Digital TypeProtection Relay
Digital TypeProtection RelayTOYO
139
202
4-M5x18
M4162
10
20 137
139
202
162
4-M5
20 137 30
210
23 4- 6
80
180
122
165
DIMENSIONS
Fixed Type
TDOG - 31 / TDOU - 33
Draw Out Type
TDOG - 31D / TDOU - 33D
PANEL CUT
119
15
17
24
4- 6
I I
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. Dec.2014
WIRING
10114.0
02.0
tpI
t x–
=
(I= If / Is , tp = t >)
SPECIFICATION
61
CONTROLPOWER
TDOG - 31DR S T
K
L
Aux.PowerAC/DC80 - 260V RS 485 COMM.
LCO CO
CO
LCO
Ta
Tc
Oa
Oc
Ea
Ec
E
S
T
T
R
G
N
Pp
PN
U V W
C+
C-
CB Trip Coil
R
S
TDOU - 33R S T
CONTROLPOWERTrip Coil
Aux.PowerAC/DC
V.T
V.T
V.T
Ua Uc
E
Ta Tc Oa Oc
A B
80 - 260V
U V W
Pp PN C
C+ C-RS 485
CB
TDOG - 31 / TDOG - 31D
TDOU - 33 / TDOU - 33D
1015.13
It x
–= tp
101802I
t x–
= tp
tpD =
I I
R S T
CONTROLPOWERTrip Coil
Ta Tc Oa EaOc Ec
G N
TDOG - 31
Pp PN C+ C-RS 485
CB
S TRR S T
CT
AUX. RELAY
E
K
L
U V W
Aux.PowerAC/DC
80 - 260V
B
C
R S T
U V W
RS 485 COMM.
Ta
Tc
Ua
Uc
Oa
Oc
E
CONTROLPOWERTrip Coil
A
Aux.PowerAC/DC80 - 260V
V.T
V.T
V.T
TDOU - 33D
Pp
PN
27
59
C+
C-
CB
59 27
ContactOutput Relay Trip: 1a CO: 1a LCO: 1aTrip Contact Capacity 12A / 250VAC / 28VDCMaking Capacity 30AContact Material Silver Alloy
Indicator (LED)CPU State (Self-diagnostic & monitoring) RUN (Green)Communication Indication COMM (Yellow)Flicker when inputted OC PICKUP (Red)Fault phase / instantaneous R.S.T.N / INST (Red)
MemoryUp to 32 records of fault data with time stamp
RS 485 CommunicationProtocol Modbus Comm. Speed 9600 / 19200 bpsParity None
Vibration Resistance <IEC 60255-21-1>Malfunction 10Hz 5mm double amplitude 30s each in X and Y directions 16.7Hz 2.5mm double amplitude 600s each in X, Y, and Z directions
Shock Resistance <IEC 60255-21-2> Destruction 300m/s² (approx. 30G) 3 times each in 3 directions
Insulation <IEC 60255-5> Dielectric Withstand 2kv for 1 minute between all terminals and case earthInsulation Resistance at 500V > 1,000MΩImpulse Voltage Withstand 5KV-1.2/50μsSurge Transient Simulator 2.5KV 1MHz/200Ω <IEC255-6>Weight 2.2kg
Environmental &EMC Conditions <IEC 61000> Dust & Drop Resistance Front cover with IP42 protection level Option: IP54 protection level (with extra charge)
ModelCO X 3 + LCOTDOG – 31 (Fixed Type with RS485 output)TDOG – 31D (Draw Out Type with RS485 output)
RatingInput AC 5AFrequency 50 / 60 Hz ± 5%Auxiliary Voltage AC / DC 80 ~ 260V Ambient Temperature -10°C / +60°C (without icing)
Current Setting[ CO ]Overcurrent Range 0.2 ~ 25A (0.1A step)Instantaneous Range 5 ~ 120A (1A step)[LCO]Overcurrent Range 0.2 ~ 20A (0.1A step)Instantaneous Range 1 ~ 80A (1A step)Operating Value 100% ( ± 10%)Thermal Withstand 15A / continuous 400A / 1S (80 times the rated input)Time Setting & Curve<IEC 60255-3> CO/LCO Time Lever (tp) 0.1 ~ 40 (0.1 step)Instantaneous 10~40ms (Option: time adjustable version)
Normal Inverse Time
Very Inverse Time
Extremely Inverse Time
Definite Time
Resetting Value > 95%Reset Time < 100ms
BurdenAC CO ≤ 0.5VAAC LCO ≤ 0.5VAAC Aux. Voltage 12VADC Aux. Voltage 6W
CHARACTERISTICSEasy coordination between wiring and receiving point of OCR with only 1 set of relay.With LCD display showing all information about the state of setting and input current value of each phase, also, LED lightsindicating the running state.Selective operating time consists of definite time, normal inverse time, very inverse time, and extremely inverse time. Protective coordination can be harmonized with 1 set of relay, regardless of distributing and receiving line.In case of induction relay, 4 sets of relays were required. But, our relay was structured as integrated type with 3 OCR and 1 OCGR; easy to install, with high accuracy and reliability based on digital system.Detecting faults correctly at the time of short circuit as well. The relay was electronically structured, therefore it works semi-permanently.Password Security preventing unexpected human operationand changing of the setting values.Condenser Tripping Device CTD (optional) is available toensure enough auxiliary power for complete tripping operation.
TIME CURVE: TDOU - 33 / TDOU - 33D
25
(Inverse time)Under voltage relay
LEVER10
5.0
1.0
0.5
0.1
10 20 30 40 50 60 70 80 90100
(%) Voltage
400
300
200
100908070605040
30
20
109876543
2
Sec
10.90.80.70.60.50.4
0.3
0.2
0.10.090.080.070.060.050.04
0.03
0.02
0.01
t= X tp-0.85
(v/100) -12.4
FRONT INFORMATION
LEVER
5.0
10
1.0
0.5
0.1
200180160140120100
(%) Voltage
Sec
200
300
400500600
10090807060504030
20
987654
3
2
10
10.90.80.70.60.50.4
0.3
0.2
0.10.090.080.070.060.050.040.03
0.02
0.01
(Inverse time) Over voltage relay
t= ( + 0.35) x tp12.15
V - 12
(Definite time)Under voltage relay
LEVER1098
6543
2
1
0.5
0.25
0.1
0 40 10060 70 80 90
100
8
70
6
5040
30
20
10
Sec
0.8
0.6
0.4
0.1
0.2
1.0
0.070.060.050.040.03
0.02
0.01
4
2
t=tp
(%) Voltage
(Definite time)
t=tp
Over voltage relay100
8
70
6
50
40
30
20
10
Sec
0.8
0.6
0.4
0.1
0.2
1.0
0.070.060.05
0.01
0.03
0.02
4
2
LEVER
10
0.1
87
5
3
1
0.5
0.3
100 120 140 160 180 200
(%) Voltage
TDOG - 31 / TDOG - 31D
1. 4 X 20 LCD Display State and information display
2. LED Indicator Trip phase and state indication
3. Control Key To set and check the state
4. CPU Reset / Trip Reset To reset CPU / Trip state
TDOU - 33 / TDOU - 33D
1. 4 X 20 LCD Display State and information display
2. LED Indicator Trip phase and state indication
3. Control Key To set and check the state
4. CPU Reset / Trip Reset To reset CPU / Trip state
I I
(tp)
(tp)
(tp)
(tp)
±
SPECIFICATION
TIME CURVE: TDOG - 31 / TDOG - 31D
43
t= x tp– 0.85
(v/100) -12.4
t= ( + 0.35) x tp12.15
V² -1
Normal Inverse
.6 .7.8.9 1 2 3 4 5 6 7 8 9 10 15 20 ( x ls)ls: Setting Value
(s)1000900800700600500
400
300
200
100908070
6050
40
30
20
10987
65
4
3
2
1.00.90.80.70.6
0.5
0.4
0.3
0.2
0.10.090.080.070.060.05
0.04
0.03
0.02
0.01
LEVER
40
30
2015
10
54
3
2
1
0.1
0.5
t= tp
10
0.14
II - 10.02
I= If / Is
If = fault current
(tp)
.6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 15 20 ( x ls)
ls: Setting Value
40
30
20
15
10
54
3
2
1
0.1 ~ 0.5
LEVER
(s)1000900800700600500
400
300
200
100908070
6050
40
30
20
10987
65
4
3
2
1.00.90.80.70.6
0.5
0.4
0.3
0.2
0.10.090.080.070.060.05
0.04
0.03
0.02
0.01
t= 13.5
I - 1tp
10
Very Inverse
(tp)
I= If / Is
If = fault current
40
30
2015
10
54
3
0.1 ~ 2
LEVER
.6 .7.8.9 1 2 3 4 5 6 7 8 9 10 15 20 ( x ls)
ls: Setting Value
(s)
100908070605040
30
20
1098765
4
3
2
1.00.90.80.70.60.50.4
0.3
0.2
0.10.090.080.070.060.050.04
0.03
0.02
0.01
1000900800700600500400
300
200
1500
2000
t= tp
10
80
I - 12
Extremely Inverse
I= If / Is
If = fault current
(tp)
Definite Time
ls: Setting Value
t= tp
8
4
0.1
2
1
0.4
0.2
LEVER
.6 .7 .8.9 1 2 3 4 5 6 7 8 9 10 15 20 ( x ls)
(s)
500
400
300
200
1009080706050
40
30
20
1098765
4
3
2
1.00.90.80.70.60.5
0.4
0.3
0.2
0.1
0.05
I= If / Is
If = fault current
(tp)
ModelOV X 3 + UV X 3TDOU – 33 (Fixed Type with RS485 output)TDOU – 33D (Draw Out Type with RS485 output)
RatingInput AC 110VFrequency 50 / 60 Hz 5%Auxiliary Voltage AC / DC 80 ~ 260V Ambient Temperature -10°C / +60°C (without icing)
Voltage Setting[ OV ] 100 ~ 160V (1V step)[ UV ] 50 ~ 120V (1V step)Instantaneous 20 ~ 90V (1V step)Operating Value 100% ( ± 10%)
Time Setting & Curve<IEC 60255> UV/OV Time Lever (tp) 0.1 ~ 10 (0.1 step)Instantaneous Time < 60ms (Option: time adjustable version)
Reset Time < 100msResetting Value[ OV ] V < 95%[ UV ] V > 105%
UV Inverse Time
OV Inverse Time
UV/OV Definite Time t= tp
Operating Time[ OV ] Inverse or Definite Time[ UV ] Inverse or Definite Time
BurdenAC Voltage ≤ 2.0VAAC Aux. Voltage 12VADC Aux. Voltage 6W
ContactOutput Relay Trip: 1a OV: 1a UV: 1aTrip Contact Capacity 12A / 250VAC / 28VDCMaking Capacity 30AContact Material Silver Alloy
Indicator (LED)CPU State (Self-diagnostic & monitoring) RUN (Green)Communication Indication COMM (Yellow)Flicker when inputted OV/UV PICKUP (Red)Display fault phase/instantaneous AB, BC, CA / OV, UV (Red)
MemoryUp to 32 records of fault data with time stamp
RS 485 CommunicationProtocol Modbus Comm. Speed 9600 / 19200 bpsParity None
Vibration Resistance <IEC 60255-21-1>Malfunction 10Hz 5mm double amplitude 30s each in X and Y directions 16.7Hz 2.5mm double amplitude 600s each in X, Y, and Z directions
Shock Resistance <IEC 60255-21-2> Destruction 300m/s² (approx. 30G) 3 times each in 3 directions
Insulation <IEC 60255-5> Dielectric Withstand 2kv for 1 minute between all terminals and case earthInsulation Resistance at 500V > 1,000MΩImpulse Voltage Withstand 5KV-1.2/50μsSurge Transient Simulator 2.5KV 1MHz/200Ω <IEC255-6>Weight 2.2kg
Environmental &EMC Conditions <IEC 61000> Dust & Drop Resistance Front cover with IP42 protection level Optional IP54 protection level (with extra charge)
CHARACTERISTICSUp to now OVR and UVR relays were separately set and operated, but now they are compacted in one relay unit. Therefore, it is very convenient for handling, too.As assembled with state of the art and multifunction, it is mostsuitable and applicable for protective coordination. Volt meter being installed, it can be used for measuring.Electronic indicator can accurately detect troubles, and surelyindicate electrical troubles.Password Security preventing unexpected human operationand changing of the setting values.Condenser Tripping Device CTD (optional) is available toensure enough auxiliary power for complete tripping operation.
10
20
30
40
±
SPECIFICATION
TIME CURVE: TDOG - 31 / TDOG - 31D
43
t= x tp– 0.85
(v/100) -12.4
t= ( + 0.35) x tp12.15
V² -1
Normal Inverse
.6 .7.8.9 1 2 3 4 5 6 7 8 9 10 15 20 ( x ls)ls: Setting Value
(s)1000900800700600500
400
300
200
100908070
6050
40
30
20
10987
65
4
3
2
1.00.90.80.70.6
0.5
0.4
0.3
0.2
0.10.090.080.070.060.05
0.04
0.03
0.02
0.01
LEVER
40
30
2015
10
54
3
2
1
0.1
0.5
t= tp
10
0.14
II - 10.02
I= If / Is
If = fault current
(tp)
.6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 15 20 ( x ls)
ls: Setting Value
40
30
20
15
10
54
3
2
1
0.1 ~ 0.5
LEVER
(s)1000900800700600500
400
300
200
100908070
6050
40
30
20
10987
65
4
3
2
1.00.90.80.70.6
0.5
0.4
0.3
0.2
0.10.090.080.070.060.05
0.04
0.03
0.02
0.01
t= 13.5
I - 1tp
10
Very Inverse
(tp)
I= If / Is
If = fault current
40
30
2015
10
54
3
0.1 ~ 2
LEVER
.6 .7.8.9 1 2 3 4 5 6 7 8 9 10 15 20 ( x ls)
ls: Setting Value
(s)
100908070605040
30
20
1098765
4
3
2
1.00.90.80.70.60.50.4
0.3
0.2
0.10.090.080.070.060.050.04
0.03
0.02
0.01
1000900800700600500400
300
200
1500
2000
t= tp
10
80
I - 12
Extremely Inverse
I= If / Is
If = fault current
(tp)
Definite Time
ls: Setting Value
t= tp
8
4
0.1
2
1
0.4
0.2
LEVER
.6 .7 .8.9 1 2 3 4 5 6 7 8 9 10 15 20 ( x ls)
(s)
500
400
300
200
1009080706050
40
30
20
1098765
4
3
2
1.00.90.80.70.60.5
0.4
0.3
0.2
0.1
0.05
I= If / Is
If = fault current
(tp)
ModelOV X 3 + UV X 3TDOU – 33 (Fixed Type with RS485 output)TDOU – 33D (Draw Out Type with RS485 output)
RatingInput AC 110VFrequency 50 / 60 Hz 5%Auxiliary Voltage AC / DC 80 ~ 260V Ambient Temperature -10°C / +60°C (without icing)
Voltage Setting[ OV ] 100 ~ 160V (1V step)[ UV ] 50 ~ 120V (1V step)Instantaneous 20 ~ 90V (1V step)Operating Value 100% ( ± 10%)
Time Setting & Curve<IEC 60255> UV/OV Time Lever (tp) 0.1 ~ 10 (0.1 step)Instantaneous Time < 60ms (Option: time adjustable version)
Reset Time < 100msResetting Value[ OV ] V < 95%[ UV ] V > 105%
UV Inverse Time
OV Inverse Time
UV/OV Definite Time t= tp
Operating Time[ OV ] Inverse or Definite Time[ UV ] Inverse or Definite Time
BurdenAC Voltage ≤ 2.0VAAC Aux. Voltage 12VADC Aux. Voltage 6W
ContactOutput Relay Trip: 1a OV: 1a UV: 1aTrip Contact Capacity 12A / 250VAC / 28VDCMaking Capacity 30AContact Material Silver Alloy
Indicator (LED)CPU State (Self-diagnostic & monitoring) RUN (Green)Communication Indication COMM (Yellow)Flicker when inputted OV/UV PICKUP (Red)Display fault phase/instantaneous AB, BC, CA / OV, UV (Red)
MemoryUp to 32 records of fault data with time stamp
RS 485 CommunicationProtocol Modbus Comm. Speed 9600 / 19200 bpsParity None
Vibration Resistance <IEC 60255-21-1>Malfunction 10Hz 5mm double amplitude 30s each in X and Y directions 16.7Hz 2.5mm double amplitude 600s each in X, Y, and Z directions
Shock Resistance <IEC 60255-21-2> Destruction 300m/s² (approx. 30G) 3 times each in 3 directions
Insulation <IEC 60255-5> Dielectric Withstand 2kv for 1 minute between all terminals and case earthInsulation Resistance at 500V > 1,000MΩImpulse Voltage Withstand 5KV-1.2/50μsSurge Transient Simulator 2.5KV 1MHz/200Ω <IEC255-6>Weight 2.2kg
Environmental &EMC Conditions <IEC 61000> Dust & Drop Resistance Front cover with IP42 protection level Optional IP54 protection level (with extra charge)
CHARACTERISTICSUp to now OVR and UVR relays were separately set and operated, but now they are compacted in one relay unit. Therefore, it is very convenient for handling, too.As assembled with state of the art and multifunction, it is mostsuitable and applicable for protective coordination. Volt meter being installed, it can be used for measuring.Electronic indicator can accurately detect troubles, and surelyindicate electrical troubles.Password Security preventing unexpected human operationand changing of the setting values.Condenser Tripping Device CTD (optional) is available toensure enough auxiliary power for complete tripping operation.
10
20
30
40
TIME CURVE: TDOU - 33 / TDOU - 33D
25
(Inverse time)Under voltage relay
LEVER10
5.0
1.0
0.5
0.1
10 20 30 40 50 60 70 80 90100
(%) Voltage
400
300
200
100908070605040
30
20
109876543
2
Sec
10.90.80.70.60.50.4
0.3
0.2
0.10.090.080.070.060.050.04
0.03
0.02
0.01
t= X tp-0.85
(v/100) -12.4
FRONT INFORMATION
LEVER
5.0
10
1.0
0.5
0.1
200180160140120100
(%) Voltage
Sec
200
300
400500600
10090807060504030
20
987654
3
2
10
10.90.80.70.60.50.4
0.3
0.2
0.10.090.080.070.060.050.040.03
0.02
0.01
(Inverse time) Over voltage relay
t= ( + 0.35) x tp12.15
V - 12
(Definite time)Under voltage relay
LEVER1098
6543
2
1
0.5
0.25
0.1
0 40 10060 70 80 90
100
8
70
6
5040
30
20
10
Sec
0.8
0.6
0.4
0.1
0.2
1.0
0.070.060.050.040.03
0.02
0.01
4
2
t=tp
(%) Voltage
(Definite time)
t=tp
Over voltage relay100
8
70
6
50
40
30
20
10
Sec
0.8
0.6
0.4
0.1
0.2
1.0
0.070.060.05
0.01
0.03
0.02
4
2
LEVER
10
0.1
87
5
3
1
0.5
0.3
100 120 140 160 180 200
(%) Voltage
TDOG - 31 / TDOG - 31D
1. 4 X 20 LCD Display State and information display
2. LED Indicator Trip phase and state indication
3. Control Key To set and check the state
4. CPU Reset / Trip Reset To reset CPU / Trip state
TDOU - 33 / TDOU - 33D
1. 4 X 20 LCD Display State and information display
2. LED Indicator Trip phase and state indication
3. Control Key To set and check the state
4. CPU Reset / Trip Reset To reset CPU / Trip state
I I
(tp)
(tp)
(tp)
(tp)
WIRING
10114.0
02.0
tpI
t x–
=
(I= If / Is , tp = t >)
SPECIFICATION
61
CONTROLPOWER
TDOG - 31DR S T
K
L
Aux.PowerAC/DC80 - 260V RS 485 COMM.
LCO CO
CO
LCO
Ta
Tc
Oa
Oc
Ea
Ec
E
S
T
T
R
G
N
Pp
PN
U V W
C+
C-
CB Trip Coil
R
S
TDOU - 33R S T
CONTROLPOWERTrip Coil
Aux.PowerAC/DC
V.T
V.T
V.T
Ua Uc
E
Ta Tc Oa Oc
A B
80 - 260V
U V W
Pp PN C
C+ C-RS 485
CB
TDOG - 31 / TDOG - 31D
TDOU - 33 / TDOU - 33D
1015.13
It x
–= tp
101802I
t x–
= tp
tpD =
I I
R S T
CONTROLPOWERTrip Coil
Ta Tc Oa EaOc Ec
G N
TDOG - 31
Pp PN C+ C-RS 485
CB
S TRR S T
CT
AUX. RELAY
E
K
L
U V W
Aux.PowerAC/DC
80 - 260V
B
C
R S T
U V W
RS 485 COMM.
Ta
Tc
Ua
Uc
Oa
Oc
E
CONTROLPOWERTrip Coil
A
Aux.PowerAC/DC80 - 260V
V.T
V.T
V.T
TDOU - 33D
Pp
PN
27
59
C+
C-
CB
59 27
ContactOutput Relay Trip: 1a CO: 1a LCO: 1aTrip Contact Capacity 12A / 250VAC / 28VDCMaking Capacity 30AContact Material Silver Alloy
Indicator (LED)CPU State (Self-diagnostic & monitoring) RUN (Green)Communication Indication COMM (Yellow)Flicker when inputted OC PICKUP (Red)Fault phase / instantaneous R.S.T.N / INST (Red)
MemoryUp to 32 records of fault data with time stamp
RS 485 CommunicationProtocol Modbus Comm. Speed 9600 / 19200 bpsParity None
Vibration Resistance <IEC 60255-21-1>Malfunction 10Hz 5mm double amplitude 30s each in X and Y directions 16.7Hz 2.5mm double amplitude 600s each in X, Y, and Z directions
Shock Resistance <IEC 60255-21-2> Destruction 300m/s² (approx. 30G) 3 times each in 3 directions
Insulation <IEC 60255-5> Dielectric Withstand 2kv for 1 minute between all terminals and case earthInsulation Resistance at 500V > 1,000MΩImpulse Voltage Withstand 5KV-1.2/50μsSurge Transient Simulator 2.5KV 1MHz/200Ω <IEC255-6>Weight 2.2kg
Environmental &EMC Conditions <IEC 61000> Dust & Drop Resistance Front cover with IP42 protection level Option: IP54 protection level (with extra charge)
ModelCO X 3 + LCOTDOG – 31 (Fixed Type with RS485 output)TDOG – 31D (Draw Out Type with RS485 output)
RatingInput AC 5AFrequency 50 / 60 Hz ± 5%Auxiliary Voltage AC / DC 80 ~ 260V Ambient Temperature -10°C / +60°C (without icing)
Current Setting[ CO ]Overcurrent Range 0.2 ~ 25A (0.1A step)Instantaneous Range 5 ~ 120A (1A step)[LCO]Overcurrent Range 0.2 ~ 20A (0.1A step)Instantaneous Range 1 ~ 80A (1A step)Operating Value 100% ( ± 10%)Thermal Withstand 15A / continuous 400A / 1S (80 times the rated input)Time Setting & Curve<IEC 60255-3> CO/LCO Time Lever (tp) 0.1 ~ 40 (0.1 step)Instantaneous 10~40ms (Option: time adjustable version)
Normal Inverse Time
Very Inverse Time
Extremely Inverse Time
Definite Time
Resetting Value > 95%Reset Time < 100ms
BurdenAC CO ≤ 0.5VAAC LCO ≤ 0.5VAAC Aux. Voltage 12VADC Aux. Voltage 6W
CHARACTERISTICSEasy coordination between wiring and receiving point of OCR with only 1 set of relay.With LCD display showing all information about the state of setting and input current value of each phase, also, LED lightsindicating the running state.Selective operating time consists of definite time, normal inverse time, very inverse time, and extremely inverse time. Protective coordination can be harmonized with 1 set of relay, regardless of distributing and receiving line.In case of induction relay, 4 sets of relays were required. But, our relay was structured as integrated type with 3 OCR and 1 OCGR; easy to install, with high accuracy and reliability based on digital system.Detecting faults correctly at the time of short circuit as well. The relay was electronically structured, therefore it works semi-permanently.Password Security preventing unexpected human operationand changing of the setting values.Condenser Tripping Device CTD (optional) is available toensure enough auxiliary power for complete tripping operation.
Digital TypeProtection Relay
Digital TypeProtection RelayTOYO
13920
2
4-M5x18
M4162
10
20 137
139
202
162
4-M5
20 137 30
210
23 4- 6
80
180
122
165
DIMENSIONS
Fixed Type
TDOG - 31 / TDOU - 33
Draw Out Type
TDOG - 31D / TDOU - 33D
PANEL CUT
119
15
17
24
4- 6
I I
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. Dec.2014
Top Related