e. shovel, mattock, hoe, fire rake, narrow pick, broad pick, quality leather axe
sheath, canvas carry case & heavy duty cardboard with handles.
Weight: 5 Kgs
H: Emergency escape sets:
The emergency escape sets shall confirm to the following specification as mentioned below.
12
Specification:
a) The Escape set must provide duration minimum of 15 minutes.
b) Weight of apparatus must not exceed 3.0 kg
c) It must be worn over beard and spectacles.
d) The apparatus should have panoramic view.
e) It should be a Constant Air Flow type apparatus and shall provide sufficient amount of air
f) The Carry bag should have High visibility with a Bright Orange colour.
g) The Hood for apparatus shall be Transparent Universal-fit which covers the head completely.
h) The pressure gauge should be fitted to the Reducer valve directly to give a constant indication
of cylinder pressure.
i) Cylinder should be of Alloy Steel material.
j) The water capacity of the apparatus should be 2.0ltr with the working pressure of 200 bar.
k) The total air present in Cylinder must not exceed 400 litres.
l) The equipment must be easy to operate by means of ON/OFF hand wheel.
m) Instruction of use should be written on the Carry bag.
Approval: The set should be supplied with CCE approved cylinders.
I: Flameproof Search light
Rechargeable Flame Proof Torch / light for use in Explosive environment with high visibility.
Product Features:
90° articulating head for greater lighting flexibility.
Three position toggle switch (choose between primary light only or primary light and LED
taillights), inset switch prevent accidental activation.
Ergonomic, ribbed texture handle ensures a sure grip, even with gloves.
Rubberized head handle and base for shock absorbency
Low battery indicator, which reveals when 30 minutes of power remains.
Specification:
Lithium ion battery available with 4 cell battery.
Xenon bulb 12 V.
Bulb life 300 Hrs maximum.
Light output 264 lumens
Weight with battery should not exceed 900 gms.
Continuous burning time 2.5 Hrs
Charging time 4 Hrs.
Components:
Body: Super-tuff, chemical, heat resistant and water proof nylon casing.
Lens: Polycarbonate.
Lens ring: Super-tuff nylon for lens protection.
Shoulder strap: Nylon.
Physical Dimension:
Length: Not more than 10” & height not more than 6”.
Diameter not more than 4”.
13
Components:
Class 1 Div 2, Groups A, B, C & D.
Class II Div 2, Groups F & G.
Temperature code for 4 cell is T1.
NFPA 1901 14.1.11.2 certified.
J:Non Sparking tool kit
Non sparking tool kit shall be made of Copper-Beryllium Alloy material. They should be of a reputed
brand. The complete set shall be supplied in a easy to carry nylon carry pouch and should consist of
items as mentioned below:
Shoe Handle Brush – 1 No. 1 ½” Blade X 15” Long 12” Tin snips
9” Crate opener -1 No. Spray booth scraper 8” Adjustable Wrench
16 Oz Claw hammer with fibre
glass handle 1 No.
3” blade X 9 ¼ “ Long 12” Adjustable Wrench
Common knife 5 ¾ Blade : 1
No., 10 ¾ OAL
Standard Screw driver – 5/16”
Tip
14” Al Pipe wrench
12” Groove Joint Pliers 6” Blade 12” Bung wrench (Fits ¾” X
2”)
Deck Scraper 3 “ Philips Screw driver
K: Electrical Tester
General purpose electrical pen tester used to detect voltage in the range of 110V/220V. The tester
shall bear CE marking and shall be of a good brand.
L: Breathing Apparatus
The self-contained breathing apparatus with spare cylinder shall the following specifications as
mentioned below.
Approvals:
Should be approved to EN 137: 2006 certificate should be attached along with the offer.
Weight:
The total weight of entire set with filled cylinder should not exceed 11.5 Kgs.
Face Mask:
Face mask should conform to EN 136. Certificate to be attached along with the offer.
Should be manufactured out of EPDM rubber.
Should have a double reflex sealing for leak tightness and cushioning effect.
Should have a polycarbonate lens with SS visor holding frame.
Should have 5 strap harness.
Should have a spring loaded exhalation valve.
Should have SS-speech diaphragm.
Should have an easy & quick fitting Plug-in connection to Demand Valve.
Should have an inner mask to minimize Co2 build-up.
14
Lung Demand Valve:
Should be connected to mask with a Plug-in connection from the front side of mask.
Should be capable of delivering up to 500 lpm of air.
Lund Demand Valve retainer should be provided on waist-belt to plug in the demand valve
when not being used to prevent dust & other particles from entering the Lung Demand Valve.
It should be single hose and end connection to pressure reducer should not be threaded type.
Warning Device:
Warning Whistle should be positioned on the shoulder in front of the user& close to the ear of
the user.
It should be high-pressure activated & medium pressure driven to prevent freezing in cold
places.
It must operate at a residual cylinder pressure of 55 +/- 5 bar.
Back Plate assembly:
Should be orthopedically designed.
Should be moulded from glass filled polyamide with carbon fibre & non-metallic.
Should be chemical, heat & flame resistant, lightweight, water resistant, anti-static & should
have incorporated moulded carrying handles.
Should have rubber boot at bottom end to absorb impact.
Should be warranted for at least 8 years.
It should be capable to use underwater up to 1 mtr depth in case of emergency for rescue
work.
Cylinder Strap:
Should be made of heat resistant material & should be capable of accommodating different
diameters of cylinders.
Should have a fail-safe cam lock mechanism.
Harness:
Should be made from strong, heat resistant material.
Should not be riveted or welded on back plate but should pass through the back plate.
Pressure Reducer:
Should be small, sturdy & tamper proof.
Should be capable of delivering up to 1000 lpm of air.
Pressure Gauge:
Should have a luminesce dial.
Should be encased in rubber cover.
Should be integrated with the warning whistle in a streamlined hose without any manifold
block.
Cylinder valve:
15
Should be provided with rachet arrangement to prevent accidental closing as per the
requirement of EN 137.
The axis of cylinder valve should be parallel to cylinder axis.
Should be provided with cylinder blank to protect valve threads.
Hose:
Should not have any non-metallic outer cover.
Should be hydro tested at twice the operating pressure.
Cylinder:
Should have NOC from CCOE, Nagpur in the name of the bidder.
Should be made from carbon composite. Cylinder should not weigh more than 6 Kg.
Should have a diameter of 140mm, water capacity of 6 ltr & filling pressure of 300 bar.
Should be hydro tested at 450 bar.
Should have CCE approved service centre in Mumbai, to provide easy service.
Cylinder life should be 20 years which should be mentioned on the cylinder.
Approvals:
Should be CE certified to EN 137:2006
Should be CE certified to EN 136 for Mask
M: Cold /Low temperature hand gloves:
Cryogenic hand gloves (low temperature protection)
Gloves for handling cryogenic liquid like liquefied petroleum gases (liquid/ Vapor/mixture) are
required for protection against low temperature.
Gloves must meet the relevant EN standards.
These gloves should be multi layered insulated design to give max protection to hands from hazards
encountered during working at ultra-cold atmospheres. These gloves should be light weight, flexible,
durable and should be comfortable to wearer for extended period.
Inside temperature of glove to remain within allowable tolerable temperature limits of human skin as
per EN standards while exposed to liquefied petroleum gases (liquid/vapor/mixture).
Gloves to be made from Poly Vinyl Chloride over a cotton liner with Polyurethane foam
coating.
The glove should protect against mechanical hazards as per EN 388 and shall meet Level 4
abrasion rating.
The gloves should be able to withstand a temperature of -30 degrees.
Gloves should be of size 10.
Gloves should be water proof.
16
Each glove should be marked with model name, name of manufacturer, relevant standards
and pictograms.
Gloves should be CE certified to EN standards.
Approvals:
Gloves should be CE certified to EN 388 for Mechanical strength, EN 511 for cold temperature and
EN 374.
N: Mechanical Tool kit:
The mechanical tool kit should be of a reputed brand and supplied as per the quantity mentioned
below in a easy to carry nylon carrying bag.
Screw Drivers - Set should consist of set of 12 different size
Adjustable Spanner – Set of 5 of different size
Ball Pein Hammer – 2 Nos
Multipurpose combination Pliers – 2 Nos.
Bolt Cutter – 1 No. each of different sizes - 200 mm / 300 mm / 350 mm / 450 mm / 600 mm / 700
mm / 900 mm / 1050 mm / 1200 mm.
Sheet Cutter - 1 No. each of different sizes – 10 mm / 12 mm / 14 mm
Double end Spanner with ribs – Set of 16 different types
Hack Saw Cutter – 1 No.
Spare Hack Saw Blade – 10 Nos.
2.0 Fixed Medium Expansion Foam generator
The medium expansion foam generator shall consist of the components designed for fire protection &
vapour suppression in bunded or dyked areas surrounding flammable liquid storage tanks. These shall
also be suitbale for other applications requiring large volumes of free flowing foam e.g. Process areas,
pump houses etc.
Medium expansion foam generator with inlet flange
Inline foam inductor with inlet and outlet branches
Foam Pick up tube, Strainer and foam valve.
a) Medium Expansion Foam Generator (MEFG) shall have the following specification.
Medium Expansion foam generator shall be designed to provide minimum foam expansion
ratio of 1:35 when used in combination with standard AFFF foam (3% concentration).
The inlet of foam generator shall be fitted with 80mm NB flange (ANSI B150).
The foam generator shall be able to generate rated flow rate of minimum 600 LPM (foam
solution) at 3.0 bar (g) inlet pressure. Foam generator shall be having “K” factor 345-380
approximately.
Glycerin filled pressure gauge of range 1.0 to 10 bar gauge shall be fitted near the inlet
coupling. Complete foam generator with inlet coupling & pressure gauge shall be made of
stainless steel (SS-316). The barrel of MEFG shall be suitably designed to handle 5 barg
17
pressure. The barrel should be of Shielded Metal Arc welded using SS-316 compatible
electrodes.
Operating / Performance parameters:
Operating Pressure Range 2.5 to 7 bar(g)
MEFG foam expansion ratio Minimum 1:35
Rated flow rate Minimum 600 litres/min @ 3.0 bar g
K factor(nozzle fixed in the MEFG) 345-380
Stream Range Minimum 3 metres
K=Q/ where Q is discharge rate (LPM) and P is pressure (bar g)
b) Fixed Inline foam Inductor shall have the following specification.
Inline inductor for foam induction shall have 80 mm inlet & outlet flanges (ANSI
B150 rating). Capacity of inlet inductor shall be minimum 600 LPM foam solution @
5-7 Kg/cm2
pressure at inlet. Foam inductor shall be able to induct 3% AFFF with inlet
pressure of 5-7 Kg/cm2. Inductor shall be fitted with inbuilt check valve, Complete
foam inductor, strainer, valve shall be made of Stainless steel (SS 316).
Operating Pressure Range 5 to 7 bar(g)
Rated flow rate Minimum 600 liters/min @ 5-7 bar g
Minimum suction lift 3 m
Maximum pressure drop across inductor 35% of inlet pressure.
c) The pick-up tube shall have the following specification:
S.NO Item Name MOC
1 Pick up tube PVC braided hose of 2m length
2 Strainer SS-316
3 Valve SS-316
Painting and Marking:
All Stainless steel metal parts of the foam generating unit shall be painted with two coats of
polyurethane paints in yellow colour. Following marking shall be permanently written on each of the
MEFG:
1. Owner’s logo on both sides
2. Name of the supplier
3. Serial Number.
4. Month & year of manufacture
Scope of TPIA
The vendor shall carry out in house inspections as per approved quality assurance plan (QAP).
Vendor shall also arrange third party inspection during manufacture and testing through M/s. Lloyds,
Bureau Veritas, DNV or EIL for quality assurance, testing and performance evaluation as per the
specifications in line with the quality assurance plan.
18
The system integrated as a whole shall be subjected to hydro test and performance test. Owner’s
representative may witness the inspection along with the third party. Therefore, vendor to intimate the
owner three weeks in advance for such inspection. The third party inspection charges shall be borne
by the vendor.
Prior to dispatch from vendor’s shop the following acceptance tests shall be carried out by vendor to
complete satisfaction of third party inspection agency and owner’s representative. All consumables
(e.g Water, foam compound etc.) required for the performance & hydrotesting shall be arranged by
vendor by his own cost. Vendor shall arrange all facilities to carry out inspection and testing covering
the following:
Review of raw materials test certificates.
Measurement of flow through foam inductor & foam generator at 7 Kg/cm2 pressure at inlet
of inline foam inductor.
Measurement of foam expansion ration of foam generator.
Measurement of foam induction rate at inline foam inductor as per the specification.
Visual and dimensional check.
Owner or his representative shall have access at all reasonable times to vendor’s works where the
appliance or its accessories are being fabricated and tested. Vendor shall submit the detailed QAP to
the owner for approval on placement of the order.
3.0 Spare Co2 Cartridge for 10 kg DCP Extinguisher:
The cartridge shall have Co2 gas capacity cartridge of capacity 200 grams confirming to IS-4947. The
cartridge shall bear a suitable ISI mark suitable for 10Kg DCP.
4.0 Fog Nozzle
Fog Nozzles made out of gunmetal chromium plated suitable for 63 mm dia fire hose, having
Arrangement for straight stream, high pressure fog and shut off as per IS: 952 and with couplings
as per IS:903.
Scope of TPIA
TPIA shall verify & certify if the material/equipment offered meets all the above mentioned
specification.
5.0 Inline foam Inductor
Specification
1.0 Design Particulars
a) Fluid to be handled Raw water & foam concentrate solution
b) Inlet Size 150 mm NB
c) End connection Flanged Same as inlet
d) Pressure drop across inductor Max 35% of inlet prrssure
e) Capacity 1900 lpm
2.0 Material of Construction
a) Housing SS 304 Stainless Steel ASTM A 351 – CF8
b) Nozzle SS 304 Stainless Steel ASTM A 351 – CF8
c) Diffuser SS 304 Stainless Steel ASTM A 351 – CF8
19
d) Flange SS 304 Stainless Steel ASTM A 351 – CF8
e) Bolt SS 304 Stainless Steel ASTM A 351 – CF8
f) Orifice SS 304
g) O Ring SS 304
3.0 Scope of TPIA
a) Hydro-test 100%
b) Body 15 kg/cm2
c) MOC Review of Material test certificate
4.0 Finish and Paint
a) Finish All burrs and sharp edges shall be removed and the
inside surface should have smooth finish
b) Paint color Yellow
5.0 Marking
The system shall have permanent marking of the following
a) Manufacturers name and trade mark
b) Year of manufacture
c) Type
d) Size
6.0 Documents to be submitted along with the offer
Catalogue / Literature
7.0 Documents to be submitted after offer
Cross sectional drawing with part number, material of construction and major dimensions
after approval from HPCL
8.0 Documents to be submitted during inspection
a) Approved QAP
b) Hydro test certificate
c) Performance test certificate
d) Chemical test certificate
e) Warranty certificate
f) Mechanical test certificate
6.0 Water curtain Nozzle
The water curtain nozzles shall be made out of chromium plated gunmetal suitable for connecting it
to a 63mm fire hose with instantaneous couplings suitable for curtain as per IS:903-1993. The nozzles
shall bear ISI mark and the hydro testing of the nozzle shall be done at a pressure of 21 kgf/cm2 as per
section 3 clause 7.3 of IS 903-1993.
Scope of TPIA
The TPI has to verify and certify the material/equipment offered in line with the specification
inclusive of all the details as mentioned above.
7.0 9 Litre Sand bucket
The sand bucket shall have a capacity of 9 ltr. each and shall confirm to IS 2546\1974. The Material
of construction must be galvanized MS. The handle and dome shaped bottom to be painted with black
colour. The outer shell of the bucket to be painted with fire red colour confirming to IS:5 and inside of
the bucket shall be painted in white. Buckets shall be provided with suitable stand with 4 number
hooks to hang sand filled buckets. Canopy over the stand to be provided to protect bucket from sun
and rain.
20
Scope of TPIA
The TPI has to verify and certify the material/equipment offered in line with the specification
inclusive of all the details as mentioned above.`
8.0 10 kg DCP Fire Extinguisher
10 kg DCP Fire extinguisher shall confirm to the standard IS 2171 with complete initial charging of
CO2 cartridge (200 gms). The system shall bear ISI mark confirming to standard IS 4947 with the 10
kg chemical powder confirming to IS 4308 (Latest edition).
Apart from the above specification the fire extinguisher shall conform to the following:
a. Size of filler opening (inner dia) shall not be less than 75mm
b. Length of inner container not less than 35 cm
c. Cap shall be gunmetal with chromium plating
d. Hose shall be of braided plastic high pressure with one metre length with nozzle of ABS
Plastic.
e. All other components, design and performance, anti-corrosive treatment shall be as per IS
2171 (latest edition).
f. Certification that every fire extinguisher shall be made with radiographic quality welding has
to be provided and all the design /fabrication shall confirm to IS 2825. The radiography has to
be performed for 10% of the weld joints and 50% for T joints. Design calculations shall be
submitted along with the offer.
g. The bottom ring shall have permanent punching at the bottom ring is required.
I. Manufacturer’s name
II. Year of manufacturing
III. Manufacturer’s serial number
IV. PO No. and date
V. Inspector stamp
VI. Date of hydraulic test shall be written with space for writing the subsequent dates for
hydraulic test.
VII. Safe DCP filling height shall be marked on the extinguisher.
SCOPE OF TPIA:
The TPIA has to inspect, verify and certify the material (equipment) for the details as mentioned in
the specification.
9.0 75 kg DCP Fire Extinguisher
The 75 kg DCP Fire Extinguisher shall confirm to IS 2171 and shall meet the following specifications
/ requirements.
a. The extinguisher shall be made of 6 mm thick MS sheet (BQ plate and design of vessel as per
IS 2825) with radiography quality welding. The extinguisher shall confirm to IS 10658-1999.
Extinguisher shall be treated to operate in anti-corrosive environment. Non-metal parts shall
be of gunmetal. Design calculations of the extinguisher shall be submitted along with the
offer.
21
b. The minimum length of the hose shall be of 5m with bursting pressure not less than 5 kg/cm2.
c. Drain plug provided on the body shall have a minimum diameter of 25 mm.
d. The nozzle shall be of trigger controlled and capable of discharging powder as per ISI
specification.
e. Automatically and manually operated safety relief valve to be provided as per IS:
10658:1999.
f. Pressure gauge shall have minimum 50mm dia and range from 0 to 42 kg/sqcm to be
provided on the body.
g. The extinguisher shall be mounted on a robust trolly having two heavy duty bearing fitted
with rubberized wheels and strong handles for easy mobility.
h. ISI marked Co2 gas cylinder shall be of 2 KG capacity and shall be approved by Department
of Explosives with protector and thermal insulation to be fitted with ISI marked wheel type
valve.
i. Dry powder provided shall confirm to IS:4308. The power shall be packed in plastic rigidex
material type bags with heavy duty LD lines duly hermetically sealed. The materials of
packing and sealing shall be made in such a way that if the pack is kept inside the water
bucket for 24 hours, not a single drop of powder shall remain unaffected against moisture.
j. The extinguisher shall be painted with two coats primer (red oxide) and then final coat of fire
red painting by spray method. The colours shall confirm to IS :5 (latest edition).
k. As per IS 2825 DPT of the fillet welds of all nozzles and attachment shall be carried out and
no discontinuities in welding will be permitted.
l. Certification that every fire extinguisher shall be made with radiographic quality welding has
to be provided and all the design /fabrication shall confirm to IS 2825. The radiography has to
be performed for 10% of the weld joints and 50% for T joints. Design calculations shall be
submitted along with the offer.
m. Extinguisher shall be hydro tested at 30 kg/cm2 and should not develop any leaks at this
pressure.
n. The bottom ring shall have permanent punching at the bottom ring is required.
Manufacturer’s name
Year of manufacturing
Manufacturer’s serial number
PO No. and date
Inspector stamp
Date of hydraulic test shall be written with space for writing the subsequent dates for
hydraulic test.
Safe DCP filling height shall be marked on the extinguisher.
SCOPE OF TPIA:
The TPIA has to inspect, verify and certify the material (equipment) for the details as mentioned in
the specification.
10.0 Alcohol Resistant Fire fighting foam:
Alcohol resistant fire fighting foam of 3% concentrate, for use with fresh water/sea water suitable for
Flammable petroleum products as per IS:4989- part 4 (Edition 2003-2005)/UL-162 shall also be
acceptable. The supplied Alcohol resistant foam shall have ISI Mark. The shelf life of the AFFF shall
22
be minimum 10 years. The foam compound shall be packed in 20/30 litre polyethylene jerry cans
conforming to IS: 7959. The product shall have a minimum shelf life of 10 years.
SCOPE OF TPIA:
The TPIA has to inspect, verify and certify the material (equipment) for the details as mentioned in
the specification.
11.0 Portable Medium Expansion Foam generator
The medium expansion foam generator shall consist of the components designed for fire protection &
vapour suppression in bunded or dyked areas surrounding flammable liquid storage tanks. These shall
also be suitable for other applications requiring large volumes of free flowing foam e.g. Process areas,
pump houses etc.
Medium expansion foam generator with inlet flange
Inline foam inductor with inlet and outlet branches
Foam Pick up tube, Strainer and foam valve.
a) Medium Expansion Foam Generator (MEFG) shall have the following specification.
Medium Expansion foam generator shall be designed to provide minimum foam expansion
ratio of 1:35 when used in combination with standard AFFF foam (3% concentration).
The inlet of foam generator shall be fitted with 63mm with male instantaneous coupling.
The foam generator shall be able to generate rated flow rate of minimum 400 LPM (foam
solution) at 3.0 bar (g) inlet pressure. Foam generator shall be having “K” factor 230-250
approximately.
Glycerin filled pressure gauge of range 1.0 to 10 bar gauge shall be fitted near the inlet
coupling. Complete foam generator with inlet coupling & pressure gauge shall be made of
stainless steel (SS-316). The barrel of MEFG shall be suitably designed to handle 5 barg
pressures. The barrel should be of Shielded Metal Arc welded using SS-316 compatible
electrodes.
Operating / Performance parameters:
Operating Pressure Range 2.5 to 7 bar(g)
MEFG foam expansion ratio Minimum 1:35
Rated flow rate Minimum 400 litres/min @ 3.0 bar g
K factor(nozzle fixed in the MEFG) 230-250
Stream Range Minimum 3 metres
K=Q/ where Q is discharge rate (LPM) and P is pressure (bar g)
b) Inline foam Inductor shall have the following specification.
23
Inline inductor for foam induction shall have 63 mm inlet male instantaneous coupling
& outlet with 63mm female instantaneous coupling. Capacity of inlet inductor shall be
minimum 400 LPM foam solution @ 5-7 Kg/cm2
pressure at inlet. Foam inductor shall
be able to induct 3% AFFF (Max. Pr. Drop permissible: 35% of inlet pressure) with
inlet pressure of 7 Kg/cm2. Inductor shall be fitted with inbuilt check valve, Complete
foam inductor, strainer, valve shall be made of Stainless steel (SS 316).
Operating Pressure Range 5 to 7 bar(g)
Rated flow rate Minimum 400 liters/min @ 5-7 bar g
Minimum suction lift 2 m
Maximum pressure drop across inductor 35% of inlet pressure.
d) The pick-up tube shall have the following specification:
S.NO Item Name MOC
1 Pick up tube PVC braided hose of 2m length
2 Strainer SS-316
3 Valve SS-316
Painting and Marking:
All Stainless steel metal parts of the foam generating unit shall be painted with two coats of
polyurethane paints in yellow colour. Following marking shall be permanently written on each of the
MEFG:
Owner’s logo on both sides
Name of the supplier
Serial Number.
Month & year of manufacture
Scope of TPIA
The vendor shall carry out in house inspections as per approved quality assurance plan (QAP).
Vendor shall also arrange third party inspection during manufacture and testing through M/s. Lloyds,
Bureau Veritas, DNV or EIL for quality assurance, testing and performance evaluation as per the
specifications in line with the quality assurance plan.
The system integrated as a whole shall be subjected to hydro test and performance test. Owner’s
representative may witness the inspection along with the third party. Therefore, vendor to intimate the
owner three weeks in advance for such inspection. The third party inspection charges shall be borne
by the vendor.
Prior to dispatch from vendor’s shop the following acceptance tests shall be carried out by vendor to
complete satisfaction of third party inspection agency and owner’s representative. All consumables
(e.g Water, foam compound etc.) required for the performance & hydro-testing shall be arranged by
vendor by his own cost. Vendor shall arrange all facilities to carry out inspection and testing covering
the following:
Review of raw materials test certificates.
24
Measurement of flow through foam inductor & foam generator at 7 Kg/cm2 pressure at inlet
of inline foam inductor.
Measurement of foam expansion ration of foam generator.
Measurement of foam induction rate at inline foam inductor as per the specification.
Visual and dimensional check.
Owner or his representative shall have access at all reasonable times to vendor’s works where the
appliance or its accessories are being fabricated and tested. Vendor shall submit the detailed QAP to
the owner for approval on placement of the order.
12 Spare Co2 Cartridges for 25 Kg DCP Extinguisher:
The cartridge shall have Co2 gas capacity cartridge of capacity confirming to IS-4947. The cartridge
shall bear a suitable ISI mark suitable for 25Kg DCP.
13. Dry Chemical Powder:
Dry Chemical Powder for fire fighting having chemical composition of sodium based, shall be highly
free flowing and siliconised to make powder water repellent and anti-caking. The powder shall be
packed in rigidex imported materials bag with heavy duty LD liners duly hermetically sealed. The
material of packing and sealing is to be made in such a way that if the packet is kept inside of the
bucket full of water for 24 hours, the characteristics of the powder shall remain unaffected against
moisture.
The dry Chemical Powder shall be conforming to IS: 4308-1982 with all the last amendments and
bearing ISI Mark.
Scope of Inspection:
All tests as per IS : 4308/1982 has to be carried out and reported expect Hygroscopicity & Caking
test for which test certificate from the vendor to be taken.
Dry Chemical Powder should have ISI Mark.
The packaging material to be tested as per clause 4.1.1 of IS:4308/1982. Also material of the
packing should be as per the specification only.
The inspector shall certify that equipment fully meets the standards as given in the specification
and BIS codes.
Vendor should confirm the third party agency from any one of the following approved agencies:
Gujarat Industrial Research & Development Agency
(A Govt. of Gujarat Organisation)
Industrial Research Laboratory
Science College Compound
Baroda - 390 002.
25
Director, Defence Institute of Fire Research
Brig. S.K. Mazumdar Road
Timarpur
New Delhi – 110 054
The vendor must also enclose the copy of executed purchase orders of Hydrocarbon Industry (PSU)
for supply of Dry Chemical Powder with the above said packing.
14. Aqueous Film Forming Foam - AFFF Concentrate
Aqueous film forming foam (AFFF) 3% concentrate, for use with fresh water / sea water suitable for
flammable petroleum products as per IS: 4989-1984 (Part-II). AFFF shall have ISI mark or UL (USA)
approval. The shelf life of AFFF shall be minimum 10 years. The foam compound shall be packed in
20/30 litre polyethylene jerry cans conforming to IS: 7959.
Scope of Third Party Inspection:
Verify and certify the material offered meets all the details mentioned in the specifications.
All tests as per IS: 4989-1984 (Part-II) has to be carried out and reported.
AFFF being offered shall have ISI mark or UL (USA ) listing for flammable hydrocarbon
liquids
AFFF should be packed in 20/30 litre polyethylene jerry cans conforming to IS:7959
Polyethylene jerry cans should bear all details including shelf life and batch number of AFFF.