DCLG Final Research Report Effectiveness of sprinklers in residential premises – an evaluation of concealed and recessed pattern sprinkler products Section 3: Stylised fires (Appendices 3A and 3B) K Annable, P Clark, C Williams and P Rock 218113
The authors of this report are employed by BRE. The work reported herein was carried out under a Contract placed by the DCLG. Any views expressed are not necessarily those of the DCLG.
March 2006
Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Contents
Appendix 3A – Water distribution measurements Appendix 3B – Observations and graphs
1 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Appendix 3A – Water distribution measurements
Figure 3A.1 shows a schematic plan view of the test facility and the set up for the water distribution tests. An array of 24 collection containers was positioned to cover a quadrant area, numbered 1 to 24. Two quadrant areas were utilised, either quadrant 1 or quadrant 2. An additional four containers were positioned close to the wall of the test facility, numbered 25 to 28, either related to quadrant 1 or quadrant 2. Notes for Figure 3A.2 to Figure 3A.25.
1. The double ended arrow on the three dimensional bar chart denotes the sprinkler frame arm orientation. The position of the sprinkler is at the midpoint of the arrow.
2. The two dimensional bar chart shows the water coverage measured in containers 25, 26, 27 and 28.
3. The scales for each bar chart have been kept constant for a set of comparable water distributions, i.e. with the same sprinkler, water flow rate, recess distance and frame arm orientation.
218113 ©
Building R
esearch Establishm
ent Ltd 2006
2 S
ection 3: Stylised fires (Appendices 3A and 3B
)
123456
789101112
131415161718
192021222324
25262728
1 2 3 4 5 6
7 8 9 10 11 12
13 14 15 16 17 18
19 20 21 22 23 24
2825 26 27
Quadrant 2 arrangement
Nominal 12 mm gap between containers and test facility wall
Nominal 12 mm gap between containers and test facility wall
Sprinkler (nominally 2350 mm abovecontainers and 2000 mm from wall)
4000 mm
8000 mm
Containers
Quadrant 1 arrangement
Figure 3A.1 – Plan view of test facility showing container arrangements for water distribution measurements
218113 ©
Building R
esearch Establishm
ent Ltd 2006
3 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
01
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (m
m)
Horizontal distance from sprinkler (mm)
25 26 27 280
1
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Location
Quadrant 1 (see Figure 3A.1 ) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) 1 2.88 7 2.28 13 2.16 19 2.64 25 3.93
2 5.47 8 1.77 14 1.28 20 1.40 26 3.78
3 4.67 9 1.61 15 0.93 21 1.12 27 6.08
4 3.14 10 1.84 16 1.13 22 1.08 28 5.57
5 2.37 11 1.92 17 1.78 23 1.11
6 1.94 12 1.76 18 2.31 24 1.48
Figure 3A.2 – Water distribution for sprinkler AP(k71) at a water flow rate of 64 litres/min
218113 ©
Building R
esearch Establishm
ent Ltd 2006
4 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
0
1
2
3
4
5
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (m
m)
Horizontal distance from sprinkler (mm)
25 26 27 280
1
2
3
4
5
Cov
erag
e (m
m/m
in)
Location
Quadrant 1 (see Figure 3A.1) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage (mm/min)
1 1.62 7 1.44 13 1.22 19 1.66 25 4.53
2 3.52 8 1.25 14 0.84 20 0.83 26 3.21
3 2.14 9 1.14 15 0.64 21 0.78 27 4.07
4 1.55 10 1.30 16 0.72 22 0.72 28 4.57
5 1.26 11 1.57 17 1.16 23 0.82
6 1.28 12 1.70 18 2.04 24 1.11
Figure 3A.3 – Water distribution for sprinkler AP (k71) at a water flow rate of 50.2 litres/min
218113 ©
Building R
esearch Establishm
ent Ltd 2006
5 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
0123456789101112
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (m
m)
Horizontal distance from sprinkler (mm)
25 26 27 280
1
2
3
4
5
6
7
8
9
10
11
12
Cov
erag
e (m
m/m
in)
Location
Quadrant 1 (see Figure 3A.1) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage (mm/min)
1 1.33 7 1.87 13 3.57 19 2.59 25 7.82
2 1.26 8 2.12 14 3.34 20 2.48 26 6.25
3 7.21 9 4.28 15 2.94 21 2.12 27 5.40
4 5.00 10 1.53 16 1.74 22 1.76 28 3.86
5 1.98 11 0.75 17 1.17 23 1.49
6 1.61 12 0.55 18 0.78 24 1.38
Figure 3A.4 – Water distribution for sprinkler BR (k62) at a water flow rate of 64 litres/min
218113 ©
Building R
esearch Establishm
ent Ltd 2006
6 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
0123456789101112
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (m
m)
Horizontal distance from sprinkler (mm)
25 26 27 280
1
2
3
4
5
6
7
8
9
10
11
12
Cov
erag
e (m
m/m
in)
Location
Quadrant 2 (see Figure 3A.1) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage (mm/min)
1 1.50 7 3.23 13 4.29 19 2.38 25 4.49
2 1.75 8 2.51 14 3.21 20 2.14 26 3.41
3 11.07 9 8.62 15 3.62 21 1.99 27 3.98
4 7.44 10 3.78 16 3.64 22 2.31 28 3.22
5 2.60 11 1.30 17 2.05 23 1.99
6 2.10 12 1.32 18 1.22 24 1.78
Figure 3A.5 – Water distribution for sprinkler BR (k62) at a water flow rate of 64 litres/min
218113 ©
Building R
esearch Establishm
ent Ltd 2006
7 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
0123456789101112131415
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (
mm)
Horizontal distance from sprinkler (mm)
25 26 27 280123456789
101112131415
Cov
erag
e (m
m/m
in)
Location
Quadrant 1 (see Figure 3A.1) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage (mm/min)
1 0.95 7 1.43 13 1.49 19 1.28 25 5.81
2 1.47 8 1.65 14 1.37 20 1.30 26 4.32
3 4.87 9 1.56 15 1.20 21 1.38 27 4.46
4 1.86 10 0.68 16 0.92 22 1.22 28 3.19
5 1.33 11 0.53 17 0.79 23 1.18
6 1.19 12 0.45 18 0.71 24 1.25
Figure 3A.6 – Water distribution for sprinkler BR (k62) at a water flow rate of 49.2 litres/min
218113 ©
Building R
esearch Establishm
ent Ltd 2006
8 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
0123456789101112131415
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (m
m)
Horizontal distance from sprinkler (mm)
25 26 27 280123456789
101112131415
Cov
erag
e (m
m/m
in)
Location
Quadrant 2 (see Figure 3A.1) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage (mm/min)
1 0.95 7 2.18 13 2.02 19 1.54 25 3.13
2 2.83 8 3.40 14 1.79 20 1.17 26 2.67
3 14.72 9 5.58 15 1.91 21 1.01 27 3.20
4 4.05 10 1.46 16 1.33 22 1.01 28 2.40
5 1.82 11 0.79 17 0.77 23 0.80
6 1.83 12 0.93 18 0.88 24 1.00
Figure 3A.7 – Water distribution for sprinkler BR (k62) at a water flow rate of 49.2 litres/min
218113 ©
Building R
esearch Establishm
ent Ltd 2006
9 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
01
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (m
m)
Horizontal distance from sprinkler (mm)
25 26 27 280
1
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Location
Quadrant 1 (see Figure 3A.1) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) 1 2.37 7 2.54 13 3.62 19 3.43 25 5.26
2 3.76 8 2.06 14 2.28 20 2.91 26 6.13
3 3.36 9 2.04 15 1.59 21 2.06 27 5.88
4 2.56 10 2.26 16 1.40 22 1.57 28 5.99
5 2.02 11 2.80 17 1.52 23 1.62
6 1.75 12 2.87 18 2.35 24 1.44
Figure 3A.8 – Water distribution for sprinkler CC (k70) at a water flow rate of 64 litres/min
218113 ©
Building R
esearch Establishm
ent Ltd 2006
10 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
01
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (m
m)
Horizontal distance from sprinkler (mm)
25 26 27 280
1
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Location
Quadrant 2 (see Figure 3A.1) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) 1 2.62 7 4.77 13 5.08 19 4.23 25 3.93
2 6.07 8 4.11 14 3.99 20 4.00 26 4.69
3 4.87 9 2.78 15 2.81 21 3.00 27 5.07
4 3.72 10 2.32 16 1.69 22 2.33 28 5.79
5 3.10 11 3.14 17 1.43 23 1.79
6 2.80 12 3.71 18 2.42 24 1.26
Figure 3A.9 – Water distribution for sprinkler CC (k70) at a water flow rate of 64 litres/min
218113 ©
Building R
esearch Establishm
ent Ltd 2006
11 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
01234
5
6
7
8
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (m
m)
Horizontal distance from sprinkler (mm)
25 26 27 280
1
2
3
4
5
6
7
8
Cov
erag
e (m
m/m
in)
Location
Quadrant 1 (see Figure 3A.1) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) 1 0.44 7 0.49 13 0.63 19 1.19 25 6.16
2 0.41 8 0.50 14 0.64 20 1.25 26 6.72
3 0.61 9 0.77 15 0.89 21 1.20 27 7.28
4 0.72 10 1.00 16 1.16 22 1.52 28 6.04
5 0.66 11 1.01 17 1.07 23 1.55
6 0.66 12 1.10 18 1.12 24 1.39
Figure 3A.10 – Water distribution for sprinkler DC (k60.5) at a water flow rate of 64 litres/min
218113 ©
Building R
esearch Establishm
ent Ltd 2006
12 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
01234
5
6
7
8
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (
mm)
Horizontal distance from sprinkler (mm)
25 26 27 280
1
2
3
4
5
6
7
8
Cov
erag
e (m
m/m
in)
Location
Quadrant 2 (see Figure 3A.1) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) 1 0.71 7 0.75 13 1.08 19 1.21 25 6.52
2 0.82 8 0.88 14 0.85 20 1.31 26 5.57
3 1.23 9 1.67 15 0.99 21 1.46 27 6.69
4 0.88 10 1.22 16 1.13 22 1.69 28 6.02
5 0.82 11 1.09 17 1.17 23 1.72
6 1.03 12 1.72 18 2.41 24 2.25
Figure 3A.11 – Water distribution for sprinkler DC (k60.5) at a water flow rate of 64 litres/min
218113 ©
Building R
esearch Establishm
ent Ltd 2006
13 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
01
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (m
m)
Horizontal distance from sprinkler (mm)
25 26 27 280
1
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Location
Quadrant 1 (see Figure 3A.1) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) 1 2.59 7 3.69 13 3.78 19 3.74 25 5.88
2 2.53 8 3.24 14 3.20 20 3.60 26 5.39
3 2.38 9 3.19 15 3.00 21 2.99 27 4.57
4 1.85 10 3.28 16 3.01 22 2.39 28 3.60
5 1.63 11 3.65 17 3.34 23 2.04
6 1.60 12 3.00 18 3.28 24 1.83
Figure 3A.12 – Water distribution for sprinkler EC (k71) at a water flow rate of 64 litres/min
218113 ©
Building R
esearch Establishm
ent Ltd 2006
14 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
01
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (m
m)
Horizontal distance from sprinkler (mm)
25 26 27 280
1
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Location
Quadrant 1 (see Figure 3A.1) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) 1 1.94 7 3.26 13 2.91 19 2.34 25 3.93
2 2.33 8 2.40 14 2.48 20 2.23 26 4.54
3 2.70 9 1.96 15 1.66 21 2.09 27 3.81
4 2.22 10 1.77 16 1.18 22 1.57 28 2.78
5 2.23 11 2.11 17 1.27 23 1.21
6 2.12 12 2.41 18 1.54 24 0.98
Figure 3A.13 – Water distribution for sprinkler EC (k71) at a water flow rate of 64 litres/min
218113 ©
Building R
esearch Establishm
ent Ltd 2006
15 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
01
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (m
m)
Horizontal distance from sprinkler (mm)
25 26 27 280
1
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Location
Quadrant 2 (see Figure 3A.1) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage (mm/min)
1 2.50 7 3.46 13 3.69 19 3.37 25 5.14
2 2.28 8 3.71 14 3.51 20 3.08 26 5.28
3 2.08 9 3.04 15 3.44 21 3.16 27 4.27
4 1.34 10 1.85 16 2.70 22 2.46 28 3.39
5 1.39 11 1.51 17 2.37 23 2.30
6 1.85 12 2.00 18 2.10 24 2.38
Figure 3A.14 – Water distribution for sprinkler EC (k71) at a water flow rate of 64 litres/min
218113 ©
Building R
esearch Establishm
ent Ltd 2006
16 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
01
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (m
m)
Horizontal distance from sprinkler (mm)
25 26 27 280
1
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Location
Quadrant 2 (see Figure 3A.1) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) 1 2.65 7 4.36 13 4.33 19 3.85 25 6.66
2 2.67 8 4.10 14 4.90 20 4.69 26 7.06
3 2.87 9 4.06 15 4.63 21 4.43 27 5.87
4 2.23 10 3.06 16 3.96 22 3.65 28 4.42
5 2.01 11 2.63 17 3.29 23 2.90
6 2.53 12 2.37 18 2.80 24 2.37
Figure 3A.15 – Water distribution for sprinkler EC (k71) at a water flow rate of 64 litres/min
218113 ©
Building R
esearch Establishm
ent Ltd 2006
17 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
0
1
2
3
4
5
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (m
m)
Horizontal distance from sprinkler (mm)
25 26 27 280
1
2
3
4
5
Cov
erag
e (m
m/m
in)
Location
Quadrant 1 (see Figure 3A.1) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) 1 1.55 7 2.72 13 3.27 19 3.44 25 5.01
2 1.54 8 2.83 14 3.68 20 3.53 26 4.80
3 1.54 9 2.66 15 3.44 21 3.36 27 3.89
4 1.48 10 2.57 16 3.17 22 2.85 28 2.45
5 1.68 11 2.35 17 3.04 23 2.50
6 2.36 12 1.63 18 2.64 24 1.89
Figure 3A.16 – Water distribution for sprinkler EC (k71) at a water flow rate of 50.2 litres/min
218113 ©
Building R
esearch Establishm
ent Ltd 2006
18 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
0
1
2
3
4
5
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (m
m)
Horizontal distance from sprinkler (mm)
25 26 27 280
1
2
3
4
5
Cov
erag
e (m
m/m
in)
Location
Quadrant 2 (see Figure 3A.1) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) 1 1.89 7 3.11 13 3.32 19 3.01 25 3.58
2 2.93 8 2.84 14 2.55 20 2.87 26 3.77
3 3.23 9 2.78 15 2.51 21 2.68 27 2.82
4 3.56 10 3.23 16 2.36 22 2.56 28 1.86
5 3.76 11 3.35 17 2.12 23 1.71
6 3.86 12 2.27 18 1.99 24 1.02
Figure 3A.17 – Water distribution for sprinkler EC (k71) at a water flow rate of 50.2 litres/min
218113 ©
Building R
esearch Establishm
ent Ltd 2006
19 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
0
1
2
3
4
5
6
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (
mm)
Horizontal distance from sprinkler (mm)
25 26 27 280
1
2
3
4
5
6
Cov
erag
e (m
m/m
in)
Location
Quadrant 1 (see Figure 3A.1) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) 1 1.58 7 2.13 13 2.02 19 1.88 25 4.34
2 1.92 8 2.15 14 1.85 20 1.72 26 4.17
3 3.36 9 2.70 15 1.84 21 1.73 27 3.00
4 2.27 10 2.11 16 1.52 22 1.62 28 3.14
5 2.25 11 1.89 17 1.54 23 1.42
6 2.32 12 1.90 18 1.57 24 1.41
Figure 3A.18 – Water distribution for sprinkler EC (k71) at a water flow rate of 64 litres/min
218113 ©
Building R
esearch Establishm
ent Ltd 2006
20 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
0
1
2
3
4
5
6
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (
mm)
Horizontal distance from sprinkler (mm)
25 26 27 280
1
2
3
4
5
6
Cov
erag
e (m
m/m
in)
Location
Quadrant 2 (see Figure 3A.1) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) 1 1.57 7 2.54 13 4.34 19 4.98 25 5.86
2 2.04 8 3.34 14 2.15 20 2.41 26 4.34
3 3.53 9 4.73 15 2.38 21 1.69 27 3.78
4 4.39 10 2.61 16 1.72 22 1.65 28 4.31
5 2.38 11 1.72 17 1.07 23 1.25
6 2.39 12 1.89 18 1.55 24 1.53
Figure 3A.19 – Water distribution for sprinkler EC (k71) at a water flow rate of 64 litres/min
218113 ©
Building R
esearch Establishm
ent Ltd 2006
21 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
01
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (
mm)
Horizontal distance from sprinkler (mm)
25 26 27 280
1
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Location
Quadrant 1 (see Figure 3A.1) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) 1 1.94 7 1.88 13 1.85 19 1.89 25 4.58
2 2.62 8 2.42 14 2.17 20 2.24 26 3.87
3 2.72 9 2.26 15 2.38 21 2.80 27 2.59
4 2.50 10 2.07 16 1.98 22 2.63 28 4.86
5 2.47 11 1.75 17 1.82 23 2.30
6 2.57 12 1.48 18 1.86 24 2.31
Figure 3A.20 – Water distribution for sprinkler EC (k71) at a water flow rate of 64 litres/min
218113 ©
Building R
esearch Establishm
ent Ltd 2006
22 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
01
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (m
m)
Horizontal distance from sprinkler (mm)
25 26 27 280
1
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Location
Quadrant 2 (see Figure 3A.1) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) 1 2.58 7 3.20 13 3.78 19 3.84 25 6.52
2 2.99 8 2.81 14 2.69 20 3.06 26 4.84
3 3.25 9 2.72 15 2.15 21 2.32 27 2.43
4 3.32 10 3.02 16 1.94 22 1.98 28 3.22
5 3.34 11 3.68 17 2.11 23 2.03
6 3.20 12 3.65 18 2.70 24 2.00
Figure 3A.21 – Water distribution for sprinkler EC (k71) at a water flow rate of 64 litres/min
218113 ©
Building R
esearch Establishm
ent Ltd 2006
23 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
01
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (m
m)
Horizontal distance from sprinkler (mm)
25 26 27 280
1
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Location
Quadrant 1 (see Figure 3A.1) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) 1 2.21 7 3.96 13 2.42 19 1.67 25 3.84
2 2.61 8 4.13 14 2.47 20 2.38 26 4.55
3 4.39 9 2.96 15 2.27 21 1.81 27 2.83
4 2.03 10 2.09 16 2.53 22 1.82 28 2.41
5 1.51 11 1.58 17 1.75 23 2.20
6 1.34 12 1.55 18 1.23 24 1.55
Figure 3A.22 – Water distribution for sprinkler FC (k59) at a water flow rate of 64 litres/min
218113 ©
Building R
esearch Establishm
ent Ltd 2006
24 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
01
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (m
m)
Horizontal distance from sprinkler (mm)
25 26 27 280
1
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Location
Quadrant 2 (see Figure 3A.1) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) 1 3.20 7 5.62 13 4.50 19 2.47 25 4.00
2 2.56 8 5.07 14 4.82 20 3.37 26 6.92
3 2.48 9 6.74 15 5.14 21 4.26 27 5.41
4 2.03 10 3.26 16 4.49 22 2.70 28 3.63
5 1.71 11 2.01 17 2.94 23 2.75
6 2.23 12 1.91 18 1.98 24 2.41
Figure 3A.23 – Water distribution for sprinkler FC (k59) at a water flow rate of 64 litres/min
218113 ©
Building R
esearch Establishm
ent Ltd 2006
25 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
01
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (
mm)
Horizontal distance from sprinkler (mm)
25 26 27 280
1
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Location
Quadrant 1 (see Figure 3A.1) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) 1 2.94 7 3.71 13 2.07 19 1.60 25 3.66
2 2.98 8 3.64 14 2.37 20 2.45 26 4.47
3 2.65 9 2.78 15 2.23 21 1.80 27 2.54
4 1.69 10 2.03 16 2.55 22 2.00 28 2.73
5 1.30 11 1.71 17 1.75 23 2.44
6 1.21 12 1.53 18 1.48 24 1.56
Figure 3A.24 – Water distribution for sprinkler FC (k59) at a water flow rate of 60.6 litres/min
218113 ©
Building R
esearch Establishm
ent Ltd 2006
26 S
ection 3: Stylised fires (Appendices 3A and 3B
)
0
400
800
1200
1600
0300
600900
12001500
1800
01
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Horizo
ntal d
istan
ce fro
m sprin
kler (m
m)
Horizontal distance from sprinkler (mm)
25 26 27 280
1
2
3
4
5
6
7
Cov
erag
e (m
m/m
in)
Location
Quadrant 2 (see Figure 3A.1) 12 mm from wall (see Figure 3A.1)
Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) Location Coverage (mm/min) Location Coverage
(mm/min) 1 2.47 7 4.79 13 4.44 19 2.66 25 4.58
2 2.17 8 4.73 14 4.70 20 3.84 26 6.60
3 2.75 9 6.03 15 4.41 21 3.79 27 4.55
4 1.96 10 3.16 16 3.84 22 2.60 28 3.55
5 1.58 11 1.97 17 2.84 23 2.49
6 2.42 12 1.90 18 1.77 24 2.37
Figure 3A.25 – Water distribution for sprinkler FC (k59) at a water flow rate of 60.6 litres/min
27 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Appendix 3B – Observations and graphs
Test details Test name – number Stylised fires - Test 1 Filename for temperatures JAN0505 Filename for water flow rate CRSTest 1 Test date 5/1/05 Test personnel KA, RH, CW, PR, DS
Test parameters Fire scenario Corner test Sprinkler model Sprinkler AP (k71) 680C glass bulb Sprinkler type Pendent Sprinkler orientation Parallel to the long length of the test
room Water flow rate for one sprinkler 64 l/min Water flow rate for two sprinklers 100.4 l/min Sprinkler spacing 4 m Room size 8 m by 4 m Lintel No lintel
Prior to test Relative humidity 55.3% inside test room Temperature 12.90C inside test room Moisture content of 2 crib sticks 3mm below surface
10.0%, 9.9%
Weight of wood crib Not weighed
Photographs of fuel arrangement Yes Extract started Yes, 10m3/s free burn Stopwatches started -3:00 Pump on -2:00 Temperature logging started -2:00 Video camera started -2:00 Flow meter logging started -1:00
28 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test observations Observation Time (min: sec) Ignition 0:00 First sprinkler operated (sprinkler 1) 1:02 Buoyant smoke layer, clear air below 1:40 Smoke logging and flames 2:20 Fire diminished 2:44 Flame observed 3:36 Small flame 7:42 Visibility lost 8:00 Second sprinkler operated Did not operate Dummy sprinkler operated Did not operate End of test and sprinkler(s) off 11:02 (10 mins post sprinkler operation) Fire extinguished manually No, fire appeared to be already out
after sprinkler system was turned off Post fire observations
Amount of fire damage See photos
No damage to plywood wall panels Wood crib sticks still mainly unburnt
Foam almost completely burnt out
Wetting pattern Not clear
29 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test details Test name - number Stylised fires - Test 2 Filename for temperatures JAN0705 Filename for water flow rate CRSTest2 Test date 7/01/05 Test personnel CW, RH, KA, PR, DS
Test parameters Fire scenario Wall test Sprinkler model Sprinkler AP (k71) 680C glass bulb Sprinkler type Pendent Sprinkler orientation Parallel with long length of test room Water flow rate for one sprinkler 64 l/min Water flow rate for two sprinklers 100.4 l/min Sprinkler spacing 4 m Room size 8 m by 4 m Lintel No lintel
Prior to test Relative humidity 69.1% in test room, 71% in Burn Hall Temperature 13.90C in test room, 12.90C in Burn Hall Moisture content of 2 crib sticks 3mm below surface
9.9%, 9.1%
Weight of wood crib 7544g (32 sticks) Photographs of fuel arrangement Yes Extract started Yes, 15m3/s free burn Stopwatches started -03:00 Pump on -02:00 Temperature logging started -02:00 Video camera started -02:00 Flow meter logging started -01:00
Test observations Observation Time (min: sec) Ignition 0:00 First sprinkler operated (sprinkler 1) 1:45 Second sprinkler operated (sprinkler 2)
1:53
Foam fire extinguished by sprinklers Crib initially burning as unsprinklered
1:52
Crib still continued to burn vigorously 2:14 Crib burning but flames just below level of plywood stands
3:42
30 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Room relatively clear of smoke, grey wood smoke observed
5:10
Dummy sprinkler operated Did not operate End of test and sprinkler(s) off 11:45 (10 minutes after first sprinkler
operation) Fire manually extinguished Yes, manual extinction at 11:45
Post fire observations Amount of fire damage See photos
Foam (left hand side) burnt to plywood backing board vertically above brick. Bottom right hand corner nearest plywood wall unburnt. Graduated burn across foam sample.
Foam (right hand side) very similar to left hand side, slightly less foam burnt.
Wood crib sticks mainly unburnt, some charring on top layer Plywood panels unscorched
Wetting pattern Not clear, water sprays discharged outside the door at both ends
Test 3 was deemed to be a void test.
31 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test details Test name - number Stylised fires - Test 4 Filename for temperatures Jan1805 Filename for water flow rate CRSTest4 Test date 18/1/05 Test personnel CW, KA, PC, PR, RH
Test parameters Fire scenario Corner test Sprinkler model Sprinkler BR (k62) glass bulb 680C Sprinkler type Recessed Depth of recess Maximum Sprinkler orientation Parallel long length of the test room Water flow rate for one sprinkler 64 l/min Water flow rate for two sprinklers 98.4 l/min Sprinkler spacing 4 m Room size 8 m by 4 m Lintel No lintel
Prior to test Relative humidity 57% in test room 64.2% in Burn Hall Temperature 11oC in test room, 8.9oC in Burn hall Moisture content 3mm below surface 10.1%, 9.8% Weight of wood crib 7349.0g Photographs of fuel arrangement Yes Extract started and mode and flow Yes, 15 m3/s free burn Pump on and air bled Yes Stopwatches started -03:00 Temperature logging started -03:00 Video camera started -02:00 Flow meter logging started -01:00
Test observations Observation Time (min: sec) Ignition 0:00 First sprinkler operated (sprinkler 1) 1:04 Appears same as unsprinklered 1:16/1:27 Foam and crib still burning 2:00 Crib burning well 3:30 Smoke logging, crib flames just above plywood stands, charring on walls
4:00
Lots of grey/white smoke from crib 8:00 Second sprinkler operated Did not operate Dummy sprinkler operated Did not operate End of test and sprinkler(s) off 11:04 (10 mins after first sprinkler
32 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
operated) Fire manually extinguished Yes, wood burning at end of test. Fire
‘picked up’ after sprinkler switched off. Post fire observations
Amount of fire damage See photos
Foam virtually entirely burnt away on both boards
Plywood was scorched but did not ignite Scorching on plywood above/next to foam on short wall
Scorching on plywood above crib, shorter on short wall than on long wall. Crib sticks look more burnt/charred than in previous tests.
Wetting pattern See photo Water line appeared very close to ceiling on plywood.
33 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test details Test name – number Stylised fires – Test 5 Filename for temperatures Jan2005 Filename for water flow rate CRSTest5 Test date 20/1/05 Test personnel CW, KA, PR, JS
Test parameters Fire scenario Wall test Sprinkler model Sprinkler BR (k62) glass bulb 680C Sprinkler type Recessed Recess depth details Same as Test 4 (maximum) Sprinkler orientation Parallel to the long length of test room Water flow rate for one sprinkler 64 l/min Water flow rate for two sprinklers 98.4 l/min Sprinkler spacing 4 m Room size 8 m by 4 m Lintel No lintel
Prior to test Relative humidity 74% in test room, 81.4% in Burn Hall Temperature 13.10C in test room, 11.40C in Burn Hall Moisture content 3mm below surface 10.0%, 10.0% Weight of wood crib 7634.0g Photographs of fuel arrangement Yes Pump on and air bled Yes Extract started and mode and flow Yes, 15 m3/s, free burn Stopwatches started -03:00 Temperature logging started -02:00 Video camera started -02:00 Flow meter logging started -01:00
Test observations Observation Time (min: sec) Ignition 0:00 First sprinkler operated (sprinkler 1) 1:48 Second sprinkler operated (sprinkler 2)
1:55
Dummy sprinkler operated Did not operate Crib still burning vigorously. Small flames near brick on left side
2:20-3:30
Flames to just above height of stands 3:43 Smoke to ground level near doorway 4:40 Small flame on foam edge 4:50-9:30 Visibility lost 9:30
34 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
End of test and sprinkler(s) off 11:48 (10 mins after first sprinkler operated)
Fire manually extinguished Yes, bottom left hand corner of foam alight
Post fire observations Amount of fire damage See photos
No damage to plywood walls
Charring through to top layer of wood crib
Foam on left hand side entirely burnt away above brick. A small amount of foam unburnt in bottom corner and a gradual burn to plywood.
Foam on right hand side entirely burnt away above brick. A small amount of foam unburnt in bottom corner and a gradual burn to plywood. Slightly less fire damage than left hand side.
35 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test details Test name – number Stylised fires - Test 6 Filename for temperatures CRSTest6 Filename for water flow rate Jan2105 Test date 21/1/05 Personnel RH, JS, KA, PR, CW
Test Parameters Fire scenario Corner test Sprinkler model Sprinkler CC (k70) domed cup, glass
bulb Sprinkler type Concealed Deflector plate depth 8 to 9 mm depth below ceiling Concealed depth Sprinklers were installed as close to
possible to their manufacturer’s maximum allowable recess distance, i.e. with sprinkler cup assembly approximately 12.7 mm above ceiling level
Sprinkler orientation Parallel to the long length of test room Water flow rate for one sprinkler 64 l/min Water flow rate for two sprinklers 99 l/min Sprinkler spacing 4 m Room size 8 m by 4 m Lintel No lintel
Prior to test Relative humidity 47.8% in test room, 48.1% in Burn Hall Temperature 140C in test room, 11.10C in Burn Hall Moisture content of 2 crib sticks 3mm below surface
9.9%, 9.8%
Weight of wood crib 7476g Photographs of fuel arrangement Yes Extract started and mode and flow Yes 15 m3/s, free burn Stopwatches started -3:00 Pump on -2:00 Temperature logging started -2:00 Video camera started -1:00 Flow meter logging started -2:00
Test observations Observation Time (min: sec) Ignition 0:00 First sprinkler cap operated 0:58 First sprinkler operated (sprinkler 1) 1:12
36 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Flames from crib and foam 1:20 Charring of plywood 1:39 Smoke layer above plywood stands, flames to bottom of layer on foam and crib
2:00
Crib still burning 2:35 Fire still burning although diminished 2:45 Crib burning vigorously and part of foam in corner near wall
3:08
Smoke logging, fire dying down 3:40 Smoke logged, fire appears to be extinguished
4:20
Second sprinkler operated Did not operate Second sprinkler cap operated Did not appear to operate although
heard “click” at 2:58 Dummy sprinkler operated Did not operate End of test and sprinkler(s) off 11:12 (10 minutes after first sprinkler) Fire extinguished manually No, fire already out, extinguished by
sprinklers Post fire observations
Very small amount of charring on plywood on short wall above foam location. No charring on plywood due to wood crib
Small amount of charring on sticks on top layer of crib (less than in some previous tests). Small amount of charring on plywood on long wall
37 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Foam almost entirely burnt out
Test details Test name – number Stylised fires - Test 7 Filename for temperatures Jan2405 Filename for water flow rate CRSTest7 Test date 24/1/05 Personnel PC, KA, JS, PR, CW
Test parameters Fire scenario Corner test Sprinkler model and details Sprinkler DC (k60.5) flat plate, solder,
vented, 570C/680C Sprinkler type Concealed Deflector plate depth below ceiling Not known Concealed depth Maximum recess distance, i.e. with
sprinkler cup assembly approx.12.7 mm above ceiling level
Sprinkler orientation Parallel to the long length of test room Water flow rate for one sprinkler 64 l/min Water flow rate for two sprinklers 106 l/min Sprinkler spacing 4 m Room size 8 m by 4 m Lintel No lintel
Prior to test Relative humidity 66.2% in test room, 66.1% in Burn Hall Temperature 10.50C in test room, 6.10C in Burn Hall Moisture content of 2 crib sticks 3mm below surface
8.5%, 8.5%
Weight of wood crib 7340.5g Photographs of fuel arrangement Yes Pump on and air bled Yes Extract started and mode and flow Yes, 15 m3/s free burn Stopwatches started -3:00 Temperature logging started -2:00 Video camera started -2:00 Flow meter logging started -1:00
Test observations Observation Time (min: sec) Ignition 0:00 First sprinkler concealer plate fell 0:59 First sprinkler operated 1:17 Second sprinkler concealer plate fell 1:23
38 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Second sprinkler operated Did not operate Dummy sprinkler operated Did not operate Dummy sprinkler concealer plate fell 1:29 Smoke logged and crib flames visible, just above plywood stands
1:37
Visibility lost 2:30 Crib and foam on left side burning 3:47 No flames 6:00 Fire appears out, no smoke 7:30 End of test and sprinkler(s) off 11:17 (10 mins after first sprinkler) Fire extinguished manually No, fire already out
Post fire observations
Crib sticks mainly unburnt. No charring on plywood due to crib
Foam on left side largely burnt but small amount remaining at edge
Foam on the right side almost entirely burnt
39 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Small amount of charring above the foam on the plywood on both sides
Test details Test name – number Stylised fires - Test 8 Filename for temperatures Jan2605 Filename for water flow rate CRSTest8 Test date 26/1/05 Personnel KA, PC, PR, CW
Test parameters Fire scenario Corner test Sprinkler model Sprinkler EC (k71) 570C/680C Sprinkler type Concealed, glass bulb, vented Deflector plate depth ~ 10 mm depth below ceiling Concealed depth ~ maximum recess distance Sprinkler orientation Parallel to the long length of test room Water flow rate for one sprinkler 64 l/min Water flow rate for two sprinklers 100.4 l/min Sprinkler spacing 4 m Room size 8 m by 4 m Lintel No lintel
Prior to test Relative humidity 49.6% in test room, 52.5% in Burn Hall Temperature 8.10C in test room, 5.90C in Burn Hall Moisture content of 2 crib sticks 3mm below surface
9.2%, 9.2%
Weight of wood crib 7300g Photographs of fuel arrangement Yes Extract started and mode and flow No, main extract to furnace building Leakage test, pump on and air bled Yes Stopwatches started -3:00 Temperature logging started -2:00 Video camera started -2:00 Flow meter logging started -1:00
40 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test observations Observation Time (min: sec) Ignition 0:00 Smoke layer approx 1m above stands 0:36 First sprinkler cap operated 0:48 First sprinkler operated (sprinkler 1) 0:58 Second sprinkler cap operated 1:03 Second sprinkler operated Did not operate Dummy sprinkler cap operated 1:13 Dummy sprinkler operated Did not operate Well defined smoke layer 1:27, 1:59 Foam and crib still burning 2:13 Wall appears charred next to left foam 2:33 Crib still burning vigorously, uncontrolled, unaffected by sprinkler
2:57
Fire diminished, flames just above plywood stands
4:09
Crib still burning, grey wood smoke, flames now not high, slightly hazy
9:30 until end of test
End of test and sprinkler(s) off 10:58 (10 mins after first sprinkler) Fire extinguished manually Yes, crib was burning and there was a
flame on the left corner of one foam Post fire observations
Charring on top layer
Charred plywood above foam sheet No charring above right foam sheet
41 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test details Test name - number Stylised fires - Test 9 Filename for temperatures Jan2705 Filename for water flow rate CRSTest 9 Test date 27/1/05 Personnel PC, KA, CW, RH, JS
Test parameters Fire scenario Corner test Sprinkler model Sprinkler FC (k59) 570C/600C Sprinkler type Concealed, solder, not vented Solder base plate depth ~ 7 mm above ceiling Concealed depth ~ maximum recess distance Sprinkler orientation Parallel to the long length of test room Water flow rate for one sprinkler 64 l/min Water flow rate for two sprinklers 121.2 l/min Sprinkler spacing 4 m Room size 8 m by 4 m Lintel No lintel
Prior to test Relative humidity 56.4% in test room, 54.1% in Burn Hall Temperature 15.10C in test room,12.60C in Burn Hall Moisture content of 2 crib sticks 3mm below surface
9.9%, 9.2% relative humidity
Weight of wood crib 7194.3 g Photographs of fuel arrangement Yes Extract started and mode and flow Yes, 15 m3/s free burn Pump on and air bled Yes Stopwatches started -3:00 Temperature logging started -2:00 Video camera started -2:00 Flow meter logging started -1:00
42 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test observations Observation Time (min: sec) Ignition 0:00 Smoke layer depth approx. 1m above plywood stands
0:40
First sprinkler cap operated 0:57 First sprinkler operated (sprinkler 1) 1:17 Second sprinkler cap operated 1:35 Second sprinkler operated Did not operate Dummy sprinkler cap operated 1:29 Dummy sprinkler operated Did not operate Fire in corner burning vigorously/layer 3:02 Crib low flames, grey smoke hazy 4:30 Smoky at low level, grey smoke 6:29 End of test and sprinkler(s) off 11:19 (10 minutes after first sprinkler
operation) Fire extinguished manually Yes, crib burning inside
Post fire observations Amount of fire damage See photos
Crib sticks charred to top layer
Charring on plywood above both foam locations
Foam almost entirely burnt out on both sides
Wetting pattern See photos
43 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test details Test name - number Stylised fires - Test 10 Filename for temperatures Feb0105 Filename for water flow rate CRSTest10 Test date 1/2/05 Personnel PR, CW, PC, KA, JS
Test parameters Fire scenario Corner test Sprinkler model Sprinkler FC (k59), 570C/600C Sprinkler type Concealed, solder, not vented Solder plate depth ~ 7 mm above ceiling Concealed depth ~ maximum recess distance Sprinkler orientation Frame arms of sprinklers 1and 2
directed towards corner/fire location. Dummy sprinkler arms across doorway.
Water flow rate for one sprinkler 64 l/min Water flow rate for two sprinklers 121.2 l/min Sprinkler spacing 4 m Room size 8 m by 4 m Lintel No lintel
Prior to test Relative humidity 44% in test room, 44.5% in Burn Hall Temperature 19.40C in test room, 17.90C in Burn Hall Moisture content 3mm below surface 9.8%, 9.8% Weight of wood crib 7245.6 g Photographs of fuel arrangement Yes Extract started and mode and flow Yes 15m3/s free burn Pump on and air bled Yes
44 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Stopwatches started -3:00 Temperature logging started -2:00 Video camera started -2:00 Flow meter logging started -1:00
Test observations Observation Time (min: sec) Ignition 0:00 First sprinkler cap operated 0:54 First sprinkler operated (sprinkler 1) 1:18 Second sprinkler cap operated 1:22 Second sprinkler operated Did not operate Dummy sprinkler cap operated 1:30 Dummy sprinkler operated Did not operate Fire burning well, clear layer underneath smoke layer
2:09
Crib burning well 2:20 Foam fire nearly out 2:35 Crib burning well 3:09 Crib burning with short flame just above plywood stands
3:45-4:33
White wood smoke produced from floor to ceiling
7:03 until end of test
End of test and sprinkler(s) off 11:20 (10 mins after first sprinkler operated)
Fire extinguished manually Yes, crib still burning Post fire observations
Amount of fire damage See photos
Wood crib particularly charred on edge perpendicular to long wall
Plywood on wall above foam on left side and right side scorched, more than most previous ‘scorching’
45 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Foam almost entirely burnt out on both boards
Wetting pattern See photos Sprinkler spray looked reasonably even around 360 degrees. No obvious area of low coverage due to frame arms. However, height of wall wetting was lower in the corner location. Large drops falling to floor beneath sprinkler head probably due to water dripping from ceiling.
46 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test details Test name - number Stylised fires - Test 11 Filename for temperatures CRSTest11 Filename for water flow rate Feb0205 Test date 2/2/05 Personnel PR, CW, PC, KA, JS
Test parameters Fire scenario Wall test Sprinkler model Sprinkler FC (k59) 570C/600C Sprinkler type Concealed, solder, not vented Deflector plate depth ~ 7 mm above ceiling Concealed depth ~ maximum recess distance Sprinkler orientation Parallel to long length of test room Water flow rate for one sprinkler 64 l/min Water flow rate for two sprinklers 121.2 l/min Sprinkler spacing 4 m Room size 8 m by 4 m Lintel No lintel
Prior to test Relative humidity 38.4% inside test room, 59.1% inside
Burn Hall Temperature 19.10C inside test room, 120C inside
Burn Hall Moisture content of 2 crib sticks 3mm below surface
9.1%, 9.1%
Weight of wood crib 7379.5g Photographs of fuel arrangement Yes Extract started and mode and flow No, extract on furnace building Pump on and air bled Yes Stopwatches started -3:00 Temperature logging started -2:00 Video camera started -2:00 Flow meter logging started -1:00
Prior to test Observation Time (min: sec) Ignition 0:00 First sprinkler cap fell (sprinkler 1)* * Two tags of concealer plate of sprinkler 1, had released prior to test
1:14
First sprinkler operated (sprinkler 2) 2:09 Second sprinkler cap fell 1:31
47 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Second sprinkler operated (sprinkler 1)
2:12
Dummy sprinkler cap fell 1:49 Dummy sprinkler operated Did not operate Crib burning vigorously 2:49-3:45 Crib fire diminishing, smoky floor to ceiling, flames just below stands
3:45
White wood smoke observed floor to ceiling
6:00
End of test and sprinkler(s) off 12:12 Fire extinguished manually Yes wood crib still burning
Post fire observations Amount of fire damage See photos
Scorching observed on plywood above foam sheets
Left hand foam burnt away except foam on bottom corner nearest plywood wall
Right hand foam burnt away except for small amount on bottom corner nearest plywood wall
Wetting pattern Wetting pattern observed on walls at high level
48 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test details Test name - number Stylised fires - Test 12 Filename for temperatures CRSTest12 Filename for water flow rate Feb0305 Test date 3/2/05 Personnel PR, KA, PC, CW, JS
Test parameters Fire scenario Corner test Sprinkler model Sprinkler EC Sprinkler type Concealed, glass bulb 570C/680C,
domed vented concealer plate Deflector plate depth ~10 mm below the ceiling Concealed depth Maximum recess distance minus 2 mm Sprinkler orientation Sprinklers in room aligned with frame
arms pointing towards the fire, dummy sprinkler orientated with frame arms across the doorway
Water flow rate for one sprinkler 64 l/min Water flow rate for two sprinklers 100.4 l/min Sprinkler spacing 4 m Room size 8 m by 4 m Lintel No lintel
Prior to test Relative humidity 62% test room, 52% Burn Hall Temperature 150C inside test room, 17.30C inside
Burn Hall Moisture content 3mm below surface 9.9%, 9.8% Weight of wood crib 7292.7g Photographs of fuel arrangement Yes Extract started and mode and flow Yes, 15 m3/s free burn Pump on and air bled Yes Stopwatches started -3:00 Temperature logging started -2:00 Video camera started -2:00 Flow meter logging started -1:00
Test observations Observation Time (min: sec) Ignition 0:00 First sprinkler cap operated 0:48
49 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
First sprinkler operated (sprinkler 1) 1:01 Second sprinkler cap operated 1:06 Second sprinkler operated (sprinkler 2)
2:10
Dummy sprinkler cap operated 1:11 Dummy sprinkler operated 2:29 Crib fire burning vigorously 2:40 Crib burning with long flames 3:10 Crib burning with long flames 4:26 Plywood alight and fire growing 5:25 approximately Flames spreading on ceiling 6:08 End of test and sprinkler(s) off 6:40
Test terminated to protect room. Fire extinguished manually Yes, plywood panels burning
Post fire observations Amount of fire damage See photos
Severe charring of plywood above crib to ceiling, some charring of plywood above foam sheets on both sides
Crib burnt on top layer
Foam burnt away on both sides Wetting pattern See photos below
50 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Examination of water pattern at 64l/min after test revealed that little water was wetting plywood walls at the wood crib location.
51 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test details Test name - number Stylised fires - Test 13 Filename for temperatures CRSTest13 Filename for water flow rate Feb0405 Test date 4/2/05 Personnel KA, PC, CW, RH, JS
Test parameters Fire scenario Corner test Sprinkler model Sprinkler EC Sprinkler type Concealed, glass bulb 570C/680C,
domed vented concealer plate Deflector plate depth ~ 22mm below ceiling Concealed depth ~ minimum recess distance Sprinkler orientation Sprinkler 1 and 2 aligned to fire corner
of room, dummy parallel with short wall Water flow rate for one sprinkler 64 l/min Water flow rate for two sprinklers 100.4 l/min Sprinkler spacing 4 m Room size 8 m by 4 m Lintel No lintel
Prior to test Relative humidity 39.5% in test room Temperature 21.50C in test room, 16.60C in Burn Hall Moisture content 3mm below surface 9.4%, 10% Weight of wood crib 7416g Photographs of fuel arrangement Yes Extract started and mode and flow No, extract to furnace building Pump on and air bled Yes Stopwatches started -3:00 Temperature logging started -2:00 Video camera started -2:00 Flow meter logging started -1:00
Test observations Observation Time (min: sec) Ignition 0:00 First sprinkler cap operated 0:51 First sprinkler operated (sprinkler 1) 1:08 Second sprinkler cap operated 1:10 Second sprinkler operated Did not operate Dummy sprinkler cap operated 1:16 Dummy sprinkler operated Did not operate
52 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Smoke buoyant, burning vigorously 2:30 Smoke logged, flames just below level of stands
4:35
No flames, grey white smoke 5:11 Fire appears out 9:11 End of test and sprinkler(s) off 11:08 (10 mins after first sprinkler
operated) Fire extinguished manually Yes, foam on right hand side burning
Post fire observations Amount of fire damage See photos
Some charring to top layer of crib No charring to plywood above crib.
Slight charring to plywood above foam.
Wetting pattern See photos
53 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test 1
0
20
40
60
80
100
120
140
160
180
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
A1 EmbeddedA2 EmbeddedA3 SurfaceA4 SurfaceA5 75mmA6 75mmA7 75mm
Figure 3B.26 – Test 1 Temperatures above crib
0
20
40
60
80
100
120
140
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from Ignition (minutes)
Tem
pera
ture
(Deg
C)
B11 75mmB12 75mmB13 75mm
Figure 3B.27 – Test 1 Temperatures at sprinkler B1
54 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
10
20
30
40
50
60
70
80
90
100
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from Ignition (minutes)
Tem
pera
ture
(Deg
C)
B21 75mmB22 75mmB23 75mm
Figure 3B.28 – Test 1 Temperatures at sprinkler B2
0
20
40
60
80
100
120
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from Ignition (minutes)
Tem
pera
ture
(Deg
C)
C1 75mmC2 1.6m
Figure 3B.29 – Test 1 Temperatures at centre of room
55 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
10
20
30
40
50
60
70
80
90
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from Ignition (minutes)
Tem
pera
ture
(Deg
C)
In Chamber
Door Centre Line
Bulb
Figure 3B.30 – Test 1 Temperatures close to dummy sprinkler
0
10
20
30
40
50
60
70
80
90
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
1752002503504506007109101010133015601930
Figure 3B.31 – Test 1 Temperatures at column 1
56 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
10
20
30
40
50
60
70
80
90
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
1601802553254255707709701370
Figure 3B.32 – Test 1 Temperatures at column 2
-2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 160
20
40
60
80
100
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
Flow meter did not display
Pre
ssur
e (b
ar) Flow
Flow
(L/m
in)
Time from ignition (minutes)
Pressure
Figure 3B.33 – Test 1 Sprinkler water flow rate and pressure
57 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test 2
0
20
40
60
80
100
120
140
160
180
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
E1 EmbeddedE2 EmbeddedE3 SurfaceE4 SurfaceE5 75mmE6 75mmE7 75mm
Figure 3B.34 – Test 2 Temperatures above crib
0
20
40
60
80
100
120
140
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
B11 75mmB12 75mmB13 75mm
Figure 3B.35 – Test 2 Temperatures at sprinkler B1
58 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
140
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
B21 75mmB22 75mmB23 75mm
Figure 3B.36 – Test 2 Temperatures at sprinkler B2
0
20
40
60
80
100
120
140
160
180
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
C1 75mm
E7 75mm
Figure 3B.37 – Test 2 Temperatures at centre of room
59 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
In Chamber D1Door Centre Line D2Bulb D3
Figure 3B.38 – Test 2 Temperatures close to dummy sprinkler
0
20
40
60
80
100
120
140
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
1752002503504506007109101010133015601930
Figure 3B.39 – Test 2 Temperatures at column 1
60 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
1601802553254255707709701370
Figure 3B.40 – Test 2 Temperatures at column 2
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 140
20
40
60
80
100
120
140
160
Flow
(L/m
in)
Time from ignition (minutes)
Figure 3B.41 – Test 2 Sprinkler water flow rate
61 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test 4
0
50
100
150
200
250
300
350
400
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
A1 EmbeddedA2 EmbeddedA3 SurfaceA4 SurfaceA5 75mmA6 75mmA7 75mm
Figure 3B.42 – Test 4 Temperatures above crib
0
20
40
60
80
100
120
140
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
B11 75mmB12 75mmB13 75mm
Figure 3B.43 – Test 4 Temperatures at sprinkler B1
62 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
B21 75mmB22 75mmB23 75mm
Figure 3B.44 – Test 4 Temperatures at sprinkler B2
0
20
40
60
80
100
120
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
C1 75mm
C2 1.6m
Figure 3B.45 – Test 4 Temperatures at centre of room
63 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
10
20
30
40
50
60
70
80
90
100
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
In Chamber D1Door Centre Line D2Bulb D3
Figure 3B.46 – Test 4 Temperatures close to dummy sprinkler
0
20
40
60
80
100
120
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
1752002503504506007109101010133015601930
Figure 3B.47 – Test 4 Temperatures at column 1
64 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
10
20
30
40
50
60
70
80
90
100
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
1601802553254255707709701370
Figure 3B.48 – Test 4 Temperatures at column 2
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 140
10
20
30
40
50
60
70
80
90
100
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0Pr
essu
re (b
ar)
Flow
Flow
(L/m
in)
Time from ignition (minutes)
Flow meter did not display Pressure
Figure 3B.49 – Test 4 Sprinkler water flow rate and pressure
65 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test 5
0
50
100
150
200
250
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
E1 EmbeddedE2 EmbeddedE3 SurfaceE4 SurfaceE5 75mmE6 75mmE7 75mm
Figure 3B.50 – Test 5 Temperatures above crib
0
20
40
60
80
100
120
140
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
B11 75mmB12 75mmB13 75mm
Figure 3B.51 – Test 5 Temperatures at sprinkler B1
66 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
140
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
B21 75mmB22 75mmB23 75mm
Figure 3B.52 – Test 5 Temperatures at sprinkler B2
0
20
40
60
80
100
120
140
160
180
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
C1 75mm
C2 1.6m
Figure 3B.53 – Test 5 Temperatures at centre of room
67 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
In Chamber D1Door Centre Line D2Bulb D3
Figure 3B.54 – Test 5 Temperatures close to dummy sprinkler
0
20
40
60
80
100
120
140
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
1752002503504506007109101010133015601930
Figure 3B.55 – Test 5 Temperatures at column 1
68 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
1601802553254255707709701370
Figure 3B.56 – Test 5 Temperatures at column 2
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 140
20
40
60
80
100
120
140
Flow
(L/m
in)
Time from ignition (minutes)
Figure 3B.57 – Test 5 Sprinkler water flow rate
69 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test 6
0
50
100
150
200
250
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
A1 EmbeddedA2 EmbeddedA3 SurfaceA4 SurfaceA5 75mmA6 75mmA7 75mm
Figure 3B.58 – Test 6 Temperatures above crib
0
20
40
60
80
100
120
140
160
180
200
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
B11 75mmB12 75mmB13 75mm
Figure 3B.59 – Test 6 Temperatures at sprinkler B1
70 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
140
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
B21 75mmB22 75mmB23 75mm
Figure 3B.60 – Test 6 Temperatures at sprinkler B2
0
20
40
60
80
100
120
140
160
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
C1 75mm
C2 1.6m
Figure 3B.61 – Test 6 Temperatures at centre of room
71 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
In Chamber D1Door Centre Line D2Bulb D3
Figure 3B.62 – Test 6 Temperatures close to dummy sprinkler
0
20
40
60
80
100
120
140
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
1752002503504506007109101010133015601930
Figure 3B.63 – Test 6 Temperatures at column 1
72 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
1601802553254255707709701370
Figure 3B.64 – Test 6 Temperatures at column 2
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 140
10
20
30
40
50
60
70
80
90
100
Flow
(L/m
in)
Time from ignition (minutes)
Figure 3B.65 – Test 6 Sprinkler water flow rate
73 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test 7
0
50
100
150
200
250
300
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
A1 EmbeddedA2 EmbeddedA3 SurfaceA4 SurfaceA5 75mmA6 75mmA7 75mm
Figure 3B.66 – Test 7 Temperatures above crib
0
50
100
150
200
250
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
B11 75mmB12 75mmB13 75mm
Figure 3B.67 – Test 7 Temperatures at sprinkler B1
74 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
140
160
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
B21 75mmB22 75mmB23 75mm
Figure 3B.68 – Test 7 Temperatures at sprinkler B2
0
20
40
60
80
100
120
140
160
180
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
C1 75mm
C2 1.6m
Figure 3B.69 – Test 7 Temperatures at centre of room
75 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
140
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
In Chamber D1Door Centre Line D2Bulb D3
Figure 3B.70 – Test 7 Temperatures close to dummy sprinkler
0
20
40
60
80
100
120
140
160
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
1752002503504506007109101010133015601930
Figure 3B.71 – Test 7 Temperatures at column 1
76 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
140
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
1801602553254255707709701370
Figure 3B.72 – Test 7 Temperatures at column 2
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 140
10
20
30
40
50
60
70
80
90
100
Flow
(L/m
in)
Time from ignition (minutes)
Figure 3B.73 – Test 7 Sprinkler water flow rate
77 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test 8
0
50
100
150
200
250
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
A1 EmbeddedA2 EmbeddedA3 SurfaceA4 SurfaceA5 75mmA6 75mmA7 75mm
Figure 3B.74 – Test 8 Temperatures above crib
0
20
40
60
80
100
120
140
160
180
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
B11 75mmB12 75mmB13 75mm
Figure 3B.75 – Test 8 Temperatures at sprinkler B1
78 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
140
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
B21 75mmB22 75mmB23 75mm
Figure 3B.76 – Test 8 Temperatures at sprinkler B2
0
20
40
60
80
100
120
140
160
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
C1 75mm
C2 1.6m
Figure 3B.77 – Test 8 Temperatures at centre of room
79 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
In Chamber D1Door Centre Line D2Bulb D3
Figure 3B.78 – Test 8 Temperatures close to dummy sprinkler
0
20
40
60
80
100
120
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
1752002503504506007109101010133015601930
Figure 3B.79 – Test 8 Temperatures at column 1
80 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
1601802553254255707709701370
Figure 3B.80 – Test 8 Temperatures at column 2
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 140
10
20
30
40
50
60
70
80
90
100
Flow
(L/m
in)
Time from ignition (minutes)
Figure 3B.81 – Test 8 Sprinkler water flow rate
81 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test 9
0
50
100
150
200
250
300
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
A1 EmbeddedA2 EmbeddedA3 SurfaceA4 SurfaceA5 75mmA6 75mmA7 75mm
Figure 3B.82 – Test 9 Temperatures above crib
0
50
100
150
200
250
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
B11 75mmB12 75mmB13 75mm
Figure 3B.83 – Test 9 Temperatures at sprinkler B1
82 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
140
160
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
B21 75mmB22 75mmB23 75mm
Figure 3B.84 – Test 9 Temperatures at sprinkler B2
0
20
40
60
80
100
120
140
160
180
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
C1 75mm
C2 1.6m
Figure 3B.85 – Test 9 Temperatures at centre of room
83 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
140
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
In Chamber D1Door Centre Line D2Bulb D3
Figure 3B.86 – Test 9 Temperatures close to dummy sprinkler
0
20
40
60
80
100
120
140
160
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
1752002503504506007109101010133015601930
Figure 3B.87 – Test 9 Temperatures at column 1
84 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
140
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
1601802553254255707709701370
Figure 3B.88 – Test 9 Temperatures at column 2
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 140
10
20
30
40
50
60
70
80
90
100
Flow
(L/m
in)
Time from ignition (minutes)
Figure 3B.89 – Test 9 Sprinkler water flow rate
85 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test 10
0
50
100
150
200
250
300
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
A1 EmbeddedA2 EmbeddedA3 SurfaceA4 SurfaceA5 75mmA6 75mmA7 75mm
Figure 3B.90 – Test 10 Temperatures above crib
0
50
100
150
200
250
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
B11 75mmB12 75mmB13 75mm
Figure 3B.91 – Test 10 Temperatures at sprinkler B1
86 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
140
160
180
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
B21 75mmB22 75mmB23 75mm
Figure 3B.92 – Test 10 Temperatures at sprinkler B2
0
20
40
60
80
100
120
140
160
180
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
C1 75mm 1.5mm C2 1.6m 1.5mm
Figure 3B.93 – Test 10 Temperatures at centre of room
87 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
140
160
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
In Chamber D1
Door Centre Line D2
Bulb D3
Figure 3B.94 – Test 10 Temperatures close to dummy sprinkler
0
20
40
60
80
100
120
140
160
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
1752002503504506007109101010133015601930
Figure 3B.95 – Test 10 Temperatures at column 1
88 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
140
160
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
1601802553254255707709701370
Figure 3B.96 – Test 10 Temperatures at column 2
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 140
10
20
30
40
50
60
70
80
90
100
Flow
(L/m
in)
Time from ignition (minutes) Figure 3B.97 – Test 10 Sprinkler water flow rate
89 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test 11
0
50
100
150
200
250
300
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
E1 EmbeddedE2 EmbeddedE3 SurfaceE4 SurfaceE5 75mmE6 75mmE7 75mm
Figure 3B.98 – Test 11 Temperatures above crib
0
20
40
60
80
100
120
140
160
180
200
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
B11 75mmB12 75mmB13 75mm
Figure 3B.99 – Test 11 Temperatures at sprinkler B1
90 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
140
160
180
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
B21 75mmB22 75mmB23 75mm
Figure 3B.100 – Test 11 Temperatures at sprinkler B2
0
50
100
150
200
250
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
C1 75mm 1.5mm C2 1.6m 1.5mm
Figure 3B.101 – Test 11 Temperatures at centre of room
91 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
140
160
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
In Chamber D1Door Centre Line D2Bulb D3
Figure 3B.102 – Test 11 Temperatures close to dummy sprinkler
0
20
40
60
80
100
120
140
160
180
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
1752002503504506007109101010133015601930
Figure 3B.103 – Test 11 Temperatures at column 1
92 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
140
160
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
1601802553254255707709701370
Figure 3B.104 – Test 11 Temperatures at column 2
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 140
20
40
60
80
100
120
140
160
Flow
(L/m
in)
Time from ignition (minutes) Figure 3B.105 – Test 11 Sprinkler water flow rate
93 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test 12
0
100
200
300
400
500
600
700
800
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
A1 EmbeddedA2 EmbeddedA3 SurfaceA4 SurfaceA5 75mmA6 75mmA7 75mm
Figure 3B.106 – Test 12 Temperatures above crib
0
20
40
60
80
100
120
140
160
180
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
B11 75mmB12 75mmB13 75mm
Figure 3B.107 – Test 12 Temperatures at sprinkler B1
94 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
140
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
B21 75mmB22 75mmB23 75mm
Figure 3B.108 – Test 12 Temperatures at sprinkler B2
0
20
40
60
80
100
120
140
160
180
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
C1 75mm
C2 1.6m
Figure 3B.109 – Test 12 Temperatures at centre of room
95 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
In Chamber D1Door Centre Line D2Bulb D3
Figure 3B.110 – Test 12 Temperatures close to dummy sprinkler
0
20
40
60
80
100
120
140
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
1752002503504506007109101010133015601930
Figure 3B.111 – Test 12 Temperatures at column 1
96 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time (minutes)
Tem
pera
ture
(Deg
C)
1601802553254255707701370
Figure 3B.112 – Test 12 Temperatures at column 2
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 140
20
40
60
80
100
120
140
160
Flow
(L/m
in)
Time from ignition (minutes)
Test terminated prematurely
Figure 3B.113 – Test 12 Sprinkler water flow rate
97 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
Test 13
0
50
100
150
200
250
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
A1 EmbeddedA2 EmbeddedA3 SurfaceA4 SurfaceA5 75mmA6 75mmA7 75mm
Figure 3B.114 – Test 13 Temperatures above crib
0
20
40
60
80
100
120
140
160
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
B11 75mmB12 75mmB13 75mm
Figure 3B.115 – Test 13 Temperatures at sprinkler B1
98 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
B21 75mmB22 75mmB23 75mm
Figure 3B.116 – Test 13 Temperatures at sprinkler B2
0
20
40
60
80
100
120
140
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
C1 75mm
C2 1.6m
Figure 3B.117 – Test 13 Temperatures at centre of room
99 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
In Chamber D1Door Centre Line D2Bulb D3
Figure 3B.118 – Test 13 Temperatures close to dummy sprinkler
0
20
40
60
80
100
120
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
1752002503504506007109101010133015601930
Figure 3B.119 – Test 13 Temperatures at column 1
100 Section 3: Stylised fires (Appendices 3A and 3B)
218113 © Building Research Establishment Ltd 2006
0
20
40
60
80
100
120
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from ignition (minutes)
Tem
pera
ture
(Deg
C)
160
180
255
325
425
570
770
970
Figure 3B.120 – Test 13 Temperatures at column 2
-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 140
10
20
30
40
50
60
70
80
90
100
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0P
ress
ure
(bar
)
Flow
Flow
(L/m
in)
Time from ignition (minutes)
Flow meter did not display
Pressure
Figure 3B.121 – Test 13 Sprinkler water flow rate and pressure
Top Related