Our production site in Sissach, Switzerland
Withalmostacenturyofexperience,wearetherightpart-ner for high-quality electrotechnical products and energydistributionsystems.
Our product portfolio
• Transformers• Railwayswitches• Highcurrentplug-inconnectors• Buildingjunctionboxes• LUswitchgearsystems
Our flexibility and commitment to innovation makes us areliablepartnerthatiscapableofsolvingallchallengespre-sentedtousbyourcustomers.Withourhigh-quality,elec-trotechnicalproductsandsustainable, innovativesolutions,weareatrustedpartnertoourcustomers.Experiencedlong-termemployeesandjunioremployeeswiththewillandam-bitiontocontinuouslylearnarethefoundationofourcom-pany.
Ourcompanyiscertifiedinaccordancewithallcurrentstan-dards.
Long TraditionFirmlyanchoredinSwitzerland
Electricityisoneofthemostimportantsourcesofenergyanddrivingforcesofmodernsociety.
5
Distribution transformers prior to delivery
Quality and ExperienceThekeytoreliability
Toprevailagainstfiercecompetitionoverthelongterm,yousimplyhavetobebetter.
Weareoneof the leadingmanufacturers in thefieldof li-quid-filleddistributiontransformers.Basedonourlongtimeexperiencewearealsoable todesignspecial low-radiationtransformerswhichfullycomplywiththeOrdinanceonPro-tectionagainstNon-IonizingRadiation.Liquid-filledtransfor-mersarealsoproducedforripplecontrolapplicationsandasoverheadlinetransformersforrailwaycompanies.
Distribution transformers from Rauscher & Stoecklin fullycomplywiththeapplicableinternationalstandardsandregu-lations.Thepowerrangeextendsfrom100 kVAto2500kVAwithamaximumratedvoltageof36kV.Wedesignfree-bre-athing or hermetically sealed transformers depending oncustomerrequirements.
6
Distribution transformer design1.Pressurereliefvalve2.USconnections3.High-voltageplug-inbushings4.High-voltagetapchanger5. Liftingeyes6.Thermometerwithtrailingpointer
7. Ironcoreclampingangle8. Tank9. High-voltagewinding10. Low-voltagewinding11. Ironcore12. Castorsforlongitudinalandlateraltravel
Transformer Design
Avariousnumberofapplicationsrequiretechnologiesthathelptoachievealongservicelife,lowoperatingcostsandensureenvironmentalsustainability.
Design of an oil-filled distribution transformer
1
2 3
4 5
6
7
8
9
10
11
12
7
Features of our distribution transformers• Ratedpowerrangingfrom100upto2,500 kVA,50 Hz• Operatingvoltageupto36kV• Max.lossesinaccordancewithEU548 / 2014• Regulationoftheprimaryvoltage±2x2.5 %oraccordingtocustomerspecifications
• Max.installationaltitude1,000 metersabovesealevel• High-voltagebushings:plug-inbushingsforouterconesystemterminalorwithporcelainbushingsforindoororoutdoorinstallation
• Low-voltagebushings:porcelainbushingswithorwithoutflatconnectionplate
• Compactandlightweightdesign• Low-radiationdesignwith8-pointsymmetriclow-voltagebushingsonrequest
• Integratedoilretentionvatavailableonrequest (mountedbetweentankandchassisframe)
• Reinforcedinsulationandgroundedshieldbetweenhigh-voltage/low-voltagewindingsfornon-sinusoidalloadavailableonrequest
Welding the low-voltage connection of the secondary coil
Main Features
8
Distribution TransformersDesignedinSwitzerland
Rauscher & Stoecklinstandsforinnovationandqualitysince1919.
High-voltage winding
The high-voltage layer winding is wound directly on thelow-voltagewindingwiththemainisolationchannel.State-of-the-artautomatedwindingmachineswithconstantwindingtension create compact coilswithmaximumstrength. Thelayerisolationmadeofhigh-qualityinsulatingpaperisdesi-gnedusingstripisolationtechnologyandmeetsthehighestdemandsinmoderndistributiongrids.
Low-voltage winding
Low-voltage stripwindings are used for transformers star-tingwithanoutputof160 kVA.Theaxialpowerdistributioncanbefreelyadjusted inthestripwindings.Thisminimizesthethrustforcesthatoccurduringshortcircuits.Duringthedryingprocess,theactivepartbondsthelayerisolationwiththeconductorstripintoacompactcoil.
Rauscher & Stoecklin offers a wide range of transformers.Free-breathingtransformers,whicharethepreferreddesigninSwissdistributionnetworks,offertheoperatingcompanyeasymaintenancewiththesmallestdimensionsand lowestweights possible. For export markets Rauscher & Stoecklinhasalonghistoryinproducinghermeticallysealedtransfor-mers.
Our production site in Sissach has around 95 trained andhighlyqualifiedemployeesandoffersgenuineSwissquality.
9
Assembling the active part
Usingclampingstrapsmadeofstripsteel,theironcoreyokeisoptimallypressedtogetherwiththecolumnsusingprofiledsteel.Thiseliminatestierodsthatadverselyaffectthemag-neticflux.Theactivepartissecurelyscrewedtothecoverandsupportedagainstthebaseofthetank.
Iron core
Thesemicircularorovalcoreshapeallowsforextensivestan-dardizationandoptimizationandmakesiteasytoadjustthecorecross-section.Thecoreisinterleavedinastep-lappro-cess.Thesheetmetaljointshaveseveraloffsets.Thistechno-logycoupledwiththeselectionofhigh-qualitymagneticsteelplateprovidesadditionalbenefitsintermsofno-loadlossesandalownoiselevel.Weoffertransformerswithamorphouscorematerialforapplicationsinwhichextremelylowno-loadlossesarerequired.
Corrosion protection
Thecorrosionprotectionisparticularlyimportant.Thetankand cover are sand-blasted and painted or power-coatedwithseverallayersinthestandardcolorRAL7033.Low-sol-ventpaintispreferredinordertoprotecttheenvironment.
Tank & cover
Thetransformertankmustwithstandallmechanicalandther-mal loads that occur during transport and operation. Rau-scher & Stoecklin uses corrugated tanksmade of cold-rolledstripsteelwithareinforcedbottomtrough.Alloftheheatlossisreleasedfromthetanksurfaceintotheambientair.Theco-ver isbenton the longitudinal sides foradditional reinforce-mentandscrewedtothetank.Twoliftingeyesareweldedtotheunittoliftthetransformerortheactivepart.
10
Free-breathing transformersOpen transformers have been adopted as the standard inSwitzerland.Thecoverhastwopressure-reliefvalveopeningsthroughwhichtheairisexchangedwiththeaircushionunderthecoverinsidethetransformer.Thisaircushionmakescon-tactwith thecooling liquidandanyabsorbedmoistureovertheentiresurfacecanescapeduringhighercoolanttempera-tures.The free-breathingdesign is characterizedby lowoilvolumeandextremely small dimensions.Duringoperation,thetransformeroperateswithoutanypressure.Inaddition,thetankisnotsubjectedtoadditionalmechanicalloads.Thefree-breathingdesignhasprovenitselfathousandtimesoverandiscost-effective.
Hermetically sealed transformersTransformerswithhermeticallysealedtanksarestandardininternationalmarkets. The unit is fully hermetically sealed,thuspreventingdirectcontactofthecoolingliquidwiththeair and further reducing maintenance costs thanks to thehigheroilquality.Theoilexpansionisabsorbedbythecoo-ling shaftsand thereforesubjects the tank toanadditionalmechanicalload.Inordertolimitthepressure,hermeticallysealedtransformersrequirelowershafts,whichresults inahigheroil volume.As a result, thedimensions andweightsincreaseaccordingly.
DesignsYourSpecification–YourTransformer
Wehavebeenmanufacturingtransformerswithstate-of-the-artequipmentaccordingtocustomerrequirementsfornearly100years.
Free-breathing design
11
Industrial transformersWerecommendonlyoperatingspeciallydesigned transfor-mersinindustrialgridsinwhichhightransientinterferencevoltagesaretobeexpected,forexampleduetopowercon-vertersorfrequency-controlleddrives.
Frequentorconstanttransientinterferencevoltagesresultintheprematureageingof thepaper insulationandwirecoa-ting,bothonthetransformer'slow-voltageandhigh-voltageside.
Inordertopreventthis,additionalmeasuresmustbetaken;thelayerinsulationmustbereinforcedandagroundedshieldmustbeinstalledbetweenthehigh-voltageandlow-voltagewinding.
Cast resin transformersRauscher & Stoecklin offers cast resin transformers fromTesar,acompanyof theR&SGroup,asanalternative to li-quid-filleddistributiontransformers.Thecastresintransfor-merscomplywiththeapplicableinternationalstandardsandareusedwhereverliquid-filledtransformersareundesirable or wherever environmental or fire prevention regulationsexist. The power range extends from 160 kVA to 25 MVAwithamaximumratedvoltageof52kV.
High-qualitymaterialscoupledwithsolidworkmanshipensu-remaximumreliability.Thelow-voltagewindingisinsulatedwithresin.Thehigh-voltagewindingiscastwithoutanycavi-tiesinacompressionmoldundervacuumandhardenedwithnocracking.Fiberglassinsulationandepoxyresinareusedtoensurehighmechanicalstrength.
Due to the lowfire risk, cast resin transformers canbe in-stalledintheload'scenterofgravity.Theyeasilywithstandshort-termpeakloads,whichoccurwhenstartingmotorsorduringweldingoperations.Afancanbeinstalledtoallowforapermanentoverloadofupto40 %.Thefansarefastenedtothetransformerclampingstructureandcanberetrofittedatanytime.
Castresintransformerscanalsobeinstalledinhousingsonrequest.ProtectionclassesIP 21,IP 23andIP 31areavailable.
Cast resin transformer
12
Customized solutionsIf standard solutions cannot meet all application require-ments, we also produce customized solutions on request.Thecustomerisinvolvedineverydevelopmentsteptode-velop the perfect solution. Rauscher & Stoecklin has pro-found expertise and a series of reference projects in thisarea.
Dry-type transformersRauscher&Stoecklinair-cooledtransformersareusedwher-ever lowvoltagemustbe transformed into lowvoltage.Theunitsaremanufacturedaccordingtocustomerspecificationsasanautotransformerorisolatingtransformerandarealsobasedonindividualcustomerrequests.
Thepowerrangeforsingle-phasetransformersextendsfrom5 kVAto100 kVAandforthree-phasetransformersfrom10kVAto400kVAwithamaximumratedvoltageof1.1kV.
The transformers are designed with insulation class B or Fdependingonthesizeorcustomerrequirements. Insulationthatischaracterizedbyhighmechanicalandelectricstrengthandgoodthermalpropertiesisuseddependingontherequi-redthermalclass.Theactivepartisimpregnatedusingava-cuum-pressureorimmersiontechniquetoprotectitagainstmoisture.ItisthenpaintedinthecolorRAL 7032.
Dry-typetransformerscanalsobe installed inhousingsonrequest.ProtectionclassesfromIP 20toIP 22areavailable.
Single-phase transformer
Special-purpose transformersLoads in thedistributiongridarecontrolledremotelyusingaudiofrequencyripplecontrol.
Wesupplyaudio-frequencytransformersforthesimultaneoussupplyof ripplecontrol systems fora frequency range from200 Hzto2000 Hzandforamaximumratedvoltageofappro-ximately36 kV.
For railway companies, Rauscher & Stoecklin produces sing-le-phaseoverheadlinetransformersupto1000 kVAforsup-plyingloadsinrailwaygridswith15 kVand162/3 Hzor25 kVand50 Hz.
Special ApplicationsNewChallenges– NewSolutions
Ourcustomizedsolutionsandspecialoptionssatisfyallcustomerrequire-ments
13
Amorphous transformersTomeettheconstantly increasingdemandsintermsof los-ses, Rauscher & Stoecklin also offers distribution transfor-merswithamorphouscores.
Amorphous transformerswithparticularly lowno-load los-sesareidealwhereversuchlossesplayamajorroleandtheassociatedcostsaretobeabsorbedoverthelongterm.Mostamorphoustransformersnowalreadysatisfythelimitvaluerequirementsthatwillcomeintoforcein2021.
The lower no-load losses compared to a convention trans-formeraretheresultofthecorematerial.Thecoreinamor-phoustransformers isproducedoutofverythinfoilsmadeofamorphousmaterials.
Thecrystallinestructureoftheamorphouscoreissignificant-lyeasiertomagnetizeanddemagnetizethanwithaconven-tionalcore.Thisproducesconsiderablyfewerno-loadlosses.
Theamorphoustransformersareavailableintheoutputran-gefrom400 kVAto1,000 kVA.Othersizesareavailableonrequest.Theyofferthesameequipmentoptionsasthestan-dardtransformers.
Distribution Transformer with on-load tap changerWhen planning and operating grids, there is an increasingnumberofobviousadvantagesachievedbydynamicallyad-justing the voltage in the distribution grid and thus also inmediumand lowvoltage.Asalreadymentioned in thehig-hervoltagelevels,vacuumon-loadtap-changersarethetoolofchoicehere–replacingthestatictransformersthathavebeenusedtodate–toexpandthevoltageadjustmentfunc-tionduringoperationinthedistributiongrid.
Controllabletransformersthatcandynamicallychangethetransformerratioandthus thevoltagesare theworldwidestandard in high-voltage and extra-high-voltage grid sys-tems. In the past, however,most transformers connectedtomediumvoltagecontaineda tapchanger,viawhich thevoltage could only be adjustedwhen the transformerwasswitchedoff.
ThisiswhyRauscher & Stoecklinoffersdistributiontransfor-merswithon-loadtapchanger.Withvacuumon-loadtapch-angers,werelyontheexperienceandproventechnologyofMaschinenfabrikReinhausen.Wewillbehappytoadviseyouaboutyourcustomizedsolution.
Low-radiation transformer
14
Test MethodsOurtestfacility
TestingAll transformers undergo standardized routine testing andatestreport isdrawnupatourtestfacility.Itcontainsthefollowingpoints:• Measurementofthewindingresistances• Measurementoftransformerratioanddeterminationofthevectorgroup
• Testwithappliedvoltage(externalvoltagetest)• Testwithinducedvoltage(internalvoltagetest)• Measurementofno-loadcurrentsandno-loadlosses• Measurementofwindinglossesandshort-circuitvoltage
Type and special testingTypetestsandspecialtestingarealsoperformedinourtestfacilityoranexternaltestfacilityoncustomerrequest:
• Noisemeasurement• Temperaturerisemeasurement• Short-circuitresistance• Surgevoltagetest• Oilanalyses
Our transformer test facility
16
Our AccessoriesCustomizedsolutions
Integrated oil retention vat
Thistransformerdesignisequippedwithanintegratedoilre-tentionvatmadeofsteel.Itissecurelyconnectedtothetrans-formerbetweenthetankandthechassisframe.Integratedoilretentionvatsmustbeincludedintheprojectfromthestart,sincethewidertransformerdimensionsmaynolongerallowinstallationthroughexistingdooropenings.
Stand-alone oil retention vat
Stand-aloneoil retention vats aremadeof lightweight alu-minumandaresuppliedseparately.Thestand-alonedesignoffersvariousadvantages.Theycanbesubsequentlyplacedundereverytransformerandinstalledseparatelyinthestati-on.Narrowdoorsnolongerpresentaproblem.Allstand-alo-neoiltroughscanbeconnectedonthelongitudinalornar-row side or completely sealed.With the EASY design, thetransformermust only be lifted a fewmillimeters and canthusberolledintothetrough.
Contact dial thermometer
• Instainlesssteel• ProtectionclassIP54• Measuringrange0–120°C• Accuracyclass1.5• ScrewconnectionG1• Withtrailingpointer(standardfrom400kVA)• Withtrailingpointerandswitchingoutput (2microswitches)
17
Castors
• AccordingtoEN50216-4withframe,switchableforlongi-tudinal and transverse travel
• Sizesupto400 kVA:Ø125 x 40 mm,nylon,bracketM16• Sizesupto630 kVA:Ø125 x 40 mm,castiron,bracketM16
• Sizesupto1600 kVA:Ø125 x 40 mm,castiron,bracketM24,colorRAL7033
• WheellockcanbefixedwithM12screws• Wheellockfornylonorcastironcastors,Ø125 x 40 mm
Additional accessories and options
Rauscher & Stoecklinoffersthefollowingcustomizedsolu-tions:• Specialdimensions• Specialaltituderequirements• Measuresforseismicsafety• Additionalmonitoringdevices(PT100,RIS,etc.)
Pleasedonothesitatetotellusaboutyourindividualrequi-rements.
Vibrastop & wheel locks
Vibrastop:• Fortransformersfrom500upto2,500 kg• Fortransformersfrom2,500upto12,000 kg
Connecting plates
• AccordingtoDIN42530• DT630hole1xØ14 mm• DT1000hole2xØ14 mm• DT2000hole3xØ14 mm• DT3150hole4xØ14 mm
18
AtRauscher & Stoecklin,weareproudofourtestfacility,aswell as the regular routine testing andwide variety of ad-ditionalmeasurementsthatweofferinaccordancewithIECstandards(seealsoourtestmethods).
Wecanalsoperformallthestandardoilinspectionsforourcustomersinourlaboratory.
Ofcourse,Rauscher & Stoecklincontinuouslymonitors,regu-larlycalibratesandcertifiesthetestequipment.Certificatescanbeprovidedonrequest.Rauscher & Stoeckliniscertifiedinaccordancewith ISO9001, ISO14001andOHSAS18001standards.
Certified Quality
Weinsistonthehighestqualitystandardsbothforourcompanyaswellasourproducts.
Michael DrechselPresident of IQNet
Roland GlauserCEO SQS
CERTIFICATEIQNet and SQS
hereby certify that the organisation
has implemented and maintains a
Management Systemwhich fulfills the requirements of the following standard(s)
ISO 9001:2015 / ISO 14001:2015 / OHSAS 18001:2007Scope No(s): 19
Issued on: 2015-10-26Validity date: 2018-10-25
Registration Number: CH-11250
IQNet Partners*:AENOR Spain AFNOR Certification France AIB-Vinçotte International Belgium APCER Portugal CCC Cyprus
CISQ Italy CQC China CQM China CQS Czech Republic Cro Cert Croatia DQS Holding GmbH GermanyFCAV Brazil FONDONORMA Venezuela ICONTEC Colombia IMNC Mexico Inspecta Certification Finland INTECO Costa Rica
IRAM Argentina JQA Japan KFQ Korea MIRTEC Greece MSZT Hungary Nemko AS Norway NSAI Ireland PCBC PolandQuality Austria Austria RR Russia SIGE Mexico SII Israel SIQ Slovenia SIRIM QAS International Malaysia
SQS Switzerland SRAC Romania TEST St Petersburg Russia TSE Turkey YUQS SerbiaIQNet is represented in the USA by: AFNOR Certification, CISQ, DQS Holding GmbH and NSAI Inc.
* The list of IQNet partners is valid at the time of issue of this certificate. Updated information is available under www.iqnet-certification.com
Rauscher & Stoecklin AGReuslistrasse 32
4450 SissachSwitzerland
Certified area
Whole company
Field of activity
Electrotechnical components and systems
Certified in accordance with the latest standards
19
ServicesMaintenance
Ourservicesalsoincludeoilanalyses,overhauls,repairs,retrofilling,anddis-posal.
MaintenanceInadditiontomanufacturinghigh-qualityproducts,wealsoof-ferourcustomersproduct-relatedservices,eitheratourcom-panyoron-site.Amongotherthings,thisincludes:
• Consultationandtechnicalsupport• Optimumavailabilityandshortdeliverytimes• Specialdesignsbasedoncustomerrequests
• Transporttotheplaceofuse,installation,and commissioning
• Insulationoilanalysiswithoilsampling• Maintenance,repairs,overhauls,andconversions• Consignmentwarehouse• Cranetransport & integration• Disposal
Transformers from Rauscher & Stoecklin are the right choice.
20
High-current connectorsPlug-inconnectorsandjunctionboxesfrom200A-400Aandupto1,000V
• Tunnelconstruction / mining
• Marineapplications• Infrastructure / transport• Militaryapplications• Buildingsites
Railway switchesOverheadlineswitchesfrom15kVto25kVACandupto2,000A.Ourproductportfolioincludes:
• Loadbreakswitches• Disconnectors• Groundingswitches• Motordrivesand rodlinkages
Distribution TransformersOil-immerseddistributiontransformerswithupto36kVand2.5 MVA(max.3.15 MVA).
• Hermeticallysealedorfree-breathingdesign
• Optionallyavailablewithstepswitch
Power transformersPowertransformerswithupto170kVand125MVA.TestedinaccordancewithIECandGOST
• Stepup / Stepdown• Convertertransformers• Furnacetransformers
3-phase outdoor switches• Outdoorpole-mountedloadbreakswitcheswitharcingchamber
• Outdoorpole-mountedloadbreakswitcheswitharcinghorns
ProductoverviewofRauscher&Stoecklin
Building connection sys-temsUpto400A,suitableforT+TandTV.
• Buildingconnectionsys-tems,surface-mounted
• Buildingconnectionsys-tems,flush-mounted
• Buildingconnectioncolumns
Switchgear systemsLow-voltageswitchandcontrolsystems,testedinaccordancewithEN61439andEN60204.
• Distributionsystems• Testingsystems• Controlsystems• Invertersystems
Cast resin transformersCastresintransformerswithupto52kVand25MVAforvariousapplica-tionssuchas:
• Energydistribution• Industrialapplications• Railwayapplications
21
A company of R&SAninternationalorientedGroup
ThecompaniesofR&Sareunitedbytheirlong-standingexperienceinthepro-ductionofpowerproductsandtheirhungerforprogress.
Foundedin2012,R&Sisaninternationalgroupheadquarte-redinSissach,Switzerlandwithbranchesallovertheworld.
The success of R&S is built on:
• long-standingexperienceoftheassociatedcompaniesintheirrespectiveproductsectors
• ahighlymotivatedandexcellentlytrainedworkforce• productsbasedonproventechnologiesthatgohandinhandwithinnovativeandefficientmanufacturingproces-ses
This results in premium-quality products and the highestpossibledegreeofreliabilityforourcustomers.
Companies of R&S
• Rauscher & Stoecklin:Distributiontransformers, overheadlineswitches,high-currentconnectors
• SERW:High-voltageandmedium-voltageswitchgear• ZREW:Powertransformers• Tesar:Cast-resintransformers,instrumenttransformers
Our branches worldwide
SERW – Czech Republic
ZREW Transformers - Poland
Tesar – Poland
Tesar – Italy
Rauscher & Stoecklin – Switzerland
Tesar – Dubai
R&S Sales Office – Germany
Tesar – UAE
Direct sales by R&S
or partners
R&S Headquarters – Switzerland
Rauscher & StoecklinReuslistrasse324450SissachSwitzerlandinfo@raustoc.chwww.raustoc.ch
SERWTymákovská42,Sedlec33202Starý[email protected]
ZREW Transformersul.Rokicińska14492-412Łódź[email protected]
TesarLoc.Chiaveretto52010Subbiano–[email protected]
Tesar Polskaul.Skarbowa3432-005Niepoł[email protected]
CompaniesoftheR&SGroup
R&S International HoldingReuslistrasse324450SissachSwitzerlandinfo@the-rsgroup.comwww.the-rsgroup.com
Rauscher & Stoecklin AG Reuslistrasse 32, CH-4450 Sissach
T +41 61 976 34 00 F +41 61 976 34 22
[email protected] www.raustoc.ch