Protection Relay for Feeder, Grid and Generator Applications

Protection Technology made simple

ApplicationThe MRA4 is a protection relay which uses the latest Dual-Core-Processor Technology to provide precise and re-liable protective functions and is very easy to operate. Its various protective functions are specifically tailored to the protection of incoming and out-going feeders in MV systems. It also can be used for grid and generator protection. All inclusive:

All protection features without • extra charge

Parameter setting and • evaluation software

Disturbance record analysis • software

Six stages phase overcurrent protection

Directional and non-directional • overcurrent/short-circuit protection

Tripping characteristics: • DEFT ANSI: NINV, VINV, EINV IEC: NINV, VINV, LINV, EINV Thermal Flat, IT, I2T, I4T

Voltage controlled•

Disturbance recorder120 s non volatile, •

32 samples per cycles

Additional highlightsAutomatic reclosing•Inrush•Thermal replica•Four stages external protection•Plausibility checks•Adaptive parameter sets•Energy counters•Status display•Comprehensive measured values •

and statisticsMasking of unused functions•

Parameter setting support by software

Copy parameter sets•Compare parameter sets•Setting files are up and down •

convertible (across versions)

Comprehensive frequency protection packageEach of the six stages can be used as:

f< or f> (over- and • underfrequency supervision)

df/dt (ROCOF) • Rate of change of frequency

(f< and df/dt) or (f> and df/dt) • combination of over-, under- and rate of change of frequency (ROCOF)

(f< and DF/DT) or (f> and DF/DT) • combination of over-, under- and increase of frequency

Delta Phi (Vector surge)•

Power protection packageSix stages power protection •

Each can be used as P>, P<, Pr, Q>, Q<, Qr, S>, S<

Two stages power factor (PF)•

SupervisionCurrent transformer supervision•Voltage transformer supervision•Circuit breaker failure protection•Trip circuit supervision•Cold load pickup•Switch onto fault•

HighPROTEC

MRA4

Four stages earth fault protectionDirectional and non-directional •

earth fault protectionTripping characteristic: •

DEFT ANSI: NINV, VINV, EINV IEC: NINV, VINV, LINV, EINV Thermal Flat, IT, I2T, I4T

Voltage controlled•

Two stages unbalanced load protection

Supervision by definite time or • tripping characteristic

Four stages voltage protectionUnder- and overvoltage•Programmable undervoltage •

time depending characteristic

Two stages residual voltage protection

VE>•

Six stages voltage asymmetry supervision

Under- and overvoltage in • positive phase sequence system, overvoltage in negative phase sequence system

Page 2: Dok Fly Mra4e Mra4

Functional Overview

PrOTeCTive FunCTiOnS elements AnSi

I, time overcurrent and short circuit protection, all stages can be configured for directional or non-direc-tional supervision. Tremendous reset options (instantaneous, definite time, reset characteristics accor-ding to IEC and ANSI). Voltage controlled overcurrent protection by means of adaptive parameters.

6 6

50P, 51P, 67P

51V

I2>, unbalanced load protection with evaluation of the negative phase sequence currents 2 46

IB, overload protection with thermal replica and separate pick-up values for alarm and trip functions 1 49

IH2/In, inrush detection with evaluation of the 2nd harmonic 1 Inrush

IE, earth overcurrent and short circuit protection, all stages can be configured for directional or non-directional supervision. Tremendous reset options (instantaneous, definite time, reset characteristics according to IEC and ANSI). Voltage controlled overcurrent protection by means of adaptive parameters.

4 4

50N,51N, 67N

51V

V<, V>, V(t)<, under- and overvoltage protection, time dependent undervoltage protection 4 27, 59

Voltage asymmetry supervision (V012)V1, under and overvoltage in positive phase sequence systemV2, overvoltage in negative phase sequence system

6 47

Each of the six frequency protection stages can be used as: 6

f< or f> (over- and under frequency supervision)• 81U/O

df/dt rate of change of frequency (ROCOF)• 81R

(f< and df/dt) or (f> and df/dt) combination of over-, under- and rate of change of frequency (ROCOF) •

(f< and DF/DT) or (f> and DF/DT) • combination of over-, under- and increase of frequency

Delta Phi (Vector surge)• 78

VE, residual voltage protection 2 59N

AR, automatic reclosing 1 79

ExP, External alarm and trip functions 4

PQS, Power protection 6 32, 37

PF, Power factor 2 55

SuPerviSiOn FunCTiOnS elements AnSi

CBF, circuit breaker failure protection 1 50BF

TCS, trip circuit supervision 1 74TC

VTS, voltage transformer supervision by comparing phase and residual voltages 1 60FL

VTS, fuse failure protection via digital input 1 60FL

CTS, current transformer supervision 1 60L

CLPU, cold load pickup 1

SOTF, switch onto fault 1

Non volatile event recorder up to 120 s with 32 samples per cycles

Page 3: Dok Fly Mra4e Mra4

3

1

4

MRA4

50BF

60FL27

Fault recorder

Event recorder

Disturbance recorder

V, VE, V012, I, IG, f, delta phi, theta , IH2,

IGH2, I012, P, Q, S, PF, cos phi, W

Measured and calculated values49 51P 67P50P46

81 U/O

67N79 Inrush

59 59N 50N 51N

74TC

7881R

37

32 60L 55

SOTF CLPU

47

51V

Functional overview in AnSi form

Connections

Page 4: Dok Fly Mra4e Mra4

Current inputs 4 (1 A and 5 A) with automatic short circuitersvoltage inputs 4 (0 - 800 V)Digital inputs Switching thresholds adjustable via softwarePower supply Wide range power supplyTerminals All terminals plug typeMounting Door mountingType of enclosure IP54Dimensions of housing 212.7 mm x 173 mm x 209 mm (W x H x D)Weight (max. components) approx. 4 kg

Woodward SEG GmbH & Co. KGKrefelder Weg 47

D - 47906 Kempen

Sales TeamPhone: +49 (0) 21 52 1 45 - 1

Fax.: +49 (0) 21 52 1 45 - 3 54e-mail: [email protected]

ServiceTelefon: +49 (0) 21 52 1 45 - 6 14/3 34

Fax.: +49 (0) 21 52 1 45 - 4 55e-mail: [email protected]

Visit us at www.eps.woodward.com DO

K_FL

Y_M

RA4_

04.0

9_EN

Enabling Electrical Power Systems Integration

Order form MrA4

Directional Feeder Protection MrA4

Digital Inputs

Binary out-put relay Housing Large

display

816

713

B2B2

--

AD

Hardware variant 2Standard

0

Housing and mountingDoor mountingDoor mounting 19“ (flush mounting)

A B

Communication protocolProtocol/without protocol RS485/terminals, Modbus RTU, IEC60870-5-103 Ethernet (RJ45), Modbus TCP, IEC61850* prepared (Hardware/Interface) Optic fiber, Modbus RTU, IEC60870-5-103 RS485/D-SUB, Profibus**, Modbus RTU, IEC60870-5-103

A B C F G

Presetting of available menu languagesStandard English/German

* Additional cost for the software update tool IEC61850 per device are 250 €. The devices can be updated via device front interface (RS232) and PC locallyExpected availability: 01.01.2010**expected 07.09