Golder Associates Ltd. 309 Exeter Road, Unit #1 London, Ontario, Canada N6L 1C1 Telephone: (519) 652-0099 Fax: (519) 652-6299
OFFICES ACROSS NORTH AMERICA, SOUTH AMERICA, EUROPE, AFRICA, ASIA AND AUSTRALIA
REPORT ON
Submitted to:
Upper Grand District School Board500 Victoria Road North
Guelph, OntarioN1E 6K2
DISTRIBUTION:
3 Copies - Upper Grand District School Board, Guelph, Ontario2 Copies - Golder Associates Ltd., London, Ontario
June 14, 2007 06-1135-044
ASBESTOS BUILDING MATERIALS SURVEY
WAVERLEY DRIVE PUBLIC SCHOOL140 WAVERLEY DRIVE
GUELPH, ONTARIOSFIS NO. 2434
Golder Associates Ltd. 309 Exeter Road, Unit #1 London, Ontario, Canada N6L 1C1 Telephone: (519) 652-0099 Fax: (519) 652-6299
OFFICES ACROSS NORTH AMERICA, SOUTH AMERICA, EUROPE, AFRICA, ASIA AND AUSTRALIA
June 14, 2007 06-1135-044
Upper Grand District School Board500 Victoria Road NorthGuelph, OntarioN1E 6K2
Attention: Ms. T. DohertyEnvironmental Engineer
RE: ASBESTOS BUILDING MATERIALS SURVEYWAVERLEY DRIVE PUBLIC SCHOOL140 WAVERLEY DRIVEGUELPH, ONTARIOSFIS NO. 2434
Dear Ms. Doherty:
Golder Associates Ltd. is pleased to submit this report providing the results of our asbestossurvey carried out in 2006 at Waverley Drive Public School in Guelph, Ontario.
We trust that this information meets your present requirements. If you have any questions or ifwe can be of additional service in this regard, please contact the undersigned.
Yours truly,
GOLDER ASSOCIATES LTD.
Keith Lesarge, M.Sc.Associate; Senior Environmental Scientist
SK/ KGL/crn:\active\2006\1135 - environmental\1135-000\06-1135-044 ugdsc - asbestos survey - sw ontario\prime\reports\2434 waverley drive ps\jun 14 07 - 2434 survey report.doc
Upper Grand District School Board June 2007SFIS No. 2434 – Waverley Drive PS - i - 06-1135-044
Golder Associates
EXECUTIVE SUMMARY
At the request of the Upper Grand District School Board (UGDSB), Golder Associates Ltd.(Golder) conducted a survey of Waverley Drive Public School (the Site) located at 140Waverley Drive in Guelph, Ontario, to identify building materials and architectural finishes thatmay contain asbestos. The survey was performed with the objective of compiling an inventory ofasbestos-containing materials (ACMs) and providing recommendations to manage thesematerials in accordance with Ontario Regulation 278/05 Designated Substance - Asbestos onConstruction Projects and in Buildings and Repair Operations (O.Reg 278/05).
Since the purpose of the survey was to identify accessible ACMs that require monitoring as partof an Asbestos Management Plan, it is possible that undiscovered ACMs may be present withininaccessible locations such as wall cavities or above inaccessible ceilings. It is recommended thata more comprehensive and invasive survey be conducted prior to any planned demolition orrenovations that involve entering previously inaccessible areas. If encountered during futurerenovations or demolition, suspect materials should be treated as asbestos-containing until provenotherwise.
Based on the results of the analytical analyses performed of the materials sampled andobservations made at the Site, the following accessible ACMs were identified as present at theSite:
9x9-inch Vinyl floor tile, dark blue with white streaks (Component 102);9x9-inch Vinyl floor tile, light blue with white streaks (Component 103);9x9-inch Vinyl floor tile, white with black streaks (Component 104);Vinyl sheet flooring, taupe (Component 151);Plaster above doors (Component 210);Exterior plaster (Component 310);Ceiling tiles small and large pinholes (Component 368);Parging cement on fittings (Component 500);Unidentified board behind radiators (Component 815); andWall board (Component 824).
More detailed information pertaining to these materials can be found in Table A-2 Summary ofAll Asbestos-Containing Materials, provided in Appendix A of this report.
For each confirmed ACM or assumed ACM identified at the Site, a specific response action wasassigned by Golder. The assigned response action is based on consideration of condition andaccessibility. These actions are based on the likely risk posed by the material with damagedmaterials that are easily accessible posing the greatest risk and good condition materials ininaccessible areas posing the least risk. Response actions range from immediate clean-up ofdebris to ongoing routine inspections of material in good condition. Descriptions of the criteria
Upper Grand District School Board June 2007SFIS No. 2434 – Waverley Drive PS - ii - 06-1135-044
Golder Associates
related to condition, accessibility, and response actions for ACMs are located in Table 3:Condition of Materials, Table 4: Accessibility, Table 5: Response Action Items, and Table 6:Action Matrix Table, all contained in the body of the report.
An abbreviated summary of materials assigned Action Codes 1 through 5 is provided below andshould be read in conjunction with Tables 4, 5, and 6. Items requiring routine inspection only(Action Item 6) have not been included in the abbreviated summary below:
Action Item 3: Remove/repair of ACM in compliance with regulatory requirements:
Approximately 7.5 metres of unidentified board (Component 815) behind radiators inthe continuing education classroom (Location 10).
Action Item 5: Repair ACM found in fair condition, and not likely to be damaged again ordisturbed by normal use of the area or room:
Approximately two parged fittings (Component 500) in Stairwell G.
All ACMs identified require routine inspection as indicated in UGDSB Asbestos ManagementProgram and O.Reg 278/05. Based on the requirements of O.Reg 278/05, Golder alsorecommends the following:
An Asbestos Management Plan must be implemented as per the requirements of Section 7and 8 of O.Reg 278/05 for this Site; andInaccessible areas should be considered to contain asbestos until they can be accessed andproperly assessed.
Additionally, based on the results of the survey, Golder recommends the following be consideredif future renovations are planned:
Should planned renovations involve the removal of the materials identified as asbestos-containing, ensure that all appropriate precautions (as detailed in O.Reg 278/05) are followed;Disturbances to materials listed in this report as presumed ACM should either be sampledprior to disturbance, such as building maintenance activities, renovation or demolition, ortreated as ACM and handled in accordance with the requirements of O.Reg 278/05; andIt is possible that undiscovered ACMs may be present within inaccessible locations such aswall cavities or above inaccessible ceilings. If encountered during future renovations ordemolition, suspect materials should be treated as asbestos-containing until proven otherwise.
Upper Grand District School Board June 2007SFIS No. 2434 – Waverley Drive PS - iii - 06-1135-044
Golder Associates
TABLE OF CONTENTS
SECTION PAGE
EXECUTIVE SUMMARY......................................................................................ITABLE OF CONTENTS .....................................................................................III1.0 INTRODUCTION......................................................................................1
1.1 Scope of Work .......................................................................................11.2 Background Information .........................................................................1
2.0 METHODOLOGY .....................................................................................32.1 General Information ...............................................................................32.2 Asbestos Sampling and Analysis ...........................................................32.3 Sampled and Presumed ACM Materials (PACM) ...................................42.4 Condition of Material ..............................................................................52.5 Accessibility of Material ..........................................................................62.6 Response Actions ..................................................................................72.7 Limitations of Survey..............................................................................82.8 General Recommendations....................................................................9
3.0 FINDINGS ..............................................................................................103.1 General Information .............................................................................103.2 Site Specific ACM Information..............................................................11
4.0 SITE SPECIFIC RECOMMENDATIONS ................................................125.0 LIMITATIONS AND USE OF REPORT...................................................136.0 CLOSURE..............................................................................................14
LIST OF TABLESTable 1 Bulk Material Sampling RequirementsTable 2 Specific Sampling and Assumption CriteriaTable 3 Condition of MaterialsTable 4 AccessibilityTable 5 Response Action ItemsTable 6 Action Matrix TableTable 7 Site-Specific Information
LIST OF FIGURESFigure 1 Sample Location Plan (Main Floor)Figure 2 Sample Location Plan (Main Floor)Figure 3 Sample Location Plan (Second Floor)Figure 4 Asbestos-Containing Material Location Plan (Main Floor)Figure 5 Asbestos-Containing Material Location Plan (Main Floor)Figure 6 Asbestos-Containing Material Location Plan (Second Floor)
Upper Grand District School Board June 2007SFIS No. 2434 – Waverley Drive PS - iv - 06-1135-044
Golder Associates
TABLE OF CONTENTS CONTINUED
LIST OF APPENDICESAppendix A SUMMARY TABLES
List of AbbreviationsTable A-1 Laboratory ResultsTable A-2 Summary of All Asbestos-Containing MaterialsTable A-3 Summary Report by Location (All Components)Table A-4 Summary Report by Location (Confirmed and Presumed ACM)Table A-5 Action Item Summary Report
Appendix B LABORATORY CERTIFICATES OF ANALYSISAppendix C PHOTO LOGS
ACM Photograph LogCeiling Tile Photograph Log
Upper Grand District School Board June 2007SFIS No. 2434 – Waverley Drive PS - 1 - 06-1135-044
Golder Associates
1.0 INTRODUCTION
At the request of the Upper Grand District School Board (UGDSB), Golder Associates Ltd.(Golder) conducted a survey of Waverley Drive Public School (the Site) located at 140Waverley Drive in Guelph, Ontario, to identify building materials and architectural finishes thatmay contain asbestos. The survey was performed with the objective of compiling an inventory ofasbestos-containing materials (ACMs) and providing recommendations to manage thesematerials in accordance with Ontario Regulation 278/05 Designated Substance - Asbestos onConstruction Projects and in Buildings and Repair Operations (O.Reg 278/05).
1.1 Scope of Work
Golder’s scope of work for this project included the following:
A review of available Site information including Site plans and existing surveys as well asinterviews with available personnel familiar with the Site;A Site reconnaissance and walk through (room-by-room) to identify suspect ACMs;Sample collection of suspected ACMs;Analysis of samples using an independent laboratory accredited by the National VoluntaryLaboratory Accreditation Program (NVLAP);Transfer of information to an electronic database; andPreparation and delivery of a report identifying the presence, location and condition of ACMs(friable and non-friable) and, where necessary, recommendations for repair and or removal ofdamaged or deteriorated ACMs.
1.2 Background Information
Asbestos is a generic term applied to a family of fibrous minerals found in metamorphic rocks.There are several different types of asbestos minerals which have been used in a variety ofproducts due to their fire, heat and chemical resistance properties. Because of these properties,and along with its relatively low cost and strong physical strength, asbestos was widely used inmany building and architectural materials, including; spray or trowel-applied fireproofing andacoustical plaster, thermal insulation, packing and gaskets, flooring, roofing, coatings, cementmaterials, architectural decoration and other miscellaneous materials.
In general, asbestos products are divided into two categories based on material strength andcohesion; “friable” and “non-friable” materials. “Friable” materials are defined as materials that,when dry, can be crumbled, pulverized or powdered by hand pressure. This includes materialssuch as sprayed fireproofing, thermal insulation, and acoustical plasters.
Upper Grand District School Board June 2007SFIS No. 2434 – Waverley Drive PS - 2 - 06-1135-044
Golder Associates
“Non-friable” are materials that are generally hard and do not readily release fibres. “Non-friable” building materials include; vinyl floor tiles, mastics, roofing materials and frictionproducts. Non-friable materials may become friable when damaged, or through deterioration.
Due to the long-standing use of asbestos, a substantial amount of information is availableregarding the increased health risk resulting from the occupational exposure to asbestos. Severaldiseases are associated with the inhalation of asbestos fibre: asbestosis, lung cancer andmesothelioma. In reaction to these findings the various authorities have developed regulationspertaining to the control and safe handling of asbestos materials.
Upper Grand District School Board June 2007SFIS No. 2434 – Waverley Drive PS - 3 - 06-1135-044
Golder Associates
2.0 METHODOLOGY
2.1 General Information
For the purposes of this survey, all materials used in the construction of the Site are considered tobe building “components”. Each component, even if not suspected to contain asbestos, isassigned a unique number and is treated as one “homogeneous material” throughout a building.Homogeneous Materials are defined by O.Reg 278/05 as materials that are uniform in colour andtexture. A component number refers to a homogeneous material throughout its full extent, even ifits occurrence is not contiguous or physically connected.
2.2 Asbestos Sampling and Analysis
The survey included a visual assessment of areas accessible at the time of the survey in order todetermine the type and extent of ACMs within the Site, with emphasis on structural, andarchitectural systems.
Bulk samples of each “homogeneous material” or “component” suspected to contain asbestoswere collected and submitted for laboratory analysis under chain-of-custody procedures. Thenumber of samples collected and submitted for analysis of each “homogeneous material” was inaccordance with Table 1 “Bulk Material Samples” of O.Reg 278/05. Sample analysis of each“homogeneous material” was stopped at the first positive result in accordance with O.Reg 278/05.Some samples may be identified by the laboratory to contain multiple phases which requireseparation and individual analysis of each separate phase.
TABLE 1 - BULK MATERIAL SAMPLING REQUIREMENTS
Type of material Size of area of homogeneous material Minimum #of samples
Less than 90 square metres 3
90 or more square metres, but less than 450square metres 5
Surfacing material, including withoutlimitation material that is applied to surfacesby spraying, by troweling or otherwise.Examples include acoustical plaster andfireproofing materials. 450 or more square metres 7
Thermal insulation, except as describedbelow Any size 3
Thermal insulation patch Less than 2 linear metres or 0.5 square metres 1
Other material Any size 3
Sample collection consisted of obtaining a small volume of suspect material, placing it in anindividual labelled plastic bag, and submitting it to an independent laboratory, International
Upper Grand District School Board June 2007SFIS No. 2434 – Waverley Drive PS - 4 - 06-1135-044
Golder Associates
Asbestos Testing Laboratories (IATL) of Mt. Laurel, New Jersey for asbestos content analysis.IATL is accredited under the NVLAP for asbestos bulk sample analysis and adheres to a QA/QCprotocol and program which governs the analysis process.
Samples were assigned a Site Identification Number (SFIS Number), Component (orHomogeneous Material) Number (typically three digits) and Sample Number (between 1 and 7)to indicate how many samples of each homogeneous material, or component, were collected. Forexample, the first sample of a component would be #-1 (e.g. 1111-105-1), the second sample #-2(e.g. 1111-105-2), and so on where 1111 represents the SFIS Number of the Site and 105represents the Component (or Homogenous Material) Number.
Samples were analyzed by IATL for asbestos type and percentage content using Polarized LightMicroscopy (PLM) in accordance with United States Environmental Protection Agency(USEPA) methodology and dispersion staining techniques EPA 600/R-93/116, as is requiredunder O.Reg 278/05. Samples were analyzed to a minimum detection limit of 0.5% to meet therequirements of O.Reg 278/05. Materials reported to contain less than 0.5% asbestos, includingthose referred to as less than the limit of detection (<LOD), are not considered to be asbestos-containing under current regulations in Ontario.
2.3 Sampled and Presumed ACM Materials (PACM)
For the purposes of this assessment, some specific materials (components) have been designatedas “Presumed Asbestos-Containing Materials” (PACM) and have not been sampled. Materialspresumed to contain asbestos may also be referred to as “Assumed” or “Suspect” materials. Allother suspect asbestos-containing materials identified have been designated as requiringsampling. As required by O.Reg 278/05, all PACM shall be treated as ACM until appropriatesampling proves otherwise. All references to ACM in this report shall include PACM unlessspecifically noted otherwise. Specifically designated materials are presented in Table 2.
Upper Grand District School Board June 2007SFIS No. 2434 – Waverley Drive PS - 5 - 06-1135-044
Golder Associates
TABLE 2 - SPECIFIC SAMPLING AND ASSUMPTION CRITERIA
Materials Sampled (if present) Materials Presumed to Contain Asbestos(PACM)
ceiling tilespipe covering paperstexture coatingspipe and other mechanical insulationsprayed fireproofingvinyl floor tilevinyl sheet flooringasbestos cement board (transite)asbestos cement pipecaulking, glazing, and masticswall and ceiling plasterdrywall joint compound
gaskets and packingexpansion jointsflex connectionsfriction materialsconcealed vermiculiteroofing felts and sealerstextileselectrical wiringother suspect materials
In some situations, materials that could affect the integrity of the building envelope, such asroofing materials (felts, mastics, etc.) and window materials (glazing, caulking, etc.) were notsampled where damage to the building envelope was possible and are presumed to containasbestos until proven otherwise.
2.4 Condition of Material
Each suspect ACM identified as part of this assessment was evaluated based on its visuallyobservable condition. Table 3, below, outlines the criteria used in the field to visually assess thecondition of materials. Assigned conditions represent materials only at the time of the field workand should not necessarily be considered accurate for future conditions due to changes incircumstances.
TABLE 3 - CONDITION OF MATERIALS
Rank Descriptions
Good
Insulation on fittings, tanks, valves, boilers, ducts, and other mechanical equipment, whichis completely enclosed.Sprayed fireproofing or acoustical texture coat showing no signs of delaminating or fall-out.Non-friable materials not exhibiting significant damage or extensive wear.
Fair Pipe insulation showing some signs of physical damage or shrinkage cracks along pipe runs.
Upper Grand District School Board June 2007SFIS No. 2434 – Waverley Drive PS - 6 - 06-1135-044
Golder Associates
TABLE 3 - CONDITION OF MATERIALS
Rank Descriptions
Poor
General damage to mechanical insulation or water damage exposing asbestos directly.In areas of sprayed fireproofing or acoustic texture coat: delaminating and the presence offallen material on horizontal surfaces.The absence of an enclosure (e.g. – canvas wrap, foil tape) around asbestos-containingmaterial which formerly had an enclosure.Non-friable ACM severely damaged to the extent that asbestos fibres may be released.
NOTE: The evaluation of the condition of non-friable materials does not utilize a fair condition rating.
2.5 Accessibility of Material
Materials are rated based on the ease with which they can be reached, and therefore physicallydisturbed. The accessibility of materials known or suspected of being ACM were rated accordingto the following criteria outlined in Table 4:
TABLE 4 - ACCESSIBILITY
Access (A)
Materials within reach (from floor level) of all Site users. These also include materialsin gymnasiums, workshops, and storage areas where activities of the Site users mayresult in disturbance of ACM not normally within reach from floor level. Visibilitywould typically be noted as “YES” for these items, except for under sinks, in closets, orother commonly accessed spaces.
Access (B)
Materials in frequently entered maintenance areas of the Site within reach ofmaintenance staff, without the need for a ladder. Includes materials within reach from afixed ladder or catwalk (i.e., tops of equipment, mezzanines, and frequently entered pipechases, tunnels and service areas). Visibility would typically be noted as “YES” forthese items.
Access (C)
Materials above 8'-0" where use of a ladder is required to reach the ACM. Only includesACMs that are exposed to view without the removal or opening of other buildingcomponents such as ceiling tiles, or service access doors or hatches. Does not includematerials in infrequently accessed service areas of the Site. Visibility would be noted as“YES” for these items.
Access (D)
Materials that can not be reached without removing a building component, includinglay-in ceilings or access panels in solid ceiling systems. Includes rarely entered crawlspaces, attic spaces, etc. Observations will be limited to the extent visible from accesspoints. Visibility would be noted as “NO” for these items.
Upper Grand District School Board June 2007SFIS No. 2434 – Waverley Drive PS - 7 - 06-1135-044
Golder Associates
TABLE 4 - ACCESSIBILITY
Access (E)
Materials behind inaccessible solid ceiling systems, walls or mechanical equipment, etc.,where demolition of the ceiling, wall or equipment etc. is required to reach the ACM.These materials are visually identified by the surveyor, often with difficulty, and theremay be uncertainty associated with them. Evaluation of condition and extent of ACM islimited or impossible, depending on the surveyor's ability to visually examine thesematerials. Visibility would be noted as “NO” for these items.
2.6 Response Actions
For each ACM or PACM identified, a specific response action has been assigned. The assignedresponse action is based on consideration of condition and accessibility. These actions are basedon the likely risk posed by the material with damaged materials that are easily accessible posingthe greatest risk and good condition materials in inaccessible areas posing the least risk.Response actions range from immediate clean-up of debris to ongoing routine inspections of non-friable material in good condition.
In any building with friable asbestos, current regulations require implementation of an AsbestosManagement Program (AMP) which includes provisions for training and routine inspections ofACM. As of November 1, 2007, these regulations will further require implementation of an AMPfor buildings containing non-friable ACM. Depending on the condition and the accessibility ofACMs, more active measures, such as repair or removal, may be required. In the event of abuilding alteration, it will be necessary to remove all ACM, regardless of condition, that is likelyto be disturbed by planned renovation, demolition or maintenance work. Response Actions andtheir definitions are presented in Table 5.
TABLE 5 - RESPONSE ACTION ITEMS
Action 1Immediate Clean-Up of DebrisRestrict access that is likely to cause a disturbance of the ACM debris and cleanup ACM debris immediately.
Action 2
Type 2 Precautions for Entry into Areas with ACM DebrisRestrict access to the area to persons utilizing Type 2 asbestos precautions as perO.Reg 278/05. These precautions will be required until the ACM debris has beencleaned up, and the source of the debris has been stabilized or removed.
Action 3
ACM Removal Required for ComplianceRemove ACM in compliance with regulatory requirements of O.Reg 278/05.Depending on the severity of the damage to the ACM, it may also be possible torepair rather than remove the ACM.
Upper Grand District School Board June 2007SFIS No. 2434 – Waverley Drive PS - 8 - 06-1135-044
Golder Associates
TABLE 5 - RESPONSE ACTION ITEMS
Action 4Type 2 Access into Areas Where ACM is Present and Likely to be DisturbedUse Type 2 asbestos precautions as per O.Reg 278/05 when entry or access intoan area is likely to disturb the ACM.
Action 5ACM RepairRepair ACM found in fair condition, and not likely to be damaged again ordisturbed by normal use of the area or room.
Action 6 Routine InspectionMaintain routine inspection of ACM to monitor condition.
Based on the accessibility and action criteria presented above, the following Action Matrix Table,Table 6, outlines appropriate action codes for all ACM and PACM identified.
TABLE 6 – ACTION MATRIX TABLE
ConditionAccess
Good Fair PoorDebris
(A) Action 6 Action 5 Action 3 Action 1
(B) Action 6 Action 5 Action 3 Action 1
(C) Action 6 Action 5 Action 4 Action 2
(D) Action 6 Action 6 Action 4 Action 2
(E) Action 6 Action 6 Action 6 Action 6
Tables 4, 5, and 6 are derived from, and based upon, Public Works and Government ServicesCanada (PWGSC) Departmental Policy 057: Asbestos Management.
2.7 Limitations of Survey
Only accessible areas of the Site were examined during our assessment. An accessible area isdefined to include areas above a suspended ceiling tile, within a manufactured access hatch orbehind a closed door, not impeded by any structure, article or item. An enclosed area thatrequires demolition to gain entry or a temporary access hatch that is not readily opened isconsidered inaccessible. Ceiling spaces (between suspended ceiling and structural deck) and wallcavities that were not accessible at the time of this assessment should be considered to containasbestos until proven otherwise. If these spaces are to be accessed for any reason, such as a roofleak, etc., an inspection should be conducted by a competent person and any suspect ACM shouldbe sampled or presumed to contain asbestos. This report reflects the observations of accessedareas, and analytical results of materials sampled during the survey.
Upper Grand District School Board June 2007SFIS No. 2434 – Waverley Drive PS - 9 - 06-1135-044
Golder Associates
Carpets were lifted where possible to determine material below. However, depending on themethod of securing the carpet to the flooring substrate, it may not have been possible to removethe carpet without causing damage to determine materials below. Nor, where it was possible tolift corners of the carpet, was the entire surface area under the carpet surveyed. Therefore, whenindicated, it is possible that asbestos materials may be present under a portion of the carpetedarea. Asbestos-containing flooring material should be suspected below all carpets until provenotherwise.
Similarly, equipment such as exhaust stacks and metal-clad breaching, boilers, kilns, electricalcomponents and mechanical piping and ducting were not disassembled for assessment.Subsequently, materials such as refractory, gaskets and other internal components should beconsidered suspect ACM until sampled and proven otherwise. Roofing components and buildingenvelope materials such as window caulking or glazing that were not sampled due to concernsabout damage to the building envelope should be presumed asbestos-containing until provenotherwise.
Analytical results reflect the sampled materials at the specific sample locations. Visually similarmaterials (colour and texture) were referenced to specific analyzed samples and were consideredto be ‘homogeneous’ (of like composition) in nature, as is stipulated in O.Reg 278/05.
2.8 General Recommendations
Should planned renovations involve the removal of the materials identified as asbestos-containing, all appropriate precautions, as detailed in O.Reg 278/05, must be followed.
This survey was conducted to identify asbestos materials in accessible areas that requiremonitoring as part of an AMP. It is possible that undiscovered ACMs may be present withininaccessible locations such as wall cavities or above inaccessible ceilings. It is recommended thata more comprehensive and invasive survey be conducted prior to any planned demolition orrenovations that involve entering previously inaccessible areas. If encountered during futurerenovations or demolition, suspect materials should be treated as asbestos-containing until provenotherwise.
If any ACM is present within the Site, an AMP must be maintained as per the requirements ofSections 7 and 8 of O.Reg 278/05. The AMP would include provisions for regular assessments ofall identified ACMs, appropriate procedures for dealing with ACMs, and training, as appropriate,for all occupants who may come into contact with ACMs.
Upper Grand District School Board June 2007SFIS No. 2434 – Waverley Drive PS - 10 - 06-1135-044
Golder Associates
3.0 FINDINGS
3.1 General Information
General information relating to the assessment of this Site is presented in Table 7:
TABLE 7 – SITE-SPECIFIC INFORMATION
SCHOOL NAME: Waverley Drive Public School SFIS No.: 2434
Approx. Bldg. Size (m2): 3,940 No. of Levels (floors) including basement(s): 2
Year of Construction: 1962 Additions (Years of Construction): 1964 and 1966
Surveyed by: S. Kime and K. Kaufmann Survey Date(s): July 24, 2006
The findings of this assessment have been summarized in tabular form and are presented in theattached appendices as follows:
Appendix A: Summary Tables;Appendix B: Laboratory Certificates of Analysis; andAppendix C: Photo Logs.
Floor plans indicating sample locations and mapping of selected ACMs are presented as figuresin an attachment immediately following the body of the main report. Please note that allmaterials may not be mapped and that detailed room descriptions should be referenced for acomprehensive list of ACM and PACM identified. A listing of all materials identified, presentedby location (Summary Report by Location), is presented in Table A-3 in Appendix A.
The location, quantity and extent of ACM has been identified throughout the Site based on thefindings during Golder’s Site assessment. A total of 114 samples of materials from 38homogeneous material groupings suspected of containing asbestos were obtained from the Siteand submitted, along with a chain of custody, for asbestos content analysis. Following thesampling protocol outlined in Section 2.1 of this report, a total of 133 sample analyses wereperformed by the laboratory.
Upper Grand District School Board June 2007SFIS No. 2434 – Waverley Drive PS - 11 - 06-1135-044
Golder Associates
3.2 Site Specific ACM Information
The following ACMs were identified in the building:
9x9-inch Vinyl floor tile, dark blue with white streaks (Component 102);9x9-inch Vinyl floor tile, light blue with white streaks (Component 103);9x9-inch Vinyl floor tile, white with black streaks (Component 104);Vinyl sheet flooring, taupe (Component 151);Plaster above doors (Component 210);Exterior plaster (Component 310);Ceiling tiles small and large pinholes (Component 368);Parging cement on fittings (Component 500);Unidentified board behind radiators (Component 815); andWall board (Component 824).
Detailed descriptions of each identified material are provided in Table A-2 Summary of AllAsbestos-Containing Materials, provided in Appendix A.
Upper Grand District School Board June 2007SFIS No. 2434 – Waverley Drive PS - 12 - 06-1135-044
Golder Associates
4.0 SITE SPECIFIC RECOMMENDATIONS
Based on the findings of this assessment, actions have been assigned for each ACM identified. Adetailed list of actions required for all ACMs is presented in Table A-5 Action Item SummaryReport, located in Appendix A. An abbreviated summary of Action Codes 1 through 5 isprovided below and should be read in conjunction with Tables 4, 5, and 6. Items requiringroutine inspection only (Action Item 6) have not been included in the abbreviated summarybelow:
Action Item 3: Remove/repair of ACM in compliance with regulatory requirements:
Approximately 7.5 metres of unidentified board (Component 815) behind radiators inthe continuing education classroom (Location 10).
Action Item 5: Repair ACM found in fair condition, and not likely to be damaged again ordisturbed by normal use of the area or room:
Approximately two parged fittings (Component 500) in Stairwell G.
All ACMs identified require routine inspection as indicated in UGDSB Asbestos ManagementProgram and O.Reg 278/05. Based on the requirements of O.Reg 278/05, Golder alsorecommends the following:
An Asbestos Management Plan must be implemented for this Site as per the requirements ofSection 7 and 8 of O.Reg 278/05; andInaccessible areas should be considered to contain asbestos until they can be accessed andproperly assessed.
Additionally, based on the results of the survey, Golder recommends the following be consideredif future renovations are planned:
Should planned renovations involve the removal of the materials identified as asbestos-containing, ensure that all appropriate precautions (as detailed in O.Reg 278/05) are followed;Disturbances to materials listed in this report as presumed ACM should either be sampledprior to disturbance, such as building maintenance activities, renovation or demolition, ortreated as ACM and handled in accordance with the requirements of O.Reg 278/05; andIt is possible that undiscovered ACMs may be present within inaccessible locations such aswall cavities or above inaccessible ceilings. If encountered during future renovations ordemolition, suspect materials should be treated as asbestos-containing until proven otherwise.
Upper Grand District School Board June 2007SFIS No. 2434 – Waverley Drive PS - 13 - 06-1135-044
Golder Associates
5.0 LIMITATIONS AND USE OF REPORT
The conclusions and recommendations contained in this assessment report are based uponprofessional opinions with regard to the subject matter. These opinions are in accordance withcurrently accepted industry practices for asbestos surveys and regulatory requirements forsampling and identifying ACMs and are subject to the following inherent limitations:
1. The data and findings presented in this report are valid as of the date(s) of the investigationonly. The passage of time, manifestation of latent conditions or occurrence of future eventsmay warrant further exploration of the Site, analysis of the data, and re-evaluation of thefindings, observations, and conclusions expressed in this report.
2. The data reported and the findings, observations, conclusions, and recommendationsexpressed in this report are limited by the Scope of Work. The Scope of Work was definedby the request of the client, the time and budgetary constraints imposed by the client, andavailability of access to the Site.
3. Because of the limitations stated above, the findings, observations, conclusions, andrecommendations expressed by Golder Associates Ltd. in this report are not, and should notbe, considered an opinion concerning compliance of any past or present owner or operator ofthe Site with any federal, provincial or local laws or regulations.
4. No warranty or guarantee, whether expressed or implied, is made with respect to the data orthe reported findings, observations, and conclusions, which are based solely upon Siteconditions in existence at the time of investigation.
5. Golder Associates Ltd. will not be responsible for any real or perceived decrease in aproperty value, its saleability or ability to gain financing through the reporting of informationin this report.
6. Golder Associates Ltd.’s assessment reports present professional opinions and findings of ascientific and technical nature. While attempts were made to relate the data and findings toapplicable environmental and occupational health & safety laws and regulations, the reportshall not be construed to offer legal opinion or representations as to the requirements of, norcompliance with, environmental and occupational health & safety laws, rules, regulations orpolicies of federal, provincial, or local governmental agencies. Any use of the assessmentreport constitutes acceptance of the limits of Golder Associates Ltd.’s liability. GolderAssociates Ltd.’s liability extends only to its client and not to other parties who may obtainthis assessment report. Issues raised by the report should be reviewed by appropriate legalcounsel.
Upper Grand District School Board June 2007SFIS No. 2434 – Waverley Drive PS - 14 - 06-1135-044
Golder Associates
6.0 CLOSURE
We trust that this report meets your requirements. If you have any questions regarding thecontent of this report, please do not hesitate to contact the undersigned.
GOLDER ASSOCIATES LTD.
Sara Kime, B.Sc.(Eng), DOHSOccupational Hygienist
Keith Lesarge, M.Sc.Associate; Senior Environmental ScientistSK/ KGL/crn:\active\2006\1135 - environmental\1135-000\06-1135-044 ugdsc - asbestos survey - sw ontario\prime\reports\2434 waverley drive ps\jun 14 07 - 2434 survey report.doc
FIGURE 1
REFERENCE
NOTES
LEGEND
THIS DRAWING IS SCHEMATIC ONLYAND IS TO BE READ IN CONJUNCTIONWITH ACCOMPANYING TEXT.
SAMPLE LOCATION PLAN(MAIN FLOOR)
DRAWING SUPPLIED BYUPPER GRAND DISTRICT SCHOOL BOARDENTITLED: Waverly Dr Floor Plan
SAMPLE
ASBESTOS SURVEY PROJECTUPPER GRAND DISTRICT SCHOOL BOARD2434 - WAVERLY DRIVE PUBLIC SCHOOL
FIGURE 2
REFERENCE
NOTES
LEGEND
THIS DRAWING IS SCHEMATIC ONLYAND IS TO BE READ IN CONJUNCTIONWITH ACCOMPANYING TEXT.
SAMPLE LOCATION PLAN(MAIN FLOOR)
DRAWING SUPPLIED BYUPPER GRAND DISTRICT SCHOOL BOARDENTITLED: Waverly Dr Floor Plan
SAMPLE
ASBESTOS SURVEY PROJECTUPPER GRAND DISTRICT SCHOOL BOARD2434 - WAVERLY DRIVE PUBLIC SCHOOL
FIGURE 3
REFERENCE
NOTES
LEGEND
THIS DRAWING IS SCHEMATIC ONLYAND IS TO BE READ IN CONJUNCTIONWITH ACCOMPANYING TEXT.
SAMPLE LOCATION PLAN(SECOND FLOOR)
DRAWING SUPPLIED BYUPPER GRAND DISTRICT SCHOOL BOARDENTITLED: Waverly Dr Floor Plan
SAMPLE
ASBESTOS SURVEY PROJECTUPPER GRAND DISTRICT SCHOOL BOARD2434 - WAVERLY DRIVE PUBLIC SCHOOL
FIGURE 4
REFERENCE
NOTES
LEGEND
THIS DRAWING IS SCHEMATIC ONLYAND IS TO BE READ IN CONJUNCTIONWITH ACCOMPANYING TEXT.
ASBESTOS-CONTAINING MATERIALLOCATION PLAN
(MAIN FLOOR)
DRAWING SUPPLIED BYUPPER GRAND DISTRICT SCHOOL BOARDENTITLED: Waverly Dr Floor Plan
Component 102 - Vinyl Floor Tile(9" x 9" dark blue with white streaks)
Component 151 - Vinyl Sheet Flooring(taupe)
Component 368 - Ceiling Tile(2' x 4' small and large pinholes)
ASBESTOS SURVEY PROJECTUPPER GRAND DISTRICT SCHOOL BOARD2434 - WAVERLY DRIVE PUBLIC SCHOOL
A
D
F
Component 103 - Vinyl Floor Tile(9" x 9" light blue with white streaks)B
Component 104 - Vinyl Floor Tile(9" x 9" white with black streaks)C
Component 310 - Exterior plasterE
FIGURE 5
REFERENCE
NOTES
LEGEND
THIS DRAWING IS SCHEMATIC ONLYAND IS TO BE READ IN CONJUNCTIONWITH ACCOMPANYING TEXT.
ASBESTOS-CONTAINING MATERIALLOCATION PLAN
(MAIN FLOOR)
DRAWING SUPPLIED BYUPPER GRAND DISTRICT SCHOOL BOARDENTITLED: Waverly Dr Floor Plan
Component 500 - Parging cement on fittings
ASBESTOS SURVEY PROJECTUPPER GRAND DISTRICT SCHOOL BOARD2434 - WAVERLY DRIVE PUBLIC SCHOOL
Component 815 - Board behind radiators
Component 210 - Plaster above doors
Component 824 - Wall boardH
G
FIGURE 6
REFERENCE
NOTES
LEGEND
THIS DRAWING IS SCHEMATIC ONLYAND IS TO BE READ IN CONJUNCTIONWITH ACCOMPANYING TEXT.
ASBESTOS-CONTAINING MATERIALLOCATION PLAN(SECOND FLOOR)
DRAWING SUPPLIED BYUPPER GRAND DISTRICT SCHOOL BOARDENTITLED: Waverly Dr Floor Plan
Component 368 - Ceiling Tile(2' x 4' small and large pinholes)
Component 500 - Parging cement on fittings
ASBESTOS SURVEY PROJECTUPPER GRAND DISTRICT SCHOOL BOARD2434 - WAVERLY DRIVE PUBLIC SCHOOL
F
Component 815 - Board behind radiators
Golder Associates
LIST OF ABBREVIATIONS
< LOD Less than the Limit of Detection for Analytical Method (no asbestosidentified in sample)
ACM Asbestos-Containing Material; in Ontario this is any material with 0.5% orgreater asbestos by dry weight
CT Ceiling Tile
FTG Pipe Fitting
LOD Limit of Detection
N/A Not Applicable and/or Not Analysed
Not Tested Previous sample of this material was found to be positive for asbestos,therefore further analysis is not required or material was not composed oftwo layers
PLM Polarized Light Microscopy (asbestos identification procedure)
Presumed ACM Presumed to contain asbestos and must be treated as such
STR Straight Pipe Run
VFT Vinyl Floor Tile
VSF Vinyl Sheet Flooring
Date: 6/8/2007
Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Job Number : 06-1135-044Laboratory ResultsTable A-1
Page: 1Golder Associates
104 VFT White With Black Streaks (9x9)
2434-104-3 2669594 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Black Mastic; A/W 9x9 Floor Tile
104 VFT White With Black Streaks (9x9)
2434-104-2 2669593 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Black Mastic; A/W 9x9 Floor Tile
104 VFT White With Black Streaks (9x9)
2434-104-1 2669592B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
101 VFT White, Beige and Taupe Mix (12x12)
2434-101-3 2669585A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; White Floor Tile; 12x12
101 VFT White, Beige and Taupe Mix (12x12)
2434-101-3 2669585B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
102 VFT Dark Blue With White Streaks (9x9)
2434-102-1 2669586A 93066 N/A PLM 1.3 Chrysotile N/A N/A 0.25 Layer 1; Blue Floor Tile; 9x9
101 VFT White, Beige and Taupe Mix (12x12)
2434-101-2 2669584B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
101 VFT White, Beige and Taupe Mix (12x12)
2434-101-1 2669583A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; White Floor Tile; 12x12
101 VFT White, Beige and Taupe Mix (12x12)
2434-101-1 2669583B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
101 VFT White, Beige and Taupe Mix (12x12)
2434-101-2 2669584A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; White Floor Tile; 12x12
102 VFT Dark Blue With White Streaks (9x9)
2434-102-1 2669586B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
103 VFT Light Blue With White Streaks (9x9)
2434-103-2 2669590 93066 N/A PLM N/A N/A N/A N/A 0.25 Sample Not Analyzed- Read Until Positive
103 VFT Light Blue With White Streaks (9x9)
2434-103-3 2669591 93066 N/A PLM N/A N/A N/A N/A 0.25 Sample Not Analyzed- Read Until Positive
104 VFT White With Black Streaks (9x9)
2434-104-1 2669592A 93066 N/A PLM 0.75 Chrysotile N/A N/A 0.25 Layer 1; White/Black Floor Tile; 9x9
103 VFT Light Blue With White Streaks (9x9)
2434-103-1 2669589B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
102 VFT Dark Blue With White Streaks (9x9)
2434-102-2 2669587 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Black Mastic; A/W 9x9 Floor Tile
102 VFT Dark Blue With White Streaks (9x9)
2434-102-3 2669588 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Black Mastic; A/W 9x9 Floor Tile
103 VFT Light Blue With White Streaks (9x9)
2434-103-1 2669589A 93066 N/A PLM 1.2 Chrysotile N/A N/A 0.25 Layer 1; Lt.Blue Floor Tile; 9x9
Building: Waverley Drive PS
Component Sample # Lab Samp ID
Lab Report Number
Location Test Method
Asbestos I %
Asbestos I Type
Asbestos II %
Asbestos II Type
LOD %
Additional Comments
Date: 6/8/2007
Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Job Number : 06-1135-044Laboratory ResultsTable A-1
Page: 2Golder Associates
107 VFT Dark Grey, Light Grey and White Mix (12x12)
2434-107-3 2669603 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Dk.Grey/White Floor Tile
108 VFT Beige With Grey Marks (12x12)
2434-108-1 2669604A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; White Floor Tile; 12x12
108 VFT Beige With Grey Marks (12x12)
2434-108-1 2669604B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black/Tan Mastic
107 VFT Dark Grey, Light Grey and White Mix (12x12)
2434-107-1 2669601B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Tan/Black Mastic
107 VFT Dark Grey, Light Grey and White Mix (12x12)
2434-107-2 2669602A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; Dk.Grey/White Floor Tile
107 VFT Dark Grey, Light Grey and White Mix (12x12)
2434-107-2 2669602B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Tan/Black Mastic
108 VFT Beige With Grey Marks (12x12)
2434-108-2 2669605A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; White Floor Tile; 12x12
107 VFT Dark Grey, Light Grey and White Mix (12x12)
2434-107-1 2669601A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; Dk.Grey/White Floor Tile
105 VFT White With Light Blue Streaks (9x9)
2434-105-2 2669596B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black/Tan Mastic
105 VFT White With Light Blue Streaks (9x9)
2434-105-3 2669597A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; White Floor Tile; 9x9
105 VFT White With Light Blue Streaks (9x9)
2434-105-2 2669596A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; White Floor Tile; 9x9
105 VFT White With Light Blue Streaks (9x9)
2434-105-1 2669595A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; White Floor Tile; 9x9
105 VFT White With Light Blue Streaks (9x9)
2434-105-1 2669595B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
106 VFT White, Grey and Light Grey Mix (12x12)
2434-106-2 2669599 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Grey/White Floor Tile
106 VFT White, Grey and Light Grey Mix (12x12)
2434-106-3 2669600 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Grey/White Floor Tile
106 VFT White, Grey and Light Grey Mix (12x12)
2434-106-1 2669598B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
105 VFT White With Light Blue Streaks (9x9)
2434-105-3 2669597B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
106 VFT White, Grey and Light Grey Mix (12x12)
2434-106-1 2669598A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; Grey/White Floor Tile
Building: Waverley Drive PS
Component Sample # Lab Samp ID
Lab Report Number
Location Test Method
Asbestos I %
Asbestos I Type
Asbestos II %
Asbestos II Type
LOD %
Additional Comments
Date: 6/8/2007
Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Job Number : 06-1135-044Laboratory ResultsTable A-1
Page: 3Golder Associates
111 VFT Beige With Taupe Streaks 2434-111-1 2669613A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; Off-White/Tan Floor Tile
110 VFT Taupe With White Streaks (12x12)
2434-110-3 2669612B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
111 VFT Beige With Taupe Streaks 2434-111-2 2669614A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; Off-White/Tan Floor Tile
111 VFT Beige With Taupe Streaks 2434-111-1 2669613B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
110 VFT Taupe With White Streaks (12x12)
2434-110-3 2669612A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; Tan Floor Tile; 12x12
109 VFT Green on Green (12x12) 2434-109-1 2669607A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; Green Floor Tile; 12x12
109 VFT Green on Green (12x12) 2434-109-1 2669607B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
109 VFT Green on Green (12x12) 2434-109-2 2669608A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; Green Floor Tile; 12x12
108 VFT Beige With Grey Marks (12x12)
2434-108-2 2669605B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black/Tan Mastic
108 VFT Beige With Grey Marks (12x12)
2434-108-3 2669606A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; White Floor Tile; 12x12
108 VFT Beige With Grey Marks (12x12)
2434-108-3 2669606B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black/Tan Mastic
109 VFT Green on Green (12x12) 2434-109-2 2669608B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
110 VFT Taupe With White Streaks (12x12)
2434-110-1 2669610B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
110 VFT Taupe With White Streaks (12x12)
2434-110-2 2669611A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; Tan Floor Tile; 12x12
110 VFT Taupe With White Streaks (12x12)
2434-110-2 2669611B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
109 VFT Green on Green (12x12) 2434-109-3 2669609A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; Green Floor Tile; 12x12
109 VFT Green on Green (12x12) 2434-109-3 2669609B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
110 VFT Taupe With White Streaks (12x12)
2434-110-1 2669610A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; Tan Floor Tile; 12x12
Building: Waverley Drive PS
Component Sample # Lab Samp ID
Lab Report Number
Location Test Method
Asbestos I %
Asbestos I Type
Asbestos II %
Asbestos II Type
LOD %
Additional Comments
Date: 6/8/2007
Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Job Number : 06-1135-044Laboratory ResultsTable A-1
Page: 4Golder Associates
114 VFT White With Green Streaks (12x12)
2434-114-2 2669623A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; White Floor Tile; 12x12
114 VFT White With Green Streaks (12x12)
2434-114-2 2669623B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
114 VFT White With Green Streaks (12x12)
2434-114-1 2669622B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
113 VFT Light Grey With White Streaks (12x12)
2434-113-3 2669621A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; Grey Floor Tile; 12x12
113 VFT Light Grey With White Streaks (12x12)
2434-113-3 2669621B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
114 VFT White With Green Streaks (12x12)
2434-114-1 2669622A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; White Floor Tile; 12x12
112 VFT Pink With White Streaks (9x9)
2434-112-1 2669616B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
112 VFT Pink With White Streaks (9x9)
2434-112-2 2669617A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; Pink Floor Tile; 9x9
112 VFT Pink With White Streaks (9x9)
2434-112-2 2669617B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
111 VFT Beige With Taupe Streaks 2434-111-2 2669614B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
111 VFT Beige With Taupe Streaks 2434-111-3 2669615 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Off-White/Tan Floor Tile
112 VFT Pink With White Streaks (9x9)
2434-112-1 2669616A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; Pink Floor Tile; 9x9
113 VFT Light Grey With White Streaks (12x12)
2434-113-1 2669619B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
113 VFT Light Grey With White Streaks (12x12)
2434-113-2 2669620A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; Grey Floor Tile; 12x12
113 VFT Light Grey With White Streaks (12x12)
2434-113-2 2669620B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
112 VFT Pink With White Streaks (9x9)
2434-112-3 2669618A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; Pink Floor Tile; 9x9
112 VFT Pink With White Streaks (9x9)
2434-112-3 2669618B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
113 VFT Light Grey With White Streaks (12x12)
2434-113-1 2669619A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; Grey Floor Tile; 12x12
Building: Waverley Drive PS
Component Sample # Lab Samp ID
Lab Report Number
Location Test Method
Asbestos I %
Asbestos I Type
Asbestos II %
Asbestos II Type
LOD %
Additional Comments
Date: 6/8/2007
Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Job Number : 06-1135-044Laboratory ResultsTable A-1
Page: 5Golder Associates
210 Plaster Above Doors 2434-210-2 2669638 93066 N/A PLM N/A N/A N/A N/A 0.25 Sample Not Analyzed- Read Until Positive
210 Plaster Above Doors 2434-210-1 2669637 93066 N/A PLM 0.75 Chrysotile N/A N/A 0.25 Grey Plaster; Above Doors
200 Drywall Joint Compound 2434-200-1 2669634 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 White Joint Compound
152 VSF Orange and White Mosaic 2434-152-3 2669633 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Grey/Tan Vinyl Sheet Flooring
200 Drywall Joint Compound 2434-200-3 2669636 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 White Joint Compound
200 Drywall Joint Compound 2434-200-2 2669635 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 White Joint Compound
115 VFT Brown With Taupe Streaks (12x12)
2434-115-1 2669625B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
115 VFT Brown With Taupe Streaks (12x12)
2434-115-2 2669626A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; Brown Floor Tile; 12x12
115 VFT Brown With Taupe Streaks (12x12)
2434-115-2 2669626B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
114 VFT White With Green Streaks (12x12)
2434-114-3 2669624A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; White Floor Tile; 12x12
114 VFT White With Green Streaks (12x12)
2434-114-3 2669624B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
115 VFT Brown With Taupe Streaks (12x12)
2434-115-1 2669625A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; Brown Floor Tile; 12x12
115 VFT Brown With Taupe Streaks (12x12)
2434-115-3 2669627A 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 1; Brown Floor Tile; 12x12
151 VSF Taupe 2434-151-3 2669630 93066 N/A PLM N/A N/A N/A N/A 0.25 Sample Not Analyzed- Read Until Positive
152 VSF Orange and White Mosaic 2434-152-1 2669631 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Grey/Tan Vinyl Sheet Flooring
152 VSF Orange and White Mosaic 2434-152-2 2669632 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Grey/Tan Vinyl Sheet Flooring
115 VFT Brown With Taupe Streaks (12x12)
2434-115-3 2669627B 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Layer 2; Black Mastic
151 VSF Taupe 2434-151-1 2669628 93066 N/A PLM 15 Chrysotile N/A N/A 0.25 Tan Vinyl Sheet Flooring
151 VSF Taupe 2434-151-2 2669629 93066 N/A PLM N/A N/A N/A N/A 0.25 Sample Not Analyzed- Read Until Positive
Building: Waverley Drive PS
Component Sample # Lab Samp ID
Lab Report Number
Location Test Method
Asbestos I %
Asbestos I Type
Asbestos II %
Asbestos II Type
LOD %
Additional Comments
Date: 6/8/2007
Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Job Number : 06-1135-044Laboratory ResultsTable A-1
Page: 6Golder Associates
363 CT Long Fissures With Few Pinholes (2x2)
2434-363-2 2669656 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile; 2x2
363 CT Long Fissures With Few Pinholes (2x2)
2434-363-1 2669655 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile; 2x2
362 CT Short Fissures With Few Pinholes (2x2)
2434-362-1 2669652 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile; 2x2
362 CT Short Fissures With Few Pinholes (2x2)
2434-362-2 2669653 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile; 2x2
362 CT Short Fissures With Few Pinholes (2x2)
2434-362-3 2669654 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile; 2x2
361 CT Long Fissures With Many Many pinholes (2x2)
2434-361-3 2669651 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile
290 Baseboard Mastic 2434-290-3 2669642 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Brown Baseboard Mastic
310 Exterior Plaster 2434-310-1 2669643 93066 N/A PLM 1.2 Chrysotile N/A N/A 0.25 Grey Plaster; Exterior
310 Exterior Plaster 2434-310-2 2669644 93066 N/A PLM N/A N/A N/A N/A 0.25 Sample Not Analyzed- Read Until Positive
210 Plaster Above Doors 2434-210-3 2669639 93066 N/A PLM N/A N/A N/A N/A 0.25 Sample Not Analyzed- Read Until Positive
290 Baseboard Mastic 2434-290-1 2669640 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Baseboard Mastic
290 Baseboard Mastic 2434-290-2 2669641 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Brown Baseboard Mastic
360 CT Small Fissures in Swirl With Pinholes (2x2)
2434-360-3 2669648 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile
361 CT Long Fissures With Many Many pinholes (2x2)
2434-361-1 2669649 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile
361 CT Long Fissures With Many Many pinholes (2x2)
2434-361-2 2669650 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile
310 Exterior Plaster 2434-310-3 2669645 93066 N/A PLM N/A N/A N/A N/A 0.25 Sample Not Analyzed- Read Until Positive
360 CT Small Fissures in Swirl With Pinholes (2x2)
2434-360-1 2669646 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile
360 CT Small Fissures in Swirl With Pinholes (2x2)
2434-360-2 2669647 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile
Building: Waverley Drive PS
Component Sample # Lab Samp ID
Lab Report Number
Location Test Method
Asbestos I %
Asbestos I Type
Asbestos II %
Asbestos II Type
LOD %
Additional Comments
Date: 6/8/2007
Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Job Number : 06-1135-044Laboratory ResultsTable A-1
Page: 7Golder Associates
500 Parging Cement on Fittings 2434-500-2 2669674 93066 N/A PLM N/A N/A N/A N/A 0.25 Sample Not Analyzed- Read Until Positive
500 Parging Cement on Fittings 2434-500-1 2669673 93066 N/A PLM 80 Chrysotile N/A N/A 0.25 Grey Piping System Insulation
368 CT Small and Large Pinholes (2x4)
2434-368-1 2669670 93066 N/A PLM 1.2 Chrysotile N/A N/A 0.25 Tan Ceiling Tile; 2x4
368 CT Small and Large Pinholes (2x4)
2434-368-2 2669671 93066 N/A PLM N/A N/A N/A N/A 0.25 Sample Not Analyzed- Read Until Positive
368 CT Small and Large Pinholes (2x4)
2434-368-3 2669672 93066 N/A PLM N/A N/A N/A N/A 0.25 Sample Not Analyzed- Read Until Positive
367 CT Short Fissures in Swirl with Pinholes (2x4)
2434-367-3 2669669 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile
364 CT Long Fissures With Medium Pinholes (2x4)
2434-364-3 2669660 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile
365 CT Short Fissures With Few Pinholes (2x4)
2434-365-1 2669661 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile; 2x4
365 CT Short Fissures With Few Pinholes (2x4)
2434-365-2 2669662 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile; 2x4
363 CT Long Fissures With Few Pinholes (2x2)
2434-363-3 2669657 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile; 2x2
364 CT Long Fissures With Medium Pinholes (2x4)
2434-364-1 2669658 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile
364 CT Long Fissures With Medium Pinholes (2x4)
2434-364-2 2669659 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile
366 CT Long Fissures With Many Many Pinholes (2x4)
2434-366-3 2669666 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile
367 CT Short Fissures in Swirl with Pinholes (2x4)
2434-367-1 2669667 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile
367 CT Short Fissures in Swirl with Pinholes (2x4)
2434-367-2 2669668 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile
365 CT Short Fissures With Few Pinholes (2x4)
2434-365-3 2669663 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile; 2x4
366 CT Long Fissures With Many Many Pinholes (2x4)
2434-366-1 2669664 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile
366 CT Long Fissures With Many Many Pinholes (2x4)
2434-366-2 2669665 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Ceiling Tile
Building: Waverley Drive PS
Component Sample # Lab Samp ID
Lab Report Number
Location Test Method
Asbestos I %
Asbestos I Type
Asbestos II %
Asbestos II Type
LOD %
Additional Comments
Date: 6/8/2007
Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Job Number : 06-1135-044Laboratory ResultsTable A-1
Page: 8Golder Associates
551 Middle Tar Paper in Pipe Insulation
2434-551-1 2669688 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Black Tar Paper; A/W Piping System
551 Middle Tar Paper in Pipe Insulation
2434-551-2 2669689 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Black Tar Paper; A/W Piping System
551 Middle Tar Paper in Pipe Insulation
2434-551-3 2669690 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Black Tar Paper; A/W Piping System
550 Tar on Pipe Wrap 2434-550-1 2669685 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Brown/Black Fibrous; A/W Piping System
550 Tar on Pipe Wrap 2434-550-2 2669686 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Brown/Black Fibrous; A/W Piping System
550 Tar on Pipe Wrap 2434-550-3 2669687 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Brown/Black Fibrous; A/W Piping System
815 Unidentified Board Behind Radiators
2434-815-1 2669691 93066 N/A PLM 55 Chrysotile N/A N/A 0.25 Grey Insulation
815 Unidentified Board Behind Radiators
2434-815-2 2669692 93066 N/A PLM N/A N/A N/A N/A 0.25 Sample Not Analyzed- Read Until Positive
532 Layered Cardboard Insulation over 6" Pipe
2434-532-3 2669684 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan/Black Fibrous; A/W 6" Pipe
530 Outer Paper Pipe Insulation 2434-530-2 2669677 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Fibrous; A/W Piping System
530 Outer Paper Pipe Insulation 2434-530-3 2669678 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Fibrous; A/W Piping System
500 Parging Cement on Fittings 2434-500-3 2669675 93066 N/A PLM N/A N/A N/A N/A 0.25 Sample Not Analyzed- Read Until Positive
530 Outer Paper Pipe Insulation 2434-530-1 2669676 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Fibrous; A/W Piping System
531 Inner Paper Pipe Insulation 2434-531-1 2669679 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Fibrous; A/W Piping System
532 Layered Cardboard Insulation over 6" Pipe
2434-532-1 2669682 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Fibrous; A/W 6" Pipe
532 Layered Cardboard Insulation over 6" Pipe
2434-532-2 2669683 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan/Black Fibrous; A/W 6" Pipe
531 Inner Paper Pipe Insulation 2434-531-2 2669680 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Fibrous; A/W Piping System
531 Inner Paper Pipe Insulation 2434-531-3 2669681 93066 N/A PLM <LOD No Asbestos Detected
N/A N/A 0.25 Tan Fibrous; A/W Piping System
Building: Waverley Drive PS
Component Sample # Lab Samp ID
Lab Report Number
Location Test Method
Asbestos I %
Asbestos I Type
Asbestos II %
Asbestos II Type
LOD %
Additional Comments
Date: 6/8/2007
Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Job Number : 06-1135-044Laboratory ResultsTable A-1
Page: 9Golder Associates
824 Wall Board 2434-824-1 2669694 93066 N/A PLM 80 Amosite N/A N/A 0.25 Grey Insulation
824 Wall Board 2434-824-2 2669695 93066 N/A PLM N/A N/A N/A N/A 0.25 Sample Not Analyzed- Read Until Positive
824 Wall Board 2434-824-3 2669696 93066 N/A PLM N/A N/A N/A N/A 0.25 Sample Not Analyzed- Read Until Positive
815 Unidentified Board Behind Radiators
2434-815-3 2669693 93066 N/A PLM N/A N/A N/A N/A 0.25 Sample Not Analyzed- Read Until Positive
Building: Waverley Drive PS
Component Sample # Lab Samp ID
Lab Report Number
Location Test Method
Asbestos I %
Asbestos I Type
Asbestos II %
Asbestos II Type
LOD %
Additional Comments
Date: 6/8/2007
Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Job Number : 06-1135-044Summary of All Asbestos-Containing Materials
Table A-2
Golder Associates Page: 1
NOTE: All quantities listed are approximate only.
824 Wall Board No 10a; WALL 1.00 square meter A Yes 80 Amosite 6
815 Unidentified Board Behind Radiators
Yes 1; 10; 11; 12; 13; 14; 15; 16; 17; 2; 22; 23; 24; 26b; 27; 28; 29; 30; 31; 32; 34; 35; 36; 37; 38; 4; 41; 42; 43; 48; 49; 50; 51; 52; 53; 55; 56; 6; 7; 8; 9;
OTHER 345.00 meter A Yes 55 Chrysotile 6
500 Parging Cement on Fittings Yes 3; 57; PIPING SYSTEMS 4 each C No 80 Chrysotile 6
500 Parging Cement on Fittings Yes 20; 33; 39; 40; 54; G; PIPING SYSTEMS 93 each A No 80 Chrysotile 6
500 Parging Cement on Fittings Yes 15; 16; 20b; 31; 32; 5; A; B; C; D; E; F; H; I; PIPING SYSTEMS 341 each D No 80 Chrysotile 6
368 CT Small and Large Pinholes (2x4)
Yes 31; 32; 39; 40; 53; 55; G; H; I; J; CEILING 503.00 square meter C Yes 1.2 Chrysotile 6
310 Exterior Plaster Yes K; STRUCTURE 10.00 square meter C Yes 1.2 Chrysotile 6
210 Plaster Above Doors Yes C; D; WALL 10.00 square meter C Yes 0.75 Chrysotile 6
151 VSF Taupe No 22; 23; 28; 29; 41; 42; FLOOR 321.00 square meter A Yes 15 Chrysotile 6
104 VFT White With Black Streaks (9x9)
No 12; 13; 14; 2; 6; 7; 8; 9; FLOOR 60.00 square meter A Yes 0.75 Chrysotile 6
103 VFT Light Blue With White Streaks (9x9)
No 12; 13; 14; 3; 34; 36; 6; 7; 8; 9; FLOOR 526.00 square meter A Yes 1.2 Chrysotile 6
102 VFT Dark Blue With White Streaks (9x9)
No 1; 4; 9; FLOOR 122.00 square meter A Yes 1.3 Chrysotile 6
Building: Waverley Drive PS
Component Description of Material Friable Locations System Quantity Units Accessibility Visible Asbestos % Type Action Code
Component Details Asbestos Content
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 1Golder Associates
NOTE: All quantities listed are approximate only.
WALL Baseboard Mastic 290 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VFT White, Beige and Taupe Mix (12x12) 101 - - - - - <LOD No Asbestos Detected
- - - -
Location: Main Floor: 10a Quantity/Condition Total Location Details: Storage (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Drywall Without Joint Compound 935 - - - - - - - - - - -
CEILING Concrete Ceiling 901.2 - - - - - - - - - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
FLOOR VFT White, Beige and Taupe Mix (12x12) 101 - - - - - <LOD No Asbestos Detected
- - - -
WALL Baseboard Mastic 290 - - - - - <LOD No Asbestos Detected
- - - -
CEILING Concrete Ceiling 901.2 - - - - - - - - - - -
PIPING SYSTEMS Synthetic Insulation on Elbow 936 - - - - - - - - - - -
OTHER Unidentified Board Behind Radiators 815 0.00 0.00 7.50 7.50 meter 55 Chrysotile Yes Yes A 3
PIPING SYSTEMS Tar on Pipe Wrap 550 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
Location: Main Floor: 10 Quantity/Condition Total Location Details: Con. Ed. Classroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Concrete Block 927.1 - - - - - - - - - - -
WALL Baseboard Mastic 290 - - - - - <LOD No Asbestos Detected
- - - -
CEILING Fibreglass CT 932 - - - - - - - - - - -
FLOOR VFT Dark Blue With White Streaks (9x9) 102 30.00 0.00 0.00 30.00 square meter
1.3 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 7.50 0.00 0.00 7.50 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 1 Quantity/Condition Total Location Details: Office (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 2Golder Associates
NOTE: All quantities listed are approximate only.
WALL Concrete Block 927.1 - - - - - - - - - - -
WALL Drywall Without Joint Compound 935 - - - - - - - - - - -
WALL Baseboard Mastic 290 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VFT Light Blue With White Streaks (9x9) 103 68.00 0.00 0.00 68.00 square meter
1.2 Chrysotile No Yes A 6
FLOOR VFT White With Black Streaks (9x9) 104 5.00 0.00 0.00 5.00 square meter
0.75 Chrysotile No Yes A 6
CEILING Concrete Ceiling 901.2 - - - - - - - - - - -
PIPING SYSTEMS Synthetic Insulation on Elbow 936 - - - - - - - - - - -
PIPING SYSTEMS Tar on Pipe Wrap 550 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
Location: Main Floor: 12 Quantity/Condition Total Location Details: Classroom #6 (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Tectum (Spaghetti Tile) 926.1 - - - - - - - - - - -
WALL Drywall Joint Compound 200 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VFT White With Light Blue Streaks (9x9) 105 - - - - - <LOD No Asbestos Detected
- - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
CEILING Tectum (Spaghetti Tile) 926.2 - - - - - - - - - - -
Location: Main Floor: 11 Quantity/Condition Total Location Details: Music (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Concrete Block 927.1 - - - - - - - - - - -
WALL Wall Board 824 1.00 0.00 0.00 1.00 square meter
80 Amosite No Yes A 6
WALL Drywall Without Joint Compound 935 - - - - - - - - - - -
Location: Main Floor: 10a Quantity/Condition Total Location Details: Storage (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 3Golder Associates
NOTE: All quantities listed are approximate only.
PIPING SYSTEMS Tar on Pipe Wrap 550 - - - - - <LOD No Asbestos Detected
- - - -
CEILING Concrete Ceiling 901.2 - - - - - - - - - - -
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
PIPING SYSTEMS Synthetic Insulation on Elbow 936 - - - - - - - - - - -
FLOOR VFT White With Black Streaks (9x9) 104 5.00 0.00 0.00 5.00 square meter
0.75 Chrysotile No Yes A 6
FLOOR VFT Light Blue With White Streaks (9x9) 103 68.00 0.00 0.00 68.00 square meter
1.2 Chrysotile No Yes A 6
WALL Concrete Block 927.1 - - - - - - - - - - -
WALL Baseboard Mastic 290 - - - - - <LOD No Asbestos Detected
- - - -
Location: Main Floor: 14 Quantity/Condition Total Location Details: Classroom #2 (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Baseboard Mastic 290 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VFT White With Black Streaks (9x9) 104 5.00 0.00 0.00 5.00 square meter
0.75 Chrysotile No Yes A 6
FLOOR VFT Light Blue With White Streaks (9x9) 103 68.00 0.00 0.00 68.00 square meter
1.2 Chrysotile No Yes A 6
WALL Concrete Block 927.1 - - - - - - - - - - -
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
CEILING Concrete Ceiling 901.2 - - - - - - - - - - -
Location: Main Floor: 13 Quantity/Condition Total Location Details: Classroom #4 (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 12 Quantity/Condition Total Location Details: Classroom #6 (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 4Golder Associates
NOTE: All quantities listed are approximate only.
WALL Concrete Block 927.1 - - - - - - - - - - -
FLOOR VFT White, Grey and Light Grey Mix (12x12) 106 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR Carpet 930 - - - - - - - - - - -
Location: Main Floor: 17 Quantity/Condition Total Location Details: Staff Room (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Tar on Pipe Wrap 550 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS Parging Cement on Fittings 500 2 0 0 2 each 80 Chrysotile Yes No D 6
OTHER Unidentified Board Behind Radiators 815 2.00 0.00 0.00 2.00 meter 55 Chrysotile Yes Yes A 6
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
FLOOR Terrazzo 929 - - - - - - - - - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
CEILING CT Short Fissures With Few Pinholes (2x2) 362 - - - - - <LOD No Asbestos Detected
- - - -
Location Accessibility Issues:
Location: Main Floor: 16 Quantity/Condition Total Location Details: Washroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
CEILING CT Long Fissures With Many Many pinholes (2x2) 361 - - - - - <LOD No Asbestos Detected
- - - -
CEILING CT Short Fissures With Few Pinholes (2x2) 362 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR Terrazzo 929 - - - - - - - - - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
PIPING SYSTEMS Parging Cement on Fittings 500 2 0 0 2 each 80 Chrysotile Yes No D 6
OTHER Unidentified Board Behind Radiators 815 2.00 0.00 0.00 2.00 meter 55 Chrysotile Yes Yes A 6
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
PIPING SYSTEMS Tar on Pipe Wrap 550 - - - - - <LOD No Asbestos Detected
- - - -
Location: Main Floor: 15 Quantity/Condition Total Location Details: Washroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 5Golder Associates
NOTE: All quantities listed are approximate only.
Location: Main Floor: 20a Quantity/Condition Total Location Details: (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Layered Cardboard Insulation over 6" Pipe 532 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS Tar on Pipe Wrap 550 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
PIPING SYSTEMS Parging Cement on Fittings 500 45 0 0 45 each 80 Chrysotile Yes No A 6
FLOOR Concrete Floor 901.1 - - - - - - - - - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
CEILING Concrete Ceiling 901.2 - - - - - - - - - - -
Location: Main Floor: 20 Quantity/Condition Total Location Details: Boiler Room (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Concrete Block 927.1 - - - - - - - - - - -
WALL Baseboard Mastic 290 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VFT White With Black Streaks (9x9) 104 20.00 0.00 0.00 20.00 square meter
0.75 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 2.00 0.00 0.00 2.00 meter 55 Chrysotile Yes Yes A 6
CEILING Fibreglass CT 932 - - - - - - - - - - -
Location: Main Floor: 2 Quantity/Condition Total Location Details: V.P. Office (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
CEILING Concrete Ceiling 901.2 - - - - - - - - - - -
CEILING CT Long Fissures With Medium Pinholes (2x4) 364 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS PVC (Piping) 922 - - - - - - - - - - -
OTHER Unidentified Board Behind Radiators 815 8.00 0.00 0.00 8.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 17 Quantity/Condition Total Location Details: Staff Room (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 6Golder Associates
NOTE: All quantities listed are approximate only.
FLOOR VSF Taupe 151 25.00 0.00 0.00 25.00 square meter
15 Chrysotile No Yes A 6
Location: Main Floor: 23 Quantity/Condition Total Location Details: Resource (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Concrete Block 927.1 - - - - - - - - - - -
WALL Baseboard Mastic 290 - - - - - <LOD No Asbestos Detected
- - - -
OTHER Unidentified Board Behind Radiators 815 4.00 0.00 0.00 4.00 meter 55 Chrysotile Yes Yes A 6
CEILING Concrete Block (Ceiling) 927.2 - - - - - - - - - - -
FLOOR Carpet 930 - - - - - - - - - - -
FLOOR VSF Taupe 151 8.00 0.00 0.00 8.00 square meter
15 Chrysotile No Yes A 6
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Location: Main Floor: 22 Quantity/Condition Total Location Details: Resource (Main Floor)
CEILING Fibreglass CT 932 - - - - - - - - - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
FLOOR Terrazzo 929 - - - - - - - - - - -
PIPING SYSTEMS Parging Cement on Fittings 500 3 0 0 3 each 80 Chrysotile Yes No D 6
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
PIPING SYSTEMS Tar on Pipe Wrap 550 - - - - - <LOD No Asbestos Detected
- - - -
Location: Main Floor: 20b Quantity/Condition Total Location Details: (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Concrete Block 927.1 - - - - - - - - - - -
CEILING Fibreglass CT 932 - - - - - - - - - - -
FLOOR Terrazzo 929 - - - - - - - - - - -
Location: Main Floor: 20a Quantity/Condition Total Location Details: (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 7Golder Associates
NOTE: All quantities listed are approximate only.
WALL Concrete Block 927.1 - - - - - - - - - - -
WALL Wood Walls 909.3 - - - - - - - - - - -
FLOOR Terrazzo 929 - - - - - - - - - - -
CEILING CT Long Fissures With Medium Pinholes (2x4) 364 - - - - - <LOD No Asbestos Detected
- - - -
Location: Main Floor: 26 Quantity/Condition Total Location Details: Boy's Washroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
CEILING Concrete Block (Ceiling) 927.2 - - - - - - - - - - -
FLOOR Terrazzo 929 - - - - - - - - - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
Location: Main Floor: 25 Quantity/Condition Total Location Details: Custodian's Room (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
CEILING CT Long Fissures With Many Many Pinholes (2x4) 366 - - - - - <LOD No Asbestos Detected
- - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
FLOOR Terrazzo 929 - - - - - - - - - - -
OTHER Unidentified Board Behind Radiators 815 0.00 2.00 0.00 2.00 meter 55 Chrysotile Yes Yes A 5
CEILING Fibreglass CT 932 - - - - - - - - - - -
Location: Main Floor: 24 Quantity/Condition Total Location Details: Girl's Washroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Concrete Block 927.1 - - - - - - - - - - -
WALL Baseboard Mastic 290 - - - - - <LOD No Asbestos Detected
- - - -
CEILING Concrete Block (Ceiling) 927.2 - - - - - - - - - - -
OTHER Unidentified Board Behind Radiators 815 4.00 0.00 0.00 4.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 23 Quantity/Condition Total Location Details: Resource (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 8Golder Associates
NOTE: All quantities listed are approximate only.
WALL Concrete Block 927.1 - - - - - - - - - - -
WALL Baseboard Mastic 290 - - - - - <LOD No Asbestos Detected
- - - -
CEILING Concrete Block (Ceiling) 927.2 - - - - - - - - - - -
FLOOR VSF Taupe 151 72.00 0.00 0.00 72.00 square meter
15 Chrysotile No Yes A 6
Location: Main Floor: 28 Quantity/Condition Total Location Details: Develop H/C (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
WALL Drywall Joint Compound 200 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR Carpet 930 - - - - - - - - - - -
FLOOR VFT White, Beige and Taupe Mix (12x12) 101 - - - - - <LOD No Asbestos Detected
- - - -
WALL Baseboard Mastic 290 - - - - - <LOD No Asbestos Detected
- - - -
CEILING Concrete Block (Ceiling) 927.2 - - - - - - - - - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
Location: Main Floor: 27 Quantity/Condition Total Location Details: Fitness Room (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Concrete Block 927.1 - - - - - - - - - - -
WALL Drywall Joint Compound 200 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR Terrazzo 929 - - - - - - - - - - -
OTHER Unidentified Board Behind Radiators 815 2.00 0.00 0.00 2.00 meter 55 Chrysotile Yes Yes A 6
CEILING CT Long Fissures With Medium Pinholes (2x4) 364 - - - - - <LOD No Asbestos Detected
- - - -
Location: Main Floor: 26b Quantity/Condition Total Location Details: (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 9Golder Associates
NOTE: All quantities listed are approximate only.
FLOOR VFT Green on Green (12x12) 109 - - - - - <LOD No Asbestos Detected
- - - -
Location: Main Floor: 30 Quantity/Condition Total Location Details: Classroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
WALL Baseboard Mastic 290 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VFT Light Blue With White Streaks (9x9) 103 20.00 0.00 0.00 20.00 square meter
1.2 Chrysotile No Yes A 6
CEILING Concrete Ceiling 901.2 - - - - - - - - - - -
PIPING SYSTEMS Tar on Pipe Wrap 550 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS Parging Cement on Fittings 500 2 0 0 2 each 80 Chrysotile Yes No C 6
Location: Main Floor: 3 Quantity/Condition Total Location Details: Storage (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Concrete Block 927.1 - - - - - - - - - - -
WALL Baseboard Mastic 290 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VSF Taupe 151 70.00 0.00 0.00 70.00 square meter
15 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
CEILING Concrete Block (Ceiling) 927.2 - - - - - - - - - - -
Location: Main Floor: 29 Quantity/Condition Total Location Details: Integrated Technology (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 28 Quantity/Condition Total Location Details: Develop H/C (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 10Golder Associates
NOTE: All quantities listed are approximate only.
CEILING CT Long Fissures With Medium Pinholes (2x4) 364 - - - - - <LOD No Asbestos Detected
- - - -
CEILING CT Long Fissures With Many Many Pinholes (2x4) 366 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR Terrazzo 929 - - - - - - - - - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
CEILING CT Short Fissures in Swirl with Pinholes (2x4) 367 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS Parging Cement on Fittings 500 10 0 0 10 each 80 Chrysotile Yes No D 6
CEILING CT Small and Large Pinholes (2x4) 368 25.00 0.00 0.00 25.00 square meter
1.2 Chrysotile Yes Yes C 6
Location: Main Floor: 32 Quantity/Condition Total Location Details: Washroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
CEILING CT Long Fissures With Many Many Pinholes (2x4) 366 - - - - - <LOD No Asbestos Detected
- - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
FLOOR Terrazzo 929 - - - - - - - - - - -
CEILING CT Small and Large Pinholes (2x4) 368 25.00 0.00 0.00 25.00 square meter
1.2 Chrysotile Yes Yes C 6
OTHER Unidentified Board Behind Radiators 815 2.00 0.00 0.00 2.00 meter 55 Chrysotile Yes Yes A 6
PIPING SYSTEMS Parging Cement on Fittings 500 10 0 0 10 each 80 Chrysotile Yes No D 6
Location: Main Floor: 31 Quantity/Condition Total Location Details: Washroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Concrete Block 927.1 - - - - - - - - - - -
FLOOR VFT Taupe With White Streaks (12x12) 110 - - - - - <LOD No Asbestos Detected
- - - -
CEILING Concrete Ceiling 901.2 - - - - - - - - - - -
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 30 Quantity/Condition Total Location Details: Classroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 11Golder Associates
NOTE: All quantities listed are approximate only.
FLOOR VFT Light Grey With White Streaks (12x12) 113 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VFT Green on Green (12x12) 109 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VFT Beige With Grey Marks (12x12) 108 - - - - - <LOD No Asbestos Detected
- - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
CEILING Concrete Ceiling 901.2 - - - - - - - - - - -
Location: Main Floor: 35 Quantity/Condition Total Location Details: Classroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Concrete Block 927.1 - - - - - - - - - - -
FLOOR VFT Pink With White Streaks (9x9) 112 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VFT Light Blue With White Streaks (9x9) 103 25.00 0.00 0.00 25.00 square meter
1.2 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
CEILING Concrete Ceiling 901.2 - - - - - - - - - - -
Location: Main Floor: 34 Quantity/Condition Total Location Details: Classroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Parging Cement on Fittings 500 30 0 0 30 each 80 Chrysotile Yes No A 6
FLOOR Concrete Ceiling 901.2 - - - - - - - - - - -
PIPING SYSTEMS Layered Cardboard Insulation over 6" Pipe 532 - - - - - <LOD No Asbestos Detected
- - - -
Location: Main Floor: 33 Quantity/Condition Total Location Details: Custodian Room (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 2.00 0.00 0.00 2.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 32 Quantity/Condition Total Location Details: Washroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 12Golder Associates
NOTE: All quantities listed are approximate only.
WALL Concrete Block 927.1 - - - - - - - - - - -
FLOOR Carpet 930 - - - - - - - - - - -
FLOOR VFT White, Beige and Taupe Mix (12x12) 101 - - - - - <LOD No Asbestos Detected
- - - -
Location: Main Floor: 38 Quantity/Condition Total Location Details: Kindergarten (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
CEILING Concrete Ceiling 901.2 - - - - - - - - - - -
FLOOR VFT Green on Green (12x12) 109 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VFT White, Beige and Taupe Mix (12x12) 101 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VFT Beige With Taupe Streaks 111 - - - - - <LOD No Asbestos Detected
- - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
Location: Main Floor: 37 Quantity/Condition Total Location Details: Special Ed. (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Concrete Block 927.1 - - - - - - - - - - -
FLOOR VFT Pink With White Streaks (9x9) 112 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VFT Light Blue With White Streaks (9x9) 103 40.00 0.00 0.00 40.00 square meter
1.2 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
CEILING Concrete Ceiling 901.2 - - - - - - - - - - -
Location: Main Floor: 36 Quantity/Condition Total Location Details: Seminar Room (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 35 Quantity/Condition Total Location Details: Classroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 13Golder Associates
NOTE: All quantities listed are approximate only.
Location: Main Floor: 40 Quantity/Condition Total Location Details: Washroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Baseboard Mastic 290 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VFT Dark Blue With White Streaks (9x9) 102 32.00 0.00 0.00 32.00 square meter
1.3 Chrysotile No Yes A 6
WALL Concrete Block 927.1 - - - - - - - - - - -
OTHER Unidentified Board Behind Radiators 815 4.00 0.00 0.00 4.00 meter 55 Chrysotile Yes Yes A 6
CEILING Fibreglass CT 932 - - - - - - - - - - -
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Location: Main Floor: 4 Quantity/Condition Total Location Details: Principal's Office (Main Floor)
CEILING CT Small and Large Pinholes (2x4) 368 4.00 0.00 0.00 4.00 square meter
1.2 Chrysotile Yes Yes C 6
PIPING SYSTEMS Parging Cement on Fittings 500 4 0 0 4 each 80 Chrysotile Yes No A 6
FLOOR VSF Orange and White Mosaic 152 - - - - - <LOD No Asbestos Detected
- - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
PIPING SYSTEMS Layered Cardboard Insulation over 6" Pipe 532 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
PIPING SYSTEMS Tar on Pipe Wrap 550 - - - - - <LOD No Asbestos Detected
- - - -
Location Accessibility Issues: No Access Above Ceiling Tile
Location: Main Floor: 39 Quantity/Condition Total Location Details: Washroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
CEILING Concrete Ceiling 901.2 - - - - - - - - - - -
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 38 Quantity/Condition Total Location Details: Kindergarten (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 14Golder Associates
NOTE: All quantities listed are approximate only.
WALL Concrete Block 927.1 - - - - - - - - - - -
WALL Baseboard Mastic 290 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VSF Taupe 151 74.00 0.00 0.00 74.00 square meter
15 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
CEILING Concrete Block (Ceiling) 927.2 - - - - - - - - - - -
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Location: Main Floor: 42 Quantity/Condition Total Location Details: Classroom (Main Floor)
WALL Baseboard Mastic 290 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR Concrete Block 927.1 - - - - - - - - - - -
FLOOR VSF Taupe 151 72.00 0.00 0.00 72.00 square meter
15 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
CEILING Concrete Block (Ceiling) 927.2 - - - - - - - - - - -
Location: Main Floor: 41 Quantity/Condition Total Location Details: Classroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Tar on Pipe Wrap 550 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS Parging Cement on Fittings 500 4 0 0 4 each 80 Chrysotile Yes No A 6
CEILING CT Small and Large Pinholes (2x4) 368 4.00 0.00 0.00 4.00 square meter
1.2 Chrysotile Yes Yes C 6
FLOOR VSF Orange and White Mosaic 152 - - - - - <LOD No Asbestos Detected
- - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
Location Accessibility Issues: No Access Above Ceiling Tile
Location: Main Floor: 40 Quantity/Condition Total Location Details: Washroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 15Golder Associates
NOTE: All quantities listed are approximate only.
WALL Concrete Block 927.1 - - - - - - - - - - -
FLOOR VFT Dark Grey, Light Grey and White Mix (12x12) 107 - - - - - <LOD No Asbestos Detected
- - - -
Location: Main Floor: 46 Quantity/Condition Total Location Details: Storage (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
CEILING Concrete Ceiling 901.2 - - - - - - - - - - -
STRUCTURE Wood Floors 909.1 - - - - - - - - - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
Location: Main Floor: 45 Quantity/Condition Total Location Details: Stage (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Concrete Block 927.1 - - - - - - - - - - -
FLOOR VFT Dark Grey, Light Grey and White Mix (12x12) 107 - - - - - <LOD No Asbestos Detected
- - - -
CEILING Wood Ceiling 909.2 - - - - - - - - - - -
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
Location: Main Floor: 44 Quantity/Condition Total Location Details: Storage/ Fan Room (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Concrete Block 927.1 - - - - - - - - - - -
CEILING Concrete Block (Ceiling) 927.2 - - - - - - - - - - -
FLOOR Carpet 930 - - - - - - - - - - -
WALL Drywall Joint Compound 200 - - - - - <LOD No Asbestos Detected
- - - -
OTHER Unidentified Board Behind Radiators 815 25.00 0.00 0.00 25.00 meter 55 Chrysotile Yes Yes A 6
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
PIPING SYSTEMS Tar on Pipe Wrap 550 - - - - - <LOD No Asbestos Detected
- - - -
Location: Main Floor: 43 Quantity/Condition Total Location Details: Library (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 16Golder Associates
NOTE: All quantities listed are approximate only.
WALL Concrete Block 927.1 - - - - - - - - - - -
FLOOR VFT Beige With Taupe Streaks 111 - - - - - <LOD No Asbestos Detected
- - - -
CEILING Concrete Block (Ceiling) 927.2 - - - - - - - - - - -
FLOOR VFT Taupe With White Streaks (12x12) 110 - - - - - <LOD No Asbestos Detected
- - - -
Location: Second Floor: 49 Quantity/Condition Total Location Details: Classroom (Second Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Concrete Block 927.1 - - - - - - - - - - -
FLOOR VFT Beige With Taupe Streaks 111 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VFT Taupe With White Streaks (12x12) 110 - - - - - <LOD No Asbestos Detected
- - - -
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
CEILING Concrete Block (Ceiling) 927.2 - - - - - - - - - - -
Location: Second Floor: 48 Quantity/Condition Total Location Details: Classroom (Second Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
FLOOR VFT Beige With Grey Marks (12x12) 108 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VFT Dark Grey, Light Grey and White Mix (12x12) 107 - - - - - <LOD No Asbestos Detected
- - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
CEILING Concrete Ceiling 901.2 - - - - - - - - - - -
Location: Main Floor: 47 Quantity/Condition Total Location Details: Gymnasium (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
CEILING Wood Ceiling 909.2 - - - - - - - - - - -
Location: Main Floor: 46 Quantity/Condition Total Location Details: Storage (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 17Golder Associates
NOTE: All quantities listed are approximate only.
WALL Baseboard Mastic 290 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VFT Light Grey With White Streaks (12x12) 113 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VFT Green on Green (12x12) 109 - - - - - <LOD No Asbestos Detected
- - - -
Location: Second Floor: 51 Quantity/Condition Total Location Details: Classroom (Second Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
CEILING Concrete Block (Ceiling) 927.2 - - - - - - - - - - -
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
WALL Concrete Block 927.1 - - - - - - - - - - -
FLOOR VFT Green on Green (12x12) 109 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VFT Light Grey With White Streaks (12x12) 113 - - - - - <LOD No Asbestos Detected
- - - -
Location: Second Floor: 50 Quantity/Condition Total Location Details: Classroom (Second Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
CEILING Concrete Ceiling 901.2 - - - - - - - - - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
FLOOR Concrete Floor 901.1 - - - - - - - - - - -
PIPING SYSTEMS Parging Cement on Fittings 500 4 0 0 4 each 80 Chrysotile Yes No D 6
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
PIPING SYSTEMS Tar on Pipe Wrap 550 - - - - - <LOD No Asbestos Detected
- - - -
Location: Main Floor: 5 Quantity/Condition Total Location Details: Custodian Room (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Second Floor: 49 Quantity/Condition Total Location Details: Classroom (Second Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 18Golder Associates
NOTE: All quantities listed are approximate only.
CEILING Concrete Block (Ceiling) 927.2 - - - - - - - - - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
FLOOR Terrazzo 929 - - - - - - - - - - -
PIPING SYSTEMS Parging Cement on Fittings 500 3 0 0 3 each 80 Chrysotile Yes No A 6
Location: Second Floor: 54 Quantity/Condition Total Location Details: Custodian Room (Second Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 2.00 0.00 0.00 2.00 meter 55 Chrysotile Yes Yes A 6
WALL Concrete Block 927.1 - - - - - - - - - - -
FLOOR Terrazzo 929 - - - - - - - - - - -
CEILING CT Small and Large Pinholes (2x4) 368 25.00 0.00 0.00 25.00 square meter
1.2 Chrysotile Yes Yes C 6
Location: Second Floor: 53 Quantity/Condition Total Location Details: Washroom (Second Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Concrete Block 927.1 - - - - - - - - - - -
FLOOR VFT Beige With Taupe Streaks 111 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VFT Taupe With White Streaks (12x12) 110 - - - - - <LOD No Asbestos Detected
- - - -
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
CEILING Concrete Block (Ceiling) 927.2 - - - - - - - - - - -
Location: Second Floor: 52 Quantity/Condition Total Location Details: Classroom (Second Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
CEILING Concrete Block (Ceiling) 927.2 - - - - - - - - - - -
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
WALL Concrete Block 927.1 - - - - - - - - - - -
Location: Second Floor: 51 Quantity/Condition Total Location Details: Classroom (Second Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 19Golder Associates
NOTE: All quantities listed are approximate only.
WALL Concrete Block 927.1 - - - - - - - - - - -
WALL Baseboard Mastic 290 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VFT Taupe With White Streaks (12x12) 110 - - - - - <LOD No Asbestos Detected
- - - -
CEILING Concrete Block (Ceiling) 927.2 - - - - - - - - - - -
PIPING SYSTEMS Parging Cement on Fittings 500 2 0 0 2 each 80 Chrysotile Yes No C 6
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Location: Second Floor: 57 Quantity/Condition Total Location Details: Classroom (Second Floor)
FLOOR VFT Brown With Taupe Streaks (12x12) 115 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VFT Taupe With White Streaks (12x12) 110 - - - - - <LOD No Asbestos Detected
- - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
OTHER Unidentified Board Behind Radiators 815 12.00 0.00 0.00 12.00 meter 55 Chrysotile Yes Yes A 6
CEILING Concrete Block (Ceiling) 927.2 - - - - - - - - - - -
Location: Second Floor: 56 Quantity/Condition Total Location Details: Classroom (Second Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Concrete Block 927.1 - - - - - - - - - - -
FLOOR Terrazzo 929 - - - - - - - - - - -
CEILING CT Small and Large Pinholes (2x4) 368 25.00 0.00 0.00 25.00 square meter
1.2 Chrysotile Yes Yes C 6
OTHER Unidentified Board Behind Radiators 815 2.00 0.00 0.00 2.00 meter 55 Chrysotile Yes Yes A 6
Location: Second Floor: 55 Quantity/Condition Total Location Details: Washroom (Second Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Layered Cardboard Insulation over 6" Pipe 532 - - - - - <LOD No Asbestos Detected
- - - -
Location: Second Floor: 54 Quantity/Condition Total Location Details: Custodian Room (Second Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 20Golder Associates
NOTE: All quantities listed are approximate only.
WALL Concrete Block 927.1 - - - - - - - - - - -
CEILING Concrete Ceiling 901.2 - - - - - - - - - - -
FLOOR VFT White With Black Streaks (9x9) 104 5.00 0.00 0.00 5.00 square meter
0.75 Chrysotile No Yes A 6
WALL Baseboard Mastic 290 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS Tar on Pipe Wrap 550 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
FLOOR VFT Light Blue With White Streaks (9x9) 103 72.00 0.00 0.00 72.00 square meter
1.2 Chrysotile No Yes A 6
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Location: Main Floor: 7 Quantity/Condition Total Location Details: Classroom (Main Floor)
CEILING Concrete Ceiling 901.2 - - - - - - - - - - -
WALL Baseboard Mastic 290 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VFT Light Blue With White Streaks (9x9) 103 68.00 0.00 0.00 68.00 square meter
1.2 Chrysotile No Yes A 6
FLOOR VFT White With Black Streaks (9x9) 104 5.00 0.00 0.00 5.00 square meter
0.75 Chrysotile No Yes A 6
PIPING SYSTEMS Tar on Pipe Wrap 550 - - - - - <LOD No Asbestos Detected
- - - -
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
PIPING SYSTEMS Synthetic Insulation on Elbow 936 - - - - - - - - - - -
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
Location: Main Floor: 6 Quantity/Condition Total Location Details: Integrated Technology (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Layered Cardboard Insulation over 6" Pipe 532 - - - - - <LOD No Asbestos Detected
- - - -
Location: Second Floor: 57 Quantity/Condition Total Location Details: Classroom (Second Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 21Golder Associates
NOTE: All quantities listed are approximate only.
WALL Drywall Joint Compound 200 - - - - - <LOD No Asbestos Detected
- - - -
WALL Baseboard Mastic 290 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR Carpet 930 - - - - - - - - - - -
FLOOR VFT Light Blue With White Streaks (9x9) 103 25.00 0.00 0.00 25.00 square meter
1.2 Chrysotile No Yes A 6
FLOOR VFT White With Black Streaks (9x9) 104 10.00 0.00 0.00 10.00 square meter
0.75 Chrysotile No Yes A 6
WALL Concrete Block 927.1 - - - - - - - - - - -
CEILING Concrete Ceiling 901.2 - - - - - - - - - - -
FLOOR VFT Dark Blue With White Streaks (9x9) 102 60.00 0.00 0.00 60.00 square meter
1.3 Chrysotile No Yes A 6
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Location: Main Floor: 9 Quantity/Condition Total Location Details: Con. Ed. Classroom (Main Floor)
WALL Baseboard Mastic 290 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR VFT White With Black Streaks (9x9) 104 5.00 0.00 0.00 5.00 square meter
0.75 Chrysotile No Yes A 6
FLOOR VFT Light Blue With White Streaks (9x9) 103 72.00 0.00 0.00 72.00 square meter
1.2 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
CEILING Concrete Ceiling 901.2 - - - - - - - - - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
Location: Main Floor: 8 Quantity/Condition Total Location Details: Classroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Synthetic Insulation on Elbow 936 - - - - - - - - - - -
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 7 Quantity/Condition Total Location Details: Classroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 22Golder Associates
NOTE: All quantities listed are approximate only.
FLOOR Terrazzo 929 - - - - - - - - - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
Location: Main Floor: B Quantity/Condition Total Location Details: Corridor B (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
PIPING SYSTEMS Middle Tar Paper in Pipe Insulation 551 - - - - - <LOD No Asbestos Detected
- - - -
CEILING CT Long Fissures With Many Many pinholes (2x2) 361 - - - - - <LOD No Asbestos Detected
- - - -
CEILING Concrete Ceiling 901.2 - - - - - - - - - - -
CEILING CT Small Fissures in Swirl With Pinholes (2x2) 360 - - - - - <LOD No Asbestos Detected
- - - -
FLOOR Terrazzo 929 - - - - - - - - - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
PIPING SYSTEMS Inner Paper Pipe Insulation 531 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS Tar on Pipe Wrap 550 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS Parging Cement on Fittings 500 100 0 0 100 each 80 Chrysotile Yes No D 6
PIPING SYSTEMS Outer Paper Pipe Insulation 530 - - - - - <LOD No Asbestos Detected
- - - -
Location: Main Floor: A Quantity/Condition Total Location Details: Corridor A (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
PIPING SYSTEMS Tar on Pipe Wrap 550 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS Synthetic Insulation on Elbow 936 - - - - - - - - - - -
OTHER Unidentified Board Behind Radiators 815 25.00 0.00 0.00 25.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 9 Quantity/Condition Total Location Details: Con. Ed. Classroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 23Golder Associates
NOTE: All quantities listed are approximate only.
FLOOR Terrazzo 929 - - - - - - - - - - -
WALL Drywall Joint Compound 200 - - - - - <LOD No Asbestos Detected
- - - -
Location: Main Floor: D Quantity/Condition Total Location Details: Vestibule D (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Tar on Pipe Wrap 550 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
WALL Plaster Above Doors 210 5.00 0.00 0.00 5.00 square meter
0.75 Chrysotile Yes Yes C 6
FLOOR Terrazzo 929 - - - - - - - - - - -
FLOOR Concrete Floor 927.3 - - - - - - - - - - -
CEILING CT Long Fissures With Many Many pinholes (2x2) 361 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS Parging Cement on Fittings 500 30 0 0 30 each 80 Chrysotile Yes No D 6
CEILING CT Long Fissures With Few Pinholes (2x2) 363 - - - - - <LOD No Asbestos Detected
- - - -
Location: Main Floor: C Quantity/Condition Total Location Details: Corridor C (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Outer Paper Pipe Insulation 530 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS Parging Cement on Fittings 500 70 0 0 70 each 80 Chrysotile Yes No D 6
CEILING CT Long Fissures With Few Pinholes (2x2) 363 - - - - - <LOD No Asbestos Detected
- - - -
CEILING CT Long Fissures With Many Many pinholes (2x2) 361 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS Middle Tar Paper in Pipe Insulation 551 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS Inner Paper Pipe Insulation 531 - - - - - <LOD No Asbestos Detected
- - - -
Location: Main Floor: B Quantity/Condition Total Location Details: Corridor B (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 24Golder Associates
NOTE: All quantities listed are approximate only.
FLOOR Terrazzo 929 - - - - - - - - - - -
Location: Main Floor: F Quantity/Condition Total Location Details: Vestibule F (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Tar on Pipe Wrap 550 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
PIPING SYSTEMS Parging Cement on Fittings 500 35 0 0 35 each 80 Chrysotile Yes No D 6
CEILING CT Long Fissures With Medium Pinholes (2x4) 364 - - - - - <LOD No Asbestos Detected
- - - -
WALL Concrete Block 927.1 - - - - - - - - - - -
FLOOR Terrazzo 929 - - - - - - - - - - -
CEILING CT Short Fissures in Swirl with Pinholes (2x4) 367 - - - - - <LOD No Asbestos Detected
- - - -
CEILING CT Long Fissures With Many Many Pinholes (2x4) 366 - - - - - <LOD No Asbestos Detected
- - - -
Location: Main Floor: E Quantity/Condition Total Location Details: Corridor E (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Concrete Block 927.1 - - - - - - - - - - -
CEILING CT Short Fissures With Few Pinholes (2x4) 365 - - - - - <LOD No Asbestos Detected
- - - -
WALL Plaster Above Doors 210 5.00 0.00 0.00 5.00 square meter
0.75 Chrysotile Yes Yes C 6
WALL Brick 916 - - - - - - - - - - -
CEILING CT Long Fissures With Many Many Pinholes (2x4) 366 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
PIPING SYSTEMS Tar on Pipe Wrap 550 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS Parging Cement on Fittings 500 8 0 0 8 each 80 Chrysotile Yes No D 6
Location: Main Floor: D Quantity/Condition Total Location Details: Vestibule D (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 25Golder Associates
NOTE: All quantities listed are approximate only.
WALL Concrete Block 927.1 - - - - - - - - - - -
FLOOR Terrazzo 929 - - - - - - - - - - -
CEILING CT Small and Large Pinholes (2x4) 368 155.00 0.00 0.00 155.00 square meter
1.2 Chrysotile Yes Yes C 6
PIPING SYSTEMS Parging Cement on Fittings 500 27 0 0 27 each 80 Chrysotile Yes No D 6
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Location: Main Floor: H Quantity/Condition Total Location Details: Corridor H (Main Floor)
WALL Concrete Block 927.1 - - - - - - - - - - -
CEILING CT Small and Large Pinholes (2x4) 368 45.00 0.00 0.00 45.00 square meter
1.2 Chrysotile Yes Yes C 6
FLOOR Terrazzo 929 - - - - - - - - - - -
WALL Brick 916 - - - - - - - - - - -
PIPING SYSTEMS Tar on Pipe Wrap 550 - - - - - <LOD No Asbestos Detected
- - - -
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
STRUCTURE Metal 903.2 - - - - - - - - - - -
PIPING SYSTEMS Parging Cement on Fittings 500 5 2 0 7 each 80 Chrysotile Yes No A 5
Location: Main Floor: G Quantity/Condition Total Location Details: Stairwell (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
CEILING CT Long Fissures With Many Many Pinholes (2x4) 366 - - - - - <LOD No Asbestos Detected
- - - -
CEILING CT Long Fissures With Medium Pinholes (2x4) 364 - - - - - <LOD No Asbestos Detected
- - - -
WALL Brick 916 - - - - - - - - - - -
PIPING SYSTEMS Parging Cement on Fittings 500 30 0 0 30 each 80 Chrysotile Yes No D 6
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
PIPING SYSTEMS Tar on Pipe Wrap 550 - - - - - <LOD No Asbestos Detected
- - - -
Location: Main Floor: F Quantity/Condition Total Location Details: Vestibule F (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 26Golder Associates
NOTE: All quantities listed are approximate only.
WALL Brick 916 - - - - - - - - - - -
STRUCTURE Exterior Plaster 310 10.00 0.00 0.00 10.00 square meter
1.2 Chrysotile Yes Yes C 6
WALL Metal Panels (Exterior) 903.1 - - - - - - - - - - -
WALL Gravel (Roof) 911 - - - - - - - - - - -
STRUCTURE Concrete Over hang (Exterior) 901.3 - - - - - - - - - - -
Location: Exterior: K Quantity/Condition Total Location Details: Exterior (Outside)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Concrete Block 927.1 - - - - - - - - - - -
FLOOR Terrazzo 929 - - - - - - - - - - -
CEILING CT Short Fissures in Swirl with Pinholes (2x4) 367 - - - - - <LOD No Asbestos Detected
- - - -
CEILING CT Small and Large Pinholes (2x4) 368 155.00 0.00 0.00 155.00 square meter
1.2 Chrysotile Yes Yes C 6
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Location: Second Floor: J Quantity/Condition Total Location Details: Corridor J (Second Floor)
CEILING CT Small and Large Pinholes (2x4) 368 40.00 0.00 0.00 40.00 square meter
1.2 Chrysotile Yes Yes C 6
WALL Concrete Block 927.1 - - - - - - - - - - -
FLOOR Terrazzo 929 - - - - - - - - - - -
STRUCTURE Metal 903.2 - - - - - - - - - - -
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
PIPING SYSTEMS Parging Cement on Fittings 500 10 0 0 10 each 80 Chrysotile Yes No D 6
Location: Main Floor: I Quantity/Condition Total Location Details: Stairwell I (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Fibreglass Straight Pipe 918 - - - - - - - - - - -
Location: Main Floor: H Quantity/Condition Total Location Details: Corridor H (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
All Components
Table A-3: Summary Report By Location
Page: 27Golder Associates
NOTE: All quantities listed are approximate only.
OTHER Rubber (Window Caulking) 912 - - - - - - - - - - -
OTHER Roof Flashing 914 - - - - - - - - - - -
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Location: Exterior: K Quantity/Condition Total Location Details: Exterior (Outside)
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Confirmed and Presumed ACM
Table A-4: Summary Report By Location
Page: 1Golder Associates
NOTE: All quantities listed are approximate only.
FLOOR VFT White With Black Streaks (9x9) 104 5.00 0.00 0.00 5.00 square meter
0.75 Chrysotile No Yes A 6
FLOOR VFT Light Blue With White Streaks (9x9) 103 68.00 0.00 0.00 68.00 square meter
1.2 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 12 Quantity/Condition Total Location Details: Classroom #6 (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 11 Quantity/Condition Total Location Details: Music (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Wall Board 824 1.00 0.00 0.00 1.00 square meter
80 Amosite No Yes A 6
Location: Main Floor: 10a Quantity/Condition Total Location Details: Storage (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 0.00 0.00 7.50 7.50 meter 55 Chrysotile Yes Yes A 3
Location: Main Floor: 10 Quantity/Condition Total Location Details: Con. Ed. Classroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
FLOOR VFT Dark Blue With White Streaks (9x9) 102 30.00 0.00 0.00 30.00 square meter
1.3 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 7.50 0.00 0.00 7.50 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 1 Quantity/Condition Total Location Details: Office (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Confirmed and Presumed ACM
Table A-4: Summary Report By Location
Page: 2Golder Associates
NOTE: All quantities listed are approximate only.
OTHER Unidentified Board Behind Radiators 815 8.00 0.00 0.00 8.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 17 Quantity/Condition Total Location Details: Staff Room (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 2.00 0.00 0.00 2.00 meter 55 Chrysotile Yes Yes A 6
PIPING SYSTEMS Parging Cement on Fittings 500 2 0 0 2 each 80 Chrysotile Yes No D 6
Location Accessibility Issues:
Location: Main Floor: 16 Quantity/Condition Total Location Details: Washroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Parging Cement on Fittings 500 2 0 0 2 each 80 Chrysotile Yes No D 6
OTHER Unidentified Board Behind Radiators 815 2.00 0.00 0.00 2.00 meter 55 Chrysotile Yes Yes A 6
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Location: Main Floor: 15 Quantity/Condition Total Location Details: Washroom (Main Floor)
FLOOR VFT White With Black Streaks (9x9) 104 5.00 0.00 0.00 5.00 square meter
0.75 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
FLOOR VFT Light Blue With White Streaks (9x9) 103 68.00 0.00 0.00 68.00 square meter
1.2 Chrysotile No Yes A 6
Location: Main Floor: 14 Quantity/Condition Total Location Details: Classroom #2 (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
FLOOR VFT White With Black Streaks (9x9) 104 5.00 0.00 0.00 5.00 square meter
0.75 Chrysotile No Yes A 6
FLOOR VFT Light Blue With White Streaks (9x9) 103 68.00 0.00 0.00 68.00 square meter
1.2 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 13 Quantity/Condition Total Location Details: Classroom #4 (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Confirmed and Presumed ACM
Table A-4: Summary Report By Location
Page: 3Golder Associates
NOTE: All quantities listed are approximate only.
OTHER Unidentified Board Behind Radiators 815 0.00 2.00 0.00 2.00 meter 55 Chrysotile Yes Yes A 5
Location: Main Floor: 24 Quantity/Condition Total Location Details: Girl's Washroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 4.00 0.00 0.00 4.00 meter 55 Chrysotile Yes Yes A 6
FLOOR VSF Taupe 151 25.00 0.00 0.00 25.00 square meter
15 Chrysotile No Yes A 6
Location: Main Floor: 23 Quantity/Condition Total Location Details: Resource (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
FLOOR VSF Taupe 151 8.00 0.00 0.00 8.00 square meter
15 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 4.00 0.00 0.00 4.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 22 Quantity/Condition Total Location Details: Resource (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Parging Cement on Fittings 500 3 0 0 3 each 80 Chrysotile Yes No D 6
Location: Main Floor: 20b Quantity/Condition Total Location Details: (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Parging Cement on Fittings 500 45 0 0 45 each 80 Chrysotile Yes No A 6
Location: Main Floor: 20 Quantity/Condition Total Location Details: Boiler Room (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 2.00 0.00 0.00 2.00 meter 55 Chrysotile Yes Yes A 6
FLOOR VFT White With Black Streaks (9x9) 104 20.00 0.00 0.00 20.00 square meter
0.75 Chrysotile No Yes A 6
Location: Main Floor: 2 Quantity/Condition Total Location Details: V.P. Office (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Confirmed and Presumed ACM
Table A-4: Summary Report By Location
Page: 4Golder Associates
NOTE: All quantities listed are approximate only.
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 30 Quantity/Condition Total Location Details: Classroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
FLOOR VFT Light Blue With White Streaks (9x9) 103 20.00 0.00 0.00 20.00 square meter
1.2 Chrysotile No Yes A 6
PIPING SYSTEMS Parging Cement on Fittings 500 2 0 0 2 each 80 Chrysotile Yes No C 6
Location: Main Floor: 3 Quantity/Condition Total Location Details: Storage (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
FLOOR VSF Taupe 151 70.00 0.00 0.00 70.00 square meter
15 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 29 Quantity/Condition Total Location Details: Integrated Technology (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
FLOOR VSF Taupe 151 72.00 0.00 0.00 72.00 square meter
15 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 28 Quantity/Condition Total Location Details: Develop H/C (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 27 Quantity/Condition Total Location Details: Fitness Room (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 2.00 0.00 0.00 2.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 26b Quantity/Condition Total Location Details: (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Confirmed and Presumed ACM
Table A-4: Summary Report By Location
Page: 5Golder Associates
NOTE: All quantities listed are approximate only.
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 35 Quantity/Condition Total Location Details: Classroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
FLOOR VFT Light Blue With White Streaks (9x9) 103 25.00 0.00 0.00 25.00 square meter
1.2 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Location: Main Floor: 34 Quantity/Condition Total Location Details: Classroom (Main Floor)
PIPING SYSTEMS Parging Cement on Fittings 500 30 0 0 30 each 80 Chrysotile Yes No A 6
Location: Main Floor: 33 Quantity/Condition Total Location Details: Custodian Room (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Parging Cement on Fittings 500 10 0 0 10 each 80 Chrysotile Yes No D 6
CEILING CT Small and Large Pinholes (2x4) 368 25.00 0.00 0.00 25.00 square meter
1.2 Chrysotile Yes Yes C 6
OTHER Unidentified Board Behind Radiators 815 2.00 0.00 0.00 2.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 32 Quantity/Condition Total Location Details: Washroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Parging Cement on Fittings 500 10 0 0 10 each 80 Chrysotile Yes No D 6
CEILING CT Small and Large Pinholes (2x4) 368 25.00 0.00 0.00 25.00 square meter
1.2 Chrysotile Yes Yes C 6
OTHER Unidentified Board Behind Radiators 815 2.00 0.00 0.00 2.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 31 Quantity/Condition Total Location Details: Washroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Confirmed and Presumed ACM
Table A-4: Summary Report By Location
Page: 6Golder Associates
NOTE: All quantities listed are approximate only.
Location: Main Floor: 40 Quantity/Condition Total Location Details: Washroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
FLOOR VFT Dark Blue With White Streaks (9x9) 102 32.00 0.00 0.00 32.00 square meter
1.3 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 4.00 0.00 0.00 4.00 meter 55 Chrysotile Yes Yes A 6
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Location: Main Floor: 4 Quantity/Condition Total Location Details: Principal's Office (Main Floor)
CEILING CT Small and Large Pinholes (2x4) 368 4.00 0.00 0.00 4.00 square meter
1.2 Chrysotile Yes Yes C 6
PIPING SYSTEMS Parging Cement on Fittings 500 4 0 0 4 each 80 Chrysotile Yes No A 6
Location Accessibility Issues: No Access Above Ceiling Tile
Location: Main Floor: 39 Quantity/Condition Total Location Details: Washroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 38 Quantity/Condition Total Location Details: Kindergarten (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 37 Quantity/Condition Total Location Details: Special Ed. (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
FLOOR VFT Light Blue With White Streaks (9x9) 103 40.00 0.00 0.00 40.00 square meter
1.2 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 36 Quantity/Condition Total Location Details: Seminar Room (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Confirmed and Presumed ACM
Table A-4: Summary Report By Location
Page: 7Golder Associates
NOTE: All quantities listed are approximate only.
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Second Floor: 49 Quantity/Condition Total Location Details: Classroom (Second Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Second Floor: 48 Quantity/Condition Total Location Details: Classroom (Second Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 25.00 0.00 0.00 25.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 43 Quantity/Condition Total Location Details: Library (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
FLOOR VSF Taupe 151 74.00 0.00 0.00 74.00 square meter
15 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 42 Quantity/Condition Total Location Details: Classroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
FLOOR VSF Taupe 151 72.00 0.00 0.00 72.00 square meter
15 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 41 Quantity/Condition Total Location Details: Classroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Parging Cement on Fittings 500 4 0 0 4 each 80 Chrysotile Yes No A 6
CEILING CT Small and Large Pinholes (2x4) 368 4.00 0.00 0.00 4.00 square meter
1.2 Chrysotile Yes Yes C 6
Location Accessibility Issues: No Access Above Ceiling Tile
Location: Main Floor: 40 Quantity/Condition Total Location Details: Washroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Confirmed and Presumed ACM
Table A-4: Summary Report By Location
Page: 8Golder Associates
NOTE: All quantities listed are approximate only.
Location: Second Floor: 55 Quantity/Condition Total Location Details: Washroom (Second Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Parging Cement on Fittings 500 3 0 0 3 each 80 Chrysotile Yes No A 6
Location: Second Floor: 54 Quantity/Condition Total Location Details: Custodian Room (Second Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 2.00 0.00 0.00 2.00 meter 55 Chrysotile Yes Yes A 6
CEILING CT Small and Large Pinholes (2x4) 368 25.00 0.00 0.00 25.00 square meter
1.2 Chrysotile Yes Yes C 6
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Location: Second Floor: 53 Quantity/Condition Total Location Details: Washroom (Second Floor)
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Second Floor: 52 Quantity/Condition Total Location Details: Classroom (Second Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Second Floor: 51 Quantity/Condition Total Location Details: Classroom (Second Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Second Floor: 50 Quantity/Condition Total Location Details: Classroom (Second Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Parging Cement on Fittings 500 4 0 0 4 each 80 Chrysotile Yes No D 6
Location: Main Floor: 5 Quantity/Condition Total Location Details: Custodian Room (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Confirmed and Presumed ACM
Table A-4: Summary Report By Location
Page: 9Golder Associates
NOTE: All quantities listed are approximate only.
FLOOR VFT White With Black Streaks (9x9) 104 5.00 0.00 0.00 5.00 square meter
0.75 Chrysotile No Yes A 6
FLOOR VFT Light Blue With White Streaks (9x9) 103 72.00 0.00 0.00 72.00 square meter
1.2 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Location: Main Floor: 7 Quantity/Condition Total Location Details: Classroom (Main Floor)
FLOOR VFT White With Black Streaks (9x9) 104 5.00 0.00 0.00 5.00 square meter
0.75 Chrysotile No Yes A 6
FLOOR VFT Light Blue With White Streaks (9x9) 103 68.00 0.00 0.00 68.00 square meter
1.2 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 6 Quantity/Condition Total Location Details: Integrated Technology (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Parging Cement on Fittings 500 2 0 0 2 each 80 Chrysotile Yes No C 6
Location: Second Floor: 57 Quantity/Condition Total Location Details: Classroom (Second Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 12.00 0.00 0.00 12.00 meter 55 Chrysotile Yes Yes A 6
Location: Second Floor: 56 Quantity/Condition Total Location Details: Classroom (Second Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
OTHER Unidentified Board Behind Radiators 815 2.00 0.00 0.00 2.00 meter 55 Chrysotile Yes Yes A 6
CEILING CT Small and Large Pinholes (2x4) 368 25.00 0.00 0.00 25.00 square meter
1.2 Chrysotile Yes Yes C 6
Location: Second Floor: 55 Quantity/Condition Total Location Details: Washroom (Second Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Confirmed and Presumed ACM
Table A-4: Summary Report By Location
Page: 10Golder Associates
NOTE: All quantities listed are approximate only.
WALL Plaster Above Doors 210 5.00 0.00 0.00 5.00 square meter
0.75 Chrysotile Yes Yes C 6
PIPING SYSTEMS Parging Cement on Fittings 500 30 0 0 30 each 80 Chrysotile Yes No D 6
Location: Main Floor: C Quantity/Condition Total Location Details: Corridor C (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Parging Cement on Fittings 500 70 0 0 70 each 80 Chrysotile Yes No D 6
Location: Main Floor: B Quantity/Condition Total Location Details: Corridor B (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Parging Cement on Fittings 500 100 0 0 100 each 80 Chrysotile Yes No D 6
Location: Main Floor: A Quantity/Condition Total Location Details: Corridor A (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
FLOOR VFT White With Black Streaks (9x9) 104 10.00 0.00 0.00 10.00 square meter
0.75 Chrysotile No Yes A 6
FLOOR VFT Light Blue With White Streaks (9x9) 103 25.00 0.00 0.00 25.00 square meter
1.2 Chrysotile No Yes A 6
FLOOR VFT Dark Blue With White Streaks (9x9) 102 60.00 0.00 0.00 60.00 square meter
1.3 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 25.00 0.00 0.00 25.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 9 Quantity/Condition Total Location Details: Con. Ed. Classroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
FLOOR VFT White With Black Streaks (9x9) 104 5.00 0.00 0.00 5.00 square meter
0.75 Chrysotile No Yes A 6
FLOOR VFT Light Blue With White Streaks (9x9) 103 72.00 0.00 0.00 72.00 square meter
1.2 Chrysotile No Yes A 6
OTHER Unidentified Board Behind Radiators 815 10.00 0.00 0.00 10.00 meter 55 Chrysotile Yes Yes A 6
Location: Main Floor: 8 Quantity/Condition Total Location Details: Classroom (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Confirmed and Presumed ACM
Table A-4: Summary Report By Location
Page: 11Golder Associates
NOTE: All quantities listed are approximate only.
CEILING CT Small and Large Pinholes (2x4) 368 40.00 0.00 0.00 40.00 square meter
1.2 Chrysotile Yes Yes C 6
Location: Main Floor: I Quantity/Condition Total Location Details: Stairwell I (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
CEILING CT Small and Large Pinholes (2x4) 368 155.00 0.00 0.00 155.00 square meter
1.2 Chrysotile Yes Yes C 6
PIPING SYSTEMS Parging Cement on Fittings 500 27 0 0 27 each 80 Chrysotile Yes No D 6
Location: Main Floor: H Quantity/Condition Total Location Details: Corridor H (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
CEILING CT Small and Large Pinholes (2x4) 368 45.00 0.00 0.00 45.00 square meter
1.2 Chrysotile Yes Yes C 6
PIPING SYSTEMS Parging Cement on Fittings 500 5 2 0 7 each 80 Chrysotile Yes No A 5
Location: Main Floor: G Quantity/Condition Total Location Details: Stairwell (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Parging Cement on Fittings 500 30 0 0 30 each 80 Chrysotile Yes No D 6
Location: Main Floor: F Quantity/Condition Total Location Details: Vestibule F (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
PIPING SYSTEMS Parging Cement on Fittings 500 35 0 0 35 each 80 Chrysotile Yes No D 6
Location: Main Floor: E Quantity/Condition Total Location Details: Corridor E (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
WALL Plaster Above Doors 210 5.00 0.00 0.00 5.00 square meter
0.75 Chrysotile Yes Yes C 6
PIPING SYSTEMS Parging Cement on Fittings 500 8 0 0 8 each 80 Chrysotile Yes No D 6
Location: Main Floor: D Quantity/Condition Total Location Details: Vestibule D (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Date: 6/8/2007
Job Number : 06-1135-044Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Confirmed and Presumed ACM
Table A-4: Summary Report By Location
Page: 12Golder Associates
NOTE: All quantities listed are approximate only.
STRUCTURE Exterior Plaster 310 10.00 0.00 0.00 10.00 square meter
1.2 Chrysotile Yes Yes C 6
Location: Exterior: K Quantity/Condition Total Location Details: Exterior (Outside)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
CEILING CT Small and Large Pinholes (2x4) 368 155.00 0.00 0.00 155.00 square meter
1.2 Chrysotile Yes Yes C 6
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Location: Second Floor: J Quantity/Condition Total Location Details: Corridor J (Second Floor)
PIPING SYSTEMS Parging Cement on Fittings 500 10 0 0 10 each 80 Chrysotile Yes No D 6
Location: Main Floor: I Quantity/Condition Total Location Details: Stairwell I (Main Floor)
System Material Description Component Good Fair Poor Quantity Units Asbestos % Asbestos Type
Friable Visible Accessibility Action Code
Building: Waverley Drive PS
Action Item Summary Report
Date: 6/8/2007 8:49:48 PM
Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Job Number : 06-1135-044
Table A-5
Page: 1Golder Associates
NOTE: All quantities listed are approximate only.
Main Floor G Stairwell 5 2 0 7 each No Good
Component System Material Category Description of Material Good Fair Poor Quantity Units Content % Type
Component Details Totals for Component Asbestos Content
Floor Location Location Description Good Fair Poor Quantity Units Visible Condition Details
500 PIPING SYSTEMS Thermal System Insulation
Parging Cement on Fittings 5.00 2.00 0 7.00 each 80 Chrysotile
Building: Waverley Drive PS
Description: Repair ACM found in fair condition, and not likely to be damaged again or disturbed by normal use of the area or room.
Action: 5 - ACM Repair
Action: 4 - Type 2 Precautions for Access into Areas Where ACM is Present and Likely to be Disturbed by Access
Description: Use Type 2 asbestos precautions when entry or access into an area is likely to disturb the ACM.
Main Floor 10 Con. Ed. Classroom 0.00 0.00 7.50 7.50 meter Yes Poor
Component System Material Category Description of Material Good Fair Poor Quantity Units Content % Type
Component Details Totals for Component Asbestos Content
Floor Location Location Description Good Fair Poor Quantity Units Visible Condition Details
815 OTHER Miscellaneous Material Unidentified Board Behind Radiators 0 0 7.50 7.50 meter 55 Chrysotile
Building: Waverley Drive PS
Action: 3 - ACM Removal Required for Compliance
Description: Remove ACM in compliance with regulatory requirements.
Action: 2 - Type 2 Precautions for Entry in Areas with ACM Debris
Description: Restrict access to the area to persons utilizing Type 2 asbestos precautions. These precautions will be required until the ACM debris has been cleaned up, and the source of the debris has been stabilized or removed.
Action: 1 - Immediate Clean up of Debris
Description: Restrict access that is likely to cause a disturbance of the ACM debris and clean up ACM debris immediately. The surveyor will immediately notify the Environmental Coordinator of this condition.
Action Item Summary Report
Date: 6/8/2007 8:49:48 PM
Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Job Number : 06-1135-044
Table A-5
Page: 2Golder Associates
NOTE: All quantities listed are approximate only.
Main Floor 3 Storage 20.00 0.00 0.00 20.00 square meter Yes Good
Main Floor 34 Classroom 25.00 0.00 0.00 25.00 square meter Yes Good
Main Floor 14 Classroom #2 68.00 0.00 0.00 68.00 square meter Yes Good
Main Floor 12 Classroom #6 68.00 0.00 0.00 68.00 square meter Yes Good
Main Floor 13 Classroom #4 68.00 0.00 0.00 68.00 square meter Yes Good
Main Floor 36 Seminar Room 40.00 0.00 0.00 40.00 square meter Yes Good
Main Floor 6 Integrated Technology 68.00 0.00 0.00 68.00 square meter Yes Good
Component System Material Category Description of Material Good Fair Poor Quantity Units Content % Type
Component Details Totals for Component Asbestos Content
Floor Location Location Description Good Fair Poor Quantity Units Visible Condition Details
103 FLOOR Miscellaneous Material VFT Light Blue With White Streaks (9x9)
526.00 0 0 526.00 square meter 1.2 Chrysotile
Main Floor 9 Con. Ed. Classroom 60.00 0.00 0.00 60.00 square meter Yes Good
Main Floor 4 Principal's Office 32.00 0.00 0.00 32.00 square meter Yes Good
Main Floor 1 Office 30.00 0.00 0.00 30.00 square meter Yes Good
Component System Material Category Description of Material Good Fair Poor Quantity Units Content % Type
Component Details Totals for Component Asbestos Content
Floor Location Location Description Good Fair Poor Quantity Units Visible Condition Details
102 FLOOR Miscellaneous Material VFT Dark Blue With White Streaks (9x9) 122.00 0 0 122.00 square meter 1.3 Chrysotile
Building: Waverley Drive PS
Action: 6 - Routine Inspection
Description: Maintain routine inspection of ACM
Main Floor 24 Girl's Washroom 0.00 2.00 0.00 2.00 meter Yes Good
Component System Material Category Description of Material Good Fair Poor Quantity Units Content % Type
Component Details Totals for Component Asbestos Content
815 OTHER Miscellaneous Material Unidentified Board Behind Radiators 0 2.00 0 2.00 meter 55 Chrysotile
Floor Location Location Description Good Fair Poor Quantity Units Visible Condition Details
Building: Waverley Drive PS
Action: 5 - ACM Repair
Description: Repair ACM found in fair condition, and not likely to be damaged again or disturbed by normal use of the area or room.
Action Item Summary Report
Date: 6/8/2007 8:49:48 PM
Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Job Number : 06-1135-044
Table A-5
Page: 3Golder Associates
NOTE: All quantities listed are approximate only.
Main Floor 28 Develop H/C 72.00 0.00 0.00 72.00 square meter Yes Good
Main Floor 23 Resource 25.00 0.00 0.00 25.00 square meter Yes Good
Main Floor 22 Resource 8.00 0.00 0.00 8.00 square meter Yes Good
Main Floor 29 Integrated Technology 70.00 0.00 0.00 70.00 square meter Yes Good
Main Floor 41 Classroom 72.00 0.00 0.00 72.00 square meter Yes Good
Component System Material Category Description of Material Good Fair Poor Quantity Units Content % Type
Component Details Totals for Component Asbestos Content
Floor Location Location Description Good Fair Poor Quantity Units Visible Condition Details
151 FLOOR Miscellaneous Material VSF Taupe 321.00 0 0 321.00 square meter 15 Chrysotile
Main Floor 9 Con. Ed. Classroom 10.00 0.00 0.00 10.00 square meter Yes Good
Main Floor 14 Classroom #2 5.00 0.00 0.00 5.00 square meter Yes Good
Main Floor 2 V.P. Office 20.00 0.00 0.00 20.00 square meter Yes Good
Main Floor 12 Classroom #6 5.00 0.00 0.00 5.00 square meter Yes Good
Main Floor 13 Classroom #4 5.00 0.00 0.00 5.00 square meter Yes Good
Main Floor 8 Classroom 5.00 0.00 0.00 5.00 square meter Yes Good
Main Floor 7 Classroom 5.00 0.00 0.00 5.00 square meter Yes Good
Main Floor 6 Integrated Technology 5.00 0.00 0.00 5.00 square meter Yes Good
Component System Material Category Description of Material Good Fair Poor Quantity Units Content % Type
Component Details Totals for Component Asbestos Content
Floor Location Location Description Good Fair Poor Quantity Units Visible Condition Details
104 FLOOR Miscellaneous Material VFT White With Black Streaks (9x9) 60.00 0 0 60.00 square meter 0.75 Chrysotile
Main Floor 8 Classroom 72.00 0.00 0.00 72.00 square meter Yes Good
Main Floor 9 Con. Ed. Classroom 25.00 0.00 0.00 25.00 square meter Yes Good
Main Floor 7 Classroom 72.00 0.00 0.00 72.00 square meter Yes Good
Component System Material Category Description of Material Good Fair Poor Quantity Units Content % Type
Component Details Totals for Component Asbestos Content
Floor Location Location Description Good Fair Poor Quantity Units Visible Condition Details
103 FLOOR Miscellaneous Material VFT Light Blue With White Streaks (9x9)
526.00 0 0 526.00 square meter 1.2 Chrysotile
Building: Waverley Drive PS
Action: 6 - Routine Inspection
Description: Maintain routine inspection of ACM
Action Item Summary Report
Date: 6/8/2007 8:49:48 PM
Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Job Number : 06-1135-044
Table A-5
Page: 4Golder Associates
NOTE: All quantities listed are approximate only.
Second Floor 53 Washroom 25.00 0.00 0.00 25.00 square meter Yes Good
Main Floor 39 Washroom 4.00 0.00 0.00 4.00 square meter Yes Good
Main Floor 40 Washroom 4.00 0.00 0.00 4.00 square meter Yes Good
Main Floor 31 Washroom 25.00 0.00 0.00 25.00 square meter Yes Good
Main Floor 32 Washroom 25.00 0.00 0.00 25.00 square meter Yes Good
Main Floor I Stairwell I 40.00 0.00 0.00 40.00 square meter Yes Good
Main Floor H Corridor H 155.00 0.00 0.00 155.00 square meter Yes Good
Main Floor G Stairwell 45.00 0.00 0.00 45.00 square meter Yes Good
Component System Material Category Description of Material Good Fair Poor Quantity Units Content % Type
Component Details Totals for Component Asbestos Content
Floor Location Location Description Good Fair Poor Quantity Units Visible Condition Details
368 CEILING Miscellaneous Material CT Small and Large Pinholes (2x4) 503.00 0 0 503.00 square meter 1.2 Chrysotile
Exterior K Exterior 10.00 0.00 0.00 10.00 square meter Yes Good
Component System Material Category Description of Material Good Fair Poor Quantity Units Content % Type
Component Details Totals for Component Asbestos Content
Floor Location Location Description Good Fair Poor Quantity Units Visible Condition Details
310 STRUCTURE Surfacing Material Exterior Plaster 10.00 0 0 10.00 square meter 1.2 Chrysotile
Main Floor C Corridor C 5.00 0.00 0.00 5.00 square meter Yes Good
Main Floor D Vestibule D 5.00 0.00 0.00 5.00 square meter Yes Good
Component System Material Category Description of Material Good Fair Poor Quantity Units Content % Type
Component Details Totals for Component Asbestos Content
Floor Location Location Description Good Fair Poor Quantity Units Visible Condition Details
210 WALL Surfacing Material Plaster Above Doors 10.00 0 0 10.00 square meter 0.75 Chrysotile
Main Floor 42 Classroom 74.00 0.00 0.00 74.00 square meter Yes Good
Component System Material Category Description of Material Good Fair Poor Quantity Units Content % Type
Component Details Totals for Component Asbestos Content
Floor Location Location Description Good Fair Poor Quantity Units Visible Condition Details
151 FLOOR Miscellaneous Material VSF Taupe 321.00 0 0 321.00 square meter 15 Chrysotile
Building: Waverley Drive PS
Action: 6 - Routine Inspection
Description: Maintain routine inspection of ACM
Action Item Summary Report
Date: 6/8/2007 8:49:48 PM
Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Job Number : 06-1135-044
Table A-5
Page: 5Golder Associates
NOTE: All quantities listed are approximate only.
Main Floor 5 Custodian Room 4 0 0 4 each No Good
Main Floor A Corridor A 100 0 0 100 each No Good
Main Floor B Corridor B 70 0 0 70 each No Good
Main Floor 33 Custodian Room 30 0 0 30 each No Good
Main Floor 39 Washroom 4 0 0 4 each No Good
Main Floor 40 Washroom 4 0 0 4 each No Good
Main Floor F Vestibule F 30 0 0 30 each No Good
Main Floor H Corridor H 27 0 0 27 each No Good
Main Floor C Corridor C 30 0 0 30 each No Good
Main Floor D Vestibule D 8 0 0 8 each No Good
Main Floor E Corridor E 35 0 0 35 each No Good
Main Floor 32 Washroom 10 0 0 10 each No Good
Main Floor 20 Boiler Room 45 0 0 45 each No Good
Main Floor 16 Washroom 2 0 0 2 each No Good
Main Floor 15 Washroom 2 0 0 2 each No Good
Main Floor 31 Washroom 10 0 0 10 each No Good
Main Floor 3 Storage 2 0 0 2 each No Good
Main Floor 20b 3 0 0 3 each No Good
Component Details Totals for Component Asbestos ContentComponent System Material Category Description of Material Good Fair Poor Quantity Units Content % Type
Floor Location Location Description Good Fair Poor Quantity Units Visible Condition Details
500 PIPING SYSTEMS Thermal System Insulation
Parging Cement on Fittings 431.00 0 0 431.00 each 80 Chrysotile
Second Floor 55 Washroom 25.00 0.00 0.00 25.00 square meter Yes Good
Second Floor J Corridor J 155.00 0.00 0.00 155.00 square meter Yes Good
Component System Material Category Description of Material Good Fair Poor Quantity Units Content % Type
Component Details Totals for Component Asbestos Content
Floor Location Location Description Good Fair Poor Quantity Units Visible Condition Details
368 CEILING Miscellaneous Material CT Small and Large Pinholes (2x4) 503.00 0 0 503.00 square meter 1.2 Chrysotile
Building: Waverley Drive PS
Action: 6 - Routine Inspection
Description: Maintain routine inspection of ACM
Action Item Summary Report
Date: 6/8/2007 8:49:48 PM
Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Job Number : 06-1135-044
Table A-5
Page: 6Golder Associates
NOTE: All quantities listed are approximate only.
Main Floor 28 Develop H/C 10.00 0.00 0.00 10.00 meter Yes Good
Main Floor 27 Fitness Room 10.00 0.00 0.00 10.00 meter Yes Good
Main Floor 29 Integrated Technology 10.00 0.00 0.00 10.00 meter Yes Good
Main Floor 31 Washroom 2.00 0.00 0.00 2.00 meter Yes Good
Main Floor 30 Classroom 10.00 0.00 0.00 10.00 meter Yes Good
Main Floor 26b 2.00 0.00 0.00 2.00 meter Yes Good
Main Floor 17 Staff Room 8.00 0.00 0.00 8.00 meter Yes Good
Main Floor 16 Washroom 2.00 0.00 0.00 2.00 meter Yes Good
Main Floor 2 V.P. Office 2.00 0.00 0.00 2.00 meter Yes Good
Main Floor 23 Resource 4.00 0.00 0.00 4.00 meter Yes Good
Main Floor 22 Resource 4.00 0.00 0.00 4.00 meter Yes Good
Main Floor 12 Classroom #6 10.00 0.00 0.00 10.00 meter Yes Good
Main Floor 11 Music 10.00 0.00 0.00 10.00 meter Yes Good
Main Floor 1 Office 7.50 0.00 0.00 7.50 meter Yes Good
Main Floor 15 Washroom 2.00 0.00 0.00 2.00 meter Yes Good
Main Floor 14 Classroom #2 10.00 0.00 0.00 10.00 meter Yes Good
Main Floor 13 Classroom #4 10.00 0.00 0.00 10.00 meter Yes Good
Component Details Totals for Component Asbestos ContentComponent System Material Category Description of Material Good Fair Poor Quantity Units Content % Type
Floor Location Location Description Good Fair Poor Quantity Units Visible Condition Details
815 OTHER Miscellaneous Material Unidentified Board Behind Radiators 335.50 0 0 335.50 meter 55 Chrysotile
Second Floor 54 Custodian Room 3 0 0 3 each No Good
Second Floor 57 Classroom 2 0 0 2 each No Good
Main Floor I Stairwell I 10 0 0 10 each No Good
Component Details Totals for Component Asbestos ContentComponent System Material Category Description of Material Good Fair Poor Quantity Units Content % Type
Floor Location Location Description Good Fair Poor Quantity Units Visible Condition Details
500 PIPING SYSTEMS Thermal System Insulation
Parging Cement on Fittings 431.00 0 0 431.00 each 80 Chrysotile
Building: Waverley Drive PS
Action: 6 - Routine Inspection
Description: Maintain routine inspection of ACM
Action Item Summary Report
Date: 6/8/2007 8:49:48 PM
Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Job Number : 06-1135-044
Table A-5
Page: 7Golder Associates
NOTE: All quantities listed are approximate only.
Second Floor 50 Classroom 10.00 0.00 0.00 10.00 meter Yes Good
Second Floor 51 Classroom 10.00 0.00 0.00 10.00 meter Yes Good
Second Floor 48 Classroom 10.00 0.00 0.00 10.00 meter Yes Good
Second Floor 49 Classroom 10.00 0.00 0.00 10.00 meter Yes Good
Second Floor 55 Washroom 2.00 0.00 0.00 2.00 meter Yes Good
Second Floor 56 Classroom 12.00 0.00 0.00 12.00 meter Yes Good
Second Floor 52 Classroom 10.00 0.00 0.00 10.00 meter Yes Good
Second Floor 53 Washroom 2.00 0.00 0.00 2.00 meter Yes Good
Main Floor 8 Classroom 10.00 0.00 0.00 10.00 meter Yes Good
Main Floor 9 Con. Ed. Classroom 25.00 0.00 0.00 25.00 meter Yes Good
Main Floor 7 Classroom 10.00 0.00 0.00 10.00 meter Yes Good
Main Floor 36 Seminar Room 10.00 0.00 0.00 10.00 meter Yes Good
Main Floor 37 Special Ed. 10.00 0.00 0.00 10.00 meter Yes Good
Main Floor 35 Classroom 10.00 0.00 0.00 10.00 meter Yes Good
Main Floor 32 Washroom 2.00 0.00 0.00 2.00 meter Yes Good
Main Floor 34 Classroom 10.00 0.00 0.00 10.00 meter Yes Good
Main Floor 38 Kindergarten 10.00 0.00 0.00 10.00 meter Yes Good
Main Floor 43 Library 25.00 0.00 0.00 25.00 meter Yes Good
Main Floor 6 Integrated Technology 10.00 0.00 0.00 10.00 meter Yes Good
Main Floor 42 Classroom 10.00 0.00 0.00 10.00 meter Yes Good
Main Floor 4 Principal's Office 4.00 0.00 0.00 4.00 meter Yes Good
Main Floor 41 Classroom 10.00 0.00 0.00 10.00 meter Yes Good
Component System Material Category Description of Material Good Fair Poor Quantity Units Content % Type
Component Details Totals for Component Asbestos Content
Floor Location Location Description Good Fair Poor Quantity Units Visible Condition Details
815 OTHER Miscellaneous Material Unidentified Board Behind Radiators 335.50 0 0 335.50 meter 55 Chrysotile
Building: Waverley Drive PS
Action: 6 - Routine Inspection
Description: Maintain routine inspection of ACM
Action Item Summary Report
Date: 6/8/2007 8:49:48 PM
Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Job Number : 06-1135-044
Table A-5
Page: 8Golder Associates
NOTE: All quantities listed are approximate only.
Action: N/A - Not Applicable
Description:
Main Floor 10a Storage 1.00 0.00 0.00 1.00 square meter Yes Good
Floor Location Location Description Good Fair Poor Quantity Units Visible Condition Details
824 WALL Miscellaneous Material Wall Board 1.00 0 0 1.00 square meter 80 Amosite
Component Details Totals for Component Asbestos ContentComponent System Material Category Description of Material Good Fair Poor Quantity Units Content % Type
Building: Waverley Drive PS
Action: 6 - Routine Inspection
Description: Maintain routine inspection of ACM
Date: 6/11/2007
Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Job Number : 06-1135-044ACM Photograph Log
Appendix C
Golder Associates Page: 1
Component 103 - VFT, Light Blue With White Streaks (9x9)
Component 102 - VFT, Dark Blue With White Streaks (9x9)
Date: 6/11/2007
Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Job Number : 06-1135-044ACM Photograph Log
Appendix C
Golder Associates Page: 2
Component 151 - VSF, Taupe
Component 151 - VFT, White With Black Streaks (9x9)
Date: 6/11/2007
Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Job Number : 06-1135-044ACM Photograph Log
Appendix C
Golder Associates Page: 3
Component 210 - Plaster Above Doors
Component 310 - Exterior Plaster
Date: 6/11/2007
Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Job Number : 06-1135-044ACM Photograph Log
Appendix C
Golder Associates Page: 4
Component 368 - CT, Small and Large Pinholes (2x4)
Component 500 - Parging Cement on Fittings
Date: 6/11/2007
Facility : 2434 - Waverley Dr. PS
Client : Upper Grand District School Board
Job Number : 06-1135-044ACM Photograph Log
Appendix C
Golder Associates Page: 5
Component 824 - Wall Board
Component 815 - Unidentified Board Behind Radiators
Golder Associates Page: 1
Ceiling Tile Photograph Log
Component 361 (Non-ACM) – 2x2-foot Ceiling Tile, Long Fissures WithMany, Many pinholes.
Client: Upper Grand DistrictSchool BoardFacility: 2434 – Waverley Drive PS
Component 360 (Non-ACM) – 2x2-foot Ceiling Tile, Small Fissures inSwirl With Pinholes.
Date: June 2007Job Number: 06-1135-044
Appendix C
Golder Associates Page: 2
Component 363 (Non-ACM) – 2x2-foot Ceiling Tile, Long Fissures WithFew Pinholes.
Component 362 (Non-ACM) – 2x2-foot Ceiling Tile, Short Fissures WithFew Pinholes.
Date: June 2007Job Number: 06-1135-044
Appendix C
Ceiling Tile Photograph Log
Client: Upper Grand DistrictSchool BoardFacility: 2434 – Waverley Drive PS
Golder Associates Page: 3
Component 365 (Non-ACM) – 2x4-foot Ceiling Tile, Short Fissures WithFew Pinholes.
Component 364 (Non-ACM) – 2x4-foot Ceiling Tile, Long Fissures WithMedium Pinholes.
Date: June 2007Job Number: 06-1135-044
Appendix C
Ceiling Tile Photograph Log
Client: Upper Grand DistrictSchool BoardFacility: 2434 – Waverley Drive PS
Golder Associates Page: 4
Component 367 (Non-ACM) – 2x4-foot Ceiling Tile, Short Fissures inSwirl with Pinholes.
Component 366 (Non-ACM) – 2x4-foot Ceiling Tile, Long Fissures WithMany, Many Pinholes.
Date: June 2007Job Number: 06-1135-044
Appendix C
Ceiling Tile Photograph Log
Client: Upper Grand DistrictSchool BoardFacility: 2434 – Waverley Drive PS
Golder Associates Page: 5
Component 368 (Non-ACM) – 2x4-foot Ceiling Tile, Small and LargePinholes.
Date: June 2007Job Number: 06-1135-044
Ceiling Tile Photograph Log
Client: Upper Grand DistrictSchool BoardFacility: 2434 – Waverley Drive PS
Golder Associates Ltd.
309 Exeter Road, Unit #1, London, Ontario, Canada N6L 1C1 Tel: +1 (519) 652 0099 Fax: +1 (519) 652 6299 www.golder.com
Golder Associates: Operations in Africa, Asia, Australasia, Europe, North America and South America
Golder, Golder Associates and the GA globe design are trademarks of Golder Associates Corporation.
Dear Ms. Millar:
Golder Associates Ltd. (Golder) is pleased to submit this letter summarizing the results of the 2014/2015 visual reassessment of previously identified asbestos-containing materials (ACMs) located at Waverley Drive Public School in Guelph, Ontario (the Site). The field work to complete the scope of work described below was performed on February 4, 2015 by A. Ismail of Golder. As noted in Golder Proposal P1415652-P01 dated October 17, 2014, Golder performed the following scope of work:
Visual reassessments of accessible ACMs previously identified in the 2013/2014 Reassessment Program, Golder Project Number 13-1134-0157, to determine the current condition of ACMs, as is required under Ontario Regulation 278/05 Designated Substance – Asbestos on Construction Projects and in Buildings
and Repair Operations, as amended (O. Reg. 278/05);
Asbestos-containing ceiling tiles, fittings, etc. that were deemed to require repair or removal were physically marked with bright coloured stickers so that they can be easily identified by maintenance staff. Note that certain materials, such as vinyl floor tiles, wall and ceiling surfacing materials, caulking, etc., were not visually marked Representative photographs of marked materials indicating an ACM requiring repair or removal are included in an attachment to this letter report1; and
Summary reporting of all previously identified ACMs remaining on-site in fair or poor condition and thus requiring action on the part of the UGDSB to repair or remove the identified ACMs. Identified ACMs in good condition do not require remedial action on the part of the UGDSB and, therefore, are not reported herein. Notwithstanding this, all previously identified ACMs remaining on-site have been re-quantified, on a room-by-room or location-by-location basis, on the attached Asbestos Inspection Form for the Site.
1 Please note that the photographs are representative only and may not have been taken at an actual location in this school. The photographs have been provided solely to assist maintenance staff in understanding the type of marking they are looking for with respect to ACMs requiring removal or repair based on the 2014/2015 reassessment findings.
April 30, 2015 Project No. 1415652-L35
Ms. Lorraine Millar, Environmental Co-ordinator Upper Grand District School Board 500 Victoria Road North Guelph, Ontario N1E 6K2
2014/2015 ASBESTOS-CONTAINING MATERIAL VISUAL REASSESSMENT WAVERLEY DRIVE PUBLIC SCHOOL 140 WAVERLEY DRIVE GUELPH, ONTARIO SFIS NO. 2434
Ms. Lorraine Millar, Environmental Co-ordinator 1415652-L35Upper Grand District School Board April 30, 2015
2/3
Reassessment methodology pertaining to the evaluation of observable ACMs, including the field criteria used to assess current condition, the accessibility of materials and assigned action responses are contained within an attachment to this letter report entitled 2014/2015 ACM Visual Reassessment Methodology and Criteria. Since the reassessment was based upon an asbestos building materials survey report provided by Golder to the UGDSB in 2007, the condition and accessibility criteria are identical to that previously used.
As previously reported in 2014, a simplified condition assessment response protocol has been implemented for the reassessment program using a three-stage action matrix rather than the original six-stage action matrix implemented in 2007. The three-stage action matrix accounts for the condition of ACM at the time of the visual reassessment and is further explained in the attached 2014/2015 ACM Visual Reassessment Methodology and
Criteria.
Visual Reassessment Findings The results of the condition reassessment are contained in the attached Asbestos Inspection Form. The ACM quantities and condition have been updated to reflect those observed during the reassessment conducted by Golder in February of 2015. Response action priorities range from prompt repair and/or encapsulation of the material and/or resulting debris to on-going routine inspections of materials identified in good condition. ACMs with an assigned Priority 1 or 2 are summarized below. Items requiring Routine Inspection (Priority 3) only, based on an observed condition of ‘good’, are not summarized below as they do not require any remedial efforts.
Priority Materials Requiring Reponse Action
Priority 1 ACM was observed to be in poor condition and requires removal, repair and/or encapsulation of the material and/or resulting debris. This action should be completed as soon as possible.
No Priority 1 materials were observed at the time of the 2014/2015 ACM reassessment.
Priority 2
ACM requires minor work which, due to the nature and/or accessibility of the material, can be scheduled for completion over periods such as the Christmas or summer break, when staff and students are not present, provided that the work is completed within a reasonable time frame. Appropriate measures should be taken to ensure that the material is not further disturbed prior to the work commencing.
Approximately 3 linear feet of aircell in fair condition was identified on a portion of pipe where the outer layer was removed in Location 54
Three metres of unidentified board behind a radiator in fair condition was identified in Location 10. This material is presumed to be present.
Limitations The conclusions and recommendations contained in this reassessment letter report are based upon professional opinions with regard to the subject matter. These opinions are in accordance with currently accepted industry practices and are subject both to the limitations contained in the 2007 asbestos building materials survey report and the following inherent limitations:
1. The data and findings presented in this report are valid as of the date(s) of the investigation only. The passage of time, manifestation of latent conditions or occurrence of future events may warrant further exploration of the Site, analysis of the data, and re-evaluation of the findings, observations, and conclusions expressed in this report.
Ms. Lorraine Millar, Environmental Co-ordinator 1415652-L35Upper Grand District School Board April 30, 2015
3/3
2. The data reported and the findings, observations, conclusions, and recommendations expressed in this letter are limited by the Scope of Work. The Scope of Work was defined by the request of the client, the time and budgetary constraints imposed by the client, and availability of access to the Site.
3. Because of the limitations stated above, the findings, observations, conclusions, and recommendations expressed by Golder Associates Ltd. in this letter are not, and should not be, considered an opinion concerning compliance of any past or present owner or operator of the Site with any federal, provincial or local laws or regulations.
4. No warranty or guarantee, whether expressed or implied, is made with respect to the data or the reported findings, observations, and conclusions, which are based solely upon Site conditions in existence at the time of investigation.
5. Golder Associates Ltd. will not be responsible for any real or perceived decrease in a property value, its saleability or ability to gain financing through the reporting of information in this letter.
6. Golder Associates Ltd.’s assessment reports present professional opinions and findings of a scientific and technical nature. While attempts were made to relate the data and findings to applicable environmental and occupational health & safety laws and regulations, the letter shall not be construed to offer legal opinion or representations as to the requirements of, nor compliance with, environmental and occupational health & safety laws, rules, regulations or policies of federal, provincial, or local governmental agencies. Any use of the letter constitutes acceptance of the limits of Golder Associates Ltd.’s liability. Golder Associates Ltd.’s liability extends only to its client and not to other parties who may obtain this assessment report. Issues raised by the report should be reviewed by appropriate legal counsel.
Closure We trust that this letter meets your current requirements. If you have any questions regarding the content of this letter report, please do not hesitate to contact the undersigned.
Yours truly,
GOLDER ASSOCIATES LTD.
Patrick Chesney. C.E.T. Chris Rahm, B.E.S. Occupational Hygienist Associate; Environmental Division Manager
SS/SFL/PNC/CJR/
Attachments: 2014/2015 ACM Visual Reassessment Methodology and Criteria
Representative Photographs of Marked Materials Asbestos Inspection Form (from 2014/2015 Visual Reassessment)
n:\active\2014\1138-ehs\1415652 ugdsb-2014 re-assmt various-on\8-correspondence\3-ltrs\l35 waverley drive ps\1415652-l35 apr 30 15 waverley drive ps.docx
2014/2015 ACM Visual Reassessment Methodology and Criteria
April 2015 Project No. 1415652 1/2
Each previously identified and accessible asbestos-containing material (ACM) – either confirmed through previous sampling and subsequent laboratory analysis or presumed as an ACM – was evaluated based on its visually observable condition at the time of the ACM visual reassessment Site visit. Table 1, below, outlines the criteria employed in the field to visually reassess the current condition of ACMs. Assigned conditions represent materials only at the time of the Site visit, should not necessarily be considered accurate for future condition, and are considered subjective.
Table 1: Condition of Asbestos-Containing Materials Rank Descriptions
Good
Thermal system insulation on fittings, tanks, valves, boilers, ducts, pipes and other mechanical equipment, which is completely enclosed without significant damage.
Sprayed fireproofing or acoustical texture coatings showing no signs of delaminating or fall-out.
Non-friable materials not exhibiting significant damage or extensive wear.
Fair Pipe insulation showing some signs of physical damage or shrinkage cracks along pipe runs.
Poor
General damage to mechanical insulation or water damage exposing asbestos directly.
In areas of sprayed fireproofing or acoustic texture coatings, delaminating and the presence of fallen material on horizontal surfaces.
The absence of an enclosure (e.g. canvas wrap, foil tape) around asbestos-containing material which formerly had an enclosure.
Non-friable ACM severely damaged to the extent that asbestos fibres may be released.
NOTE: The evaluation of the condition of non-friable materials does not utilize a fair condition rating.
In addition to the current condition, all previously identified and accessible ACMs were also rated by Golder based on the ease with which they can be reached and, therefore, physically disturbed. The accessibility of materials known or suspected of being ACM were rated according to the following criteria outlined in Table 2.
Table 2: Accessibility
Access (A)
Materials within reach (from floor level) of all Site users. These also include materials in gymnasiums, workshops, and storage areas where activities of the Site users may result in disturbance of ACM not normally within reach from floor level. Visibility would typically be noted as “YES” for these items, except for under sinks, in closets, or other commonly accessed spaces.
Access (B)
Materials in frequently entered maintenance areas of the Site within reach of maintenance staff, without the need for a ladder. Includes materials within reach from a fixed ladder or catwalk (i.e., tops of equipment, mezzanines, and frequently entered pipe chases, tunnels and service areas). Visibility would typically be noted as “YES” for these items.
2014/2015 ACM Visual Reassessment Methodology and Criteria
April 2015 Project No. 1415652 2/2
Access (C)
Materials above 8'-0" where use of a ladder is required to reach the ACM. Only includes ACMs that are exposed to view without the removal or opening of other building components such as ceiling tiles, or service access doors or hatches. Does not include materials in infrequently accessed service areas of the Site. Visibility would be noted as “YES” for these items.
Access (D)
Materials that cannot be reached without removing a building component, including lay-in ceilings or access panels in solid ceiling systems. Includes rarely entered crawl spaces, attic spaces, etc. Observations will be limited to the extent visible from access points. Visibility would be noted as “NO” for these items.
Access (E)
Materials behind inaccessible solid ceiling systems, walls or mechanical equipment, etc., where demolition of the ceiling, wall or equipment etc. is required to reach the ACM. These materials are visually identified by the surveyor, often with difficulty, and there may be uncertainty associated with them. Evaluation of condition and extent of ACM is limited or impossible, depending on the surveyor's ability to visually examine these materials. Visibility would be noted as “NO” for these items.
For each ACM or PACM identified, a specific response action priority has been assigned. The assigned priority is based on consideration of the type of asbestos present, the observed condition of the material and the accessibility of the material. These priorities are based on the likely risk posed by the material, with damaged materials that are easily accessible posing the greatest risk and materials in good condition in inaccessible areas posing the least risk. Response action priorities range from immediate clean-up of debris to on-going routine inspections of materials identified in good condition.
The following is a summary of the response action priorities assigned as a part of this reassessment:
Priority 1 – ACM was observed to be in poor condition and requires removal, repair and/or encapsulation of the material and/or resulting debris. This action should be completed as soon as possible.
Priority 2 – ACM that requires minor work which, due to the nature and/or accessibility of the material, can be scheduled for completion over periods such as the winter or summer break, when staff and students are not present, provided that the work is completed within a reasonable time frame. Appropriate measures should be taken to ensure that the material is not further disturbed prior to the work commencing. Continue with routine inspection of the ACM to monitor the condition, as per the Asbestos Management Program.
Priority 3 – ACM was observed to be in good condition and no work is currently required. Continue with routine inspection of the ACM to monitor the condition, as per the Asbestos Management Program. In the event of a building alteration which could impact the material, it will be necessary to remove the ACM, regardless of condition, that is likely to be disturbed by renovation, demolition or maintenance work.
Representative Photographs of Marked Materials
April 2015 1415652 1/1
Photo 1: The yellow marker on the ceiling grid indicates that there is an ACM above the ceiling tile that required repair or removal.
Photo 2: The yellow marker on the ceiling tile indicates that the asbestos-containing ceiling tile requires removal.
YELLOW MARKER
YELLOW MARKER
2434 - Waverley Drive PSUpper Grand District School Board
Asbestos Inspeciton FormConfirmed and Presumed ACM
1415652-L35
Date: February 4, 2015
Location:
System Comp Material Description Units Accessibility Fair Poor
STRUCTURE 310 Exterior Plaster 10.00 square meter
C
Location:
System Comp Material Description Units Accessibility Fair Poor
FLOOR 102 VFT Dark Blue With White Streaks (9x9)
30.00 square meter
A
OTHER 815 Unidentified Board Behind Radiators
3 meter E
Comments:
Location:
System Comp Material Description Units Accessibility Fair Poor
FLOOR 104 VFT White With Black Streaks (9x9)
20.00 square meter
A
Location:
System Comp Material Description Units Accessibility Fair Poor
FLOOR 103 VFT Light Blue With White Streaks (9x9)
20.00 square meter
A
Location:
System Comp Material Description Units Accessibility Fair Poor
FLOOR 102 VFT Dark Blue With White Streaks (9x9)
32.00 square meter
A
OTHER 815 Unidentified Board Behind Radiators
3 meter E
Comments:
Description of Action Required
Inspector's Name: Ali Ismail
1.2
Exterior: KLocation Details: Exterior (Outside) Quantity/Condition
ActionAsbestos
%Asbestos
TypeFriable Good Debris
2014/2015 Quantity
Main Floor: 1Location Details: Office (Main Floor) Quantity/Condition Description of Action
Required(if applicable)
2014/2015 Quantity
(if applicable)
Action 3Chrysotile Yes 10.00
Completed(dd-mm-yyyy)
Action 3- see comment below
ActionAsbestos
%Asbestos
TypeFriable Good Debris
1.3 Chrysotile No 30.00
55 Chrysotile Yes * See Comments Below
(if applicable)
Main Floor: 2Location Details: V.P. Office (Main Floor) Quantity/Condition Description of Action
RequiredAsbestos
%Asbestos
TypeFriable Good Debris
2014/2015 Quantity
0.75 Chrysotile No 20.00 Action 3
1.2
Description of Action Required
Asbestos %
Main Floor: 3Location Details: Storage (Main Floor) Quantity/Condition
2014/2015 Quantity
Action 3
Asbestos Type
Friable Good Debris (if applicable)
Chrysotile No 20.00
(if applicable)
Main Floor: 4Location Details: Principal's Office (Main Floor) Quantity/Condition Description of Action
RequiredAsbestos
%Asbestos
TypeFriable Good Debris
1.3 Chrysotile No 32.00 Action 3
*See Comment Below55 Chrysotile Yes
Wallboard ladt observed in 2011 and assumed to have been removed.
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
Completed(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
2014/2015 Quantity
Approximately half of the VFT were covered with carpet in 2014. Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
Golder Associates Page: 1
2434 - Waverley Drive PSUpper Grand District School Board
Asbestos Inspeciton FormConfirmed and Presumed ACM
1415652-L35
Location:
System Comp Material Description Units Accessibility Fair Poor
PIPING SYSTEMS
500 Parging Cement on Fittings
4 each C
Location:
System Comp Material Description Units Accessibility Fair Poor
FLOOR 103 VFT Light Blue With White Streaks (9x9)
68.00 square meter
A
FLOOR 104 VFT White With Black Streaks (9x9)
5.00 square meter
A
Location:
System Comp Material Description Units Accessibility Fair Poor
FLOOR 103 VFT Light Blue With White Streaks (9x9)
72.00 square meter
A
FLOOR 104 VFT White With Black Streaks (9x9)
5.00 square meter
A
Location:
System Comp Material Description Units Accessibility Fair Poor
FLOOR 103 VFT Light Blue With White Streaks (9x9)
72.00 square meter
A
FLOOR 104 VFT White With Black Streaks (9x9)
5.00 square meter
A
Location:
System Comp Material Description Units Accessibility Fair Poor
FLOOR 102 VFT Dark Blue With White Streaks (9x9)
10.00 square meter
A
FLOOR 104 VFT White With Black Streaks (9x9)
10.00 square meter
A
Description of Action Required
Asbestos %
Main Floor: 5Location Details: Custodian Room (Main Floor) Quantity/Condition
80 Chrysotile Yes 4
Asbestos Type
Friable Good Debris (if applicable)
Description of Action Required
Asbestos %
Action 3
Main Floor: 6Location Details: Integrated Technology (Main Floor) Quantity/Condition
1.2 Chrysotile No 68.00
Action 3
Asbestos Type
Friable Good Debris (if applicable)
Action 3
0.75 Chrysotile No 5.00
(if applicable)
Main Floor: 7Location Details: Classroom (Main Floor) Quantity/Condition Description of Action
RequiredAsbestos
%Asbestos
TypeFriable Good Debris
1.2 Chrysotile No 72.00 Action 3
0.75 Chrysotile No 5.00 Action 3
Description of Action Required
Asbestos %
Main Floor: 8Location Details: Classroom (Main Floor) Quantity/Condition
1.2 Chrysotile No 72.00
Action 3
Asbestos Type
Friable Good Debris (if applicable)
Action 3
0.75 Chrysotile No 5.00
(if applicable)
Main Floor: 9Location Details: Con. Ed. Classroom (Main Floor) Quantity/Condition Description of Action
RequiredAsbestos
%Asbestos
TypeFriable Good Debris
1.3 Chrysotile No 10.00 Action 3
0.75 Chrysotile No 10.00 Action 3
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
2014/2015 Quantity
2014/2015 Quantity
2014/2015 Quantity
2014/2015 Quantity
2014/2015 Quantity
Golder Associates Page: 2
2434 - Waverley Drive PSUpper Grand District School Board
Asbestos Inspeciton FormConfirmed and Presumed ACM
1415652-L35
Location:
System Comp Material Description Units Accessibility Fair Poor
OTHER 815 Unidentified Board Behind Radiators
3 meter A 3
Location:
System Comp Material Description Units Accessibility Fair Poor
WALL 824 Wall Board 1.00 square meter
A
Comments:
Location:
System Comp Material Description Units Accessibility Fair Poor
OTHER 815 Unidentified Board Behind Radiators
3 meter E
OTHER Gold Sink Acoustic 1 each AComments:
Location:
System Comp Material Description Units Accessibility Fair Poor
FLOOR 103 VFT Light Blue With White Streaks (9x9)
68.00 square meter
A
FLOOR 104 VFT White With Black Streaks (9x9)
5.00 square meter
A
OTHER 815 Unidentified Board Behind Radiators
3 meter E
OTHER Gold Sink Acoustic 0 each A
Comments:
Action 33.2 Chrysotile No 1Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
3.2 Chrysotile No Please see comments below
Asbestos %
(if applicable)
Main Floor: 10Location Details: Con. Ed. Classroom (Main Floor) Quantity/Condition Description of Action
RequiredAsbestos
TypeFriable Good Debris
55 Chrysotile Yes
Asbestos %
Action 2
(if applicable)
Main Floor: 10aLocation Details: Storage (Main Floor) Quantity/Condition Description of Action
RequiredAsbestos
TypeFriable Good Debris
80 Amosite No
Asbestos %
Please see comments below
(if applicable)
Main Floor: 11Location Details: Music (Main Floor) Quantity/Condition Description of Action
RequiredAsbestos
TypeFriable Good Debris
55 Chrysotile Yes
(if applicable)
Main Floor: 12Location Details: Classroom #6 (Main Floor) Quantity/Condition Description of Action
RequiredAsbestos
%Asbestos
TypeFriable Good Debris
1.2 Chrysotile No 68.00 Action 3
0.75 Chrysotile No 5.00 Action 3
55 Chrysotile Yes * See Comments Below
Sink replaced 2013. Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
Action
Wall board lst observed in 2011 and assumed to have been removed.
*See Comments Below
Completed(dd-mm-yyyy)
2014/2015 Quantity
2014/2015 Quantity
2014/2015 Quantity
2014/2015 Quantity
Golder Associates Page: 3
2434 - Waverley Drive PSUpper Grand District School Board
Asbestos Inspeciton FormConfirmed and Presumed ACM
1415652-L35
Location:
System Comp Material Description Units Accessibility Fair Poor
FLOOR 103 VFT Light Blue With White Streaks (9x9)
68.00 square meter
A
FLOOR 104 VFT White With Black Streaks (9x9)
5.00 square meter
A
OTHER 815 Unidentified Board Behind Radiators
3 meter E
Comments:
Location:
System Comp Material Description Units Accessibility Fair Poor
FLOOR 103 VFT Light Blue With White Streaks (9x9)
68.00 square meter
A
FLOOR 104 VFT White With Black Streaks (9x9)
5.00 square meter
A
OTHER 815 Unidentified Board Behind Radiators
3 meter E
Comments:
Location:
System Comp Material Description Units Accessibility Fair Poor
OTHER 815 Unidentified Board Behind Radiators
2.00 meter E
Comments:
Location:
System Comp Material Description Units Accessibility Fair Poor
OTHER 815 Unidentified Board Behind Radiators
2.00 meter E
Comments:
Location:
System Comp Material Description Units Accessibility Fair Poor
OTHER 815 Unidentified Board Behind Radiators
8.00 meter E
Comments:
(if applicable)
Main Floor: 13Location Details: Classroom #4 (Main Floor) Quantity/Condition Description of Action
RequiredAsbestos
%Asbestos
TypeFriable Good Debris
1.2 Chrysotile No 68.00 Action 3
0.75 Chrysotile No 5.00 Action 3
55 Chrysotile Yes *See Comments Below
(if applicable)
Main Floor: 14Location Details: Classroom #2 (Main Floor) Quantity/Condition Description of Action
RequiredAsbestos
%Asbestos
TypeFriable Good Debris
1.2 Chrysotile No 68.00 Action 3
0.75 Chrysotile No 5.00 Action 3
55 Chrysotile Yes *See Comments Below
Main Floor: 15Location Details: Washroom (Main Floor) Quantity/Condition Description of Action
Required2014/2015 Quantity
*See Comments Below
Asbestos %
Asbestos Type
Friable Good Debris (if applicable)
55 Chrysotile Yes
Main Floor: 16Location Details: Washroom (Main Floor) Quantity/Condition Description of Action
Required(if applicable)Asbestos
%Asbestos
TypeFriable Good Debris
2014/2015 Quantity
55 Chrysotile Yes *See Comments Below
(if applicable)
Main Floor: 17Location Details: Staff Room (Main Floor) Quantity/Condition Description of Action
RequiredAsbestos
%Asbestos
TypeFriable Good Debris
2014/2015 Quantity
55 Chrysotile Yes *See Comments Below
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
Action
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
Completed(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
2014/2015 Quantity
2014/2015 Quantity
Golder Associates Page: 4
2434 - Waverley Drive PSUpper Grand District School Board
Asbestos Inspeciton FormConfirmed and Presumed ACM
1415652-L35
Location:
System Comp Material Description Units Accessibility Fair Poor
PIPING SYSTEMS
Aircell (presumed ACM) 10 meter E
Comments:
Location:
System Comp Material Description Units Accessibility Fair Poor
FLOOR 151 VSF Taupe 8.00 square meter
A
OTHER 815 Unidentified Board Behind Radiators
4.00 meter E
Comments:
Location:
System Comp Material Description Units Accessibility Fair Poor
FLOOR 151 VSF Taupe 25.00 square meter
A
OTHER 815 Unidentified Board Behind Radiators
4.00 meter E
OTHER Gold Sink Acoustic 1 each A
Comments:
Location:
System Comp Material Description Units Accessibility Fair Poor
OTHER 815 Unidentified Board Behind Radiators
2.00 meter E
Comments:
Location:
System Comp Material Description Units Accessibility Fair Poor
OTHER 815 Unidentified Board Behind Radiators
3 meter E
Comments:
(if applicable)
Main Floor: 22Location Details: Resource (Main Floor) Quantity/Condition Description of Action
RequiredAsbestos
%Asbestos
TypeFriable Good Debris
15 Chrysotile No 8.00 Action 3
55 Chrysotile Yes *See Comments Below
Main Floor: 23Location Details: Resource (Main Floor) Quantity/Condition Description of Action
RequiredAsbestos
TypeFriable Good Debris (if applicable)
*See Comments Below
15 Chrysotile No 25.00 Action 3
Asbestos %
55 Chrysotile Yes
Main Floor: 24Location Details: Girl's Washroom (Main Floor) Quantity/Condition
Asbestos Type
FriableAsbestos %
Yes *See Comments Below
Description of Action Required
Good Debris (if applicable)
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
55 Chrysotile
Location Details: (Main Floor) Quantity/Condition Description of Action Required
Asbestos %55 Chrysotile Yes
Asbestos Type
Friable Good Debris (if applicable)
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
*See Comments Below
3.2 Chrysotile No 1 Action 3
ActionCompleted
(dd-mm-yyyy)
2014/2015 Quantity
Action
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
Main Floor: 26b
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
2014/2015 Quantity
2014/2015 Quantity
2014/2015 Quantity
Description of Action RequiredMain Floor: 20 2014/2015
Quantity
Location Details: Quantity/Condition
Completed(dd-mm-yyyy)
Asbestos %
Asbestos Type
Friable Good Debris
Presumed Yes 10
(if applicable)
Aircell presumed to be present beneath layered cardboard insulation over 6" pipe, not previously identified.
Action 3- See Comments Below
Golder Associates Page: 5
2434 - Waverley Drive PSUpper Grand District School Board
Asbestos Inspeciton FormConfirmed and Presumed ACM
1415652-L35
Location:
System Comp Material Description Units Accessibility Fair Poor
OTHER 815 Unidentified Board Behind Radiators
3 meter E
Comments:
Location:
System Comp Material Description Units Accessibility Fair Poor
FLOOR 151 VSF Taupe 0.00 square meter
A
OTHER 815 Unidentified Board Behind Radiators
8.00 meter E
OTHER Gold Sink Acoustic 1 each AComments:
Location:
System Comp Material Description Units Accessibility Fair Poor
FLOOR 151 VSF Taupe 70.00 square meter
A
OTHER Gold Sink Acoustic 1 each A
Location:
System Comp Material Description Units Accessibility Fair Poor
OTHER 815 Unidentified Board Behind Radiators
3 meter E
OTHER Gold Sink Acoustic 1 each AComments:
Location:
System Comp Material Description Units Accessibility Fair Poor
OTHER 815 Unidentified Board Behind Radiators
3 meter E
Comments: Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
3.2 Chrysotile No 1 Action 3
Chrysotile No 1
Description of Action Required
Asbestos %
Main Floor: 27Location Details: Fitness Room (Main Floor) Quantity/Condition
Asbestos Type
Friable Good Debris
55 Chrysotile Yes
Main Floor: 28Location Details: Develop H/C (Main Floor) Quantity/Condition Description of Action
RequiredAsbestos
%Asbestos
TypeFriable Good Debris
2014/2015 Quantity
55 Chrysotile Yes
Asbestos %
Asbestos Type
Please see comments below
15 Chrysotile No
*See Comments Below
Action 33.2
Integrated Technology (Main Floor) Quantity/Condition Description of Action Required
15 Chrysotile No 70.00
Friable Good
Action 3
Debris (if applicable)
(if applicable)
*See Comments Below
(if applicable)
(if applicable)
55 Chrysotile
Main Floor: 30Location Details: Classroom (Main Floor) Quantity/Condition Description of Action
RequiredAsbestos
%Asbestos
TypeFriable
*See Comments Below
Action 3Chrysotile No 1
Yes
DebrisGood
3.2
Main Floor: 31Location Details: Washroom (Main Floor) Quantity/Condition Description of Action
Required
*See Comments Below
(if applicable)Asbestos %
Asbestos Type
Friable Good Debris
55 Chrysotile Yes
2014/2015 Quantity
2014/2015 Quantity
2014/2015 Quantity
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
VSF replaced 2012. Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
Main Floor: 29Location Details:
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
2014/2015 Quantity
Golder Associates Page: 6
2434 - Waverley Drive PSUpper Grand District School Board
Asbestos Inspeciton FormConfirmed and Presumed ACM
1415652-L35
Location:
System Comp Material Description Units Accessibility Fair Poor
OTHER 815 Unidentified Board Behind Radiators
3 meter E
Comments:
Location:
System Comp Material Description Units Accessibility Fair Poor
PIPING SYSTEMS
Aircell (presumed ACM) 10 meter E
Comments:
Location:
System Comp Material Description Units Accessibility Fair Poor
FLOOR 103 VFT Light Blue With White Streaks (9x9)
25.00 square meter
A
OTHER 815 Unidentified Board Behind Radiators
3 meter E
Comments:
Location:
System Comp Material Description Units Accessibility Fair Poor
OTHER 815 Unidentified Board Behind Radiators
3 meter E
Comments:
Location:
System Comp Material Description Units Accessibility Fair Poor
FLOOR 103 VFT Light Blue With White Streaks (9x9)
40.00 square meter
A
OTHER 815 Unidentified Board Behind Radiators
3 meter E
OTHER Gold Sink Acoustic 1 each AComments:
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
Main Floor: 32Location Details: Washroom (Main Floor) Quantity/Condition Description of Action
Required
*See Comments Below
(if applicable)Asbestos %
Asbestos Type
Friable Good Debris
55 Chrysotile Yes
(if applicable)
Main Floor: 34Location Details: Classroom (Main Floor) Quantity/Condition Description of Action
RequiredAsbestos
%Asbestos
TypeFriable Good Debris
1.2 Chrysotile No 25.00 Action 3
55 Chrysotile Yes *See Comments Below
(if applicable)
Main Floor: 35Location Details: Classroom (Main Floor) Quantity/Condition Description of Action
RequiredAsbestos
%Asbestos
TypeFriable Good Debris
55 Chrysotile Yes *See Comments Below
(if applicable)
Main Floor: 36Location Details: Seminar Room (Main Floor) Quantity/Condition Description of Action
RequiredAsbestos
%1.2 Chrysotile No 40.00
55 Chrysotile Yes
Asbestos Type
Friable Good Debris
Action 3
*See Comments Below
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.3.2 Chrysotile No
2014/2015 Quantity
1 Action 3
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
2014/2015 Quantity
2014/2015 Quantity
2014/2015 Quantity
Asbestos Type
Friable Completed(dd-mm-yyyy)
Main Floor: 33 2014/2015 Quantity
Location Details:
Asbestos %
Yes 10
Good Debris
Quantity/Condition Description of Action Required Action
Aircell presumed to be present beneath layered cardboard insulation over 6" pipe, not previously identified.
(if applicable)
Action 3- See Comments Below
Presumed
Golder Associates Page: 7
2434 - Waverley Drive PSUpper Grand District School Board
Asbestos Inspeciton FormConfirmed and Presumed ACM
1415652-L35
Location:
System Comp Material Description Units Accessibility Fair Poor
OTHER 815 Unidentified Board Behind Radiators
3 meter E
Comments:
Location:
System Comp Material Description Units Accessibility Fair Poor
OTHER 815 Unidentified Board Behind Radiators
3 meter E
OTHER Gold Sink Acoustic 1 each AComments:
Location:
System Comp Material Description Units Accessibility Fair Poor
PIPING SYSTEMS
Aircell (presumed ACM) 10 meter E
Comments:
Location:
System Comp Material Description Units Accessibility Fair Poor
FLOOR 151 VSF Taupe 72.00 square meter
A
OTHER 815 Unidentified Board Behind Radiators
3 meter E
OTHER Gold Sink Acoustic 1 each AComments: Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
*See Comments Below
Asbestos %
Asbestos Type
Friable Good
55 Chrysotile
Location Details:
Yes
Debris
Quantity/ConditionSpecial Ed. (Main Floor)
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
Main Floor: 37Description of Action
Required
(if applicable)
Main Floor: 38Location Details: Kindergarten (Main Floor) Quantity/Condition Description of Action
RequiredAsbestos
%Asbestos
TypeFriable Good Debris
55 Chrysotile Yes *See Comments Below
(if applicable)
Main Floor: 41Location Details: Classroom (Main Floor) Quantity/Condition Description of Action
RequiredAsbestos
%Asbestos
TypeFriable Good Debris
15 Chrysotile No 72.00 Action 3
55 Chrysotile Yes *See Comments Below
(if applicable)
3.2 Chrysotile No 1 Action 3
3.2 Chrysotile No 1 Action 3
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
2014/2015 Quantity
2014/2015 Quantity
2014/2015 Quantity
Main Floor: 39 2014/2015 Quantity
Location Details: Quantity/Condition Description of Action Required Action
Asbestos %
Asbestos Type
Friable Good Debris (if applicable) Completed(dd-mm-yyyy)
Presumed Yes 10 Action 3- See Comments Below
Aircell presumed to be present beneath layered cardboard insulation over 6" pipe, not previously identified.
Golder Associates Page: 8
2434 - Waverley Drive PSUpper Grand District School Board
Asbestos Inspeciton FormConfirmed and Presumed ACM
1415652-L35
Location:
System Comp Material Description Units Accessibility Fair Poor
FLOOR 151 VSF Taupe 74.00 square meter
A
OTHER 815 Unidentified Board Behind Radiators
3 meter E
OTHER Gold Sink Acoustic 1 each AComments:
Location:
System Comp Material Description Units Accessibility Fair Poor
OTHER 815 Unidentified Board Behind Radiators
3 meter E
OTHER Gold Sink Acoustic 1 each AComments:
Location:
System Comp Material Description Units Accessibility Fair Poor
OTHER 815 Unidentified Board Behind Radiators
3 meter E
OTHER Gold Sink Acoustic 1 each AComments:
Location:
System Comp Material Description Units Accessibility Fair Poor
OTHER 815 Unidentified Board Behind Radiators
3 meter E
OTHER Gold Sink Acoustic 1 each AComments:
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
Main Floor: 42Location Details: Classroom (Main Floor) Quantity/Condition Description of Action
RequiredAsbestos
TypeFriable Good Debris (if applicable)
2014/2015 Quantity
*See Comments Below
15 Chrysotile No 74.00
Action 3
Action 3
Asbestos %
55 Chrysotile
Second Floor: 48Location Details: Classroom (Second Floor) Quantity/Condition
Asbestos %
2014/2015 Quantity
55 Chrysotile Yes
Asbestos Type
Friable Good Debris (if applicable)
Action 3
(if applicable)
Second Floor: 49Location Details: Classroom (Second Floor) Quantity/Condition Description of Action
RequiredAsbestos
%Asbestos
TypeFriable Good Debris
55 Chrysotile Yes *See Comments Below
(if applicable)
Second Floor: 50Location Details: Classroom (Second Floor) Quantity/Condition Description of Action
RequiredAsbestos
%Asbestos
TypeFriable Good Debris
55 Chrysotile Yes *See Comments Below
3.2 Chrysotile No 1
*See Comments Below
Description of Action Required
Action 3
Yes
3.2 Chrysotile No 1
3.2 Chrysotile No 1
3.2 Chrysotile No 1 Action 3
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
2014/2015 Quantity
2014/2015 Quantity
Golder Associates Page: 9
2434 - Waverley Drive PSUpper Grand District School Board
Asbestos Inspeciton FormConfirmed and Presumed ACM
1415652-L35
Location:
System Comp Material Description Units Accessibility Fair Poor
OTHER 815 Unidentified Board Behind Radiators
3 meter E
OTHER Gold Sink Acoustic 1 each AComments:
Location:
System Comp Material Description Units Accessibility Fair Poor
OTHER 815 Unidentified Board Behind Radiators
3 meter E
OTHER Gold Sink Acoustic 1 each AComments:
Location:
System Comp Material Description Units Accessibility Fair Poor
OTHER 815 Unidentified Board Behind Radiators
3 meter E
Comments:
Location:
System Comp Material Description Units Accessibility Fair Poor
PIPING SYSTEMS
500 Parging Cement on Fittings
1 each A
PIPING SYSTEMS
Aircell (presumed ACM) 1 meter A 1
Comments:
Location:
System Comp Material Description Units Accessibility Fair Poor
OTHER 815 Unidentified Board Behind Radiators
3 meter E
Comments:
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
Presumed Yes Action 2- See Comments Below
Aircell identified during 2014 reassessment in portion of pipe where outer layer was removed, possibly under other cellulose insulation, not previously observed.
(if applicable)
Second Floor: 51Location Details: Classroom (Second Floor) Quantity/Condition Description of Action
RequiredAsbestos
%Asbestos
TypeFriable Good Debris
55 Chrysotile Yes *See Comments Below
(if applicable)
Second Floor: 52Location Details: Classroom (Second Floor) Quantity/Condition Description of Action
RequiredAsbestos
%Asbestos
TypeFriable Good Debris
55 Chrysotile Yes
Description of Action Required
*See Comments Below
Second Floor: 53Location Details: Boy's Washroom (Second Floor) Quantity/Condition
Asbestos %
Asbestos Type
Friable Good Debris (if applicable)
55 Chrysotile Yes
(if applicable)
*See Comments Below
80
Second Floor: 54Location Details: Custodian Room (Second Floor) Quantity/Condition Description of Action
RequiredAsbestos
%Asbestos
TypeFriable Good Debris
Chrysotile Yes 1 Action 3
Second Floor: 55Location Details: Washroom (Second Floor) Quantity/Condition Description of Action
Required(if applicable)Asbestos
%Asbestos
TypeFriable Good Debris
2014/2015 Quantity
55 Chrysotile Yes *See Comments Below
3.2 Chrysotile No 1 Action 3
3.2 Chrysotile No 1 Action 3
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
2014/2015 Quantity
2014/2015 Quantity
2014/2015 Quantity
2014/2015 Quantity
Golder Associates Page: 10
2434 - Waverley Drive PSUpper Grand District School Board
Asbestos Inspeciton FormConfirmed and Presumed ACM
1415652-L35
Location:
System Comp Material Description Units Accessibility Fair Poor
OTHER 815 Unidentified Board Behind Radiators
3 meter E
OTHER Gold Sink Acoustic 1 each AComments:
Location:
System Comp Material Description Units Accessibility Fair Poor
PIPING SYSTEMS
500 Parging Cement on Fittings
2 each C
PIPING SYSTEMS
Aircell (presumed ACM) 10 meter E
Comments:
Board behind radiator was not observed; however, it is assumed to be behind the radiator in this area.
Description of Action Required
Asbestos %
Second Floor: 56Location Details: Classroom (Second Floor) Quantity/Condition
2014/2015 Quantity
55 Chrysotile Yes
Asbestos Type
Friable Good Debris (if applicable)
Asbestos %
Asbestos Type
Friable
*See Comments Below
Second Floor: 57Location Details: Storage (Second Floor) Quantity/Condition
(if applicable)
Description of Action Required
80 Chrysotile Yes 2 Action 3
Good Debris
3.2 Chrysotile No 1 Action 3
ActionCompleted
(dd-mm-yyyy)
ActionCompleted
(dd-mm-yyyy)
2014/2015 Quantity
Presumed Yes 10 Action 3- See Comments Below
Aircell presumed to be present beneath layered cardboard insulation over 6" pipe, not previously identified.
Golder Associates Page: 11
Golder Associates Ltd. 309 Exeter Road, Unit #1, London, Ontario, Canada N6L 1C1
Tel: +1 (519) 652 0099 Fax: +1 (519) 652 6299 www.golder.com
Golder Associates: Operations in Africa, Asia, Australasia, Europe, North America and South America
Golder, Golder Associates and the GA globe design are trademarks of Golder Associates Corporation.
Dear Ms. Millar:
Golder Associates Ltd. (Golder) is pleased to submit this letter summarizing the results of the 2016 visual reassessment of previously identified asbestos-containing materials (ACMs) located at Waverley Drive Public School in Guelph, Ontario (the Site). The field work to complete the scope of work described below was performed on July 26, 2016 by Tyler Thornton of Golder. As noted in Golder Proposal P1546270 dated April 20, 2016, Golder performed the following scope of work:
Visual reassessments of accessible ACMs previously identified in the 2014/2015 Reassessment Program, Golder Project Number 1415652, to determine the current condition of ACMs, as is required under Ontario Regulation 278/05 Designated Substance – Asbestos on Construction Projects and in Buildings and Repair Operations, as amended (O. Reg. 278/05);
Asbestos-containing ceiling tiles, fittings, etc. that were deemed to require repair or removal were physically marked with bright coloured stickers so that they can be easily identified by maintenance staff. Note that certain materials, such as vinyl floor tiles, wall and ceiling surfacing materials, caulking, etc., were not visually marked; and
Summary reporting of all previously identified ACMs remaining on-site in fair or poor condition and thus requiring action on the part of the UGDSB to repair or remove the identified ACMs. Identified ACMs in good condition do not require remedial action on the part of the UGDSB and, therefore, are not reported herein. Notwithstanding this, all previously identified ACMs remaining on-site have been re-quantified, on a room-by-room or location-by-location basis, on the attached eBase Report: All Asbestos-Containing Materials for the Site.
Reassessment methodology pertaining to the evaluation of observable ACMs, including the field criteria used to assess current condition, the accessibility of materials and assigned action responses are contained within an attachment to this letter report titled 2016 ACM Visual Reassessment Methodology and Criteria. Since the reassessment was based upon an asbestos building materials survey report provided by Golder to the UGDSB in 2007, the condition and accessibility criteria are identical to that previously used.
October 14, 2016 Project No. 1546270-L41
Ms. Lorraine Millar, Environmental Health & Safety Co-ordinator Upper Grand District School Board 500 Victoria Road North Guelph, Ontario N1E 6K2
2016 ASBESTOS-CONTAINING MATERIAL VISUAL REASSESSMENT WAVERLEY DRIVE PUBLIC SCHOOL 140 WAVERLEY DRIVE GUELPH, ONTARIO N1E 1H2 SFIS NO. 2434
Ms. Lorraine Millar, Environmental Health & Safety Co-ordinator 1546270-L41Upper Grand District School Board October 14, 2016
2/3
As previously reported in 2015, a simplified condition assessment response protocol has been implemented for the reassessment program using a three-stage action matrix rather than the original six-stage action matrix implemented in 2007. The three-stage action matrix accounts for the condition of ACM at the time of the visual reassessment and is further explained in the attached 2016 ACM Visual Reassessment Methodology and Criteria.
Visual Reassessment Findings The results of the condition reassessment are contained in the attached eBase Report: All Asbestos-Containing
Materials. The ACM quantities and condition have been updated to reflect those observed during the reassessment conducted by Golder in July of 2016. Response action priorities range from prompt repair and/or encapsulation of the material and/or resulting debris to on-going routine inspections of materials identified in good condition. ACMs with an assigned Priority 1 or 2 are summarized below. Items requiring Routine Inspection (Priority 3) only, based on an observed condition of ‘good’, are not summarized below as they do not require any remedial efforts.
Priority Materials Requiring Reponse Action
Priority 1 ACM was observed to be in poor condition and requires removal, repair and/or encapsulation of the material and/or resulting debris. This action should be completed as soon as possible.
No Priority 1 materials were observed at the time of the 2016 asbestos reassessment.
Priority 2
ACM requires minor work which, due to the nature and/or accessibility of the material, can be scheduled for completion over periods such as the Christmas or summer break, when staff and students are not present, provided that the work is completed within a reasonable time frame. Appropriate measures should be taken to ensure that the material is not further disturbed prior to the work commencing.
No Priority 2 materials were observed at the time of the 2016 asbestos reassessment.
Should the UGDSB required further information with regards to the information in this letter report, please contact Golder.
Limitations The conclusions and recommendations contained in this reassessment letter report are based upon professional opinions with regard to the subject matter. These opinions are in accordance with currently accepted industry practices and are subject both to the limitations contained in the 2007 asbestos building materials survey report and the following inherent limitations:
1. The data and findings presented in this report are valid as of the date(s) of the investigation only. The passage of time, manifestation of latent conditions or occurrence of future events may warrant further exploration of the Site, analysis of the data, and re-evaluation of the findings, observations, and conclusions expressed in this report.
2. The data reported and the findings, observations, conclusions, and recommendations expressed in this letter are limited by the Scope of Work. The Scope of Work was defined by the request of the client, the time and budgetary constraints imposed by the client, and availability of access to the Site.
3. Because of the limitations stated above, the findings, observations, conclusions, and recommendations expressed by Golder Associates Ltd. in this letter are not, and should not be, considered an opinion
Ms. Lorraine Millar, Environmental Health & Safety Co-ordinator 1546270-L41Upper Grand District School Board October 14, 2016
3/3
concerning compliance of any past or present owner or operator of the Site with any federal, provincial or local laws or regulations.
4. No warranty or guarantee, whether expressed or implied, is made with respect to the data or the reported findings, observations, and conclusions, which are based solely upon Site conditions in existence at the time of investigation.
5. Golder Associates Ltd. will not be responsible for any real or perceived decrease in a property value, its saleability or ability to gain financing through the reporting of information in this letter.
6. Golder Associates Ltd.’s assessment reports present professional opinions and findings of a scientific and technical nature. While attempts were made to relate the data and findings to applicable environmental and occupational health & safety laws and regulations, the letter shall not be construed to offer legal opinion or representations as to the requirements of, nor compliance with, environmental and occupational health & safety laws, rules, regulations or policies of federal, provincial, or local governmental agencies. Any use of the letter constitutes acceptance of the limits of Golder Associates Ltd.’s liability. Golder Associates Ltd.’s liability extends only to its client and not to other parties who may obtain this assessment report. Issues raised by the report should be reviewed by appropriate legal counsel.
Closure We trust that this letter meets your current requirements. If you have any questions regarding the content of this letter report, please do not hesitate to contact the undersigned.
Yours truly,
GOLDER ASSOCIATES LTD.
Jesse Clay Christopher Rahm, B.E.S. EHS Consultant Associate, Senior Occupational Hygienist JC/CJR/ly Attachments: 2016 ACM Visual Reassessment Methodology and Criteria
eBase Report: All Asbestos-Containing Materials (updated from 2016 Visual Reassessment)
n:\active\2015\3 proj\1546270 ugdsb_2016 reassessments_swo\7-correspondence\3-ltrs\l41 waverley drive ps\1546270-l41 oct 2016 waverley drive ps asbestos reassess.docx
2016 ACM Visual Reassessment Methodology and Criteria
October 2016 Project No. 1546270 1/2
Each previously identified and accessible asbestos-containing material (ACM) – either confirmed through previous sampling and subsequent laboratory analysis or presumed as an ACM – was evaluated based on its visually observable condition at the time of the ACM visual reassessment site visit. Table 1, below, outlines the criteria employed in the field to visually reassess the current condition of ACMs. Assigned conditions represent materials only at the time of the site visit, should not necessarily be considered accurate for future condition, and are considered subjective.
Table 1: Condition of Asbestos-Containing Materials Rank Descriptions
Good
Thermal system insulation on fittings, tanks, valves, boilers, ducts, pipes and other mechanical equipment, which is completely enclosed without significant damage.
Sprayed fireproofing or acoustical texture coatings showing no signs of delaminating or fall-out.
Non-friable materials not exhibiting significant damage or extensive wear.
Fair Pipe insulation showing some signs of physical damage or shrinkage cracks along pipe runs.
Poor
General damage to mechanical insulation or water damage exposing asbestos directly.
In areas of sprayed fireproofing or acoustic texture coatings, delaminating and the presence of fallen material on horizontal surfaces.
The absence of an enclosure (e.g. canvas wrap, foil tape) around asbestos-containing material which formerly had an enclosure.
Non-friable ACM severely damaged to the extent that asbestos fibres may be released.
NOTE: The evaluation of the condition of non-friable materials does not utilize a fair condition rating.
In addition to the current condition, all previously identified and accessible ACMs were also rated by Golder based on the ease with which they can be reached and, therefore, physically disturbed. The accessibility of materials known or suspected of being ACM were rated according to the following criteria outlined in Table 2.
Table 2: Accessibility
Access (A)
Materials within reach (from floor level) of all site users. These also include materials in gymnasiums, workshops, and storage areas where activities of the site users may result in disturbance of ACM not normally within reach from floor level. Visibility would typically be noted as “YES” for these items, except for under sinks, in closets, or other commonly accessed spaces.
Access (B)
Materials in frequently entered maintenance areas of the Site within reach of maintenance staff, without the need for a ladder. Includes materials within reach from a fixed ladder or catwalk (i.e., tops of equipment, mezzanines, and frequently entered pipe chases, tunnels and service areas). Visibility would typically be noted as “YES” for these items.
2016 ACM Visual Reassessment Methodology and Criteria
October 2016 Project No. 1546270 2/2
Access (C)
Materials above 8'-0" where use of a ladder is required to reach the ACM. Only includes ACMs that are exposed to view without the removal or opening of other building components such as ceiling tiles, or service access doors or hatches. Does not include materials in infrequently accessed service areas of the Site. Visibility would be noted as “YES” for these items.
Access (D)
Materials that cannot be reached without removing a building component, including lay-in ceilings or access panels in solid ceiling systems. Includes rarely entered crawl spaces, attic spaces, etc. Observations will be limited to the extent visible from access points. Visibility would be noted as “NO” for these items.
Access (E)
Materials behind inaccessible solid ceiling systems, walls or mechanical equipment, etc., where demolition of the ceiling, wall or equipment etc. is required to reach the ACM. These materials are visually identified by the surveyor, often with difficulty, and there may be uncertainty associated with them. Evaluation of condition and extent of ACM is limited or impossible, depending on the surveyor's ability to visually examine these materials. Visibility would be noted as “NO” for these items.
For each ACM or PACM identified, a specific response action priority has been assigned. The assigned priority is based on consideration of the type of asbestos present, the observed condition of the material and the accessibility of the material. These priorities are based on the likely risk posed by the material, with damaged materials that are easily accessible posing the greatest risk and materials in good condition in inaccessible areas posing the least risk. Response action priorities range from immediate clean-up of debris to on-going routine inspections of materials identified in good condition.
The following is a summary of the response action priorities assigned as a part of this reassessment:
Priority 1 – ACM was observed to be in poor condition and requires removal, repair and/or encapsulation of the material and/or resulting debris. This action should be completed as soon as possible.
Priority 2 – ACM that requires minor work which, due to the nature and/or accessibility of the material, can be scheduled for completion over periods such as the winter or summer break, when staff and students are not present, provided that the work is completed within a reasonable time frame. Appropriate measures should be taken to ensure that the material is not further disturbed prior to the work commencing. Continue with routine inspection of the ACM to monitor the condition, as per the Asbestos Management Program.
Priority 3 – ACM was observed to be in good condition and no work is currently required. Continue with routine inspection of the ACM to monitor the condition, as per the Asbestos Management Program. In the event of a building alteration which could impact the material, it will be necessary to remove the ACM, regardless of condition, that is likely to be disturbed by renovation, demolition or maintenance work.
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
Waverley Drive PS140 Waverley DrGuelph N1E 1H2
Last survey date: Jul 12th, 2016
1 Office (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 30 square metre
Material VFT Dark Blue With White Streaks (9x9) Quantity Good 30 square metre
Application Quantity Fair
Notes Quantity Poor
Comments
Approximately half of the VFT were covered
with carpet in 2014. Board behind radiator
was not observed; however, it is assumed to
be behind the radiator in this area.
Access/Action Action 3
Condition Sample No. 102
Friable No Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
10 Con. Ed. Classroom (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
Comments Access/Action Action 3
Page 1/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
Condition Sample No. 815
Friable Yes Debris N/A
11 Music (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 1 each
Material Gold Sink Acoustic Quantity Good 1 each
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No.
Friable No Debris N/A
12 Classroom #6 (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 68 square metre
Material VFT Light Blue With White Streaks (9x9) Quantity Good 68 square metre
Application Quantity Fair
Notes Quantity Poor
CommentsSink replaced 2013. Board behind radiator
was not observed; however, it is assumed to
be behind the radiator in this area.
Access/Action Action 3
Condition Sample No. 103
Page 2/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
Friable No Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 5 square metre
Material VFT White With Black Streaks (9x9) Quantity Good 5 square metre
Application Quantity Fair
Notes Quantity Poor
CommentsSink replaced 2013. Board behind radiator
was not observed; however, it is assumed to
be behind the radiator in this area.
Access/Action Action 3
Condition Sample No. 104
Friable No Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsSink replaced 2013. Board behind radiator
was not observed; however, it is assumed to
be behind the radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
13 Classroom #4 (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 68 square metre
Material VFT Light Blue With White Streaks (9x9) Quantity Good 68 square metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 103
Friable No Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 5 square metre
Page 3/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
Material VFT White With Black Streaks (9x9) Quantity Good 5 square metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 104
Friable No Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
14 Classroom #2 (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 68 square metre
Material VFT Light Blue With White Streaks (9x9) Quantity Good 68 square metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 103
Friable No Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 5 square metre
Material VFT White With Black Streaks (9x9) Quantity Good 5 square metre
Application Quantity Fair
Notes Quantity Poor
Page 4/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 104
Friable No Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
15 Washroom (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 2 metre
Material Unidentified Board Behind Radiators Quantity Good 2 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
16 Washroom (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 2 metre
Material Unidentified Board Behind Radiators Quantity Good 2 metre
Application Quantity Fair
Notes Quantity Poor
Board behind radiator was not observed;
Page 5/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
Comments however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
17 Staff Room (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 8 metre
Material Unidentified Board Behind Radiators Quantity Good 8 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
2 V.P. Office (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 20 square metre
Material VFT White With Black Streaks (9x9) Quantity Good 20 square metre
Application Quantity Fair
Notes Quantity Poor
Comments Access/Action Action 3
Condition Sample No. 104
Friable No Debris N/A
20
ACM Yes Asbestos Type Presumed
Structural Element PIPING SYSTEMS Quantity 10 metre
Material Aircell (presumed ACM) Quantity Good 10 metre
Application Quantity Fair
NotesAircell presumed to be present beneath
layered cardboard insulation over 6" pipe,
not previously identified.
Quantity Poor
Page 6/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
Comments 2016: unable to locate Access/Action Action 3
Condition Sample No.
Friable Yes Debris N/A
22 Resource (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 8 square metre
Material VSF Taupe Quantity Good 8 square metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 151
Friable No Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 4 metre
Material Unidentified Board Behind Radiators Quantity Good 4 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
23 Resource (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 25 square metre
Material VSF Taupe Quantity Good 25 square metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Page 7/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
Condition Sample No. 151
Friable No Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 4 metre
Material Unidentified Board Behind Radiators Quantity Good 4 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 1 each
Material Gold Sink Acoustic Quantity Good 1 each
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No.
Friable No Debris N/A
24 Girl's Washroom (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 2 metre
Material Unidentified Board Behind Radiators Quantity Good 2 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
Page 8/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
26b (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
27 Fitness Room (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
28 Develop H/C (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 8 metre
Material Unidentified Board Behind Radiators Quantity Good 8 metre
Application Quantity Fair
Notes Quantity Poor
CommentsVSF replaced 2012. Board behind radiator
was not observed; however, it is assumed to
be behind the radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Page 9/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
Friable Yes Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 1 each
Material Gold Sink Acoustic Quantity Good 1 each
Application Quantity Fair
Notes Quantity Poor
CommentsVSF replaced 2012. Board behind radiator
was not observed; however, it is assumed to
be behind the radiator in this area.
Access/Action Action 3
Condition Sample No.
Friable No Debris N/A
29 Integrated Technology (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 70 square metre
Material VSF Taupe Quantity Good 70 square metre
Application Quantity Fair
Notes Quantity Poor
Comments Access/Action Action 3
Condition Sample No. 151
Friable No Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 1 each
Material Gold Sink Acoustic Quantity Good 1 each
Application Quantity Fair
Notes Quantity Poor
Comments Access/Action Action 3
Condition Sample No.
Friable No Debris N/A
3 Storage (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 20 square metre
Material VFT Light Blue With White Streaks (9x9) Quantity Good 20 square metre
Application Quantity Fair
Page 10/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
Notes Quantity Poor
Comments Access/Action Action 3
Condition Sample No. 103
Friable No Debris N/A
30 Classroom (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 1 each
Material Gold Sink Acoustic Quantity Good 1 each
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No.
Friable No Debris N/A
31 Washroom (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the Access/Action *Action 3
Page 11/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
radiator in this area.
Condition Sample No. 815
Friable Yes Debris N/A
32 Washroom (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
33
ACM Yes Asbestos Type Presumed
Structural Element PIPING SYSTEMS Quantity 10 metre
Material Aircell (presumed ACM) Quantity Good 10 metre
Application Quantity Fair
Notes 2016: No access to ceiling space. Quantity Poor
CommentsAircell presumed to be present beneath
layered cardboard insulation over 6" pipe,
not previously identified.
Access/Action Action 3
Condition Sample No.
Friable Yes Debris N/A
34 Classroom (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 25 square metre
Material VFT Light Blue With White Streaks (9x9) Quantity Good 25 square metre
Application Quantity Fair
Notes Quantity Poor
Board behind radiator was not observed;
Page 12/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
Comments however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 103
Friable No Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
35 Classroom (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
36 Seminar Room (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 40 square metre
Material VFT Light Blue With White Streaks (9x9) Quantity Good 40 square metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the Access/Action Action 3
Page 13/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
radiator in this area.
Condition Sample No. 103
Friable No Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
37 Special Ed. (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
38 Kindergarten (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Page 14/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
Condition Sample No. 815
Friable Yes Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 1 each
Material Gold Sink Acoustic Quantity Good 1 each
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No.
Friable No Debris N/A
39
ACM Yes Asbestos Type Presumed
Structural Element PIPING SYSTEMS Quantity 10 metre
Material Aircell (presumed ACM) Quantity Good 10 metre
Application Quantity Fair
Notes Quantity Poor
CommentsAircell presumed to be present beneath
layered cardboard insulation over 6" pipe,
not previously identified.
Access/Action Action 3
Condition Sample No.
Friable Yes Debris N/A
4 Principal's Office (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 32 square metre
Material VFT Dark Blue With White Streaks (9x9) Quantity Good 32 square metre
Application Quantity Fair
Notes Quantity Poor
CommentsWallboard ladt observed in 2011 and
assumed to have been removed.Access/Action Action 3
Condition Sample No. 102
Friable No Debris N/A
Page 15/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
41 Classroom (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 72 square metre
Material VSF Taupe Quantity Good 72 square metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 151
Friable No Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 1 each
Material Gold Sink Acoustic Quantity Good 1 each
Page 16/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No.
Friable No Debris N/A
42 Classroom (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 74 square metre
Material VSF Taupe Quantity Good 74 square metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 151
Friable No Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 1 each
Material Gold Sink Acoustic Quantity Good 1 each
Application Quantity Fair
Notes Quantity Poor
Board behind radiator was not observed;
Page 17/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
Comments however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No.
Friable No Debris N/A
48 Classroom (Second Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
49 Classroom (Second Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 1 each
Material Gold Sink Acoustic Quantity Good 1 each
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the Access/Action Action 3
Page 18/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
radiator in this area.
Condition Sample No.
Friable No Debris N/A
5 Custodian Room (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element PIPING SYSTEMS Quantity 4 each
Material Parging Cement on Fittings Quantity Good 4 each
Application Quantity Fair
Notes Quantity Poor
Comments Access/Action Action 3
Condition Sample No. 500
Friable Yes Debris N/A
50 Classroom (Second Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
51 Classroom (Second Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Page 19/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
Condition Sample No. 815
Friable Yes Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 1 each
Material Gold Sink Acoustic Quantity Good 1 each
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No.
Friable No Debris N/A
52 Classroom (Second Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 1 each
Material Gold Sink Acoustic Quantity Good 1 each
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No.
Friable No Debris N/A
Page 20/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
53 Boy's Washroom (Second Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
54 Custodian Room (Second Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element PIPING SYSTEMS Quantity 1 each
Material Parging Cement on Fittings Quantity Good 1 each
Application Quantity Fair
Notes Quantity Poor
Comments
Aircell identified during 2014 reassessment
in portion of pipe where outer layer was
removed, possibly under other cellulose
insulation, not previously observed.
Access/Action Action 3
Condition Sample No. 500
Friable Yes Debris N/A
ACM Yes Asbestos Type Presumed
Structural Element PIPING SYSTEMS Quantity 1 metre
Material Aircell (presumed ACM) Quantity Good 1 metre
Application Quantity Fair
Notes Quantity Poor
Comments
Aircell identified during 2014 reassessment
in portion of pipe where outer layer was
removed, possibly under other cellulose
insulation, not previously observed.
Access/Action Action 3
Condition Sample No.
Page 21/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
Friable Yes Debris N/A
55 Washroom (Second Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
56 Classroom (Second Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 3 metre
Material Unidentified Board Behind Radiators Quantity Good 3 metre
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No. 815
Friable Yes Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element OTHER Quantity 1 each
Material Gold Sink Acoustic Quantity Good 1 each
Application Quantity Fair
Notes Quantity Poor
CommentsBoard behind radiator was not observed;
however, it is assumed to be behind the
radiator in this area.
Access/Action Action 3
Condition Sample No.
Friable No Debris N/A
Page 22/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
57 Storage (Second Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element PIPING SYSTEMS Quantity 2 each
Material Parging Cement on Fittings Quantity Good 2 each
Application Quantity Fair
Notes Quantity Poor
CommentsAircell presumed to be present beneath
layered cardboard insulation over 6" pipe,
not previously identified.
Access/Action Action 3
Condition Sample No. 500
Friable Yes Debris N/A
ACM Yes Asbestos Type Presumed
Structural Element PIPING SYSTEMS Quantity 10 metre
Material Aircell (presumed ACM) Quantity Good 10 metre
Application Quantity Fair
Notes Quantity Poor
CommentsAircell presumed to be present beneath
layered cardboard insulation over 6" pipe,
not previously identified.
Access/Action Action 3
Condition Sample No.
Friable Yes Debris N/A
6 Integrated Technology (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 68 square metre
Material VFT Light Blue With White Streaks (9x9) Quantity Good 68 square metre
Application Quantity Fair
Notes Quantity Poor
Comments Access/Action Action 3
Condition Sample No. 103
Friable No Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 15 square metre
Material VFT White With Black Streaks (9x9) Quantity Good 15 square metre
Page 23/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
Application Quantity Fair
Notes Quantity Poor
Comments Access/Action Action 3
Condition Sample No. 104
Friable No Debris N/A
7 Classroom (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 72 square metre
Material VFT Light Blue With White Streaks (9x9) Quantity Good 72 square metre
Application Quantity Fair
Notes Quantity Poor
Comments Access/Action Action 3
Condition Sample No. 103
Friable No Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 15 square metre
Material VFT White With Black Streaks (9x9) Quantity Good 15 square metre
Application Quantity Fair
Notes Quantity Poor
Comments Access/Action Action 3
Condition Sample No. 104
Friable No Debris N/A
8 Classroom (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 72 square metre
Material VFT Light Blue With White Streaks (9x9) Quantity Good 72 square metre
Application Quantity Fair
Notes Quantity Poor
Comments Access/Action Action 3
Condition Sample No. 103
Friable No Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 15 square metre
Page 24/25
All Asbestos-Containing MaterialsGenerated: Sep 29, 2016 - 6:22 pm
Material VFT White With Black Streaks (9x9) Quantity Good 15 square metre
Application Quantity Fair
Notes Quantity Poor
Comments Access/Action Action 3
Condition Sample No. 104
Friable No Debris N/A
9 Con. Ed. Classroom (Main Floor)
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 10 square metre
Material VFT Dark Blue With White Streaks (9x9) Quantity Good 10 square metre
Application Quantity Fair
Notes Quantity Poor
Comments Access/Action Action 3
Condition Sample No. 102
Friable No Debris N/A
ACM Yes Asbestos Type Chrysotile
Structural Element FLOOR Quantity 10 square metre
Material VFT White With Black Streaks (9x9) Quantity Good 10 square metre
Application Quantity Fair
Notes Quantity Poor
Comments Access/Action Action 3
Condition Sample No. 104
Friable No Debris N/A
K Exterior (Outside)
ACM Yes Asbestos Type Chrysotile
Structural Element STRUCTURE Quantity 10 square metre
Material Exterior Plaster Quantity Good 10 square metre
Application Quantity Fair
Notes Quantity Poor
Comments Access/Action Action 3
Condition Sample No. 310
Friable Yes Debris N/A
Page 25/25