Fire protection. Box, housing and sealing systems for fire-protection walls and ceilings.
2 www.kaiser-elektro.de
For safe functions, rooms and escape routes.Fire-protection technology.When it comes to protecting buildings against danger from fire,
planners and installers of building technology play a vital role. Even strict
fire regulations provide no guarantee against fire. The greatest risk is not
caused by the building itself, but by technical and electrical equipment.
More than 90% of fire victims and approximately 70% of property
damage are not the direct result of the fire but of the hazardous and
toxic smoke produced by the fire. So, in addition to avoiding and
combating fire, the main aim is to prevent the formation and dispersion
of smoke gas.
The most important tasks of preventative fire protection are the
saving of human life and minimising of property damage. To do this,
above all it is necessary to guarantee the functional integrity of the
fire-protection equipment, the usability of the escape routes, and access
by the emergency services.
KAISER fire-protection systems offer you reliable solutions for
installations in fire protection ceilings and walls. These solutions also
ensure the required fire-protection classes if a fire starts. Intelligent
products for active and preventative fire-protection are produced in
halogen-free and fire-resistant materials which correspond to the
current statutory and technical requirements. Products for walls and
ceilings in buildings and for shipbuilding walls. Products whose
reliability can save lives and prevent catastrophes.
3
Fire protection
Legal requirements. Fire-protection technology. 04Building material and fire-resistance classes. DIN 4102. 06European Technical Approval ETA-11/0188 08Walls and ceilings. DIN 4102. 10Keeps escape routes free in an emergency. KAISER AFS-technology. 12
Further information on KAISER fire-protection technology and products can be found on our website or obtained directly from KAISER (see also last page). Technical advice - Telephone: +49(0)2355.809.61
Fire-proof and smokeproof walls in ship cabins. Fire-protection technology in shipbuilding. 40For cabin walls in shipbuilding. HWD B15 fire-protection one-gang boxes. 42
Installationin walls
Installationin ship walls
Installation in walls. Penetration
and entry
Installationin ceilings
Safety and fire-protection in electrical installation. Fire-resistant and halogen-free. 44Fire-protection technology. At a glance. 46KAISER product range 48
Requirement Product solution
Penetration and entries in cavity calls, masonry and concrete. Fire sealings. 20Safe penetration and entry. Also retrofitting Cable sealing systems LS 90. Conduit sealing systems RS 90. 22 Installation also in concrete and masonry. Cable and conduit sealing systems LS 90 / RS 90. 24Bundled through any wall. Safe. Also for retrofitting. Box sealing systems DS 90 and DS 90/120 mm. 26Installation also in concrete and masonry. Box sealing systems DS 90 and DS 90 / 120 mm. 30Easy sealing - permanently tight Sealing plugs. 32
Safe up to class F90. HWD 90 fire-protection one-gang boxes. 14Installation shafts and ducts. Fire-protection technology. 16For safe room seperation Electronics box HWD 90. 18
For fire-protection ceilings up to F90. HWD 30 fire-protection one-gang boxes. 34For luminaires and loudspeakers. FlamoX® fire-protection housings. 36Preventative fire-protection in insulated ceilings. ThermoX® installation housings. 38
4 www.kaiser-elektro.de
Legal requirements.Fire-protection technology.
*§ 14 MBO fire protection Nov. 2002
Building installations are to be laid out, built, altered and maintained in
such a way that the occurrence of fire and the spreading of fire and
smoke are prevented, and in the event of a fire it will be possible to
save people and animals and fight the fire effectively.
As a result of federalism, building law in Germany is the responsibility of
the Federal States. In a joint working group (ARGEBAU), the Federal min-
istries responsible for the building industry are drawing up sample draft
laws which can, depending on the Federal State, and with more or fewer
amendments, become valid as a law, regulation or guideline for that
State. § 14* of the standard building regulations (MBO) defines the basis
for fire protection:
The requirements of the building regulations and Federal State
building regulations are supplemented by various decrees, by-laws,
technical building regulations and general technical standards. In addi-
tion, lack of fire protection is considered to be an intentionally
concealed defect with a 30-year term of liability. Furthermore, planners
and contractors have a legal duty to implement safety precautions during
the entire period of use of a building. In the event of physical injuries
(fatality), the full extent of §319* (endangerment in construction) of the
German Criminal Code applies, and substantial fines or even imprison-
ment can be imposed on those responsible.
5
Legal requirements | Fire protection
The state building regulations (LBO) differentiate between:
• Buildings of normal type or usage
(residential and buildings of comparable usage)
• Buildings of special type or usage
(industrial, public assembly or hospitals ...)
DIN 4102 defines the requirements in respect of the quality of walls
and ceilings for fire resistance classes. The specified fire resistance class
depends on the use and class of the building (see also table on page 07).
Additional regulations apply to "buildings of normal type or
usage" including for public assembly, mobile shops, and hospital, school
or industrial buildings.
FFL ≤ 13 m
other buildingsH > 8 m
tower blocksone recreation room
buildings
FFL > 22 m
FFL ≤ 7 m
≤ 8
m
residential buildings
low heightladder accessibility H ≤ 8 m
FFL ≤ 7 m
fire-fighting operation with scaling ladders
Building
classification 1
• Free-standing building
up to 7 m high
max. two usable
units (max. 400 m²)
and
• Free-standing building
for agricultural or
forestry use
Building
classification 2
• Up to 7 m high
max. two usable units
(max. 400 m²)
Building
classification 4
• Up to 13 m high
Usable units up to
max. 400 m²
Building
classification 5
• Other buildings
including under-
ground structures
Building
classification 3
• Other buildings up
to 7 m high
Further information on KAISER fire-protection technology and products can be found on our website or obtained directly from KAISER (see also last page). Technical advice - Telephone: +49(0)2355.809.61
The building regulations (BauO) specify the conditions which all
construction projects must observe. The requirements apply to the land
and to any buildings erected on it, and include:
• Observation of clearances
• The statics
• Regulations for emergency exits
• Protection against moisture
• Fire protection and heat protection
6 www.kaiser-elektro.de
Building material classes and fire resistance classes.DIN 4102.
A1 non-combustible materialswithout organic elements
combustible materialsflame-retardant B1
The fire behaviour of building materials is influenced by the type,
design, surface, mass, material combinations and processing technology.
Building materials are grouped into classes A or B according to their fire
behaviour:
Building material class A – non-combustible materials
A1 - without organic elements
A2 - with organic elements
Building material class B – combustible materials
B1 - flame-retardant building materials
B2 - building materials of normal flammability
B3 - easily flammable building materials
A2 non-combustible materialswith organic elements
B2 combustible materialsnormal flammability
The fire-resistance period is the minimum time in minutes during
which a building component exposed to fire must not exceed an average
rise in temperature of 140 K (max. 180 K at individual sites) on the side
not exposed to the fire (acc. to DIN 4102-2).
The fire-resistance period is divided into the following classes:
F0/30 fire-retardant
F60 extremely fire-retardant
F90/120/180 fire-resistant / extremely fire-resistant
7
Building material and fire resistance classes | DIN 4102
DIN 4102 specifies test procedures and in part 4 contains a list and application of clas-sified building materials, building components and special parts for various building protection classes.
Fire protection classes acc. to DIN 4102
are designated with abbreviations depending on the component
Examples of fire-protection classes:
Walls, ceilings, supports F30/60/...
Fire-protection walls F90/120/...
FS closures (doors etc.) T30/60/...
Cable sealings S30/60/90/...
Installation channels I30/60/90/...
Conduit feed-throughs R30/60/90/...
Functional integrity of electr. cables E30/60/90/...
Examples of designations
F30-A fire-retardant/non-combustible building materials
F30-B fire-retardant/combustible building materials
F90-A fire-resistant/non-combustible building materials
F30-AB fire-resistant/non-combustible and combustible building
materials
Component
§ MBO building class§ 2 1 2 3 4 51) h ≤ 7 m h ≤ 13 m h ≤ 22 m
Load-bearing walls § 27 F0 F30 F30 F60 F90
Load-bearing walls, supports in basement F30 F30 F90 F90 F90
Load-bearing walls, supports in attic, if there are recreation rooms above F0 F30 F30 F 60 F90
Non load-bearing external walls § 28 none A or F30 A or F30
Separator walls § 29 F0 F302) F30 F60 F90
Ceilings § 31 F0 F30 F30 F60 F90
Ceilings in attic if there are recreation rooms above F0 F30 F30 F60 F90
Ceilings in basement F30 F30 F90 F90 F90
1) The height relates to the top edge of the floor on the top storey over the ground 2) Does not apply to residential buildings
Fire-protection specifications acc. to MBO
Assignment of fire-protection and fire-resistance classes in building construction
8 www.kaiser-elektro.de
English translation prepared by DIBt - Original version in German language
Handelsbezeichnung
Trade name
"KSS Kaiser Schott System (DS 90, RS 90, LS 90)"
Zulassungsinhaber
Holder of approval
KAISER GMBH & CO. KG
Ramsloh 4
58579 Schalksmühle
DEUTSCHLAND
Kabelabschottungen
European Technical Approval ETA-11/0188
Page 11 of European technical approval ETA-11/0188 on 22 June 2011 English translation prepared by DIBt
"LS 90"
"RS 90"
Opening slit
Opening slit
Number of ETA and CE-marking
Zulassungsinhaber
Holder of approval DEUTSCHLAND
Zulassungsgegenstand
und Verwendungszweck
Kabelabschottungen
Generic type and use
of construction product
cable penetration seals
Geltungsdauer:
Validity:
vomfrom
22 June 2011
bisto
22 June 2016
KAISER GMBH & CO. KG
Ramsloh 4
58579 Schalksmühle Plug for cable conduits
ETA-11/0188
Diese Zulassung umfasst This Approval contains
17 Seiten einschließlich 9 Anlagen 17 pages including 9 annexes
E u r o p ä i s c h e O r g a n i s a t i o n f ü r T e c h n i s c h e Z u l a s s u n g e n
E u r o p e a n O r g a n i s a t i o n f o r T e c h n i c a l A p p r o v a l s
Z12878.11 8.11.04-5/10
English translation prepared by DIBt - Original version in German language
HandelsbezeichnungTrade name
"KSS Kaiser Schott System (DS 90, RS 90, LS 90)"
ZulassungsinhaberHolder of approval
KAISER GMBH & CO. KG Ramsloh 4 58579 Schalksmühle DEUTSCHLAND
Zulassungsgegenstandund Verwendungszweck
Kabelabschottungen
Generic type and use of construction product
cable penetration seals
Geltungsdauer:Validity:
vomfrom
22 June 2011
bisto
22 June 2016
HerstellwerkManufacturing plant
KAISER GMBH & CO. KG Ramsloh 4 58579 Schalksmühle DEUTSCHLAND
European Technical Approval ETA-11/0188
KAISER has Europe-wide approvalfor fire-sealings!ETA-11/0188The German Institute for Building Technology (DIBt) has officially confirmed it:
KAISER fire sealings are perfect for professional electrical installations in fire-
protection walls. As a brand-name manufacturer of electrical installation sys-
tems, KAISER has been awarded the Europe-wide European Technical
Approval for its innovative fire sealings.
In addition to the successful fire test - approval ETA-11/0188 - safe, easy,
clean installation of the KAISER sealing is the principal factor for successful
positioning in the electrical trade. These sealings are easily installed using
standard tools - with no smoothing and filling at all. There is no need for spe-
cial training.
The fire sealings are certified for installation in drywalls, solid masonry and con-
crete construction walls. Non-destructive fitting of additional cables is easy.
The European Technical Approval applies to all three KAISER fire sealing sys-
tems i.e. for cable, conduit and box sealings. Each of the tested products is
given the wall's fire resistance class and does not release any hazardous
materials. This means that in every respect, KAISER fire sealings make possi-
ble fast, professional and safe sealing in fire-protection walls.
9
Attachment part "DS 90 Dichtelement"
Attachment part "DS 90 Dichtelement"
Attachment part "DS 90 Dichtelement"
Attachment part "DS 90 Dichtelement"
* = Diameter of
the opening
Space for the
"Dichteinsatz"
ETA N° and
CE marking
Attachment part "DS 90 Dichtelement"
Attachment part "DS 90 Dichtelement"
Attachment part "DS 90 Dichtelement"
Attachment part "DS 90 Dichtelement"
*
*
* = Diameter of the opening
Number of ETA and CE-marking
Article number
Article number
"KSS Kaiser Schott System (DS 90, RS 90, LS 90)"
APPENDIX 1 – DESCRIPTION OF THE PRODUCT
Description of the product components – Dimensions
Annex 2
Dimensions in mm
Number of ETA and CE-marking
* = Diameter of the opening "KSS Kaiser Schott System (DS 90, RS 90, LS 90)"
"KSS Kaiser Schott System (DS 90, RS 90, LS 90)"
"KSS Kaiser Schott System (DS 90, RS 90, LS 90)"
APPENDIX 1 – DESCRIPTION OF THE PRODUCT Number of ETA and
* = Diameter of the opening * = Diameter of the opening "KSS Kaiser Schott System (DS 90, RS 90, LS 90)"
"KSS Kaiser Schott System (DS 90, RS 90, LS 90)"
"KSS Kaiser Schott System (DS 90, RS 90, LS 90)"
Dimensions in mm Dimensions in mm
AustriaBelgiumCyprusCzech RepublicDenmarkFinlandFranceGermanyGreat BritainGreeceHungaryIcelandIrelandItaly
LatviaLithuaniaLuxembourgNetherlandsNorwayPolandPortugalSlovakiaSloveniaSpainSwedenSwitzerlandTurkey
The following 27 countries are members of EOTA (the European Organi-
sation for Technical Approvals), the international association which draws
up the guidelines for a European Technical Approval.
KAISER's cable sealing system LS 90, conduit sealing system RS 90 and box sealing DS 90 are shown on pages 18-23.
10 www.kaiser-elektro.de
Walls and ceilings.DIN 4102.
In principle, fire-protection walls or ceilings must not have any open-
ings. However, if these are required to enable the building to be used as
specified, covers for windows, channels or installations must be fitted
with fire resistance lasting at least 30 to 90 minutes (e.g. F90 / T90 / S90).
Incorrectly executed openings would considerably weaken the fire section
separation.
Fire-protection walls with fire resistance class F30-F180 acc. to
DIN 4102-4 are single or double shell, non load-bearing, internal separa-
tor walls with wall thicknesses of 100 mm and above, insulating material
acc. to DIN 4102-17, and 2 x 12.5 mm plasterboard panels. According to
DIN 4102, the opposing installation of conventional cavity wall boxes is
not allowed and the installation of individual boxes is only permitted to a
limited extent. The customer must fit some form of sheath, e.g. with plas-
ter, fibre silicate or similar.
KAISER fire-protection one-gang boxes and housings completely
satisfy these requirements.
• Construction of F90 metal stud walling
acc. to DIN 4102 part 4
11
Walls and ceilings | DIN 4102
• Construction type I, II, III
Sub-ceilings below rough ceilings in accordance with DIN 4102-4 of
construction type I, II, III. The ceiling construction - rough ceilings and
sub-ceiling - provides the required fire resistance.
Fire-protection ceilings in accordance with DIN 4102 are either inde-
pendent ceiling constructions or suspended ceilings used with ceilings of
construction type I, II or III (concrete ceilings, brick ceilings). From fire-pro-
tection class F30 upwards, DIN 4102 requires a closed visible surface.
Openings, for example for luminaires, must be equipped with a suitable
sealing.
FlamoX® installation housings from KAISER (see page 18) are fire-
protection housings specially developed for F30 ceilings.
Fire load from the underside of the ceiling
Fire load from the ceiling void
Fire load from the underside of the ceiling and fire load from the topside of the ceiling
• Installation of a 2-layer F30 fire-protection ceiling in accordance
with DIN 4102 Part 4
a) Spacing of the vernier brackets 1000 mm
b) Spacing of the carrier profile 500 mm
c) Spacing of the basic profile 1000 mm
• I ndependent sub-ceilings
The self-supporting sub-ceiling provides the necessary fire resistance
independently of the rough ceiling.
DIN 4102 establishes testing procedures. and Part 4 contains a composition and applica-tion of classified materials, components and special parts for different fire-protection classes.
Measurement points
a
bc
12 www.kaiser-elektro.de
Protects escape routes in emergencies.KAISER AFS-technology.
In the event of a fire, KAISER AFS-technology maintains the fire-pro-
tection class of ceilings and walls, even with opposing installation without
encasing. The ready-to-fit systems with AFS-technology guarantee certi-
fied security and problem-free installation.
AFS – Active Fire Stop. This technology guarantees preventative, active
fire protection. Whether a fire starts from above, below, the front or the
back, the fast-acting insulation layer in housings and boxes reacts imme-
diately, generating foam which reliably seals the installation opening. The
fire-protection class of the ceiling is retained up to F30 and of the wall up
to F90. This successfully prevents the spread of smoke and fire.
EI 90
EI 90
TECHNIK
13
Fire protection | AFS-technology
S30
The high level of quality and the reliability of the AFS-technology
save lives and prevent catastrophes in buildings and on ships. In cavity
wall and ceiling boxes as well as in FlamoX® installation housings, this
intelligent technology is already the new KAISER standard.
KAISERTECHNOLOGY. For your future.
More information on KAISER fire-protection technology and products can be foundon our website or obtained directly from KAISER (see also last page). Technical advice - Telephone: +49(0)2355.809.61
Heat generation causes the intumescing material to foam.
14 www.kaiser-elektro.de
For safety up to F90.HWD 90 fire-protection boxes.
Smoke and fire have no chance against the cavity wall boxes for
F30 - F90 fire-protection walls. Intelligent AFS-technology reacts
immediately to fire and heat and automatically seals the installation open-
ings. This guarantees the fire-protection class of the fire-protection wall,
protects escape routes and saves lives.
DiBt approval and various awards prove the reliable quality of KAISER
HWD 90 one-gang boxes and HWD 90 one-gang junction boxes.
• For fire-protection walls F30-F90
• Also for retrofitting
• Installation up to 5-unit combinations
• Also for opposing installation
• If fitted with a fire-protection cover, can be used as a junction box
DIBt approvalZ-19.21-1788
(German Institute of Building Technology)
TECHNIK
Production innovation award for refur-bishing
15
Fire protection | Fire-protection one-gang box HWD 90
Without encasing, and with its certified safety levels, the HWD90
lets you install switches or sockets in fire-protection walls without chang-
ing the fire-protection class. Even opposing box installation and retrofits
can be carried out without any problems. Installation is as easy as with a
cavity wall box.
If there is a fire, the integrated insulation layer used in KAISER AFS-tech-
nology reacts automatically in the shortest possible time. The material
generates foam and reliably seals the installation opening in the fire-pro-
tection wall.
HWD 90 one-gang box | Art. No. 9463-01
HWD 90 one-gang junction box | Art. No. 9464-01
Fire-protection cover | Art. No. 1184-94
KAISER one-gang junction boxes are shown on pages 26/27.Fire-protection boxes for shipbuilding walls are shown on pages 32/33.
1
2
34
1 FX4 technology | 2 One-gang box | 3 One-gang junction box
4 Fire-protection cover
16 www.kaiser-elektro.de
Installation shafts and ducts.Fire-protection technology.
In installation shafts and ducts, the HWD 90 one-gang boxes guaran-
tee fire-resistance class 130 to 190 for up to 5-unit combinations. Fire
resistance class 130 is achieved without insulation, and even up to class
190 with insulation.
• For insulation shafts 130-190
• Without encasing
• Certified security up to 5-unit combinations
• Also for retrofitting
• With a fire-protection cover, also as a junction box
• Easy fitting in just a few steps
TECHNIK
DIBt approvalZ-19.21-1788
(German Institute of Building Technology)
17
HWD 90 boxes are ideal for front fitting in installation shafts. They
guarantee that fire resistance class 130 is maintained.
HWD 90 boxes can also be retrofitted. Installation takes place via a
wall opening through the shaft wall. Insulation is fitted in accordance
with the fire resistance class, and the cut-out is closed before installation
of the cavity wall box.
The easy fitting of HWD cavity wall boxes in shaft walls and using
standard tools is an efficient, secure alternative to complicated, time-con-
suming encasing from the rear.
HWD 90 one-gang box | Art. No. 9463-01
HWD 90 one-gang junction box | Art. No. 9464-01
Fire-protection cover | Art. No. 1184-94
KAISER one-gang boxes for fire-protection ceilings are shown on pages 26/27.Fire-protection boxes for shipbuilding walls are shown on pages 32/33.
Fire protection | Installation shafts and ducts
1
2
34
1 FX4 technology | 2 One-gang box | 3 One-gang junction box
4 Fire-protection cover
18 www.kaiser-elektro.de
For safe room separation.Electronics box HWD 90.
The electronics box HWD 90 maintains the wall's fire-resistance class (F30 –
F90) and makes possible the necessary installation space for electronic switch-
ing devices, data boxes, cables and terminals. The electronics box makes
possible population with cables and also with installation conduits up to M25.
• For fire-protection walls F30 – F90
• For cables and conduits up to M25
• Also for use as a double box
• Extra-large terminal area for communications and network technology
• Additional space for electronic components (EIB actuators, relays, radio
module, communications technology)
TECHNIK
19
The electronics box HWD90 creates safe, certified, fire-protection room
separation. Fires spread more slowly. The period of fire resistance up to
F90 is guaranteed. The bridge creates additional installation space for
electronic components. The easy removal of the bridge allows fast, easy
replacement of the electronic components at any time. When the remov-
able cover is used together with the removable bridge, connection and
insertion of the components and cables is easy. Removal of the bridge and
the cover allows easy connection and insertion of components and cables,
and also use as a double box.
Screw fixing ensures fast, easy mounting. Additional encasing is not nec-
essary, so the electronics box HWD90 can also be retrofitted. Variable
cable and conduit entry up to M25 permits flexible installation.
Electronics box HWD 90 | Art. No. 9462-94
Fire protection | Installation shafts /ducts
1
3
2
1 FX4 technology | 2 Screw | 3 Bridge
20 www.kaiser-elektro.de
Sealings in fire-protection walls are needed when cables or conduits
are fed through walls with a specific fire resistance class. To retain the fire
resistance class, expert sealing of the opening is needed to prevent fire or
smoke from spreading.
KAISER's tried-and-tested AFS-technology immediately ensures that
the KAISER sealings intumesce and seal the wall opening against fire and
smoke. This guarantees that the wall's fire protection class is maintained.
Penetrations and entries in cavity walls, masonry and concrete.Fire sealings.
KAISER solutions guarantee fast, and above all absolutely safe and reli-
able sealing if a fire breaks out. There is no need at all for the time-con-
suming and messy use of fire-protection putty, foam, mortar of a fire-
protection coating. Installation is as easy as fitting a KAISER cavity wall
box.
More information on KAISER AFS-technology (Active Fire Stop) can be foundon pages 12/13.
EI 90
TECHNIK
21
KAISER products which have been given European Technical Approval
for sealings in fire-protection walls can be used in cavity wall, masonry
and also concrete construction walls.
KAISER fire sealings are the safest way for you to achieve secure and
reliable protection against fires
The sealings are approved in accordance with DIN 4102-9 and EN 1366-
3 and can be used for:
• Penetrations and entries in dry walls in accordance with DIN 4102-4
• Penetrations through solid masonry walls in accordance with DIN 1053
• Penetrations through concrete walls in accordance with DIN 1045
More information on KAISER fire-protection technology and products can be foundon our website or obtained directly from KAISER (see also last page). Technical advice - Telephone: +49(0)2355.809.61.
Fire protection | Sealing
ETA-11/0188
Diese Zulassung umfasst This Approval contains
17 Seiten einschließlich 9 Anlagen 17 pages including 9 annexes
E u r o p ä i s c h e O r g a n i s a t i o n f ü r T e c h n i s c h e Z u l a s s u n g e n
E u r o p e a n O r g a n i s a t i o n f o r T e c h n i c a l A p p r o v a l s
Z12878.11 8.11.04-5/10
English translation prepared by DIBt - Original version in German language
HandelsbezeichnungTrade name
"KSS Kaiser Schott System (DS 90, RS 90, LS 90)"
ZulassungsinhaberHolder of approval
KAISER GMBH & CO. KG Ramsloh 4 58579 Schalksmühle DEUTSCHLAND
Zulassungsgegenstandund Verwendungszweck
Kabelabschottungen
Generic type and use of construction product
cable penetration seals
Geltungsdauer:Validity:
vomfrom
22 June 2011
bisto
22 June 2016
HerstellwerkManufacturing plant
KAISER GMBH & CO. KG Ramsloh 4 58579 Schalksmühle DEUTSCHLAND
European Technical Approval ETA-11/0188
22 www.kaiser-elektro.de
The appropriate closing of penetrations for cables and conduits through
fire-protection walls creates additional safety. KAISER's certified sealings
are easily and quickly fitted, including for retrofitting over cables and con-
duits.
• Safe, secure, visible, certified sealing against fire
• For wall penetrations and entries
• No filling or smoothing
• Joints automatically seal themselves
• For 5-15 mm Ø cables
• For M16-M25 conduits
TECHNIKSafe penetrations and entries.Also for retrofitting. Cable and conduit sealing systems LS 90 / RS 90.
Diese Zulassung umfasst This Approval contains
17 Seiten einschließlich 9 Anlagen 17 pages including 9 annexes
E u r o p ä i s c h e O r g a n i s a t i o n f ü r T e c h n i s c h e Z u l a s s u n g e n
E u r o p e a n O r g a n i s a t i o n f o r T e c h n i c a l A p p r o v a l s
Z12878.11 8.11.04-5/10
English translation prepared by DIBt - Original version in German language
HandelsbezeichnungTrade name
"KSS Kaiser Schott System (DS 90, RS 90, LS 90)"
ZulassungsinhaberHolder of approval
KAISER GMBH & CO. KG Ramsloh 4 58579 Schalksmühle DEUTSCHLAND
Zulassungsgegenstandund Verwendungszweck
Kabelabschottungen
Generic type and use of construction product
cable penetration seals
Geltungsdauer:Validity:
vomfrom
22 June 2011
bisto
22 June 2016
HerstellwerkManufacturing plant
KAISER GMBH & CO. KG Ramsloh 4 58579 Schalksmühle DEUTSCHLAND
European Technical Approval ETA-11/0188
ETA-11/0188
23
Fire protection | Cable and conduit seal
It is easy to fit the cable and conduit seal with just a few simple actions.
Make the installation opening using a suitable cutter and insert the flex-
ible seal. For retrofitting, open the seal and push it over the existing cable
or conduit. In each case, up to three cable or conduit seals can be
arranged as a group.
Diameter of installation opening
Product designation Cavity wall Solid masonry wall
Cable sealing system LS 90 20 mm 20 mm
Conduit sealing system RS 90 35 mm 32 mm
Cable sealing system LS 90 | Art. No. 9459-01
Conduit sealing system | Art. No. 9459-02
KAISER cable seals for variable cable bundles are shown on pages 22/23. KAISER sealing plugs are on pages 24-25.
24 www.kaiser-elektro.de
Installation also in concrete and masonry. Cable and conduit sealing systems LS 90 / RS 90. The cable and conduit sealing systems can also be fitted in concrete
and masonry walls with just a few steps and actions. No need for additional
attachment equipment. A Ø 20 mm drill hole is needed for the cable sealing
system LS 90. The cable is then fed through the installation opening and the
cable sealing placed around the cable and pressed into the installation open-
ing - finished!
25
Fire protection | Solid wall
The conduit sealing system RS 90 can be fitted just as easily and quickly as
the cable sealing system LS 90. The installation opening must be made with
a Ø 32 mm drill. To adapt the conduit sealing system RS 90 to the installation
opening, first remove the pull-off lug. Then feed the electrical installation
conduit through the installation opening, place the conduit sealing around the
conduit and press into the opening - finished!
26 www.kaiser-elektro.de
Bundled through any wall.Safe, and for retrofitting.Box sealing system DS 90.The safe sealing for cable bundles. The fireproof and smokeproof box
seal can be installed quickly and easily by using a 74 mm Ø KAISER cutter,
and can also be retrofitted over cables. The innovative KAISER solution
provides certified safety and is easy to fit.
• Safe, secure, visible, certified sealing against fire
• For wall penetrations and entries
• No filling or smoothing
• Joints and ribs automatically seal themselves
• Non-destructive addition of cables
• For cable bundles or individual installation conduits
TECHNIK
Improves maximum cable occupancy!
• Cable bundle Ø ≤ 40 mm (full occupancy)
• Biggest individual cable in bundle Ø ≤ 15 mm
• Biggest individual cable Ø ≤ 21 mm
• Electrical installation conduit Ø ≤ 40 mm
EI 90
"Praxis Altbau" prize for product innovation 2011
ETA-11/0188
Diese Zulassung umfasst This Approval contains
17 Seiten einschließlich 9 Anlagen 17 pages including 9 annexes
E u r o p ä i s c h e O r g a n i s a t i o n f ü r T e c h n i s c h e Z u l a s s u n g e n
E u r o p e a n O r g a n i s a t i o n f o r T e c h n i c a l A p p r o v a l s
Z12878.11 8.11.04-5/10
English translation prepared by DIBt - Original version in German language
HandelsbezeichnungTrade name
"KSS Kaiser Schott System (DS 90, RS 90, LS 90)"
ZulassungsinhaberHolder of approval
KAISER GMBH & CO. KG Ramsloh 4 58579 Schalksmühle DEUTSCHLAND
Zulassungsgegenstandund Verwendungszweck
Kabelabschottungen
Generic type and use of construction product
cable penetration seals
Geltungsdauer:Validity:
vomfrom
22 June 2011
bisto
22 June 2016
HerstellwerkManufacturing plant
KAISER GMBH & CO. KG Ramsloh 4 58579 Schalksmühle DEUTSCHLAND
European Technical Approval ETA-11/0188
27
Fire protection | Box sealing system DS 90
The box sealing system DS 90 consists of two parts which are simply
placed on each other and locked. The sealing cylinder, which uses AFS-
technology to close the wall, is inserted into the Ø 74 mm cut opening
and easily fitted, like a KAISER cavity wall box. The sealing element is then
placed round the cables, pushed onto the sealing cylinder and, by means
of the bayonet fitting, sealed with a right-hand turn. An audible click can
be heard. This process ensures secure room separation.
For the non-destructive addition of more cables, the sealing element can
be opened and more cables added in a moment. The box seal can be
closed again without additional sealing.
Box sealing system DS 90 | Art. No. 9459-03
KAISER cable seal and conduit seal are on pages 20/21.
1
23
1 FX4 screw attachment | 2 Two-part sealing cylinder | 3 Sealing element
28 www.kaiser-elektro.de
Bundled through any wall.Safe, and for retrofitting. Box sealing system DS 90/120 mmThe new box sealing system DS 90 / 120 mm makes possible fast, flexible
and secure sealing, retains the wall's fire resistance class, and automatically
seals joints and gaps between cables - no need for smoothing and filling or
time-consuming painting with fire-protection coating. The box sealing system
DS 90 / 120 mm allows full occupancy in the form of mixed occupancy of
bundles or cables and conduits.
• Safe. secure, visible, certified fire sealings
• For wall feed-throughs
• Automatic sealing of the joints and gaps between cables, without filling
or smoothing
• Non-destructive later addition of cables
• Also for mixing cable and conduit bundles
TECHNIK
29
Fire protection | Box sealing system DS 90
The box sealing system DS 90 / 120 mm makes possible the secure, visible
and certified fire-protection sealing of cable and conduit feed-through in EI30
- EI90 fire-protection walls. It allows the sealing of a large number of sheathed
cables up to a diameter of 29 mm, and also for electrical installation conduits
up to M63. The two-part sealing cylinder and the hinged sealing element also
make installation possible when cables or conduits are already in place. The
extension of the sealing element with the cooling ribs achieves and guarantees
ordered bundling and optimal sealing for smoke-proof room separation by
means of the special foam inserts. The extra-large sealing collar ensures smoke-
proof room separation even when openings are not cut exactly. For fast, clean
and easy installation, a 120 mm opening is required into which the sealing
cylinder is inserted and fixed with tried-and-tested FX4 technology. Finally, snap
the sealing element onto the sealing cylinder using the bayonet fitting.
Box sealing system DS 90 / 120 mm | Art. No. 9459-04
1 FX4 screw attachment | 2 Sealing cylinder | 3 Sealing element with cooling ribs
2
31
30 www.kaiser-elektro.de
The box sealing system DS 90 can be installed in all concrete and masonry
walls without the need for special fire-protection materials. All that is needed is
an 82 mm Ø drilling hole and standard fixing materials such as plaster, mortar
or fast cement.
Installation also in concrete and masonry. Box sealing system DS 90 and DS 90 / 120 mm.
31
Fire protection | Solid wall
The box sealing system DS 90 / 120 mm is as easy to fit as the box seal-
ing system DS 90. It can also be inserted into an installation opening using all
standard fixing materials. The installation needs a 150 mm Ø core drilling hole.
The sealing collar ensures clean room separation.
32 www.kaiser-elektro.de
Air-tightness certifi cate Component: Sealing plug (Kaiser GmbH & Co. KG) Sealing plug type 16/20/25/32/40 Test object: Chipboard housing with 28 sealing plugs of the brand listed above.The sealing plugs were mounted in cable conduits with cable entries. Results: Using the Blower Door Measurement System and the DG-700, the following values were established for the volume fl ow and A value with a pressure difference of 10 Pascal:
Volume fl ow at 10 Pascal based on 28 sealing plugs:
V10 = 0,23 m³/h A value at 10 Pascal based on the joint length: a-Wert = 0,1 m³/h*m
Ingenieurgemeischaft Bau + Energie + Umwelt GmbH Zum Energie- und Umweltzentrum 1 31832 Springe Telephone 05044 / 975-30 11.07.2011 Paul Simons Telefax 05044 / 975-44
According to DIN 4108-2:2003-07 chapter 7 para. 3, the requirement for component connection joints is ≤ 0.1 m³/mh (daPa ²/³).
The tightness of component connection joints 16/20/25/32/40 satisfi es the requirements.
Air-tightness certificate
During comprehensive blower door tests, a neutral
institute tested and confirmed the air-tightness of the
M16 – M40 sealing plugs.
Easy closing - permanently sealed.Sealing plugs.
Sealing plugs with ECON® technology for sealing all standard electrical
installation conduits in one-gang boxes or at cable outlets. The long sealing
plug with three sealing lips and in different widths adapts itself to the
installation conduit in use and guarantees an air-tight and smoke-tight end
even when conduits are cut at an angle. From conduit size M25 upwards,
the membrane areas are divided by bridges which prevent damage and
ensure secure cable routing and air-tightness where the cables pass
through.
• For empty conduit installations in an air-tight design or in fire protection
areas
• Three sealing lips with different spacings adapt perfectly to the installa-
tion conduit
• Guaranteed air-tightness
• Toolless cable entry
• For all M16 - M40, Pg 9 – Pg 36, 3/4" and 5/8" installation conduits
33
Sealing plug M16Art. No. 1040-16
M16Pg 9
Sealing plug M20Art. No. 1040-20
M20Pg 11
Sealing plug M25Art. No. 1040-25
M25Pg 16
Sealing plug M32Art. No. 1040-32
M32Pg 21M40Pg 36
Sealing plug M40Art. No. 1040-40
The long sealing plug with three sealing lips and different widths adapts itself perfectly to the instal-lation conduit...
From conduit size M25 upwards, the membrane areas are reinforced with ribs …
… which ensure secure cable rout-ing and air-tightness where the cables pass through.
… and guarantees an air-tight and smoke-tight closure even when conduits are cut at an angle.
Our "Sealing plug" folder contains more information on KAISER sealing plugs.
x>x
5/8"3/4"
34 www.kaiser-elektro.de
For fire-protection ceilings up to F90.HWD 30 fire-protection boxes.
The HWD 30 installation boxes for fire-protection ceilings guaran-
tee reliable fire protection from F30 to F90. KAISER AFS-technology's
integrated fire-retardant coating intumesces immediately a fire breaks
out and closes the opening in the ceiling. Even when retrofitted, the HWD
30 ensures safety.
• For fire-protection ceilings F30-F90
• No encasing required
• Suitable for fitting smoke alarms
• With fire-protection cover as a junction box
• Also for retrofitting
TECHNIK
DIBt approvalZ-19.21-1788
(German Institute of Building Technology)
35
Fire protection | Fire-protection box HWD 30
With mineral wool acc. to DIN 4102-17, the installation resists a fire up
to fire-resistance class F60, and with Rockwool/Termarock 100 up to fire-
resistance class F90.
Without mineral wool, the installation corresponds to fire-resistance
class F30.
Fitting is easy in accordance with the tried-and-test principle of fast cav-
ity wall installation using KAISER FX4 technology.
HWD 30 ceiling junction box | Art. No. 9464-50
HWD 30 ceiling box | Art. No. 9463-50
Fire-protection cover | Art. No. 1184-94
KAISER one-gang boxes for fire-protection walls and installation shafts or ducts are shown on pages 14-17.
12
3
1 Ceiling junction box | 2 Ceiling box | 3 Fire-protection cover
36 www.kaiser-elektro.de
For luminaires and loudspeakers.FlamoX® fire-protection housings.
The installation housings for luminaires and loudspeakers with KAISER
AFS-technology protect people and materials if a fire breaks out. In the
case of luminaire and loudspeaker installations in F30 fire-protection ceil-
ings, the housings maintain the fire-protection class, prevent smoke and
fire from spreading, and in this way they secure the escape routes and
installation levels in buildings.
• For fire-load from above and below
• Intelligent, automatic sealing
• Smokeproof, halogen-free
• For new build and as a fire-protection upgrade in existing buildings
TECHNIK
37
Preventative fire protection | FlamoX® fire-protection housings
The FlamoX® fire-protection housings provide certified safety. KAISER
AFS-technology's fast-acting fire-retardant coating reacts immediately a
fire breaks out and safely fills the housing with foam. Within the shortest
possible time, the ceiling opening is completely closed and the S30 fire
sealing is safe.
ABP and DIBt approval
fire-resistance class S30in accordance with DIN 4102-9
The FlamoX®-System has been subjected to repeated tests in accordance
with DIN 4102 and has been awarded the following DIBt approvals:
Z-19.15-1582 (FlamoX®-S30 H)
Z-19.15-1623 (FlamoX®-S30 E)
Z-19.11-1583 (fire-protection putty)
and also the Allgemeines Bauaufsichtliches Prufzeugnis
(General building test certificate) no. P-MPA-E-04-033 issued by the
Materials Testing Office NRW.
Approvals for Switzerland, Austria and the Netherlands have also been issued.
S30
FlamoX®-S30 H | Art. No. 9430-01
FlamoX®-S30 E | Art. No. 9435-01
Further information on KAISER fire-protection technology and products can be found on our website or obtained directly from KAISER (see also last page). Technical advice - Telephone: +49(0)2355.809.61
21
1 FlamoX®-S30 H for halogen luminaires
2 FlamoX®-S30 E for energy-saving lamps (TC) and loudspeakers
Production innovation award for refurbish-ing
DIBt Z-19_15-1582 FlamoX HDIBt Z-19_15-1623 FlamoX E
38 www.kaiser-elektro.de
Preventative fire protection ininsulated hollow ceilings.ThermoX® installation housings.
> 200˚C
The intelligent housing system offers protection against the latent risk
of fire caused by the heat from some types of lamps. In suspended ceil-
ings and roof areas, ThermoX® protects the moisture barrier foil and
other surrounding materials against heat-generating halogen lamps and
LED lamps.
• Prevents fires, air-tight
• Ceiling outlet up to Ø 86 mm
• Installation from above or below
• Also for retrofitting
In addition to preventative fire protection, the housing provides air-tight
installation room. The integrated transformer flap allows the transformer
to be positioned next to the housing, so the transformer is thermally-pro-
tected.
Optional decor rings with four different surfaces conceal the housing
when it is retrofitted, creating an attractive appearance.
< 80˚C
39
There is a latent risk of danger because the halogen lamps generate a
temperature of over 200°C after a short period of time. This extreme
heat development is dangerous for all surrounding materials in the roof
construction and can lead to a catastrophe for human beings and prop-
erty.
The ThermoX® housing was developed for the installation of halogen
luminaires in wood-panelled and tiled ceilings and also for seamless sub-
ceiling constructions made of plasterboard, mineral fibreboards, MDF and
plywood with double slats and a layer of insulation above. It is ideal for
the installation of luminaires in new buildings, or in buildings which are
being refurbished, for low-voltage or high-voltage or LED lamps. It is ideal
for use in climate-controlled rooms, and prevents dust rings round the
built-in luminaires.
Further information on KAISER fire-protection technology and products can be found on our website or obtained directly from KAISER (see also last page). Technical advice - Telephone: +49(0)2355.809.61
Preventative fire protection | ThermoX® fire-protection housings
1
2
3
4
5
6
ThermoX® housing |
Art. No. 9300-01/02/03/22
Decorative coverings |
Art. No. 9301-…
1 Transformer flap | 2 FX4 screw attachment | 3 Housing | 4 Front part with
bayonet fitting | 5 Mineral fibre front part | 6 Decorative covering Ø 125 mm
40 www.kaiser-elektro.de
Fireproof and smokeproof walls in ship cabins. Fire-protection technology in shipbuilding.Electrical installations on cruise ships, ferries or yachts must pro-
vide optimal functionality and ensure the safety of the passengers and
crew. Our many years of experience of fire-protection technology in
buildings are now used to deal with the fast installation needs of ship-
yards, cabin builders and the shipping industry. The user now has a fire-
protection box which is very easy to install and prevents - absolutely reli-
ably - the spread of fire and smoke via category B0 to B15 partitions.
41
KAISER's AFS-technology is also integrated in fire-protection one-gang
boxes for shipbuilding. The fire-retardant coating reacts immediately to
fire and heat, and intumesces so effectively that the cabin wall's fire pro-
tection class is maintained and the escape routes are kept free of smoke.
This is especially important on fully-occupied cruise ships with narrow
corridors.
Mounting of HWD B15 fire-protection boxes is carried out with KAISER's
tried-and-tested system tools, e.g. the Ø 74 mm cutter
TECHNIK
HWD B15 one-gang box | Art. No. 9463-15
HWD B15 one-gang junction box | Art. No. 9464-15
Fire-protection cover | Art. No. 1184-94
Further information on KAISER fire-protection technology and products can be found on our website or obtained directly from KAISER (see also last page). Technical advice - Telephone: +49(0)2355.809.61
Fire protection | Ship's cabin building
1
2
3
4
1 FX4 technology | 2 One-gang box | 3 One-gang junction box
4 Fire-protection cover
42 www.kaiser-elektro.de
For cabin walls in shipbuilding.HWD B15 fire-protection one-gang boxes.
The certified one-gang boxes are suitable for both metal-clad and
mineral-based shipbuilding walls. They offer maximum safety and satisfy
the requirements of current legislation.
The intelligent fire-protection one-gang boxes for B0 to B15 partitions
react to a fire very quickly. The HWD B15 cavity wall boxes provide screen-
ing on the fire and smoke side of the fire-protection zone and preserve
the B15 function of the fire-protection wall for at least 30 minutes of
flames.
• For partitions in categories B0 to B15
• Without encasing
• Also for retrofitting
• When fitted with a fire-protection cover, can be used as a junction box
TYPE-APPROVED PRODUCT
TECHNIK
43
The HWD B15 fire-protection boxes make complicated and heavy
metal encasing unnecessary. The user is guaranteed a certified and fast
installation with standardised working processes.
Combinations of one-gang junction boxes at a standardised combi-
nation distance can easily be created by separating the marked area on
the holding ring. Installation is as easy as for cavity wall boxes.
We offer special solutions for all
types of walls. For example, there are
types for mineral wall constructions
which permit countersinking, and
also FX4 technology for thin boarding
thicknesses from 0.2 to 40 mm.
NEW
HWD B15 one-gang box | Art. No. 9461-14
HWD B15 one-gang box | Art. No. 9463-14
HWD B15 one-gang junction box | Art. No. 9464-15
Fire-protection cover | Art. No. 1184-94
KAISER one-gang boxes for fire-protection walls and installation shafts or ducts are shown on pages 14 to 17.
Fire protection | Fire-protection one-gang box
12 3
4
1 FX4 technology | 2 One-gang box | 3 One-gang box | 4 One-gang
junction box | 5 Fire-protection cover
5
44 www.kaiser-elektro.de
The fire resistance of cavity wall boxes and casings is tested at
850°C in a glow wire test (without an open flame). It must be shown that
the boxes are self-extinguishing, i.e. if there is a fault in the electrical
installation, a fire cannot be caused because of the cavity wall boxes. In
addition, it is necessary to comply with all the current fire prevention
measures for wall construction.
For cavity wall boxes with the VDE mark, fire resistance is tested and con-
firmed acc. to VDE 0471/ EN 60695-T. 2-10.
Safety and fire protection in electrical installation.Fire-resistant and halogen-free.
850˚C
650˚C
650˚C
750˚C
750˚C
850˚C
960˚C
Test temperatures
650°C Flush-mounting
650°C Concrete construction
750°C In-plaster
750°C Covers
850°C Cavity wall
960°C Clamps
45
Halogen-free cavity wall boxes / Fire-resistance
All KAISER one-gang boxes and casings for cavity wall installation, and
also many accessories, are available as halogen-free articles. They are also
available in white for an individual note.
• Fire-resistant up to 850°C
• Temperature-resistant up to 105°C
• Good electrical insulation, impact-proof and pressure-resistant
• No oxygen is combined as a result of chemical reactions
• No corroding materials such as hydrochloric acid gas or hydrogen bro-
mide are released
The fire resistance of cavity wall boxes and casings which bear a VDE mark is tested at 850°C in a glow wire test in accordance with VDE 0471 / DIN EN 60695-2-11.
It must be shown that if electrical installation is faulty, a fire cannot be caused because of the cavity wall boxes. In addition, it is necessary to comply with all the current fire prevention measures for wall construction.
Further information on KAISER fire-protection technology and products can be found on our website or obtained directly from KAISER (see also last page). Technical advice - Telephone: +49(0)2355.809.61
Fire protection | Fire-resistant and halogen-free
Halogen-free sound insulation box | Art. No. 9069-77
The new KAISER sound insulation box is available in a
halogen-free version.
INNOVATION
46 www.kaiser-elektro.de
Installation housingFlamoX®-S 30 H
9430-01 | p. 36
Ceiling box HWD 30
9463-50 | p. 34
Universal opening cutter
1085-80
Installation housingFlamoX®-S 30 E
9435-01 | p. 36
Turbo cutterMULTI 4000
1083-10
Installation housingFlamoX®-S 30 E
9435-02 | p. 36
VARIOCUT
1089-10 | 1089-00
Stripping pliersAMZ 2
1190-02
Centering insert 68/74
1083-99
FlamoX® replacementmineral fibreboard
9400-02
Bi-metal cutterØ 120 mm
1084-00/1082-79/86/20
FlamoX® fire-protection putty
9400-05
FlamoX® replacementcable entry
9400-04
Ceiling junction boxHWD 30
9464-50 | p. 34
Fire-protection coverHWD 30-90
1184-94 | p. 34
Support connector
9060-78
Tools
Fire-protection housings
HWD 30 fire-protection ceiling box
Installation in ceilings.
ThermoX® housings for LV and HV luminaires
9300-01/02/03 | p. 38
ThermoX® universal housingwith mineral fibreboard
9300-22 | p. 38
ThermoX®
decorative coverings
9301-... | p. 38
ThermoX® front ringssingle
9300-41/42/43 | p. 38
ThermoX®
universal front part
9300-93 | p. 38
Preventative fire protection
Ø 74 mmØ 74 mm
Ø 68 mm
Ø 24 - 68 mm Ø 65 - 120 mm
Ø 120 mmØ 120 mm
One-gang box HWD 90
9463-01 | p. 14
One-gang junction boxHWD 90
9464-01 | p. 14
Fire-protection coverHWD 30-90
1184-94 | p. 14
Support connector
9060-78
HWD 90 fire-protection boxØ 74 mm Ø 74 mm
Installation in walls.
The complete range of products and all technical information can be found in the KAISER catalogue and on our website at www.kaiser-elektro.de
Electronics boxHWD 90
9462-94 | p. 18
Produkt-AnimationBrandschutz Programm
http://www.kaiser-elektro.org/brandschutz
KAISER fire-protection systems.At a glance.
47More information on KAISER fire-protection technology and products can be foundon our website or obtained directly from KAISER (see also last page). Technical advice - Telephone: +49(0)2355.809.61.
Fire protection | Product overview
One-gang box HWD B15
9461-14 | p. 42
One-gang box HWD B15
9461-15 | p. 42
One-gang junction box HWD B15
9464-14 | p. 42
One-gang junction boxHWD B15
9464-15 | p. 42
HWD B15 fire-protection one-gang box (Ø 74 mm)
One-gang box HWD B15
9463-14 | p. 42
One-gang box HWD B15
9463-15 | p. 42
Seal identification tag
9473-91
Accessories
Seal identification tag
9473-92
Hardened metal cutterØ 20 mm
1088-06
M16
1040-16 | p. 32
Turbo cutterMULTI 4000
1084-10
M25
1040-25 | p. 32
Tools
Sealing plugs
Turbo cutterMULTI 4000
1082-10
M20
1040-20 | p. 32
Turbo cutterMULTI 4000
1084-10
Tools
Universalopening cutter
1085-80
Installation for walls. Feed-through and entry.
Installation in shipbuilding walls.
PS: 7 - 40 mmT: 40 mm
PS: 7 - 40 mmT: 44 mm
PS: 7 - 40 mmT: 54.5 mm
PS: 0.2 - 40 mmT: 40 mm
PS: 0.2 - 40 mmT: 44 mm
PS: 0.2 - 40 mmT: 54.5 mm
Hardened metal cutter for sheet metal boarding Ø 74 mm | 1083-74 (no illus.) (PS: board thickness | T: depth)
Ø 20 mm
Box sealing system DS 90
9459-03 | p. 26 ETA-11/0188
Ø 74 mm
DE / GBF / I
DE / GBF / NLØ 35 mm Ø 74 mm
Ø 74 mm
Stripping pliersAMZ 2
1190-02
Installation in walls.
M32
1040-32 | p. 32
M40
1040-40 | p. 32
The complete range of products and all technical information can be found in the KAISER catalogue and on our website at www.kaiser-elektro.de
The complete range of products and all technical information can be found in the KAISER catalogue and on our website at www.kaiser-elektro.de
The complete range of products and all technical information can be found in the KAISER catalogue and on our website at www.kaiser-elektro.de
Box sealing system DS 90 / 120 mm
9459-04 | p. 28
Ø 120 mm
Box sealing system DS 90 and DS 90 / 120 mm
Bi-metal cutterØ 120 mm
1084-00/1082-79/86/20
Bi-metal cutterØ 120 mm
1084-00/1082-79/86/20
Centering insert 68/74
1083-99
Ø 25 mm Ø 40 mmØ 20 mm Ø 32 mmØ 16 mm
Cable sealing systemLS 90
9459-01 | p. 22 ETA-11/0188
Cable and conduit sealing systems LS 90 and RS 90European Technical Approval: First series of seals with European approval
Conduit sealing system RS 90
9459-02 | p. 22 ETA-11/0188
Ø 20 mm Ø 35 / 32 mm
Systems and solutions for the professional electrical installation.Since 1904, KAISER has developed and manufactured systems and products as a basis for good installation.
Planners and users benefit internationally from the practical solutions for their daily operations in all areas of installation.
Product systems
Fire protectionBox, housing and sealing systems for fire
protection walls and ceilings
Energy efficiencyElectrical installation for energy-saving buildings
RefurbishmentFor the refurbishment and reconstruction of
private and industrial properties
System solutions
Radiation protectionElectrical installation in radiation protection
walls
Sound insulationElectrical installation in sound insulation walls
Technical information and advice
You will find more information about products, system solutions and
communication media on our website: www.kaiser-elektro.de
For additional questions or information, please contact our
technical staff. KAISER Tel.: ++49(0)2355.809.61
KAISER Email: [email protected]
Flush-mountinginstallationProducts and systems for classic flush-mounting
installation
Cavity wall installationProducts and systems for classic cavity wall
installation
Concrete construction installationProducts and systems for concrete construction
installation for on-site mixed concrete and pre-
fabrication
EarthingProducts and systems for additional equipotential
bonding and especially hazardous rooms and areas
Installation housingsProducts and systems for luminaires, loud-
speakers and display installation in walls and
ceilings
Cable glandsProducts and systems made of plastic or metal
for everyday installations and specialist techni-
cal products
KAISER GmbH & Co. KG
Ramsloh 4 · D-58579 Schalksmühle
Tel.+49(0)2355.809.0 · Fax+49(0)2355.809.21
www.kaiser-elektro.de · [email protected]
© K
AIS
ER G
mbH
& C
o. K
G.2
012/
13
kai
0313
web
GB
Picture sources: KAISER Archiv / headlineWerbeagentur.de Archiv / istockphoto.de / fotolia.de / ingrid-fiebak.de / panthermedia.net / digitalstock.de / fotosearch.de / shutterstock.com / VELUX Deutschland GmbH / keweloh
Top Related