FORM 160.80-EG1 (808
Model YS Rotary Screw Liquid ChillersDesign Level E
100 thru 675 tons
(315 thru 2375 KW)
r-22 and r-134aRated in Accordance
ith the latest edition of ARI
STANDARD 550/590
7/28/2019 Chiller - YR
2/56
JOHNSON CONTROLS
INTRODUCTION ........................................................... 3
RATINGS ....................................................................... 4
OpTIVIew CONTROL CeNTeR ................................... 5
MeCHANICAL SpeCIFICATIONS ................................ 13
ACCeSSORIeS & MODIFICATIONS ............................ 17
UNIT COMpONeNTS ................................................... 19
AppLICATION DATA ..................................................... 20
DIMeNSIONS STD..................................................... 28
S0-S3 Comrssor .................................................... 28
S4 & S5 Comrssor ............................................... 29
Comact watr Box Nozzl Arrangmnts ............... 30
Floor Layout .............................................................. 31
Coolr Nozzl Arrangmnts .................................... 32
Condnsr Nozzl Arrangmnts ............................. 34
weIGHTS STD........................................................... 36
DIMeNSIONS MeTRIC .............................................. 38
S0-S3 Comrssor .................................................... 38
S4 & S5 Comrssor ............................................... 39
Comact watr Box Nozzl Arrangmnts ............... 40
Floor Layout .............................................................. 41
Coolr Nozzl Arrangmnts .................................... 42
Condnsr Nozzl Arrangmnts ............................. 44
weIGHTS MeTRIC .................................................... 46
GUIDe SpeCIFICATIONS ............................................ 48MeTRIC CONVeRSION TABLeS ................................. 53
NOMENCLATURE
Th modl numbr dnots th folloing charactristics of th unit:
YS BB BA S0 CF E S
Modl
Coolr Cod Dsign Lvl
por Suly:
for 60 Hz
5 for 50 Hz
Condnsr Cod
Comrssor Cod
Motor Cod
Scial Faturs
TABLE OF CONTENTS
pAGe
LIST OF TABLES
1 watr Flo Rat Limits.................. 20
2 Motor Voltag Variations ................ 23
3 60 Hz elctrical Data ..................... 25
4 Motor Startrs ................................ 25
5 50 Hz elctrical Data ..................... 26
6 Availabl Comrssor/Shll/
Motor Combinations
(R-22 & R-134a) ............................ 26
7 Availabl Comrssor/Shll/
Motor Combinations
(50 Hz, R-134a Only)..................... 27
pAGeTABLeNO.
7/28/2019 Chiller - YR
3/56
JOHNSON CONTROLS
FORM 160.80-EG1 (808
Introduction
Th YORK Millennium YS Chillr offrs a comlt com-
bination of faturs for total onr satisfaction.
MATCHED COMPONENTS MAXIMIZE EFFICIENCY
Actual chiller efciency cannot be determined by analyzing
the theoretical efciency of any one chiller component.It requires a specic combination of heat exchanger,
comrssor, and motor rformanc to achiv th lo-
st systm kw/Ton. YORK Millennium chillr tchnology
matchs chillr systm comonnts to rovid maximum
chiller efciency under actual not just theoretical op-
rating conditions.
REAL-wORLD ENERGY PERFORMANCE
Johnson Controls ionrd th trm Ral-world enrgy
to illustrat th nrgy-saving otntial of focusing on
chillr rformanc during off-dsign conditions. Off-d-
sign is not only art load, but full load oration as ll,
ith rducd ntring condnsr atr tmraturs
(eCwTs). This is hr chillrs orat 99% of th tim,
and hr orating costs add u.
Th YS Millennium chillrs ar th only chillrs dsignd
to orat on a continuous basis ith cold eCwT and full
condenser ow at all load points, taking full advantage of
Real-World conditions. This type of operation benets the
cooling tor as ll; rducing cycling of th fan motor
and ensuring good coverage of the cooling ll.
YORK Millennium chillers offer the most efcient Real-world oration of any chillr, maning lor orating
costs and an xcllnt rturn on your chillr invstmnt.
OPEN DRIVE DESIGN
Hrmtic-motor burnout can caus catastrohic damag
to a chillr. Th ntir chillr must b cland, and th
rfrigrant rlacd. YORK Millennium scr chillrs
liminat this risk by utilizing air-coold motors. Rfrig-
rant nvr coms in contact ith th motor, rvnting
contamination of th rst of th chillr.
Insuranc comanis that offr olicis on larg air condi-
tioning quimnt oftn considr air-coold motors a sig-
nicant advantage over hermetic refrigerant cooled units.
HIGH-EFFICIENCY HEAT EXCHANGERS
Millennium chillr hat xchangrs offr th latst tchnology in hat transfr surfac dsign to giv you maxi-
mum efciency and compact design. Water-side and
rfrigrant-sid dsign nhancmnts minimiz both
nrgy consumtion and tub fouling.
FACTORY PACKAGING REDUCES FIELD LABOR
COSTS
YORK Millennium scr chillrs ar dsignd to k
installation costs lo. whr installation accss is not a
roblm, th unit can b shid comltly ackagd
rquiring minimal iing and iring to comlt th in-
stallation.
For thos units utilizing a factory installd Solid-Stat
Startr, th thr or lads rovid all or to th
chillr and its auxiliaris.
TAKE ADVANTAGE OF COLDER COOLING TOwER
wATER TEMPERATURES
YORK Millennium scr chillrs ar dsignd to tak ful
advantag of coldr cooling tor atr tmraturs
hich ar naturally availabl during most orating hours
Considrabl nrgy savings ar availabl by ltting tor
water temperature drop, rather than articially holding itabov 75F (23.9C), scially at lo load, as som
chillrs rquir.
U.L. ACCEPTANCE YOUR ASSURANCE OF RELI
ABILITY
YORK Millennium scr chillrs ar arovd for listing
by Undrritrs Laboratoris for th Unitd Stats and
Canada. Rcognition of safty and rliability is your as-
suranc of troubl-fr rformanc in day-to-day building
oration.
7/28/2019 Chiller - YR
4/56
JOHNSON CONTROLS
Ratings
ARI CERTIFICATION PROGRAM
Th rformanc of YORK Millennium chillers is certied
to th Air Conditioning and Rfrigration Institut (ARI)
complying with the certication sections of the latest issue
of ARI Standard 550/590. Under this Certication Pro-
gram, chillrs ar rgularly tstd in strict comlianc ith
this Standard. This rovids an indndnt, third-arty
verication of chiller performance.
COMPUTERIZED PERFORMANCE RATINGS
each chillr is custom-matchd to mt th individual
building load and nrgy rquirmnts. A larg numbr
of standard hat xchangrs and ass arrangmnts ar
availabl to rovid th bst ossibl match.
It is not ractical to rovid tabulatd rformanc for
ach combination, as th nrgy rquirmnts at both full
and part- load vary signicantly with each heat exchanger
and ass arrangmnt. Comutrizd ratings ar avail-
able through each Johnson Controls sales ofce. These
ratings can be tailored to specic job requirements, and
are part of the ARI Certication Program.
OFF-DESIGN PERFORMANCE
Since the vast majority of its operating hours are spentat off-dsign conditions, a chillr should b chosn not
only to mt th full-load dsign, but also for its ability to
perform efciently at lower loads and lower tower water
tmraturs. It is not uncommon for chillrs ith th
sam full-load Kw/TON to hav an orating cost diffr-
nc of ovr 10% du to art-load oration.
part-load information can b asily and accuratly gnr-
atd by comutr. And bcaus it is so imortant to an
onrs orating budgt, this information is no stan-
dard within the ARI Certication Program in the form of
an Intgratd part-Load Valu (IpLV), and Non-Standardpart-Load Valu (NpLV).
Th IpLV / NpLV formulas from ARI Standard 550/590
closly track chillr orations, and rovid a mor ac-
curat indication of chillr rformanc than th rvi-
ous IpLV / ApLV formula. A mor dtaild analysis must
take into account actual building load proles, and local
athr data. part-load rformanc data should b ob-
tained for each job using its own design criteria.
Ratd in accordanc ith th latst
issu of ARI Standard 550/590.
7/28/2019 Chiller - YR
5/56
5JOHNSON CONTROLS
FORM 160.80-EG1 (808
OptiView Control Center
OPTIVIEw CONTROL CENTER
Th YORK OtiVi Control Cntr, furnishd as standard
on each chiller, provides the ultimate in efciency, monitor-
ing, data rcording, chillr rotction and orating as.
Th control cntr is a factory mountd, ird, and tstd
stat-of-th-art microrocssor basd control systm for
R-134a or R-22 screw chillers. The panel is congured
ith a 10.4 inch diagonal color Liquid Crystal Dislay(LCD) surrounded by soft keys, which are redened with
on kystrok basd on th scrn dislay at that tim.
This rvolutionary dvlomnt maks chillr oration
quickr and asir than vr bfor. Instad of rquiring
kystrok aftr kystrok to hunt for information on a small
monochrom LCD scrn, a singl button rvals a id
array of information on a larg, full-color illustration of th
aroriat comonnt, hich maks information asir
to intrrt. This is all mountd in th middl of a kyad
intrfac and installd in a lockd nclosur.
Th LCD dislay allos grahic animatd dislay of th
chillr, chillr sub-systms and systm aramtrs; thisallos th rsntation of svral orating aramtrs
at onc. In addition, th orator may vi a grahical
rrsntation of th historical oration of th chillr as
ll as th rsnt oration. A Status Bar is dislayd
at all tims on all scrns. It contains th Systm - Status
Lin and Dtails Lin, th Control Sourc, Accss Lvl,
Dat and Tim. All dat rrsntations and calculations
us four digits for th yar to rovid Yar 2000 comli-
anc.
During th Start Squnc and Systm Lockout Dlay, th
systm status ill includ a countdon timr indicating th
tim rmaining. Th control anl is comatibl ith th
YORK Solid Stat Startr (otional), elctro-mchanica
(e-M) startr, or any customr sulid e-M startr tha
comlis ith th YORK R-1051 standard. Th locations
of various chillr aramtrs ar clarly markd and in-
structions for specic operations are provided. The pane
vrbiag is availabl in othr languags as an otion, ith
english alays availabl. Data can b dislayd in ith
english or Mtric units, lus kyad ntry stoints of 0.1
incrmnts.
Scurity accss is rovidd to rvnt unauthorizd ac
css and/or a chang of stoints. This is accomlishd
ith thr diffrnt lvls of accss and assords fo
ach lvl. Thr ar scrns, dislayd valus, rogram
mabl stoints and manual controls not shon availabl
to srvic th chillr. Thy ar only dislayd hn loggd
in at th srvic accss lvl. Th Advancd Diagnostics
and troublshooting information for th chillr and thanl is also includd.
Th anl is fusd through a 1-1/2 or 2 KVA transform
in th comrssor motor startr to rovid individua
ovr-currnt rotctd or for all controls. Numbrd
trminal stris for iring such as Rmot Start/Sto
Flo Sitch, Chilld watr pum and Local or Rmot
Cycling Dvic ar rovidd. Th panl also rovids
eld interlocks that indicate the chiller status. These con
tacts includ a Rmot Mod Rady To Start, a Cycling
7/28/2019 Chiller - YR
6/56
6 JOHNSON CONTROLS
OptiView Control Center- continued
Shutdon, a Safty Shutdon and a chillr Run Contact.
prssur transducrs sns systm rssurs and thrm-
istors sns systm tmraturs. Th outut of ach
transducr is a DC voltag that is analogous to th rs-
sur inut. Th outut of ach thrmistor is a DC voltag
that is analogous to th tmratur it is snsing.
Stoints can b changd from a rmot location via
0-10VDC, 4-20mA, contact closurs or through srial
communications. The adjustable remote reset range [up
to 20F (11.1C)] provides exible, efcient use of remote
signal dnding on rst nds. Srial data intrfac
to th YORK ISN Building Automation Systm (BAS) is
through th Gnral protocol Intrfac Card (GpIC), hich
can b mountd insid th Control Cntr.
This rintd circuit board rqusts th rquird data from
th Micro Board and maks it availabl for th YORK
ISN ntork. This otional board is availabl through thJohnson Controls BAS grou. Th orating rogram
is stord in non-volatil mmory (epROM) to liminat
chillr failur du to AC or failur/battry discharg.
programmd stoints ar rtaind in lithium battry-
backd RTC mmory for 11 yars minimum.
Smart Frz point protction can orat th chillr as
lo as 36F (2.22C) laving chilld atr tmratur,
ithout nuisanc tris on Lo watr Tmratur. Th
sohisticatd rogram and snsor monitors th chillr a-
tr tmratur to rvnt frz-u. each rogrammabl
oint has a o-u scrn ith th alloabl rangs, so
th chillr cannot b rogrammd to orat outsid ofits dsign limits.
Thrmal ic storag systms ar basd on th conct
of using off-ak, lor cost lctricity to build ic for
handling th cooling load during ak hours. Th most
efcient way to build ice is to maximize chiller load and
minimiz run tim. Standard chillr control systms ar not
dsignd for this orating mod. In a tyical alication,
chillrs ill load and unload to maintain a laving chilld
liquid stoint. whn th YORK YS chillr orats in th
thrmal storag control mod, th unit ill rmain at 100%
load until th stoint shutdon tmratur is rachd.
To add greater operating exibility and eliminate unnec-
ssary chillr cycling, to diffrnt Lo watr (Liquid)
Tmratur Rstart Thrsholds can b rogrammd, on
for th ic mod and on for th standard cooling mod.
This control nhancmnt is standard on all YS chillrs.
Th chillr can also b lft in th standard control mod
for tmraturs ranging btn 20 and 70F (-6.7 and
21.1C), for alications involving a rocss cooling duty
that rquirs laving chilld liquid tmratur stoint
control.
whn or is alid to th chillr, th HOME scrn
is dislayd. This scrn dislays a visual rrsntation
of th chillr and a collction of data dtailing imortant
orations and aramtrs. whn th chillr is running,
the ow of chilled liquid is animated by the alternating
shads of color moving in and out of th i nozzls. Thrimary valus that nd to b monitord and controlld
ar shon on this scrn. Thy ar as follos:
Display Only:
Chilld Liquid Tmratur Laving
Chilld Liquid Tmratur Rturn
Condnsr Liquid Tmratur Rturn
Condnsr Liquid Tmratur Laving
Motor Run (LeD)
% Full Load Ams
Orating Hours
with th soft kys th orator is only on touch aay
from the 8 main screens that allow access to the major
information and comonnts of th chillr. Th 8 scrns
ar th SYSTEM, EVAPORATOR, CONDENSER, COM-
PRESSOR, OIL SUMP, MOTOR, SETPOINTS, and th
HISTORY. Also on th Hom Scrn is th ability to LOG
IN, LOG OUT and PRINT. Log In and Log Out is th mans
by hich diffrnt scurity lvls ar accssd.
Th SYSTEM scrn givs a gnral ovrvi of common
chillr aramtrs for both shlls. This is an nd vi ofth chillr ith a 3-D cutaay of both th shlls. Th fol-
loing can b vid from this scrn:
Display Only:
Discharg Tmratur
Chilld Liquid Tmratur Laving
Chilld Liquid Tmratur Rturn
Chilld Liquid Tmratur Stoint
evaorator prssur
evaorator Saturation Tmratur
Condnsr Liquid Tmratur Laving Condnsr Liquid Tmratur Rturn
Condnsr prssur
Condnsr Saturation Tmratur
Oil Tmratur
Diffrntial Oil prssur
% Full Load Ams
Currnt Limit
Slid Valv position
7/28/2019 Chiller - YR
7/56
JOHNSON CONTROLS
FORM 160.80-EG1 (808
Th EVAPORATOR scrn dislays a cutaay vi of
th chillr vaorator. All stoints rlating to th vao-
rator sid of th chillr ar maintaind on this scrn.
Animation of th vaoration rocss indicats hthr
th chillr is rsntly in RUN condition (bubbling) andliquid ow in the pipes is indicated by alternating shades
of color moving in and out of the pipes. Adjustable limits
on th lo atr tmratur stoints allo th chillr
to cycle on and off for greater efciency and less chiller
cycling. Th chillr cycls off hn th laving chilld
water temperature is below setpoint and is adjustable
from 1F (0.55C) blo to a minimum of 36F (2.22C).
Restart is adjustable from setpoint up to a max of 80F
(44.4C). The Panel will check for ow to avoid freeze-
up of the tubes. If ow is interrupted, shutdown will occur
aftr a minimum of to sconds. Th folloing can also
b rformd through this scrn:
Display Only:
Chilld Liquid Flo Sitch (On/Closd)
Chilld Liquid pum (Run/Sto)
evaorator prssur
evaorator Saturation Tmratur
Rturn Chilld Liquid Tmratur
Laving Chilld Liquid Tmratur
evaorator Rfrigrant Tmratur
Small Tmratur Diffrnc
Laving Chilld Liquid Tmratur Stoints
Stoint
Laving Chilld Liquid Tmratur Stoints
Rmot Rang
Laving Chilld Liquid Tmratur Stoints
Shutdon
Laving Chilld Liquid Tmratur Stoints
Shutdon Offst
Laving Chilld Liquid Tmratur Stoints
Rstart
Laving Chilld Liquid Tmratur Stoints
Rstart Offst
Ic Storag Activ (LeD)
Programmable:
Local Laving Chilld Liquid Tmratur Rang
Local Laving Chilld Liquid Tmratur Stoint
Laving Chilld Liquid Tmratur Cycling Offst
Shutdon
Laving Chilld Liquid Tmratur Cycling Offst
Rstart
Th CONDENSER scrn dislays a cutaay vi of th
chiller condenser. The liquid ow is animated to indicate
ow through the condenser. All setpoints relating to the
condnsr sid of th chillr ar maintaind on this scrn
with th ror accss lvl this scrn also srvs as agatay to controlling th Rfrigrant Lvl. Th folloing
can also b vid through this scrn:
Display Only:
Laving Condnsr Liquid Tmratur
Rturn Condnsr Liquid Tmratur
Condnsr prssur
Condnsr Saturation Tmratur
Small Tmratur Diffrnc
High prssur Sitch (On/Closd)
Condnsr Liquid Flo Sitch Condnsr Liquid pum (Run/Sto)
Programmable:
High prssur warning Thrshold
Frz warning (enabld/Disabld)
Frz Tim
Th VARIABLE ORIFICE CONTROL scrn, accssd
from th CONDeNSeR scrn in SeRVICe accss lvl
displays all of the applicable Variable Orice contro
aramtrs and allos a Srvic Tchnician to rogramth Dlta p stoint. Th Lo evaorator prssur and
Surhat Ovrrid LeDs ar locatd on this scrn
A view of the liquid ow piping to the chiller condenser
along with the solenoid ow control valve, is shown. The
folloing can also b rformd through this scrn:
Display Only:
Condnsr prssur
evaorator prssur
Dlta p (Condnsr evaorator)
Discharg Tmratur
Condnsr Saturation Tmratur
Surhat Tmratur
Lo evaorator Ovrrid (LeD)
Surhat Ovrrid (LeD)
Programmable:
Dlta p Stoint
7/28/2019 Chiller - YR
8/56
8 JOHNSON CONTROLS
OptiView Control Center- continued
Th COMPRESSOR scrn dislays a cutaay vi of
th chillr comrssor, rvaling th rotary scr, and
shos all conditions associatd ith th comrssor. Th
slid valv ositioning is animatd and ith th ror
Accss lvl, it can b manually controlld. Animation
of th comrssor rotors indicats hthr th chillr isrsntly in a RUN condition. This scrn also srvs as
a gatay to sub-scrns for calibrating th slid valv
or conguring the optional Hot Gas Bypass. From this
scrn you can vi th folloing:
Display Only:
Diffrntial Oil prssur
Oil Tmratur
Discharg Tmratur
Discharg Surhat
Slid Valv position
Oil Rturn Solnoid (LeD)
Full Load Ams (e.M. Startr Only)
phas A, B, C Currnt (SSS Only)
Programmable:
Slid Valv Load (Manual)
Slid Valv Hold (Manual)
Slid Valv Unload (Manual)
Slid Valv Auto
Max. Load Tmratur
Minimum Load FLA
Minimum Load Control Sourc
The HOT GAS BYPASSscrn, accssd from th COM-
PRESSOR scrn, dislays a ictorial of th byass lin
and solnoid valv location on th chillr. Th Hot Gas
ON and OFF Stoints ar rogrammd on this scrn
and systm aramtrs rtinnt to Hot Gas Byass
oration ar dislayd. An LeD illuminats hn th
Hot Gas solnoid is ON. If th chillr is quid ith
th Hot Gas Byass otion, oration must b nabld
on th OPERATIONS scrn. From this scrn you can
rform th folloing:
Display Only:
Slid Valv position
Rturn Chilld Liquid Tmratur
Laving Chilld Liquid Tmratur
Hot Gas Solnoid (LeD)
Programmable:
On Stoint
Off Stoint
Th SLIDE VALVE CALIBRATION scrn dislays a
cutaay vi of th chillr comrssor, rvaling th
rotary scr and slid valv and rovids th caability
of calibrating th slid valv. From this scrn, you can
rform th folloing:
Display Only:
Slid Valv Loading (LeD)
Slid Valv Unloading (LeD)
Calibration Mssag
Programmable:
Start Calibration
Cancl Calibration
Th OIL SEPARATOR scrn dislays a clos-u vi
of th chillr oil sarator/sum and rovids all th nc-
ssary stoints for maintaining th Variabl Sd Oil
pum (VSOP). This scrn also allos manual control
of th Frquncy Command snt to th VSOP. From this
scrn you can rform th folloing:
Display Only:
Discharg Tmratur
Oil Sum Tmratur
Discharg Surhat
Oil prssur
Filtr prssur
Sal prssur
Diffrntial Oil prssur
Diffrntial Filtr prssur
Diffrntial Sal prssur
Offst prssur
Oil Rturn Solnoid (LeD)
Lo Sarator Oil Lvl (LeD)
1.Th MOTOR soft ky on th HOMe scrn, hn
rssd, shos a ictur of ithr a YORK elctro-
Mchanical Startr or a Solid Stat Startr, dnding
on chiller conguration. The Programmable pulldown
dmand to automatically limit motor loading can b
usd to minimiz building dmand chargs. pulldon
7/28/2019 Chiller - YR
9/56
9JOHNSON CONTROLS
FORM 160.80-EG1 (808
time period control over four hours, and verication of
tim rmaining in ulldon cycl from dislay radout.
Sarat digital stoint for currnt limiting btn
30 and 100%.
ThELECTRO-MECHANICAL STARTER (EM) scrndislays a ictur of th startr and th folloing valus.
Th ons blo ar common among both offrings and th
valus ill b dislayd on both tys of startr scrns.
From this scrn you can rform th folloing:
Display Only:
Motor Run (LeD)
Motor Currnt % Full Load Ams
Currnt Limit Stoints
pulldon Dmand Tim Lft
Programmable:
Local Motor Currnt Limit
pulldon Dmand Limit
pulldon Dmand Tim
Th SOLID STATE STARTER (SSS) scrn dislays a
ictur of th startr and th folloing valus, hich ar
dislayd in addition to th common ons listd abov.
From this scrn, you can rform th folloing:
Display Only:
Inut por
kw Hours
Startr Modl
Voltag phas A, B, C
Currnt phas A, B, C
Tmratur phas A, B, C
Programmable:
Full Load Ams
Voltag Rang
Starting Currnt
On SCR
Shortd SCR
kwH Rst
Th SETPOINTS scrn rovids a convnint location
for rogramming th most common stoints involvd
in th chillr control. Th Stoints ar shon on othr
individual scrns, but to cut don on ndlss sarch-
ing, thy can all b found on this scrn. This scrn also
serves as a gateway to a sub-screen for dening the setup
of gnral systm aramtrs. From this scrn you can
rform th folloing:
Display Only: Laving Chilld Liquid Tmratur Stoint
Laving Chilld Liquid Tmratur Cycling
Shutdon
Laving Chilld Liquid Tmratur Cycling
Rstart
Currnt Limit Stoint
Programmable:
Local Laving Chilld Liquid Tmratur Rang
Local Laving Chilld Liquid Tmratur Stoint
Laving Chilld Liquid Tmratur Cycling Offst
Shutdon
Laving Chilld Liquid Tmratur Cycling Offst
Rstart
Rmot Analog Inut Rang
Local Motor Currnt Limit
pulldon Dmand Limit
pulldon Dmand Tim
Th SETUP is the top level of the general conguration aramtrs. It allos rogramming of th tim and
date, along with specications as to how the time will be
displayed. In addition, the chiller conguration as deter
mined by the micro board program jumpers and program
sitchs is dislayd. From this scrn you can rform
th folloing:
Display Only:
Chilld Liquid pum Oration (Dislays Standardo
Enhanced)
Rfrigrant Slction (Dislays R-22orR-134a)
Anti-Rcycl (Dislays DisabledorEnabled)
por Failur Rstart (Dislays Manual orAuto-
matic)
Liquid Ty (Dislays WaterorBrine)
Programmable:
St Dat
St Tim
Clock (enabld/Disabld)
12/24 Hour
7/28/2019 Chiller - YR
10/56
10 JOHNSON CONTROLS
OptiView Control Center- continued
The folloing six subscreens can be accessed from
the SETUP screen:
Th SCHEDULE scrn contains mor rogrammabl
valus than a normal dislay scrn. each rogrammabl
value is not linked to a specic button; instead, the selectky is usd to nabl th cursor arros and chck ky to
rogram th Start/Sto tims for any day of th k u
to 6 eeks in advance. The user has the ability to dene
a standard st of Start/Sto tims that ar utilizd vry
k or scify xctions to crat a scial k.
Programmable:
exction Start/Sto Tims
Schdul (enabl/Disabl)
Rat Sunday Schdul
Standard wk Start/Sto Tims
Rst All exction Days
Slct
Th USER screen allows denition of the language for the
chiller to display and denes the unit of measure.
Programmable:
Systm Languag
english/Mtric Units
Th COMMS screen allows the user to dene commu-nications aramtrs.
Programmable:
Chillr ID
COM 2 Baud Rat
COM 2 Data Bit(s)
COM 2 parity Bit(s)
COM 2 Sto Bit(s)
printr Baud Rat
printr Data Bit(s)
printr parity Bit(s)
printr Sto Bit(s)
Th PRINTER screen permits the user to dene com-
munications paramtrs for th printr.
Display Only
Tim Rmaining Until Nxt print
Programmable
Log Start Tim
Outut Intrval
Automatic printr Logging (enabld/Disabld)
print Ty
print Rort
print All Historis
Th SALES ORDER screen allows denition of the order
aramtrs. Note: This information is loaded at the factory
or by the installation service technician.
Display Only
Modl Numbr
panl Srial Numbr
Chillr Srial Numbr
YORK Ordr Numbr
Systm Information
Condnsr and evaorator Dsign Load Information
Namlat Information
Th OPERATIONS screen permits denition of param-
eters pertaining to operation of the chiller. What is dened
is hthr th control of th chillr ill b Local, Digital R-
mot, Analog Rmot, Modm Rmot or ISN Rmot.
Programmable
Control Sourc
Th HISTORY scrn allos th usr to bros throughth last tn faults; ithr safty or cycling shutdons ith
th conditions, hil th chillr is running or stod.
Th faults ar color codd for as in dtrmining
th svrity at a glanc, rcording th dat, tim and
dscrition. (S Dislay Mssags for Color Cod
manings.)
Display Only
Last Normal Shutdon
Last Fault whil Running
Last Tn Faults
Programmable:
print History
print All Historis
By rssing th VIEw DETAILS ky you ill mov to th
HISTORY DETAILS scrn. From ths scrns you
ar abl to s an on-scrn rintout of all th systm
aramtrs at th tim of th slctd shutdon.
7/28/2019 Chiller - YR
11/56
11JOHNSON CONTROLS
FORM 160.80-EG1 (808
Display Only:
History printout
Programmable:
pag U pag Don
print History
Also undr th HISTORY scrn is th TRENDING
scrn, accssibl by th ky markd th sam. On this
scrn, u to six orator-slctd aramtrs, slctd
from a list of ovr 140, can b lottd in an X/Y grah
format. Th grah can b customizd to rcord oints
onc vry scond u to onc vry hour. Thr ar
to tys of charts that can b cratd: singl scrn,
or continuous scrn. Th singl scrn collcts data for
on scrn idth (450 data oints across th X-axis), thnstos. Th continuous scrn ks collcting th data,
but th oldst data dros off th grah from lft to right
at the next data collection interval. For ease of identica-
tion, ach lottd aramtr, titl and associatd Y-axis
labling is color coordinatd.
Display Only:
This scrn allos th usr to vi th grahical
trnding of th slctd aramtrs and is a gatay
to th grah stu scrns.
Programmable: Start
Sto
Y-axis
X-axis
Th TREND SETUP screen is used to congure the trend-
ing scrn. Th aramtrs to b trndd ar slctd
from th Trnd Common Slots scrn, accssd from
th Slot Numbrs button or th Mastr Slot Numbrs
List found in th Orating Manual. Th intrval at hich
all th aramtrs ar samld is slctd undr th
Collction Intrval button. Th data oint minimum andmaximum values may be adjusted closer to increase
viing rsolution.
Programmable:
Chart Ty (slct continuous orone screen)
Collction Intrval
Slct
Data point Slot Numbr (1 - 6)
Data point Min (1 - 6)
Data point Max (1 - 6)
Th TREND COMMON SLOTS scrn dislays th Mas
tr Slot Numbrs List of th monitord aramtrs.
Display Only:
Slot Numbrs
Programmable:
pag U
pag Don
DISPLAY MESSAGES
Th Control Cntr continuously monitors th oratingsystm, dislaying and rcording th caus of any shut
dons (Safty, Cycling or Normal). Th condition of th
chillr is dislayd at th Systm Status lin that contains
a mssag dscribing th orating stat of th chillr
hthr it is stod, running, starting or shutting don
A Systm Dtails Lin dislays warning, Cycling, Safty
Start Inhibit and othr mssags that rovid furth
dtails of th Status Bar mssags. Mssags ar color-
codd: Grn Normal Orations; Yllo warnings
Orang Cycling Shutdons; and Rd Safty Shut
dons to aid in idntifying roblms quickly.
Status mssags includ: Systm Rady To Start
Cycling Shutdon Auto Rstart
Safty Shutdon Manual Rstart
Start Squnc Initiatd
Systm Run (ith countdon timrs)
Start Inhibit
Slid Valv Closing Bfor Shutdon
Systm Lockout Dlay
Run Mssags includ:
Laving Chilld Liquid Control
Motor pulldon Limit
Motor High Currnt Limit
Start Inhibit Mssags includ:
Anti-Rcycl XX min/sc.
Slid Valv position >30%
Motor Currnt >15% FLA
LCSSS High-Tmratur phas X - Stod
7/28/2019 Chiller - YR
12/56
1 JOHNSON CONTROLS
warning Mssags includ:
Ral Tim Clock Failur
Stoint Ovrrid
Condnsr High prssur Limit
evaorator Lo prssur Limit
Frz Thrat From Orating Chillr
Frz Thrat, Condnsr Flo Sitch On
Lo Discharg Surhat Limit
Lo Discharg Surhat Dtctd
Maximum Load Load Limit
Minimum Load Load Limit
Oil Dirty Filtr
Oil High Tmratur
Slid Valv Uncalibratd
Routin Shutdon Mssags Includ: Rmot Sto
Local Sto
plac Comrssor Sitch In Run position
Cycling Shutdon Mssags Includ:
Multiunit Cycling Contacts On
Systm Cycling Contacts On
Control panl por Failur
Laving Chilld Liquid Lo Tmratur
Laving Chilld Liquid Flo Sitch On
Condnsr Flo Sitch On
Motor Controllr Contacts On
Motor Controllr Loss of Currnt
por Fault
Control panl Schdul
Solid State Starter Only (LCSSS)
Initialization Faild
Srial Communications
Rqusting Fault Data
Sto Contacts On
por Fault
Lo phas (X) Tmratur Snsor
Run Signal
Invalid Currnt Scal Slction
phas Lockd Loo
Lo Suly Lin Voltag
High Suly Lin Voltag
Logic Board procssor
Logic Board por Suly
phas Loss
Safty Shutdon Mssags includ:
evaorator Lo prssur
evaorator Lo prssur Smart Frz
evaorator Transducr or Laving Liquid prob
evaorator Transducr or Tmratur Snsor
Condnsr High prssur Contacts On
Condnsr High prssur
Condnsr prssur Transducr Out of Rang
Auxiliary Safty Contacts Closd
Discharg High Tmratur
Discharg Lo Tmratur
Oil High Tmratur
Oil Lo Diffrntial prssur
Oil Lo Diffrntial Sal prssur
Oil or Condnsr Transducr error
Oil Cloggd Filtr
Oil High prssur Oil Sarator Lo Lvl
Control panl por Failur
watchdog Softar Rboot
Solid Stat Startr Only (LCSSS)
Shutdon Rqusting Fault Data . . .
High Instantanous Currnt
High phas (X) Hatsink Tmratur Running
105% Motor Currnt Ovrload
Motor or Startr Currnt Imbalanc
On SCR phas Rotation
OptiView Control Center- continued
7/28/2019 Chiller - YR
13/56
1JOHNSON CONTROLS
FORM 160.80-EG1 (808
Mechanical Specifcations
STANDARD UNIT
General
Th YORK Millnnium YS Rotary Scr Chillr is com-
ltly factory-ackagd, including vaorator, condnsr,
sub-coolr, oil sarator, comrssor, motor, lubricationsystm, control cntr and rfrigrant isolation valvs.
Th factory ackag consists of a lak tight dsign. All
units shi as standard ith a full charg of rfrigrant
and oil. Units can also b shid in sctions (otional)
to accommodate job site requirements.
The services of a Johnson Controls factory-trained, eld
srvic rrsntativ ar incurrd to survis or rform
the nal leak testing, charging, the initial start-up, and
concurrnt orator instructions.
Compressor
Th Frick Rotary Tin Scr Comrssor is nginrd
and constructd to mt th xact rquirmnts of th
industrial rfrigration markt. It utilizs stat-of-th-art
tchnology to rovid th most rliabl and nrgy-f-
cient compressor available at all operating conditions.
Th comrssor orats at 3750 RpM for 60 Hrtz and
2975 RpM for 50 Hrtz. Th comrssor housing is mad
of cast iron, rcision-machind to rovid minimal clar-
anc for th rotors. Comrssor housing has a dsign
orking rssur (Dwp) of 300 pSIG (2068 kpa) mini-
mum, and hydro-tstd at 544 pSIG (3751 kpa).
Th rotors ar manufacturd from forgd stl and usasymmetric proles. The compressor incorporates a
comlt anti-friction baring dsign for rducd or
and incrasd rliability. Four sarat cylindrical rollr
barings handl radial loads. To 4-oint angular contact
ball barings handl axial loads. Togthr, thy maintain
accurat rotor ositioning at all rssur ratios, thrby
minimizing blow-by and maintaining efciency.
A chck valv is installd in th comrssor discharg
housing (suction housing for S4 and S5 comrssor) to
rvnt comrssor rotor back sin bcaus of systm
rfrigrant rssur gradints during shutdon.
Th on-driv comrssor shaft sal consists of rci-
sion cramic sal facs, mtallic bllos, rotating mmbr,
PTFE C-Ring static seal, and multi-port oil injection ring.
Th sal cavity is maintaind at intrmdiat rssur
ith its oil dischargd to th oil drain from th comrssor.
Combining intermediate pressure with direct oil injection
rovids cool, non-foaming lubricant to th sal assuring
a longr lifsan.
Capacity Control
Caacity control is achivd by us of a slid valv hich
rovids fully modulating caacity control from 100% to
10% of full load. Th slid valv is actuatd by oil rssur
controlld by xtrnal solnoid valvs via th OtiVi
Control Cntr.
Oil SeparatorTh oil sarator is a horizontal dsign ithout moving
arts. effctiv oil saration is achivd by gravity dro
out of oil from th rfrigrant gas as vlocity dcrass
uon ntring th sarator, and by msh ads to rovid
nal gas/oil separation before gas enters the condenser
Th oil sarator is dsignd for 345 pSIG (2378 kpa
dsign orking rssur, tstd at 517 pSIG (3565 kpa)
and stamd in accordanc ith ASMe Boilr and prs
sur Vssl Cod, Sction VIII - Division 1.
each vssl has a rfrigrant rlif dvic(s) st at 300
pSIG (2068 kpa). In addition to th sring-loadd, r-sat
ing-ty rlif valvs sizd for rssur vssl volum
ach unit is quid ith a rutur disk. This rutur
disk is abl to rliv th ntir uming caacity of th
comrssor if lctronic saftis fail, roviding rotc-
tion for rorty and rsonnl. This dvic is st for
345 pSIG (2378 kpa). Altrnativly, th shll sid may
b dsignd to euroan prssur Vssl Cods and
stamd in accordanc ith A.D. Mrkblattr or othr
euroan prssur Vssl dsign cod. whn rquird
by th rfrigration safty cod, ach vssl has a dua
rfrigrant rlif dvic(s).
LubricationTh main unit oil rsrvoir is locatd in th oil sarator
Th comrssor also has an oil rsrvoir locatd at th
rotor barings to rovid lubrication during start-u, coa
don, and in th vnt of a or failur. During ora
tion, system pressure differential provides proper oil ow
ithout th nd of an auxiliary oil um. This minimizs
nrgy consumtion.
The chiller is shipped with a 3 Micron absolute oil lter
nsuring a clan oil systm and surior comrssor
life. An external, replaceable cartridge oil lter is supplied
ith manual isolation sto valvs for as of srvicing
An optional dual oil lter housing with isolation valves is
availabl on all units. This allos immdiat sitching
from one lter to the other, eliminating downtime during
lter changes. The off-line oil lter can be changed during
chillr oration.
A 500 att (115 volt - 1-has - 60/50Hz) immrsion
oil hatr is locatd in th oil sarator rsrvoir, tm-
perature actuated to efciently remove refrigerant from
th oil. Oil hatr or suly is factory ird from
th control anl. A factory-id rfrigrant-coold oi
7/28/2019 Chiller - YR
14/56
1 JOHNSON CONTROLS
coolr is rovidd as standard. No auxiliary atr i-
ing is rquird. An oil ductor automatically rmovs oil
hich may hav migratd to th vaorator and rturns
it to th comrssor.
MOTOR DRIVELINETh comrssor motor is an on dri-roof, squirrl
cag, induction ty constructd to Johnson Controls
design specications. 60 Hertz motors operate at 3750
RpM; 50 Hrtz motors orat at 2975 RpM. Th on
motor is rovidd ith a D-Flang and is factory-mountd
to a cast-iron adator mountd on th comrssor. This
uniqu dsign allos th motor to b rigidly could to
th comrssor to rovid factory alignmnt of motor and
comrssor shafts.
Motor driv shaft is dirctly connctd to th comrssor
shaft with a exible disc coupling. Coupling has all metal
construction ith no aring arts to assur long lif.
Additionally, no lubrication is rquird roviding lo
maintnanc.
For units utilizing rmot lctro-mchanical startrs,
a larg stl trminal box ith gasktd front accss
cover is provided for eld connected conduit. There are
six trminals (thr for mdium voltag) brought through
th motor casing into th trminal box. Jumrs ar fur-
nishd for thr-lad ty of starting. Motor trminal lugs
ar not furnishd. Ovrload/ovrcurrnt transformrs ar
furnishd ith all units. For units furnishd ith factory-
ackagd Solid Stat Startrs, rfr to th Accssorisand Modications section (page 17).
HEAT EXCHANGERS
Shells
evaorator and condnsr shlls ar fabricatd from
rolld carbon stl lats ith fusion ldd sams.
Carbon stl tub shts, drilld and ramd to accom-
modat th tubs, ar ldd to th nd of ach shll.
Intrmdiat tub suorts ar fabricatd from carbon
stl lats, drilld and ramd to liminat shar dgs,
and sacd no mor than four ft aart. Th rfrigrant
sid of ach shll is dsignd, tstd, and stamd in
accordanc ith ASMe Boilr and prssur Vssl Cod,
Sction VIII Division I, or othr rssur vssl cod
as aroriat.
Tubes
Heat exchanger tubes are state-of-the-art, high efciency,
xtrnally and intrnally nhancd ty to rovid o-
timum rformanc. Tubs in both th vaorator and
condnsr ar 3/4 O.D. cor alloy and utiliz th
skip-n design, providing a smooth internal and external
surfac at ach intrmdiat tub suort. This rovids
xtra all thicknss (u to tic as thick) and non-ork
hardnd cor at th suort location, xtnding th
lif of th hat xchangrs. each tub is rollr xandd
into th tub shts roviding a lak-roof sal, and is
individually rlacabl.
Evaporator
The evaporator is a shell and tube, ooded type heat ex-
changr. A distributor trough rovids uniform distribution
of rfrigrant ovr th ntir shll lngth to yild otimum
heat transfer. A suction bafe or aluminum mesh elimina-
tors ar locatd abov th tub bundl to rvnt liquid
rfrigrant carryovr into th comrssor. A 1-1/2 liquid
lvl sight glass is convnintly locatd on th sid of th
shll to aid in dtrmining ror rfrigrant charg. Th
vaorator shll contains a dual rfrigrant rlif valv
arrangmnt st at 180 pSIG (1241 kpa); or singl-rlif
valv arrangmnt, if th chillr is sulid ith th o-
tional rfrigrant isolation valvs. A 1 rfrigrant chargingvalv is rovidd.
Condenser
Th condnsr is a shll and tub ty, ith a discharg
gas bafe to prevent direct high velocity impingement on
the tubes. The bafe is also used to distribute the refrig-
erant gas ow properly for most efcient heat transfer.
An intgral sub-coolr is locatd at th bottom of th
condnsr shll roviding highly ffctiv liquid rfrigr-
ant subcooling to provide the highest cycle efciency. The
condnsr contains dual rfrigrant rlif valvs st at
235 pSIG (1620 kpa).
water Boxes
Th rmovabl atr boxs ar fabricatd of stl. Th
dsign orking rssur is 150 pSIG (1034 kpa) and th
boxs ar tstd at 225 pSIG (1551 kpa). Intgral stl
water bafes are located and welded within the water box
to rovid th rquird ass arrangmnts. Stub-out atr
nozzl connctions ith ANSI/AwwA C-606 groovs ar
ldd to th atr boxs. Ths nozzl connctions
ar suitabl for ANSI/AwwA C-606 coulings lding or
anges, and are capped for shipment. Plugged 3/4 drain
and vnt connctions ar rovidd in ach atr box.
REFRIGERANT FLOw CONTROL
Th YS Chillr is quid ith a rfrigrant mtring
device consisting of a xed orice and bypass solenoid
valve, which automatically adjusts to all real-world operat-
ing conditions. This control ensures proper refrigerant ow
to th vaorator ovr a id rang of orating condi-
tions, including thrmal storag alications and chilld
atr rst. Valv oration is rogrammabl and can
be customized for a specic application via the control
anl kyboard.
Mechanical Specifcations - continued
7/28/2019 Chiller - YR
15/56
15JOHNSON CONTROLS
FORM 160.80-EG1 (808
REFRIGERANT ISOLATION
Th condnsr shll srvs as a rfrigrant rcivr
to stor th systm charg during srvicing. Manually
oratd isolation valvs ar locatd at th inlt and
outlt of th condnsr. Valvs ar also rovidd to fa-
cilitat rmoval of th rfrigrant from th systm hnncssary.
OPTIVIEw CONTROL CENTER
General
Th chillr is controlld by a stand-alon microrocssor-
basd control cntr. Th chillr control anl rovids
control of chillr oration and monitoring of chillr sn-
sors, actuators, rlays and sitchs.
Control Panel
Th control anl includs a 10.4 inch diagonal color liquidcrystal dislay (LCD) surroundd by soft kys, hich
are redened based on the screen displayed at that time,
mountd in th middl of a kyad intrfac and installd
in a lockd nclosur. Th scrn dtails all orations
and aramtrs, using a grahical rrsntation of th
chiller and its major components. Panel verbiage is avail-
abl in othr languags as an otion ith english alays
availabl. Data can b dislayd in ithr english or Mtric
units. Smart Frz point protction ill run th chillr at
36F (2.22C) laving chilld atr tmratur and not
xrinc nuisanc tris on lo atr tmratur. Th
sohisticatd rogram and snsor monitors th chillr a-
tr tmratur to rvnt frz-u. whn ndd, HotGas Byass is availabl as an otion. Th anl dislays
countdon timr mssags so th orator knos hn
functions ar starting and stoing. evry rogrammabl
oint has a o-u scrn ith th rangs includd, so
th chillr can not b rogrammd to orat outsid of
its dsign limits.
Th control anl includs a thrmal ic storag control
mod hich nhancs systm rformanc during ic
building oration hn comard to standard cooling
logic. In thrmal storag control mod, th chillr ill
orat at 100% load until th stoint shutdon tm-
perature is reached. To add greater operating exibility
and liminat unncssary chillr cycling, to diffrnt
Lo watr (Liquid) Tmratur Rstart Thrsholds ar
rogrammabl, on for th ic mod and on for th stan-
dard cooling mod. Th chillr has th caability to rmain
in th standard control mod for tmraturs btn
20F to 70F (6.7C to 21.1C) for alications involving
a rocss cooling duty that rquirs laving chilld liquid
tmratur stoint control.
The chiller control panel also provides:
1. Systm orating information including:
Rturn and Laving Chilld watr Tmratur
Rturn and Laving Condnsr watr Tm
ratur
evaorator and Condnsr Saturation Tm
ratur
Oil prssur at Comrssor and Oil Filtr
Diffrntial
prcnt Motor Currnt
evaorator and Condnsr Saturation Tm
ratur
Comrssor Discharg Tmratur
Oil Tmratur
prcnt Slid Valv position
Orating Hours
Numbr of Unit Starts
2. Digital programming of Stoints Through Th Uni
vrsal Kyad Including:
Laving Chilld watr Tmratur
prcnt Currnt Limit
pull-Don Dmand Limiting
Six-wk Schdul For Starting and Stoing
Th Chillr, pums and Tor
Rmot Rst Tmratur Rang
3. Status Mssags Indicating:
Systm Rady To Start
Systm Running
Systm Coastdon
Systm Safty Shutdon Manual Rstart
Systm Cycling Shutdon Auto Rstart
Systm prlub
Start Inhibit
4. Th txt dislayd ithin th systm status and sys
tem details eld is displayed as a color-coded mes
sag to indicat svrity: rd for safty fault; orang
for cycling faults; yllo for arnings; and grn fonormal mssags.
5. Safty shutdons ar nunciatd through th dislay
and th status bar, and consist of systm status, sys
tm dtails, day, tim, caus of shutdon, and ty o
restart required. Safety shutdowns with a xed speed
driv includ:
evaorator Lo prssur
evaorator Lo prssur - Smart Frz
evaorator Transducr or Laving Liquid
prob
7/28/2019 Chiller - YR
16/56
16 JOHNSON CONTROLS
evaorator Transducr or Tmratur Sn-
sor
Condnsr High prssur Contacts On
Condnsr High prssur
Condnsr prssur Transducr Out Of
Rang
Auxiliary Safty Contacts Closd
Discharg High Tmratur
Discharg Lo Tmratur
Oil High Tmratur
Oil Lo Diffrntial prssur
Oil Lo Diffrntial Sal prssur
Oil Or Condnsr Transducr error
Oil Cloggd Filtr
Oil High prssur
Oil Sarator Lo Lvl
Control panl por Failur
watchdog Softar Rboot
5.1 Safty shutdons ith a Solid Stat Startr (LCSSS)
includ:
Shutdon - Rqusting Fault Data...
High Instantanous Currnt
High phas (X) Hatsink Tmratur - Run
ning
105% Motor Currnt Ovrload
Motor Or Startr Currnt Imbalanc
phas (X) Shortd SCR
On SCR
phas Rotation
6. Cycling shutdons nunciatd through th dislay
and th status bar, and consists of systm status,
systm dtails, day, tim, caus of shutdon, and
ty of rstart rquird.
Cycling shutdons ith a fixd sd driv in-
clud:
Multiunit Cycling - Contacts On
Systm Cycling - Contacts On
Control panl - por Failur
Laving Chilld Liquid Lo Tmratur
Laving Chilld Liquid Flo Sitch On
Condnsr - Flo Sitch On
Motor Controllr Contacts On
Motor Controllr Loss Of Currnt
por Fault
Mechanical Specifcations - continued
Control panl Schdul
6.1 Cycling shutdons ith a Solid Stat Startr (LCSSS)
includ:
Initialization Faild
Srial Communications Rqusting Fault Data
Sto Contacts On
por Fault
Lo phas (X) Tmratur Snsor
Run Signal
Invalid Currnt Scal Slction
phas Lockd Loo
Lo Suly Lin Voltag
High Suly Lin Voltag
Logic Board procssor Logic Board por Suly
phas Loss
7. Scurity accss to rvnt unauthorizd chang of
stoints, to rmit local or rmot control of th
chillr, and to allo manual oration of th rrota-
tion vans and oil um. Accss is through ID and
password recognition, which is dened by three
diffrnt lvls of usr comtnc: vi, orator,
and srvic.
8. Trnding data ith th ability to customiz oints of
onc vry scond to onc vry hour. Th anlill trnd u to 6 diffrnt aramtrs from a list of
ovr 140, ithout th nd of an xtrnal monitoring
systm.
9. Th orating rogram is stord in non-volatil
mmory (epROM) to liminat rrogramming th
chillr du to AC or failur or battry discharg.
programmd stoints ar rtaind in lithium bat-
try-backd RTC mmory for a minimum of 11 yars
ith or rmovd from th systm.
10. A fusd connction through a transformr in th
comrssor motor startr to rovid individual
ovr-currnt rotctd or for all controls.
11. A numbered terminal strip for all required eld inter-
lock iring.
12. An RS-232 ort to outut all systm orating data,
shutdon/cycling mssag, and a rcord of th last
10 cycling or safety shutdowns to a eld-supplied
rintr. Data logs to a rintr at a st rogrammabl
intrval. This data can b r-rograrnmd to rint
from 1 minut to 1 day.
13. Th caability to intrfac ith a building automation
7/28/2019 Chiller - YR
17/56
1JOHNSON CONTROLS
FORM 160.80-EG1 (808
systm to rovid:
rmot chillr start and sto
remote leaving chilled liquid temperature adjust
remote current limit setpoint adjust
rmot rady to start contacts
safty shutdon contacts
cycling shutdon contacts
run contacts
CODES AND STANDARDS
ASMe Boilr and prssur Vssl Cod Sction
Vlll Division 1.
ARI Standard 550/590 c/U.L. Undrritrs Laboratory
ASHRAe 15 Safty Cod for Mchanical Rfrigra-
tion
ASHRAe Guidlin 3 Rducing emission of Halog-
natd Rfrigrants in Rfrigration and Air-Condition-
ing equimnt and Systms
NeC National elctrical Cod
OSHA Occuational Safty and Halth Act
A.D. Mrkblattr
ISOLATION MOUNTING
Th unit is rovidd ith four vibration isolation mounts
consisting of 1 (25.4 mm) thick norn isolation ads
for eld mounting under the steel mounting pads located
on th tub shts.
REFRIGERANT CONTAINMENT
Th standard unit has bn dsignd as a comlt and
comact factory ackagd chillr. As such, it has mini
mum joints from which refrigerant can leak. The entire
assmbly has bn thoroughly lak tstd at th factory
rior to shimnt. Th YORK chillr includs srvic
valvs convnintly locatd to facilitat transfr of rfrig
rant to a rmot rfrigrant storag/rcycling systmOtional condnsr isolation valvs rmit storag of th
charg in th condnsr.
PAINT
extrior surfacs ar rotctd ith on coat of Carib-
bean blue, durable alkyd-modied, vinyl enamel, ma
chinry aint.
7/28/2019 Chiller - YR
18/56
18 JOHNSON CONTROLS
Accessories and Modifcations
SOLID STATE STARTER
Th Solid Stat Startr is a rducd voltag startr that
controls and maintains a constant current ow to the motor
during startu. It is comact and mountd on th chillr at
th motor trminals. por and control iring is factory
sulid. Availabl for 200-600 volts, th startr nclosur
is NeMA-1 ith a hingd accss door ith lock and ky.
elctrical lugs for incoming or iring ar rovidd.
Standard faturs includ: digital radout at th OtiVi
Control Cntr of th folloing:
Display Only:
3-has voltag A, B, C
3-has currnt A, B, C
Inut or (kw)
kw Hours
Startr Modl
Motor Run (LeD)
Motor Currnt % Full Load Ams
Currnt Limit Stoints
pulldon Dmand Tim Lft
Programmable:
Local Motor Currnt Limit
pulldon Dmand Limit
pulldon Dmand Tim
Othr faturs includ: lo lin voltag; 115-volt controltransformr; thr-lg snsing ovrloads; has rotation
and singl-has failur rotction; high tmratur
safty rotction; motor currnt imbalanc and undrvolt-
ag saftis; on and clos SCR rotction; momntary
or intrrution rotction. Th LCSSS is coold by a
closd-loo, frsh atr circuit consisting of a atr-to-
atr hat xchangr and 1/25 Hp circulating um. All
intrconncting atr iing is factory installd and ratd
for 150 pSIG orking rssur. Optional unit-mountd
circuit brakr includs ground fault rotction and
rovids 65,000 am short-circuit ithstand rating in ac-
cordanc ith UL Standard 508. A non-fusd disconnct
sitch is also availabl. Both otions ar adlockabl.
BAS REMOTE CONTROL
A communication intrfac rmitting comlt xchang
of chillr data ith any BAS systm is availabl ith
otional ISN translator. ISN translator also allos BAS
systm to issu commands to th chillr to control its
oration. ISN translators com in to modls, controlling
u to four chillrs and ight chillrs rsctivly.
FACTORY INSULATION OF COOLER
Factory-applied thermal insulation of the exible, closed-
cll lastic ty, 3/4 (19mm) thick is attachd ith va-
por-proof cement to the evaporator shell, ow chamber,
vaorator tub shts, suction connction, and (as
ncssary) to th auxiliary tubing. Not includd is th
insulation of atr boxs and nozzls. This insulation
ill normally rvnt condnsation in nvironmnts ith
rlativ humiditis u to 75% and dry bulb tmraturs
ranging from 50 to 90F (10 to 32C). 1-1/2 (38mm)
thick insulation is also availabl for rlativ humiditis u
to 90% and dry bulb tmraturs ranging from 50 to
90F (10 to 32C).
wATER FLANGES
Four 150 Ib. ANSI raised-face anges, for condenser and
vaorator atr connctions, ar factory ldd to atr
nozzles. Companion anges, bolts, nuts and gaskets are
not includd.
SPRING ISOLATION MOUNTING
Sring Isolation mounting is availabl instad of standard
isolation mounting pads when desired. Four level-adjust-
ing/sring-ty vibration isolator assmblis ith non-skid
pads are provided with mounting brackets for eld instal-lation. Isolators ar dsignd for on-inch (25.4 mm)
deection.
wATER FLOw SwITCHES
Paddle-type, vapor-proof water ow switches suitable
for 150 sig (1034 Kpa) Dwp for chilld and condnsr
atr circuits. Sitch for 115V-1-50/60 Hz srvic. A
chilled water ow switch is required. Condenser water
ow switch is optional.
SEqUENCE CONTROL KIT
For to, thr or four units ith chilld atr circuits con-
nctd in sris or aralll, th kit consists of rturn atr
thrmostat, lad-lag slctor sitch for squnc starting,
and tim dlay rlay, ith NeMA-1 nclosurs, dsignd
for 115V-1-50/60 Hz.
7/28/2019 Chiller - YR
19/56
19JOHNSON CONTROLS
FORM 160.80-EG1 (808
STARTER FIELD INSTALLED
A eld installed, electro-mechanical compressor motor
startr is availabl, slctd for ror siz and ty for
job requirements and in accordance with Johnson Controls
enginring Standard R-1079 for Startrs.
MARINE wATER BOXES
Marin atr boxs allo srvic accss for claning of
th hat xchangr tubs ithout th nd to brak th
atr iing. Boltd-on covrs ar arrangd for conv-
nint accss. ANSI/AwwA C-606 nozzl connctions ar
standard; anges are optional. Marine water boxes are
availabl for condnsr and/or vaorator.
KNOCK-DOwN SHIPMENT
The chiller can be shipped knocked-down into majo
assmblis (vaorator, condnsr, drivlin, tc.) as
rquird to rig into tight sacs. This is articularly conv-
nint for xisting buildings hr quimnt room accss
dos not allo rigging a factory ackagd chillr.
REFRIGERANT STORAGE/RECYCLING SYSTEM
A rfrigrant storag/rcycling systm is a slf-containd
ackag consisting of a rfrigrant comrssor ith oi
separator, storage receiver, water-cooled condenser, lte
drir and ncssary valvs and hoss to rmov, rlac
and distill rfrigrant. All ncssary controls and safty
dvics ar a rmannt art of th systm. Tyically no
rquird if unit isolation valvs ar rovidd.
7/28/2019 Chiller - YR
20/56
0 JOHNSON CONTROLS
Unit Components
7/28/2019 Chiller - YR
21/56
1JOHNSON CONTROLS
FORM 160.80-EG1 (808
29040A
OIL SepARATOR
MOTOR
TeRMINAL
BOX
CONDeNSeR
REAR VIEw
7/28/2019 Chiller - YR
22/56
JOHNSON CONTROLS
Th folloing is a usrs guid in th alication and
installation ofMillennium Chillrs, and ill nsur th rli-
ability and troubl-fr lif for hich this quimnt as
dsignd. whil this guid is dirctd toards normal,
atr-chilling alications, th Johnson Controls sals
rrsntativs can rovid comlt rcommndationson othr tys of alications.
Location
Millnnium Chillrs ar virtually vibration-fr and gn-
rally can b locatd at any lvl in a building hr
th construction ill suort th total systm orating
ight.
The unit site must be a oor, mounting pad or foundation
hich is lvl ithin 1/4 (6.4 mm) and caabl of su-
orting th orating ight of th chillr.
Application Data
Sufcient clearance to permit normal service and mainte-
nanc ork should b rovidd all around and abov th
unit. Additional sac should b rovidd at on nd of
th unit to rmit claning of vaorator and condnsr
tubs as rquird. A dooray or othr rorly locatd
oning may b usd.
Th chillr should b installd in an indoor location
hr tmraturs rang from 40F to 110F (4.4C to
43.3C).
water Circuits
Flow Rate For normal atr chilling duty, vaorator
ow rates are permitted at water velocity levels in the
hat xchangrs tubs of btn 3 ft./scond and 12
ft./second (0.91 m/s and 3.66 m/s). Condenser ow rates
ar rmittd btn 3.33 ft./sc. and 12 ft./sc. (1.01
m/s and 3.66 m/s). Variable ow applications are possible,
TABLE 1 wATeR FLOw RATe LIMITS GpM (L/s)
shELL
CodE
EVaPorator CondEnsEr
Pass MInIMuM MaXIMuM MInIMuM MaXIMuM
Ba
1 308 -19.4 1173 -74 399 -25.2 1435 -90.5
2 147 -9.3 586 -37 209 -13.2 751 -47.4
3 97 -6.1 387 -24.4
BB
1 412 -25 8/9 1572 -99.2 510 -32 1/5 1830 -115.5
2 197 -12 2/5 786 -49.6 264 -16 2/3 948 -59 4/5
3 130 -8 1/5 516 -32.6
Ca
1 535 -33 4/5 2041 -128.8 677 -42.7 2438 -153 4/5
2 256 -16 1/5 1020 -64.4 355 -22.4 1277 -80 3/5
3 171 -10 4/5 680 -42 8/9
CB
1 700 -44.2 2675 -168.8 880 -55.5 3164 -80.6
2 335 -21.1 1337 -84.4 455 -28.7 1639 -103.4
3 223 -14.1 891 -56.2
da
1 664 -41.9 2534 -159.9 1215 -76.7 4376 -276.1
2 317 -20 1267 -79.9 630 -39.8 2269 -143.2
3 212 -13.4 844 -53.3
dB
1 943 -59.5 3602 -227.3 1595 -100.6 5740 -362.2
2 451 -28.5 1793 -113.1 820 -51.7 2950 -186.1
3 301 -19 1195 -175.4
dC
1 1257 -79.3 4810 -303.5
2 602 -38 2405 -151.8
3 399 -25.2 1595 -100.6
Ea
1 637 -40.2 2546 -160.6 1223 -77.2 4406 -270.8
2 317 -20 1267 -79.7 639 -40.3 2300 -145.1
3 212 -13.4 844 -53.3
EB
1 904 -57 3613 -228 1602 -101.1 5770 -364.1
2 452 -28.5 1805 -113.9 828 -55.2 2982 -188.23 301 -19 1196 -75.5
EC
1 1203 -75.9 4810 -303.5
2 602 -38 2405 -151.8
3 399 -25.2 1595 -100.6
Fa
1 1203 -75.9 4810 -303.5 2019 -127.4 7267 -458.5
2 602 -38 2405 -151.8 1043 -65.8 3755 -236.9
3 399 -25.2 1595 -100.6
FB
1 1605 -101.3 6418 -405 2726 -172 9822 -619.8
2 802 -50.6 3202 -202 1397 -88.2 5030 -317.4
3 534 -33.7 2135 -134.7
FC
1 2136 -134.8 8541 -538.9
2 1068 -67.4 4270 -269.4
3 710 -44.8 2839 -179.1
7/28/2019 Chiller - YR
23/56
JOHNSON CONTROLS
FORM 160.80-EG1 (808
and initial chillr slctions should b mad accordingly to
permit proper range of ow while maintaining the minimum
velocity noted above. Variable ow in the condenser is not
rcommndd, as it gnrally raiss th nrgy consum-
tion of th systm by king th condnsr rssur
high in th chillr. Additionally, th rat of fouling in thcondnsr ill incras at lor atr vlocitis associ-
ated with variable ow, raising system maintenance costs.
Cooling tors tyically hav narro rangs of oration
with respect to ow rates, and will be more effective with
full design ow. Ref. Table 1 for ow limits.
Temperature Ranges For normal atr chilling duty,
laving chilld atr tmraturs may b slctd
between 38F (3.3C) [36F (2.2C) with Smart Freeze
nabld) and 70F (21.1C) for atr tmratur rangs
btn 3F and 30F (1.7C and 16.7C).
water quality Th ractical and conomical alica-tion of liquid chillrs rquirs that th quality of th atr
suly for th condnsr and vaorator b analyzd by
a atr tratmnt scialist. watr quality may affct th
rformanc of any chillr through corrosion, dosition of
hat-rsistant scal, or sdimntation or organic groth.
Ths ill dgrad chillr rformanc and incras o-
rating and maintnanc costs. Normally, rformanc
may b maintaind by corrctiv atr tratmnt and
riodic claning of tubs. If atr conditions xist hich
cannot b corrctd by ror atr tratmnt, it may b
ncssary to rovid a largr alloanc for fouling, and/or
to scify scial matrials of construction.
General Piping All chilld atr and condnsr atr
iing should b dsignd and installd in accordanc
ith acctd iing ractic. Chilld atr and con-
dnsr atr ums should b locatd to discharg
through the chiller to assure positive pressure and ow
through th unit. piing should includ offsts to rovid
exibility and should be arranged to prevent drainage of
atr from th vaorator and condnsr hn th ums
ar shut off. piing should b adquatly suortd and
bracd indndntly of th chillr to avoid th imosi-
tion of strain on chillr comonnts. Hangrs must allo
for alignmnt of th i. Isolators in th iing and in
th hangrs ar highly dsirabl in achiving sound andvibration control.
Convenience Considerations To facilitat th r-
formanc of routin maintnanc ork, som or all of th
folloing sts may b takn by th urchasr. Coolr and
condnsr atr boxs ar quid ith luggd vnt and
drain connctions. If dsird, vnt and drain valvs may b
installd ith or ithout iing to an on drain. prssur
gaugs ith sto cocks, and sto valvs, may b installd
in th inlts and outlts of th condnsr and chilld atr
lin as clos as ossibl to th chillr. An ovrhad monorail
or bam may b usd to facilitat srvicing.
Connections Th standard chillr is dsignd for 150
sig (1034 kpa) dsign orking rssur in both th
chilld atr and condnsr atr circuits. Th connc
tions (atr nozzls) to ths circuits ar furnishd ith
groovs for ANSI/AwwA C-606 coulings. piing should
b arrangd for as of disassmbly at th unit for tubclaning. All atr iing should b thoroughly cland
of all dirt and debris before nal connections are made
to th chillr.
Chilled water A ow switch must be installed in the
chilld atr lin of vry unit. Th sitch must b locatd
in th horizontal iing clos to th unit, hr th straigh
horizontal runs on each side of the ow switch are at leas
ve pipe diameters in length. The switch must be electri
cally connctd to th chilld atr intrlock osition in
th unit control cntr. A atr strainr of maximum 1/8
(3.2 mm) perforated holes must be eld-installed in the
chilld atr inlt lin as clos as ossibl to th chillrIf locatd clos nough to th chillr, th chilld atr
pump may be protected by the same strainer. The ow
switch and strainer assure chilled water ow during unit
operation. The loss or severe reduction of water ow could
sriously imair th chillr rformanc or vn rsult in
tub frz u.
Condenser water Th chillr is nginrd for maxi-
mum efciency at both design and part-load operation
by taking advantag of th coldr cooling tor atr
tmraturs hich naturally occur during th int
months. Arciabl or savings ar ralizd from
ths rducd hads.
Th minimum ntring condnsr atr tmratur fo
othr full and art load conditions is rovidd by th fol-
loing quation:
For R-22; Min ECWT = LCHWT + 11+ [(% load/100)
x
(15 - full load condnsr atr T)]
For R-134a; Min ECWT = LCHWT + 16 + [(% load/100)
x
(10 - full load condnsr atr T)]
whr: eCwT = ntring condnsr atr tmra-
turLCHwT = laving chilld atr tmratur
MULTIPLE UNITS
Selection Many alications rquir multil units
to mt th total caacity rquirmnts as ll as to
provide exibility and some degree of protection agains
quimnt shutdon. Thr ar svral common uni
arrangmnts for this ty of alication. Th Millennium
Chillr has bn dsignd to b radily adatd to th
rquirmnts of ths various arrangmnts.
7/28/2019 Chiller - YR
24/56
JOHNSON CONTROLS
Application Data - continued
FIG. 1 pARALLeL COOLeRS
pARALLeL CONDeNSeRS
FIG. SeRIeS COOLeRS
pARALLeL CONDeNSeRS
Parallel Arrangement (Rfr to Fig. 1) Chillrs may
b alid in multils ith chilld and condnsr atr
circuits connctd in aralll btn th units. Fig. 1 r-
rsnts a aralll arrangmnt ith to chillrs. paralll
chillr arrangmnts may consist of qually or unqually
sizd units. whn multil units ar in oration, thyill load and unload at qual rcntags of dsign full
load for th chillr.
Dnding on th numbr of units and orating char-
actristics of th units, loading and unloading schms
should be designed to optimize the overall efciency of
th chillr lant. It is rcommndd to us an vaora-
tor by-pass piping arrangement to bypass uid around
vaorator of any unit hich has cycld off at rducd load
conditions. It is also rcommndd to altrnat th chillr
cycling ordr to qualiz chillr starts and run hours.
Series Arrangement (Rfr to Fig. 2) Th chillrs mayb alid in airs ith chilld atr circuits connctd in
sris and condnsr atr circuits connctd in aralll.
All of the chilled water ows through both evaporators
ith ach unit handling aroximatly on-half of th
total load. whn th load dcrass to a customr s-
lctd load valu, on of th units ill b shut don by a
sequence control. Since all water is owing through the
orating unit, that unit ill cool th atr to th dsird
tmratur.
BRINE APPLICATIONS
Th YS Scr Chillr, utilizing th Frick Rfrigration com-rssor, is a good match for th high had rquirmnts of
lo tmratur brin alications. This is articularly tru
of thrmal ic storag systms, tyically rquiring 22F
(5.6C) to 24F (4.4C) laving brin tmraturs.
This rformanc is nhancd ith th standard thrmal
storag control mod dscribd on ag 6.
particular attntion must b aid to th alication of
to or mor chillrs ith vaorators in aralll or sris
hn th brin tmratur is blo 32F (0C). Th
brin MUST NOT ow through the evaporator of theidl chillr, bcaus it can caus th condnsr atr to
frz. A byass or othr ty of arrangmnt is rquird
that shuts off ow to the idle evaporator. When units are
alid in sris ith lad/lag caability, th units should
b idntical.
REFRIGERANT RELIEF PIPING
each chillr is quid ith rssur rlif dvics. Th
uros of th rlif dvics is to quickly rliv xcss
rssur of th rfrigrant charg to atmoshr, as a
safty rcaution in th vnt of an mrgncy such as
a re. They are set to relieve at an internal pressure of300 sig (2069 Kpa) and ar locatd on th condnsr,
vaorator and oil sarator; and ar rovidd in ac-
cordanc ith ASHRAe 15 Safty Cod and ASMe or
alicabl rssur vssl cod. whn rquird and ds-
ignatd on th ordr form, th rlif dvics ill satisfy th
euroan rquirmnts: (xaml VBG20). Undr ths
circumstancs th rlif dvics may b rlif valvs,
overow valves or type tested Safety Pressure switches
or a combination of ths dvics.
In addition to th sring-loadd, r-sating-ty rlif
valvs that ar sizd for rssur vssl volum, ach unit
is quid ith a rutur disk. This rutur disk is abl
to rliv th ntir uming caacity of th comrssor
if lctronic saftis fail, roviding rotction for rorty
and rsonnl. This dvic is st for 345 sig (2379 Kpa)
[45 psig above the re-seating relief valves set at 300 psig
(2069 Kpa)].
Sizd to th rquirmnts of alicabl cods, a vnt lin
must run from th rlif dvic to th outsid of th build-
ing. This rfrigrant rlif iing must includ a clanabl,
7/28/2019 Chiller - YR
25/56
5JOHNSON CONTROLS
FORM 160.80-EG1 (808
TABLE MOTOR VOLTAGe VARIATIONS
vrtical-lg dirt tra to catch vnt-stack condnsation.
Vnt iing must b arrangd to avoid imosing a strain
on the relief connections and should include one exible
connction.
SOUND AND VIBRATION CONSIDERATIONS
AMillennium chiller is not a source of objectionable sound
and vibration in normal air conditioning alications.
Norn isolation mounts ar furnishd as standard
with each unit. Optional level-adjusting spring isolator as-
semblies designed for 1 static deection are available.
Millennium chillr sound rssur lvl ratings ill b
furnishd uon rqust.
Control of sound and vibration transmission must b takn
into account in th quimnt room construction as ll
as in th slction and installation of th quimnt.
THERMAL INSULATION
No arciabl orating conomy can b achivd by
thrmally insulating th chillr. Hovr, th chillrs
cold surfacs should b insulatd ith a vaor barrir
insulation sufcient to prevent condensation. A chiller can
b factory insulatd ith 3/4 (19mm) or 1-1/2 (38mm)
thick insulation, as an otion. This insulation ill normally
rvnt condnsation in nvironmnts ith dry bulb tm-
raturs of 50F to 90F (10C to 32C) and rlativ
humidities up to 75% [3/4 (19mm) thickness] or 90% [1-
1/2 (38mm) thicknss]. Th insulation is aintd and thsurface is exible and reasonably resistant to wear. It is
intndd for a chillr installd indoors and, thrfor, no
rotctiv covring of th insulation is usually rquird
If insulation is applied to the water boxes at the job site
it must b rmovabl to rmit accss to th tubs for
routin maintnanc.
VENTILATION
Th ASHRAe Standard 15 Safty Cod for Mchanica
Rfrigration rquirs that all machinry rooms b vntd
to th outdoors utilizing mchanical vntilation by on
or mor or-drivn fans. This standard, lus Nationa
Fir protction Association Standard 90A, stat, loca
and other related codes should be reviewed for specic
rquirmnts. Sinc th Millennium chillr motor is air-
coold, vntilation should allo for th rmoval of ha
from th motor.
In addition, th ASHRAe Standard 15 rquirs a rfrigr
ant vaor dtctor to b mloyd for all rfrigrants. It isto b locatd in ara hr rfrigrant from a lak ould
b likly to concntrat. An alarm is to b activatd and
th mchanical vntilation startd at a valu no gratr
than th TLV (Thrshold Limit Valu) of th rfrigrant.
ELECTRICAL CONSIDERATIONS
Motor Voltage Lo voltag motors (200 - 600 volts) ar
furnishd ith six lads. Mdium voltag (2300 - 4160
volts) motors hav thr lads. Motor circuit conducto
siz must b in accordanc ith th National elctrica
Cod (NeC), or othr alicabl cods, for th motor
full-load amrs (FLA). Flxibl conduit should b usdfor th last svral ft to th chillr in ordr to rovid
vibration isolation. Tabl 2 lists th alloabl variation in
voltag sulid to th chillr motor. Th unit namlat
is stamped with the specic motor voltage and frequency
for th aroriat motor.
Starters Th chillr is availabl ith a factory-mountd
and ird YORK Solid Stat Startr for 200 - 600 vol
alications. Othr tys of rmot mountd startrs ar
availabl. Ths lctro-mchanical startrs must b
furnishd in accordanc ith Johnson Controls Standard
R-1079 Specication. This will ensure that starter com
onnts, controls, circuits, and trminal markings ill bsuitabl for rquird ovrall systm rformanc.
Controls A 115 volt, singl has, 60 or 50 Hrtz (4.5
kVa) or suly must b furnishd to th chillr from a
sarat, fusd disconnct or from a control transform
includd as an otion ith lctro-mchanical startrs
No eld control wiring is required, when the YORK SSS
is sulid.
Copper Conductors Only copper conductors should be
connected to compressor motors and starters.Aluminum
conductors hav rovn to b unsatisfactory hn con
nctd to cor lugs. Aluminum oxid and th diffrnc
Freq Rated VoltageOperating Voltage
Min. Max.
60Hz
200 200/208 180 220
230 220/240 208 254
380 380 342 415
416 416 375 457
460 440/460/480 414 508
575 575/600 520 635
2300 2300 2070 2530
3300 3300 2970 3630
4000 4000/4160 3600 4576
50Hz
346 346 311 381
380 380/400 342 423
415 415 374 440
3300 3300 2970 3630
NameplateVoltage
7/28/2019 Chiller - YR
26/56
6 JOHNSON CONTROLS
Application Data - continued
in thrmal conductivity btn cor and aluminum
cannot guarant th rquird tight connction ovr a
long riod of tim.
Poer Factor Correction Capacitors Caacitors can
b alid to a chillr for th uros of or factor cor-
rction. For rmot-Mountd elctro-Mchanical Startrs,th caacitors should b locatd on th load sid of th
startr. For YORK SSS, th caacitors must b locatd on
th lin sid of th startr. Th caacitors must b sizd
and installd to mt th National elctrical Cod (NeC)
and be veried by JOHNSON CONTROLS.
Ampacity on Load Side of Starter elctrical or
ir siz to th chillr is basd on th minimum unit am-
acity. For YORK SSS, this iring is don at th factory.
For remote starters, the National Electrical Code denes
th calculation of amacity, as summarizd blo. Mor
specic information on actual amperage ratings will be
sulid ith th submittal draings.
Six-lad ty of starting (Star-Dlta)
Minimum circuit amacity r conductor (1 of 6):
Amacity = .721 x comrssor motor ams.
Thr-lad ty of starting
(Across-th-Lin, Autotransformr and
primary Ractor)
Minimum circuit amacity r conductor (1 of 3):
Amacity = 1.25 x comrssor motor ams.
Ampacity on Line Side of Starter Th only additional load on th circuit for th chillr ould
b th control transformr, unlss it is sulid by a
sarat sourc.
125% of compr. + FLA of all otherMin. Circuit Ampacity =
motor amps loads on the circuit
Branch Circuit Overcurrent Protection Th branch
circuit ovrcurrnt rotction dvic(s) should b a
tim-dlay ty, ith a minimum rating qual to th nxtstandard fus/brakr rating abov th calculatd valu.
It is calculatd taking into account th comrssor motor
ams and may also includ control transformr. Rfr to
submittal drawings for the specic calculations for each
alication.
MOTOR ELECTRICAL DATA
Th smallst motor availabl hich quals or xcds
th Inut or (kw) from th chillr rating rogram is
slctd from Tabls 3 and 4. Th full load amrs (FLA)
listd in th tabls ar maximum valus and corrsond
to th maximum motor kw listd. whn th Inut or
(kw) is lss than maximum motor kw, th FLA should b
rducd using th folloing quation:
FLA = Motor kw x Max. Motor FLA
Max. Motor kw
The benet from the FLA correction is the possible use of
smallr or iring and/or startr siz.
Th lockd rotor amrs (LRA) ar rad dirctly from
Tables 3 and 4 for specic Motor Code and voltage. This
is bcaus th LRA is dndnt only on motor siz and
voltag and is indndnt of inut or (kw).
Inrush amrs (IRA) dnd on LRA and th ty of
startr alid. Th inrush can b calculatd using a
rcntag of LRA shon in Tabl 5.
7/28/2019 Chiller - YR
27/56
JOHNSON CONTROLS
FORM 160.80-EG1 (808
TABLE 60 HZ eLeCTRICAL DATA
NOTE: FLA = Full Load Ams; LRA = Lockd Rotor Ams
TABLE MOTOR STARTeRS
MOTOR CODE CF CG CH CJ CK CL CM CN CP CR CS CT CU CV CW CX CY CZ
KW (MAX.) 125 144 161 190 214 240 257 276 302 333 368 395 435 478 514 542 578 617
SHAFT HP 154 177 201 237 270 302 327 351 385 424 468 503 554 608 655 690 740 790FL EFF. % 92 92 93 93 94 94 95 95 95 95 95 95 95 95 95 95 95.5 95.5
FL PF 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9
VOLTS
208FLA 389 447 507 594 680 757 799 886 975 1043 1162
LRA 2702 3235 3235 3962 4732 5096 5689 6011 6011 7644 8106
230FLA 352 404 464 540 610 685 749 804 882 944 1050 1130 1250
LRA 2598 2598 2865 3460 3 788 4 260 4 755 5 162 5 780 5 780 6900 7400 7724
240FLA 337 387 445 518 585 656 718 771 845 905 1006 1083 1198
LRA 2711 2711 3120 3610 3 953 4 445 4 962 5 386 6 031 6 031 7200 7722 8060
380FLA 217 249 285 336 378 421 453 487 534 571 636 684 756 817 879 942 997 1065
LRA 1385 1385 1730 2153 2500 2577 2955 3254 3637 3810 4179 4480 4671 5326 5780 6782 5780 6644
416 FLA199 228 260 307 346 385 412 445 488 522 581 625 691 747 810 860 911 973
LRA 1385 1385 1638 1967 2190 2356 2700 2976 3536 3637 3810 3810 4270 4869 5640 5780 5694 6069
440FLA 184 211 238 281 319 358 392 397 461 493 549 591 646 706 759 813 861 920
LRA 1177 1301 1320 1655 1865 2037 2485 2485 2976 2976 3300 3644 3644 4209 4783 5357 4783 5249
460
FLA 176 202 228 269 305 342 375 380 441 472 525 565 618 675 726 778 824 880
LRA 1230 1360 1380 1730 1950 2130 2598 2598 3111 3111 3450 3810 3810 4400 5000 5600 5000 5488
480FLA 169 194 219 258 292 328 359 364 423 452 503 541 592 647 696 746 790 843
LRA 1283 1419 1440 1805 2035 2223 2711 2711 3246 3246 3600 3976 3976 4591 5217 5843 5217 5727
575FLA 141 162 185 216 250 274 300 318 353 377 420 452 500 540 581 622 659 704
LRA 909 909 1100 1384 1556 1700 1900 2066 2078 2413 2760 2960 3089 3550 4039 4440 4300 4200
600FLA 135 155 177 207 240 263 288 305 338 361 403 433 479 518 557 596 632 675
LRA 949 949 1148 1444 1624 1774 1983 2156 2168 2518 2880 3089 3223 3704 4215 4633 4484 4383
2300 FLA 36 41 46 54 61 68 74 79 87 95 105 113 124 135 146 154 165 176LRA 240 267 298 340 397 435 480 520 530 570 669 719 791 867 935 960 1008 1100
3300FLA 25 29 32 38 43 48 52 55 61 66 73 79 86 94 102 108 115 123
LRA 160 175 210 240 280 310 310 343 382 383 466 501 551 576 652 682 719 744
4000FLA 21 24 27 31 36 40 43 46 50 54 60 65 71 78 84 89 95 101
LRA 135 154 166 195 230 240 260 283 315 315 384 413 455 499 538 540 554 631
4160FLA 20 23 26 30 34 38 41 44 48 52 58 63 68 75 81 85 91 97
LRA 140 160 173 203 239 250 270 294 328 328 399 430 473 519 560 562 576 656
TYPE STARTER STAR DELTA AUTO TRANSFORMER ACROSS THE LINE PRIMARY REACTOR
VOLTAGE LOW LOW LOW LOW LOW/HIGH LOW/HIGH LOW/HIGH HIGH HIGH
60HZ 200-600 200-600 200-600 200-600 200-4160 200-4160 200-4160 2300-4160 2300-4160
50 HZ 380-415 346-415 346-415 346-415 346-3300 346-3300 346-3300 2300-3300 2300-3300
NONE 45 CLOSED 33 OPEN 33 CLOSED 80 64 100 CLOSED 65 65 CLOSED 80 80
SOLID STATE
STARTER
TRANSITION % TAP
INRUSH AS A % OF
LRA
CLOSED 57.7
33
CLOSED 65
42.3
7/28/2019 Chiller - YR
28/56
8 JOHNSON CONTROLS
TABLE 5 50 HZ eLeCTRICAL DATA
NOTE: 1. Chiller performance for 50 Hertz applications is outside the scope of the ARI Certication Program.2. FLA = Full Load Ams; LRA = Lockd Rotor Ams
Application Data - continued
TABLE 6 AVAILABLe COMpReSSOR/SHeLL/MOTOR COMBINATIONS (R-22 & R-134a)
Motor
CodE5CC 5Cd 5CE 5CF 5CG 5Ch 5CI 5CJ 5CK 5CL 5CM 5Cn 5Co 5CP 5CQ 5Cr 5Cs
shaFt hP
FL EFF. %FL PF
121 136 160 180 201 215 231 254 280 309 332 366 402 432 455 481 518
148 168 198 225 252 272 292 321 353 390 419 462 507 546 575 608 658
91.1 92.4 92.4 93.4 93.4 94.2 94.2 94.2 94.2 94.2 94.2 94.2 94.2 94.2 94.2 94.2 94.7
0.86 0.86 0.86 0.86 0.86 0.86 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.88
VoLts aMPErEs (MaX)
346FLa 224 258 302 340 380 417 437 481 528 584 630 692 578 816 860 909 982
Lra 1385 1721 1790 2208 2467 2598 2840 3081 3350 3706 3810 4177 4830 4944 5373 5780 5780
380FLa 204 235 275 309 346 379 398 438 481 532 572 630 690 743 783 841 895
Lra 1385 1385 1640 1890 2144 2464 2590 2806 3050 3375 3700 3810 4400 4500 4892 5600 5491
400FLa 194 223 261 294 329 360 378 416 457 505 543 599 656 706 744 799 850
Lra 1458 1458 1726 1990 2257 2594 2726 2954 3211 3553 3895 4011 4632 4737 5150 5895 5780
415FLa 187 215 252 284 317 347 364 401 441 487 526 577 632 680 717 764 819
Lra 1283 1385 1490 1700 2031 2175 2366 2569 2794 3088 3402 3478 3810 4117 4480 5130 5108
3300FLa 24 27 32 36 41 44 47 50 56 62 66 73 80 87 91 96 103
Lra 159 162 209 236 241 274 294 318 317 388 423 455 499 516 572 614 644
CoMPrEssor
CodE
CooLEr
shELL
CondEnsEr
shELL
Motor CodE
r-22, 60 hZ r-134a, 60 hZ r-22, 50 hZ
s0BA, BB BA, BB, CA, CB
CF, CG, CH CF, CG, CH 5 CC, 5 CDCA, CB BA, BB, CA, CB
s1 BA, BB BA, BB, CA, CB CF, CG, CH,CJ, CK
CF, CG, CH, 5 CC, 5 CD, 5 CE,5 CFCA, CB BA, BB, CA, CB CJ, CK
s2CA, CB CA, CB, DA, DB CG, CH, CJ,
CK, CL, CM
CF, CG, CH, CJ
CK, CL, CM
5 CD, 5 CE, 5 CF,
DA, DB, DC CA, CB, DA, DB 5 CG, 5 CH
s3 DA, DB, DC CA, CB, DA, DBCJ, CK, CL, CM,
CN, CP, CR
CG, CH, CJ, CK
CL, CM, CN, CP, CR
5 CF, 5 CG, 5 CH,
5 CI, 5 CJ, 5 CK
s4EA, EB, EC
FA, FB, FC
EA, EB, FA, FB
FA, FB
CK, CL, CM, CJ, CK, CL, CM, CN, CP, 5 CF, 5 CG,
CN, CP, CR, CR, CS, CT, CU, CV 5 CH, 5 CI,
s5 FA, FB, FC FA, FBCS, CT, CU,
CV
CK, CL, CM, CN, CP, CR
CS, CT, CU, CV
5 CJ, 5 CK,
5 CL, 5 CM,
5 CN, 5 CO
7/28/2019 Chiller - YR
29/56
9JOHNSON CONTROLS
FORM 160.80-EG1 (808
TABLE AVAILABLe COMpReSSOR/SHeLL/MOTOR COMBINATIONS (50 HZ, R-134a ONLY)
CoMPrEssor
CodE
CooLEr
shELL
CondEnsEr
shELLMotor CodE
s0
BA, BB BA, BB, CA, CB 5 CC, 5 CD
CA, CB BA, BB, CA, CB
s1BA, BB BA, BB, CA, CB 5 CC, 5 CD,
CA, CB BA, BB, CA, CB 5 CE, 5 CF
s2
BA, BB BA, BB, CA, CB 5 CC, 5 CD,
CA, CB BA, BB, CA, CB, DA, DB 5 CE, 5 CF,
DA, DB, DC CA, CB, DA, DB 5 CG, 5 CH
s3CA, CB CA, CB, DA, DB 5 CC, 5 CD, 5 CE, 5 CF,
DA, DB, DC CA, CB, DA, DB 5 CG, 5 CH, 5 CI, 5 CJ, 5 CK
s4
DA, DB, DC CA, CB, DA, DB 5 CE, 5 CF, 5 CG, 5 CH,
EA, EB, EC EA, EB, FA, FB 5 CI, 5 CJ, 5 CK, 5 CL,
FA, FB, FC EA, EB, FA, FB 5 CM, 5 CN, 5 CO
s5
EA, EB, EC EA, EB, FA, FB 5 CF, 5 CG, 5 CH, 5 CI,
FA, FB, FC EA, EB, FA, FB5 CJ, 5 CK, 5 CL,
5 CM, 5 CN, 5 CO
7/28/2019 Chiller - YR
30/56
0 JOHNSON CONTROLS
Dimensions Std
NOTES:
1. All dimensions are approximate. Certied dimensions are available on request.
2. Dtrmin ovrall unit lngth by adding atr box dimnsion to tub sht lngth:
5-1/4 for comact rturn box
14 for comact atr box ith ANSI/AwwA C-606 coulings atr nozzls
Add 1/2 to each compact water box with optional anged water nozzles
3. Unit hight includs stl mounting lats undr tub shts. To dtrmin ovrall hight, add 7/8 for norn isolators
(1 for otional sring isolators).
S0 - S COMPRESSORR- & R-1a UNITS
(50 and 60 Hz)
REFRIGERANT RELIEF VALVE CONNECTIONS
Rfr to Tabls 6 and 7 on ags 26 & 27 for valid comrssor/shll/motor combinations.
dIMEnsIon
s0 and s1 CoMPrEssor s2 CoMPrEssor s2 and s3 CoMPrEssor
shELL CodEs (EVaPorator CondEnsEr)
B-B B-C C-B C-C B-B B-C C-B C-C C-d d-C d-d
a 42-7/8 52-1/2 52-1/2
a1 46-3/4 46-1/4 4-6-3/4 46-1/4 53-3/4 53-3/4
B oVEraLL hEIGht3 58-5/8 511-1/2 510-1/4 511-1/2 511-1/4 63-1/4 63-1/4 63-1/4 67-5/8 68-3/4 69-3/8
C CooLEr C/L 11-7/8 15 15
d CondEnsEr C/L 011-5/8 12-1/4 12-1/4
shELL CodE EVaPorator sIZE CondEnsEr sIZE
B, C 3/4 FPT SINGLE 3/4 FPT DUAL
d 1 FPT SINGLE 3/4 FPT DUAL
CoMPrEssor CodE oIL sEParator sIZE
S0, S1 2 RUPTURE DISK & 3/4 FPT SINGLE
S2, S3 2 RUPTURE DISK & 3/4 FPT DUAL