INTRODUCTION
National Pipe Hanger Corporation is proud to present our new Pre-Insulated PipeSupport Catalog containing a complete and versatile line of pre-insulated pipesupports and thermal shields which have been selected to accommodate pipesupport requirements in the commercial and industrial piping fields. This selectionresults from nearly three decades of concentrated and direct exposure to the pip-ing industry, from the design engineer’s selection to the piping contractor’s instal-lation efforts. This is where needs are discovered and where products andservices are genuinely tested. In this area our experiences are unequalled.
A constant awareness of our customers' requirements and efforts is the founda-tion in the development of our manufacturing skills. All National Pipe Hanger Cor-poration products are carefully manufactured to meet the highest standards in theindustry. National Pipe Hanger Corporation is a participating member of the Man-ufactures Standardization Society (MSS).
To complement National Pipe Hanger Corporation’s line of pre-insulated pipe sup-ports, we have added thermal shields manufactured by Value Engineered ProductsIncorporated. Value Engineered Products Incorporated has been in business fortwenty years and they are specified as a thermal shield supplier by most engi-neering firms throughout the United States of America.
Contact National Pipe Hanger Corporation for special pre-insulated pipe supportrequirements including: other pipe sizes and types, insulation thickness, insulationmaterials, slide materials, dimensional requirements, installation methods, fin-ishes, etc. Our people are equipped to respond quickly to your product and serv-ice needs on both standards items and specialized fabrications. Visit our websitefor additional information on pre-insulated pipe supports such as: submittalsheets, installation instructions, competitor model number cross-references, etc.
All units used in this catalog are inch-pound unless otherwise noted. Additionalinformation provided in the end of this catalog can aid the user in: estimating pipesupport loads, determining pipe support spacing, selecting thermal conductivitiesat other operating temperatures, selecting the correct size pipe support for ther-mal shields, and determining the outside diameter of adjoining insulation.
1
GENERAL SELECTION
AXIAL TRAVEL = ± 11/2” AXIAL TRAVEL = ± 41/2”
AXIAL TRAVEL = ± 11/2” AXIAL TRAVEL = ± 41/2”
LAT
ER
AL
LOA
D =
LIG
HT
DU
TY
LAT
ER
AL
LOA
D =
HE
AV
Y D
UT
YLA
TE
RA
L T
RA
VE
L =
± 1 / 2
”LA
TE
RA
L T
RA
VE
L ≥
±11 /2
”
2
NS10 NS20
NS50 NS60
NG30 NG40
NG70 NG80
PRE-INSULATED PIPE SLIDES
PRE-INSULATED PIPE GUIDES
PRE-INSULATED PIPE ANCHOR
3
GENERAL SELECTION
VERTICAL LOAD = LIGHT DUTY VERTICAL LOAD = HEAVY DUTY
SIN
GLE
RO
DT
WO
RO
D
NC30 - NC33NC10
NH40 NH60
PRE-INSULATED PIPE CLAMPS AND HANGERS
FOR AXIAL & VERTICAL LOADS
NA40
PRE-INSULATED STRUT CLAMPS
4
GENERAL SELECTION
HOLDDOWN STRUT CLAMP GUIDED STRUT CLAMP
NC70 NC80
PRE-INSULATED PIPE RISER CLAMPS
FOR DOWNWARD RISER LOADS FOR UPWARD & DOWNWARD RISER LOADS
NR10 NR20
WIT
H T
OP
PR
OT
EC
TIO
N S
HIE
LDW
ITH
OU
T T
OP
PR
OT
EC
TIO
N S
HIE
LD
THERMAL SHIELDS
VALUE ENGINEERED PRODUCTS, INC.
PRO-SHIELD N.T.
PRO-SHIELD CHILL-SHIELD
MAXSPAN R.H.
MAXSPAN
QUIK-SHIELD
VERTICAL LOAD = LIGHT DUTY VERTICAL LOAD = HEAVY DUTY
For Use: In Clevis Hanger On Trapeze
For Use: In Clevis Hanger On Trapeze
For Use: In Clevis Hanger In Two-Bolt Clamp
For Use: In Clevis HangerOn Trapeze
For Use: In Clevis Hanger On Trapeze
For Use: On Roller Support On Flat Surface
5
GENERAL SELECTION
± 11/2” Axial Movement, ± 1/2” Lateral Movement
Applications:
• Allows moderate axial travel and smalllateral travel while providing vertical support
• Designed for use on:Chilled Water Hot Water Steam
• Installation: welded to flat steel surface• Temperature Range: +20°F to +1200°F• Axial Travel: ± 11/2”• Lateral Travel: ± 1/2”
Features:
• Eliminates welding to pipe• Provides continuous vapor barrier• Insulation extends 3” beyond shield• Structural insulation for load transfer• Stainless steel to UHMW polyethylene slide• Static Coefficient of Friction = 0.15• ASTM E-84 Flame Spread/Smoke Developed: 10/5• Thermal Conductivity
Grade 5 = 0.54 Btu•in/(hr•ft2•°F) @ 200°FGrade 6 = 0.61 Btu•in/(hr•ft2•°F) @ 200°F
• Insulation mechanically and chemically bonded
Material Data:
Insulation: Calcium Silicate meetingASTM C-585 and C-656 Type IIGrade 5: 450 psi, 18 pcf Grade 6: 900 psi, 28 pcf
Base/Clamp: ASTM A-36 Carbon SteelFasteners: ASTM A-307 Electro-Galv. PlatedSlide: ASTM A-240 304 Stainless Steel
on UHMW PolyethyleneShield: ASTM A-653 G-90, 18 ga Galv. SteelVapor Barrier: ASTM E-96 All Service JacketFinishes: Painted Red Shop Primer
Hot-Dip Galv. per ASTM A-123
PIPESIZE
VERT. LOADGRADE 5
VERT. LOADGRADE 6
INS. THK. = 1” INS. THK. = 11/2” INS. THK. = 2” INS. THK. = 21/2” INS. THK. = 3” INS. THK. = 4”
A B A B A B A B A B A B
2” 1100 1500 4 2.5 4 3 4 4 4 4.5 6 5.5 6 7.521/2” 1350 1800 4 2.5 4 4 4 4.5 4 5.5 6 6.5 6 83” 1600 2100 4 3 4 4 4 4.5 4 5.5 6 6.5 6 84” 2500 3350 4 4 4 4.5 4 5.5 4 6.5 6 7.5 6 95” 3100 4200 4 4.5 4 5.5 4 6.5 4 7.5 6 8 6 9.56” 3800 5100 4 5.5 4 6.5 4 7.5 4 8 6 9 6 10.58” 5100 6800 4 7.5 4 8 4 9 6 9.5 6 10.5 6 12
10” 6000 8000 4 9 4 9.5 4 10.5 6 11 6 12 6 1312” 6600 8800 4 10.5 4 11 4 12 6 12.5 6 13 6 14.514” 7500 10000 4 11 4 12 4 12.5 6 13 6 14 6 15.516” 8700 11600 4 12.5 4 13 6 14 6 14.5 6 15.5 8 16.518” 9600 12800 4 14 4 14.5 6 15.5 6 16 6 16.5 8 1820” 10200 13600 4 15.5 4 16 6 16.5 6 17.5 6 18 8 19.524” 10800 14400 4 18 4 19 6 19.5 6 20.5 6 21 8 22.530” 14100 18800 4 22.5 6 23 6 24 6 24.5 6 25 8 26.536” 16500 22000 4 26.5 6 27.5 6 28 6 28.5 6 29.5 8 3142” 18600 24800 4 31 6 31.5 6 32.5 6 33 6 33.5 8 35
Ordering: Fig. NS10 - (Pipe Size) x (Insulation Thickness) - (Insulation Grade)
PRE-INSULATED SLIDING PIPE SUPPORTFIG. NS10
6
NATIONAL PIPE HANGER CORPORATION
± 41/2” Axial Movement, ± 1/2” Lateral Movement
Applications:
• Allows large axial travel and smalllateral travel while providing verticalsupport
• Designed for use on:Chilled Water Hot Water Steam
• Installation: welded to flat steel surface• Temperature Range: +20°F to +1200°F• Axial Travel: ± 41/2”• Lateral Travel: ± 1/2”
Features:
• Eliminates welding to pipe• Provides continuous vapor barrier• Insulation extends 3” beyond shield• Structural insulation for load transfer• Stainless steel to UHMW polyethylene slide• Static Coefficient of Friction = 0.15• ASTM E-84 Flame Spread/Smoke Developed: 10/5• Thermal Conductivity
Grade 5 = 0.54 Btu•in/(hr•ft2•°F) @ 200°FGrade 6 = 0.61 Btu•in/(hr•ft2•°F) @ 200°F
• Insulation mechanically and chemically bonded
Material Data:
Insulation: Calcium Silicate meetingASTM C-585 and C-656 Type IIGrade 5: 450 psi, 18 pcf Grade 6: 900 psi, 28 pcf
Base/Clamp: ASTM A-36 Carbon SteelFasteners: ASTM A-307 Electro-Galv. PlatedSlide: ASTM A-240 304 Stainless Steel
on UHMW PolyethyleneShield: ASTM A-653 G-90, 18 ga Galv. SteelVapor Barrier: ASTM E-96 All Service JacketFinishes: Painted Red Shop Primer
Hot-Dip Galv. per ASTM A-123
PIPESIZE
VERT. LOADGRADE 5
VERT. LOADGRADE 6
INS. THK. = 1” INS. THK. = 11/2” INS. THK. = 2” INS. THK. = 21/2” INS. THK. = 3” INS. THK. = 4”
A B A B A B A B A B A B
2” 1100 1500 4 2.5 4 3 4 4 4 4.5 6 5.5 6 7.521/2” 1350 1800 4 2.5 4 4 4 4.5 4 5.5 6 6.5 6 83” 1600 2100 4 3 4 4 4 4.5 4 5.5 6 6.5 6 84” 2500 3350 4 4 4 4.5 4 5.5 4 6.5 6 7.5 6 95” 3100 4200 4 4.5 4 5.5 4 6.5 4 7.5 6 8 6 9.56” 3800 5100 4 5.5 4 6.5 4 7.5 4 8 6 9 6 10.58” 5100 6800 4 7.5 4 8 4 9 6 9.5 6 10.5 6 12
10” 6000 8000 4 9 4 9.5 4 10.5 6 11 6 12 6 1312” 6600 8800 4 10.5 4 11 4 12 6 12.5 6 13 6 14.514” 7500 10000 4 11 4 12 4 12.5 6 13 6 14 6 15.516” 8700 11600 4 12.5 4 13 6 14 6 14.5 6 15.5 8 16.518” 9600 12800 4 14 4 14.5 6 15.5 6 16 6 16.5 8 1820” 10200 13600 4 15.5 4 16 6 16.5 6 17.5 6 18 8 19.524” 10800 14400 4 18 4 19 6 19.5 6 20.5 6 21 8 22.530” 14100 18800 4 22.5 6 23 6 24 6 24.5 6 25 8 26.536” 16500 22000 4 26.5 6 27.5 6 28 6 28.5 6 29.5 8 3142” 18600 24800 4 31 6 31.5 6 32.5 6 33 6 33.5 8 35
Ordering: Fig. NS20 - (Pipe Size) x (Insulation Thickness) - (Insulation Grade)
PRE-INSULATED SLIDING PIPE SUPPORT FIG. NS20
7
NATIONAL PIPE HANGER CORPORATION
± 11/2” Axial Movement, Lateral Movement as Noted
Applications:
• Allows moderate axial travel and moderate lateral travel while providingvertical support
• Designed for use on:Chilled Water Hot Water Steam
• Installation: welded to flat steel surface• Temperature Range: +20°F to +1200°F• Axial Movement: ± 11/2”• Lateral Movement: Varies
Features:
• Eliminates welding to pipe• Provides continuous vapor barrier• Insulation extends 3” beyond shield• Structural insulation for load transfer• Stainless steel to UHMW polyethylene slide• Static Coefficient of Friction = 0.15• ASTM E-84 Flame Spread/Smoke Developed: 10/5• Thermal Conductivity
Grade 5 = 0.54 Btu•in/(hr•ft2•°F) @ 200°FGrade 6 = 0.61 Btu•in/(hr•ft2•°F) @ 200°F
• Insulation mechanically and chemically bonded
Material Data:
Insulation: Calcium Silicate meetingASTM C-585 and C-656 Type IIGrade 5: 450 psi, 18 pcf Grade 6: 900 psi, 28 pcf
Base/Clamp: ASTM A-36 Carbon SteelFasteners: ASTM A-307 Electro-Galv. PlatedSlide: ASTM A-240 304 Stainless Steel
on UHMW PolyethyleneShield: ASTM A-653 G-90, 18 ga Galv. SteelVapor Barrier: ASTM E-96 All Service JacketFinishes: Painted Red Shop Primer
Hot-Dip Galv. per ASTM A-123
PIPESIZE
VERT. LOADGRADE 5
VERT. LOADGRADE 6
INS. THK. = 1”LAT. MOV’T. ± 11/2”
INS. THK. = 11/2”LAT. MOV’T. ± 13/4”
INS. THK. = 2”LAT. MOV’T. ± 2”
INS. THK. = 21/2”LAT. MOV’T. ± 21/4”
INS. THK. = 3”LAT. MOV’T. ± 21/2”
INS. THK. = 4”LAT. MOV’T. ± 3”
A B A B A B A B A B A B
2” 1100 1500 4 6.75 4 7.75 4 8.75 4 9.75 6 10.75 6 12.7521/2” 1350 1800 4 7.25 4 8.75 4 9.75 4 10.75 6 11.75 6 13.753” 1600 2100 4 7.75 4 8.75 4 9.75 4 10.75 6 11.75 6 13.754” 2500 3350 4 8.25 4 9.25 4 10.25 4 11.25 6 12.25 6 14.255” 3100 4200 4 9 4 10 4 11 4 12 6 13 6 156” 3800 5100 4 9.5 4 10.5 4 11.5 4 12.5 6 13.5 6 15.58” 5100 6800 4 10.5 4 11.5 4 12.5 6 13.5 6 14.5 6 16.5
10” 6000 8000 4 11.5 4 12.5 4 13.5 6 14.5 6 15.5 6 17.512” 6600 8800 4 12.5 4 13.5 4 14.5 6 15.5 6 16.5 6 18.514” 7500 10000 4 13 4 14 4 15 6 16 6 17 6 1916” 8700 11600 4 14 4 15 6 16 6 17 6 18 8 2018” 9600 12800 4 15 4 16 6 17 6 18 6 19 8 2120” 10200 13600 4 16 4 17 6 18 6 19 6 20 8 2224” 10800 14400 4 18.5 4 19.5 6 20 6 21 6 22 8 2430” 14100 18800 4 23.5 6 24 6 25 6 25.5 6 26 8 27.536” 16500 22000 4 27.5 6 28.5 6 29 6 29.5 6 30.5 8 3242” 18600 24800 4 32 6 32.5 6 33.5 6 34 6 34.5 8 36
Ordering: Fig. NS50 - (Pipe Size) x (Insulation Thickness) - (Insulation Grade)
PRE-INSULATED SLIDING PIPE SUPPORTFIG. NS50
8
NATIONAL PIPE HANGER CORPORATION
± 41/2” Axial Movement, Lateral Movement as Noted
Applications:
• Allows large axial travel and moderate lateral travel while providing vertical support
• Designed for use on:Chilled Water Hot Water Steam
• Installation: welded to flat steel surface• Temperature Range: +20°F to +1200°F• Axial Movement: ± 41/2”• Lateral Movement: Varies
Features:
• Eliminates welding to pipe• Provides continuous vapor barrier• Insulation extends 3” beyond shield• Structural insulation for load transfer• Stainless steel to UHMW polyethylene slide• Static Coefficient of Friction = 0.15• ASTM E-84 Flame Spread/Smoke Developed: 10/5• Thermal Conductivity
Grade 5 = 0.54 Btu•in/(hr•ft2•°F) @ 200°FGrade 6 = 0.61 Btu•in/(hr•ft2•°F) @ 200°F
• Insulation mechanically and chemically bonded
Material Data:
Insulation: Calcium Silicate meetingASTM C-585 and C-656 Type IIGrade 5: 450 psi, 18 pcf Grade 6: 900 psi, 28 pcf
Base/Clamp: ASTM A-36 Carbon SteelFasteners: ASTM A-307 Electro-Galv. PlatedSlide: ASTM A-240 304 Stainless Steel
on UHMW PolyethyleneShield: ASTM A-653 G-90, 18 ga Galv. SteelVapor Barrier: ASTM E-96 All Service JacketFinishes: Painted Red Shop Primer
Hot-Dip Galv. per ASTM A-123
PIPESIZE
VERT. LOADGRADE 5
VERT. LOADGRADE 6
INS. THK. = 1”LAT. MOV’T. ± 11/2”
INS. THK. = 11/2”LAT. MOV’T. ± 13/4”
INS. THK. = 2”LAT. MOV’T. ± 2”
INS. THK. = 21/2”LAT. MOV’T. ± 21/4”
INS. THK. = 3”LAT. MOV’T. ± 21/2”
INS. THK. = 4”LAT. MOV’T. ± 3”
A B A B A B A B A B A B
2” 1100 1500 4 6.75 4 7.75 4 8.75 4 9.75 6 10.75 6 12.7521/2” 1350 1800 4 7.25 4 8.75 4 9.75 4 10.75 6 11.75 6 13.753” 1600 2100 4 7.75 4 8.75 4 9.75 4 10.75 6 11.75 6 13.754” 2500 3350 4 8.25 4 9.25 4 10.25 4 11.25 6 12.25 6 14.255” 3100 4200 4 9 4 10 4 11 4 12 6 13 6 156” 3800 5100 4 9.5 4 10.5 4 11.5 4 12.5 6 13.5 6 15.58” 5100 6800 4 10.5 4 11.5 4 12.5 6 13.5 6 14.5 6 16.5
10” 6000 8000 4 11.5 4 12.5 4 13.5 6 14.5 6 15.5 6 17.512” 6600 8800 4 12.5 4 13.5 4 14.5 6 15.5 6 16.5 6 18.514” 7500 10000 4 13 4 14 4 15 6 16 6 17 6 1916” 8700 11600 4 14 4 15 6 16 6 17 6 18 8 2018” 9600 12800 4 15 4 16 6 17 6 18 6 19 8 2120” 10200 13600 4 16 4 17 6 18 6 19 6 20 8 2224” 10800 14400 4 18.5 4 19.5 6 20 6 21 6 22 8 2430” 14100 18800 4 23.5 6 24 6 25 6 25.5 6 26 8 27.536” 16500 22000 4 27.5 6 28.5 6 29 6 29.5 6 30.5 8 3242” 18600 24800 4 32 6 32.5 6 33.5 6 34 6 34.5 8 36
Ordering: Fig. NS60 - (Pipe Size) x (Insulation Thickness) - (Insulation Grade)
PRE-INSULATED SLIDING PIPE SUPPORT FIG. NS60
9
NATIONAL PIPE HANGER CORPORATION
± 11/2” Axial Movement, Laterally Guided - Light Duty
Applications:
• Allows guided moderate axial travel while providing light duty lateral support for buckling and movement control and vertical support
• Designed for use on:Chilled Water Hot Water Steam
• Installation: welded to flat steel surface• Temperature Range: +20°F to +1200°F• Axial Travel: ± 11/2”• Lateral Guide Gap: ± 1/8”• Vertical Guide Gap: + 1/8”
Features:
• Allowable Lateral Load = 20% of Vertical Load• Eliminates welding to pipe• Provides continuous vapor barrier• Insulation extends 3” beyond shield• Structural insulation for load transfer• Stainless steel to UHMW polyethylene slide• Static Coefficient of Friction = 0.15• ASTM E-84 Flame Spread/Smoke Developed: 10/5• Thermal Conductivity
Grade 5 = 0.54 Btu•in/(hr•ft2•°F) @ 200°FGrade 6 = 0.61 Btu•in/(hr•ft2•°F) @ 200°F
• Insulation mechanically and chemically bonded
Material Data:
Insulation: Calcium Silicate meetingASTM C-585 and C-656 Type IIGrade 5: 450 psi, 18 pcfGrade 6: 900 psi, 28 pcf
Base/Clamp: ASTM A-36 Carbon SteelFasteners: ASTM A-307 Electro-Galv. PlatedSlide: ASTM A-240 304 Stainless Steel
on UHMW PolyethyleneShield: ASTM A-653 G-90, 18 ga Galv. SteelVapor Barrier: ASTM E-96 All Service JacketFinishes: Painted Red Shop Primer
Hot-Dip Galv. per ASTM A-123
PIPESIZE
VERT. LOADGRADE 5
VERT. LOADGRADE 6
INS. THK. = 1” INS. THK. = 11/2” INS. THK. = 2” INS. THK. = 21/2” INS. THK. = 3” INS. THK. = 4”
A B A B A B A B A B A B
2” 1100 1500 4 7 4 7.5 4 8.5 4 9 6 10 6 1221/2” 1350 1800 4 7 4 8.5 4 9 4 10 6 11 6 12.53” 1600 2100 4 7.5 4 8.5 4 9 4 10 6 11 6 12.54” 2500 3350 4 8.5 4 9 4 10 4 11 6 12 6 13.55” 3100 4200 4 10 4 11 4 12 4 13 6 13.5 6 156” 3800 5100 4 11 4 12 4 13 4 13.5 6 14.5 6 168” 5100 6800 4 13.5 4 14 4 15 6 15.5 6 16.5 6 18
10” 6000 8000 4 15 4 15.5 4 16.5 6 17 6 18 6 1912” 6600 8800 4 17 4 17.5 4 18.5 6 19 6 19.5 6 2114” 7500 10000 4 17.5 4 18.5 4 19 6 19.5 6 20.5 6 2216” 8700 11600 4 20.5 4 21 6 22 6 22.5 6 23.5 8 24.518” 9600 12800 4 22 4 22.5 6 23.5 6 24 6 24.5 8 2620” 10200 13600 4 23.5 4 24 6 24.5 6 25.5 6 26 8 27.524” 10800 14400 4 26 4 27 6 27.5 6 28.5 6 29 8 30.530” 14100 18800 4 32.5 6 33 6 34 6 34.5 6 35 8 36.536” 16500 22000 4 36.5 6 37.5 6 38 6 38.5 6 39.5 8 4142” 18600 24800 4 41 6 41.5 6 42.5 6 43 6 43.5 8 45
Ordering: Fig. NG30 - (Pipe Size) x (Insulation Thickness) - (Insulation Grade)
PRE-INSULATED GUIDED PIPE SUPPORTFIG. NG30
10
NATIONAL PIPE HANGER CORPORATION
± 41/2” Axial Movement, Laterally Guided - Light Duty
Applications:
• Allows guided large axial travel while providing light duty lateral support for buckling and movement control and vertical support
• Designed for use on:Chilled Water Hot Water Steam
• Installation: welded to flat steel surface• Temperature Range: +20°F to +1200°F• Axial Travel: ± 41/2”• Lateral Guide Gap: ± 1/8”• Vertical Guide Gap: + 1/8”
Features:
• Allowable Lateral Load = 20% of Vertical Load• Eliminates welding to pipe• Provides continuous vapor barrier• Insulation extends 3” beyond shield• Structural insulation for load transfer• Stainless steel to UHMW polyethylene slide• Static Coefficient of Friction = 0.15• ASTM E-84 Flame Spread/Smoke Developed: 10/5• Thermal Conductivity
Grade 5 = 0.54 Btu•in/(hr•ft2•°F) @ 200°FGrade 6 = 0.61 Btu•in/(hr•ft2•°F) @ 200°F
• Insulation mechanically and chemically bonded
Material Data:
Insulation: Calcium Silicate meetingASTM C-585 and C-656 Type IIGrade 5: 450 psi, 18 pcf Grade 6: 900 psi, 28 pcf
Base/Clamp: ASTM A-36 Carbon Steel Fasteners: ASTM A-307 Electro-Galv. PlatedSlide: ASTM A-240 304 Stainless Steel
on UHMW PolyethyleneShield: ASTM A-653 G-90, 18 ga Galv. SteelVapor Barrier: ASTM E-96 All Service JacketFinishes: Painted Red Shop Primer
Hot-Dip Galv. per ASTM A-123
PIPESIZE
VERT. LOADGRADE 5
VERT. LOADGRADE 6
INS. THK. = 1” INS. THK. = 11/2” INS. THK. = 2” INS. THK. = 21/2” INS. THK. = 3” INS. THK. = 4”
A B A B A B A B A B A B
2” 1100 1500 4 7 4 7.5 4 8.5 4 9 6 10 6 1221/2” 1350 1800 4 7 4 8.5 4 9 4 10 6 11 6 12.53” 1600 2100 4 7.5 4 8.5 4 9 4 10 6 11 6 12.54” 2500 3350 4 8.5 4 9 4 10 4 11 6 12 6 13.55” 3100 4200 4 10 4 11 4 12 4 13 6 13.5 6 156” 3800 5100 4 11 4 12 4 13 4 13.5 6 14.5 6 168” 5100 6800 4 13.5 4 14 4 15 6 15.5 6 16.5 6 18
10” 6000 8000 4 15 4 15.5 4 16.5 6 17 6 18 6 1912” 6600 8800 4 17 4 17.5 4 18.5 6 19 6 19.5 6 2114” 7500 10000 4 17.5 4 18.5 4 19 6 19.5 6 20.5 6 2216” 8700 11600 4 20.5 4 21 6 22 6 22.5 6 23.5 8 24.518” 9600 12800 4 22 4 22.5 6 23.5 6 24 6 24.5 8 2620” 10200 13600 4 23.5 4 24 6 24.5 6 25.5 6 26 8 27.524” 10800 14400 4 26 4 27 6 27.5 6 28.5 6 29 8 30.530” 14100 18800 4 32.5 6 33 6 34 6 34.5 6 35 8 36.536” 16500 22000 4 36.5 6 37.5 6 38 6 38.5 6 39.5 8 4142” 18600 24800 4 41 6 41.5 6 42.5 6 43 6 43.5 8 45
Ordering: Fig. NG40 - (Pipe Size) x (Insulation Thickness) - (Insulation Grade)
PRE-INSULATED GUIDED PIPE SUPPORT FIG. NG40
11
NATIONAL PIPE HANGER CORPORATION
± 11/2” Axial Movement, Laterally Guided - Heavy Duty
Applications:
• Allows guided moderate axial travel while providing heavy duty lateral support and vertical support
• Designed for use on:Chilled Water Hot Water Steam
• Installation: welded to flat steel surface• Temperature Range: +20°F to +1200°F• Axial Travel: ± 11/2”• Lateral Guide Gap: ± 1/8”
Features:
• Allowable Lateral Load = 50% of Vertical Load• Eliminates welding to pipe• Provides continuous vapor barrier• Insulation extends 3” beyond shield• Structural insulation for load transfer• Stainless steel to UHMW polyethylene slide• Static Coefficient of Friction = 0.15• ASTM E-84 Flame Spread/Smoke Developed: 10/5• Thermal Conductivity
Grade 5 = 0.54 Btu•in/(hr•ft2•°F) @ 200°FGrade 6 = 0.61 Btu•in/(hr•ft2•°F) @ 200°F
• Insulation mechanically and chemically bonded
Material Data:
Insulation: Calcium Silicate meetingASTM C-585 and C-656 Type IIGrade 5: 450 psi, 18 pcf Grade 6: 900 psi, 28 pcf
Base/Clamp: ASTM A-36 Carbon SteelFasteners: ASTM A-307 Electro-Galv. PlatedSlide: ASTM A-240 304 Stainless Steel
on UHMW PolyethyleneShield: ASTM A-653 G-90, 18 ga Galv. SteelVapor Barrier: ASTM E-96 All Service JacketFinishes: Painted Red Shop Primer
Hot-Dip Galv. per ASTM A-123
PIPESIZE
VERT. LOADGRADE 5
VERT. LOADGRADE 6
INS. THK. = 1” INS. THK. = 11/2” INS. THK. = 2” INS. THK. = 21/2” INS. THK. = 3” INS. THK. = 4”
A B A B A B A B A B A B
2” 1005 1340 4 7 4 7.5 4 8.5 4 9 6 10 6 1221/2” 1230 1640 4 7 4 8.5 4 9 4 10 6 11 6 12.53” 1425 1900 4 8 4 9 4 9.5 4 10.5 6 11.5 6 134” 2250 3000 4 10 4 10.5 4 11.5 4 12.5 6 13.5 6 155” 2820 3760 4 13 4 13.5 4 15 4 16.5 6 17.5 6 19.56” 3420 4560 4 13 4 14.5 4 16 4 17 6 18.5 6 19.58” 4500 6000 4 17 4 18 4 19.5 6 20 6 21 6 22.5
10” 5400 7200 4 20 4 20.5 4 21.5 6 22 6 23 6 24.512” 5850 7800 4 21.5 4 22 4 23 6 24 6 24.5 6 26.514” 6750 9000 4 22.5 4 23.5 4 24.5 6 25 6 26 6 2816” 7800 10400 4 24.5 4 25 6 26 6 27 6 28 8 2918” 8550 11400 4 26.5 4 27.5 6 28.5 6 29 6 29.5 8 30.520” 9150 12200 4 29 4 29.5 6 30 6 30.5 6 31 8 32.524” 9600 12800 4 31.5 4 32.5 6 33 6 33.5 6 34.5 8 3630” 12600 16800 4 37.5 6 38.5 6 39 6 40 6 41 8 42.536” 14700 19600 4 44 6 44.5 6 45.5 6 46.5 6 47 8 48.542” 16650 22200 4 50 6 51 6 52 6 52.5 6 53.5 8 55
Ordering: Fig. NG70 - (Pipe Size) x (Insulation Thickness) - (Insulation Grade)
PRE-INSULATED GUIDED PIPE SUPPORTFIG. NG70
12
NATIONAL PIPE HANGER CORPORATION
± 41/2” Axial Movement, Laterally Guided - Heavy Duty
Applications:
• Allows guided large axial travel while providing heavy duty lateral support and vertical support
• Designed for use on:Chilled Water Hot Water Steam
• Installation: welded to flat steel surface• Temperature Range: +20°F to +1200°F• Axial Travel: ± 41/2”• Lateral Guide Gap: ± 1/8”
Features:
• Allowable Lateral Load = 50% of Vertical Load• Eliminates welding to pipe• Provides continuous vapor barrier• Insulation extends 3” beyond shield• Structural insulation for load transfer• Stainless steel to UHMW polyethylene slide• Static Coefficient of Friction = 0.15• ASTM E-84 Flame Spread/Smoke Developed: 10/5• Thermal Conductivity
Grade 5 = 0.54 Btu•in/(hr•ft2•°F) @ 200°FGrade 6 = 0.61 Btu•in/(hr•ft2•°F) @ 200°F
• Insulation mechanically and chemically bonded
Material Data:
Insulation: Calcium Silicate meetingASTM C-585 and C-656 Type IIGrade 5: 450 psi, 18 pcf Grade 6: 900 psi, 28 pcf
Base/Clamp: ASTM A-36 Carbon SteelFasteners: ASTM A-307 Electro-Galv. PlatedSlide: ASTM A-240 304 Stainless Steel
on UHMW PolyethyleneShield: ASTM A-653 G-90, 18 ga Galv. SteelVapor Barrier: ASTM E-96 All Service JacketFinishes: Painted Red Shop Primer
Hot-Dip Galv. per ASTM A-123
PIPESIZE
VERT. LOADGRADE 5
VERT. LOADGRADE 6
INS. THK. = 1” INS. THK. = 11/2” INS. THK. = 2” INS. THK. = 21/2” INS. THK. = 3” INS. THK. = 4”
A B A B A B A B A B A B
2” 1005 1340 4 7 4 7.5 4 8.5 4 9 6 10 6 1221/2” 1230 1640 4 7 4 8.5 4 9 4 10 6 11 6 12.53” 1425 1900 4 8 4 9 4 9.5 4 10.5 6 11.5 6 134” 2250 3000 4 10 4 10.5 4 11.5 4 12.5 6 13.5 6 155” 2820 3760 4 13 4 13.5 4 15 4 16.5 6 17.5 6 19.56” 3420 4560 4 13 4 14.5 4 16 4 17 6 18.5 6 19.58” 4500 6000 4 17 4 18 4 19.5 6 20 6 21 6 22.5
10” 5400 7200 4 20 4 20.5 4 21.5 6 22 6 23 6 24.512” 5850 7800 4 21.5 4 22 4 23 6 24 6 24.5 6 26.514” 6750 9000 4 22.5 4 23.5 4 24.5 6 25 6 26 6 2816” 7800 10400 4 24.5 4 25 6 26 6 27 6 28 8 2918” 8550 11400 4 26.5 4 27.5 6 28.5 6 29 6 29.5 8 30.520” 9150 12200 4 29 4 29.5 6 30 6 30.5 6 31 8 32.524” 9600 12800 4 31.5 4 32.5 6 33 6 33.5 6 34.5 8 3630” 12600 16800 4 37.5 6 38.5 6 39 6 40 6 41 8 42.536” 14700 19600 4 44 6 44.5 6 45.5 6 46.5 6 47 8 48.542” 16650 22200 4 50 6 51 6 52 6 52.5 6 53.5 8 55
Ordering: Fig. NG80 - (Pipe Size) x (Insulation Thickness) - (Insulation Grade)
PRE-INSULATED GUIDED PIPE SUPPORT FIG. NG80
13
NATIONAL PIPE HANGER CORPORATION
Applications:
• Provides light duty vertical support in low overhead clearance pipe runs
• Designed for use on:Chilled Water Hot Water Steam
• Installation: hung from two threaded rods
• Temperature Range: +20°F to +1200°F
Features:
• Eliminates welding to pipe• Provides continuous vapor barrier• Insulation extends 2” beyond shield• Structural insulation for load transfer• ASTM E-84 Flame Spread/Smoke Developed: 10/5• Thermal Conductivity
0.41 Btu•in/(hr•ft2•°F) @ 200°F• Insulation chemically bonded
Material Data:
Insulation: Calcium Silicate meetingASTM C-585 and C-533 Type IValue Engineered Products, Inc.Pro-Shield: 100 psi, 14.5 pcf
Clamp: ASTM A-36 Carbon SteelFasteners: ASTM A-307 Electro-Galv. PlatedShield: ASTM A-653 G-90 Galv. Steel
(see Pro-Shield for gauge)Vapor Barrier: ASTM E-96 All Service JacketFinishes: Painted Red Shop Primer
Hot-Dip Galv. per ASTM A-123
PIPESIZE
VERTICALLOAD
A BINS. THK. = 1” INS. THK. = 11/2” INS. THK. = 2” INS. THK. = 21/2” INS. THK. = 3” INS. THK. = 4”
C D E C D E C D E C D E C D E C D E
2” 230 3/8 x 2 0.375 2.31 8 6 3.13 9 6 3.63 10 6 4.13 11 6 4.63 12 6 5.69 14 621/2” 275 3/8 x 2 0.375 2.88 9 6 3.63 10 6 4.13 11 6 4.63 12 6 5.13 13 6 6.19 15 63” 325 3/8 x 2 0.375 3.13 9 6 3.63 10 6 4.13 11 6 4.63 12 6 5.13 13 6 6.19 15 64” 380 3/8 x 2 0.375 3.63 10 6 4.13 11 6 4.63 12 6 5.13 13 6 5.69 14 6 6.69 16 6
Ordering: Fig. NH40 - (Pipe Size) x (Insulation Thickness)
PRE-INSULATED TWO-ROD PIPE HANGERFIG. NH40
14
Hung from Two Rods
NATIONAL PIPE HANGER CORPORATION
PIPESIZE
VERTICALLOAD
A BINS. THK. = 1” INS. THK. = 11/2” INS. THK. = 2” INS. THK. = 21/2” INS. THK. = 3” INS. THK. = 4”
C D E C D E C D E C D E C D E C D E
5” 1200 1/2 x 3 0.5 4.13 11 6 4.63 12 6 5.13 13 6 5.69 14 6 6.19 15 6 7.31 18 66” 1600 1/2 x 3 0.5 4.63 12 6 5.13 13 6 5.69 14 6 6.19 15 6 6.69 16 6 7.81 19 68” 2600 1/2 x 3 0.625 5.69 15 6 6.19 16 6 6.69 17 6 7.31 18 6 7.81 19 6 8.81 21 6
10” 4000 5/8 x 3 0.75 6.88 17 6 7.5 18 6 8 19 6 8.5 20 6 9 21 6 10 23 912” 4800 3/4 x 3 0.75 8 20 6 8.5 21 6 9 22 6 9.5 23 6 10 24 6 11 26 914” 5000 3/4 x 3 0.75 8.5 21 6 9 22 6 9.5 23 6 10 24 9 10.5 25 9 11.5 27 916” 6600 1 x 5 1.25 9.63 25 6 10.13 26 9 10.63 27 9 11.13 28 9 11.63 29 9 12.63 31 918” 7000 1 x 5 1.25 10.63 27 9 11.13 28 9 11.63 29 9 12.13 30 9 12.63 31 9 13.63 33 920” 8200 1 x 6 1.25 11.63 29 9 12.13 30 9 12.63 31 9 13.13 32 9 13.63 33 9 14.63 35 1224” 11400 1 x 8 1.5 13.63 33 9 14.13 34 12 14.63 35 12 15.13 36 12 15.63 37 12 16.63 39 1230” 11400 1 x 8 1.5 16.63 39 12 17.13 40 12 17.63 41 12 18.13 42 12 18.63 43 12 19.63 45 12
Ordering: Fig. NH60 - (Pipe Size) x (Insulation Thickness)
PRE-INSULATED TWO-ROD PIPE HANGER FIG. NH60
Applications:
• Provides heavy duty vertical support in low overhead clearance pipe runs
• Designed for use on:Chilled Water Hot Water Steam
• Installation: hung from two threaded rods
• Temperature Range: +20°F to +1200°F
Features:
• Eliminates welding to pipe• Provides continuous vapor barrier• Insulation extends 2” to 3” beyond shield• Structural insulation for load transfer• ASTM E-84 Flame Spread/Smoke Developed: 10/5• Thermal Conductivity
0.54 Btu•in/(hr•ft2•°F) @ 200°F• Insulation chemically bonded
Material Data:
Insulation: Calcium Silicate meeting ASTM C-585 and C-656 Type II Grade 5450 psi, 18 pcf
Clamp: ASTM A-36 Carbon SteelFasteners: ASTM A-307 Electro-Galv. PlatedShield: ASTM A-653 G-90, 18 ga Galv. SteelVapor Barrier: ASTM E-96 All Service JacketFinishes: Painted Red Shop Primer
Hot-Dip Galv. per ASTM A-123
15
Hung from Two Rods
NATIONAL PIPE HANGER CORPORATION
Applications:
• Provides moderate duty vertical support and horizontal movement from rod swing
• Designed for use on:Chilled Water Hot Water Steam
• Installation: hung from single threadedrod
• Temperature Range: +20°F to +1200°F
Features:
• Eliminates welding to pipe• Provides continuous vapor barrier• Insulation extends 2” to 3” beyond shield• Structural insulation for load transfer• ASTM E-84 Flame Spread/Smoke Developed: 10/5• Thermal Conductivity
0.54 Btu•in/(hr•ft2•°F) @ 200°F• Insulation chemically bonded
Material Data:
Insulation: Calcium Silicate meeting ASTM C-585 and C-656 Type II Grade 5450 psi, 18 pcf
Clamp: ASTM A-36 Carbon SteelFasteners: ASTM A-307 Electro-Galv. PlatedShield: ASTM A-653 G-90, 18 ga Galv. SteelVapor Barrier: ASTM E-96 All Service JacketFinishes: Painted Red Shop Primer
Hot-Dip Galv. per ASTM A-123
PIPESIZE
VERT.LOAD
A B C DINS. THK. = 1” INS. THK. = 11/2” INS. THK. = 2” INS. THK. = 21/2” INS. THK. = 3” INS. THK. = 4”
E F E F E F E F E F E F
2” 320 3/16 x 2 0.375 0.675 0.75 3.31 6 3.88 6 4.38 6 4.88 6 5.38 6 6.44 621/2” 540 1/4 x 2 0.375 0.675 0.75 3.69 6 4.38 6 5 6 5.5 6 6 6 7.06 63” 540 1/4 x 2 0.375 0.675 0.75 4 6 4.5 6 5 6 5.5 6 6 6 7.06 64” 770 1/4 x 3 0.5 0.84 0.75 4.63 6 5.13 6 5.63 6 6.19 6 6.69 6 7.69 65” 1125 3/8 x 3 0.5 0.84 0.75 5.38 6 5.88 6 6.38 6 6.94 6 7.44 6 8.56 66” 1430 3/8 x 3 0.625 1.05 0.75 6 6 6.56 6 7.06 6 7.56 6 8.06 6 9.18 68” 1805 1/2 x 3 0.625 1.05 0.75 7.31 6 7.81 6 8.31 6 8.88 6 9.44 6 10.44 610” 2310 1/2 x 3 0.75 1.05 0.75 8.44 6 9 6 9.56 6 10.06 6 10.56 6 11.56 612” 2705 5/8 x 3 0.75 1.05 0.75 9.69 6 10.19 6 10.69 6 11.19 6 11.69 6 12.69 614” 2705 5/8 x 3 0.75 1.05 0.75 10.19 6 10.69 6 11.19 6 11.69 6 12.18 6 13.19 616” 3035 5/8 x 3 0.875 1.315 1 11.31 6 11.81 6 12.31 6 12.81 6 13.31 6 14.31 618” 3750 3/4 x 3 0.875 1.315 1 12.56 6 13.06 6 13.56 6 14.06 6 14.56 6 15.56 620” 3855 3/4 x 3 1 1.315 1 13.69 6 14.19 6 14.69 6 15.19 6 15.69 6 16.69 624” 4935 1 x 3 1 1.315 1 16.19 6 16.69 6 17.19 6 17.69 6 18.19 6 19.18 630” 5295 1 x 3 1.25 1.66 1.25 19.44 6 19.94 6 20.44 6 20.94 6 21.44 6 22.44 636” 7855 1 x 6 1.25 1.66 1.25 22.44 9 22.94 9 23.44 9 23.94 9 24.44 9 25.44 942” 7970 1 x 6 1.25 1.66 1.25 25.44 9 25.94 9 26.44 9 26.94 9 27.44 9 28.44 9
Ordering: Fig. NC30 - (Pipe Size) x (Insulation Thickness)
PRE-INSULATED TWO-BOLT PIPE CLAMPFIG. NC30
16
Hung from Single Rod
NATIONAL PIPE HANGER CORPORATION
Applications:
• Provides moderate duty vertical support and horizontal movement from rod swing
• Designed for use on:Chilled Water Hot Water Steam
• Installation: hung from single threadedrod
• Temperature Range: +20°F to +1200°F
Features:
• Eliminates welding to pipe• Provides continuous vapor barrier• Insulation extends 2” to 3” beyond shield• Structural insulation for load transfer• ASTM E-84 Flame Spread/Smoke Developed: 10/5• Thermal Conductivity
0.54 Btu•in/(hr•ft2•°F) @ 200°F• Insulation chemically bonded
Material Data:
Insulation: Calcium Silicate meeting ASTM C-585 and C-656 Type II Grade 5450 psi, 18 pcf
Clamp: ASTM A-36 Carbon SteelFasteners: ASTM A-307 Electro-Galv. PlatedShield: ASTM A-653 G-90, 18 ga Galv. SteelVapor Barrier: ASTM E-96 All Service JacketFinishes: Painted Red Shop Primer
Hot-Dip Galv. per ASTM A-123
PIPESIZE
VERT.LOAD
A B C DINS. THK. = 1” INS. THK. = 11/2” INS. THK. = 2” INS. THK. = 21/2” INS. THK. = 3” INS. THK. = 4”
E F E F E F E F E F E F
2” 605 1/4 x 3 0.375 0.675 0.75 3.44 6 4 6 4.5 6 5 6 5.5 6 6.56 621/2” 810 1/4 x 3 0.5 0.84 0.75 3.81 6 4.5 6 5.13 6 5.63 6 6.13 6 7.19 63” 1125 3/8 x 3 0.5 0.84 0.75 4.38 6 4.88 6 5.38 6 5.88 6 6.38 6 7.44 64” 1720 3/8 x 3 0.625 1.05 0.75 5 6 5.5 6 6 6 6.56 6 7.06 6 8.06 65” 2340 1/2 x 3 0.75 1.05 0.75 5.88 6 6.38 6 6.88 6 7.44 6 7.94 6 9.06 66” 2705 1/2 x 3 0.75 1.05 0.75 6.38 6 6.94 6 7.44 6 7.94 6 8.44 6 9.56 68” 3605 5/8 x 3 0.875 1.315 1 7.69 6 8.19 6 8.69 6 9.25 6 9.81 6 10.81 6
10” 3630 5/8 x 3 0.875 1.315 1 8.69 6 9.25 6 9.81 6 10.31 6 10.81 6 11.81 612” 4660 3/4 x 3 1 1.315 1 10.19 6 10.69 6 11.19 6 11.69 6 12.19 6 13.19 614” 4660 3/4 x 3 1 1.315 1 10.69 6 11.19 6 11.69 6 12.19 6 12.69 6 13.69 616” 6820 3/4 x 5 1.25 1.66 1.25 11.94 9 12.44 9 12.94 9 13.44 9 13.94 9 14.94 918” 6820 3/4 x 5 1.25 1.66 1.25 12.94 9 13.44 9 13.94 9 14.44 9 14.94 9 15.94 920” 7970 1 x 6 1.25 1.66 1.25 14.44 9 14.94 9 15.44 9 15.94 9 16.44 9 17.44 924” 10285 1 x 6 1.5 1.9 1.25 16.69 9 17.19 9 17.69 9 18.19 9 18.69 9 19.69 930” 10600 1 x 6 1.5 1.9 1.25 19.69 9 20.19 9 20.69 9 21.19 9 21.69 9 22.69 936” 13020 11/4 x 6 2 2.375 1.75 23.69 9 24.19 9 24.69 9 25.19 9 25.69 9 26.69 942” 13020 11/4 x 6 2 2.375 1.75 26.69 9 27.19 9 27.69 9 28.19 9 28.69 9 29.69 9
Ordering: Fig. NC31 - (Pipe Size) x (Insulation Thickness)
PRE-INSULATED TWO-BOLT PIPE CLAMP FIG. NC31
17
Hung from Single Rod
NATIONAL PIPE HANGER CORPORATION
Applications:
• Provides heavy duty vertical support and horizontal movement from rod swing
• Designed for use on:Chilled Water Hot Water Steam
• Installation: hung from single threaded rod
• Temperature Range: +20°F to +1200°F
Features:
• Eliminates welding to pipe• Provides continuous vapor barrier• Insulation extends 2” to 3” beyond shield• Structural insulation for load transfer• ASTM E-84 Flame Spread/Smoke Developed: 10/5• Thermal Conductivity
0.54 Btu•in/(hr•ft2•°F) @ 200°F• Insulation mechanically and chemically bonded
Material Data:
Insulation: Calcium Silicate meeting ASTM C-585 and C-656 Type II Grade 5450 psi, 18 pcf
Clamp: ASTM A-36 Carbon SteelFasteners: ASTM A-307 Electro-Galv. PlatedShield: ASTM A-653 G-90, 18 ga Galv. SteelVapor Barrier: ASTM E-96 All Service JacketFinishes: Painted Red Shop Primer
Hot-Dip Galv. per ASTM A-123
PIPESIZE
VERT.LOAD
A B C DINS. THK. = 1” INS. THK. = 11/2” INS. THK. = 2” INS. THK. = 21/2” INS. THK. = 3” INS. THK. = 4”
E F E F E F E F E F E F
2” 1215 1/4 x 5 0.625 1.05 0.75 3.69 9 4.25 9 4.75 9 5.25 9 5.75 9 6.81 921/2” 1215 1/4 x 5 0.625 1.05 0.75 3.94 9 4.63 9 5.25 9 5.75 9 6.25 9 7.31 93” 1805 3/8 x 5 0.625 1.05 0.75 4.5 9 5 9 5.5 9 6 9 6.5 9 7.56 94” 2585 3/8 x 5 0.75 1.05 0.75 5.13 9 5.63 9 6.13 9 6.69 9 7.19 9 8.19 95” 2705 1/2 x 5 0.75 1.05 0.75 5.88 9 6.38 9 6.88 9 7.44 9 7.94 9 9.06 96” 3750 1/2 x 5 0.875 1.315 1 6.5 9 7.06 9 7.56 9 8.06 9 8.56 9 9.69 98” 4215 1/2 x 5 1 1.315 1 7.81 9 8.31 9 8.81 9 9.38 9 9.94 9 10.94 910” 6045 5/8 x 5 1.25 1.66 1.25 9.06 9 9.63 9 10.19 9 10.69 9 11.19 9 12.19 912” 7770 3/4 x 5 1.25 1.66 1.25 10.44 9 10.94 9 11.44 9 11.94 9 12.44 9 13.44 914” 7770 3/4 x 5 1.25 1.66 1.25 10.94 9 11.44 9 11.94 9 12.44 9 12.94 9 13.94 916” 7970 1 x 5 1.25 1.66 1.25 12.44 9 12.94 9 13.44 9 13.94 9 14.44 9 15.44 918” 11270 1 x 5 1.5 1.9 1.25 13.69 9 14.19 9 14.69 9 15.19 9 15.69 9 16.69 920” 11465 1 x 6 1.5 1.9 1.25 14.69 9 15.19 9 15.69 9 16.19 9 16.69 9 17.69 924” 12220 1 x 6 2 2.375 1.75 17.06 9 17.56 9 18.06 9 18.56 9 19.06 9 20.06 930” 16480 11/4 x 6 2 2.375 1.75 20.69 9 21.19 9 21.69 9 22.19 9 22.69 9 23.69 936” 17370 11/4 x 8 2 2.375 1.75 23.69 12 24.19 12 24.69 12 25.19 12 25.69 12 26.69 1242” 17370 11/4 x 8 2 2.375 1.75 26.69 12 27.19 12 27.69 12 28.19 12 28.69 12 29.69 12
Ordering: Fig. NC32 - (Pipe Size) x (Insulation Thickness)
PRE-INSULATED TWO-BOLT PIPE CLAMPFIG. NC32
18
Hung from Single Rod
NATIONAL PIPE HANGER CORPORATION
Applications:
• Provides heavy duty vertical support and horizontal movement from rod swing
• Designed for use on:Chilled Water Hot Water Steam
• Installation: hung from single threadedrod
• Temperature Range: +20°F to +1200°F
Features:
• Eliminates welding to pipe• Provides continuous vapor barrier• Insulation extends 2” to 3” beyond shield• Structural insulation for load transfer• ASTM E-84 Flame Spread/Smoke Developed: 10/5• Thermal Conductivity
0.61 Btu•in/(hr•ft2•°F) @ 200°F• Insulation mechanically and chemically bonded
Material Data:
Insulation: Calcium Silicate meeting ASTM C-585 and C-656 Type II Grade 6900 psi, 28 pcf
Clamp: ASTM A-36 Carbon SteelFasteners: ASTM A-307 Electro-Galv. PlatedShield: ASTM A-653 G-90, 18 ga Galv. SteelVapor Barrier: ASTM E-96 All Service JacketFinishes: Painted Red Shop Primer
Hot-Dip Galv. per ASTM A-123
PIPESIZE
VERT.LOAD
A B C DINS. THK. = 1” INS. THK. = 11/2” INS. THK. = 2” INS. THK. = 21/2” INS. THK. = 3” INS. THK. = 4”
E F E F E F E F E F E F
2” 1715 1/4 x 6 0.625 1.05 0.75 3.69 9 4.25 9 4.75 9 5.25 9 5.75 9 6.81 921/2” 1805 3/8 x 6 0.625 1.05 0.75 4.19 9 4.88 9 5.5 9 6 9 6.5 9 7.56 93” 2705 3/8 x 6 0.75 1.05 0.75 4.59 9 5.13 9 5.63 9 6.13 9 6.63 9 7.69 94” 3445 3/8 x 6 0.875 1.315 1 5.25 9 5.75 9 6.25 9 6.81 9 7.31 9 8.31 95” 3750 1/2 x 6 0.875 1.315 1 6 9 6.50 9 7 9 7.56 9 8.06 9 9.19 96” 4935 1/2 x 6 1 1.315 1 6.75 9 7.31 9 7.81 9 8.31 9 8.81 9 9.94 98” 7215 5/8 x 6 1.25 1.66 1.25 8.06 9 8.56 9 9.06 9 9.63 9 10.19 9 11.19 9
10” 7250 5/8 x 6 1.25 1.66 1.25 9.06 9 9.63 9 10.19 9 10.69 9 11.19 9 12.19 912” 9320 3/4 x 6 1.5 1.9 1.25 10.69 9 11.19 9 11.69 9 12.19 9 12.69 9 13.69 914” 9320 3/4 x 6 1.5 1.9 1.25 11.19 9 11.69 9 12.19 9 12.69 9 13.19 9 14.19 916” 11465 1 x 6 1.5 1.9 1.25 12.69 9 13.19 9 13.69 9 14.19 9 14.69 9 15.69 918” 14445 1 x 6 2 2.375 1.75 14.06 9 14.56 9 15.06 9 15.56 9 16.06 9 17.06 920” 16580 11/4 x 6 2 2.375 1.75 15.69 9 16.19 9 16.69 9 17.19 9 17.69 9 18.69 924” 19005 11/4 x 6 2 2.375 1.75 17.69 9 18.19 9 18.69 9 19.19 9 19.69 9 20.69 930” 20605 11/4 x 8 2 2.375 1.75 20.69 12 21.19 12 21.69 12 22.19 12 22.69 12 23.69 1236” 24905 11/2 x 8 2.5 3.5 1.75 24.44 12 24.94 12 25.44 12 25.94 12 26.44 12 27.44 1242” 24905 11/2 x 8 2.5 3.5 1.75 27.44 12 27.94 12 28.44 12 28.94 12 29.44 12 30.44 12
Ordering: Fig. NC33 - (Pipe Size) x (Insulation Thickness)
PRE-INSULATED TWO-BOLT PIPE CLAMP FIG. NC33
19
Hung from Single Rod
NATIONAL PIPE HANGER CORPORATION
Applications:
• Provides light duty vertical support and horizontal movement from rod swing
• Designed for use on:Chilled Water Hot Water Steam
• Installation: hung from single threadedrod
• Temperature Range: +20°F to +1200°F
Features:
• Eliminates welding to pipe• Provides continuous vapor barrier• Insulation extends 2” beyond shield• Structural insulation for load transfer• ASTM E-84 Flame Spread/Smoke Developed: 10/5• Thermal Conductivity
0.41 Btu•in/(hr•ft2•°F) @ 200°F• Insulation chemically bonded
Material Data:
Insulation: Calcium Silicate meeting ASTM C-585 and C-533 Type IValue Engineered Products, Inc.Pro-Shield: 100 psi, 14.5 pcf
Clamp: ASTM A-36 Carbon SteelFasteners: ASTM A-307 Electro-Galv. PlatedShield: ASTM A-653 G-90 Galv. Steel
(see Pro-Shield for gauge)Vapor Barrier: ASTM E-96 All Service JacketFinishes: Painted Red Shop Primer
Hot-Dip Galv. per ASTM A-123
PIPESIZE
VERT.LOAD
A B C DINS. THK. = 1” INS. THK. = 11/2” INS. THK. = 2” INS. THK. = 21/2” INS. THK. = 3” INS. THK. = 4”
E F E F E F E F E F E F
2” 230 1/4 x 11/2 0.5 0.84 0.63 3.56 6 4.13 6 4.63 6 5.13 6 5.63 6 6.69 621/2” 275 1/4 x 11/2 0.5 0.84 0.63 3.81 6 4.5 6 5.13 6 5.63 6 6.13 6 7.19 63” 325 1/4 x 11/2 0.63 1.05 0.63 4.25 6 4.75 6 5.25 6 5.75 6 6.25 6 7.31 64” 380 1/4 x 11/2 0.63 1.05 0.63 4.75 6 5.25 6 5.75 6 6.31 6 6.81 6 7.81 6
Ordering: Fig. NC10 - (Pipe Size) x (Insulation Thickness)
PRE-INSULATED TWO-BOLT PIPE CLAMPFIG. NC10
20
Hung from Single Rod
NATIONAL PIPE HANGER CORPORATION
Applications:
• Provides vertical support and resistanceto axial forces
• Designed for use on:Chilled Water Hot Water SteamStraight runs with expansion jointsproducing axial thrust forces
• Installation: welded to flat steel surface• Temperature Range: +20°F to +1200°F• Axial Load ratings do not include local
stress evaluation at thrust plate/pipewall interface. Contact factory for assistance.
Features:
• Structural insulation for load transfer• ASTM E-84 Flame Spread/Smoke Developed: 10/5• Thermal Conductivity
0.61 Btu•in/(hr•ft2•°F) @ 200°F• Insulation chemically bonded• B.O.P. to T.O.S. matched to NS and NG models• Four thrust plates shipped loose for field welding
Material Data:
Insulation: Calcium Silicate meeting ASTM C-585 andC-656 Type II Grade 6900 psi, 28 pcf
Base/Clamp: ASTM A-36 Carbon SteelFasteners: ASTM A-307 Electro-Galv. PlatedShield: ASTM A-653 G-90, 18 ga Galv. SteelVapor Barrier: ASTM E-96 All Service JacketFinish: Painted Red Shop Primer
Hot-Dip Galv. per ASTM A-123
PIPESIZE
VERT. LOAD
INS. THK. = 1” INS. THK. = 11/2” INS. THK. = 2” INS. THK. = 21/2” INS. THK. = 3” INS. THK. = 4”
AXIAL A B AXIAL A B AXIAL A B AXIAL A B AXIAL A B AXIAL A B
2” 1640 730 4 2.5 1160 4 3 1620 4 4 2460 4 4.5 2460 6 5.5 2460 6 7.521/2” 1980 890 4 2.5 1410 4 4 1960 4 4.5 2980 4 5.5 2980 6 6.5 2980 6 83” 2420 1400 4 3 2400 4 4 3450 4 4.5 3620 4 5.5 3620 6 6.5 3620 6 84” 3110 1730 4 4 2900 4 4.5 4100 4 5.5 4660 4 6.5 4660 6 7.5 4660 6 95” 3840 2060 4 4.5 3400 4 5.5 4750 4 6.5 5760 4 7.5 5760 6 8 5760 6 9.56” 4570 2400 4 5.5 3900 4 6.5 5400 4 7.5 6860 4 8 6860 6 9 6860 6 10.58” 5950 3020 4 7.5 4850 4 8 6675 4 9 8930 6 9.5 8930 6 10.5 8930 6 12
10” 7420 3700 4 9 5850 4 9.5 8000 4 10.5 11130 6 11 11130 6 12 11130 6 1312” 8800 4320 4 10.5 6800 4 11 9300 4 12 13200 6 12.5 13200 6 13 13200 6 14.514” 10000 4700 4 11 7350 4 12 10000 4 12.5 15000 6 13 15000 6 14 15000 6 15.516” 11600 5340 4 12.5 8320 4 13 11300 6 14 17400 6 14.5 17400 6 15.5 17400 8 16.518” 12800 5970 4 14 9240 4 14.5 12500 6 15.5 19200 6 16 19200 6 16.5 19200 8 1820” 13600 6600 4 15.5 10200 4 16 13800 6 16.5 20400 6 17.5 20400 6 18 20400 8 19.524” 14400 7850 4 18 12000 4 19 16300 6 19.5 21600 6 20.5 21600 6 21 21600 8 22.530” 18800 9740 4 22.5 14900 6 23 20100 6 24 28200 6 24.5 28200 6 25 28200 8 26.536” 22000 11600 4 26.5 17750 6 27.5 23900 6 28 33000 6 28.5 33000 6 29.5 33000 8 3142” 24800 13500 4 31 20500 6 31.5 23900 6 32.5 37200 6 33 37200 6 33.5 37200 8 35
Ordering: Fig. NA40 - (Pipe Size) x (Insulation Thickness)
PRE-INSULATED PIPE ANCHOR FIG. NA40
21
For Axial & Vertical Loads
NATIONAL PIPE HANGER CORPORATION
Applications:
• Provides vertical support to downwardriser loads
• Designed for use on:Chilled Water Hot Water Steam
• Installation: hung from two threaded rods or rest on a flat surface
• Temperature Range: +20°F to +1200°F • Vertical Load ratings do not include
local stress evaluation at thrust plate/pipe wall interface. Contact factory for assistance.
Features:
• Provides continuous vapor barrier• Structural insulation for load transfer• ASTM E-84 Flame Spread/Smoke Developed: 10/5• Thermal Conductivity
0.61 Btu•in/(hr•ft2•°F) @ 200°F• Insulation chemically bonded• Two thrust plates shipped loose for field welding
Material Data:
Insulation: Calcium Silicate meeting ASTM C-585 andC-656 Type II Grade 6900 psi, 28 pcf
Base/Clamp: ASTM A-36 Carbon SteelFasteners: ASTM A-307 Electro-Galv. PlatedShield: ASTM A-653 G-90, 18 ga Galv. SteelVapor Barrier: ASTM E-96 All Service JacketFinishes: Painted Red Shop Primer
Hot-Dip Galv. per ASTM A-123
PIPESIZE
VERT.LOAD
A B C DINS. THK. = 1” INS. THK. = 11/2” INS. THK. = 2” INS. THK. = 21/2” INS. THK. = 3” INS. THK. = 4”
E F E F E F E F E F E F
2” 750 0.63 1.05 1/2 x 4 2 12.38 5.63 13.5 6.69 14.5 7.75 15.5 8.75 16.5 9.75 18.63 11.8821/2” 900 0.63 1.05 1/2 x 4 2 12.88 6.13 14.25 7.75 15.5 8.75 16.5 9.75 17.5 10.75 19.63 12.883” 1200 0.63 1.05 1/2 x 4 2 13.5 6.69 14.5 7.75 15.5 8.75 16.5 9.75 17.5 10.75 19.63 12.884” 1800 0.63 1.05 1/2 x 4 2 14.5 7.75 15.5 8.75 16.5 9.75 17.63 10.75 18.63 11.88 20.63 13.885” 2400 0.63 1.05 1/2 x 4 2 15.5 8.75 16.5 9.75 17.5 10.75 18.63 11.88 19.63 12.88 21.88 15.136” 3000 0.88 1.05 1/2 x 6 4 16.5 9.75 17.63 10.75 18.63 11.88 19.63 12.88 20.63 13.88 22.88 16.138” 3900 0.88 1.05 1/2 x 6 4 18.63 11.88 19.63 12.88 20.63 13.88 21.75 15.13 22.88 16.13 24.88 18.1310” 4800 0.88 1.05 1/2 x 6 4 21.38 13.88 22.5 15.13 23.63 16.13 24.63 17.13 25.63 18.13 27.63 20.1312” 6800 1.13 1.315 1/2 x 8 6 23.88 16.13 24.88 17.13 25.88 18.13 26.88 19.13 27.88 20.13 29.88 22.1314” 8000 1.13 1.315 1/2 x 8 6 24.88 17.13 25.88 18.13 26.88 19.13 27.88 20.13 28.88 21.13 30.88 23.1316” 9200 1.13 1.315 5/8 x 8 6 27.38 19.38 28.38 20.38 29.38 21.38 30.38 22.38 31.38 23.38 33.38 25.3818” 10000 1.13 1.315 5/8 x 8 6 29.38 21.38 30.38 22.38 31.38 23.38 32.38 24.38 33.38 25.38 35.38 27.3820” 10800 1.13 1.315 5/8 x 8 6 31.38 23.38 32.38 24.38 33.38 25.38 34.38 26.38 35.38 27.38 37.38 29.3824” 11200 1.13 1.66 5/8 x 8 6 36.38 27.38 37.38 28.38 38.38 29.38 39.38 30.38 40.38 31.38 42.38 33.38
Ordering: Fig. NR10 - (Pipe Size) x (Insulation Thickness)
For Downward Riser LoadsPRE-INSULATED PIPE RISER CLAMPFIG. NR10
22
NATIONAL PIPE HANGER CORPORATION
Applications:
• Provides vertical support to upward and downward riser loads
• Designed for use on:Chilled Water Hot Water Steam
• Installation: welded to a flat surface orrigidly braced
• Temperature Range: +20°F to +1200°F• Vertical Load ratings do not include
local stress evaluation at thrust plate/pipe wall interface. Contact factory for assistance.
Features:
• Provides continuous vapor barrier• Structural insulation for load transfer• ASTM E-84 Flame Spread/Smoke Developed: 10/5• Thermal Conductivity
0.61 Btu•in/(hr•ft2•°F) @ 200°F• Insulation chemically bonded• Four thrust plates shipped loose for field welding
Material Data:
Insulation: Calcium Silicate meeting ASTM C-585 andC-656 Type II Grade 6900 psi, 28 pcf
Base/Clamp: ASTM A-36 Carbon SteelFasteners: ASTM A-307 Electro-Galv. PlatedShield: ASTM A-653 G-90, 18 ga Galv. SteelVapor Barrier: ASTM E-96 All Service JacketFinishes: Painted Red Shop Primer
Hot-Dip Galv. per ASTM A-123
PIPESIZE
VERT.LOAD
A B C DINS. THK. = 1” INS. THK. = 11/2” INS. THK. = 2” INS. THK. = 21/2” INS. THK. = 3” INS. THK. = 4”
E F E F E F E F E F E F
2” 750 0.63 1.05 1/2 x 4 2 12.38 5.63 13.5 6.69 14.5 7.75 15.5 8.75 16.5 9.75 18.63 11.8821/2” 900 0.63 1.05 1/2 x 4 2 12.88 6.13 14.25 7.75 15.5 8.75 16.5 9.75 17.5 10.75 19.63 12.883” 1200 0.63 1.05 1/2 x 4 2 13.5 6.69 14.5 7.75 15.5 8.75 16.5 9.75 17.5 10.75 19.63 12.884” 1800 0.63 1.05 1/2 x 4 2 14.5 7.75 15.5 8.75 16.5 9.75 17.63 10.75 18.63 11.88 20.63 13.885” 2400 0.63 1.05 1/2 x 4 2 15.5 8.75 16.5 9.75 17.5 10.75 18.63 11.88 19.63 12.88 21.88 15.136” 3000 0.88 1.05 1/2 x 6 4 16.5 9.75 17.63 10.75 18.63 11.88 19.63 12.88 20.63 13.88 22.88 16.138” 3900 0.88 1.05 1/2 x 6 4 19.62 11.88 20.63 12.88 21.63 13.88 21.75 15.13 23.88 16.13 24.88 18.13
10” 4800 1.13 1.05 1/2 x 6 4 21.38 13.88 22.5 15.13 23.63 16.13 24.63 17.13 25.63 18.13 27.63 20.1312” 6800 1.13 1.315 1/2 x 8 6 23.88 16.13 24.88 17.13 25.88 18.13 26.88 19.13 27.88 20.13 29.88 22.1314” 8000 1.13 1.315 1/2 x 8 6 24.88 17.13 25.88 18.13 26.88 19.13 27.88 20.13 28.88 21.13 30.88 23.1316” 9200 1.13 1.315 5/8 x 8 6 27.38 19.38 28.38 20.38 29.38 21.38 30.38 22.38 31.38 23.38 33.38 25.3818” 10000 1.13 1.315 5/8 x 8 6 29.38 21.38 30.38 22.38 31.38 23.38 32.38 24.38 33.38 25.38 35.38 27.3820” 10800 1.13 1.315 5/8 x 8 6 31.38 23.38 32.38 24.38 33.38 25.38 34.38 26.38 35.38 27.38 37.38 29.3824” 11200 1.13 1.66 5/8 x 8 6 36.38 27.38 37.38 28.38 38.38 29.38 39.38 30.38 40.38 31.38 42.38 33.38
Ordering: Fig. NR20 - (Pipe Size) x (Insulation Thickness)
For Upward and Downward Riser LoadsPRE-INSULATED PIPE RISER CLAMP FIG. NR20
23
NATIONAL PIPE HANGER CORPORATION
Applications:
• Provides light duty vertical support and lateral support
• Designed for use on:Chilled Water Hot Water Steam
• Installation: clamped to 15/8" wide strut• Temperature Range: +20°F to +1200°F
Features:
• Eliminates welding to pipe• Provides continuous vapor barrier• Insulation extends 2” to 3” beyond shield• Structural insulation for load transfer• ASTM E-84 Flame Spread/Smoke Developed: 10/5• Thermal Conductivity
0.41 Btu•in/(hr•ft2•°F) @ 200°F• Insulation chemically bonded
Material Data:
Insulation: Calcium Silicate meeting ASTM C-585 and C-533 Type IValue Engineered Products, Inc.Pro-Shield: 100 psi, 14.5 pcf standard with 450 psi, 18 pcf insert for 12" pipe
Clamp: ASTM A-36 Carbon Steel, ¼" x 1½"Fasteners: ASTM A-307 Electro-Galv. PlatedShield: ASTM A-653 G-90 Galv. Steel
(see Pro-Shield for Gauge) Vapor Barrier: ASTM E-96 All Service JacketFinishes: Painted Red Shop Primer
Hot-Dip Galv. per ASTM A-123
PIPESIZE
VERTICALLOAD
LATERALLOAD
INS. THK. = 1” INS. THK. = 11/2” INS. THK. = 2” INS. THK. = 21/2” INS. THK. = 3” INS. THK. = 4”
A / B C A / B C A / B C A / B C A / B C A / B C
2” 130 50 4 / 6 2.06 4 / 6 2.81 4 / 6 3.38 4 / 6 3.88 4 / 6 4.38 4 / 6 5.4421/2” 150 50 4 / 6 2.56 4 / 6 3.38 4 / 6 3.88 4 / 6 4.38 4 / 6 4.88 4 / 6 5.943” 165 50 4 / 6 2.81 4 / 6 3.38 4 / 6 3.88 4 / 6 4.38 4 / 6 4.88 4 / 6 5.944” 170 50 4 / 6 3.38 4 / 6 3.88 4 / 6 4.38 4 / 6 4.88 4 / 6 5.44 4 / 6 6.445” 260 50 4 / 6 3.88 4 / 6 4.38 4 / 6 4.88 4 / 6 5.44 4 / 6 5.94 4 / 6 7.066” 330 50 6 / 9 4.38 6 / 9 4.88 6 / 9 5.44 6 / 9 5.94 6 / 9 6.44 6 / 9 7.568” 510 50 6 / 9 5.44 6 / 9 5.94 6 / 9 6.44 6 / 9 7.06 6 / 9 7.56 6 / 9 8.56
10” 830 50 6 / 9 6.44 6 / 9 7.06 6 / 9 7.56 6 / 9 8.06 6 / 9 8.56 6 / 9 9.5612” 1200 50 6 / 9 7.56 6 / 9 8.06 6 / 9 8.56 6 / 9 9.06 6 / 9 9.56 6 / 9 10.56
Ordering: Fig. NC70 - (Pipe Size) x (Insulation Thickness)
PRE-INSULATED HOLDDOWN STRUT CLAMP
FIG. NC70
For Use on Strut
24
NATIONAL PIPE HANGER CORPORATION
Applications:
• Provides light duty vertical support and lateral support for buckling and movement control
• Designed for use on:Chilled Water Hot Water Steam
• Installation: clamped to 15/8" wide strut• Temperature Range: +20°F to +1200°F• Lateral Travel: ± 1/16”• Vertical Travel: + 1/16” up
Features:
• Eliminates welding to pipe• Provides continuous vapor barrier• Insulation extends 2” to 3” beyond shield• Structural insulation for load transfer• ASTM E-84 Flame Spread/Smoke Developed: 10/5• Thermal Conductivity
0.41 Btu•in/(hr•ft2•°F) @ 200°F• Insulation chemically bonded
Material Data:
Insulation: Calcium Silicate meeting ASTM C-585 and C-533 Type IValue Engineered Products, Inc.Pro-Shield: 100 psi, 14.5 pcf standard with 450 psi, 18 pcf insert for 12" pipe
Clamp: ASTM A-36 Carbon Steel, ¼" x 1½"Fasteners: ASTM A-307 Electro-Galv. PlatedShield: ASTM A-653 G-90 Galv. Steel
(see Pro-Shield for Gauge) Vapor Barrier: ASTM E-96 All Service Jacket Finishes: Painted Red Shop Primer
Hot-Dip Galv. per ASTM A-123
PIPESIZE
VERTICALLOAD
LATERALLOAD
INS. THK. = 1” INS. THK. = 11/2” INS. THK. = 2” INS. THK. = 21/2” INS. THK. = 3” INS. THK. = 4”
A / B C A / B C A / B C A / B C A / B C A / B C
2” 130 230 4 / 6 2.06 4 / 6 2.81 4 / 6 3.38 4 / 6 3.88 4 / 6 4.38 4 / 6 5.4421/2” 150 275 4 / 6 2.56 4 / 6 3.38 4 / 6 3.88 4 / 6 4.38 4 / 6 4.88 4 / 6 5.943” 165 325 4 / 6 2.81 4 / 6 3.38 4 / 6 3.88 4 / 6 4.38 4 / 6 4.88 4 / 6 5.944” 170 380 4 / 6 3.38 4 / 6 3.88 4 / 6 4.38 4 / 6 4.88 4 / 6 5.44 4 / 6 6.445” 260 400 4 / 6 3.88 4 / 6 4.38 4 / 6 4.88 4 / 6 5.44 4 / 6 5.94 4 / 6 7.066” 330 400 6 / 9 4.38 6 / 9 4.88 6 / 9 5.44 6 / 9 5.94 6 / 9 6.44 6 / 9 7.568” 510 400 6 / 9 5.44 6 / 9 5.94 6 / 9 6.44 6 / 9 7.06 6 / 9 7.56 6 / 9 8.56
10” 830 400 6 / 9 6.44 6 / 9 7.06 6 / 9 7.56 6 / 9 8.06 6 / 9 8.56 6 / 9 9.5612” 1200 400 6 / 9 7.56 6 / 9 8.06 6 / 9 8.56 6 / 9 9.06 6 / 9 9.56 6 / 9 10.56
Ordering: Fig. NC80 - (Pipe Size) x (Insulation Thickness)
FIG. NC80
25
For Use on Strut, Laterally Guided
NATIONAL PIPE HANGER CORPORATION
PRE-INSULATED GUIDED STRUT CLAMP
PRO-SHIELD
Description / Features Pro-Shields are 360° thermal hanger shields designed to meet the broadest range of pipe support applications. They providea continuous section of insulation and vapor barrier through a wide variety of pipe hangers for piping systems operating between +20°F and +1200°F. The insulation and vapor barrier extend beyond the galvanized steel shield for a neat, vapor-tight joint with the adjoining insulation. Pro-Shields are suitable for use in any type of clamp as well as in band-type hangers and on flatsurfaces. To assure proper support in all situations, high density 450 psi inserts are installed in units for 10” pipe with 1” insulation thickness and in all units for 12” pipe and larger. Pro-Shields meet the MSS standard for Type 40 shields per MSS SP-58, Para-graph 7.6.
Applications• For indoor use on clamping support systems, flat surfaces, clevis or other band-type hangers (see WeatherShield
Upgrade submittal for outdoor applications).• Pipe sizes 16” and larger in clevis or two bolt hangers only.• Chilled to steam piping and dual temperature lines.• Hanger spans per MSS SP-58 Table A3.• Available for pipe 1/2” through 24”, insulation thickness 1/2” through 4”.
Materials / Construction• 100 psi Calcium silicate meeting ASTM C-533 Type I, C-585, C-795, E-84 Flame Spread/Smoke Developed: 0/0,
Thermal Conductivity = 0.41 Btu•in/(hr•ft2•°F) @ 200°F.• Adhesive complying with NFPA 90-A, ASTM E-84 Flame Spread/Smoke Developed: 10/0.• G-90 Galvanized steel shield, small check per ASTM A-653 (replaces A-527).• Vapor barrier of all service jacket meeting ASTM D-774, D-828 and E-84 Flame Spread/Smoke Developed: 5/5.• Structural insert (12" pipe and larger) minimum 450 psi calcium silicate meeting ASTM C-656 Type II Grade 5,
C-795 and E-84 Flame Spread/Smoke Developed: 0/0.• All units and components are asbestos free and 100% made and assembled in the U.S.A.
PIPE SIZE 1/2” TO 11/2” 2” TO 5” 6” TO 8” 10” TO 12” 14” TO 24”INSULATION LENGTH - in. 6 6 9 9 12
SHIELD LENGTH - in. 4 4 6 6 10SHIELD GAUGE 22 20 16 14 12
COMPRESSIVE STRENGTH - psi 100 100 100 100 / 450 100 / 450
DIMENSIONS
PIPE SIZE 1/2” 1” 11/2” 2” 3” 4” 6” 8” 10” 12” 14” 16” 18” 20” 24”
CLEVIS80 lbf7 ft.
130 lbf7 ft.
185 lbf9 ft.
230 lbf10 ft.
325 lbf10 ft.
380 lbf10 ft.
605 lbf10 ft.
800 lbf10 ft.
1160 lbf10 ft.
1400 lbf10 ft.
1800 lbf10 ft.
2600 lbf10 ft.
3300 lbf10 ft.
4000 lbf10 ft.
6175 lbf10 ft.
TRAPEZE40 lbf7 ft.
60 lbf7 ft.
85 lbf9 ft.
130 lbf10 ft.
165 lbf10 ft.
170 lbf10 ft.
330 lbf10 ft.
510 lbf10 ft.
830 lbf10 ft.
1200 lbf10 ft.
1250 lbf10 ft.
SeeMaxSpan
SeeMaxSpan
SeeMaxSpan
SeeMaxSpan
ALLOWABLE LOADS / RECOMMENDED SPANS
26
NATIONAL PIPE HANGER CORPORATION
PRO-SHIELD N.T.
Description / FeaturesPro-Shield N.T. units provide a continuous section of insulation and vapor barrier through a wide variety of pipe hangers for piping systems operating between +20°F and +1200°F. The Pro-Shield N.T. is designed for use in band-type hangers and on flat surfaces. The insulation and vapor barrier extend beyond the galvanized steel shield for a neat, vapor-tight joint with the adjoining insulation. Pro-Shield N.T. meets the MSS standard for Type 40 shields per MSS SP-58, Paragraph 7.6. To assureproper support in all situations, high density 450 psi inserts are installed in units for 10” pipe with 1” insulation thickness and inall units for 12” pipe and larger.
Applications• For indoor use on flat surfaces, clevis or other band-type hangers (see WeatherShield Upgrade submittal for
outdoor applications).• Pipe sizes 16” and larger in clevis hangers only. • Chilled to steam piping and dual temperature lines.• Hanger spans per MSS SP-58 Table A3.• Available for pipe 1/2” through 24”, insulation thickness 1/2” through 4”.
Materials / Construction• 100 psi Calcium silicate meeting ASTM C-533 Type I, C-585, C-795, E-84 Flame Spread/Smoke Developed: 0/0,
Thermal Conductivity = 0.41 Btu•in/(hr•ft2•°F) @ 200°F.• Adhesive complying with NFPA 90-A, ASTM E-84 Flame Spread/Smoke Developed: 10/0.• G-90 Galvanized steel shield, small check per ASTM A-635 (replaces A-527).• Vapor barrier of all service jacket meeting ASTM D-774, D-828 and E-84 Flame Spread/Smoke Developed: 5/5.• Structural insert (12" pipe and larger) minimum 450 psi calcium silicate meeting ASTM C-656 Type II Grade 5,
C-795 and E-84 Flame Spread/Smoke Developed: 0/0.• All units and components are asbestos free and 100% made and assembled in the U.S.A.
PIPE SIZE 1/2” TO 11/2” 2” TO 5” 6” TO 8” 10” TO 12” 14” TO 24”INSULATION LENGTH - in. 6 6 9 9 12
SHIELD LENGTH - in. 4 4 6 6 10SHIELD GAUGE 22 20 16 14 12
COMPRESSIVE STRENGTH - psi 100 100 100 100 / 450 100 / 450
DIMENSIONS
ALLOWABLE LOADS / RECOMMENDED SPANS
27
PIPE SIZE 1/2” 1” 11/2” 2” 3” 4” 6” 8” 10” 12” 14” 16” 18” 20” 24”
CLEVIS80 lbf7 ft.
130 lbf7 ft.
185 lbf9 ft.
230 lbf10 ft.
325 lbf10 ft.
380 lbf10 ft.
605 lbf10 ft.
800 lbf10 ft.
1160 lbf10 ft.
1400 lbf10 ft.
1800 lbf10 ft.
2600 lbf10 ft.
3300 lbf10 ft.
4000 lbf10 ft.
6175 lbf10 ft.
TRAPEZE40 lbf7 ft.
60 lbf7 ft.
85 lbf9 ft.
130 lbf10 ft.
165 lbf10 ft.
170 lbf10 ft.
330 lbf10 ft.
510 lbf10 ft.
830 lbf10 ft.
1200 lbf10 ft.
1250 lbf10 ft.
SeeMaxSpan
SeeMaxSpan
SeeMaxSpan
SeeMaxSpan
NATIONAL PIPE HANGER CORPORATION
QUIK-SHIELD
Description / FeaturesQuik-Shields are economically priced 180° thermal hanger shields providing a continuous section of insulation and vapor barrier through a variety of pipe hangers. The vapor barrier jacket extends beyond the galvanized steel shield and beyond the insulation insert for a neat, vapor-tight fit with both the adjoining and the field-applied top insulation. To assure proper support in all situations, high density 450 psi structural inserts are installed in units for 10" pipe with 1" insulation thickness and in all unitsfor 12" pipe and larger.
Applications• For indoor use on flat surfaces, clevis or other band-type hangers. • Pipe sizes 16” and larger in clevis hangers only.• Chilled to steam piping and dual temperature lines.• Hanger spans per MSS SP-58 Table A3.• Available for pipe 1/2” through 24”, insulation thickness 1/2” through 4”.
Materials / Construction• 100 psi Calcium silicate meeting ASTM C-533 Type I, C-585, C-795, E-84 Flame Spread/Smoke Developed: 0/0,
Thermal Conductivity = 0.41 Btu•in/(hr•ft2•°F) @ 200°F.• Adhesive complying with NFPA 90-A, ASTM E-84 Flame Spread/Smoke Developed: 10/0.• G-90 Galvanized steel shield, small check per ASTM A-653 (replaces A-527).• Vapor barrier of all service jacket meeting ASTM D-774, D-828 and E-84 Flame Spread/Smoke Developed: 5/5.• Structural insert (12" pipe and larger) minimum 450 psi calcium silicate meeting ASTM C-656 Type II Grade 5,
C-795 and E-84 Flame Spread/Smoke Developed: 0/0.• All units and components are asbestos free and 100% made and assembled in the U.S.A.
PIPE SIZE 1/2” TO 11/2” 2” TO 5” 6” TO 8” 10” TO 12” 14” TO 24”INSULATION LENGTH - in. 6 6 9 9 12
SHIELD LENGTH - in. 4 4 6 6 10SHIELD GAUGE 22 20 16 14 12
COMPRESSIVE STRENGTH - psi 100 100 100 100 / 450 100 / 450
DIMENSIONS
ALLOWABLE LOADS / RECOMMENDED SPANS
28
PIPE SIZE 1/2” 1” 11/2” 2” 3” 4” 6” 8” 10” 12” 14” 16” 18” 20” 24”
CLEVIS80 lbf7 ft.
130 lbf7 ft.
185 lbf9 ft.
230 lbf10 ft.
325 lbf10 ft.
380 lbf10 ft.
605 lbf10 ft.
800 lbf10 ft.
1160 lbf10 ft.
1400 lbf10 ft.
1800 lbf10 ft.
2600 lbf10 ft.
3300 lbf10 ft.
4000 lbf10 ft.
6175 lbf10 ft.
TRAPEZE40 lbf7 ft.
60 lbf7 ft.
85 lbf9 ft.
130 lbf10 ft.
165 lbf10 ft.
170 lbf10 ft.
330 lbf10 ft.
510 lbf10 ft.
830 lbf10 ft.
1200 lbf10 ft.
1250 lbf10 ft.
SeeMaxSpan
SeeMaxSpan
SeeMaxSpan
SeeMaxSpan
NATIONAL PIPE HANGER CORPORATION
CHILL-SHIELD
Description / Features Chill-Shields are 360° thermal hanger shields designed to meet a broad range of pipe support applications on low temperaturelines. They provide a continuous section of insulation and vapor barrier, and are designed for piping systems operating between -250°F and +225°F. The insulation and vapor barrier extend beyond the galvanized steel shield for a neat, vapor-tight joint withthe adjoining insulation. Chill-Shields are suitable for use in any type of clamp as well as in band-type hangers. High compres-sive strength polyisocyanurate inserts and heavy gauge steel shields ensure proper pipe support. These cost effective designsmeet the requirements of either pipe or tube systems.
Applications• For indoor use on clamping support systems, clevis or other band-type hangers. • Chilled piping to domestic hot water. • Hanger spans per MSS SP-58 Table A3 (not suitable for extended hanger spans).• Available for pipe 1/2” through 24”, insulation thickness 1/2” through 4”.
Materials / Construction• Polyisocyanurate meeting ASTM C-591 Type IV Grade 2 (24 psi, 2 pcf), Type V Grade 2 (80 psi, 4 pcf),
Type VI Grade 2 (130 psi, 6 pcf), C-203, C-518, C-585, C-795, D-1621, D-1622, D-1623 andE-84 Flame Spread/Smoke Developed: 25/450,Thermal Conductivity = 0.19 to 0.20 Btu•in/(hr•ft2•°F) @ 75°F.
• 375 psi Polyurethane high compressive insert, standard for 14” pipe and larger, meeting ASTM C-585 and C-795• 360° Non-reactive vapor barrier jacket meeting ASTM D-774, D-828 and E-84 Flame Spread/Smoke Developed: 5/5.• Adhesive complying with NFPA 90-A and ASTM E-84 Flame Spread/Smoke Developed: 10/0.• G-90 Galvanized steel shield, small check per ASTM A-653 (replaces A-527).• All units and components are asbestos free and 100% made and assembled in the U.S.A.
PIPE SIZE 1/2” TO 11/2” 2” TO 4” 5” TO 6” 8” 10” TO 24”INSULATION LENGTH - in. 6 6 9 9 12
SHIELD LENGTH - in. 4 4 6 6 10SHIELD GAUGE 20 18 16 16 14
COMPRESSIVE STRENGTH - psi 24 80 80 130 130 / 375
DIMENSIONS
PIPE SIZE 1/2” 1” 11/2” 2” 3” 4” 6” 8” 10” 12” 14” 16” 18” 20” 24”
CLEVIS30 lbf7 ft.
40 lbf7 ft.
65 lbf9 ft.
185 lbf10 ft.
270 lbf10 ft.
350 lbf10 ft.
600 lbf10 ft.
900 lbf10 ft.
1110 lbf10 ft.
1400 lbf10 ft.
1500 lbf10 ft.
1800 lbf10 ft.
2200 lbf10 ft.
2700 lbf10 ft.
3500 lbf10 ft.
TRAPEZE20 lbf7 ft.
25 lbf7 ft.
45 lbf9 ft.
100 lbf10 ft.
150 lbf10 ft.
180 lbf10 ft.
350 lbf10 ft.
580 lbf10 ft.
850 lbf10 ft.
1050 lbf10 ft.
CallFactory
CallFactory
CallFactory
CallFactory
CallFactory
ALLOWABLE LOADS / RECOMMENDED SPANS
29
NATIONAL PIPE HANGER CORPORATION
MAXSPAN
Description / FeaturesMaxSpan thermal hanger shield is specifically designed to provide a superior safety margin when supporting pipe with hangerspans up to the maximum allowed in Table 4 of MSS SP-58 in clevis or clamp hangers. These 360° thermal hanger shields pro-vide a continuous section of insulation and vapor barrier through the hanger and can be used on piping systems operating be-tween +20°F and +1200°F. The insulation and vapor barrier extend beyond the galvanized steel shield for a neat, vapor-tight joint with the adjoining insulation. To achieve the protection required by long hanger spans, the MaxSpan thermal hanger shieldsutilize heavier gauge shields, and 900 psi structural inserts (10” pipe and larger). The MaxSpan meets or exceeds the MSS standard for Type 40 shields per MSS SP 58, Paragraph 7.6.
Applications• For indoor use on all band and clamping hanger systems (see WeatherShield Upgrade submittal for outdoor
applications).• Chilled to steam piping and dual temperature lines.• Hanger spans per MSS SP-58 Table 4 in clevis or two-bolt clamp hangers.• Available for pipe 4” through 24”, insulation thickness 1/2” through 4”.
Materials / Construction• 100 psi Calcium silicate meeting ASTM C-533 Type I, C-585, C-795, E-84 Flame Spread/Smoke Developed: 0/0,
Thermal Conductivity = 0.41 Btu•in/(hr•ft2•°F) @ 200°F.• Adhesive complying to NFPA 90-A and ASTM E-84 Flame Spread/Smoke Developed: 10/0.• G-90 Galvanized steel shield, small check per ASTM A-653 (replaces A-527).• Vapor barrier of all service jacket meeting ASTM D-774, D-828 and E-84, Flame Spread/Smoke Developed: 5/5.• Structural insert (10” pipe and larger) of 900 psi calcium silicate per ASTM C-656 Type II Grade 6.• All units and components are asbestos free and 100% made and assembled in the U.S.A.
PIPE SIZE 1/2” TO 11/2” 2” TO 3” 4” TO 8” 10” TO 12” 14” TO 24”INSULATION LENGTH - in. See Pro-Shield 9 9 12 14
SHIELD LENGTH - in. See Pro-Shield 6 6 9 12SHIELD GAUGE See Pro-Shield 16 14 14 12
COMPRESSIVE STRENGTH - psi See Pro-Shield 100 100 100 / 900 100 / 900
DIMENSIONS
PIPE SIZE 1/2” 1” 11/2” 2” 3” 4” 6” 8” 10” 12” 14” 16” 18” 20” 24”
CLEVIS80 lbf7 ft.
130 lbf7 ft.
185 lbf9 ft.
275 lbf10 ft.
375 lbf12 ft.
405 lbf14 ft.
1015 lbf17 ft.
1555 lbf19 ft.
2450 lbf22 ft.
3480 lbf23 ft.
4770 lbf25 ft.
8050 lbf27 ft.
9025 lbf28 ft.
9550 lbf30 ft.
15500 lbf32 ft.
TWOBOLT
40 lbf7 ft.
60 lbf7 ft.
85 lbf9 ft.
300 lbf10 ft.
375 lbf12 ft.
405 lbf14 ft.
1070 lbf17 ft.
1625 lbf19 ft.
2575 lbf22 ft.
3550 lbf23 ft.
4820 lbf25 ft.
8250 lbf27 ft.
9505 lbf28 ft.
10550 lbf30 ft.
17350 lbf32 ft.
ALLOWABLE LOADS / RECOMMENDED SPANS
30
NATIONAL PIPE HANGER CORPORATION
MAXSPAN R.H.
Description / FeaturesThe MaxSpan R.H. thermal hanger shield is specifically designed to provide a superior safety margin for pipe mounted on piperollers, flat surfaces or with supports where point loading may be a concern. These rugged units allow hanger spans up to themaximum allowed in Table 4 of MSS SP-58. They are appropriate for either hot or cold piping systems. The insulation andvapor barrier extend beyond the galvanized steel shield for a neat, vapor-tight joint with the adjoining insulation. Units for pipe4” and larger include a wear/weight distribution plate of carbon steel (primer painted). Additionally, a segment of ultra high density, 900 psi calcium silicate is fabricated into units for 10” pipe size and larger. The MaxSpan R.H. meets or exceeds theMSS standard for Type 40 shields per MSS SP 58, Paragraph 7.6.
Applications• For indoor use on all roller hanger systems and flat surfaces (see WeatherShield Upgrade submittal for outdoor
applications).• Chilled to steam piping and dual temperature lines.• Hanger spans per MSS SP-58 Table 4.• Available for pipes 1/2” through 24”, insulation thickness 1/2” through 4”.
Materials / Construction• 100 psi Calcium silicate meeting ASTM C-533 Type 1, C-585, C-795, E-84 Flame Spread/Smoke Developed: 0/0.• Adhesive complying with NFPA 90-A and ASTM E-84, Flame Spread/Smoke Developed: 10/0,
Thermal Conductivity = 0.41 Btu•in/(hr•ft2•°F) @ 200°F.• G-90 Galvanized steel shield, small check per ASTM A-623 (replaces A-527).• Wear/weight distribution plate - carbon steel meeting ASTM A-36.• Vapor barrier of all service jacket meeting ASTM D-774, D-828 and E-84.• Structural insert (10” pipe and larger) of 900 psi calcium silicate per ASTM C-656 Type II Grade 6.• All units and components are asbestos free and 100% made and assembled in the U.S.A.
PIPE SIZE 1/2” TO 11/2” 2” TO 3” 4” TO 8” 10” TO 12” 14” TO 24”INSULATION LENGTH - in. See Pro-Shield 9 9 12 14
SHIELD LENGTH - in. See Pro-Shield 6 6 9 12SHIELD GAUGE See Pro-Shield 16 14 14 12
PLATE THK. x LENGTH - in. x in. N/A N/A 1/8 x 6 1/4 x 6 1/4 x 10COMPRESSIVE STRENGTH - psi See Pro-Shield 100 100 100 / 900 100 / 900
DIMENSIONS
ALLOWABLE LOADS / RECOMMENDED SPANS
31
PIPE SIZE 1/2” 1” 11/2” 2” 3” 4” 6” 8” 10” 12” 14” 16” 18” 20” 24”
ROLLER80 lbf7 ft.
130 lbf7 ft.
185 lbf9 ft.
275 lbf10 ft.
375 lbf12 ft.
405 lbf14 ft.
1015 lbf17 ft.
1555 lbf19 ft.
2450 lbf22 ft.
3480 lbf23 ft.
4770 lbf25 ft.
8050 lbf27 ft.
9025 lbf28 ft.
9550 lbf30 ft.
15500 lbf32 ft.
TRAPEZE40 lbf7 ft.
60 lbf7 ft.
85 lbf9 ft.
300 lbf10 ft.
375 lbf12 ft.
405 lbf14 ft.
1070 lbf17 ft.
1625 lbf19 ft.
2575 lbf22 ft.
3550 lbf23 ft.
4820 lbf25 ft.
8250 lbf27 ft.
9505 lbf28 ft.
10550 lbf30 ft.
17350 lbf32 ft.
NATIONAL PIPE HANGER CORPORATION
Description / FeaturesWeatherShield modifications are appropriate for hostile environment or outdoor applications. The calcium silicate insulation istreated with a water-resistant compound to provide additional protection from moisture. The WeatherShield is constructed withthe specified jacketing material laminated between the steel protection shield and the all service vapor barrier jacket. WeatherShield modifications may be specified for all Pre-Insulated Pipe Supports and Pro-Shield, Pro-Shield N.T., MaxSpanand MaxSpan R.H. Thermal Shields. WeatherShields must be installed as 360° units to maintain their integrity and weather resistance.
Construction / Installation ProcedureThe bottom shield's weather barrier covers approximately 240° of the unit's circumference. The top weather barrier is providedas a separate piece from the top half of insulation. Once the top insulation piece is installed, this top weather barrier overlapsthe bottom weather barrier to act as a watershed, and is then attached with two strips of self-sealing tape, sealing it to the lower half of the unit. If a top metal shield is required, it can be slid into place completing the unit. Insulation and jacketing extend beyond the steel protection shield for a neat, weather-tight connection with the adjoining insulation.
Standard weather barrier layer is Ventureclad aluminum jacketing, either smooth or stucco embossed.
We can also provide :• PVC Jacketing - 0.020” or 0.030” thickness. Colors to match adjoining system requirements.• Aluminum Jacketing - 0.016” or 0.020” thickness. Smooth or stucco embossed.• Stainless Steel Jacketing - 0.010” or 0.015” thickness. Smooth or stucco embossed.
32
WEATHERSHIELD UPGRADEProtection System for Outdoor Applications
Upgrade to Pro-Shield Illustrated
NATIONAL PIPE HANGER CORPORATION
2” PIPE SIZE - 2.375” O.D.SCHEDULE NO. 40 80 160
WALL DESIGNATION STD. XS XXSTHICKNESS - in. 0.154 0.218 0.343 0.436
PIPE - lbf./ft. 3.65 5.02 7.44 9.03WATER - lbf./ft. 1.46 1.28 0.97 0.77
21/2” PIPE SIZE - 2.875” O.D.40 80 160
STD. XS XXS0.203 0.276 0.375 0.5525.79 7.66 10.01 13.702.08 1.84 1.54 1.07
3” PIPE SIZE - 3.5” O.D.SCHEDULE NO. 40 80 160
WALL DESIGNATION STD. XS XXSTHICKNESS - in. 0.216 0.300 0.438 0.600
PIPE - lbf./ft. 7.58 10.25 14.32 18.58WATER - lbf./ft. 3.20 2.86 2.35 1.80
4” PIPE SIZE - 4.5” O.D.40 80 160
STD. XS XXS0.237 0.337 0.531 0.67410.79 14.98 22.51 27.545.51 4.98 4.02 3.38
5” PIPE SIZE - 5.5625” O.D.SCHEDULE NO. 40 80 160
WALL DESIGNATION STD. XS XXSTHICKNESS - in. 0.258 0.375 0.625 0.750
PIPE - lbf./ft. 14.62 20.78 32.96 38.55WATER - lbf./ft. 8.66 7.89 6.33 5.62
6” PIPE SIZE - 6.625” O.D.40 80 160
STD. XS XXS0.280 0.432 0.718 0.86418.97 28.57 45.3 53.212.51 11.29 9.2 8.2
8” PIPE SIZE - 8.625” O.D.SCHEDULE NO. 20 40 80 160
WALL DESIGNATION STD. XS XXSTHICKNESS - in. 0.250 0.322 0.500 0.875 0.906
PIPE - lbf./ft. 22.36 28.55 43.4 72.4 74.7WATER - lbf./ft. 22.48 21.69 19.8 16.1 15.8
10” PIPE SIZE - 10.75” O.D.20 40 60 80 160
STD. XS0.250 0.365 0.500 0.593 1.12528.04 40.5 54.7 64.3 115.735.77 34.1 32.3 31.1 24.6
12” PIPE SIZE - 12.75” O.D.SCHEDULE NO. 20 40 80 160
WALL DESIGNATION STD. XSTHICKNESS - in. 0.250 0.375 0.406 0.500 0.687 1.312
PIPE - lbf./ft. 33.38 49.6 53.5 65.4 88.5 160.3WATER - lbf./ft. 51.10 49.0 48.5 47.0 44.0 34.9
14” PIPE SIZE - 14” O.D.10 30 40 80 160
STD. XS0.250 0.375 0.438 0.500 0.750 1.40636.71 54.6 63.4 72.1 106.1 189.162.06 59.7 58.7 57.5 53.2 42.6
PIPE CHART
33
16” PIPE SIZE - 16” O.D.SCHEDULE NO. 10 30 40 80 160
WALL DESIGNATION STD. XSTHICKNESS - in. 0.250 0.375 0.500 0.843 1.593
PIPE - lbf./ft. 42.1 62.6 82.8 136.5 245.1WATER - lbf./ft. 81.8 79.1 76.5 69.7 55.9
18” PIPE SIZE - 18” O.D.10 40 80 160
STD. XS0.250 0.375 0.500 0.562 0.937 1.78147.4 70.6 93.5 104.8 170.8 308.5
104.3 101.2 98.4 97.0 88.5 71.0
20” PIPE SIZE - 20” O.D.SCHEDULE NO. 10 20 30 40 80 160
WALL DESIGNATION STD. XSTHICKNESS - in. 0.250 0.375 0.500 0.593 1.031 1.968
PIPE - lbf./ft. 52.7 78.6 104.1 122.9 208.9 379.0WATER - lbf./ft. 129.5 126.0 122.8 120.4 109.4 87.9
24” PIPE SIZE - 24” O.D.10 20 40 80 160
STD. XS0.250 0.375 0.500 0.687 1.218 2.34363.4 94.6 125.5 171.2 296.4 541.9
188.0 183.8 180.1 174.3 158.3 127.0
30” PIPE SIZE - 30” O.D.SCHEDULE NO. 10 20
WALL DESIGNATION STD. XSTHICKNESS - in. 0.312 0.375 0.500
PIPE - lbf./ft. 98.9 118.7 157.6WATER - lbf./ft. 293.5 291.0 286.0
36” PIPE SIZE - 36” O.D.10 20 40
STD. XS0.312 0.375 0.500 0.750119.1 142.7 189.6 282.4425.9 422.6 416.6 405.1
42” PIPE SIZE - 42” O.D.SCHEDULE NO. 20
WALL DESIGNATION STD. XSTHICKNESS - in. 0.375 0.500
PIPE - lbf./ft. 166.7 221.6WATER - lbf./ft. 578.7 571.7
PIPE CHART
34
INSULATION TYPETHERMAL CONDUCTIVITY, Btu•in/(hr•ft2•°F)
MATERIAL PROPERTIES 75°F 200°F 400°F 600°F 800°F
ASTM C-656 TYPE I Calcium Silicate 100 psi, 14.5 pcf 0.41 0.49 0.60
ASTM C-656 TYPE II GRADE 5 Calcium Silicate 450 psi, 18 pcf 0.54 0.61 0.67 0.73
ASTM C-656 TYPE II GRADE 6 Calcium Silicate 900 psi, 28 pcf 0.61 0.66 0.73 0.80
ASTM C-591 TYPE IV GRADE 2 Polyisocyanurate 24 psi, 2 pcf 0.19
ASTM C-591 TYPE V GRADE 2 Polyisocyanurate 80 psi, 4 pcf 0.19
ASTM C-591 TYPE VI GRADE 2 Polyisocyanurate 130 psi, 6 pcf 0.20
INSULATION MATERIAL THERMAL CONDUCTIVITY
MAXIMUM HORIZONTAL PIPE HANGERAND SUPPORT SPACING
NOMINAL PIPE SIZE 2” 21/2” 3” 4” 5” 6” 8” 10” 12” 14” 16” 18” 20” 24” 30” 36” 42”WATER SERVICE - ft. 10 11 12 14 16 17 19 22 23 25 27 28 30 32 33 35 37VAPOR SERVICE - ft. 13 14 15 17 19 21 24 26 30 32 35 37 39 42 44 47 51
SHEET METAL THICKNESS
SHEET GAUGE - ga. 22 20 18 16 14 12THICKNESS - in. 0.0336 0.0396 0.0516 0.0635 0.0785 0.1084
Sheet metal thickness based on galvanized steel.
INSULATION OUTSIDE DIAMETER
NOMINALPIPE SIZE
NOMINAL INSULATION THICKNESS
INS. THK. = 1” INS. THK. = 11/2” INS. THK. = 2” INS. THK. = 21/2” INS. THK. = 3” INS. THK. = 4”
2” 4 5.5625 6.625 7.625 8.625 10.7521/2” 5 6.625 7.625 8.625 9.625 11.753” 5.5625 6.625 7.625 8.625 9.625 11.754” 6.625 7.625 8.625 9.625 10.75 12.755” 7.625 8.625 9.625 10.75 11.75 146” 8.625 9.625 10.75 11.75 12.75 158” 10.75 11.75 12.75 14 15 17
10” 12.75 14 15 16 17 1912” 15 16 17 18 19 2114” 16 17 18 19 20 2216” 18 19 20 21 22 2418” 20 21 22 23 24 2620” 22 23 24 25 26 2824” 26 27 28 29 30 3230” 32 33 34 35 36 3836” 38 39 40 41 42 4442” 44 45 46 47 48 50
NOMINALPIPE SIZE
NOMINAL INSULATION THICKNESS
INS. THK. = 1” INS. THK. = 11/2” INS. THK. = 2” INS. THK. = 21/2” INS. THK. = 3” INS. THK. = 4”
2” 4 4 4 4 6 621/2” 4 4 4 4 6 63” 4 4 4 4 6 64” 4 4 4 4 6 65” 4 4 4 4 6 66” 4 4 4 4 6 68” 4 4 4 6 6 6
10” 4 4 4 6 6 612” 4 4 4 6 6 614” 4 4 4 6 6 616” 4 4 6 6 6 818” 4 4 6 6 6 820” 4 4 6 6 6 824” 4 4 6 6 6 830” 4 6 6 6 6 836” 4 6 6 6 6 842” 4 6 6 6 6 8
BOTTOM-of-PIPE (B.O.P.) to TOP-of-STEEL (T.O.S.)
For models NS10, NS20, NS50, NS60, NG30, NG40, NG70, NG80 and NA40.
35
AGREEMENTS: All agreements are subject to strikes, accidents or other causes beyond our control. Prices anddesigns are subject to change without notice.
TAXES: The buyer is liable for any Federal or State taxes, imposed on the seller.
WARRANTY: We guarantee for one year from date of shipment our manufactured products to the extent that wewill replace those having manufacturing defects when used for the purpose which we recommended. If goodsare defective, the amount of damage is the price of the defective goods only and no allowance will be made forlabor or expense of repairing defective goods or damage resulting from the same. We warrant the products wesell of other manufacturers to the extent of the warranties of their respective maker.
RETURNS: Permission to return standard stocked merchandise must be obtained in writing. Credit will be issuedsubject to the following:
1. Return freight charges must be prepaid.
2. All material must be in first-class condition and in box quantities on arrival at our plant; if not, reconditioning costs will be deducted from the credit memo.
3. Credit will be allowed on the basis of the price charges less a minimum handling charge of 20% and less any out-bound freight allowed or paid by us.
4. All Special, non-stocked and redesigned merchandise is Non-Returnable.
TERMS AND DESIGN: Subject to change without notice, refer to current price list for terms of sale.
CLAIMS: No claims for shortages allowed unless made in writing within ten (10) days of receipt of goods. Allmaterial sent out will be carefully counted and packed. Claims for goods damaged or lost in transit should bemade to the carrier as our responsibility ceases on delivery to the carrier.