KEY PLANKEY PLAN
N
10
9
8
67
111
3
5
4
2
18101
DESCRIPTIONDATEREV.
ISSUE/REVISION:
PROJECT NO:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
SCALE:
SHEET NO.
(708) 236-0330 FAX
Hillside, IL 60162
(708) 236-0300
30 N. Wolf Rd., Second Floor
PROJECT:
DRAWING TITLE:
333 WEST 35TH STREETCHICAGO, IL 60616
GUARANTEED RATE FIELD -HVAC / AHU RENOVATION -PHASE VIII
10.26.2018 ISSUED FOR BID
11.14.2018 ISSUED FOR ADDENDUM 1
M0.01
MECHANICAL NOTES,SYMBOLS, ANDABBREVIATIONS
AS NOTED
AS
AS
MS
GENERAL
PIPING
NEW PIPING
EXISTING PIPING TO REMAIN
EXISTING PIPING TO BE DEMOLISHED
CHWR CHILLED WATER RETURN PIPING
CHWS CHILLED WATER SUPPLY PIPING
DRAIN PIPING (CONDENSATE)D
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
CIRCUIT SETTER BALANCING VALVE
DIRECTION OF FLOW
DIRECTION OF PIPE PITCH, DOWN
DRAIN VALVE WITH 3/4" THREADED HOSE ADAPTOR
GATE VALVE
MANUAL AIR VENT
NEW PIPE CONNECTION
PIPE CAP
PIPE DROP/RISE
PIPE ELBOW, TURNED DOWN
PIPE ELBOW, TURNED UP
PIPE SLEEVE
PIPE TEE, BOTTOM CONNECTION, 45° OR 90° ELBOW
PIPE TEE, DOWN
PIPE TEE, HORIZONTAL
PIPE TEE, TOP CONNECTION, 45° OR 90° ELBOW
PIPE UNION
PRESSURE GAUGEPSI
STRAINER
TWO-WAY, MODULATING AUTOMATIC CONTROL VALVE
TWO-WAY, TWO-POSITION AUTOMATIC CONTROL VALVE
DUCTWORK
NEW DUCTWORK
EXISTING DUCTWORK TO REMAIN
EXISTING DUCTWORK TO BE DEMOLISHED
DIRECTION OF AIRFLOW
DDC OR STANDALONE PROGRAMMABLE THERMOSTATT
EQUIPMENT TAGTYPENUMBER
P1
POINT OF CONNECTION OF NEW TO EXISTING WORK
ACCESS DOORAD
RECTANGULAR EXHAUST/RETURN DUCTWORK DOWN
RECTANGULAR EXHAUST/RETURN DUCTWORK UP
RECTANGULAR SUPPLY DUCTWORK DOWN
RECTANGULAR SUPPLY DUCTWORK UP
DUCTWORK BREAK LINE (OR CONTINUATION)
FLEXIBLE DUCTWORK CONNECTION
FC
MANUAL VOLUME (OR BALANCING) DAMPERVD
AUTOMATIC CONTROL (OR MOTOR OPERATED) DAMPER
GRILLE/REGISTER/DIFFUSER TAG
NECK SIZE
SERVICECFM
TYPE
A 6x6 NK100-S
ACD AUTOMATIC CONTROL DAMPERACV AUTOMATIC CONTROL VALVEAD ACCESS DOORAFF ABOVE FINISHED FLOORAHU AIR HANDLING UNITAPD AIR PRESSURE DROPBAS BUILDING AUTOMATION SYSTEMBASC BUILDING AUTOMATION SYSTEM CONTRACTORBFV BUTTERFLY VALVEBHP BRAKE HORSEPOWERBTU BRITISH THERMAL UNITBTUH BRITISH THERMAL UNIT PER HOURBV BALL VALVECBV CIRCUIT BALANCING VALVECC COOLING COILCFM CUBIC FEET PER MINUTECHWR CHILLED WATER RETURNCHWS CHILLED WATER SUPPLYCKV CHECK VALVECO CLEANOUTCOND CONDENSATECO2 CARBON DIOXIDEDR DRAINDAT DISCHARGE AIR TEMPERATUREDB DRY BULBDDC DIRECT DIGITAL CONTROLDN DOWN-E EXHAUSTEA EXHAUST AIR
EAD EXHAUST AIR DAMPEREAT ENTERING AIR TEMPERATUREEC ELECTRICAL CONTRACTORECM ELECTRONICALLY COMMUTATED MOTOREDH ELECTRIC DUCT HEATEREER ENERGY EFFICIENCY RATIOEF EXHAUST FANEG ETHYLENE GLYCOLESP EXTERNAL STATIC PRESSUREETR EXISTING TO REMAINEWT ENTERING WATER TEMPERATUREF FAHRENHEITFC FLEXIBLE CONNECTOR (OR CONNECTION)FLA FULL LOAD AMPSFPM FEET PER MINUTEFV FACE VELOCITYGA GAUGEGPM GALLONS PER MINUTEGV GATE VALVEHC HEATING COILHP HORSEPOWERLAT LEAVING AIR TEMPERATURELH LEFT HANDLWT LEAVING WATER TEMPERATUREMBH THOUSAND BRITISH THERMAL UNITS PER HOURMC MECHANICAL CONTRACTORMCA MINIMUM CIRCUIT AMPACITYMOCP MAXIMUM OVER-CURRENT PROTECTIONMOD MOTOR OPERATED DAMPER
NC NORMALLY CLOSEDNIC NOT IN CONTRACTNK NECKNO NORMALLY OPENNR NOT REQUIREDNTS NOT TO SCALEOA OUTDOOR AIRPD PRESSURE DROPPSI POUNDS PER SQUARE INCH-R RETURNRA RETURN AIRRAD RETURN AIR DAMPERRH RIGHT HANDRPM REVOLUTIONS PER MINUTE-S SUPPLYSA SUPPLY AIRSEER SEASONAL ENERGY EFFICIENCY RATIOSF SUPPLY FANSP STATIC PRESSURESTR STRAINERT THERMOSTAT-T TRANSFERTYP TYPICALTSP TOTAL STATIC PRESSUREVD VOLUME DAMPERVFD VARIABLE FREQUENCY DRIVEWB WET BULBWC WATER COLUMNWG WATER GAUGEWMS WIRE MESH SCREENWPD WATER PRESSURE DROP
MECHANICAL ABBREVIATIONS
MECHANICAL SYMBOLS
NOTE: NOT ALL ABBREVIATIONS LISTED MAY APPEAR IN DRAWINGS.NOTE: NOT ALL SYMBOLS LISTED MAY APPEAR IN DRAWINGS.
A. ALL WORK SHALL BE PERFORMED IN A CLEAN AND WORKMANLIKE MANNER. CARESHALL BE EXERCISED TO MINIMIZE ANY INCONVENIENCE OR DISTURBANCE TOOTHER AREAS OF THE BUILDING WHICH ARE TO REMAIN IN OPERATION.
B. ALL DEMOLITION OF THE HVAC SYSTEM AS CALLED FOR ON THE DEMOLITIONDRAWINGS SHALL BE UNDER THIS CONTRACTOR'S WORK.
C. CONTRACTOR SHALL VISIT THE BUILDING, BEFORE SUBMITTING HIS BID, TO VERIFYALL DIMENSIONS AND EXISTING CONDITIONS WHICH MAY AFFECT HIS WORK.
D. BEFORE STARTING ANY DEMOLITION WORK ON HVAC EQUIPMENT WHICH HAS ANELECTRICAL CONNECTION AND IS INDICATED TO BE REMOVED, THIS CONTRACTORSHALL MEET WITH ELECTRICAL CONTRACTOR TO IDENTIFY ALL SUCH EQUIPMENT.ELECTRICAL CONTRACTOR SHALL DISCONNECT THE POWER TO EACH UNIT ANDREMOVE CONDUIT, WIRING, DISCONNECT SWITCHES, AND STARTERS UNDER THISCONTRACT, UNLESS NOTED OTHERWISE. THIS CONTRACTOR SHALL REMOVE ALLEQUIPMENT, ELECTRICAL TEMPERATURE CONTROL WIRING, AND CONDUIT UNDERTHIS CONTRACT.
E. CONTRACTOR IS RESPONSIBLE FOR SCANNING WALLS, FLOORS, ETC., TO LOCATEOBSTRUCTIONS (SUCH AS EXISTING ELECTRICAL CONDUIT, WIRING, PIPING, SLABRE-INFORCING, ETC.) PRIOR TO MAKING ANY PENETRATIONS IN WALLS, FLOORS,ETC. CONTRACTOR TO LOCATE ALL SLAB REINFORCING PRIOR TO MAKING ANY SLABPENETRATIONS. NO SLAB REINFORCING SHALL BE DAMAGED OR CUT. ANY DAMAGERESULTING FROM CORING OR WALL AND/OR FLOOR PENETRATIONS IS THE SOLERESPONSIBILITY OF THE CONTRACTOR AND SHALL BE REPAIRED AT NO ADDITIONALCOST TO THE OWNER.
F. CONTRACTOR SHALL BE RESPONSIBLE FOR HIS OWN CLEANUP THROUGHOUT THECOURSE OF THE DEMOLITION WORK.
G. NO EQUIPMENT, PIPING, VALVES, ETC. SHALL BE REMOVED, DISCONNECTED ORSHUT DOWN WITHOUT PRIOR REVIEW WITH THE OWNER AND/OR ENGINEER TOCONFIRM THAT AREAS TO REMAIN IN OPERATION WILL NOT BE AFFECTED. IF ANYAREAS NOT WITHIN THE SCOPE OF WORK ARE AFFECTED BY ANY SHUTDOWN, ONE(1) WEEK ADVANCE NOTICE SHALL BE GIVEN TO THE OWNER. SHUTDOWNS SHALLBE A MAXIMUM OF FOUR (4) HOURS UNLESS OTHERWISE INDICATED.
H. ALL EQUIPMENT, MATERIAL, ETC. THAT IS BEING DEMOLISHED WILL BECOME THEPROPERTY OF THE CONTRACTOR UNLESS OTHERWISE NOTED OR SPECIFIEDBELOW. ALL SUCH ITEMS WILL BE REMOVED FROM THE BUILDING SITE BY THECONTRACTOR IN A PROPER AND LEGAL MANNER. NO ITEM WHICH IS BEINGREMOVED UNDER THE DEMOLITION CONTRACT MAY BE REUSED UNDER THE NEWWORK CONTRACT UNLESS NOTED ON THE DRAWINGS. ALL ITEMS TO BE TURNEDOVER TO THE OWNER SHALL BE STORED PER THE OWNER'S INSTRUCTION.
I. ALL SALVAGEABLE MATERIAL AND EQUIPMENT, INCLUDING BUT NOT NECESSARILYLIMITED TO HEATING UNITS, AC UNITS, DIFFUSERS, VALVES, ETC., SHALL BEREMOVED AND MAINTAINED IN AS GOOD CONDITION AS POSSIBLE AND TURNEDOVER TO THE BUILDING OWNER'S REPRESENTATIVE. HOWEVER, IF THE BUILDINGOWNER'S REPRESENTATIVE DECIDES ANY SUCH MATERIALS ARE OF NO VALUE TOTHE BUILDING, THEN THEY SHALL BECOME THE PROPERTY OF THE MECHANICALCONTRACTOR WHO SHALL REMOVE SUCH DISCARDED WORK FROM THE PREMISESAND DISPOSE OF SAME.
J. EXISTING EQUIPMENT OR SYSTEMS WHICH ARE SPECIFIED TO BE REPLACED BY NEWEQUIPMENT OR SYSTEMS SHALL NOT BE REMOVED FROM SERVICE UNTIL THE NEWEQUIPMENT OR SYSTEMS HAVE ACTUALLY ARRIVED AT THE PROJECT SITE.
K. SEQUENCE OF ALL DEMOLITION WORK SHALL BE IN STRICT ACCORDANCE WITH THECONTRACT DOCUMENTS AND/OR AS DIRECTED BY THE ENGINEER. ALL SHUTDOWNSOF EXISTING SYSTEMS SHALL BE SCHEDULED AND APPROVED BY THE OWNER.
L. COORDINATE USE OF THE BUILDING ELEVATORS AND ALL MATERIAL DELIVERIESWITH THE OWNER.
M. IF ANY ISOLATION VALVES SHOULD FAIL DURING DEMOLITION, OTHER THAN THOSECALLED OUT TO BE REPLACED, THIS CONTRACTOR SHALL REPAIR/REPLACE THEVALVE AND SUBMIT A CHANGE ORDER REQUEST FOR APPROVAL.
N. THE CONTRACTOR PERFORMING THE DEMOLITION WORK SHALL REMOVE NO MORETHAN 8" OF BUILDING MATERIAL AROUND EACH DEVICE BEING DEMOLISHED.PROVIDE PATCHING AS REQUIRED FOR FINISHED WORK. THE CONTRACTOR SHALLOBTAIN APPROVAL FROM OWNER OR ENGINEER PRIOR TO PERFORMING REMOVALOF MATERIAL FROM EXISTING BUILDING CONSTRUCTION.
O. CONTRACTOR SHALL PROTECT ALL WINDOWS AND SURFACES DURING DEMOLITION.ANY COSTS INCURRED BY DAMAGE FROM CUTTING TORCHES, SPARKS, HEAT, OROTHER DEMOLITION PROCEDURES WILL NOT BE THE RESPONSIBILITY OF THEOWNER.
P. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL LABOR AND MATERIALREQUIRED TO PATCH ALL OPENINGS IN EXISTING WALLS, FLOORS, AND FIRESEPARATIONS CREATED BY THE REMOVAL OF EACH TRADE'S MATERIAL ANDEQUIPMENT WHERE THESE OPENINGS ARE NOT TO BE REUSED. CONTRACTORSHALL BE RESPONSIBLE FOR REPAIR AT AREAS THAT MECHANICAL EQUIPMENT WASREMOVED BACK TO ITS ORIGINAL CONDITION INCLUDING ALL DRYWALL, PLASTER,PAINTING, ETC. CONTRACTOR SHALL EMPLOY TRADES EXPERIENCED IN GENERALCONSTRUCTION TO PATCH ALL OPENINGS. TOOTH IN MASONRY USING WHOLEUNITS TO MATCH EXISTING MASONRY CONSTRUCTION.
Q. EXISTING PLUMBING, ELECTRICAL, AND FIRE PROTECTION SYSTEMS NOT SHOWNSHALL REMAIN UNLESS INDICATED TO BE DEMOLISHED ON THE MECHANICAL ANDELECTRICAL PLANS. INSTALLATION OF NEW EQUIPMENT MAY NECESSITATE THEREROUTING OF EXISTING SYSTEMS TO REMAIN. COORDINATE WITH ENGINEER ANDOWNER.
R. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
GENERAL MECHANICAL DEMOLITION NOTESA. THE PRIME CONTRACTOR AND ALL HIS SUB-CONTRACTORS SHALL REVIEW IN
DETAIL AND UNDERSTAND THE DRAWINGS, SPECIFICATIONS, AND BIDDOCUMENTS PRIOR TO PROVIDING A BID. IF ANY CONFLICTS ORCONTRADICTIONS BETWEEN THE DRAWINGS, SPECIFICATIONS, OR BIDDOCUMENTS ARE IDENTIFIED, OR IF THE DRAWINGS, SPECIFICATIONS, OR BIDDOCUMENTS CONFLICT WITH OBSERVED FIELD CONDITIONS, IT IS THE PRIMECONTRACTOR'S RESPONSIBILITY TO IMMEDIATELY SUBMIT A REQUEST FORINFORMATION (RFI) TO THE ENGINEER FOR A RESOLUTION PRIOR TO BID. IF NORFI'S ARE RECEIVED, IT IS THEN UNDERSTOOD THAT NO CONFLICTS ORCONTRADICTIONS UNDER THE ABOVE CONDITIONS EXIST.
B. ALL WORK SHALL BE PERFORMED IN A CLEAN AND WORKMANLIKE MANNER.CARE SHALL BE EXERCISED TO MINIMIZE ANY INCONVENIENCE OR DISTURBANCETO OTHER AREAS OF THE BUILDING WHICH ARE TO REMAIN IN OPERATION.
C. MECHANICAL CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND FIELDCONDITIONS PRIOR TO PROCEEDING WITH ANY WORK. ANY DISCREPANCIESSHALL BE REPORTED TO THE ENGINEER FOR RESOLUTION.
D. EXISTING MATERIALS THAT ARE REMOVED SHALL NOT BE REUSED IN NEWSYSTEMS UNLESS SPECIFIED.
E. MEASURES SHALL BE TAKEN TO ENSURE ALL SURFACES, INCLUDING BUT NOTLIMITED TO FINISHED FLOORS, ELEVATORS, AND INTERIOR WALLS, AREPROTECTED DURING DEMOLITION, EQUIPMENT INGRESS, AND OTHER MATERIALMOVEMENTS. ANY DAMAGE RESULTING FROM ACTIVITIES RELATED TO THISPROJECT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
F. MECHANICAL CONTRACTOR SHALL TAKE CARE TO PROTECT ADJACENT SPACESFROM CONSTRUCTION DUST/DEBRIS.
G. REFER TO MECHANICAL DRAWINGS, PROJECT SCHEDULE, CONSTRUCTIONPHASING, AND SCOPE OF WORK FOR ADDITIONAL INFORMATION. ALL WORKAFFECTING SHUTDOWN OF BUILDING UTILITY SYSTEMS SHALL BE COORDINATEDWITH OWNER.
H. ALL SHUT DOWNS OF EXISTING SYSTEMS SHALL BE SCHEDULED AND APPROVEDBY THE OWNER. SHUTDOWNS OF BUILDING SYSTEMS SHALL BE MINIMIZED TOFOUR (4) HOURS.
I. COORDINATE USE OF THE BUILDING ELEVATORS AND MATERIAL DELIVERIESWITH THE OWNER.
J. ANY PENETRATIONS MADE THROUGH EXTERIOR WALLS ARE TO BE SEALEDWEATHER TIGHT AND REPAIRED TO MATCH EXISTING SURFACES.
K. MAINTAIN ALL MANUFACTURER RECOMMENDED SERVICE CLEARANCES,INCLUDING BOTH NEW AND EXISTING EQUIPMENT.
L. THE CONTRACTOR SHALL PROVIDE MANUFACTURER'S INSTALLATIONINSTRUCTION TO BE AVAILABLE ON THE JOB SITE AT THE TIME OF INSPECTIONFOR EVERY APPLIANCE, APPURTENANCE, OR PIECE OF MECHANICALEQUIPMENT. IF SITE-FABRICATED EQUIPMENT IS TO BE A PART OF ANY SYSTEM,THE INSTALLATION INSTRUCTION SHALL BE AVAILABLE FOR EACH COMPONENT.LISTING AND LABELING FOR EQUIPMENT INSTALLED OUTDOORS SHALL ALSO BEAVAILABLE.
M. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
GENERAL MECHANICAL NEW WORK NOTES
A. ALL WORK SHALL BE IN ACCORDANCE WITH THE CITY OF CHICAGO BUILDINGCODE REQUIREMENTS.
B. ALL EQUIPMENT FURNISHED AND INSTALLED SHALL BE IN FULL COMPLIANCE WITHTHE CURRENT STANDARDS SET BY THE CITY OF CHICAGO DEPARTMENT OFINSPECTIONAL SERVICES.
C. ALL NEW DUCTWORK INSTALLED SHALL BE OF GALVANIZED METAL. ALL SHEETMETAL INSTALLATION SHALL COMPLY WITH THE LATEST STANDARDS OF SMACNAAND ASHRAE.
D. ALL DUCT JOINTS, SEAMS, AND CONNECTIONS SHALL BE SEALED IN ACCORDANCEWITH THE CHICAGO ENERGY CONSERVATION CODE.
E. ALL NEW EQUIPMENT PROVIDED SHALL BE U.L. LISTED AND SHALL BEAR THE U.L.LABEL.
F. ALL OUTSIDE AIR INTAKES SHALL BE A MINIMUM DISTANCE OF 15'-0" FROM ANYEXHAUST LOUVERS, PLUMBING VENTS, OR ANY OTHER POSSIBLE CONTAMINANTSAND SHALL BE A MINIMUM DISTANCE OF 10'-0" ABOVE GRADE.
G. IF FLEXIBLE DUCTS ARE USED, DO NOT EXCEED 5'-0' IN LENGTH. ALL FLEXIBLEDUCTWORK TO BE CITY OF CHICAGO APPROVED.
H. NOISE FROM ALL MECHANICAL EQUIPMENT INSTALLED SHALL NOT EXCEED 55 DBAT THE PROPERTY LINE.
I. CLEARANCES FOR ALL VENTILATION EQUIPMENT MUST CONFORM TOMANUFACTURER'S REQUIREMENTS.
CITY OF CHICAGO NOTES
GUARANTEED RATE FIELD
HVAC / AHU RENOVATION PHASE VIII
333 W. 35TH STREET
CHICAGO, ILLINOIS 60616
SCOPE OF WORK
10/26/2018
062-056281
Address:
Fully comply with the requirements of Chapter 18-13. Energy Conservation of theMunicipal Code of Chicago as effective April 22, 2009
Signed: Date:(Arch. S.E. or P.E.)
Illinois License Number:
I certify that I am a Registered Energy Professional (REP). I also certify that tothe best of my professional knowledge and belief that the plans for
ENERGY CODE COMPLIANCE STATEMENT
I hereby certify that these plans were prepared under my direct supervision andto the best of my professional knowledge they conform to the Chicago BuildingCode.
Signed: Date:(Arch. S.E. or P.E.)
CHICAGO BUILDING CODE COMPLIANCE STATEMENT
I hereby certify that the heating system will heat all rooms regularly occupied byhumans to an inside temperature of 68° when the outside temperature is minus10°F (As required by the Sections 34 (13-196-410) and 4 (5-4-270) of the 2010Chicago Building Code and by Paragraph 1204.1 of Chapter 18-12 (InteriorEnvironment) of the proposed Building Planning and Life Safety portion of theCode).
Signed:(Owner, Contractor, or Owner's Licensed Engineer Representative)
HEATING CERTIFICATION STATEMENT
18101
DESCRIPTIONDATEREV.
ISSUE/REVISION:
PROJECT NO:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
SCALE:
SHEET NO.
(708) 236-0330 FAX
Hillside, IL 60162
(708) 236-0300
30 N. Wolf Rd., Second Floor
PROJECT:
DRAWING TITLE:
333 WEST 35TH STREETCHICAGO, IL 60616
GUARANTEED RATE FIELD -HVAC / AHU RENOVATION -PHASE VIII
10.26.2018 ISSUED FOR BID
11.14.2018 ISSUED FOR ADDENDUM 1
333 W. 35TH ST, CHICAGO, IL 60616
Sheet List TableSheet Number Sheet Title
M0.01 MECHANICAL NOTES, SYMBOLS, AND ABBREVIATIONS
M0.02 SERVICE LEVEL OVERALL PLAN
M0.03 100 LEVEL OVERALL PLAN
M0.04 300 LEVEL OVERALL PLAN
M0.05 400 LEVEL OVERALL PLAN
M0.06 500 LEVEL OVERALL PLAN
M1.01 SERVICE LEVEL AND 100 LEVEL ENLARGED PLANS
M1.02 300 LEVEL AND 500 LEVEL ENLARGED PLANS
M1.03 400 LEVEL SECTION 04 ENLARGED PLANS
M1.04 400 LEVEL SECTION 05 ENLARGED PLANS
M1.05 400 LEVEL SECTION 09 ENLARGED PLANS
M2.01 MECHANICAL DETAILS
M3.01 MECHANICAL SCHEDULES
M4.01 MECHANICAL SPECIFICATIONS
M4.02 MECHANICAL SPECIFICATIONS
10/26/2018
REFER TO ENTIRE SET OF DOCUMENTS, PLANS, AND SPECIFICATIONS FORCOMPLETE PROJECT SCOPE. REFER TO BID DOCUMENTS FOR BID PACKAGES.
SERVICE LEVEL AHU MOTOR REPLACEMENTREPLACE AHU MOTOR AS DEFINED ON SHEET M0.02.
SERVICE LEVEL RETAIL AREA EQUIPMENT REPLACEMENTREPLACE EXISTING SPLIT SYSTEM AND CONDENSING UNIT AS DEFINED ON SHEETM1.01.
100 LEVEL ORGAN BOOTH EQUIPMENT REPLACEMENTREPLACE EXISTING EQUIPMENT AND ACCESSORIES AS DEFINED ON SHEET M1.01.
100 LEVEL MERCHANDISE HAT STORE EQUIPMENT REPLACEMENTREPLACE EXISTING EQUIPMENT AND ACCESSORIES AS DEFINED ON SHEET M1.01.
100 LEVEL CLUB ELEVATOR LOBBY EQUIPMENT REPLACEMENTREPLACE EXISTING EQUIPMENT AND ACCESSORIES AS DEFINED ON SHEET M1.01.
300 LEVEL BROADCAST ROOM NEW EQUIPMENTPROVIDE NEW EQUIPMENT AND ACCESSORIES AS DEFINED ON SHEET M1.02.
400 LEVEL MISCELLANEOUS EQUIPMENT REPLACEMENTREPLACE EXISTING EQUIPMENT AND ACCESSORIES AS DEFINED ON SHEETS M1.03,M1.04, & M1.05.
500 LEVEL ELEVATOR LOBBY EQUIPMENT REPLACEMENTREPLACE EXISTING EQUIPMENT AND ACCESSORIES AS DEFINED ON SHEET M1.02.
500 LEVEL ELEVATOR MACHINE ROOM EQUIPMENT REPLACEMENTREPLACE EXISTING EQUIPMENT AND ACCESSORIES AS DEFINED ON SHEET M1.02.
MISCELLANEOUS FIRE CAULKINGPROVIDE FIRE CAULKING IN MISCELLANEOUS MECHANICAL AND ELECTRICALROOMS, AS DEFINED ON SHEETS M0.04 AND M0.05.
VALVE TAGGING STANDARDAS PART OF THIS PROJECT, A VALVE TAGGING STANDARD SHALL BE IMPLEMENTEDFOR ALL WORK MOVING FORWARD. REFER TO DETAILS AND SPECIFICATIONS.
SIEMENS SHALL INCLUDE A MINIMUM OF 40 HOURS OF TIME TO MANIPULATE THECONTROLS SEQUENCE OF THE AIR HANDLING UNITS ASSOCIATED WITH THE WHITESOX OFFICES.
SIEMENS CONTACT:
CRAIG CRAWFORD, P.E., LEED APSIEMENS INDUSTRY, INC.INFRASTRUCTURE & CITIES SECTORBUILDING TECHNOLOGIES DIVISION585 SLAWIN COURTMT. PROSPECT, IL 60056CELL: (847) 305-0665FAX: (866)[email protected]
01
01
LOT #6
S. PRIN
CETON AVE.
SERVICE LEVELREFER TO SHEET M1.01 FORSCOPE OF WORK IN RETAILOFFICE SPACE.
REPLACE EXISTING SUPPLY FAN MOTOR WITH NEW(EMERSON, 15 HP, 480V, 3PH, 1775 RPM) MOTOR.PROVIDE FULL START UP AND ENSURE PROPERFUNCTIONALITY. ALTERNATE PRICE TO REPLACEBEARINGS ON EXISTING MOTOR. AHU LOCATED ONCATWALK ABOVE CEILING. THIS WORK SHALL OCCUROVER THE WINTER HOLIDAY BREAK, COORDINATEWITH OWNER.
REFER TO REFERENCE PHOTO ON THIS SHEET.
KEY PLANKEY PLAN
N
10
9
8
67
111
3
5
4
2
18101
DESCRIPTIONDATEREV.
ISSUE/REVISION:
PROJECT NO:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
SCALE:
SHEET NO.
(708) 236-0330 FAX
Hillside, IL 60162
(708) 236-0300
30 N. Wolf Rd., Second Floor
PROJECT:
DRAWING TITLE:
333 WEST 35TH STREETCHICAGO, IL 60616
GUARANTEED RATE FIELD -HVAC / AHU RENOVATION -PHASE VIII
10.26.2018 ISSUED FOR BID
11.14.2018 ISSUED FOR ADDENDUM 1
M0.02
SERVICE LEVEL OVERALLPLAN
1/32" = 1'-0"
AS
AS
MS
SCALE:
SERVICE LEVEL OVERALL PLAN - MECHANICAL WORK
1 1/32" = 1'-0"
0 16' 32' 64'32'
SCALE: 1/32" = 1'-0"
01
REFERENCE PHOTO OF EXISTING MOTOR TO BE REPLACED ABOVE OFFICES.
01
01
AHU1
ELECTRIC DUCT HEATERTO REMAIN.
EXISTING EXHAUST FAN AND ASSOCIATED DUCTWORK TOREMAIN WITHOUT MODIFICATION. PROTECT DURINGCONSTRUCTION. SIEMENS TO CONTROL EXISTING EXHAUSTFAN WITH ECONOMIZER MODE IN NEW SEQUENCE.
EXHAUSTDISCHARGE
OA INTAKE
DISCONNECT AND REPLACE EXISTING CONDENSINGUNIT SERVING ASSOCIATED RETAIL SPACE. REPLACE
EXISTING REFRIGERANT PIPING (NOT SHOWN).REFRIGERANT PIPING SIZED PER MANUFACTURER
REQUIREMENTS. ENSURE ALL EXTERIOR WALLPENETRATIONS ARE SEALED WEATHER TIGHT.
DISCONNECT AND REPLACE EXISTING SPLIT SYSTEMSERVING ASSOCIATED RETAIL SPACE. REPLACE
EXISTING RETURN PLENUM AND SUPPLY DISCHARGEFITTING AS REQUIRED TO FIT NEW UNIT. SIEMENS TO
CONTROL NEW UNIT IN NEW SEQUENCE.
M
M
PROVIDE NEW OA DAMPER, CONFIRM DUCTSIZE PRIOR TO SUBMITTALS. SIEMENS TOCONTROL NEW DAMPER IN NEW SEQUENCE.
PROVIDE NEW RA DAMPER, CONFIRM DUCTSIZE PRIOR TO SUBMITTALS. SIEMENS TOCONTROL NEW DAMPER IN NEW SEQUENCE.
20x20
24x1824x18
DISCONNECT AND REMOVE POWER CONNECTIONFROM EXISTING FAN COIL UNIT. EXISTING WIRES
AND CONDUIT SHALL REMAIN. DISCONNECT,REMOVE, AND RE-INSTALL EXISTING LOCAL
DISCONNECT SWITCH TO NEW FAN COIL UNIT.EXTEND CONDUIT AND WIRES AS REQUIRED TO
RECONNECT EXISTING BRANCH CIRCUITS TO NEWFAN COIL UNIT.
CU1
ACD6
ACD7
3000CFM
FCU2
400CFM
DISCONNECT AND REPLACE EXISTING FAN COIL UNIT.MODIFY AND TRANSITION DUCTWORK CONNECTIONAS REQUIRED TO RE-USE EXISTING DUCTWORK.REMOVE AND REPLACE ALL CHILLED WATER PIPINGBACK TO EXISTING ISOLATION VALVE. REFER TODETAILS AND SCHEDULES FOR ADDITIONALINFORMATION. REFER TO DETAIL 2 ON SHEET M1.03FOR SIMILAR NOTES AND REQUIREMENTS.
EXISTING OUTDOOR AIR SERVING FAN COILUNIT TO BE DISCONNECTED AND CAPPED.
SIEMENS TO TAKE CONTROL OF EXISTINGBASEBOARD HEAT IN ORGAN BOOTH.
T
x3
DISCONNECT AND REMOVE POWER CONNECTION FROMEXISTING FAN COIL UNIT. EXISTING WIRES AND CONDUITSHALL REMAIN. DISCONNECT, REMOVE, AND RE-INSTALL
EXISTING LOCAL DISCONNECT SWITCH TO NEW FAN COILUNIT. EXTEND CONDUIT AND WIRES AS REQUIRED TO
RECONNECT EXISTING BRANCH CIRCUITS TO NEW FANCOIL UNIT.
DISCONNECT AND REPLACE EXISTING FCU. SIEMENS TOCONTROL NEW FCU. MODIFY AND TRANSITION DUCTWORKCONNECTION AS REQUIRED TO RE-USE EXISTINGDUCTWORK. REMOVE AND REPLACE ALL CHILLED WATERPIPING BACK TO EXISTING ISOLATION VALVE. REFER TODETAILS AND SCHEDULES FOR ADDITIONAL INFORMATION.REFER TO DETAIL 2 ON SHEET M1.03 FOR SIMILAR NOTESAND REQUIREMENTS.
EXISTING EXHAUST FAN TO REMAIN.EXISTING CONTROLS OF EXHAUST FAN AND
ALL ASSOCIATED DAMPERS TO REMAIN.
EF
FCU3
600CFM
18x1
2
10"∅
10"∅
14x8
14x8
M
EXISTING 14x14 OA DUCT
16x10
M
12x10 EXH DUCT
12x1
0
12x10
M
EXISTING 12x12 RA GRILLE
14x1
2
EXISTING 12x12 EXH GRILLE
EXISTING TRANSFER GRILLE
ELECTRIC DUCT HEATER TO REMAIN.
DISCONNECT AND REMOVE POWER CONNECTION FROMEXISTING FAN COIL UNIT. EXISTING WIRES AND CONDUIT SHALL
REMAIN. DISCONNECT, REMOVE, AND RE-INSTALL EXISTINGLOCAL DISCONNECT SWITCH TO NEW FAN COIL UNIT. EXTENDCONDUIT AND WIRES AS REQUIRED TO RECONNECT EXISTING
BRANCH CIRCUITS TO NEW FAN COIL UNIT.
VERIFY LOCATION OF EXISTINGTHERMOSTAT SERVING THIS SPACE,REPLACE WITH NEW SIEMENSTHERMOSTAT IN SAME LOCATION.
FCU5
1200CFM
REPLACE EXISTING SUPPLY AND RETURNLINEAR SLOTS. CONTRACTOR TO VERIFYEXACT DIMENSIONS OF GRILLES PRIOR TOSUBMITTAL BE SUBMITTED.
DISCONNECT AND REPLACE EXISTING FAN COIL UNIT.MODIFY AND TRANSITION DUCTWORK CONNECTIONAS REQUIRED TO RE-USE EXISTING DUCTWORK.REMOVE AND REPLACE ALL CHILLED WATER PIPINGBACK TO EXISTING ISOLATION VALVE. REFER TODETAILS AND SCHEDULES FOR ADDITIONALINFORMATION. REFER TO DETAIL 2 ON SHEET M1.03FOR SIMILAR NOTES AND REQUIREMENTS.
DEMOLISH AND RESTORE CURVED VAULTED CEILINGAS NEEDED TO REPLACE FAN COIL UNIT. RESTORETO FINISH PAINT.
ELECTRIC DUCT HEATER TO REMAIN.
10"∅
10"∅
24x1
2
10"∅
10"∅18x1
0
T
DISCONNECT AND REMOVE POWER CONNECTION FROMEXISTING FAN COIL UNIT. EXISTING WIRES AND CONDUIT SHALL
REMAIN. DISCONNECT, REMOVE, AND RE-INSTALL EXISTINGLOCAL DISCONNECT SWITCH TO NEW FAN COIL UNIT. EXTENDCONDUIT AND WIRES AS REQUIRED TO RECONNECT EXISTING
BRANCH CIRCUITS TO NEW FAN COIL UNIT.
REPLACE EXISTING THERMOSTATWITH NEW SIEMENS THERMOSTAT
KEY PLANKEY PLAN
N
10
9
8
67
111
3
5
4
2
18101
DESCRIPTIONDATEREV.
ISSUE/REVISION:
PROJECT NO:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
SCALE:
SHEET NO.
(708) 236-0330 FAX
Hillside, IL 60162
(708) 236-0300
30 N. Wolf Rd., Second Floor
PROJECT:
DRAWING TITLE:
333 WEST 35TH STREETCHICAGO, IL 60616
GUARANTEED RATE FIELD -HVAC / AHU RENOVATION -PHASE VIII
10.26.2018 ISSUED FOR BID
11.14.2018 ISSUED FOR ADDENDUM 1
SCALE:
SERVICE LEVEL (SECTION 10) - PARTIAL MECHANICAL PLAN
1 1/8" = 1'-0"
0 4' 8' 16'8'
SCALE: 1/8" = 1'-0"
SCALE:
100 LEVEL (SECTION 06) - PARTIAL MECHANICAL PLAN
2 1/4" = 1'-0"
0 2' 4' 84'
SCALE: 1/4" = 1'-0"
SCALE:
100 LEVEL (SECTION 10) - PARTIAL MECHANICAL PLAN
3 1/4" = 1'-0"
0 2' 4' 84'
SCALE: 1/4" = 1'-0"
SCALE:
100 LEVEL (SECTION 04) - PARTIAL MECHANICAL PLAN
4 1/4" = 1'-0"
0 2' 4' 84'
SCALE: 1/4" = 1'-0"
M1.01
SERVICE LEVEL AND 100LEVEL ENLARGED PLANS
VARIES
AS
AS
MS
01
01
01
01
FCU1
300CFM
CONDCHWSCHWR
RELOCATE EXISTING DUCTWORK, CONDUIT, ANDFIRE PROTECTION AS NECESSARY TOACCOMMODATE NEW FAN COIL UNITINSTALLATION (NOT SHOWN).
FURNISH AND INSTALL NEW LITTLE GIANTCONDENSATE PUMP, MODEL VCL-45ULS
T
6x6
NEW FAN COIL UNIT. ROUTE ALL NEW 1" CHILLED WATERAND 1" CONDENSATE PIPING BACK TO EXISTING MAINS IN
CORRIDOR. INTEGRATE FCU INTO SIEMENS CONTROLSYSTEM. REFER TO DETAILS AND SCHEDULES FORADDITIONAL INFORMATION. REFER TO DETAIL 2 ON
SHEET M1.03 FOR SIMILAR NOTES AND REQUIREMENTS.
PROVIDE NEW POWER FEED FROM NEARESTCIRCUIT FEEDING EXISTING FAN COIL UNITS.
PROVIDE NEW DISCONNECT AT NEW FCU.
NEW SIEMENS THERMOSTAT
FCU4
1000CFM
M
MM
FURNISH AND INSTALL NEW RETURN, OA, AND RELIEFAIR DAMPERS WITH NEW ACTUATORS. PROVIDE
SEQUENCE WHICH INCLUDES ECONOMIZER. MAINTAINROOM TEMPERATURE NO HIGHER THAN 80°F (ADJ.)
ACD3
ACD4
ACD5
IN ELEVATOR MACHINE ROOM ABOVE LOBBY,DISCONNECT AND REPLACE EXISTING FAN COIL UNIT.
MODIFY AND TRANSITION DUCTWORK CONNECTION ASREQUIRED TO RE-USE EXISTING DUCTWORK. REMOVE
AND REPLACE ALL CHILLED WATER PIPING BACK TOEXISTING ISOLATION VALVE. REFER TO DETAILS AND
SCHEDULES FOR ADDITIONAL INFORMATION. REFER TODETAIL 2 ON SHEET M1.03 FOR SIMILAR NOTES AND
REQUIREMENTS.
OA
RA
DISCONNECT AND REMOVE POWER CONNECTION FROMEXISTING FAN COIL UNIT. EXISTING WIRES AND CONDUITSHALL REMAIN. DISCONNECT, REMOVE, AND RE-INSTALL
EXISTING LOCAL DISCONNECT SWITCH TO NEW FAN COILUNIT. EXTEND CONDUIT AND WIRES AS REQUIRED TO
RECONNECT EXISTING BRANCH CIRCUITS TO NEW FANCOIL UNIT.
T
REPLACE EXISTING THERMOSTATWITH NEW SIEMENS THERMOSTAT
24x12
18x1
218
x12
REFER TO VIEW 4 ON THIS SHEET FORREFERENCE PHOTOS OF MACHINE ROOM
FCU3
600CFM
T
REPLACE EXISTING THERMOSTATWITH NEW SIEMENS THERMOSTAT
DISCONNECT AND REPLACE EXISTING FAN COIL UNIT.MODIFY AND TRANSITION DUCTWORK CONNECTION ASREQUIRED TO RE-USE EXISTING DUCTWORK. REMOVEAND REPLACE ALL CHILLED WATER PIPING BACK TOEXISTING ISOLATION VALVE. REFER TO DETAILS ANDSCHEDULES FOR ADDITIONAL INFORMATION. REFER TODETAIL 2 ON SHEET M1.03 FOR SIMILAR NOTES ANDREQUIREMENTS.
EXISTING ELECTRIC DUCT HEATER TO REMAIN.
16x1
0
DISCONNECT AND REMOVE POWER CONNECTION FROMEXISTING FAN COIL UNIT. EXISTING WIRES AND CONDUITSHALL REMAIN. DISCONNECT, REMOVE, AND RE-INSTALL
EXISTING LOCAL DISCONNECT SWITCH TO NEW FAN COILUNIT. EXTEND CONDUIT AND WIRES AS REQUIRED TO
RECONNECT EXISTING BRANCH CIRCUITS TO NEW FANCOIL UNIT.
KEY PLANKEY PLAN
N
10
9
8
67
111
3
5
4
2
18101
DESCRIPTIONDATEREV.
ISSUE/REVISION:
PROJECT NO:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
SCALE:
SHEET NO.
(708) 236-0330 FAX
Hillside, IL 60162
(708) 236-0300
30 N. Wolf Rd., Second Floor
PROJECT:
DRAWING TITLE:
333 WEST 35TH STREETCHICAGO, IL 60616
GUARANTEED RATE FIELD -HVAC / AHU RENOVATION -PHASE VIII
10.26.2018 ISSUED FOR BID
11.14.2018 ISSUED FOR ADDENDUM 1
SCALE:
300 LEVEL (SECTION 06) - PARTIAL MECHANICAL PLAN
2 1/4" = 1'-0"
0 2' 4' 84'
SCALE: 1/4" = 1'-0"
SCALE:
ELEVATOR MACHINE RM (SECTION 04) - PARTIAL MECHANICAL PLAN
3 1/4" = 1'-0"
0 2' 4' 84'
SCALE: 1/4" = 1'-0"
SCALE:
500 LEVEL (SECTION 06) - PARTIAL MECHANICAL PLAN
1 1/4" = 1'-0"
0 2' 4' 84'
SCALE: 1/4" = 1'-0" M1.02
300 LEVEL AND 500 LEVELENLARGED PLANS
VARIES
AS
AS
MS
01
01
01
01
SCALE:
ELEVATOR MACHINE RM (SECTION 04) - EXISTING CONDITIONS REFERENCE PHOTOGRAPHS
4 N.T.S.
01
01
FAN COIL SCHEDULE - (2-PIPE CHILLED WATER) (FCU)
TAG
GENERAL DATA DIMENSIONAL DATA (INCHES) UNIT DATA COOLING DATA ELECTRICAL DATA
NOTESSERVICE LOCATION MFR MODEL ORIENTATION
APPROX.WEIGHT
(LBS)L W H FAN
SPEED
NOMINALAIRFLOW
(CFM)
WATERFLOW(GPM)
ESP(IN. WG)
WATERPRESSURE
DROP(FT. HD.)
COILROWS
MIN. COILWORKING
PRESSURE(PSIG)
E.A.T.DB(°F)
E.A.T.WB(°F)
L.A.T.DB(°F)
L.A.T.WB(°F)
E.W.T.(°F)
TOTALCAP.
(MBH)
SENS.CAP.
(MBH)FLA VOLTS HZ PHASE
BROADCASTROOM CORRIDOR CARRIER 42CAA03BLFY6YYAR HORIZONTAL
DUCTED 39 17.5 25.25 8.75 HIGH 300 1.4 0.4 8.6 4 175.0 75.0 67.0 54.7 54.1 44.0 6.3 3.5 0.35 277 60 1 SEEBELOW
ORGANBOOTH
ORGANBOOTH CARRIER 42CAA04BLFY6YYAR HORIZONTAL
DUCTED 49 17.5 31.25 8.75 HIGH 400 2.6 0.4 35.1 4 175.0 75.0 67.0 55.7 55.0 44.0 12.1 6.8 0.69 277 60 1 SEEBELOW
HAT MERCH /ELEV. LOBBY
HAT MERCH /ELEV. LOBBY CARRIER 42DAA06BLFY6YYAR HORIZONTAL
DUCTED 64 27.5 23.0 16.4 HIGH 600 2.9 0.5 1.07 4 175.0 75.0 67.0 61.6 60.5 44.0 13.5 9.3 1.35 277 60 1 SEEBELOW
ELEVATORPENT. 500
ELEVATORPENT. 500 CARRIER 42DAA10BLFY6YYAR HORIZONTAL
DUCTED 90 27.5 32.0 16.4 HIGH 1000 5.3 0.5 4.23 4 175.0 75.0 67.0 59.4 58.4 44.0 24.4 15.1 1.85 277 60 1 SEEBELOW
ELEVATORLOBBY 100
ELEVATORLOBBY 100 CARRIER 42DAA12BLFY6YYAR HORIZONTAL
DUCTED 108 27.5 37.0 16.38 HIGH 1200 7.6 0.5 10.35 4 175.0 75.0 67.0 59.3 58.2 44.0 34.6 21.3 2.7 277 60 1 SEEBELOW
GENERAL SUITES &CONF. CARRIER 42DAA16BLFY6YYAR HORIZONTAL
DUCTED 124 27.5 47.0 16.4 HIGH 1600 10.9 0.5 7.84 4 175.0 75.0 67.0 60.3 59.1 44.0 50.1 31.8 3.7 277 60 1 SEEBELOW
NOTES:
2. CAPACITIES INDICATED AT HIGH SPEED.
3. COIL CONNECTION HAND TO BE DETERMINED BY MECHANICAL CONTRACTOR.
4. ALL EXISTING ELECTRIC DUCT HEATING COILS TO REMAIN AND BE RE-USED.
5. COORDINATE CONTROLS WITH BUILDING TEMPERATURE CONTROLS CONTRACTOR FOR THERMOSTATS, CONTROL VALVES, INTERCONNECTION OF FAN COIL AND ELECTRIC HEATING COIL.
6. FABRICATE RETURN AIR REAR PLENUM AS REQUIRED FOR SEALED HOUSING AROUND FANS.
7. INCLUDE 1" THROWAWAY FILTERS.
8. ALL UNITS SHALL BE SIZED FOR 30% ETHYLENE GLYCOL CONCENTRATION IN CHILLED WATER.
9. NON FUSED DISCONNECT.
10. NO ALTERNATE MANUFACTURERS PERMITTED. UNIT TO BE SOLE-SOURCED TO MATCH EXISTING UNITS AND SYSTEM ALREADY IN FACILITY.
FCU1
FCU2
FCU3
FCU4
FCU5
FCU6
GRILLES, REGISTERS, AND DIFFUSER SCHEDULE
TAG MFR MODEL TYPE SERVICE MODULE SIZE MATERIAL BORDERTYPE MAXIMUM NC NOTES
A PRICE 530FF RETURN AIR FILTERGRILLE RETURN 24x24 STEEL LAY-IN 30 SEE BELOW
B TITUS OMNI SQ. PLAQUE SUPPLY VARIES STEEL LAY-IN 30 SEE BELOW
C TITUS FLOWBAR FLOWBAR SUPPLY (4) 1" SLOTS, 8'-0" LENGTH STEEL DRYWALL 30 SEE BELOW
D TITUS FLOWBAR FLOWBAR RETURN (5) 1" SLOTS, 8'-0" LENGTH STEEL DRYWALL 30 SEE BELOW
NOTES:
1. ALL GRILLES, REGISTERS, AND DIFFUSERS TO BE COLOR #35 WHITE.
2. PROVIDE OPPOSED BLADE DAMPER.
3. PROVIDE (1) ADDITIONAL FILTER FOR OWNERS STOCK FOR EVERY TYPE A FILTER GRILLE.
4. ADDITIONAL ACCEPTABLE MANUFACTURERS INCLUDE TITUS, NAILOR, KRUEGER.
MECHANICAL / ELECTRICAL COORDINATION SCHEDULE
NOTES:
1. DEVICES TO BE FURNISHED BY THE ELECTRICAL CONTRACTOR (MARKED 'EC'), OR THE MECHANICAL CONTRACTOR (MARKED 'MC'), THE BUILDING AUTOMATION SYSTEM CONTRACTOR (MARKED 'BASC'), OR THE MANUFACTURER (MARKED 'MFR')
2. ALL CONDUIT AND WIRING FOR TEMPERATURE CONTROL AND EQUIPMENT INTERLOCK SHALL BE BY MECHANICAL CONTRACTOR. OTHER CONTROLS AND CONTROL CONDUIT/WIRING BY TRADE FURNISHING RESPECTIVE EQUIPMENT.
3. IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO COORDINATE AND REVIEW THE ELECTRICAL CHARACTERISTICS, AMPACITY, AND OTHER REQUIREMENTS OF COMPONENTS BEFORE INSTALLATION OF WORK. ALL OTHER CONTRACTORS SHALLADVISE ELECTRICAL CONTRACTOR OF ANY MOTOR/DEVICE CHANGES.
4. ALL LOOSE STARTERS SHALL INCLUDE HOA SWITCH, PILOT LIGHT MOUNTED IN COVER, CONTROL TRANSFORMER, AND ONE N.O. AND ONE N.C. AUXILIARY CONTACTS.
5. SEE SPECIFICATIONS AND DRAWINGS FOR TYPES AND LOCATIONS OF DEVICES SCHEDULED BELOW.
6. VERIFY FINAL LOADS AND REQUIREMENTS OF ALL EQUIPMENT WITH FINAL MECHANICAL AND ELECTRICAL DRAWINGS.
EQUIP.TAG EQUIPMENT DESCRIPTION
UNIT MOUNTED DEVICES REMOTE OR LOOSE DEVICES ELECTRICAL
REMARKSVFD STARTER DISCONNECT OVERCURRENT
PROTECTION
SINGLEPOINT
CONNECTIONVFD STARTER DISCONNECT OVERCURRENT
PROTECTION VOLTS HZ PHASE
FAN COIL UNIT - - - - YES - - EC EC VARIES 60 VARIESEXISTING DISCONNECT SWITCHMAY BE RE-USED FOR FCU-1 TYPE.
CONDENSING UNIT - - - - YES - - EC EC
FCU
CU
AUTOMATIC CONTROL DAMPER SCHEDULE (ACD)
TAG SERVICE LOCATION MANUF. MODELSIZE (WIDTHX HEIGHT) BLADE STYLE DAMPER FAIL
POSITION NOTES
CONF. ROOM FCUOUTDOOR AIR
PRESS BOX462L RUSKIN CDTI-50 6x8 OPPOSED CLOSED SEE BELOW
SUPPLY AIR ISFA OFFICESINTERNAL ZONE RUSKIN CD-50 12"∅ OPEN SEE BELOW
OUTDOOR AIR ELEVATORMACHINE ROOM RUSKIN CD-50 18X12 OPPOSED CLOSED SEE BELOW
RETURN AIR ELEVATORMACHINE ROOM RUSKIN CD-50 18X12 OPPOSED OPEN SEE BELOW
RELIEF ELEVATORMACHINE ROOM RUSKIN CD-50 24X12 OPPOSED CLOSED SEE BELOW
OUTDOOR AIR SERVICE LEVELGATE 6 RUSKIN CD-50 24X18 OPPOSED CLOSED SEE BELOW
RETURN AIR SERVICE LEVELGATE 6 RUSKIN CD-50 24X18 OPPOSED OPEN SEE BELOW
NOTES:
1. DAMPER SHALL BE FURNISHED BY MC. ACTUATOR WITH FAIL POSITION INDICATED IN SCHEDULE SHALL BE FURNISHED BY BASC.
2. VERIFY EXACT SIZES ON SITE.
ACD1
ACD2
ACD3
ACD4
ACD5
ACD6
ACD7
WALL LOUVER SCHEDULE (WL)
TAG SERVICE LOCATION MFR MODEL SIZE (WIDTHX HEIGHT)
AIRFLOW(CFM)
FREE AREA(S.F.)
MAX. FACEVELOCITY
(FPM)NOTES
ROOMVENTILATION
PRESS BOX462L RUSKIN ELF375X 12x12 150 0.26 600 SEE BELOW
NOTES:
1. PROVIDE BIRDSCREEN.
2. ANODIZED COLOR AND FINISH TO BE SELECTED BY OWNER.
3. EXTRUDED ALUMINUM CONSTRUCTION, VERIFY EXISTING WALL THICKNESS.
4. PROVIDE WITH FLANGED FRAME.
5. NEW OPENING IN EXISTING WALL, CUT AND PATCH WALL AS REQUIRED TO INSTALL. PROVIDE NEW LINTEL AS REQUIRED.
WL1
C O N D E N S I N G U N I T S C H E D U L E ( C U )
TAG
GENERAL DATA DIMENSIONAL DATA (INCHES) PERFORMANCE DATA ELECTRICAL DATA
NOTESSERVICE LOCATION MFR MODEL
SHIPPINGWEIGHT
(LBS)
OPERATINGWEIGHT
(LBS)L W H # OF
CIRCUITSCOMP.TYPE
TOTALCAPACITY
(MBH)
SENSIBLECAPACITY
(MBH)EER REFRIG.
TYPE EAT (°F) MCA MOCP VOLTS HZ PHASE
SERVICE LEVELGATE 6 EXTERIOR AT GRADE CARRIER 38AUZ 391 391 59.4 45.9 42.4 1 SCROLL 95.3 73.0 11.2 PURON 95 18 25 460 60 3 SEE BELOW
NOTES:
1. REFRIGERANT LIQUID AND SUCTION PIPING TO MATCH CONNECTION SIZE OF CONDENSING UNIT.
2. UL LISTED.
3. ADDITIONAL ACCEPTABLE MANUFACTURERS INCLUDE CARRIER, YORK, DAIKIN.
CU1
I N D O O R A I R H A N D L I N G U N I T S C H E D U L E ( A H U )
TAG
GENERAL DATA DIMENSIONAL DATA (INCHES) SUPPLY FAN DATA COOLING DATA FILTER DATA ELECTRICAL DATA
NOTESSERVICE LOCATION MFR MODEL SYSTEM
TYPE
SHIPPINGWEIGHT
(LBS)
OPERATINGWEIGHT
(LBS)L W H AIR FLOW
(CFM)
ESP(IN.WG)
EER FANQTY.
FANHP
FANBHP
FANRPM
E.A.T.DB(°F)
E.A.T.WB(°F)
L.A.T.DB(°F)
L.A.T.WB(°F)
TOTALCAP.
(MBH)
SENS.CAP.
(MBH)THICK-NESS TYPE MERV MCA MOCP VOLTS HZ PHASE
SERVICE LEVELGATE 6 SERVICE CORRIDOR CARRIER 40RUA SPLIT
SYSTEM 404 404 49.0 28.2 56.1 3000 1.0 11.2 1 1.56 898 80 67 57.5 57.0 95.3 73.0 5 15 460 60 3 SEEBELOW
NOTES:
1. ONE YEAR WARRANTY.
2. 2 SPEED FAN CONTROLLER AND VFD DISPLAY KIT.
3. ECONOMIZER - TEMPERATURE DRY BULB CONTROLLED - ULTRA LOW LEAK.
4. OVERHEAD SUSPENSION BRACKETS.
5. CONDENSATE OVERFLOW SWITCH ASSEMBLY.
6. STD STATIC, STD EFFY MOTOR / MEDIUM DRIVE
7. FACTORY MOUNTED DISCONNECT SWITCH.
8. BACNET INTERFACE.
9. PROVIDE FACTORY START UP.
10. SINGLE POINT PANEL CONNECTION.
19. UNIT TO BE SOLE SOURCED, NO ADDITIONAL ACCEPTABLE MANUFACTURERS.
AHU1
01
KEY PLANKEY PLAN
N
10
9
8
67
111
3
5
4
2
18101
DESCRIPTIONDATEREV.
ISSUE/REVISION:
PROJECT NO:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
SCALE:
SHEET NO.
(708) 236-0330 FAX
Hillside, IL 60162
(708) 236-0300
30 N. Wolf Rd., Second Floor
PROJECT:
DRAWING TITLE:
333 WEST 35TH STREETCHICAGO, IL 60616
GUARANTEED RATE FIELD -HVAC / AHU RENOVATION -PHASE VIII
10.26.2018 ISSUED FOR BID
11.14.2018 ISSUED FOR ADDENDUM 1
M3.01
MECHANICAL SCHEDULES
AS NOTED
AS
AS
MS