7/24/2019 Automated Parameter Optimization of a Water Distribution
1/16
71
IWA Publishing 2013
Journai of iHydroinformatics | 1 5 1 | 2013
Automated parameter optimization of
water distribution
system
Maikel Mndez, Jos A . Araya and Luis D. Snchez
ABSTRACT
The hydraulic model EPANET was applied and calibrated for the water distribution system (WDS) of La
Sirena, Colombia. The Parameter ESTimator (PEST) was used for parameter optimization and
sensitivity analysis. Observation data included levels at water storage tanks and pressures at
monitoring nodes. Adjustable parameters were grouped into different classes according to two
different scenarios identified as constrained and unconstrained. These scenarios were established to
evaluate the effect of parameter space size and compensating errors over the calibration process.
Results from the unconstrained scenario, where 723 adjustable parameters were declared, showed
that considerable compen sating errors are introduced into the optimization process if all parameters
wer e open to ad justment. The constrained scenario on the other h and, represented a more properly
discretized scheme as parameters were grouped into classes of similar characteristics and
Insensitive parameters w ere fixed . This had a profound impact on th e param eter space as adjustable
parameters we re reduced to 24. The constrained solution, even whe n it is valid only for the system s
normal operating conditions, clearly demonstrates that Parallel PEST (PPEST) has the potential to be
used in the calibration of WDS models. Nevertheless, further investigation is needed to determine
PPEST s perfo rman ce in complex WDS models.
Key words
| calibration, EPANET, model, optimization, parameter, sensitivity
iVlaikel Mndez
(corresponding author)
Jos A Araya
Centro de Investigaciones en Vivienda y
construccin (CIVCO), Escuela de ingeniera en
Construccin,
Instituto Tecnolgico de Costa Rica,
APDO 159-7050,
Cartago,
Costa Rica
E-mail:
mamendez@itcr ac cr
Luis D S nciiez
Instituto Cinara,
universidad del Valle - Facultad de Ingeniera,
Cali,
Colombia
INTRODUCTION
W ater distribution system (WDS) models canbeused foravar-
iety of purposes including design, managem ent, m aintenance,
planning and scenario studies. Nevertheless, in order to be
reliable
a model must adequately predict the behavior of the
actual system under a wide range of conditions and for an
extended period of time (Machell
et al
2010). This can b e
accom plished by calibrating th e m odel using a set of field
measurements or observations, mainly water storage tanit
(WST) levels, nodal pressures and flow rates. The calibration
ofa W Smodeliscarried out by optimizingthevalues of
phys-
ical and conceptual parameters involved in the model,
including pipe roughness-coefficients, minor losses, demand
pattern factors, nodal demands, control valves and pump
characteristics (USEPA2005; Koppel Vassiljevaoog).
Calibration is also referred to as an inverse problem,
since observed values are quantitatively compared to
doi: 10.2166/hydro.2012.028
model predictions until the optimum set of parameters is
found (Gallagher Doh erty 2007). A mo del is considered
to be calibrated for one set of operating conditions if it
can predict outcomes
with
reasonable agreement. Neverthe-
less, this does not necessarily imply calibration in general.
Models should be calibrated over a wide range of operating
conditions so that the modeler can rely on model predic-
tions (Walski 1986). As models are only approximations of
the actual systems
that are
being represen ted, the reliability
of model predictions depends on how weU the model struc-
ture is deflned and how well the model is parameterized
(Hogue et al 2006).
A critical step in m odel calibration relates to the quality
and density of observation data which may contain
significant measurement errors. Even small measurement
errors can lead to large errors in estimated parameters
7/24/2019 Automated Parameter Optimization of a Water Distribution
2/16
72 M Mndez eta l Automated parameter optimization of a water distr ibution system
Journal of Hydroinformatics | 15 1 { 2013
(Goegebeur Pauwels 2007). As observation data accuracy
migbt be in tbe same order of magnitude of tbe measure-
ment errors, including this kind of data in tbe calibration
process will most likely produce misleading results. Only
accurate observation data sbould be used for calibration.
Walski
et al
(2004) suggest tbat very high quality field
data (e.g. pressure and elevation data) would be accurate
to 0.1 m. Good quality field data are considered accurate
to m. Model predictions would significantly deteriorate
wb en field data are accurate to 3 m, whicb reflects po orly
collected data. On the other hand, sufficient observation
data may be infrequent an d only collected at select locations
(Kang Lansey 2009). Tbis is particularly true in develop-
ing countries wbere severe limitations constrain the scope
and success of public sector projects, particularly water
supply and water quality (Lee Scbwab 2005).
Calibration by param eter optim ization is a bigbly under-
determined problem as the number of unlaiowns is greater
than the number of observations (Walski
et al
2006). In a
real system, tbere can be hundreds of unlmowns and only
a relatively small number of observations. As tbe number
of unknowns greatly exceeds the number of observations,
tbere is little confidence in the model predictions. Tbere
can be too many solutions tbat yield equally good results
in terms of a predefined objective function witbin the
model's parameter space (Duan
et al
1992). Tbis situation
has resulted in tbe development of tbe concept of 'equifinal-
ity' which recognizes that alternative sets of control
parameters within a model are capable of producing reason-
able estimates of the system response as measured by
objective functions defining tbe goodness of fit (Beven
Binley 1992; Fang Ball 2007). Tbis ambiguity bas serious
impacts on parameter and predictive uncertainty and conse-
quently limits tbe applicability of a model. To reduce tbe
number of unlcnowns and improve reliability on model pre-
dictions, the parameter space must be constrained (Walski
et al 2004).
An obvious constraint for any model would be grouping
param eters into classes of similar cbaracteristics (e.g. groups
of same internal diameter, m aterial, demand sector, etc.). If
all parameters witbin a model are open to adjustment,
mo delers m igbt end u p d oing wb at Walsld (1986) calls 'Cali-
bration by compensating errors'. An error in tbe estimated
roughness can be compensated for by an error in demand.
Compensating errors can take over tbe calibration process
and produce numerically correct, but pbysically meaning-
less, solutions. Under these circumstances, a model would
be matcbing observations rather than determining the sys-
tem's optimal parameters. On the other hand, only those
parameters sensitive to field observations sbould be
included in the calibration p rocess. If insensitive para meters
are included, the parameter space would increase and
model predictions will have littie chance of improving tbe
goo dne ss of fit (Zagblou l Abu Iefa 2001).
Model calibration b as traditionally been a trial-and-error
process. In tbis approach, values of selected parameters are
individually adjusted in a systematic manner until corre-
lation between observed and modeled values no longer
improves. Calibration by trial-and-error is a time-consuming
and difficult task, as tbe large number of potential
unlinowns makes it impossible to analytically solve all cali-
bration parameters (Walski et al 2006). Wben a trial-and-
error optimization approacb is followed, tbe goodness of
fit of tbe optimized model is essentially based on tbe mode-
ler's judgmen ts and experience (Ibrabim Liong 1992; Kbu
et al
2006). Since the judgment involved is subjective, it is
difficult to explicitiy assess tbe confidence of tbe model pre-
dictions (Kumar et al 2009). As deviations between
observed and modeled values migbt be outside tbe accepta-
ble tolerance range, a mucb more 'tuned' optimization may
be required. In tbis case an automated optimization
approacb may be used.
In an automated optimization app roacb, parameters are
adjusted automatically according to a specified search
scheme and quantitative numerical measures of tbe good-
ness of fit (Skahill Dob erty 2006). Tbe development of
automated optimization procedures bas mainly focused on
using a series of objective functions to evaluate the goodness
of fit of the o ptimized m odel. Algorithms try to minim ize tbe
deviations between the observed and modeled values in
order to find the global minimum of tbe selected objective
function (Savic
et al
2009). Nevertbeless, as calibration is
a bighly underdetermined problem, it is impossible to
know whether any automated or manual calibration
approach is actually correct. This situation migbt worsen if
an automated calibration approach is followed, as cali-
bration algorithms might contain little knowledge of the
physical laws that govern a model's structure.
7/24/2019 Automated Parameter Optimization of a Water Distribution
3/16
73 M Mndez e al Automated parameter optimization of a water distr ibution system
Journai of Hydroinforma tics | 15 1 | 2013
Several automated techniques have been used to cali-
brate WDS models including genefic algorithms (Jamasb
et
al
2oo8; Nicklow et
al
2009; Kovalenkoe t
al
2010), B aye-
sian-type procedures (Kapelan et al 2007) and Markov
Chain Monte Carlo simulations (Peng
et al
2009). V arious
calibration tools have been incorporated into commercially
available software packages including WaterGEMS's
Darwin-Calibrator (Wu
et al
2002; Walski
et al
2006),
H2ONET Calibrator (Wu et al 2000) and InfoWafer Cali-
brator (de Schaetzen et al 2010). Although these
applications are robust and well proven, little attention has
been paid to end-user applications and product development
(Abe & C heung 2010). This is particularly true in the context
of free and open source software applicafions. Water ufilifies
in developing countries might not have access to commer-
cial packages due to budget restricfions. Still the use and
proper calibrafion of WDS models is a necessity.
The parameter estimator package PEST; an acronym for
Parameter ESTimation (Doherty 2005) might eventually be
used to calibrate a WDS model such as EPANET (Rossman
2000).
PEST offers several strategic advantages to m odelers.
Firstly, PEST is a model-independent application. This
avoids changes to the original code as it communicates
with a model through its own input and output files. Sec-
ondly, PEST has successfully been used to calibrate
numerous types of models including, groundwater models
(Doherty 2005; Christensen & Doherty 2008), hydroiogicai
models (Arabi
et al
2007; Immerzeel & Droogers
2008;
Bah-
remand & de Smedt 2010), soil layer and soil moisture
analysis (Tischler
et al
2007) and hydraulic models
(Koppel & Vassiljev 2009; Maslia
et al
2009). Thirdly,
PEST can be used to carry out various predictive and
exploratory tasks including sensitivity, correlation and
uncertainty analysis. Fourthly, PEST is freely available fo
the public and is user-oriented. As modeling of WDSs is
just emerging in developing regions, particularly in small
water supply systems (municipalifies and rural commu-
nifies), it would be of great importance to explore the
possibility of using available free and open source software
applications in this context. This would gradually promote
a 'modeling culture' which may generate demand for more
comprehensive, commercially available tools.
The aim of this study is to determine if model indepen-
dent parameter estimator PEST can be used to develop a
fully calibrated extended-period model for a WDS using
the public domain model EPANET.
METHODOLOGY
La Sirena's WDS was used as a case study to examine the
advantages of using a fully automated optimization
approach versus a trial-and-error opfimization. La Sirena is
a rural community located in the department of Valle del
Cauca, Municipality of Cali, Colombia (Figure 1).
The system is served by a single mulfi-stage filtrafion
(MSF) water treatment plant which produces approximately
0.012 m'' s ^ and consists of small diameter PVC pipes, ran-
ging from 20 to 85 mm (Table 1). The system contains four
ground WSTs that create four different pressure zones
(Figure 1). Each WST is equipped with a Float Actuated
Valve (FAV) that co ntrols flow admission an d p revents over-
flow. Isolation valves prevent flows among pressure zones.
A comp lete topographic survey of the system was performed
using a total station which allowed elevation data to be accu-
rate to 0.02 m.
Since the system co nsists mainly of small diameter pipes
and minor losses could have a significant impact, the
number of fitfings for each individual pipe was carefully
identified. The types of fittings included tees, elbows,
bends, contracfions, expansions and fully open isolafion
valves. Mino r loss coefficients (K) we re assigned to thes e fit-
tings based on typical values found in the literature (Mays
2000
Observation data for the calibration process included
water levels in the four storage tardes and nodal pressures
in seven nodes (Figure 1). A period of 7 consecutive days
(168 hr) was used for observafions recording. Observafions
were taken during normal operafing conditions and there-
fore,
considered highly representative. Pressure gauges
used to record nodal pressures were accurate to
m while
pressure sensors at WSTs were accurate to 0.1 m. The fime
interval of water level and nodal pressure observafions
was 60 min, sparsely distributed through out the enfire
recording period. In most cases, these observations rep-
resent discrete values recorded at the top of the hour. As
recommended by Walski
et al
(2001), when possible, nodal
pressure observafions were performed at maximum head
7/24/2019 Automated Parameter Optimization of a Water Distribution
4/16
74 M. Mndez eta i Automated parameter optimization of a water distribution system
Journal of Hydroin fortnatics | 15 1
2013
/
y il
^
>v II
\
y
Legend:
isolation Vaiv es
Monitoring Node s
A Wate r Storage
Tanks
Pressure Zone 1
i Pressure Zone 2
1 Pressure Zone 3
, I
i ; Pressure Zone 4
0 75 150 225 300
1 , 1 , 1
Scaie in Meters
Figure 1 I La Sirena s water distribution s ystem mod el.
Tabie 1 I Town of La sirena s water d istribution system characteristics
C o m p o n e n t Quanti ty
Number of nodes
Number of pipelines
Float Actuated Valves (FAVs)
Internal pipe diameter range (mm)
Total pipeline lengtb (m)
Water storage tank, elevation ( MASL)
and capacity (m'^)
Tank 1
Tank 2
Tank 3
Tank 4
325
27 9
5
20-85
9,554
1 178;56
1,113; 79
1 112;200
1 097;54
Meters above sea level.
loss,
which also corresponded to the system's highest water
demand.
At the time the field data were collected, there was a
total of 851 consumers registered in the Water Utility
records. Each consumer was supplied with a flow meter
which was read once a month. This information was used
to estimate and allocate water demand per consumer.
A period of 12 months between 2009 and 2010 was ana-
lyzed for this purpose. Nearly 96% of water demand was
classified as residential. The remaining 4% was classified
as commercial and/or industrial. A point-based method
was used for nodal demand allocation. This required a
detailed field survey to determine the precise number of
households that were connected to the WDS.
As actual
flow
meter locations were k now n, a spatial func-
tion was used to assign each meter to the closest demand node
(Cabreraet l 1996). To include u nacc oun ted for water, field
measurements of production and metered consumption were
recorded and compared during a period of 24 hr and then
added proportionally to nodal demands. Estimations of leak-
age for each pressure zone were prepared from night flow
and water level measurements. Nevertheless, severe inconsis-
tencies regarding consum ption records an d tmaccounted-for-
water estimations were detected. Therefore, nodal demand
exhibits the highest input data uncertainty for this case study.
This situation has been identified in the literature
(Lansey & Basnet 1991; Kenw ard & H ow ard 1999; Zho u
et l
2000) and solutions such as on-line implementation
of Supervisory Control and Data Acquisition (SCADA) sys-
tems have been suggested to improve knowledge of water
7/24/2019 Automated Parameter Optimization of a Water Distribution
5/16
75 M Mndez et
a l \
Automated parameter optimization of a water distr ibution system
Journai of Hydroinformatics | 15 1 | 20 13
dem and temp oral variation (Kang Lansey 2009; Machell
et al.
2010). However, SCADA systems are beyond the
reach of most water utilities in developing countries. In
recent years, researchers have identified the necessity to
include uncertainty in the calibration of WDS models
including pipe roughness coefficients and nodal demands
(Alvisi Fran chini 2010; Giustolisi Berard i 2on ). Uncer-
tainty quantification of model parameters such as nodal
demands implies a profound knowledge of the system and
the availability of sufficiently long time series data. Again,
this might not be the case for many water utilities.
Demand patterns for each WST and their respective
pressure zones were constructed by analyzing diurnal
dynamics of water demand. These temporal variations
were measured for various consumers of each pressure
zone. The effect of the day of the week on the demand pat-
tern s wa s also analyzed . Since significant differences
between weekday and weekend consumption w ere detected,
two 24-hr diurnal demand patterns (with a temporal resol-
ution of
hr) were constructed for each pressure zone;
one known as weekday demand pattern (Monday to
Friday) and the other known as weekend demand pattern
(Saturday and Sunday). In total, eight 24-hr demand patterns
for the entire system w ere con structed. As this project faced
budget limitations, it was not possible to obtain an indepen-
dent set of data that could have been used for model
validation.
Parameter o ptimization
Calibration and sensitivity analysis of EPANET were per-
formed using PEST, a nonlinear parameter estimation and
optimization package, which offers model independent
optimization routines (Doherty 2005). PEST is based on
the Gauss-Marquardt-Levenberg algorithm (GML) which
searches for the optimum values of the model parameters
by minimizing the deviations between field measurements
(observations) and modeled values (predictions). PEST
uses the sum of the squared deviations PHI (0) as its objec-
tive function (Skahill 2009) and can be mathematically
expressed as:
(1)
where n equals the total number of observations, O, the
observed value on timestep i. Mi is the modeled value on
timestep i an d w is the relative weight attached to each
observed value.
At the beginning of each iteration timestep, the relation-
ship between model parameters and modeled output values
is evaluated for the current set of parameters. For instance,
the derivatives of all observations with respect to all adjusta-
ble parameters must be calculated. These derivatives are
stored as the elements of a Jacobian matrix used for sensi-
tivity an alysis.
During each iteration timestep, PEST varies each adjus-
table parameter incrementally from its currently estimated
value and re-runs the model. The ratio of modeled output
differences to parameter differences approximates the
derivative. For greater accuracy in derivatives' calculation,
parameter values can be both increased or decreased until
the objective function PHI is minimized. PEST determines
whether additional iterations are required by comparing
the parameter change and objective function improvement
achieved through the current and previous iterations
(Skahill Do herty 2006).
PEST also calculates a composite relative sensitivity for
each adjustable param eter wh ich me asures the sensitivity of
all observations with respect to a relative change in the
value of that specific parameter. The sensitivity of a par-
ameter describes the effect that a variation on that specific
parameter has over the whole model generated values. Sen-
sitivity is a useful indicator for assessing the degree to which
a parameter is capable of estimating the variables on the
basis of the o bservation dataset available for mo del optimiz-
ation (Doherty 2005).
PEST communicates with a model through the
model's own input and output files. For PEST to be able
to take control of the model, the model itself must be
executable from the command line. Hence, the optimiz-
ation of a model can be carried out without the
requirement for the model to undergo any changes in its
original structure.
To couple EPANET with PEST, several input files must
be prepared (Figure 2). In the case of EPANET, the model's
master input file has a suffix 'inp' (Rossman 2000). This
ASCII-file contains all the necessary information to run
EPANET from the command line using the EPANET2D.EXE
7/24/2019 Automated Parameter Optimization of a Water Distribution
6/16
76 M. Mndez et
al \
Automated parameter optimization of a water distribution system
Journal of Hydroinformatics | 15 1 | 20 13
f
Model liiput:
EPANET AS CII file
MNP)
>
f
Read m odel input and
replace input
parameters on
PPESTtemplate files
*. TPL; MN S)
Define objectives:
Model parameters +
observations series
Model:
EPANET2D.EXE
>
PPEST.exe
Programa modules
control over EPANET
Analysis *. PST)
>
>
>
f
Reads and compare
mode l simulations
againts observed
values *. INP)
Figure 2
I Coupling schematics of EPANET and PEST.
extension. After EPAN ET is run, ASCII and binary files with
the suffixes txt and grd are respectively created. For PEST,
three types of input files must be created; a template files
(with suffix tpl ) wh ich is basically a copy of the inp
input-file, a con trol file (with suffix pst ) w hich con tains
all the PEST S control an d nu meric param eters, and finally
an instruction file (with suffix ins ), which allows PEST to
properly read observations from the E PAN ET s txt
output-files. In the course of the optimization process,
PEST creates several output files which are stored for later
inspection (Doherfy 2005).
In mo st cases, the bulk of PEST s run time is consum ed
in running the model
itself
Therefore, a special version of
PEST lmown as Parallel PEST (PPEST) was used instead.
PPEST does not only have all the functionalities of PEST
but also facilitates a dramatic enhancement in the optimiz-
ation performance by allowing PEST to run in parallel.
This is particularly useful when the amount of adjustable
parameters and the model run-times are large. It also
allows modelers to take full advantage of the most recent
and powerful multi-core processors, significantly reducing
the time needed to achieve convergence.
7/24/2019 Automated Parameter Optimization of a Water Distribution
7/16
77 M Mndez et a/ Automated parameter optimization of a water distribution system
Journal of Hydroinformatics | 15 1 | 2013
Model setup
Model optimization for the La Sirena's WDS was achieved
in two steps. In the first step, a trial-and-error approach
was followed. Values of the selected p aram eters were indivi-
dually modified in a systematic manner until correlation
between observations and modeled values no longer
improved. Three groups of parameters were taken into
account for tbis step: demand pattern factors [-], nodal
demands (L/s) and (C-factors) [-].
In the second step, an automated parameter optimiz-
ation process was executed by linking EPANET with
PPEST. Two different scenarios identified as 'constrained'
and 'unconstrained' were establisbed to evaluate tbe effects
of parameter space size and compensating errors over tbe
PPEST calibration process. In botb scenarios, 12 parameter
groups were created and tbey included: demand pattern fac-
tors [-], nodal demands (L/s), local losses [-], (FAVs) [-] and
C-factors [-] (Table 2).
For tbe constrained scenario, a total of 24 adjustable
parameters were declared. Demand pattern factors were
fixed to their original values as sufficient confidence was
obtained during their derivation. Nodal demands were
aggregated into four different demand groups, one for each
pressure zone. The same demand multiplier was assigned
to each node witbin eacb demand group. Tberefore, all
nodes experienced a proportionally equal cbange in
demand witbin each specific pressure zone. Minor loss
Tab ie 2 I Set of control settings used for ppEST
coefficients (K) for fittings were not adjusted either. FAVs
loss coefficients w ere adjusted as significant differences
between manufacturer's curves and field bebavior were
detected. Tbrottle Control Valves (TCVs) were used in
EPANET to simulate FAVs. TCVs are commonly used to
simulate a partially closed valve by adjusting tbe minor
head loss coefficient of the valve (Rossman 2000). C-factors
were classified into groups of tbe same pipe diameter. No
distinction was made regarding the age of tbe pipes as tbe
entire system w as co nstructed of relatively yotmg PVC.
For tbe uncon strained scenario, a total of 723 adjustable
parameters were declared, which accounted for the 12
parameter groups mentioned above. Each parameter within
these groups w as individually adjusted by PPEST. Nevertbe-
less, a unique C-factor was used for all pipes in the system.
Observations in botb scenarios, wbicb included water
levels and no dal pressures, were group ed in five observation
groups, four for WSTs and one for monitoring nodes. Since
observations were of two different types, the objective func-
tion relative weight attached to each observation, varied
according to its relative impo rtance in tbe overall pa rame ter
estimation process. Consequently, greater weigbts were
assigned to water level observations since tbey were con-
sidered more reliable tban tbose of tbe nodal pressures.
Concerning tbe ranges for parameter adjustments, a
30%
variation for demand patterns factors was allowed
for tbe un constrain ed scenario (Table 3). As severe inconsis-
tencies regarding consumption records and unaccounted-
for-water estimations were detected, a 30% and 50%
variation in nodal demands multipliers were assigned to
item
Number of adjustable parameters
Num ber of fixed parameters
Number of tied parameters
Number
of observation groups
Num ber and type of parameter groups
Demand patterns factors
Nodal demands
Minor loss coefficients (Ks)
Float Actuated Valves (FAVs) loss
coefficients
C-factors
Scenario
Constrained
723
0
0
5
8
1
1
1
1
Unconstrained
24
192
5 7
5
8
1
1
1
1
Table 3
Ranges for param eters adjustments
Parametergroup
Demand patterns factors (%)
Nodal demands multiplier (%)
Minor loss coefficients (Ks) (-)
Float Actuated Valves (FAVs)
loss coefficients (-)
C-factors (-)
'Walski e t
al
(2001).
Mays (2000).
Ranges of parameters vaiues per
scenario
Constrained
Not applicable
30%
Not applicable
0-350
130-150='
Unconstrained
30%
50%
0-20''
0-350
130-150
7/24/2019 Automated Parameter Optimization of a Water Distribution
8/16
78 M Mndeztal Automated parameter optimization of a water distr ibution system
Journai of Hydroinformatics | 15.1 | 2013
the constrained and unconstrained scenarios, respectively.
Minor loss coefficients {K ) for pipe fittings were allowed
to vary from 0 to 20 based o n typical values found in the lit-
eratu re (Mays 2000). FAVs loss coefficients (K) were
allowed to vary from 0 to 350 based on manufacturer's
pressure drop curves and field measurements. Two fiow
tests con ducted in 69 mm PVC showed C-factor values of
130 and 134 correspondingly. For instance, a lower value
of 130 was selected for C-factors in each scenario while a
feasible upper value of 150 was obfained from the literature
(Walskiet al.2001).
Even when observations were recorded every 60 min a
hydraulic timestep of
min was used for the entire 168-hr
simulation period regardless of the optimization approach
(trial-and-error or PPEST). This is due to the fact that
many observations (mainly nodal pressures) were sparsely
and manually recorded throughout the enfire recording
period and no specific timing for field measurements was
possible.
An Intel Core 7-930, 2.80 GHz multi-core processor
with 24 GB of RAM mem ory was used to run PPEST by con-
trolling one master and eight slaves (two for each of the four
cores of the i-7 processor). PPEST was run in esfimation
mode which means that PPEST confinued with the iteration
procedure until the global minimum was found. All other
PPEST numerical parameters were assigned typical values
as noted in the PEST manual (Doherty 2005).
Efficiency of the model opfimizafion process was
assessed according to two indicators (Maslia et al. 2009):
the Pearson correlation coefficient R),
.ti OiMi) - [nM ]
U m) - (Of))] [Er=i
and the root mean square error (RMSE),
2)
2
3)
where n equals the total number of observations, O, is the
observed-value on timestep i, is the average of the
observed values, M,- is the modeled-value on timestep ian d
M is the average of the modeled values.
R
serves as an indicator of the correlation degree
between observed and modeled values. A value of 1 yields
perfect correlation whereas a value of 0 indicates that data
are uncorrelated. The RMSE provides information on the
average error between observed and modeled values.
RESULTS AN D DISCUSSION
RMSE and R for modeled values of water levels and nodal
pressures were obtained from the two opfimization
approaches: trial-and-error and PPEST. Overall, both PPEST
optimization scenarios resulted in lower RMSE and higher R
than those ob tained by trial-and-error. Nevertheless, little vari-
ation in RMSE andRbetween PPES T scenarios can be seen
(Table 4).
This is more evident for water levels in WSTs as RMSE
remains within the 0.1 m accuracy expected for pressure
sensors. In the trial-and-error approach, RMSE for water
levels remains over the 0.1 m accuracy except for WST 2
(0.06 m). Sfill, RMSE values obtained by trial-and-error are
considered acceptable if limitations in observation data
acquisition are taken into account.
WSTs 1, 3 and 4 experienced the highest RMSE
reductions, 54.8, 31.2 and 32.8%, respectively for the
PPEST constrained scenario. Very similar values (57.6,
41.4 and 36.7%) were obtained for the PPEST uncon-
strained scenario. WST 2 is the excepfion for both PPEST
scenarios since its RMSE increased rather than decreased
with respect to the trial-and-error approach.
As mentioned, PPEST attempts to globally m inimize the
objective function PHI taking into consideration the contri-
bufions of the available observation groups. Since the
relative weight of the water level observation group was
the same for all tanks, it appears that PPEST allowed for
higher deviations in WST 2 in order to compensate for
errors in the remaining WSTs and pressure monitoring
nodes. Maslia et al. (2009) obtained similar results in their
EPANET-PEST analysis of the Holcomb Boulevard WDS,
with RMSE reducfions between 26.5 and 91.4%. Their
study included four WSTs, one of which experienced an
increase in RMSE after fhe optimization with PEST.
In our case, correlation coefficients increased in both
PPEST scenarios, with WST 1 presenfing the highest R
7/24/2019 Automated Parameter Optimization of a Water Distribution
9/16
79
M
Mndez
et
a i Automated parameter optimization
of a
water distribution system
Journaiof ydroinformatics | 15 1 | 2013
Tab ie4 RMSE
and i?
modeled values
of
water levels
and
nodal pressures
for the
town
of La
Sirena s wa ter distribution system model
Optimization approach
Component
Water levelsinTank1
Water levels
in
Tank
2
Water levels
in
Tank
3
Water levelsinTank4
Nodal pressures
Triai-and-error
Objective function
RMSE (m)
0.134
0.064
0.116
0.158
4.678
R(-)
0.821
0.895
0.946
0.879
0.981
Constrained PPEST scenario
Objective function
RMSE (m)
0.061
0.068
0.080
0.106
1.852
0.965
0.917
0.982
0.940
0.998
Percentage change
R S m)
-54.781
6.438
-31.194
-32.825
-60.407
R(-)
17.548
2.429
3.733
6.979
1.732
unconstrained PPEST scenario
Objective function
RMSE (m)
0.057
0.073
0.068
0.100
1.545
0.975
0.911
0.987
0.947
0.999
Percentage change
RMSE (m)
-57.617
13.633
-41.437
-36.713
-66.976
18.707
1.796
4.252
7.777
1.776
increase,
17.6 and 18.7 for the
constrained
and
uncon-
strained scenarios, respectively.
In the
case
of
nodal
pressures, PPEST significantly reduced RMSE with respect
to
the
trial-and-error approach
as it
passed from
4.7 to
1.9 m for the
constrained scenario
and 1.5 m for the
uncon-
strained scenario.
In all
cases, RMSE
for
nodal pressures
weis higher than
the m
accuracy expected
for
pressure
gauges.
The
difference
of
roughly
0.4 m in
RMSE between
th e
two
PPEST scenarios might seem trivial,
but it
does
have profound implications
in the
optimization process.
As
the
method used
in
EPANET
to
solve
the now
conti-
nuity
and
headloss equations
is
driven
by
nodal demands
and energy losses (Rossman 2000), small measurement
errors
and
large parameter spaces
can
lead
to
large errors
in estimated parameters. This
is
clearly
the
case
of the
PPEST unconstrained scenario, where every single
par-
ameter
was
declared adjustable
in
PPEST (Table
3).
These
conditions defined
an
unmanageable parameter space
of
723 parameters, which implied
the
optimization
of
every
single nodal demand, dem and pattern
and
minor loss coeffi-
cient
in the
system.
The
conditions stated
for
this scenario
evidently forced PPESTtocalibratethemodelbycompen-
sating
for
errors
as
suggested
by
Walsld (1986). Errors
in
nodal demands were most likely compensated
by
errors
in
demand patterns, minor loss coefficients, C-factors
and
pretty much
any
other adjustable parameter.
The
problem
is aggravated
by the
fact that nodal demand
is
still
the
most uncertain
and
variable parameter
in
this case study.
The large parameter space
and
considerable compensating
errors resulted
in a 1.5 m
RMSE
for
nodal pressures,
but
also required considerable change
in the
individual nodal
demands.
After
the
PPEST optimization,
all
nodes experienced
some level
of
change
in
demand (Figure
3)
with
an
absolute
average change
of
34.2%. Several nodes were pushed
towards
the
predefined upper
and
lower demand bounds
(Table
3).
Over
40
nodes exhibited
a -50
change
i
demand
and
over
50
nodes experienced
a -f50
change
in
demand.
The
parameter space
was too big for
PPEST
t
search effectively.
Total water demand
for the
system changed only
slightly,
as it
passed from
10.58 to
10.471s ' after
th
PPEST unconstrained optimization. This represents
a per
centage change
in
total water demand
of
around
1 .
This
reaffirms once more
the
presence
of
considerable compen-
sating errors.
In
this respect, PPEST
is
most likely
producing
a
numerically correct
but
physically meaningless
solution. Furthermore, PPEST
is
possibly matching obser-
vations rather than determining
the
system's optimal
parameters
as
there
is an
excessive number
of
parameter
groups
and
insufficient observation data. Baranowski
(2007) encountered similar conditions when calibrating
nodal demands
in two
experimental EPANET networks
using PEST and Newton-Raphson algorithms. Both methods
maximized hydraulic
and
water quality standards
but
also
required significant change
in the
nodal demands. C-factors
had little chance
to
actively participate
in the
optimization
process
as one
unique parameter
was
defined
for all
pipes.
An optimized C-factor value
of 137 was
found
for al
pipes that remain close
to the
C-factor values found
fo
th e
two
fiow tests conducted
in 69 mm PVC (130 and 13
correspondingly).
At the end of the
optimization process,
the percentage change between trial-and-error
and
PPEST
optimized values
was
2.1%
for
local losses
and 8.5 fo
7/24/2019 Automated Parameter Optimization of a Water Distribution
10/16
8
M Mndez t
al
| Automated parameter optimizationofa water distribution system
JournaiofHydroinformatics | 15.1 | 2013
-50-40 -40-30 -30-20 -20-10 -10-0 0-10 10-20
Difference in nodal demand
Figure3
I
Percent change
for
nodal demand after PPEST unconstrained optimization scenario.
20-30 30-40 40-50
FAVs. These percentages could seem small compared to
those experienced by nodal demands or demand pattern fac-
tors; however,it isrelativetothe overall sensitivityofeach
adjustable parameter.
In the case
of
the PPE ST constrained scenario, only
24
adjustable parameters were declared (Table 3). The remain-
ing parameters were either fixedortiedtoother param eters.
In PEST,a tied parameter represents a parameter thatis
linkedto amaster parameter.Inthis case, only the master
parameteris optimized andthe tied parametersaresimply
varied with this parameter, maintaining a constant ratio,
through the calibration process.
This representsamuch smaller parameter space. Nodal
demands were aggregated into four different demand
groups, one
for
each pressure zo ne. Since demand pattern
and minor loss coefficients were fixed,thesolution of the
parameter space was limited tofour noda l dem ands (four
parameters), four FAV valves 12parameters) and eight
C-factors (eight parameters). In this case, the absolute
average changeofnodal demand w as 13.4 , much lower
than the 34.2 found for the unconstrained scenario.
None of thenodes w ere pushed towards the predefined
upper and lower demand bounds. This would appearto be
the resultof compensating errors from theC-factors group
(Table 5).
Table5
I
Optimized C-fac tor vaiues after PPEST constra ined optimiz ation sc enario
Pipe internal diameter mm) initial c-factor
PEST optimized C-factor
84
69
57
45
40
31
25
19
36
36
36
36
36
36
36
36
36
37
36
4
4
36
4
Nevertheless, almost all diameter groups remainedin
the lower bound
of
130. Only pipes with internal diameters
of 69 and 45 mm w ere moved to higher values (138 and 150,
respectively). Since demand patterns and minor loss coeffi-
cients were fixed, compensating errors for this scenario
are considerably lower than those of the unconstrained
scenario. For instance, this solutionis more physically cor-
rect asPPESThad a higher chance to findtheoptimum
setofparam eter v alues. Still, no validation data exist to sus-
tain this statement. Maslia et al (2009) experienced
comparable resultsintheir analysisofHolcomb Boulevard
WD S as PVC C-factor change from its original 145 proposed
7/24/2019 Automated Parameter Optimization of a Water Distribution
11/16
81 M. Mndez et
al \
Autom ated parameter optimization of a water distribution system
Journal of Hydroinformatics | 15 1 | 201 3
value to an optimized range of 147-151 optimized values.
This is more likely to be a consequence of the inherent
smoothness of plastic materials and low relative sensibility
as compared to other materials such as cast iron or steel
which are greatly affected by age, corrosion and deposition
processes (Koppel & Vassiljev 2009).
Total system water demand also changed only slightly,
as it passed from 10.58 to 10.50 ls ^ for th e PPE ST con-
strained scenario. Regarding temporal variation of water
levels at WSTs, a closer match between observed and mod-
eled values can be appreciated for the PPEST scenarios
(Figure 4). This is particularly true for WSTs 1 and 3
(Figure 4(a),(c)), whereas little difference can be seen for
tank s 2 and 4 (Figure 4(b),(d)) regardless of the optimization
approach. The PPEST unconstrained scenario was partly
based on the adjustment of the demand pattem factors
(Table 3).
PPEST optimized weekday demand factors are gener-
ally in good agreement with those initially obtained by
analyzing diurnal dynamics of water demand, particularly
for WSTs 1 and 3 (Figure 5(a),(c)).
There are, however, local differences that show a
larger variation around the hours of higher water
demand , betw een 0900 and 1400 hr, p rincipally for
WSTs 2 and 4 (Figure 5(b),(d)). This could be attributed
to the relative sensitivity of those pattern factors. None-
theless, little confidence can be attributed to these
patterns as compensating errors are very high for the
PPEST unconstrained scenario.
Parameter sensitivity
As calculated by PPEST, the WDS model is mostly
sensitive to nodal demands since this group of
parameters exhibits the highest average composite sensi-
tivities for both constrained and unconstrained
scenarios, 2.86 and 2. 2 6 x lO \ respectively (Table 6).
As discussed above, EPANET is controlled by water
12 24 36 48 6
0.5
12
24 36
Time hrs)
48 60
12 24 36 48
Time hrs)
60 72
EXPLANATION Obs ervations - PPEST Con strained PPEST Unco nstraine d Trial-and-Error
Figure 4
I PPEST optim ized wa ter-lev el values for a time lapse of 72-hr.
7/24/2019 Automated Parameter Optimization of a Water Distribution
12/16
82
Mndez
et
s/ Automa ted parameter optimization
of
a water distribution system
JournalofHydroinformatics | 15.1 | 2013
10 12 14 16 18 20 22 24
Time iirs)
6 8
1 12 14
Time iirs)
16 18 20 22 24
EXPLANATION
Initial Estimation
PPEST Unconstrained
igure
5I
Initially estimated versus PPEST unconstrained optimized weei
7/24/2019 Automated Parameter Optimization of a Water Distribution
13/16
83 M Mndez eta l | Automated parameter optimization of a water distribution system
Journai of Hydroinformatics | 15 1 | 2013
are only determinant if sufficient head loss is experienced
across the WDS. This is clearly not our case, as velocities
and head losses are quite small most of the fime.
Objective function
From a practical standpoint, it is essenfial to assess the
number of model calls that PPEST required to minimize
its objective funcfion PHI {0 . For the unconstrained scen-
ario,
PPEST needed to run EPANET 6507 fimes in order
to find what PPEST considers to be the global minimum .
This global min imu m w as found after the fifth iterafion,
achieving a PHI reduction of nearly 77%, as its initial value
was reduced from 7.77 to 1.817 m^. As stated by G oegebeur
& Pauwels (2007), even when PHI differs from RMSE, the
minimization of this function also leads to a minimization
of the RMSE (Table 4).
After running in estimafion-mode, PPEST executed four
addifional iterafions after the global minimum was found,
just to ensure that it did not encounter a local minimum.
A total of 10,845 EPANET calls were needed to complete
the optimization process, wh ich lasted for 13.2 hr, clearly
indicafing a high computational burden. If PEST instead
of PPEST had been used in this case, an estimated 90.4 hr
run would have been needed to accomplish the same
result. This is quite predictable as PEST's final report
states how long it needs to complete one EPANET's run.
For the m ore realistic and physically correct co nstrained
scenario, PPEST com pleted the who le opfimizafion process
in 0.74 hr, almost 18 times faster th an the unco nstrained
scenario and with similar outcomes as PHI was reduced
from its original trial-and-error value of 7.77-2.065 m^.
The most fime consuming part of PPEST's operafions is
related to the calculation of the Jacobian matrix through par-
tial derivatives, which requires two model calls for each
adjustable parameter. Nonetheless, the calculation of the
Jacobian matrix permits PPEST to derive important by-
products such as relative and absolute sensitivity, corre-
lation, uncertainty and Eigenvectors which are of great
importance in post-optimization analysis.
On the other hand, PPEST is capable of fixing par-
ameters based on a given sensitivity threshold. This could
help improve PPEST's performance through modeler inter-
venfion (Doherty 2005). Finally, it is important to note that
EPANET is a fully distributed complex hydraulic solver
which demands a great deal of computafional resources by
its lf
This clearly increases the time lapse needed for
PPEST to achieve convergence.
CONCLUSIONS
The feasibility of using the model independent parameter
esfimator PPE ST to develop a fully-calibrated extend ed
period model for a WDS using EPANET was investigated.
It was found that the results from a fully automated cali-
brafion technique like PPEST should be used with caufion.
As calibration is a highly underdetermined problem,
PPEST may produce numerically correct but physically
meaningless solutions if insufficient restrictions are applied.
The two PPEST scenarios analyzed in this study further
emphasize this situation.
The uncon strained scenario show ed that if all parameters
are open to adjustment, considerable com pensating errors are
introduced into the optimization process. Under these cir-
cumstances, PPEST was capable of matching observations
but incapable of determining the opfimtim set of param eters
for the system. As the number of unknown s was mu ch greater
than the number of observafions, the parameter space was
simply too large for PPEST to find a proper solufion. It was
demonstrated that including insensitive parameters signifi-
cantly deteriorates model's solufions and imposed a heavy
computational burden on the whole optimization process.
On the other hand, the constrained scenario represents
a more properly discretized and therefore, more reliable
scheme as parameters were grouped in classes of similar
characteristics and insensitive parameters were fixed. This
had a profound impact on the parameter space as adjustable
parameters were reduced from 723 in the unconstrained
scenario to 24 in the constrained scenario. In this regard,
the computational requirements were much lower as the
whole opfimization process took 0.74 hr as com pared to
the 13.2 hr needed for the uncons trained scenario.
The model was mainly sensitive to nodal demands as
average composite sensitivities for both constrained and
unco nstrained PPEST scenarios reache d 2.86 and 2.26 x
10 \ respectively. The FAVs loss coefficients r epre sente d
the second most sensitive group of parameters as their
7/24/2019 Automated Parameter Optimization of a Water Distribution
14/16
8 M Mndez et
ai
| Automated parameter optimizationof awater distr ibution system
Journai
of
Hydroinformatics
| 15 1 | 2013
average composite sensitivity reached values of
1.8080
x
10 ^ and 2.5980 x 10 for the constrained and uncon-
strained PEST scenarios, respectively. The remaining
groups of parameters, including C-factors, showed very low
sensitivities, two to three orders in magnitude lower than
that of nodal demands. A considerable RMSE reduction
was obtained for the constrained scenario, particularly for
nodal pressures as its value decreased from 4.68 to 1.85 m.
The constrained solution, even when it is valid only for
the system's normal operating conditions, clearly demon-
strates that PPEST has the potential to be used in the
calibration of WDS models.
FUTURE WORK
Further investigation is needed to determine PPEST's per-
formance in complex WDS models over a wide range of
operating conditions. This may include the evaluation of
control valves, pump curves, control rules and water quality
issues.
An EPANET-PEST utility software could be devel-
oped to facilitate communication between both packages.
This would allow users to run PEST directly in a graphical
environment, where many of the variables and outcomes
of the calibration process could be viewed and externally
manipulated.
C K N O W L E D G M E N T S
The authors wish to thank Junta Administradora del
Acueducto La Sirena, La comunidad de la Sirena,
Estacin de Investigacin y Transferencia de Tecnologa
de Puerto Mallarino and Cinara-Universidad del Valle for
their help and guidance in the development of this project.
REFERENCES
Abe,
N. &
Cheung,
P.
B. 2010 E panet Calibrator
- an
integrated
computational toolto calibrate hydraulic models.Int. Water
Syst.V,
129-133.
Alvisi,
S. &
Franchini, M. 2010 Pipe roughness calibration
in
water distribution systems using grey numbers.
/.
Hydroinf
12
424-445.
Arabi,
M.,
Govindaraju,
R. S. &
Hantush, M. M. 2007 A
probabilistic approach
for
analysis
of
uncertainty
in the
evaluation of watershed management practice. /.
Hydrol
333
459-471.
Bahremand, A.& deSmedt, F. 2010 Predictive analysisand
simulation uncertainty
of a
distributed hydrological model.
/. Water Res. Manage.24 2869-2880.
Baranowski, T. 2007 Development
of
Consequence Management
Strategiesfor Water Distribution Systems. Doctoral
Dissertation, Graduate School
of
Vanderbilt University,
Nashville, Tennessee, USA.
Beven,
K. &
Binley, A. 1992 Tbe future
of
distributed models:
model calibrationand uncertainty prediction.Hydrol.
Process.
6,
279-298.
Cabrera,E.,Espert, V., Garcia-Serra,J. &Martinez, F. 1996
Ingenierahidrulica.Aplicada
a
los sistemas de d istribuein
de agua. Universidad PolitcnicadeValencia, Spain.
Cbristensen,
S. &
Doherty, B. 2008 Predictive error dependencies
when using pilot points
and
singular value decomposition
in groundwater model calibration. Adv. WaterResour
31
674-700.
de Sch aetzen, W ., Hung, J., Clark, S., Gottfred,C,Acosta, B.&
Reynolds, P. 2010 How mu eb is your uncalibrated model
costing your utility? Ten lessons learned from calibrating th e
CRD Water M odel. In
Proc.WaterD istribution System
Anlisis(A. Z. Tucson,
ed.).
USA, Sept.
12-15, pp.
1053-1065.
Doberty, J. 2005 PEST:Model IndependentParameterEstimation
Users
Manual.
Watermark Numerical Computing, Brisbane.
Duan,
Q.,
Soroosbian,
S. &
Gupta, V.
K.
1992 Effective
and
efficient global optimization
for
conceptual rainfall runoff
models.WaterResour Res.24 1163-1173.
Fang, T.&Ball, J. E. 2007 Evaluationofspatially variable control
parameters
in a
complex catchment modelling system:
a
genetic algorithm ap plication./.Hydroinf 9,163-174.
Gallagher, M.
R. &
Doherty, ]. 2007 Parameter interdependence
and uncertainty inducedbylumpingin a hydrologie model.
Water Resour Res.
43
1-18.
Giustolisi,
O. &
Berardi, L. 2on Water distribution network
calibration using enhanced GGA
and
topological analysis.
/. Hydroinf 13 621-641.
Goegebeur,M. &Pauwels,R. N. 2007 Improvementofthe PEST
parameter estimation algorithm through Extended Kaiman
Filtering.
/.
Hydrol 337
436-451.
Hogue,
T.,
Gupta,
H. &
Soroosbianc,
S.
2006
A
'User-Friendly'
approach
to
parameter estimation
in
hydrologie models.
/.
ydroL
320 202-217.
Ibrahim, Y.
&
Liong,
S.
Y. 1992 Calibration strategy
for
urban
eatebment parameters. ASCE . Hydraul Eng.
118
1550-1570.
Immerzeel, W. W.&Droogers, P. 2008 Calibration of a distributed
bydrologieal model based
on
satellite evapotranspiration.
/. Hydro/.349 411-424.
Jamasb, M., Tabesh,M. &Rahimi, M. 2008 C alibrationof
EPANET using Genetie Algorithm.
In
Proc. 10 th Annu al
Water Distribution Systems Analysis Conference Kruger
7/24/2019 Automated Parameter Optimization of a Water Distribution
15/16
85 M Mndez et
a l
Automated parameter optimization of a water distr ibution system
Journal of Hydroinformatics | 15 1 | 201 3
National Park, South Africa, August 17-20th, 2008,
pp. 881-889.
Kang, D. Lansey, K. 2009 Real-time dem and estimation and
confidence limit analysis for water distribution systems.
ASCE ]. Hydraul. Eng.135 825-837.
Kapelan, Z., Savie, D. A. Walters, G. A. 2007 Calibration of
water distribution hydraulic models using a Bayesian-Type
procedure.
ASCE
/.
Hydraul. Eng.
133, 927-936.
Kenward,
T.
C. How ard, C. D. 1999 Forecasting for urban water
demand management. In Proe.
Annual Water Resources
Planning and ManagementConf. ASCE, Tempe, A rizona,
USA. June6-9th 1999, ch. 9A188, pp. 1-15.
Kliu, S. T., di Pierro, F., Savic, D., Djordjevic, S. W alters, G. A.
2006 Incorporating sp atial and tempo ral information for urban
drainage model calibration: an approach using preference
ordering genetic algorithm.Adv.
Water
Res.29,1168-1181.
Kopp el, A. Vassiljev, A. 2009 Calibration of a model of an
operational water distribution system containing pipes of
different age.Adv. Eng. Softw.40, 659-664.
Kovalenko , Y., Gorev, N . B., Kodzhespirova, I. F., Alvarez, R.,
Prokho rov, E. Ramos, A. 2010 Experim ental analysis of
hydraulic solver convergence with Genetic Algorithms.
ASCE]. Hydraul. Eng. 136 331-335.
Kum ar, S. M., Nara simh an, S. Bhallamudi, S. M. 2009
Parameter estimation in water distribution networks. /.
Water
Res. Manage.24, 1251-1272.
Lansey, K. E. Basnet, C. 1991 Param eter estimation for water
distribution networks. ASCE
J.
Water Res. Plann. Manage.
117,
126-144.
Lee, E. J. Schwab , K. J. 2005 Deficiencies in drinking water
distribution systems in developing countries. /. Water Health
3, 109-127.
Machell, J., Mo unce, S. R. Boxall, J.B.2010 Online modelling of
water distribution systems: a UK case study.Drink.
Water
Eng. Sei 3, 21-27.
Maslia, M. L., Surez-Soto,R.] .,Wang, J., Aral, M. M., Faye, R. E.,
Sautner, J. B., Valenzuela, C. Graym an, W. M. 2009
Analysis of Groundwater
Flow
Contaminant
Fate
an d
Transport and Distribution of Drinking Water at
Tarawa
Terrace
an d
Vieinity U.S.
Marine
Corps
Base Camp Lejeune
North Carolina: Historieal Reeonstruetion and
Present Day
Conditions.
Agency for Toxic Substances and Disease
Registry. US Department of Health and Human Services,
Atlanta, Georgia.
Mays, L. W. 2000 Water Distribution Systems Handbook.
McGraw-Hill, New York.
Nicklow,J.W., Reed, P., Savic, D. A., Dessalegne, T., Harrell, L.,
Chan-Hilton, A., Karamouz, M., Minsker,
B.,
Ostfeld, A., Singh,
A. Zechm an, A. 2009 State of the art for genetic algorithms
and beyond in water resources planning and management.
ASCEJ.
Water
Res.
Plann. Manage. 136 412-432.
Peng, S., Wu, Q. Zhu ang, B. 2009 Param eter identification by
MCMC method for water quality model of distribution
system. In Proe. 3th Intemational
Conferenee
on
Bioinformaties and Biomdical
Engineering Beijing, China,
June ll-13th, 2009, pp. 1-5.
Rossman, L. A. 2000 EPANET 2
Users
Manual. National Risk
Management Research Laboratory, Office of Research and
Development. US E nvironmental Protection Agency,
Cincinnati, Ohio, USA.
Savic, D. A., Kapelan, Z. Jonkergouw , P. 2009 Quo vadis wa ter
distribution model calibration?
Urban
WaterJ. 6, 3-22.
Skahill, B. E. 2009 More efficient PEST com patible m odel
independent model calibration. /.
Environ. Model. Softw.
24,
517-529.
Skahill, B. E. Doherty, J. 2006 An advanced regularization
methodology for use in watershed model calibration. /.
Hydrol.327, 564-577.
Tischler, M., Garcia, M., Peters-Lidard, C, Moran, M. S., Miller, S.,
Thoma, D., Kumar, S. Geiger,
J.
2007 A G IS framework for
surface-layer soil moisture estimation combining satellite radar
measurem ents and land surface m odeling with soil physical
property estimation. /.
Environ. Model. Softw.
22, 891-898.
USEPA 2005
W ater Distribution System Ana lysis: Field Studies
Modeling and Management: A Reference Guide for Utilities.
Office of Research and Development. National Risk
Management Research Laboratory, Water Supply and W ater
Resources Division, Cincinnati, Ohio, USA.
Walski, T. M. 1986 Case study: pipe network model calibration
issues. ASCE f. Water Res. Plann. Manage. 112 238-249.
Walski, T., DeF rank, N., Voglino, T., Wood , R. Wh itman, B. E.
2006 Determining the accuracy of automated calibration of
pipe network models. In Proe. 8th Annual Water
Distribution Systems Analysis Symposium Cincinnati, O hio,
USA, August 27-30th, 2006, pp. 1-18.
Walski, T., Wu, Z. Hartell, W. 2004 Performance of automated
calibration for water distribution systems. In Proe. World
Water and Environmental Resources Congress
Salt Lake
City, Utah, USA, June 27th-July 1st, 2004, pp. 1-10.
Walski, T. M., Chase, D. V. Savic, D. A.
2 1
Water Distribution
Modeling. Haestad Press, Waterbury.
Wu, Z. Y, B oulos,P. F.,Orr,C.H. Ro,J. J.
2
An efficient g enetic
algorithms approach to an intelligent decision supp ort system
for water distribution networks. InProe. H ydroinformaties 2000
Conference Iowa, IW, USA, July 23-27 th, 2000.
Wu, Z. Y, Walski, T. M., Mankowski, R., Herrin, G., Gurrieri, R.
Tryby, M. 2002 Calibrating water distribution model via
genetic algorithms. In Proe. AWWA IMTech Conference
Kansas City, Missouri, USA, April 14-17th, 2002, pp. 1-10.
Zaghloul, N. A. Abu Kiefa, M. A.
2 1
Neural network solution
of inverse parameters used in the sensitivity-calibration
analyses of the SWMM model simulations. Adv. Eng. Softw.
32,587-595.
Zhou, S. L., McMahon,T.A. Lewis, W.J.2000 Forecasting d aily
urban water demand: a case study of Melbourne. /. Hydrol.
236,
153-164.
First received 8 February 2012; accepted in revised form 19 May 2012. Available online 11 September 2012
7/24/2019 Automated Parameter Optimization of a Water Distribution
16/16
Copyright of Journal of Hydroinformatics is the property of IWA Publishing and its content may not be copied
or emailed to multiple sites or posted to a listserv without the copyright holder's express written permission.
However, users may print, download, or email articles for individual use.
Top Related