Distribution Automation Project – BPL Network Design
© Copyright IBM Corporation 2006
BPL Introduction
CNP is installing a Broadband over Power Line (BPL) communications infrastructure to facilitate distribution system automation. The BPL equipment injects/receives a high frequency (3-30 Mhz) data signal into/from one phase of an existing distribution ckt. There is an injector unit at or near the substation that is connected to a high speed data communication path fiber/ethernet). Then there are repeaters installed along the circuit to amplify and re-broadcast the signal. The BPL equipment will be connected to utility devices to provide a communication path.
| January 17, 2006 | 2
Distribution Automation Project – BPL Network Design
© Copyright IBM Corporation 2006
BPL Introduction
For 2006, 41 12kV ckts are scheduled to have BPL equipment installed.
IBM has been hired as the BPL system integrator, and they will be doing the BPL design. The design consists of determining how many devices will be required per ckt and approximately where the devices should be located.
Distribution Automation Project
© Copyright IBM Corporation 2006
BPL Network DesignBellaire BI01 Circuit
March 12th, 2006
V1.9
| January 17, 2006 | 4
Distribution Automation Project – BPL Network Design
© Copyright IBM Corporation 2006
Table of Contents
Overall circuit map
GIS map of individual installation point
Injection Point + Sensor (comfort stn) design
BPL + CCU design
RF design
Logical network design
Network address design
| January 17, 2006 | 5
Distribution Automation Project – BPL Network Design
© Copyright IBM Corporation 2006
The BI01 circuit will have two BPL nodes at the pole locations shown below.
Node #1
TP-Bi01
Node #2
Node Type Notes
Node #1 BPL Injection + comfort stn
HE point
Node #2 BPL + CCU
| January 17, 2006 | 6
Distribution Automation Project – BPL Network Design
© Copyright IBM Corporation 2006
Node #1 is the BPL injection point + sensor station for BI01, it is the first pole past the Terminal Pole of BI01.
| January 17, 2006 | 7
Distribution Automation Project – BPL Network Design
© Copyright IBM Corporation 2006
Node #2 is a BPL + CCU installation point
| January 17, 2006 | 8
Distribution Automation Project – BPL Network Design
© Copyright IBM Corporation 2006
The injector node (Node #1) will be connected with multimode fiber to the backhaul network at the Bellaire substation control-house.
CNP Backhaul Network
BPL/AMM ServersCheckpoint Firewall
IBM Server Rack
Cisco 6509 Switch
Cisco 2960 SwitchFujitsu FW4100
Centerpoint ECDC
Fujitsu FW4020-1
Cisco 3750 Switch
Bellaire Substation Controlhouse
Fiber Dist. Panel
BPL MV Coupler
BPL MV Gateway
LV 120V
12 KV MV Tap
Cat5e
Fiber –MM 50/125RG-58
Ground
AC 120V
MV 12KV
C-Phase
Comfort Station
| January 17, 2006 | 9
Distribution Automation Project – BPL Network Design
© Copyright IBM Corporation 2006
Cat5e
Fiber –MM 50/125
RG-58
Ground
AC 120V
12 KV MV Tap
BPL Repeater Node With RF Meter Collector
BPL MV Coupler
BPL MV Gateway
CCU
RF Diplexer*
The second node (Node #2) will also a have an AMR Collector Unit (CCU).
C - Phase
Node #2
| January 17, 2006 | 10
Distribution Automation Project – BPL Network Design
© Copyright IBM Corporation 2006
RF Band allocation for BI01 Frequency Mode: 1 for Node #1 and Node #2 Frequency range 3MHz – 13 MHz Frequency notching will be used to notch out the amateur radio bands
Node #1 Node #2
MV Coupler MV CouplerMode 1 Filter
“next” port
“Previous” port
12 KV line, C-Phase
| January 17, 2006 | 11
Distribution Automation Project – BPL Network Design
© Copyright IBM Corporation 2006
BI01 network logical diagram
| January 17, 2006 | 12
Distribution Automation Project – BPL Network Design
© Copyright IBM Corporation 2006
This table shows the BPL IP addressing for BI01.
Site Type Network Addr Address Range Subnet Mask Assigned To
Bellaire 10.144.0.0 10.144.0.1 - 10.144.31.254 255.255.240.0 -or- /19 Bellaire Substation
Bellaire Circuits Address Range Mask Assigned to
Bi01 10.144.0.X /24 10.144.0.1 - 10.144.0.254 255.255.255.0 VLAN Bi01
AMM Collectors Meter collectors 10.144.0.10 - 10.144.0.29 255.255.255.0
Sensors Sensors 10.144.0.30 - 10.144.0.59 255.255.255.0
BPL Gateways BPL devices 10.144.0.60 - 10.144.0.99 255.255.255.0
Reserved 10.144.0.100 - 10.144.0.254 255.255.255.0
| January 17, 2006 | 13
Distribution Automation Project – BPL Network Design
© Copyright IBM Corporation 2006
| January 17, 2006 | 14
Distribution Automation Project – BPL Network Design
© Copyright IBM Corporation 2006
| January 17, 2006 | 15
Distribution Automation Project – BPL Network Design
© Copyright IBM Corporation 2006
| January 17, 2006 | 16
Distribution Automation Project – BPL Network Design
© Copyright IBM Corporation 2006
BPL Pictures
Top Related