Prepared for
Whitecleave Quarry: IBA Facility External Lighting Assessment
June 2011
Whitecleave Quarry
Scott Wilson 3rd Floor Mayflower House Armada Way PlymouthPL1 1LD Tel 01752 676700 Fax 0870 238 6023
www.scottwilson.com
This document has been prepared in accordance with the scope of Scott Wilson'sappointment with its client and is subject to the terms of that appointment. It is addressedto and for the sole and confidential use and reliance of Scott Wilson's client. Scott Wilsonaccepts no liability for any use of this document other than by its client and only for thepurposes for which it was prepared and provided. No person other than the client maycopy (in whole or in part) use or rely on the contents of this document, without the priorwritten permission of the Company Secretary of Scott Wilson Ltd. Any advice, opinions,or recommendations within this document should be read and relied upon only in thecontext of the document as a whole. The contents of this document do not provide legalor tax advice or opinion.
© Scott Wilson Ltd 2010
Revision Schedule
External Lighting Assessment May 2011
Rev Date Details Prepared by Reviewed by Approved by
01 02.06.11 Final Bonnie Brooks Assistant Electrical Engineer
Mike Ainger Senior Electrical Engineer
Neil Cumming Technical Director
Whitecleave Quarry
Environmental Statement External Lighting Assessment June 2011
1
Table of Contents
1� Executive Summary ......................................................................... 2�
2� Introduction ...................................................................................... 3�
2.1� Scope of External Lighting Report .................................................................................... 3�
2.2� Objectives ......................................................................................................................... 3�
3� Assessment Methodology ............................................................... 4�
4� The Proposed Lighting Scheme ...................................................... 5�
4.1� General ............................................................................................................................. 5�
4.2� Recommended Lighting Values ....................................................................................... 5�
4.3� Strategy for Minimising Obtrusive Light, Mitigating the Effect on Bats and Reducing the Visual Impact of the Lighting Scheme ........................................................ 6�
4.4� Strategy for Luminaire Types ........................................................................................... 8�
4.5� Luminaire Control Strategy ............................................................................................... 8�
5� Assessment of the Impact of the Lighting Scheme ...................... 9�
6� Conclusions .................................................................................... 10�
7� Bibliography ................................................................................... 11�
Drawing E01: Levels of Illuminance Drawing E02: Sky Glow Calculation
Appendix 1: Definitions Appendix 2: Extract from SLL Code for Lighting – Obtrusive – Recommended Lighting Values Appendix 3: Extract from SLL code for Lighting – General Areas in
Outdoor Work Places – Recommended Lighting Values
Appendix 4: Schedule of Luminaires and Luminaire Details Appendix 5: Relux Calculation Results
Appendix 6: Sketch of Defined Areas and Final Lighting Levels to be Achieved
Whitecleave Quarry
Environmental Statement External Lighting Assessment June 2011
2
1 Executive Summary
An appropriate lighting scheme for the site has been assessed in order to establish its effects on the surrounding environment and neighbouring properties.
The lighting scheme in this report is to be viewed as a lighting design strategy rather than a detailed design solution. It is recommended that the lighting strategy outlined in this report is adopted including criteria, luminaries, switching methods, lamp types etc. by the developer’s designers when undertaking the full external lighting design of the site.
This lighting scheme ensures that there will be zero illuminance from the proposed lighting scheme at the site boundary. Lighting as proposed will not cause excessive glare to neighbouring residential properties from this site. The majority of the fittings will not be visible to neighbouring domestic properties. Consideration has been given to mitigating the impact on the bats in the area, and in particular their flight paths through the site. Drawing E02 shows that the effect on the night sky will be negligible inside the site and zero outside the site. An adequate level of lighting will be provided for site tasks and amenity in accordance with the Clients Risk Assessment and Method Statements, whilst maintaining a minimal impact on the site surroundings, environment and neighbouring properties. There is no requirement for lighting for security.
Whitecleave Quarry
Environmental Statement External Lighting Assessment June 2011
3
2 Introduction
2.1 Scope of External Lighting Report This report has been prepared in order to establish the potential effects of the proposed development’s fixed lighting installation on the bat conservation areas and the site surrounding areas. The report accompanies the planning application for the proposed IBA Facility, hereafter referred to as the ‘site’.
2.2 Objectives The general objective of this report is to assess the impact of a suitable lighting scheme for the proposed IBF Facility on the surrounding area and environment.
Specific objectives of the proposed lighting scheme when fully designed include:
� To limit light pollution and sky glow.
� To limit obtrusive light, spill light / trespass light and glare to neighbouring land and properties.
� To mitigate the effects of the lighting scheme on bats.
� To provide an adequate level of illuminance for the proposed exterior areas, in accordance with the Clients Risk Assessment and Method Statements. The lighting is to be controlled via photocell and time clock, so that it is only switched on during the site opening hours of 7am – 7pm. (The time clock will bring the lighting on at 7am and the photocell will switch it off at dawn, then the photocell will bring the lighting back on at dusk and the time clock will switch it off at 7pm.) The only exception to this is the luminaire lighting the material handling area which will be manually switched on/off from the IBA Processing Plant building as and when it is required, within the site opening hours.
Whitecleave Quarry
Environmental Statement External Lighting Assessment June 2011
4
3 Assessment Methodology
An appropriate lighting scheme for the site has been assessed using standard industry software Relux.
Relux is a computer calculation package which utilizes 3D modelling to model the real world output of chosen light fittings. The results from the computer model produce the contour lines detailed on drawing D134633/E01.
The lighting outputs have been calculated with all the luminaries switched on. However, this level of illuminance will only be during the site working hours and will represent the maximum level of illuminance at any time, as the levels will be reduced when the manually switched task lighting over the material handling area is switched off. All external lighting will switched off via a time clock at the end of the site opening period. From these calculations, drawings illustrating the illuminance levels throughout the site and at the boundary have been produced so that the lightings scheme’s impact can be assessed. Refer to Drawing E01 for detail. The calculation model (Lux levels on drawing) does not include the proposed planting / hedgerows / trees, however this is accounted for when assessing and making conclusions about the light spill.
Light trespass has been assessed and the line of sight from neighbouring residential properties has also been considered.
The sky glow impact from the site has been calculated for the ‘worst case scenario’, with all the luminaries switched on. For detail see Drawing E02.
Full calculations have been included in Appendix 5.
Whitecleave Quarry
Environmental Statement External Lighting Assessment June 2011
5
4 The Proposed Lighting Scheme
The lighting scheme outlined in this report is to be viewed as a lighting design strategy rather than a detailed design solution.
4.1 General Lighting throughout the site will only be operational during the site opening hours. The site opening hours are 7am – 7pm daily. The operating hours will be 8am – 6pm daily.
All luminaires will utilise High Pressure Sodium lamps to reduce the impact on bats.
4.2 Recommended Lighting Values
Lighting levels have been designed in accordance with the Clients requirements and to mitigate the sites impact on bats. Consideration has been given to CIBSE Lighting Guides, SLL Code for Lighting 2006 – Obtrusive Light Guide, Guidance Notes on Reduction of Light Pollution, and BS 5489. However, the final agreed illuminance levels in which this report is based upon have been decided by the Client following their risk assessment, method statements and consideration of the site H&S strategy.
Recommended Levels
The recommended levels according to SLL Code for Lighting – Obtrusive Light Guide (refer to Annex 2 of this report) are as follows:
� Area Lighting for Lorry Area is 20-30 Lux Maintained Average (horizontal).
� Area Lighting for Loading Area is 50 Lux Maintained Average (horizontal) and 25 Lux Maintained Minimum (horizontal).
The recommended lighting levels according to SLL Code for lighting – General Areas in Outdoor Work Places (refer to Annex 3) are as follows:
� Walkways exclusively for pedestrians are 5 Lux Maintained Average (horizontal).
� Traffic areas for slowly moving vehicles (max 10 km/h) e.g. bicycles, trucks and excavators is 10 Lux Maintained Average (horizontal).
� Pedestrian passages, vehicle turning, loading and unloading points is 30 Lux Maintained Average (horizontal).
� Lighting requirements for safety in medium risk areas is 20 Lux.
� Lighting requirements for safety in high risk areas is 50 Lux.
Whitecleave Quarry
Environmental Statement External Lighting Assessment June 2011
6
Agreed Levels for this site
Good uniformity across the defined areas is not achievable due to restrictions placed by the client on the positioning of luminaires. See Appendix 6 for definition of areas.
� Area 1 – This area will be lit using portable task lighting as required, during site operating hours. This report considers the fixed lighting installation only.
� Area 2 – Bat flight path to be unlit.
� Area 3 – Turning circle and Weighbridge to be unlit. Maximum illuminance 3 Lux at ground level due to requirements for bat mitigation.
� Area 4 – Access road to be unlit.
� Area 5 – MRF area, site offices, staff car-parking area to be lit to an average illuminance of 5 Lux across whole area using a combination of low level bollard lighting and building mounted luminaires. Lighting to be concentrated around the front of the buildings, storage containers and car parking spaces so that there is higher levels of illuminance in these areas, and as lower level as possible close to the bat flight path and in the vehicle circulation area, between the buildings, as this route will be lit by vehicle headlights.
� Area 6 – IBA Processing Yard to be illuminated to a minimum average illuminance of 20 Lux.
� Area 7 – Material handling area considered to be a high risk area, to be illuminated to an average illuminance level of 50 Lux.
4.3 Strategy for Minimising Obtrusive Light, Mitigating the Effect on Bats and Reducing the Visual Impact of the Lighting Scheme Careful consideration has been given to reducing obtrusive light during the hours when the site is lit and the visual impact of the lighting scheme during the day, whilst maintaining an adequate level of illuminance for its application on the site. Particular attention has been paid to minimising the presence of the scheme and any intrusion, glare or sky glow produced by the scheme.
There will be no security lighting anywhere on the site; therefore all lighting will be switched off when the site is closed.
Area 2, 3 & 4
To mitigate the impact of the lighting scheme on bats many areas of the site will remain unlit at all times. These include areas 2, 3 & 4. The main access route, turning circle and weighbridge will remain unlit to mitigate the impact on bats; this includes the old workshop that contains the bat roost. Luminaires have been chosen that have good control of light spill so that only the intended areas are lit.
Whitecleave Quarry
Environmental Statement External Lighting Assessment June 2011
7
Area 5
In Area 5 a combination of low level bollard and building mounted luminaires have been utilised to reduce the impact on bats and so that the bat flight path in that area will remain unlit.
Where ever possible luminaires are to be orientated towards the site, away from the land outside the site to make them less intrusive. This has been particularly considered in Area 5 - the MRF area, site offices, staff car-parking area, ensuring that the majority of luminaires are orientated away from the residential properties. The light sources in this area will not be visible from the residential properties. Luminaires have been chosen that have good light control and cut off angles to reduce light spillage.
Area 6
The IBA Processing Yard shall be lit by a combination of column and building mounted luminaires. The mounting height in this area will be 8 metres. This area is less sensitive to bats which is why column mounted luminaires have been proposed. There is a bat flight path to the left of the yard behind the push walls and proposed hedgerows, this area will not be affected and will remain unlit, as illustrated by drawing E01.
The column mounted luminaires have been chosen to be as inconspicuous as possible. The luminaire, bracket and column shall all be coloured grey. The luminaries will be angled at a maximum of 10º above horizontal which will minimise sky glow whilst providing a wide light distribution at ground level reducing shadows produced from obstructions i.e. lorries, parked for loading. The luminaire itself has 0% upward light ratio, and the beam spread is controlled to within 50º from the vertical when the glass is horizontal. Therefore this would only increase to 60º when the luminaire is adjusted to 10º from the horizontal, which will still produce negligible upward light. It is also fitted with flat glass to reduce the visibility of the light source.
Area 7
A building mounted luminaire will be utilised to light the material handling area, this luminaire will be mounted at 8m at a 30º angle to horizontal, however this luminaire will be manually switched on/off as and when required up to site closing time.
General
The red line on drawing E01 represents 5 Lux and the purple, 1 Lux. The drawing shows that at worst case with all the luminaries switched on, there will be no light spill onto the boundary and that there will be minimal impact on the bat flight paths from the lighting scheme. Where possible it has been proposed that dense shrubs and woodland will be planted to help to shield and screen the lighting scheme. Consideration has been given to reducing the extent of illuminance falling on the building façade to reduce the visual impact of the site and buildings from a distance.
Whitecleave Quarry
Environmental Statement External Lighting Assessment June 2011
8
4.4 Strategy for Luminaire Types High Pressure Sodium (SON) lamps shall be utilised throughout the site, as recommended by the ecologists working on the project proposals, to mitigate the impact of the lighting scheme on the bats. The SON lamp will provide a Colour Rendering of approx 20 Ra which is acceptable for the application. Using this type of lamp will provide an energy efficient solution and will be Building Regulations Part L and BREEAM compliant. These luminaries, or equal and approved, have been chosen as they have been designed to be anti light pollution and low glare with good levels of efficiency between 50 – 80% for the chosen lamp types and low upward light ratio. All the luminaries are IP66 rated and impact resistant. See Appendix 4 – Schedule of Luminaries and Details.
4.5 Luminaire Control Strategy A photocell and programmable 7 day time clock are to be used to control the majority of the exterior lighting so that no luminaries will be left on during daylight hours or when the site is closed. The only exception to this is the lighting for the material handling area which will be manually switched on/off from the IBA Processing Plant building as and when it is required up to 7pm.
Whitecleave Quarry
Environmental Statement External Lighting Assessment June 2011
9
5 Assessment of the Impact of the Lighting Scheme
Drawing E01 shows the lighting scheme for the site, with the illuminance levels shown throughout the site and at the boundary. The calculation model was prepared using industry standard software, Relux. It shows that adequate levels of lighting have been achieved on the site with minimal effect on the surrounding area. There will be zero illuminance from the proposed lighting scheme at the site boundary. There will be a maximum of 3 Lux measured at any point on the bat flight path, but mostly the path will be completely unlit. And once the proposed site planting / hedgerows are in place the effect on the bats will be further reduced. Cowls and louvre attachments are available for the column mounted fittings as a retro fit item, but these will be unnecessary as long as the final luminaire choices and locations are as calculated.
Drawing E02 illustrates the additional sky glow caused by the lighting scheme. This calculation was provided by a simulation of a measuring reference plane approx 50m above the ground. The results show an average illuminance above the site of 0.43 Lux. This means that when the site is fully lit the sky glow will be approximately equivalent to the light produced by a full moon at 0.3 Lux, which is very low. The sky glow above the surroundings of the site will be negligible.
Whitecleave Quarry
Environmental Statement External Lighting Assessment June 2011
10
6 Conclusions
By adopting the lighting strategy including criteria, luminaries, switching methods, lamp types, etc. outlined in this report it can be concluded that:
� There will be minimal impact on bats due to the position of the luminaires and types. Also, due to the times bats emerge and the short hours that the lighting will be on for, there is little overlap between the two.
� There will be zero illuminance from the proposed lighting scheme at the site boundary.
� Lighting as proposed would not cause excessive glare to neighbouring domestic properties from this site.
� The majority of the luminaries will not be visible to neighbouring domestic properties.
� The effect on the night sky will be minimal inside the site and zero outside the site.
� The lighting scheme will be energy efficient utilising luminaires with an efficiency of between 50-80%, combined with energy efficient lighting controls.
� An adequate level of lighting can be provided for site tasks, amenity and security, whilst maintaining a minimal impact on the site surroundings, environment and neighbouring properties.
Whitecleave Quarry
Environmental Statement External Lighting Assessment June 2011
11
7 Bibliography
SLL Lighting Handbook 2009.
SLL Code of Lighting 2006
CIBSE Obtrusive Light Guide
Guide on the limitation of the effects of obtrusive light from outdoor lighting installations 2003. Technical Report 150/2003. CIE.
Lighting Guide LG6 CIBSE 1992. Outdoor Environment.
For the purpose of this report, the definitions given below apply:
Colour Rendering Index (CRI): A scale of the colour appearance of an object under a particular light source compared to its colour appearance under a reference light source. Expressed on a scale of 1 to 100 Ra, where 100 Ra represents the colour rendering of natural daylight i.e. perfect colour.
Illuminance: Illuminance is the quantity of light, or luminous flux, falling on a unit area of a surface. It is designated by the symbol E. The unit is the lux (lx). One lux equals one lumen per square metre (lm/m²).
Light Pollution: The spillage of light into areas where it is not required.
Light Trespass: Light that impacts on a surface outside of the area designed to be lit by a lighting installation.
Disability Glare: Glare which impairs the vision of objects but may not cause discomfort.
Discomfort Glare: Glare causing discomfort which may not impair the ability to see objects.
Photocell: A unit which senses light to control luminaires.
Curfew: The time after which stricter requirements (for the control of obtrusive light) will apply; often a condition of use of lighting applied by a government controlling authority, usually the local government (CIE, 2003).
Environmental Zones: Area where specific activities take place or are planned and where specific requirements for the restriction of obtrusive light are recommended. Zones are indicated by the zone rating (E1… E4) (CIE, 2003).
Obtrusive Light: Spill light which because of quantitative, directional or spectral attributes in a given context, gives rise to annoyance, discomfort, distraction or a reduction in the ability to see essential information (CIE, 2003).
Residential Property: Land upon which a dwelling exists (CIE, 2003).
Sky Glow: The brightening of the night sky caused by artificial lighting resulting from the reflection of radiation (visible and non-visible), scattered from the constituents of the atmosphere (gas molecules, aerosols and particulate matter), in the direction of observation. It comprises two separate components as follows:
(a) Natural sky glow - That part of the sky glow which is attributable to radiation from celestial sources and luminescent processes in the Earth’s upper atmosphere.
(b) Man-made sky glow - That part of the sky glow which is attributable to man-made sources of radiation (e.g. outdoor electric lighting), including radiation that is emitted directly upwards and radiation that is reflected from the surface of the Earth (CIE, 2003).
Spill Light (Stray Light): Light emitted by a lighting installation which falls outside the boundaries of the property for which the lighting installation is designed (CIE, 2003).
SCHEDULE OF LUMINAIRES
Ref Manufacturer Details / Reference
Lamp Luminaire Efficiency & ULOR (Upward
light ratio)
Appearance
A,
B &
C
ABACUS
LIGHTING
TRENT AL5000 WITH FLAT
GLASS
REFLECTOR
MOUNTED ON
8M COLUMN
400W
SON
80%
When
horizontal
ULOR= 0%
50º
DARK SKIES
FRIENDLY
D HOLOPHANE DENVER WALL MOUNTED
AT 2.5m
APPROX
50W
SON
78%
ULR= 24.7%
E HOLOPHANE DENVERBOLLARD
(SINGLE SIDED)
0.75M
70W
SON
50%
ULR= 31%
1.13
denv
er™
bolla
rd
denver™ bollardap
plic
atio
ns Landscaped areas
Pedestrian walkways
Driveways
Entrances
Gardens
Parks
Precincts
Combining style and performance, the Denver™
bollard creates distinctive illumination for a variety
of landscapes and walkway surrounds. The unique
contours of the body are styled in high quality
aluminium with single or double-sided optics offering
a choice of prismatic refractor or louvre to provide
maximum efficiency and flexibility for a wide range
of applications. With a selection of lamp types, heights
and an array of colour options, the Denver™ bollard
provides aesthetic flexibility by day whilst creating
efficient illumination at night.
denv
er™
bolla
rd
1.14
contactHolophanefor details
contactHolophanefor details
amenity
lamp types included
35W - 70W metal halide (various)
50W - 70W high pressure sodium
18W - 42W compact fluorescent (various)
IP rating
IP65
approvals
Complies with EN60598
1000mm bollard withprismatic lens (.PAY)
features and benefits
Contemporary styling
> Unique aesthetic appeal to
complement today’s architecture
High quality construction
> Durability
> Fully weather sealed
Single or double-sided optics
> Suitable for a wide range of
applications
Refractor or louvre optics
> Versatility
Symmetric or asymmetric distribution
> Maximum efficiency and uniformity
for any application
Wide spacing ability
> Cost savings due to reduced
number of luminaires
Three heights
> Flexibility
> Different visual effects
Vandal resistant option
> Improved security
^ special emergency option -sage sofware - newcastle.
^ DBL special dutch railways.< national assembly for wales – merthyr.
1.15
denv
er™
bolla
rd
240
157
415
App
rox
refractor lens (.PAY)
refractor lens (.DP) louvre (.DL)
weights & thermal data
Lamp Type Weight* (kg) Min Operating Max AmbientTemperature (˚C) Temperature** (˚C)
50W High Pressure Sodium 9.2 -30 40
70W High Pressure Sodium 9.3 -30 35
35W Metal Halide 9.0 -20 45
70W Metal Halide 9.3 -20 35
18W-26W Compact Fluorescent 9.4 -5 45
32W-42W Compact Fluorescent 9.4 -10 45
* Weights shown are for 1.0m version. For 0.75 deduct 1.5kg and for 0.5m deduct 3.0.kg ** Themaximum ambient temperatures stated are for exterior use only. For interior use deduct 10ºC fromthe temperature stated.
specification
The luminaire shall consist of an extruded
aluminium body, housing integral control gear
for a variety of high intensity discharge or
compact fluorescent lamps. The optical
arrangement shall consist of an aluminium
reflector and prismatic refractive lens, with
optional louvre. A gasket sealed top plate shall
be secured by two stainless steel nuts. Root
mount option available. The luminaire complies
with EN60598 with a choice of options and
accessories.
light distributions
Double-sided
1000
/75
0/50
0
louvre (.LYA)
Root Mount Option
Note: 157mm deep
Secure to Flange Basewith M10 Bolts
415
App
rox
350/
600/
850
Opt
ical
Cen
tre
(Thi
sle
ngth
unde
rgro
und)
ground
level
Ø25 Knock Out forthrough wiring Ø25 Entry Hole
3 off Ø10.5 Fixing Holes
Flange Base Details
Photometric data is availableat www.holophane.co.uk
Single sided
denv
er™
bolla
rd
1.16
amenity
Both optics are available as a single-sided or double-sided arrangement.
Double sided for symmetrical illumination. Single sided for asymmetrical distribution.
optical versatility
Refractor A precision designed pre-anodised
semi-specular aluminium reflector and
prismatic refractor ensures maximum lateral
and forward distribution combined with
excellent uniformity.
Louvre For applications that require a fuller cut-
off distribution a louvre optic is also available.
Fixed pre-anodised internal aluminium louvres
are positioned to control the distribution of light
ensuring wide and uniform output coupled with
precise vertical cut off.
1.17
denv
er™
bolla
rd
ordering details : luminaire
* All ceramic lamp circuits contain timed ignitors.**Please specify RAL colour reference. ***Only available for 0.75m & 1m height. ****Plug available asaccessory. †Specify HEL.VK to be supplied separately. Vehicle Prohibitor Bollards available via unique solutions. Note: Luminaires are supplied as standardfor use on 240V 50Hz supply and complete with lamp. For 230V 50Hz add prefix ‘N’ Other voltages available on request.
CodeDBL Denver™ Bollard
Code Lamp Type.50XT 50W Clear high output HPS lamp (E27) base
.70XT 70W Clear high output HPS lamp (E27) base
.35CDMTF3 35W Clear CDMT 3000K protected metal halide lamp (G12) base*
.70CDMT3 70W Clear CDMT 3000K protected metal halide lamp (E27) base*
.70MA 70W Clear 4000K protected metal halide lamp (E27) base
.18PL4 18W 4000K compact fluorescent 4-Pin lamp (G24q-2) base
.26PL4 26W 4000K compact fluorescent 4-Pin lamp (G24q-3) base
.32PL4 32W Triple Tube 4000K compact fluorescent 4-Pin lamp (GX24q-3) base
.42PL4 42W Triple Tube 4000K compact fluorescent 4-Pin lamp (GX24q-4) base
Code Light Distribution.LYA Louvre
.PAY Prismatic lens
.RAY Prismatic lens and reflector
Code Enclosure Type.SO Single sided (Asymmetric)
.DL Double sided louvre (Symmetric)
.DP Double sided prismatic lens (Symmetric)
Code Height.H50 500mm
.H75 750mm
.H100 1000mm
Code Colour.C1 White (RAL 9016)
.C4 Graphite (RAL 7011)
.C6 Grey (RAL 7035)
.C7 Black (RAL 9005)
.C9 Metallic Silver (RAL 9006)
.RAL**** RAL colour (customer choice)**
Code Options.A Acrylic
.C Enhanced paint finish
.CB Cut out box (Factory Fitted)
.CB1 Gear tray extension for
Customers own cut out box***
.PP Power point socket****
.V1 Vandal resistant screws†
DBL .18PL4 .LYA .SO .H75 .C9 .V1Example
denv
er™
bolla
rd
1.18
amenity
luminaire accessories for standard & emergency versions order separately for on-site installation by others
Code
DBL.PLUG Plug for powerpoint socket
DBL.ROOT Root Mounting Spike (including bolts)
DBL.FT Bolts M10 x 100 for Flange Base Fixing (set of 3)
HEL.CBEPAC Cut Out Box with Earth Plate for Armoured Cable (fuse by others)*
(please contact Holophane for details)
HEL.VK Key for Vandal Resistant Screw
* Only usable with single sided 0.75m and 1m versions.
ordering details : emergency luminaire
.V1 Vandal resistant screws
Example
CodeDBE Denver™ Bollard Emergency Version
Code Lamp Type.18PL4 18W 4000K compact fluorescent 4-Pin lamp (G24q-2) base.26PL4 18W 4000K compact fluorescent 4-Pin lamp (G24q-3) base.32PL4 32W Triple tube 4000K compact fluorescent 4-Pin lamp (GX24q-3) base.42PL4 42W Triple tube 4000K compact fluorescent 4-Pin lamp (GX24q-4) base
Code Light Distribution.PAY Prismatic lens.RAY Prismatic lens and reflector
Code Enclosure Type.SO Single sided (Asymmetric).DP Double sided (Symmetric)
Code Height.H75 750mm.H100 1000mm
Code Colour.C1 White (RAL 9016).C4 Graphite (RAL 7011).C6 Grey (RAL 7035).C7 Black (RAL (9005).C9 Metallic Silver (RAL 9006).RAL**** RAL colour (customer choice)*
Code Emergency.ME1 Maintained emergency (3 Hour)
Code Options.A Acrylic.C Enhanced paint finish.CB Cut out box (factory fitted).PP Power point socket**
.V1 Vandal resistant screws***
DBE .18PL4 .PAY .SO .H100 .C9 .ME1 .V1
* Please specify RAL colour reference. **Plug available as accessory. ***Specify HEL.VK to be supplied separately.
1.23
denv
erTM
wal
l
denver™ wallap
plic
atio
ns Corporate office
Frontages
Building perimeters
Amenity areas
Walkways
Passage ways
Precincts
With its contemporary styling, the Denver™ Wall
mount luminaire blends with surrounding
architecture by day, maintaining efficient illumination at
night. Designed for low to medium mounting heights
(3m to 5m), the compact Denver™ Wall Mount luminaire
offers exceptional performance characteristics for a
highly effective solution for wall mounted applications.
The latest in control gear and lamp technology, coupled
with a precisely engineered refractive lens and pre-
anodised reflector assembly, achieve maximum
performance combined with high efficiency.
denv
erTM
wal
l
1.24
amenity
lamp types included
35W - 100W metal halide (various)
50W - 70W high pressure sodium
18W - 42W compact fluorescent (various)
IP rating
IP65
approvals
Complies with EN60598
features and benefits
Contemporary styling
> Unique aesthetic appeal to
complement today’s architecture
High quality construction
> Durability
> Fully weather sealed
Optional photocell
> Flexibility
Single bottom entry option
& through-wire option
> Offers installation flexibility
Emergency options
> Improved security
Self-retaining strap
> Ease of maintenance
< grand arcade - wigan
1.25
denv
erTM
wal
l
148
217
CN
TR
120
325
215
285
108.
5
105 CNTR
specification
The luminaire shall consist of a high pressure
die-cast aluminium body, housing integral
control gear to suit a wide choice of high
intensity discharge or compact fluorescent
lamps. The optical arrangement shall consist of
an aluminium reflector and prismatic injection-
moulded polycarbonate refractive lens. An
acrylic lens shall be available as an option. A
closed cell resilient gasket with four stainless
steel screws maintains uniform gasket
compression ensuring an IP65 rating at all
times. The luminaire shall be suitable for wall
mounting and complies with EN60598 with a
choice of options and accessories.
light distributions
weights & thermal data
Lamp Type Weight (kg) Min. Operating Max. AmbientTemperature (˚C) Temperature* (˚C)
50W High Pressure Sodium 4.7 -30 50
70W High Pressure Sodium 4.7 -30 45
35W Metal Halide 4.7 -20 55
70W Metal Halide 4.7 -20 45
100W Metal Halide 4.7 -20 40
18W Compact Fluorescent 4.2 -5 60
26W Compact Fluorescent 4.2 -5 55
32W Compact Fluorescent 4.2 -10 45
42W Compact Fluorescent 4.2 -10 40
* The maximum ambient temperatures stated are for exterior use only. For interior use deduct 10ºCfrom the temperature stated.
Photometric data is availableat www.holophane.co.uk
Ø21 bottomcable entry
2 off Ø6.5fixing holes
Ø21.5 rearcable entry
denv
erTM
wal
l
1.26
amenity
easy maintenance
A retaining strap holds the luminaire front in
place, allowing for easy maintenance.
optical arrangement
A combination of reflector and refractive lens
arrangement provides precise optical control
The horizontal and vertical prism arrangement
allows for improved visual comfort with
excellent spacing capabilities
denver wall mounting heights
Lamp Type Min. Recommended Recommended Mounting Mounting Height Height
18PL 2.5m 2.5m-3m
26PL 2.5m 2.5m-3m
32PL 2.5m 2.5m-3m
42PL 2.5m 2.5m-3m
35CDMTF3 3m 3m-4m
50XT 3m 3m-4m
70CDMT3 4m 4m-5m
70XT 4m 4m-5m
1.27
ordering details : luminaire
luminaire accessoriesorder separately for on-site installation by others
Code
DWS.TC70 Photocell (Retro-fit).
CodeDWS Denver Wall
Code Lamp Type.50XT 50W Clear high output HPS lamp (E27) base
.70XT 70W Clear high output HPS lamp (E27) base
.35CDMTF3 35W Clear CDMT 3000K metal halide lamp (G12) base*
.70CDMT3 70W Clear CDMT 3000K metal halide lamp (E27) base*
.100CDMT3 Clear CDM-T 3000K metal halide lamp (E27) base
.18PL2 18W 4000K Compact fluorescent 2-Pin lamp (G24d-2) base
.18PL4 18W 4000K Compact fluorescent 4-Pin lamp (G24q-2) base
.26PL2 26W 4000K Compact fluorescent 2-Pin lamp (G24d-3) base
.26PL4 26W 4000K Compact fluorescent 4-Pin lamp (G24q-3) base
.32PL4 32W Triple tube 4000K compact fluorescent 4-Pin lamp (GX24q-3) base
.42PL4 42W Triple tube 4000K compact fluorescent 4-Pin lamp (GX24q-4) base
Code Colour.C1 White (RAL 9016)
.C4 Graphite (RAL 7011)
.C6 Grey (RAL 7035)
.C7 Black (RAL (9005)
.C9 Metallic Silver (RAL 9006)
.RAL**** RAL colour (customer choice)**
Code Options.A Acrylic
.C Enhanced paint finish
.T Photocell (Factory Fitted)
.S5 Single bottom entry***
.S6 Twin bottom entry****
DWS .18PL2 .C9 .S6
* All ceramic lamp circuits contain timed ignitors. ** Please specify RAL colour reference. *** S5 accepts 2.5mm2 cable and single 21.5mm Ø bottomentry. **** S6 accepts 2.5mm2 cable and twin 21.5mm Ø bottom entry, allowing through wiring.Note: Luminaires are supplied as standard for use on 240V50Hz supply and complete with lamp. For 230V 50Hz add prefix ‘N’ Other voltages available on request.
Example
1.28
denv
erTM
wal
l
amenity
ordering details : emergency luminaire
CodeDWE Denver Wall Emergency Version
Code Lamp Type .18PL4 18W 4000K Compact fluorescent 4-Pin lamp (G24q-2) base
.26PL4 26W 4000K Compact fluorescent 4-Pin lamp (G24q-3) base
.32PL4 32W Triple Tube 4000K compact fluorescent 2-Pin lamp (GX24q-3) base
.42PL4 42W Triple Tube 4000K compact fluorescent 2-Pin lamp (GX24q-4) base
Code Colour.C1 White (RAL 9016)
.C4 Graphite (RAL 7011)
.C6 Grey (RAL 7035)
.C7 Black (RAL (9005)
.C9 Metallic Silver (RAL 9006)
.RAL**** RAL colour (customer choice)*
Code Emergency.ME Maintained emergency (3 hour)
Code Options.A Acrylic
.C Enhanced paint finish
.T Photocell (Factory Fitted)
.S5 Single bottom entry***
.S6 Twin bottom entry****
DWE .18PL4 .C9 .ME .S6
* Please specify RAL colour reference.* All ceramic lamp circuits contain timed ignitors. ** Please specify RAL colour reference. *** S5 accepts 2.5mm2cable and single 21.5mm Ø bottom entry. **** S6 accepts 2.5mm2 cable and twin 21.5mm Ø bottom entry, allowing through wiring.
Example
FLOODLIGHTING
TRENT AL5000
84 www.abacuslighting.com
Lamp Lamp Lamp Description Weight Watts Type Holder (Kg)
AL5021 150W SONP-T / HQI-T E40 Narrow Symmetric Beam 10.50 250W Integral Control Gear 11.03 400W 12.22
AL5022 150W SONP-T / HQI-T E40 Asymmetric Beam 10.50 250W Integral Control Gear 11.03 400W 12.22
AL5023 150W SONP-T / HQI-T E40 Double Asymmetric (50°) Beam 10.50 250W Integral Control Gear 11.03 400W 12.22
Benefits
for architectural and
commercial locations
reflector available to give highly
efficient light output
all-weather and corrosion resistant
polyester powder
wide range of applications
the long catch for quick
and simple servicing
the body dissipate heat effectively
grid, cowl and flux control louvre
Technical Features
polyester powder coated
and wiring box
asymmetric reflector option
central bolt hole (add suffix /M12
to bracket reference)
or metal halide lamps
Accessories
Colours
RAL9006 Silver
RAL9005 Black
ØM8
178
ØM12
ØM8
430
544
461
Professional lighting systems to suit any project. Call 01623 518 333 85
AL5099 Protection grid
AL5097 - Silver AL5097/B Vertical louvre - Black
AL5098 - Silver AL5098/B Cowl - Grey
5m-20m
50º
Key features
Dimensions
Dimensions in mm
50º flat glass reflector dark skies friendly FLOO
DLIG
HTIN
G
AL5022 400w-SONP-T
Asymmetric
2.
AL5023 400w-SONP-T
Double Asymmetric
3.
-90 -50 -300
30 70 900
50
100
150
200
250
300
350
400
450
500cd/klm
-10 10-70 50 -90 -50 -300
30 70 900
200
300
400
500
600
700
800cd/klm
-10 10-70 50
100
AL5021 400w-SONP-T
Symmetric
1.
-90 -60 -30 0 30 60 90V0
1000
2000
3000
4000
5000
6000
7000
8000
9000
10000cd/klm
Accessories
Description, Site & surround
.1 3D view, View from the front
ObjectInstallationProject numberDate
:::: 11.05.2011
-please put your own address here-
Page 1/16D134633-152 (phase 2 plan) E.rdf
Description, Site & surround
.2 3D view, View from the back
ObjectInstallationProject numberDate
:::: 11.05.2011
-please put your own address here-
Page 2/16D134633-152 (phase 2 plan) E.rdf
Description, Site & surround
.3 3D view, View from the left
ObjectInstallationProject numberDate
:::: 11.05.2011
-please put your own address here-
Page 3/16D134633-152 (phase 2 plan) E.rdf
Description, Site & surround
.4 3D view, View from the right
ObjectInstallationProject numberDate
:::: 11.05.2011
-please put your own address here-
Page 4/16D134633-152 (phase 2 plan) E.rdf
Summary, Site & surround
.5 Result overview, Reference plane 1
ObjectInstallationProject numberDate
:::: 11.05.2011
-please put your own address here-
Page 5/16D134633-152 (phase 2 plan) E.rdf
0 50 100 150 200 250 300 350 400[m]
0
50
100
150
200
250
300
350
400
450[m]
N
1.5 2 3 5 7.5Illuminance [lx]
GeneralCalculation algorithm used Average indirect fractionHeight of evaluation surface 0.00 mMaintenance factor 0.80
Total luminous flux of all lamps 484800 lmTotal power 3600 WTotal power per area (145986.80 m²) 0.02 W/m² (0.63 W/m²/100lx)
IlluminanceAverage illuminance Eav 4 lxMinimum illuminance Emin 0 lxMaximum illuminance Emax 698 lxUniformity g1 Emin/Em 1:--- (---)Uniformity g2 Emin/Emax 1:--- (---)
ABACUS LIGHTING LTD11 9 Order No. : AL5023 400W SONP-T
Luminaire name : AL5023 Trent AS SHP-T 400WEquipment : 1 x ST 400 / 48000 lm
Holophane UK13 3 Order No. : !DBL.50XT.RAY.SO
Luminaire name : DENVER BOLLARD 50W SSEquipment : 1 x 50XT / 4400 lm
18 9 Order No. : DWS.50XTLuminaire name : DENVER WALLEquipment : 1 x 50XT / 4400 lm
Summary, Site & surround
.6 Result overview, workshop area
ObjectInstallationProject numberDate
:::: 11.05.2011
-please put your own address here-
Page 6/16D134633-152 (phase 2 plan) E.rdf
0 50 100 150 200 250 300 350 400[m]
0
50
100
150
200
250
300
350
400
450[m]
N
0.0075 0.01 0.015 0.02 0.03Illuminance [lx]
GeneralCalculation algorithm used Average indirect fractionHeight of evaluation surface 0.00 mMaintenance factor 0.80
Total luminous flux of all lamps 484800 lmTotal power 3600 WTotal power per area (145986.80 m²) 0.02 W/m²
IlluminanceAverage illuminance Eav 0.02 lxMinimum illuminance Emin 0 lxMaximum illuminance Emax 0.04 lxUniformity g1 Emin/Em 1:--- (---)Uniformity g2 Emin/Emax 1:--- (---)
ABACUS LIGHTING LTD11 9 Order No. : AL5023 400W SONP-T
Luminaire name : AL5023 Trent AS SHP-T 400WEquipment : 1 x ST 400 / 48000 lm
Holophane UK13 3 Order No. : !DBL.50XT.RAY.SO
Luminaire name : DENVER BOLLARD 50W SSEquipment : 1 x 50XT / 4400 lm
18 9 Order No. : DWS.50XTLuminaire name : DENVER WALLEquipment : 1 x 50XT / 4400 lm
Summary, Site & surround
.7 Result overview, MRF area
ObjectInstallationProject numberDate
:::: 11.05.2011
-please put your own address here-
Page 7/16D134633-152 (phase 2 plan) E.rdf
0 50 100 150 200 250 300 350 400[m]
0
50
100
150
200
250
300
350
400
450[m]
N
3 5 7.5 10 15Illuminance [lx]
GeneralCalculation algorithm used Average indirect fractionHeight of evaluation surface 0.00 mMaintenance factor 0.80
Total luminous flux of all lamps 484800 lmTotal power 3600 WTotal power per area (145986.80 m²) 0.02 W/m²
IlluminanceAverage illuminance Eav 6.5 lxMinimum illuminance Emin 0 lxMaximum illuminance Emax 97.6 lxUniformity g1 Emin/Em 1:--- (---)Uniformity g2 Emin/Emax 1:--- (---)
ABACUS LIGHTING LTD11 9 Order No. : AL5023 400W SONP-T
Luminaire name : AL5023 Trent AS SHP-T 400WEquipment : 1 x ST 400 / 48000 lm
Holophane UK13 3 Order No. : !DBL.50XT.RAY.SO
Luminaire name : DENVER BOLLARD 50W SSEquipment : 1 x 50XT / 4400 lm
18 9 Order No. : DWS.50XTLuminaire name : DENVER WALLEquipment : 1 x 50XT / 4400 lm
Summary, Site & surround
.8 Result overview, IBA processing
ObjectInstallationProject numberDate
:::: 11.05.2011
-please put your own address here-
Page 8/16D134633-152 (phase 2 plan) E.rdf
0 50 100 150 200 250 300 350 400[m]
0
50
100
150
200
250
300
350
400
450[m]
N
7.5 10 15 20 30Illuminance [lx]
GeneralCalculation algorithm used Average indirect fractionHeight of evaluation surface 0.00 mMaintenance factor 0.80
Total luminous flux of all lamps 484800 lmTotal power 3600 WTotal power per area (145986.80 m²) 0.02 W/m²
IlluminanceAverage illuminance Eav 13 lxMinimum illuminance Emin 0 lxMaximum illuminance Emax 668 lxUniformity g1 Emin/Em 1:--- (---)Uniformity g2 Emin/Emax 1:--- (---)
ABACUS LIGHTING LTD11 9 Order No. : AL5023 400W SONP-T
Luminaire name : AL5023 Trent AS SHP-T 400WEquipment : 1 x ST 400 / 48000 lm
Holophane UK13 3 Order No. : !DBL.50XT.RAY.SO
Luminaire name : DENVER BOLLARD 50W SSEquipment : 1 x 50XT / 4400 lm
18 9 Order No. : DWS.50XTLuminaire name : DENVER WALLEquipment : 1 x 50XT / 4400 lm
Summary, Site & surround
.9 Result overview, IBA processing main vehicle circulation area
ObjectInstallationProject numberDate
:::: 11.05.2011
-please put your own address here-
Page 9/16D134633-152 (phase 2 plan) E.rdf
0 50 100 150 200 250 300 350 400[m]
0
50
100
150
200
250
300
350
400
450[m]
N
15 20 30 50 75Illuminance [lx]
GeneralCalculation algorithm used Average indirect fractionHeight of evaluation surface 0.00 mMaintenance factor 0.80
Total luminous flux of all lamps 484800 lmTotal power 3600 WTotal power per area (145986.80 m²) 0.02 W/m²
IlluminanceAverage illuminance Eav 39 lxMinimum illuminance Emin 1 lxMaximum illuminance Emax 732 lxUniformity g1 Emin/Em 1:57.1 (0.02)Uniformity g2 Emin/Emax 1:1070 (0)
ABACUS LIGHTING LTD11 9 Order No. : AL5023 400W SONP-T
Luminaire name : AL5023 Trent AS SHP-T 400WEquipment : 1 x ST 400 / 48000 lm
Holophane UK13 3 Order No. : !DBL.50XT.RAY.SO
Luminaire name : DENVER BOLLARD 50W SSEquipment : 1 x 50XT / 4400 lm
18 9 Order No. : DWS.50XTLuminaire name : DENVER WALLEquipment : 1 x 50XT / 4400 lm
Summary, Site & surround
.10 Result overview, main loading area for IBA plant
ObjectInstallationProject numberDate
:::: 11.05.2011
-please put your own address here-
Page 10/16D134633-152 (phase 2 plan) E.rdf
0 50 100 150 200 250 300 350 400[m]
0
50
100
150
200
250
300
350
400
450[m]
N
50 75 100 150 200Illuminance [lx]
GeneralCalculation algorithm used Average indirect fractionHeight of evaluation surface 0.00 mMaintenance factor 0.80
Total luminous flux of all lamps 484800 lmTotal power 3600 WTotal power per area (145986.80 m²) 0.02 W/m²
IlluminanceAverage illuminance Eav 110 lxMinimum illuminance Emin 5 lxMaximum illuminance Emax 429 lxUniformity g1 Emin/Em 1:22.6 (0.04)Uniformity g2 Emin/Emax 1:88.4 (0.01)
ABACUS LIGHTING LTD11 9 Order No. : AL5023 400W SONP-T
Luminaire name : AL5023 Trent AS SHP-T 400WEquipment : 1 x ST 400 / 48000 lm
Holophane UK13 3 Order No. : !DBL.50XT.RAY.SO
Luminaire name : DENVER BOLLARD 50W SSEquipment : 1 x 50XT / 4400 lm
18 9 Order No. : DWS.50XTLuminaire name : DENVER WALLEquipment : 1 x 50XT / 4400 lm
Summary, Site & surround
.11 Result overview, turning area
ObjectInstallationProject numberDate
:::: 11.05.2011
-please put your own address here-
Page 11/16D134633-152 (phase 2 plan) E.rdf
0 50 100 150 200 250 300 350 400[m]
0
50
100
150
200
250
300
350
400
450[m]
N
0.15 0.2 0.3 0.5 0.75Illuminance [lx]
GeneralCalculation algorithm used Average indirect fractionHeight of evaluation surface 0.00 mMaintenance factor 0.80
Total luminous flux of all lamps 484800 lmTotal power 3600 WTotal power per area (145986.80 m²) 0.02 W/m²
IlluminanceAverage illuminance Eav 0.25 lxMinimum illuminance Emin 0.04 lxMaximum illuminance Emax 1.28 lxUniformity g1 Emin/Em 1:6.07 (0.16)Uniformity g2 Emin/Emax 1:30.6 (0.03)
ABACUS LIGHTING LTD11 9 Order No. : AL5023 400W SONP-T
Luminaire name : AL5023 Trent AS SHP-T 400WEquipment : 1 x ST 400 / 48000 lm
Holophane UK13 3 Order No. : !DBL.50XT.RAY.SO
Luminaire name : DENVER BOLLARD 50W SSEquipment : 1 x 50XT / 4400 lm
18 9 Order No. : DWS.50XTLuminaire name : DENVER WALLEquipment : 1 x 50XT / 4400 lm
Summary, Site & surround
.12 Result overview, 7
ObjectInstallationProject numberDate
:::: 11.05.2011
-please put your own address here-
Page 12/16D134633-152 (phase 2 plan) E.rdf
0 50 100 150 200 250 300 350 400[m]
0
50
100
150
200
250
300
350
400
450[m]
N
20 30 50 75 100Illuminance [lx]
GeneralCalculation algorithm used Average indirect fractionHeight of evaluation surface 0.00 mMaintenance factor 0.80
Total luminous flux of all lamps 484800 lmTotal power 3600 WTotal power per area (145986.80 m²) 0.02 W/m²
IlluminanceAverage illuminance Eav 52 lxMinimum illuminance Emin 1 lxMaximum illuminance Emax 746 lxUniformity g1 Emin/Em 1:41.3 (0.02)Uniformity g2 Emin/Emax 1:592 (0)
ABACUS LIGHTING LTD11 9 Order No. : AL5023 400W SONP-T
Luminaire name : AL5023 Trent AS SHP-T 400WEquipment : 1 x ST 400 / 48000 lm
Holophane UK13 3 Order No. : !DBL.50XT.RAY.SO
Luminaire name : DENVER BOLLARD 50W SSEquipment : 1 x 50XT / 4400 lm
18 9 Order No. : DWS.50XTLuminaire name : DENVER WALLEquipment : 1 x 50XT / 4400 lm
Summary, Site & surround
.13 Result overview, 3
ObjectInstallationProject numberDate
:::: 11.05.2011
-please put your own address here-
Page 13/16D134633-152 (phase 2 plan) E.rdf
0 50 100 150 200 250 300 350 400[m]
0
50
100
150
200
250
300
350
400
450[m]
N
0.2 0.3 0.5 0.75 1Illuminance [lx]
GeneralCalculation algorithm used Average indirect fractionHeight of evaluation surface 0.00 mMaintenance factor 0.80
Total luminous flux of all lamps 484800 lmTotal power 3600 WTotal power per area (145986.80 m²) 0.02 W/m²
IlluminanceAverage illuminance Eav 0.5 lxMinimum illuminance Emin 0.1 lxMaximum illuminance Emax 15.9 lxUniformity g1 Emin/Em 1:6.41 (0.16)Uniformity g2 Emin/Emax 1:187 (0.01)
ABACUS LIGHTING LTD11 9 Order No. : AL5023 400W SONP-T
Luminaire name : AL5023 Trent AS SHP-T 400WEquipment : 1 x ST 400 / 48000 lm
Holophane UK13 3 Order No. : !DBL.50XT.RAY.SO
Luminaire name : DENVER BOLLARD 50W SSEquipment : 1 x 50XT / 4400 lm
18 9 Order No. : DWS.50XTLuminaire name : DENVER WALLEquipment : 1 x 50XT / 4400 lm
Summary, Site & surround
.14 Result overview, 8
ObjectInstallationProject numberDate
:::: 11.05.2011
-please put your own address here-
Page 14/16D134633-152 (phase 2 plan) E.rdf
0 50 100 150 200 250 300 350 400[m]
0
50
100
150
200
250
300
350
400
450[m]
N
30 50 75 100 150Illuminance [lx]
GeneralCalculation algorithm used Average indirect fractionHeight of evaluation surface 0.00 mMaintenance factor 0.80
Total luminous flux of all lamps 484800 lmTotal power 3600 WTotal power per area (145986.80 m²) 0.02 W/m²
IlluminanceAverage illuminance Eav 83 lxMinimum illuminance Emin 0 lxMaximum illuminance Emax 311 lxUniformity g1 Emin/Em 1:927 (0)Uniformity g2 Emin/Emax 1:3470 (0)
ABACUS LIGHTING LTD11 9 Order No. : AL5023 400W SONP-T
Luminaire name : AL5023 Trent AS SHP-T 400WEquipment : 1 x ST 400 / 48000 lm
Holophane UK13 3 Order No. : !DBL.50XT.RAY.SO
Luminaire name : DENVER BOLLARD 50W SSEquipment : 1 x 50XT / 4400 lm
18 9 Order No. : DWS.50XTLuminaire name : DENVER WALLEquipment : 1 x 50XT / 4400 lm
Summary, Site & surround
.15 Result overview, 6a
ObjectInstallationProject numberDate
:::: 11.05.2011
-please put your own address here-
Page 15/16D134633-152 (phase 2 plan) E.rdf
0 50 100 150 200 250 300 350 400[m]
0
50
100
150
200
250
300
350
400
450[m]
N
7.5 10 15 20 30Illuminance [lx]
GeneralCalculation algorithm used Average indirect fractionHeight of evaluation surface 0.00 mMaintenance factor 0.80
Total luminous flux of all lamps 484800 lmTotal power 3600 WTotal power per area (145986.80 m²) 0.02 W/m²
IlluminanceAverage illuminance Eav 16 lxMinimum illuminance Emin 0 lxMaximum illuminance Emax 486 lxUniformity g1 Emin/Em 1:--- (---)Uniformity g2 Emin/Emax 1:--- (---)
ABACUS LIGHTING LTD11 9 Order No. : AL5023 400W SONP-T
Luminaire name : AL5023 Trent AS SHP-T 400WEquipment : 1 x ST 400 / 48000 lm
Holophane UK13 3 Order No. : !DBL.50XT.RAY.SO
Luminaire name : DENVER BOLLARD 50W SSEquipment : 1 x 50XT / 4400 lm
18 9 Order No. : DWS.50XTLuminaire name : DENVER WALLEquipment : 1 x 50XT / 4400 lm
Summary, Site & surround
.16 Result overview, 6b
ObjectInstallationProject numberDate
:::: 11.05.2011
-please put your own address here-
Page 16/16D134633-152 (phase 2 plan) E.rdf
0 50 100 150 200 250 300 350 400[m]
0
50
100
150
200
250
300
350
400
450[m]
N
10 15 20 30 50Illuminance [lx]
GeneralCalculation algorithm used Average indirect fractionHeight of evaluation surface 0.00 mMaintenance factor 0.80
Total luminous flux of all lamps 484800 lmTotal power 3600 WTotal power per area (145986.80 m²) 0.02 W/m²
IlluminanceAverage illuminance Eav 17.8 lxMinimum illuminance Emin 4 lxMaximum illuminance Emax 29.8 lxUniformity g1 Emin/Em 1:4.42 (0.23)Uniformity g2 Emin/Emax 1:7.4 (0.14)
ABACUS LIGHTING LTD11 9 Order No. : AL5023 400W SONP-T
Luminaire name : AL5023 Trent AS SHP-T 400WEquipment : 1 x ST 400 / 48000 lm
Holophane UK13 3 Order No. : !DBL.50XT.RAY.SO
Luminaire name : DENVER BOLLARD 50W SSEquipment : 1 x 50XT / 4400 lm
18 9 Order No. : DWS.50XTLuminaire name : DENVER WALLEquipment : 1 x 50XT / 4400 lm