ADAMS HOUSE AND TOLLGATE LODGE GP PRACTICE
Job Nr 5547
Appendix E – Room Data Sheets
1 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: WAITING AREA 1
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. bed
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. Anti‐ligature luminaires to CIBSE LG7 1 2. Anti‐ligature luminaires with integral emergency inverter/battery pack. To CIBSE LG7 1 3. Heating via Radiators LTHW 1 4. Fire alarm combined smoke detector/sounder 1 5. 2 No. twin socket outlets at 1800mm. AFFL 1 6. 2 No. data outlet socket at 1800mm. AFFL 1 7. 4 No. twin socket outlets at 450mm. AFFL 1 8. 15 x bench style seating 3 9. Blinds and tracks 3 10. anti‐ligature door stops 3
2 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC db. 50% RH Summer : DESIGN : NOTES ‐4ºC sat. Winter : DATA :
AIR : : Winter Temperature (degC) : 18 +/‐ 2c : Summer Temperature (degC) : 24 +/‐ 2c : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : : Pressure – Rel. to Adj. Space : : Filtration (% Dust Sp Eff & % Arr) : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 200 : Service Illumination Night (Lux) : 200 : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 80 : Uniformity : 0.4 : Standby Lighting Grade : NA : Lighting Control : Manual :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : NR 35 : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion Sheet vinyl Heavy duty emulsion
Windows (HBN 00‐10 D) : Openable UPVC frame double glazed window with toughened glass (as
existing).
3 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: Reception
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. bed
Group 4 Small items of loose equipment e.g. computer, waste bin
Group 1. Luminaires to CIBSE LG7 1 2. Luminaire with integral emergency inverter/battery pack. 1 3. Heating via Radiators LTHW 1 4. Fire alarm combined smoke detector/sounder 1 5. Fire alarm repeater panel 1 6. Entry system intercom 1 7. Natural fresh air supply system 1 8. 3 No. single socket outlet at 450mm. AFFL 1 9. 6 no twin socket outlets beneath reception counter worktop 1 10. 3 x receptionist chairs 3 11. Reception counter, with lowered section for wheelchair users 3 12. Hearing loop 1
4 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC db. 50% RH Summer : DESIGN : NOTES ‐4ºC sat. Winter : DATA :
AIR : : Winter Temperature (degC) : 21 +/‐ 2c : Summer Temperature (degC) : 24 +/‐ 2c : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : : Pressure – Rel. to Adj. Space : : Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 300 : Service Illumination Night (Lux) : 200 : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 80 : Uniformity : 0.6 : Standby Lighting Grade : NA : Lighting Control : :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : NR35 : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion : Sheet vinyl : Heavy duty emulsion
Doorsets Solid core light beech veneer FD30S. 2 x Vision panels. Lever handles and mortice lock with internal thumb turn per door. 2 x kick plates. Overhead door closer
Windows (HBN 00‐10 D) : Openable UPVC frame double glazed window with toughened glass (as
existing). Film applied to window
5 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: SERVER
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coathook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. bed
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. Luminaires to CIBSE LG7 1 2. Luminaire to CIBSE LG7 with integral emergency inverter/battery pack. 1 3. Cooling 1 4. Fire alarm combined smoke detector/sounder 1 5. Natural fresh air supply system 1 6. 1 No. single socket outlet at 450mm. AFFL 1 7. 9 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking 1
6 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 28ºC d.b. 20ºC w.b. summer : DESIGN : NOTES ‐4ºC sat. winter : DATA :
AIR : : Winter Temperature (degC) : 22 +/‐ 2c : Summer Temperature (degC) : 22 +/‐ 2c : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : : Pressure – Rel. to Adj. Space : : Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 300 : Service Illumination Night (Lux) : NA : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 60 : Uniformity : 0.4 : Standby Lighting Grade : NA : Lighting Control : :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion Raised anti‐station Heavy duty emulsion
Doorsets : Solid core painted timber door. FD30S. Lever handles and mortice lock with internal thumb turn. 2 x kick plates. Overhead door closer.
Windows (HBN 00‐10 D) : Openable UPVC frame double glazed window with toughened glass (as
existing). Film applied to window
7 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: DISABLED WC
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. bed
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. Patient Call Switch with pull cord and reassurance with local reset (Nurse call) with infra‐red receiver and external over door indicator. 1
2. Luminaire 1 3. Luminaire with integral emergency inverter/battery pack
1 4. Heating via Radiators LTHW 1 5. Doc M Pack comprising wash hand basin with lever mixer tap, close coupled WC pan
with back rest and grab rails 1 6. Extract Ventilation system with door transfer grille. 7. Concealed drainage from wash hand basin and W.C. 1 8. 1 x Anti ligature coat hook 1 9. toilet magazine dispenser 2 10. soap dispenser 2 11. Unbreakable Mirror 300 x 450 1 12. alcohol gel dispenser 2 13. Paper towel dispenser 2 14. bin 4
8 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC db. 50% RH summer : DESIGN : NOTES ‐4ºC sat. Winter : DATA :
AIR : : Winter Temperature (degC) : 18 : Summer Temperature (degC) : Uncontrolled : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : 0.015 : Pressure – Rel. to Adj. Space : : Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 200 : Service Illumination Night (Lux) : 200 : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 80 : Uniformity : 0.6 : Standby Lighting Grade : NA : Lighting Control : N :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion Non slip vinyl Heavy duty emulsion
Altro whiterock splasback
Doorsets : Solid core light beech veneer double swing door. Lever handles with indicator lock with external emergency access. 2 x kick plates
Windows (HBN 00‐10 D) : Openable UPVC frame double glazed window with toughened glass (as
existing). Film applied to window
9 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: PATIENT WC
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. bed
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. Patient Call Switch and reassurance with local reset (Nurse call) with infra‐red receiver and external over door indicator. 1
2. Luminaire with integral emergency inverter/battery pack. 1 3. Wash hand basin with percussion outlets served from thermostatic mixing
valve and isolation valves. 1 4. W.C. with air push button flushing cistern. 5. Natural fresh air supply system 1 6. Concealed drainage from wash hand basin and W.C. 1 7. 1 x Anti ligature coat hook 1 8. toilet magazine dispenser 2 9. soap dispenser 2 10. Unbreakable Mirror 300 x 450 1 11. alcohol gel dispenser 2 12. Paper towel dispenser 2 13. bin 4
10 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC db. 50% RH summer : DESIGN : NOTES ‐4ºC sat. Winter : DATA :
AIR : : Winter Temperature (degC) : 18 : Summer Temperature (degC) : Uncontrolled : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : 0.015 : Pressure – Rel. to Adj. Space : : Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 200 : Service Illumination Night (Lux) : 200 : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 80 : Uniformity : 0.6 : Standby Lighting Grade : NA : Lighting Control : N :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : NR 35 : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion Non slip vinyl Heavy duty emulsion
Altro whiterock splasback
Doorsets : Solid core light beech veneer double swing door. Lever handles with indicator lock with external emergency access. 2 x kick plates
11 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: PATIENT CORRIDOR
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. bed
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. 3 Staff alarm points (linked to Eddison system) 1 2. Luminaires to CIBSE LG7 1 3. Luminaire to CIBSE LG7 with integral emergency inverter/battery pack. 1 4. Fire alarm combined smoke detector/sounder 1 5. Fire alarm call point with key switch 1 6. 4 No. single socket outlets at 450mm. AFFL 1
12 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC db. 50% RH summer : DESIGN : NOTES ‐4ºC sat. Winter : DATA :
AIR : : Winter Temperature (degC) : 15 : Summer Temperature (degC) : : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : : : : Pressure – Rel. to Adj. Space : : Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 200 : Service Illumination Night (Lux) : 200 : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 80 : Uniformity : 0.4 : Standby Lighting Grade : NA : Lighting Control : N :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : NR35 : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion Sheet vinyl : Heavy duty emulsion
Doorsets Solid core light beech veneer door and a half arrangement. FD30S. Flush bolts to slave leaf. Lever handles and mortice lock with internal thumb turn to master leaf. 2 x vision panels to master leaf. 2 x kick plates to both leaves. Overhead door closer to master leaf.
Windows (HBN 00‐10 D) : Openable UPVC frame double glazed window with toughened glass (as
existing). Film applied to window
13 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: C/E 1
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. treatment couch
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. Staff alarm point (linked to Eddison system) 1 2. Luminaires to CIBSE LG7 1 3. Luminaires to CIBSE LG7 with integral emergency inverter/battery pack. 1 4. Heating via Radiators LTHW 1 5. Fire alarm combined smoke detector/sounder 1 6. 4 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking 1 7. 2 No. twin socket outlets at 450mm. AFFL 1 8. 2 No. data outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking
with Cat 6e data cabling to patch panel. 1 9. 1 No. telephone outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking 1 10. 1 x No. Clinical basin with elbow taps mounted on full height IPS panel 1 11. Lockable wall cupboard 1 12. Worktop and lockable cupboard and draws underneath 1 13. Natural fresh air supply system 1 14. Desk 2 15. 1 x doctor’s chair 3 16. 1 x patient chair 3 17. Examination couch 3 18. 1 x curtain and track 2 19. 2 x bins 4 20. 1 x computer 4 21. Alcohol gel dispenser 2 22. Paper towel dispenser 2 23. Soap dispenser 2 24. Door stops and hook 1 25. Washable roller blinds to windows 1
14 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC d.b.50% RH. Summer : DESIGN : NOTES ‐4ºC sat. Winter : DATA :
AIR : : Winter Temperature (degC) : 21 +/‐ 2c : Summer Temperature (degC) : 24 +/‐ 2c : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : : Pressure – Rel. to Adj. Space : : Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 500 : Service Illumination Night (Lux) : NA : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 90 : Uniformity : 0.6 : Standby Lighting Grade : NA : Lighting Control : N :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : NR 35 : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion : Sheet vinyl : Heavy duty emulsion
Door sets : Solid core light beech veneer with lever handles and mortice lock with internal thumb turn. 2 x kick plates
Windows (HBN 00‐10 D) : Openable UPVC frame double glazed window with toughened glass (as
existing). Film applied to window
15 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: C/E 2
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. treatment couch
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. Staff alarm point (linked to Eddison system) 1 2. Luminaires to CIBSE LG7 1 3. Luminaires to CIBSE LG7 with integral emergency inverter/battery pack. 1 4. Heating via Radiators LTHW 1 5. Fire alarm combined smoke detector/sounder 1 6. 4 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking 1 7. 2 No. twin socket outlets at 450mm. AFFL 1 8. 2 No. data outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking
with Cat 6e data cabling to patch panel. 1 9. 1 No. telephone outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking 1 10. 1 x No. Clinical basin with elbow taps mounted on full height IPS panel 1 11. Lockable wall cupboard 1 12. Worktop and lockable cupboard and draws underneath 1 13. Natural fresh air supply system 1 14. Desk 2 15. 1 x doctor’s chair 3 16. 1 x patient chair 3 17. Examination couch 3 18. 1 x curtain and track 2 19. 2 x bins 4 20. 1 x computer 4 21. Alcohol gel dispenser 2 22. Paper towel dispenser 2 23. Soap dispenser 2 24. Door stops and hook 1 25. Washable roller blinds to windows 1
16 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC d.b.50% RH. Summer : DESIGN : NOTES ‐4ºC sat. Winter : DATA :
AIR : : Winter Temperature (degC) : 21 +/‐ 2c : Summer Temperature (degC) : 24 +/‐ 2c : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : : Pressure – Rel. to Adj. Space : : Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 500 : Service Illumination Night (Lux) : NA : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 90 : Uniformity : 0.6 : Standby Lighting Grade : NA : Lighting Control : N :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : NR 35 : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion : Sheet vinyl : Heavy duty emulsion
Door sets : Solid core light beech veneer with lever handles and mortice lock with internal thumb turn. 2 x kick plates
Windows (HBN 00‐10 D) : Openable UPVC frame double glazed window with toughened glass (as
existing). Film applied to window
17 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: C/E 3
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. treatment couch
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. Staff alarm point (linked to Eddison system) 1 2. Luminaires to CIBSE LG7 1 3. Luminaires to CIBSE LG7 with integral emergency inverter/battery pack. 1 4. Heating via Radiators LTHW 1 5. Fire alarm combined smoke detector/sounder 1 6. 4 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking 1 7. 2 No. twin socket outlets at 450mm. AFFL 1 8. 2 No. data outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking
with Cat 6e data cabling to patch panel. 1 9. 1 No. telephone outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking 1 10. 1 x No. Clinical basin with elbow taps mounted on full height IPS panel 1 11. Lockable wall cupboard 1 12. Worktop and lockable cupboard and draws underneath 1 13. Natural fresh air supply system 1 14. Desk 2 15. 1 x doctor’s chair 3 16. 1 x patient chair 3 17. Examination couch 3 18. 1 x curtain and track 2 19. 2 x bins 4 20. 1 x computer 4 21. Alcohol gel dispenser 2 22. Paper towel dispenser 2 23. Soap dispenser 2 24. Door stops and hook 1 25. Washable roller blinds to windows 1
18 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC d.b.50% RH. Summer : DESIGN : NOTES ‐4ºC sat. Winter : DATA :
AIR : : Winter Temperature (degC) : 21 +/‐ 2c : Summer Temperature (degC) : 24 +/‐ 2c : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : : Pressure – Rel. to Adj. Space : : Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 500 : Service Illumination Night (Lux) : NA : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 90 : Uniformity : 0.6 : Standby Lighting Grade : NA : Lighting Control : N :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : NR 35 : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion : Sheet vinyl : Heavy duty emulsion
Door sets : Solid core light beech veneer with lever handles and mortice lock with internal thumb turn. 2 x kick plates
Windows (HBN 00‐10 D) : Openable UPVC frame double glazed window with toughened glass (as
existing). Film applied to window
19 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: C/E 4
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. treatment couch
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. Staff alarm point (linked to Eddison system) 1 2. Luminaires to CIBSE LG7 1 3. Luminaires to CIBSE LG7 with integral emergency inverter/battery pack. 1 4. Heating via Radiators LTHW 1 5. Fire alarm combined smoke detector/sounder 1 6. 4 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking 1 7. 2 No. twin socket outlets at 450mm. AFFL 1 8. 2 No. data outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking
with Cat 6e data cabling to patch panel. 1 9. 1 No. telephone outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking 1 10. 1 x No. Clinical basin with elbow taps mounted on full height IPS panel 1 11. Lockable wall cupboard 1 12. Worktop and lockable cupboard and draws underneath 1 13. Natural fresh air supply system 1 14. Desk 2 15. 1 x doctor’s chair 3 16. 1 x patient chair 3 17. Examination couch 3 18. 1 x curtain and track 2 19. 2 x bins 4 20. 1 x computer 4 21. Alcohol gel dispenser 2 22. Paper towel dispenser 2 23. Soap dispenser 2 24. Door stops and hook 1 25. Washable roller blinds to windows 1
20 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC d.b.50% RH. Summer : DESIGN : NOTES ‐4ºC sat. Winter : DATA :
AIR : : Winter Temperature (degC) : 21 +/‐ 2c : Summer Temperature (degC) : 24 +/‐ 2c : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : : Pressure – Rel. to Adj. Space : : Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 500 : Service Illumination Night (Lux) : NA : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 90 : Uniformity : 0.6 : Standby Lighting Grade : NA : Lighting Control : N :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : NR 35 : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion : Sheet vinyl : Heavy duty emulsion
Door sets : Solid core light beech veneer with lever handles and mortice lock with internal thumb turn. 2 x kick plates
Windows (HBN 00‐10 D) : Openable UPVC frame double glazed window with toughened glass (as
existing). Film applied to window
21 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: TREATMENT/ MULTI
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. bed
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. Staff alarm point (linked to Eddison system) 1 2. Luminaires to CIBSE LG7 1 3. Luminaires to CIBSE LG7 with integral emergency inverter/battery pack. 1 4. Heating via Radiators LTHW 1 5. Fire alarm combined smoke detector/sounder 1 6. 4 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking 1 7. 2 No. twin socket outlets at 450mm. AFFL 1 8. 2 No. data outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking
with Cat 6e data cabling to patch panel. 1 9. 1 No. telephone outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking 1 10. 1 x No. Clinical basin with elbow taps.served from thermostatic mixing valve and 1 11. lockable wall cupboards 1 12. worktop and lockable cupboards and draws underneath 1 13. Natural fresh air supply system 1 14. Alcohol gel dispenser 2 15. Paper towel dispenser 2 16. Soap dispenser 2 17. Door stops and hook 1
22 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC db. 50% RH summer : DESIGN : NOTES ‐4ºC sat. Winter : DATA :
AIR : : Winter Temperature (degC) : 21 +/‐ 2c : Summer Temperature (degC) : 23 +/‐ 2c : Mechanical Ventilation: Supply (m3/s) : 0.110 : Supply air to 10 ACH Mechanical Ventilation: Extract (m3/s) : 0.110 : Pressure – Rel. to Adj. Space : Positive to corridor 0.107m3/s & 0.050m3/s Dirty utility. Filtration (% Dust Sp Eff & % Arr) : F7 : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 500 : Service Illumination Night (Lux) : 200 : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 90 : Uniformity : 0.6 : Standby Lighting Grade : NA : Lighting Control : N :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : NR 35 : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion : Sheet vinyl : Heavy duty emulsion
Altro whiterock splasback
Doorsets : 2 x Solid core light beech veneer door and a half arrangement. Flush bolts to slave leaves. Lever handles and mortice lock with internal thumb turn to master leaves. 2 x kick plates to both leaves of both sets of doors.
Windows (HBN 00‐10 D) : Openable UPVC frame double glazed window with toughened glass (as
existing). Film applied to window
23 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: DIRTY UTILITY
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. bed
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. Luminaires to CIBSE LG7 1 2. Luminaire to CIBSE LG7 with integral emergency inverter/battery pack. 1 3. Fire alarm combined smoke detector/sounder 1 4. Stainless steel sink with drainer at mixer taps with lockable cupboards 1 5. Clinical wash hand basin with elbow taps with thermostatic mixing valve 1 6. Stainless steel slop hopper sink 1 7. Worktop 1 8. Lockable cupboards with drawers beneath worktops 1 9. Lockable wall mounted cupboards 1 10. 2 No. twin socket outlets at 450mm. AFFL 1 11. Natural fresh air supply system 1 12. 2 large waste bins – 1 black and 1 clinical waste (yellow) 4 13. Sharps bin holder 4 14. Glove and apron dispensers 2 15. soap dispenser 2 16. Paper towel dispenser 2 17. 1500 long adjustable height white melamine shelves 1200 x 1800 high 1 18. Alcohol gel dispenser 2 19. 4 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking 1 20. 2 No. twin socket outlets at 450mm. AFFL 1 21. 2 No. data outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking
with Cat 6e data cabling to patch panel. 1 22. 1 No. telephone outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking 1
24 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC db. 50% RH summer : DESIGN : NOTES ‐4ºC sat. Winter : DATA :
AIR : : Winter Temperature (degC) : 15 : Summer Temperature (degC) : Uncontrolled : Mechanical Ventilation: Supply (m3/s) : : : : Mechanical Ventilation: Extract (m3/s) : 0.050 : Air transfer from Treatment & : : corridor to provide 6 ACH as Pressure – Rel. to Adj. Space : Negative pressure HTM requirements. Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 200 : Service Illumination Night (Lux) : 200 : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 80 : Uniformity : 0.6 : Standby Lighting Grade : NA : Lighting Control : N :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : NR35 : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion Non slip vinyl :Heavy duty emulsion
Altro whiterock splasback
Door sets : 2 x Solid core light beech veneer FD30S with lever handles and mortice lock with internal thumb turns. 2 x kick plates per door. 2 x overhead door closers.
Windows (HBN 00‐10 D) : Openable UPVC frame double glazed window with toughened glass (as
existing). Film applied to window
25 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: WAITING AREA 2
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. bed
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. Anti‐ligature luminaires to CIBSE LG7 1 2. Anti‐ligature luminaires with integral emergency inverter/battery pack. To CIBSE LG7 1 3. Heating via Radiators LTHW 1 4. Fire alarm combined smoke detector/sounder 1 5. 2 No. twin socket outlets at 1800mm. AFFL 1 6. 2 No. data outlet socket at 1800mm. AFFL 1 7. 4 No. twin socket outlets at 450mm. AFFL 1 8. 15 x bench style seating 3 9. Blinds and tracks 3 10. anti‐ligature door stops 3
26 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC db. 50% RH Summer : DESIGN : NOTES ‐4ºC sat. Winter : DATA :
AIR : : Winter Temperature (degC) : 18 +/‐ 2c : Summer Temperature (degC) : 24 +/‐ 2c : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : : Pressure – Rel. to Adj. Space : : Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 200 : Service Illumination Night (Lux) : 200 : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 80 : Uniformity : 0.4 : Standby Lighting Grade : NA : Lighting Control : N :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : NR 35 : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion Sheet vinyl Heavy duty emulsion
Windows (HBN 00‐10 D) : Openable UPVC frame double glazed window with toughened glass (as
existing). Film applied to window
27 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: STORE
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. bed
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. Luminaire 1 2. Luminaire to CIBSE LG7 with integral emergency inverter/battery pack. 1 3. Electric Tube Heating. 1 4. Fire alarm combined smoke detector/sounder 1 5. Fresh air supply and Ventilation 1 6. Full height and width timber slatted shelving at 600mm vertical centers 1
28 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC db. 50% RH Summer : DESIGN : NOTES ‐4ºC sat. Winter : DATA :
AIR : : Winter Temperature (degC) : 15 : Summer Temperature (degC) : Uncontrolled : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : : Pressure – Rel. to Adj. Space : : Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 300 : Service Illumination Night (Lux) : 200 : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 80 : Uniformity : 0.6 : Standby Lighting Grade : NA : Lighting Control : N :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : NR35 : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion : Sheet vinyl : Heavy duty emulsion
Doorsets : Solid core light beech veneer FD30S. Lever handles and mortice lock with internal thumb turn. 2 x kick plates. Overhead door closer
:Windows (HBN 00‐10 D) : Non‐openable steel frame double glazed window with toughened glass (as
existing).
29 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: PATIENT CORRIDOR
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. bed
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. 3 Staff alarm points (linked to Eddison system) 1 2. Luminaires to CIBSE LG7 1 3. Luminaire to CIBSE LG7 with integral emergency inverter/battery pack. 1 4. Fire alarm combined smoke detector/sounder 1 5. Fire alarm call point with key switch 1 6. 1 No. single socket outlets at 450mm. AFFL 1
30 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC db. 50% RH summer : DESIGN : NOTES ‐4ºC sat. Winter : DATA :
AIR : : Winter Temperature (degC) : 15 : Summer Temperature (degC) : : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : : : : Pressure – Rel. to Adj. Space : : Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 200 : Service Illumination Night (Lux) : 200 : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 80 : Uniformity : 0.4 : Standby Lighting Grade : NA : Lighting Control : N :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : NR35 : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion Sheet vinyl : Heavy duty emulsion
Doorsets Solid core light beech veneer door and a half arrangement. FD30S. Flush bolts to slave leaf. Lever handles and mortice lock with internal thumb turn to master leaf. 2 x vision panels to master leaf. 2 x kick plates to both leaves. Overhead door closer to master leaf.
Windows (HBN 00‐10 D) : Openable UPVC frame double glazed window with toughened glass (as
existing). Film applied to window
31 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: STAFF CORRIDOR
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. bed
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. Luminaires to CIBSE LG7 1 2. Luminaire to CIBSE LG7 with integral emergency inverter/battery pack. 1 3. Fire alarm combined smoke detector/sounder 1 4. Natural fresh air supply system 1 5. 1 No. magnetic door locks and proximity sensor readers and associated power supplies 1 6. 2 No. single socket outlets at 450mm. AFFL 1
32 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC db. 50% RH Summer : DESIGN : NOTES ‐4ºC sat. Winter : DATA :
AIR : : Winter Temperature (degC) : 15 : Summer Temperature (degC) : Uncontrolled : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : : Pressure – Rel. to Adj. Space : Balanced : Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 200 : Service Illumination Night (Lux) : 200 : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 80 : Uniformity : 0.4 : Standby Lighting Grade : NA : Lighting Control : N :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : NR 35 : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion Sheet vinyl : Heavy duty emulsion
Doorsets 2 x Solid core light beech veneer doors FD30S. Push plates and pull handles. Mortice locks with internal thumb turns. 2 x kick plates to both doors. 2 x vision panels per door. Overhead door closers.
33 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: CLEANERS CUPBOARD
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. bed
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. Luminaire with integral emergency inverter/battery pack 1 2. High back cleaners sink with integral grating 1 3. Natural fresh air supply system 1
34 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC db. 50% RH. Summer : DESIGN : NOTES ‐4ºC sat. Winter : DATA :
AIR : : Winter Temperature (degC) : 15 : Summer Temperature (degC) : Uncontrolled : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : : : : Pressure – Rel. to Adj. Space : : Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 300 : Service Illumination Night (Lux) : 200 : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 80 : Uniformity : 0.6 : Standby Lighting Grade : NA : Lighting Control : N :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion Non slip vinyl Heavy duty emulsion
Door sets : Solid core light beech veneer door FD30S. Lever handles with mortice lock with internal thumb turn override. 2 x kick plates. Overhead door closer.
35 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: PATIENT WC
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. bed
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. Patient Call Switch and reassurance with local reset (Nurse call) with infra‐red receiver and external over door indicator. 1
2. Luminaire with integral emergency inverter/battery pack. 1 3. Wash hand basin with percussion outlets served from thermostatic mixing
valve and isolation valves. 1 4. W.C. with air push button flushing cistern. 1 5. Natural fresh air supply system 1 6. Concealed drainage from wash hand basin and W.C. 1 7. 1 x Anti ligature coat hook 1 8. toilet magazine dispenser 2 9. soap dispenser 2 10. Unbreakable Mirror 300 x 450 1 11. alcohol gel dispenser 2 12. Paper towel dispenser 2 13. bin 4
36 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC db. 50% RH summer : DESIGN : NOTES ‐4ºC sat. Winter : DATA :
AIR : : Winter Temperature (degC) : 18 : Summer Temperature (degC) : Uncontrolled : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : 0.015 : : : Pressure – Rel. to Adj. Space : : Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 200 : Service Illumination Night (Lux) : 200 : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 80 : Uniformity : 0.6 : Standby Lighting Grade : NA : Lighting Control : N :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : NR 35 : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion Non slip vinyl Heavy duty emulsion
Altro whiterock splasback
Doorsets : Solid core light beech veneer double swing door. Lever handles with indicator lock with external emergency access. 2 x kick plates
Windows (HBN 00‐10 D) : Openable UPVC frame double glazed window with toughened glass (as
existing). Film applied to window
37 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: PLANT ROOM
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coathook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. bed
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. Luminaires to CIBSE LG7 1 2. Luminaire to CIBSE LG7 with integral emergency inverter/battery pack. 1 3. Heating via Radiators LTHW 1 4. Fire alarm combined smoke detector/sounder 1 5. Naturally Ventilated 1 6. 3 No. double socket outlets at 450mm. AFFL 1
38 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 28ºC d.b. 20ºC w.b. summer : DESIGN : NOTES ‐4ºC sat. winter : DATA :
AIR : : Winter Temperature (degC) : Uncontrolled : Summer Temperature (degC) : Uncontrolled : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : : Pressure – Rel. to Adj. Space : : Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 300 : Service Illumination Night (Lux) : NA : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 60 : Uniformity : 0.4 : Standby Lighting Grade : NA : Lighting Control N :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion Painted resin Heavy duty emulsion
Doorsets : Solid core painted timber door. FD30S. Lever handles and mortice lock with internal thumb turn. 2 x kick plates. Overhead door closer.
39 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: C/E 5
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. treatment couch
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. Staff alarm point (linked to Eddison system) 1 2. Luminaires to CIBSE LG7 1 3. Luminaires to CIBSE LG7 with integral emergency inverter/battery pack. 1 4. Heating via Radiators LTHW 1 5. Fire alarm combined smoke detector/sounder 1 6. 4 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking 1 7. 2 No. twin socket outlets at 450mm. AFFL 1 8. 2 No. data outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking
with Cat 6e data cabling to patch panel. 1 9. 1 No. telephone outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking 1 10. 1 x No. Clinical basin with elbow taps mounted on full height IPS panel 1 11. Lockable wall cupboard 1 12. Worktop and lockable cupboard and draws underneath 1 13. Natural fresh air supply system 1 14. Desk 2 15. 1 x doctor’s chair 3 16. 1 x patient chair 3 17. Examination couch 3 18. 1 x curtain and track 2 19. 2 x bins 4 20. 1 x computer 4 21. Alcohol gel dispenser 2 22. Paper towel dispenser 2 23. Soap dispenser 2 24. Door stops and hook 1 25. Washable roller blinds to windows 1
40 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC d.b.50% RH. Summer : DESIGN : NOTES ‐4ºC sat. Winter : DATA :
AIR : : Winter Temperature (degC) : 21 +/‐ 2c : Summer Temperature (degC) : 24 +/‐ 2c : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : : Pressure – Rel. to Adj. Space : : Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 500 : Service Illumination Night (Lux) : NA : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 90 : Uniformity : 0.6 : Standby Lighting Grade : NA : Lighting Control : N :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : NR 35 : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion : Sheet vinyl : Heavy duty emulsion
Door sets : Solid core light beech veneer with lever handles and mortice lock with internal thumb turn. 2 x kick plates
Windows (HBN 00‐10 D) : Openable UPVC frame double glazed window with toughened glass (as
existing). Film applied to window
41 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: C/E 6
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. treatment couch
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. Staff alarm point (linked to Eddison system) 1 2. Luminaires to CIBSE LG7 1 3. Luminaires to CIBSE LG7 with integral emergency inverter/battery pack. 1 4. Heating via Radiators LTHW 1 5. Fire alarm combined smoke detector/sounder 1 6. 4 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking 1 7. 2 No. twin socket outlets at 450mm. AFFL 1 8. 2 No. data outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking
with Cat 6e data cabling to patch panel. 1 9. 1 No. telephone outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking 1 10. 1 x No. Clinical basin with elbow taps mounted on full height IPS panel 1 11. Lockable wall cupboard 1 12. Worktop and lockable cupboard and draws underneath 1 13. Natural fresh air supply system 1 14. Desk 2 15. 1 x doctor’s chair 3 16. 1 x patient chair 3 17. Examination couch 3 18. 1 x curtain and track 2 19. 2 x bins 4 20. 1 x computer 4 21. Alcohol gel dispenser 2 22. Paper towel dispenser 2 23. Soap dispenser 2 24. Door stops and hook 1 25. Washable roller blinds to windows 1
42 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC d.b.50% RH. Summer : DESIGN : NOTES ‐4ºC sat. Winter : DATA :
AIR : : Winter Temperature (degC) : 21 +/‐ 2c : Summer Temperature (degC) : 24 +/‐ 2c : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : : Pressure – Rel. to Adj. Space : : Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 500 : Service Illumination Night (Lux) : NA : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 90 : Uniformity : 0.6 : Standby Lighting Grade : NA : Lighting Control : N :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : NR 35 : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion : Sheet vinyl : Heavy duty emulsion
Door sets : Solid core light beech veneer with lever handles and mortice lock with internal thumb turn. 2 x kick plates
Windows (HBN 00‐10 D) : Openable UPVC frame double glazed window with toughened glass (as
existing). Film applied to window
43 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: C/E 7
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. treatment couch
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. Staff alarm point (linked to Eddison system) 1 2. Luminaires to CIBSE LG7 1 3. Luminaires to CIBSE LG7 with integral emergency inverter/battery pack. 1 4. Heating via Radiators LTHW 1 5. Fire alarm combined smoke detector/sounder 1 6. 4 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking 1 7. 2 No. twin socket outlets at 450mm. AFFL 1 8. 2 No. data outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking
with Cat 6e data cabling to patch panel. 1 9. 1 No. telephone outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking 1 10. 1 x No. Clinical basin with elbow taps mounted on full height IPS panel 1 11. Lockable wall cupboard 1 12. Worktop and lockable cupboard and draws underneath 1 13. Natural fresh air supply system 1 14. Desk 2 15. 1 x doctor’s chair 3 16. 1 x patient chair 3 17. Examination couch 3 18. 1 x curtain and track 2 19. 2 x bins 4 20. 1 x computer 4 21. Alcohol gel dispenser 2 22. Paper towel dispenser 2 23. Soap dispenser 2 24. Door stops and hook 1 25. Washable roller blinds to windows 1
44 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC d.b.50% RH. Summer : DESIGN : NOTES ‐4ºC sat. Winter : DATA :
AIR : : Winter Temperature (degC) : 21 +/‐ 2c : Summer Temperature (degC) : 24 +/‐ 2c : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : : Pressure – Rel. to Adj. Space : : Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 500 : Service Illumination Night (Lux) : NA : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 90 : Uniformity : 0.6 : Standby Lighting Grade : NA : Lighting Control : N :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : NR 35 : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion : Sheet vinyl : Heavy duty emulsion
Door sets : Solid core light beech veneer with lever handles and mortice lock with internal thumb turn. 2 x kick plates
Windows (HBN 00‐10 D) : Openable UPVC frame double glazed window with toughened glass (as
existing). Film applied to window
45 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: ADMIN OFFICE
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. bed
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. Luminaires to CIBSE LG7 1 2. Luminaires to CIBSE LG7 with integral emergency inverter/battery pack. 1 3. Patient alarm control panel. 1 4. Staff alarm control panel (Eddison system) 1 5. Heating via Radiators LTHW 1 6. Fire alarm combined smoke detector/sounder 1 7. 12 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking 1 8. 2 No. twin socket outlets at 450mm. AFFL 1 9. 12 No. data outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking with
Cat 6e data cabling to patch panel. 1 10. 6 No. telephone outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking 1 11. Natural fresh air supply system 1 12. 1 No. magnetic door lock and proximity sensor reader and associated power supply for the door
between admin and waiting area 1 13. 6 x computers 4 14. 6 x Desks 1 15. 6 x coat hooks 1 16. 6 x office chairs 3 17. Blinds 2 18. Blind tracks 1 19. Full height storage cabinets 3
46 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC d.b. 50% RH summer : DESIGN : NOTES ‐4ºC sat. winter : DATA :
AIR : : Winter Temperature (degC) : 21 +/‐ 2c : Summer Temperature (degC) : 24 +/‐ 2c : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : : Pressure – Rel. to Adj. Space : : Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 300 ‐ 500 : Service Illumination Night (Lux) : NA : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 80 : Uniformity : 0.6 : Standby Lighting Grade : NA : Lighting Control : N :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : NR 35 : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion : Sheet vinyl : Heavy duty emulsion
Door sets : 2 x Solid core light beech veneer FD30S. 2 x Vision panel per door. Lever handles and mortice lock with internal thumb turn per door. 2 x kick plates per door. 2 x overhead door closers
Windows (HBN 00‐10 D) : Openable UPVC frame double glazed window with toughened glass (as
existing). Film applied to window
47 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: PM OFFICE
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. bed
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. Luminaires to CIBSE LG7 1 2. Luminaire to CIBSE LG7 with integral emergency inverter/battery pack. 1 3. Heating via Radiators LTHW 1 4. Fire alarm combined smoke detector/sounder 1 5. 3 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking 1 6. 2 No. twin socket outlets at 450mm. AFFL 1 7. 3 No. data outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking with
Cat 6e data cabling to patch panel. 1 8. 1 No. telephone outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking 1 9. Natural fresh air supply system 1 10. 1 x computer 4 11. 1 x Desk 1 12. 1 x coat hook 1 13. 1 x office chair 3 14. 2 x visitors chairs 3 15. 2 x filing cabinets 3 16. Blind 2 17. Blind track 1 18. Bookcase 3
48 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC db. 50% RH Summer : DESIGN : NOTES ‐4ºC sat. Winter : DATA :
AIR : : Winter Temperature (degC) : 21 +/‐ 2c : Summer Temperature (degC) : 24 +/‐ 2c : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : : Pressure – Rel. to Adj. Space : : Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 300‐ 500 : Service Illumination Night (Lux) : NA : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 80 : Uniformity : 0.6 : Standby Lighting Grade : NA : Lighting Control : N :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : NR 35 : Speech Privacy Required : : Quality which cannot be tolerated : : SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion : Sheet vinyl : Heavy duty emulsion
Doorsets : Solid core light beech veneer FD30S. 2 x Vision panels. Lever handles and mortice lock with internal thumb turn. 2 x kick plates. Overhead door closer
Windows (HBN 00‐10 D) : Openable UPVC frame double glazed window with toughened glass (as
existing). Film applied to window
49 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: STAFF ROOM
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. bed
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. Luminaires to CIBSE LG7 1 2. Luminaire with integral emergency inverter/battery pack. 1 3. Heating via Radiators LTHW 1 4. Stainless steel sink with drainer with mixer tap 1 5. Sink base unit with drawer 1 6. Kitchen base units with drawers 1 7. Kitchen worktop 1 8. Kitchen wall units 1 9. Fire alarm combined heat detector/sounder 1 10. Natural fresh air supply system 1 11. 3no twin socket outlets above worktop level 1 12. 2 No. twin socket outlets at 450mm. AFFL 1 13. Microwave 4 14. Toaster 4 15. Kettle 4 16. Fridge Freezer 1 17. Table 3 18. 4 x dining chairs 3 19. Large waste bin 4
50 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC db. 50% RH Summer : DESIGN : NOTES ‐4ºC sat. Winter : DATA :
AIR : : Winter Temperature (degC) : 21 +/‐ 2c : Summer Temperature (degC) : 24 +/‐ 2c : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : 0.030 : Pressure – Rel. to Adj. Space : : Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 300 : Service Illumination Night (Lux) : NA : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 80 : Uniformity : 0.6 : Standby Lighting Grade : NA : Lighting Control : N :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : NR 35 : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion Non slip vinyl : Heavy duty emulsion Altro whiterock splasback
Doorsets : Solid core light beech veneer FD30S. 2 x Vision panels. Lever handles and mortice lock with internal thumb turn. 2 x kick plates. Overhead door closer
Windows (HBN 00‐10 D) : Openable UPVC frame double glazed window with toughened glass (as
existing). Film applied to window
51 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
PROJECT: Adams House Medical Centre Date: 4th July 2017
ACTIVITY SPACE DATA SHEET: STAFF WC
Version: 1 Revision:
EQUIPMENT Group 1 Items to be provided and fixed by the builder e.g. sink, coat hook
Group 2 Items supplied by Trust and fixed by builder e.g. soap dispenser
Group 3 Loose equipment taking up significant floor space e.g. bed
Group 4 Small items of loose equipment e.g. computer, waste bin
Group
1. Luminaire to CIBSE LG7 with integral emergency inverter/battery pack. 1 2. Electric Panel heating 1 3. Wash hand basin with percussion outlets served from thermostatic mixing
valve and isolation valves. 1 4. W.C. with air push button flushing cistern. 1 5. Natural fresh air supply system 1 6. 1 coat hook 1 7. toilet magazine dispenser 2 8. soap dispenser 2 9. Unbreakable Mirror300 x 450 1 10. alcohol gel dispenser 2 11. Paper towel dispenser 2 12. bin 4
52 | P a g e A d a m s H o u s e – 0 0 5 5 4 7 – R e v 1
TECHNICAL DATA SHEET
ENVIRONMENTAL 29ºC db. 50% RH Summer : DESIGN : NOTES ‐4ºC sat. Winter : DATA :
AIR : : Winter Temperature (degC) : 18 : Summer Temperature (degC) : Uncontrolled : Mechanical Ventilation: Supply (m3/s) : : Mechanical Ventilation: Extract (m3/s) : 0.015 : Pressure – Rel. to Adj. Space : : Filtration (% Dust Sp Eff & % Arr) : : Humidity (%RH) : :
LIGHTING : : Service Illumination (Lux) : 200 : Service Illumination Night (Lux) : 200 : Local Illumination (Lux) : NA : Colour Rendering Required : Ra 80 : Uniformity : 0.6 : Standby Lighting Grade : NA : Lighting Control : N :
NOISE : : Acceptable Sound Level [ (L10dB (A) ] : NR 35 : Speech Privacy Required : : Quality which cannot be tolerated : :
SAFETY : : Accessible Hot Surface Max temp (C) : 43 : Domestic Hot Water Max temp (C) : 41 :
DESIGN CHARACTER
Internal Finishes : Walls (HBN 00‐10 B) : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B) : Heavy duty emulsion Non slip vinyl Heavy duty emulsion
Altro whiterock splasback
Doorsets : Solid core light beech veneer door. Lever handles with indicator lock with external emergency access. 2 x kick plates
Windows (HBN 00‐10 D) : Openable UPVC frame double glazed window with toughened glass (as
existing). Film applied to window