Five good reasons to appreciate the AEG MCB'sBenefits of the MCB's - Series E90Selection table Series E90N - Miniature circuit breakers 3kASeries E90E - Miniature circuit breakers 4.5kASeries E90 - Miniature circuit breakers 6kASeries E90S - Miniature circuit breakers 10kASeries E90X - Miniature circuit breakers 25kASeries E90S UC - Miniature circuit breakers 6kASeries E880 - Miniature circuit breakers 6kASeries E880S - Miniature circuit breakers 10kASeries S90 - Miniature circuit breakers 25kAAccessoriesTechnical data Short-circuit capacity IEC 60898 standard - Magnetic release - Thermal releaseIEC 60947-2 standard - Magnetic release - Thermal releaseInfluence of ambient temperatureVoltage drop and energy lossCompact UnibisTM MCB'S - Series EC, EPC90, DA41Screwless & plugin FixwellTM MCB'S - Series EC, EP90P, E305P
A.2A.3A.5A.6A.8
A.10A.12A.14A.16A.18A.20A.22A.24A.26A.28A.30
A.31A.31A.33A.53
A.2
A
Five good reasons to appreciate the AEG miniature circuit breakers: Line protection - People protection
1. Total protectionAEG Low Voltage MCB's provide the best answer to the obligation of circuit protection. They give comprehensive protection to circuits against:- Overload currents (0.5A to 125A)- Short-circuit currents (3000 up to 50000 A)- Earth fault currents (30mA up to 1000mA) - combined with RCD's- The handle being sealable or equipped with padlock bracket avoids dangereous
operation changes (ON / OFF)- The handle provides a clear indication of the contact positio- Top and bottom protection caps give save installation facilities- Sealing accessories for top and bottom connections allow protection of original
wiring- Adequate printing of all data on the front provides long-term identifi cation
2. Total quality- The MCB's are able to accomplish the line protection for more than 10.000
times, by a simple manual, or motor operated reset- The quality of the shells can cope with the hardest ambient circumstances
(-25°C to +55°C)- All MCB's are current limiting MCB's, the let-through energy being reduced
far below the standard limits. Energy limiting class: 3- The low let-through peak-currents ensure the long life-time of the contacts
of isolators or loadbreak switches upstream- The emission of ionised gases are limited to the severest restrictions
(35 mm grid distance)
3. A wide rangeAEG Low Voltage offers: - MCB's for household in accordance with: IEC 60898 - B, C and D tripping
characteristics- MCB's for industry in accordance with: IEC 60947-2 - instantaneous tripping
3-5 In, 5-10 In, 10-20 In- MCB's in accordance with: IEC 1009 - BS 4293
4. Stock reducing systemThe residential and industrial markets are covered by five appropriate series of MCB's: Series E.Their external advantages allow the consumer to extend the MCB at any time with: - A wide range of RCD's / people protection- Five types of display contacts- Shunt trip releases- Accessories
5. Time saving connectionsInsulated or non insulated busbar systems with maximum connection possibilities, can be very fast put on the top or bottom terminals of the MCB's.
Min
iatu
re c
ircu
it b
reak
ers
A.3
A
Benefits of the MCB’s Series E90
Safety terminal:
- easy wiring
- no wrong fixing
- protection degree IP20.
Pozidriv and slot screw head.
Torque up to 4.5 N.m.
Incoming/outgoing terminal capacity
up to 35 mm2 or 2 x 16 mm2.
Terminal side for fork busbar is
isolated between the poles.
Two positions of the DIN-rail clip.
Easy installation.
MCB's and RCCB's can be
connected with PIN type busbar at
the top terminals.
MCB's and RCCB's can be connected
with PIN type busbar at the bottom
terminals, with easy DIN-rail
extraction.
MCB's and RCCB's can be connected
with FORK type busbar at the bottom
terminals, with easy DIN-rail extrac-
tion.
Auxiliary contacts can be added on
the left hand side of the MCB.
Series E90
A.4
A
Notes
Min
iatu
re c
ircu
it b
reak
ers
A.5
A
10 10
14 14
20 20 20
Series
E90N
E90E
E90
E90S
E90X
E90S UC
E880
E880S
S90
Poles
1, 2, 3, 4
1, 1+N, 2, 3, 3+N, 4
1, 1+N, 2, 3, 3+N, 4
1, 1+N, 2, 3, 3+N, 4
1, 2, 3, 4
1, 2
1, 2, 3, 4
1, 2, 3, 4
1, 3x1, 3, 1+N, 3+N
1, 3x1
1, 3x1
Add-on devices
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
(1)
(1)
(1)
Pageno.
A.6
A.8
A.10
A.12
A.14
A.16
A.18
A.20
A.22
Applications Trippingcharac-teristic
B
C
B
C
B
C
D
B
C
D
B
C
D
B
C
B
C
D
B
C
D
Cs
E
F
Ratingcurrent
(A)
6-40
2-40
6-40
2-40
6-63
0.5-63
0.5-63
6-63
0.5-63
0.5-63
6-63
0.5-63
0.5-63
6-63
0.5-63
80-125
80-125
80-125
80-125
80-125
80-125
10-100
10-100
10-100
Selection table MCB’s
IEC 60898
IEC 60947-2
NEMA AB1
domestic
commercial
industrial
(1) on requestCompact MCB's e.g. 1+1N (1 mod.), see Series EC91…NR, page A.36 - A.38
B : 3-5 In
C : 5-10 In
D : 10-20 In
30 30
30
Short-circuit capacity(kA)
3 5
3 5
4.5 6
4.5 6
6 10
6 10
6 10
10 15
10 15
10 15
15 20 25
15 20 25
15 20 25
6 10
6 10
6 10
6 10
6 10
10 15
10 15
10 15
25
25
25
MC
B's
A.6
Min
iatu
re c
ircu
it b
reak
ers
A
Applications
Approval/Marking
Series E90N
Performances
Short-circuit capacity
Acc. to EN/IEC 60898 Poles V Icn/Ics (kA) 1-4 230/400 3
AC acc. to EN/IEC 60947-2 Poles V Icu (kA) 1 240 5 2 127 - 240 10 415 5 3, 4 240 10 415 5
DIN VDE 0641 3kAEN/IEC 60898
EN/IEC 60947-2 5kA
AccessoriesBusbars
Dimensions
Miniature circuit breakers
Thermal setting In
Rated voltage AC Un
Minimum operating voltage UB min
Tripping characteristics
Selectivity class
Mechanical/electrical endurance
Tropicalisation acc.to IEC 60068-2
Terminal capacity flexible/rigid cable
Poles
Weight
Thermal operating limit
Magnetic operating
(A) 2-40
(V) 240/415
(V) 12
B-C
3
20000/10000
95%RH at 55°C
(mm2) 25-35
1, 2, 3, 4
(g/pole) 120
(1.13 - 1.45) x In
B: (3 - 5) x In
C: (5 - 10) x In
pg A.25chapter-cpg A.7
pg B.15pg A.24pg A.24pg A.24pg A.24
Add-on RCDAuxiliary contacts
Shunt tripUndervoltage release
Motor operator
Add-on devices
Add-on RCD
Auxiliaries
Motor operator
30003
A.7
A
Pole width
18mm
18mm
18mm
18mm
Ratedcurrent [A]
246101620253240
246101620253240
246101620253240
246101620253240
Cat. No.
––
E91N B06E91N B10E91N B16E91N B20E91N B25E91N B32E91N B40
––
E92N B06E92N B10E92N B16E92N B20E92N B25E92N B32E92N B40
––
E93N B06E93N B10E93N B16E93N B20E93N B25E93N B32E93N B40
––
E94N B06E94N B10E94N B16E94N B20E94N B25E94N B32E94N B40
Ref. No.
––
552405552407552409552410552411552412552413
––
552421552423552425552426552427552428552429
––
552437552439552441552442552443552444552445
––
552453552455552457552458552459552460552461
Cat. No.
E91N C02E91N C04E91N C06E91N C10E91N C16E91N C20E91N C25E91N C32E91N C40
E92N C02E92N C04E92N C06E92N C10E92N C16E92N C20E92N C25E92N C32E92N C40
E93N C02E93N C04E93N C06E93N C10E93N C16E93N C20E93N C25E93N C32E93N C40
E94N C02E94N C04E94N C06E94N C10E94N C16E94N C20E94N C25E94N C32E94N C40
Ref. No.
552466552468552469552471552473552474552475552476552477
552482552484552485552487552489552490552491552492552493
552498552500552501552503552505552506552507552508552509
552514552516552517552519552521552522552523552524552525
Pack.
121212121212121212
666666666
444444444
333333333
B C
Series E90N - 3kA - AC MCB's
1P1 mod.
2P2 mod.
3P3 mod.
4P4 mod.
Dimensions - Series E90N, E90E, E90, E90S, E90X
Series E90N
A.8
Min
iatu
re c
ircu
it b
reak
ers
A
AccessoriesBusbars
Dimensions
pg A.25chapter Cpg A.7
pg B.15pg A.24pg A.24pg A.24pg A.24
Add-on RCDAuxiliary contacts
Shunt tripUndervoltage release
Motor operator
Applications
Approval/Marking
Series E90E
Performances
Short-circuit capacity
AC acc. to EN/IEC 60898 Poles V Icn/Ics (kA) 1-4 230/400 4.5
AC acc. to EN/IEC 60947-2 Poles V Icu (kA) 1 240 6 2 127 15 240 10 415 6 3, 4 240 10 415 6
DIN VDE 0641 4.5kAEN/IEC 60898
EN/IEC 60947-2 6kA
Miniature circuit breakers
Thermal setting In
Rated voltage AC Un
Minimum operating voltage UB min
Tripping characteristics
Selectivity class
Mechanical/electrical endurance
Tropicalisation acc.to IEC 60068-2
Terminal capacity flexible/rigid cable
Poles
Weight
Thermal operating limit
Magnetic operating
(A) 2-40
(V) 240/415
(V) 12
B-C
3
20000/10000
95%RH at 55°C
(mm2) 25-35
1, 1+N, 2, 3, 3+N, 4
(g/pole) 120
(1.13 - 1.45) x In
B: (3 - 5) x In
C: (5 - 10) x In
Add-on devices
Add-on RCD
Auxiliaries
Motor operator
45003
A.9
A
Series E90E
Pole width
18mm
18mm
18mm
18mm
18mm
18mm
Ratedcurrent [A]
246101620253240
246101620253240
246101620253240
246101620253240
24610131620253240
24610131620253240
Cat. No.
––
E91E B06E91E B10E91E B16E91E B20E91E B25E91E B32E91E B40
––
E92E B06E92E B10E92E B16E92E B20E92E B25E92E B32E92E B40
––
E93E B06E93E B10E93E B16E93E B20E93E B25E93E B32E93E B40
––
E94E B06E94E B10E94E B16E94E B20E94E B25E94E B32E94E B40
––
E91E B06 NE91E B10 NE91E B13 NE91E B16 NE91E B20 NE91E B25 NE91E B32 NE91E B40 N
––
E93E B06 NE93E B10 NE93E B13 NE93E B16 NE93E B20 NE93E B25 NE93E B32 NE93E B40 N
Ref. No.
––
552533552535552537552538552539552540552541
––
552549552551552553552554552555552556552557
––
552565552567552569552570552571552572552573
––
552581552583552585552586552587552588552589
––
552592552593552594552595552596552597552598552599
––
552600552601552602552603552604552605552606552607
Cat. No.
E91E C02E91E C04E91E C06E91E C10E91E C16E91E C20E91E C25E91E C32E91E C40
E92E C02E92E C04E92E C06E92E C10E92E C16E92E C20E92E C25E92E C32E92E C40
E93E C02E93E C04E93E C06E93E C10E93E C16E93E C20E93E C25E93E C32E93E C40
E94E C02E94E C04E94E C06E94E C10E94E C16E94E C20E94E C25E94E C32E94E C40
E91E C02 NE91E C04 NE91E C06 NE91E C10 NE91E C13 NE91E C16 NE91E C20 NE91E C25 NE91E C32 NE91E C40 N
E93E C02 NE93E C04 NE93E C06 NE93E C10 NE93E C13 NE93E C16 NE93E C20 NE93E C25 NE93E C32 NE93E C40 N
Ref. No.
552610552612552613552615552617552618552619552620552621
552626552628552629552631552633552634552635552636552637
552642552644552645552647552649552650552651552652552653
552658552660552661552663552665552666552667552668552669
552672552673552674552675552676552677552678552679552680552681
552682552683552684552685552686552687552688552689552690552691
Pack.
121212121212121212
666666666
444444444
333333333
6666666666
3333333333
Series E90E - 4.5kA - AC MCB's
1P1 mod.
2P2 mod.
3P3 mod.
4P4 mod.
1P+N2 mod.
3P+N4mod.
N
N
B C
A.10
Min
iatu
re c
ircu
it b
reak
ers
A
AccessoriesBusbars
Dimensions
pg A.25chapter Cpg A.7
pg B.15pg A.24pg A.24pg A.24pg A.24
Add-on RCDAuxiliary contacts
Shunt tripUndervoltage release
Motor operator
Applications
Approval/Marking
Series E90
Performances
Short-circuit capacity
AC acc. to EN/IEC 60898 Poles V Icn/Ics (kA) 1-4 230/400 6
AC acc. to EN/IEC 60947-2 Poles V Icu (kA)(1)
1 240 10 1+N.2 127 30 240 20 2 415 10 3, 4 240 20 415 10 (1) Ics = 75% Icu
DC acc. to EN/IEC 60947-2(2)
Poles V Icu/Ics (kA) 1 60 20 2 125 25
DIN VDE 0641 6kAEN/IEC 60898
EN/IEC 60947-2 10kA
Miniature circuit breakers
Thermal setting In
Rated voltage AC Un
Minimum operating voltage UB min
Tripping characteristics
Selectivity class
Mechanical/electrical endurance
Tropicalisation acc.to IEC 60068-2
Terminal capacity flexible/rigid cable
Poles
Weight
Thermal operating limit
Magnetic operating
(A) 0.5-63
(V) 240/415
(V) 12
B-C-D
3
20000/10000
95%RH at 55°C
(mm2) 25-35
1, 1+N, 2, 3, 3+N, 4
(g/pole) 120
(1.13 - 1.45) x In
B: (3 - 5) x In
C: (5 - 10) x In
D: (10 - 20) x In
Add-on devices
Add-on RCD
Auxiliaries
Motor operator
60003
(2) Nominal and maximum VDC in page A.26-A.29
A.11
A
Series E90
Pole width
18mm
18mm
18mm
18mm
18mm
18mm
Ratedcurrent [A]
0.5123461013162025324050630.5123461013162025324050630.5123461013162025324050630.5123461013162025324050630.5123461013162025324050630.512346101316202532405063
Cat. No.
-----
E91 B06E91 B10E91 B13E91 B16E91 B20E91 B25E91 B32E91 B40E91 B50E91 B63
-----
E92 B06E92 B10E92 B13E92 B16E92 B20E92 B25E92 B32E92 B40E92 B50E92 B63
-----
E93 B06E93 B10E93 B13E93 B16E93 B20E93 B25E93 B32E93 B40E93 B50E93 B63
-----
E94 B06E94 B10E94 B13E94 B16E94 B20E94 B25E94 B32E94 B40E94 B50E94 B63
-----
E91 B06 NE91 B10 NE91 B13 NE91 B16 NE91 B20 NE91 B25 NE91 B32 NE91 B40 NE91 B50 NE91 B63 N
-----
E93 B06 NE93 B10 NE93 B13 NE93 B16 NE93 B20 NE93 B25 NE93 B32 NE93 B40 NE93 B50 NE93 B63 N
Ref. No.
-----
552697552699552700552701552702552703552704552705552706552707
552732552734552735552736552737552738552739552740552741552742
-----
552751552753552754552755552756552757552758552759552760552761
-----
552770552772552773552774552775552776552777552778552779552780
–––––
552716552718552719552720552721552722552723552724552725552726
-----
681181681183681184681185681186681187681188681189681190681191
Cat. No.
E91 C0.5E91 C01E91 C02E91 C03E91 C04E91 C06E91 C10E91 C13E91 C16E91 C20E91 C25E91 C32E91 C40E91 C50E91 C63E92 C0.5E92 C01E92 C02E92 C03E92 C04E92 C06E92 C10E92 C13E92 C16E92 C20E92 C25E92 C32E92 C40E92 C50E92 C63E93 C0.5E93 C01E93 C02E93 C03E93 C04E93 C06E93 C10E93 C13E93 C16E93 C20E93 C25E93 C32E93 C40E93 C50E93 C63E94 C0.5 E94 C01 E94 C02 E94 C03 E94 C04 E94 C06 E94 C10 E94 C13 E94 C16 E94 C20 E94 C25 E94 C32 E94 C40 E94 C50E94 C63
E91 C0.5 NE91 C01 NE91 C02 NE91 C03 NE91 C04 NE91 C06 NE91 C10 NE91 C13 NE91 C16 NE91 C20 NE91 C25 NE91 C32 NE91 C40 NE91 C50 NE91 C63 NE93 C0.5 NE93 C01 NE93 C02 NE93 C03 NE93 C04 NE93 C06 NE93 C10 NE93 C13 NE93 C16 NE93 C20 NE93 C25 NE93 C32 NE93 C40 NE93 C50 NE93 C63 N
Ref. No.
552784552785552786552787552788552789552791552792552793552794552795552796552797552798552799552819552820552821552822552823552824552826552827552828552829552830552831552832552833552834552838552839552840552841552842552843552845552846552847552848552849552850552851552852552853552857552858552859552860552861552862552864552865552866552867552868552869552870552871552872552803552804552805552806552807552808552810552811552812552813552814552815552816552817552818681192681193681194681195681196681197681199681200681201681202681203681204681205681206681207
Pack.
121212121212121212121212121212666666666666666444444444444444333333333333333666666666666666333333333333333
Cat. No.
E91 D0.5E91 D01E91 D02E91 D03E91 D04E91 D06E91 D10E91 D13E91 D16E91 D20E91 D25E91 D32E91 D40E91 D50E91 D63E92 D0.5E92 D01E92 D02E92 D03E92 D04E92 D06E92 D10E92 D13E92 D16E92 D20E92 D25E92 D32E92 D40E92 D50E92 D63E93 D0.5E93 D01E93 D02E93 D03E93 D04E93 D06E93 D10E93 D13E93 D16E93 D20E93 D25E93 D32E93 D40E93 D50E93 D63E94 D05E94 D01E94 D02 E94 D03 E94 D04 E94 D06 E94 D10 E94 D13 E94 D16 E94 D20 E94 D25 E94 D32 E94 D40 E94 D50 E94 D63
E91 D0.5 NE91 D01 NE91 D02 NE91 D03 NE91 D04 NE91 D06 NE91 D10 NE91 D13 NE91 D16 NE91 D20 NE91 D25 NE91 D32 NE91 D40 NE91 D50 NE91 D63 NE93 D0.5 NE93 D01 NE93 D02 NE93 D03 NE93 D04 NE93 D06 NE93 D10 NE93 D13 NE93 D16 NE93 D20 NE93 D25 NE93 D32 NE93 D40 NE93 D50 NE93 D63 N
Ref. No.
552876552877552878552879552880552881552883552884552885552886552887552888552889552890552891552911552912552913552914552915552916552918552919552920552921552922552923552924552925552926552930552931552932552933552934552935552937552938552939552940552941552942552943552944552945552949552950552951552952552953552954552956552957552958552959552960552961552962552963552964552895552896552897552898552899552900552902552903552904552905552906552907552908552909552910681208681209681210681211681212681213681215681216681217681218681219681220681221681222681223
Series E90 - 6kA - AC MCB's
1P1 mod.
2P2 mod.
3P3 mod.
4P4 mod.
1P+N2 mod.
3P+N4 mod.
N
N
B C D
A.12
Min
iatu
re c
ircu
it b
reak
ers
A
Applications
Approval/Marking
Series E90S
Performances
Short-circuit capacity
AC acc. to EN/IEC 60898 Poles V Icn (kA)(1)
1-4 230/400 10 (1) Ics = 75% Icn
AC acc. to EN/IEC 60947-2 Poles V Icu (kA)(1)
1 240 15 1+N.2 127 40 240 30 2 415 15 3, 4 240 30 415 15 (1) Ics = 50% Icu
DC acc. to EN/IEC 60947-2(2)
Poles V Icu/Ics (kA) 1 60 25 2 125 30
DIN VDE 0641 10kAEN/IEC 60898
EN/IEC 60947-2 15kA
Miniature circuit breakers
Thermal setting In
Rated voltage AC Un
Minimum operating voltage UB min
Tripping characteristics
Selectivity class
Mechanical/electrical endurance
Tropicalisation acc.to IEC 60068-2
Terminal capacity flexible/rigid cable
Poles
Weight
Thermal operating limit
Magnetic operating
(A) 0.5-63
(V) 240/415
(V) 12
B-C-D
3
20000/10000
95%RH at 55°C
(mm2) 25-35
1, 1+N, 2, 3, 3+N, 4
(g/pole) 120
(1.13 - 1.45) x In
B: (3 - 5) x In
C: (5 - 10) x In
D: (10 - 20) x In
100003
(2) Nominal and maximum VDC in page A.26-A.29
AccessoriesBusbars
Dimensions
pg A.25chapter Cpg A.7
pg B.15pg A.24pg A.24pg A.24pg A.24
Add-on RCDAuxiliary contacts
Shunt tripUndervoltage release
Motor operator
Add-on devices
Add-on RCD
Auxiliaries
Motor operator
A.13
A
Series E90S
Pole width
18mm
18mm
18mm
18mm
18mm
18mm
Ratedcurrent [A]
0.512346101316202532405063
0.512346101316202532405063
0.512346101316202532405063
0.512346101316202532405063
0.512346101316202532405063
0.512346101316202532405063
Cat. No.
–––––
E91S B06E91S B10E91S B13E91S B16E91S B20E91S B25E91S B32E91S B40E91S B50E91S B63
–––––
E92S B06E92S B10E92S B13E92S B16E92S B20E92S B25E92S B32E92S B40E92S B50E92S B63
–––––
E93S B06E93S B10E93S B13E93S B16E93S B20E93S B25E93S B32E93S B40E93S B50E93S B63
–––––
E94S B06 E94S B10 E94S B13 E94S B16 E94S B20 E94S B25 E94S B32 E94S B40 E94S B50 E94S B63
–––––
E91S B06 NE91S B10 NE91S B13 NE91S B16 NE91S B20 NE91S B25 NE91S B32 NE91S B40 NE91S B50 NE91S B63 N
–––––
E93S B06 NE93S B10 NE93S B13 NE93S B16 NE93S B20 NE93S B25 NE93S B32 NE93S B40 NE93S B50 NE93S B63 N
Ref. No.
–––––
552973552975552976552977552978552979552980552981552982552983
–––––
552992552994552995552996552997552998552999553000553001553002
–––––
553011553013553014553015553016553017553018553019553020553021
–––––
553030553032553033553034553035553036553037553038553039553040
–––––
681053681055681056681057681058681059681060681061681062681063
–––––
681133681135681136681137681138681139681140681141681142681143
Cat. No.
E91S C0.5E91S C01E91S C02E91S C03E91S C04E91S C06E91S C10E91S C13E91S C16E91S C20E91S C25E91S C32E91S C40E91S C50E91S C63
E92S C0.5E92S C01E92S C02E92S C03E92S C04E92S C06E92S C10E92S C13E92S C16E92S C20E92S C25E92S C32E92S C40E92S C50E92S C63
E93S C0.5E93S C01E93S C02E93S C03E93S C04E93S C06E93S C10E93S C13E93S C16E93S C20E93S C25E93S C32E93S C40E93S C50E93S C63
E94S C0.5 E94S C01 E94S C02 E94S C03 E94S C04 E94S C06 E94S C10 E94S C13 E94S C16 E94S C20 E94S C25 E94S C32 E94S C40 E94S C50E94S C63
E91S C0.5 NE91S C01 NE91S C02 NE91S C03 NE91S C04 NE91S C06 NE91S C10 NE91S C13 NE91S C16 NE91S C20 NE91S C25 NE91S C32 NE91S C40 NE91S C50 NE91S C63 N
E93S C0.5 NE93S C01 NE93S C02 NE93S C03 NE93S C04 NE93S C06 NE93S C10 NE93S C13 NE93S C16 NE93S C20 NE93S C25 NE93S C32 NE93S C40 NE93S C50 NE93S C63 N
Ref. No.
553044553045553046553047553048553049553051553052553053553054553055553056553057553058553059
553063553064553065553066553067553068553070553071553072553073553074553075553076553077553078
553082553083553084553085553086553087553089553090553091553092553093553094553095553096553097
553101553102553103553104553105553106553108553109553110553111553112553113553114553115553116
681064681065681066681067681068681069681071681072681073681074681075681076681077681078681079
681144681145681146681147681148681149681151681152681153681154681155681156681157681158681159
Pack.
121212121212121212121212121212
666666666666666
444444444444444
333333333333333
666666666666666
333333333333333
B CCat. No.
E91S D0.5E91S D01E91S D02E91S D03E91S D04E91S D06E91S D10E91S D13E91S D16E91S D20E91S D25E91S D32E91S D40E91S D50E91S D63
E92S D0.5E92S D01E92S D02E92S D03E92S D04E92S D06E92S D10E92S D13E92S D16E92S D20E92S D25E92S D32E92S D40E92S D50E92S D63
E93S D0.5E93S D01E93S D02E93S D03E93S D04E93S D06E93S D10E93S D13E93S D16E93S D20E93S D25E93S D32E93S D40E93S D50E93S D63
–E94S D01 E94S D02 E94S D03 E94S D04 E94S D06 E94S D10 E94S D13 E94S D16 E94S D20 E94S D25 E94S D32 E94S D40 E94S D50 E94S D63
E91S D0.5 NE91S D01 NE91S D02 NE91S D03 NE91S D04 NE91S D06 NE91S D10 NE91S D13 NE91S D16 NE91S D20 NE91S D25 NE91S D32 NE91S D40 NE91S D50 NE91S D63 N
E93S D0.5 NE93S D01 NE93S D02 NE93S D03 NE93S D04 NE93S D06 NE93S D10 NE93S D13 NE93S D16 NE93S D20 NE93S D25 NE93S D32 NE93S D40 NE93S D50 NE93S D63 N
Ref. No.
553120553121553122553123553124553125553127553128553129553130553131553132553132553134553135
553139553140553141553142553143553144553146553147553148553149553150553151553152553153553154
553158553159553160553161553162553163553165553166553167553168553169553170553171553172553173
–553178553179553180553181553182553184553185553186553187553188553189553190553191553192
681080681081681082681083681084681085681087681088681089681090681091681092681093681094681095
681160681161681162681163681164681165681167681168681169681170681171681172681173681174681175
D
Series E90S - 10kA - AC MCB's
1P1 mod.
2P2 mod.
3P3 mod.
4P4 mod.
1P+N2 mod.
3P+N4 mod.
N
N
A.14
Min
iatu
re c
ircu
it b
reak
ers
A
Applications
Marking
Series E90X
Performances
Short-circuit capacity
Acc. to EN/IEC 60947-2 In(A) Poles V Icu (kA)(1)
0.5-4 1 240 100 2-4 415 100 6-25 1 240 25 2-4 240 50 415 25 32-40 1 240 20 2-4 240 40 415 20 50-63 1 240 15 2-4 240 30 415 15 (1) Ics = 50% Icu
DC acc. to EN/IEC 60947-2(2)
Poles V Icu/Ics (kA) 1 60 20 2 125 25
EN/IEC 60947-2 100kA25kA20kA15kA
Miniature circuit breakers
Thermal setting In
Rated voltage AC Un
Minimum operating voltage UB min
Tripping characteristics
Selectivity class
Mechanical/electrical endurance
Tropicalisation acc.to IEC 60068-2
Terminal capacity flexible/rigid cable
Poles
Weight
Thermal operating limit
Magnetic operating
(A) 0.5-63
(V) 240/415
(V) 12
(3 - 5) In (B)
(5 - 10) In (C)
(10 - 20) In (D)
3
20000/10000
95%RH at 55°C
(mm2) 25-35
1.2.3.4
(g/pole) 120
(1.05 - 1.30) x In
(3 - 5) In (B)
(5 - 10) In (C)
(10 - 20) In (D)
AccessoriesBusbars
Dimensions
pg A.25chapter Cpg A.7
pg B.15pg A.24pg A.24pg A.24pg A.24
Add-on RCDAuxiliary contacts
Shunt tripUndervoltage release
Motor operator
Add-on devices
Add-on RCD
Auxiliaries
Motor operator
(2) Nominal and maximum VDC in page A.26-A.29
A.15
A
Series E90X
Pole width
18mm
18mm
18mm
18mm
Ratedcurrent [A]
0.512346101316202532405063
0.512346101316202532405063
0.512346101316202532405063
0.512346101316202532405063
Cat. No.
–––––
E91X B06E91X B10E91X B13E91X B16E91X B20E91X B25E91X B32E91X B40E91X B50E91X B63
–––––
E92X B06E92X B10E92X B13E92X B16E92X B20E92X B25E92X B32E92X B40E92X B50E92X B63
–––––
E93X B06E93X B10E93X B13E93X B16E93X B20E93X B25E93X B32E93X B40E93X B50E93X B63
– – – – –
E94X B06 E94X B10 E94X B13 E94X B16 E94X B20 E94X B25 E94X B32 E94X B40 E94X B50 E94X B63
Ref. No.
–––––
553341553343553344553345553346553347553348553349553350553351
–––––
553357553359553360553361553362553363553364553365553366553367
–––––
553373553375553376553377553378553379553380553381553382553383
–––––
553389553391553392553393553394553395553396553397553398553399
Cat. No.
E91X C0.5E91X C01E91X C02E91X C03E91X C04E91X C06E91X C10E91X C13E91X C16E91X C20E91X C25E91X C32E91X C40E91X C50E91X C63
E92X C0.5E92X C01E92X C02E92X C03E92X C04E92X C06E92X C10E92X C13E92X C16E92X C20E92X C25E92X C32E92X C40E92X C50E92X C63
E93X C0.5E93X C01E93X C02E93X C03E93X C04E93X C06E93X C10E93X C13E93X C16E93X C20E93X C25E93X C32E93X C40E93X C50E93X C63
E94X C0.5 E94X C01 E94X C02 E94X C03 E94X C04 E94X C06 E94X C10 E94X C13 E94X C16 E94X C20 E94X C25 E94X C32 E94X C40 E94X C50 E94X C63
Ref. No.
553400553401553402553403553404553405553407553408553409553410553411553412553413553414553415
553416553417553418553419553420553421553423553424553425553426553427553428553429553430553431
553432553433553434553435553436553437553439553440553441553442553443553444553445553446553447
553448553449553450553451553452553453553455553456553457553458553459553460553461553462553463
Pack.
121212121212121212121212121212
666666666666666
444444444444444
333333333333333
B CCat. No.
E91X D0.5E91X D01E91X D02E91X D03E91X D04E91X D06E91X D10E91X D13E91X D16E91X D20E91X D25E91X D32E91X D40E91X D50E91X D63
E92X D0.5E92X D01E92X D02E92X D03E92X D04E92X D06E92X D10E92X D13E92X D16E92X D20E92X D25E92X D32E92X D40E92X D50E92X D63
E93X D0.5E93X D01E93X D02E93X D03E93X D04E93X D06E93X D10E93X D13E93X D16E93X D20E93X D25E93X D32E93X D40E93X D50E93X D63
E94X D0.5 E94X D01 E94X D02 E94X D03 E94X D04 E94X D06 E94X D10 E94X D13 E94X D16 E94X D20 E94X D25E94X D32 E94X D40E94X D50E94X D63
Ref. No.
553464553465553466553467553468553469553471553472553473553474553475553476553477553478553479
553480553481553482553483553484553485553487553488553489553490553491553492553493553494553495
553496553497553498553499553500553501553503553504553505553506553507553508553509553510553511
553512553513553514553515553516553517553519553520553521553522553523553524553525553526553527
D
Series E90X - 25kA - AC MCB's(1)
1P1 mod.
2P2 mod.
3P3 mod.
4P4 mod.
(1) 1P, 240V: In ≤ 4 Icu = 100kA 4A < In ≤ 25A Icu = 25kA 25A < In ≤ 40A Icu = 20kA 40A < In ≤ 63A Icu = 15kA
A.16
Min
iatu
re c
ircu
it b
reak
ers
A
Applications
Standard/Marking
EN/IEC 60898-2
DIN VDE 0641
Series E90S UC
Performances
Short-circuit capacity
AC/DC acc. to IEC 60898-2(4)
Poles V Icn=Ics (kA)(1)
1 125 DC 10 220 DC 6 230/400 AC 6 2 250 DC 10 440 DC 6 400 AC 6
AC/DC acc. to IEC 60947-2 Poles V Icu (kA) 1 220 DC 10(2)
2 440 DC 10(2)
1 230 AC 6(3)
1 440 AC 6(3)
(1) Polarity labeling to be respected due to the permanent magnet in the MCB(2) T = 4ms(3) 4.5kA for 50A & 63A(4) After a switching of the net with more than 6kA in AC, is use in DC impossible
Miniature circuit breakers
Thermal setting In
Rated voltage AC Un
Minimum operating voltage UB min
Tripping characteristics
Mechanical/electrical endurance
Tropicalisation acc.to IEC 60068-2
Terminal capacity flexible/rigid cable
Poles(1)
Weight
Thermal operating limit
Magnetic operating
(A) 0.5-63
(V) 230/400
220/440
(V) 12
12
B-C
20000/10000
95%RH at 55°C
(mm2) 25-35
1.2
(g/pole) 125
(1.13 - 1.45) x In
B: (3 - 5) x In
C: (5 - 10) x In
AccessoriesBusbars
Dimensions
pg A.25chapter Cpg A.17
pg B.15pg A.24pg A.24pg A.24pg A.24
Add-on RCDAuxiliary contacts
Shunt tripUndervoltage release
Motor operator
Add-on devices
Add-on RCD
Auxiliaries
Motor operator
EN/IEC 60898 DIN VDE 0641
EN/IEC 60947-2 10kA
6000 T15
A.17
A
Series E90S
UC
Pole width Rated
current [A]
0.5123468101316202532405063
0.5123468101316202532405063
Cat. No.
–––––
E91S UC B06E91S UC B08E91S UC B10E91S UC B13E91S UC B16E91S UC B20E91S UC B25E91S UC B32E91S UC B40E91S UC B50E91S UC B63
–––––
E92S UC B06E92S UC B08E92S UC B10E92S UC B13E92S UC B16E92S UC B20E92S UC B25E92S UC B32E92S UC B40E92S UC B50E92S UC B63
Ref. No.
–––––
553271553272553273553274553275553276553277553278553279553280553281
–––––
553290553291553292553293553294553295553296553297553298553299553300
Cat. No.
E91S UC C0.5E91S UC C01E91S UC C02E91S UC C03E91S UC C04E91S UC C06E91S UC C08E91S UC C10E91S UC C13E91S UC C16E91S UC C20E91S UC C25E91S UC C32E91S UC C40E91S UC C50E91S UC C63
E92S UC C0.5E92S UC C01E92S UC C02E92S UC C03E92S UC C04E92S UC C06E92S UC C08E92S UC C10E92S UC C13E92S UC C16E92S UC C20E92S UC C25E92S UC C32E92S UC C40E92S UC C50E92S UC C63
Ref. No.
553304553305553306553307553308553309553310553311553312553313553314553315553316553317553318553319
553320553321553322553323553324553325553326553327553328553329553330553331553332553333553334553335
B C
Series E90S UC - 6kA - AC/DC MCB's
1P1 mod.
2P2 mod.
Pack.
12121212121212121212121212121212
6666666666666666
Dimensions - Series E90S UC
A.18
Min
iatu
re c
ircu
it b
reak
ers
A
Applications
Standard/Marking
EN/IEC 609047-2
Add-on devices
Add-on RCD
Auxiliaries
Series E880 (80, 100, 125A)
Performances
Short-circuit capacity
Acc. to EN/IEC 60947-2 Poles V Icu (kA) 1 230/400 6 2 230 10 3, 4 230 10 400 6
EN/IEC 60947-2 6kA
Miniature circuit breakers
Thermal setting In
Rated voltage AC Un
Tripping characteristicsMechanical/electrical enduranceOperating temperature
Terminal capacity flexible/rigid cable
Poles
Weight
Thermal operating limit
Magnetic operating
(A) 80-100-125
(V) 240/415
B-C-D
10000/4000
(°C) -25 up to 55
(mm2) 70
1.2.3.4
(g/pole) 210
(1.13 - 1.45) x In
B: (3 - 5) x In
C: (5 - 10) x In
D: (10 - 20) x In
Dimensions pg A.19
pg B.15pg A.24pg A.24pg A.24
Add-on RCDAuxiliary contacts
Shunt tripUndervoltage release
A.19
A
Series E880
Pole width
27mm
27mm
27mm
27mm
Ratedcurrent [A]
80100125
80100125
80100125
80100125
Cat. No.
E881 B080E881 B100E881 B125
E882 B080E882 B100E882 B125
E883 B080E883 B100E883 B125
E884 B080E884 B100E884 B125
Ref. No.
676600676601676602
676603676604676605
676606676607676608
676609676610676611
Cat. No.
E881 C080E881 C100E881 C125
E882 C080E882 C100E882 C125
E883 C080E883 C100E883 C125
E884 C080E884 C100E884 C125
Ref. No.
676612676613676614
676615676616676617
676618676619676620
676621676622676623
Pack.
811
411
111
111
B CCat. No.
E881 D080E881 D100E881 D125
E882 D080E882 D100E882 D125
E883 D080E883 D100E883 D125
E884 D080E884 D100E884 D125
Ref. No.
676624676625676626
676627676628676629
676630676631676632
676633676634676635
D
Series E880 - 6kA - AC MCB's
1P1.5 mod.
2P3 mod.
3P4.5 mod.
4P6 mod.
Dimensions - Series E880, E880S
54 81 108
79
58
44
9445
73
27
A.20
Min
iatu
re c
ircu
it b
reak
ers
A
Applications
Standard/Marking
EN/IEC 609047-2
Add-on devices
Add-on RCD
Auxiliaries
Series E880S (80, 100, 125A)
Performances
Short-circuit capacity
Acc. to EN/IEC 60947-2 (B-C) Poles V Icu (kA)(1)
1 230 10(2)
2 230 15(3)
3, 4 230 15(3)
400 10(2)
(1) Only for B and C(2) 7.5kA for D(3) 10kA for D
EN/IEC 60947-2 10kA
Miniature circuit breakers
Thermal setting In
Rated voltage AC Un
Tripping characteristics
Mechanical/electrical endurance
Operating temperature
Terminal capacity flexible/rigid cable
Poles
Weight
Thermal operating limit
Magnetic operating
(A) 80-100-125
(V) 240/415
B-C-D
10000/4000
(°C) -25 up to 55
(mm2) 70
1, 2, 3, 4
(g/pole) 210
(1.13 - 1.45) x In
B: (3 - 5) x In
C: (5 - 10) x In
D: (10 - 20) x In
Dimensions pg A.19
pg B.15pg A.24pg A.24pg A.24
Add-on RCDAuxiliary contacts
Shunt tripUndervoltage release
A.21
A
Series E880S
Pole width
27mm
27mm
27mm
27mm
Ratedcurrent [A]
80100125
80100125
80100125
80100125
Cat. No.
E881S B080E881S B100E881S B125
E882S B080E882S B100E882S B125
E883S B080E883S B100E883S B125
E884S B080E884S B100E884S B125
Ref. No.
676636676637676638
676639676640676641
676642676643676644
676645676646676647
Cat. No.
E881S C080E881S C100E881S C125
E882S C080E882S C100E882S C125
E883S C080E883S C100E883S C125
E884S C080E884S C100E884S C125
Ref. No.
676648676649676650
676651676652676653
676654676655676656
676657676658676659
Pack.
888
444
222
222
B CCat. No.
E881S D080E881S D100E881S D125
E882S D080E882S D100E882S D125
E883S D080E883S D100E883S D125
E884S D080E884S D100E884S D125
Ref. No.
676660676661676662
676663676664676665
676666676667676668
676669676670676671
D(1)
Series E880S - 10kA - AC MCB's
1P1.5 mod.
2P3 mod.
3P4.5 mod.
4P6 mod.
(1) Rated breaking capacity see footnotes (2) and (3) on page A.20
A.22
Min
iatu
re c
ircu
it b
reak
ers
A
Applications
Marking
Series S90
Performances
Short-circuit capacity
AC/DC acc. to EN/IEC 60898 Poles V Icn (kA) 1, 3, 3+N 230/400 25
Miniature circuit breakers
Thermal setting In
Rated voltage AC Un
Minimum operating voltage AC UB min
Tripping characteristics
Selectivity class
Electrical endurance
Tropicalisation acc.to IEC 60068-2
Terminal capacity
Poles
Weight
Thermal operating limit
Magnetic operating
(A) 10-100
(V) 230/400
(V) 207
E, F, Cs
3
4000
95%RH at 55°C
(mm2) 2.5-50 (1.5-35)
1, 1+N, 3, 3+N, 3x1
(g/pole) 350
Cs: (1.13 - 1.45) x In
E: (1.05 - 1.2) x In
F:(1.05 - 1.3) x In
Cs:(6.5 - 10) x In
E: (5 - 6.5) x In
F: (6.5 - 10) x In
Add-on devices
Auxiliary contact (1)
(1) Only for single pole units
EN 60898
EN 60947-2 25kA
25000
AccessoriesBusbars
Dimensions
pg A.25chapter Cpg A.23
pg A.25Auxiliary contacts
A.23
A
Series S
90
Pole width
27mm
27mm
27mm
27mm
27mm
Ratedcurrent [A]
2025323540506380100
2025323540506380100
2025323540506380100
10162025323540506380100
2025323540506380100
Cat. No.
S91+N CS020S91+N CS025S91+N CS032S91+N CS035S91+N CS040S91+N CS050S91+N CS063S91+N CS080S91+N CS100
S93 CS020S93 CS025S93 CS032S93 CS035S93 CS040S93 CS050S93 CS063S93 CS080S93 CS100
S93+N CS020S93+N CS025S93+N CS032S93+N CS035S93+N CS040S93+N CS050S93+N CS063S93+N CS080S93+N CS100
––
S91 CS020S91 CS025S91 CS032S91 CS035S91 CS040S91 CS050S91 CS063S91 CS080S91 CS100
S91.3 CS020S91.3 CS025S91.3 CS032S91.3 CS035S91.3 CS040S91.3 CS050S91.3 CS063S91.3 CS080S91.3 CS100
Ref. No.
672540672541672542672543672544672545672546672547672548
672549672550672551672552672553672554672555672556672557
672558672559672560672561672562672563672564672565672566
––
672482672483672484672485672486672487672488672489672490
672491672492672493672494672495672496672497672498672499
Cat. No.
S91 E010S91 E016S91 E020S91 E025S91 E032S91 E035S91 E040S91 E050S91 E063S91 E080S91 E100
S91.3 E020S91.3 E025S91.3 E032S91.3 E035S91.3 E040S91.3 E050S91.3 E063S91.3 E080S91.3 E100
Ref. No.
672500672501672502672503672504672505672506672507672508672509672510
672511672512672513672514672515672516672517672518672519
Pack.
222222222
111111111
111111111
33333333333
111111111
Cs ECat. No.
S91 F010S91 F016S91 F020S91 F025S91 F032S91 F035S91 F040S91 F050S91 F063S91 F080S91 F100
S91.3 F020S91.3 F025S91.3 F032S91.3 F035S91.3 F040S91.3 F050S91.3 F063S91.3 F080S91.3 F100
Ref. No.
672520672521672522672523672524672525672526672527672528672529672530
672531672532672533672534672535672536672537672538672539
F
Series S90 - 25kA - AC MCB's
1P+N3 mod.
3P4.5 mod.
3P+N6 mod.
1P1.5 mod.
3 x 1P6 mod.
Dimensions - Series S90
1P+N 3P 3P+N 1P 3x1P
A.24
Min
iatu
re c
ircu
it b
reak
ers
A
Accessories
Auxiliary contact block 1/2 mod.
Tripping-signal or auxiliary contact block 1/2 mod.
Tripping-signal switch with reset button 1/2 mod.
Miniature circuit breakers interlock 1/2 mod.
Remote release 1 mod.
Undervoltage trip 1 mod.
Remote drive 3 mod.
Description
To be coupled to Series E90, E90P EFI, EHFI, D/HD90 1CO
To be coupled to Series E880 1CO
To be coupled to Series E880 1CO
To be coupled to Series E90, E90P EFI, EHFI, D/HD90 1CO2CO
To be coupled to Series E880 1CO
Panelboard switch
To be coupled to Series E90, EC90, EC91, E90P EFI, EHFI, D/HD90 AC 24 - 60V, DC 24 - 48VAC 110 - 415V, DC 110 - 125V
To be coupled to Series E90, EC90, EC91, E90P EFI, EHFI, D/HD90 can be subsequently fi tted to both sides of miniature circuitbreakers
AC 230VAC/DC 12VAC/DC 24VAC/DC 48V
To be coupled to Series E90, EC90, EC91, E90P EFI, EHFI, D/HD90
Width (mm)
9
9
9
99
9
9
1818
18181818
54
Cat. No.
H
H
S/H
S/HSRH/HH
NLVS
NF4NF5
NUVR 230NUVR 12NUVR 24NUVR 48
NFA
Ref. No.
676034
671597
671599
676035567819
671602
676038
567820567821
676039676040676041676042
676043
Pack.
10
10
10
1010
10
10
1010
1111
1
A.25
A
Accessories
Description
Padlocking bracket for E90 + S90
Sealing plate for 4 poles
Auxiliary contact block for series S90 2CO
Disconnect inhibiter for series S90, 3-pole to lock the mcb from disconnecting
Actuation inhibiter for series S90, 3-pole to seal or inhibit the toggle in the open or closed state
Busbar adapter for S90 1-pole (up to 63A)
Masking strip for lower meter wiring space lockable
Accessory forN-connection S90 Ferrule 12/18mm, 300mm long, 2.5mm2
With base plate and mounting rail to DIN EN 50 022/05.78 sealable, protection degree IP20
1- or 2-pole
With base plate and mounting rail to DIN EN 50 022/05.78 sealable, protection degree IP54
Cat. No.
KS
EPP
H5590ZW
AST
BST
SAV 91
VST
ZE3 2.5
GH 1
LGW 4
Ref. No.
624929
669486
555402
555681
546243
546292
564549
546294
546222
546110
Pack.
2
10
1
10
6
10
1
1
1
Accessories
For Series E90
For Series S90
Enclosure, grey
Enclosure, watertight
A.26
Min
iatu
re c
ircu
it b
reak
ers
A
(1) Preferred values of rated control supply voltage (IEC 60947-2): 24V, 48V, 110V, 125V, 220V, 250V
E90N
EN/IEC 60898B, C2-4030
1/2/3/4-
240/415-
415415
--
50/60-
400: magn.trip +50%250/440
123
yes5004406
10.0002.53g
10.00020.000
Aanyyes
IP20/IP40V2
+55°C/95% RH-25/+55-55/+55
1/350.75/25
1/350.75/25
4.5 yesyes yes yes yes
yes/yes-/yesyes
1812012
VDEyesA.6
E90E
EN/IEC 60898B, C2-4030
1/2/3/4-
240/415240415415
--
50/60-
400: magn.trip +50%250/440
123
yes5004406
10.0002.53g
10.00020.000
Aanyyes
IP20/IP40V2
+55°C/95% RH-25/+55-55/+55
1/350.75/25
1/350.75/25
4.5 yesyes yes yes yes
yes/yes-/yesyes
1812012
VDEyesA.8
E90
EN/IEC 60898B,C,D
B 6-63, C/D 0.5-6330
1/2/3/4, 1+N, 3+Nyes
240/41524041541548110
50/60DC: magn.trip +40%400: magn.trip +50%250/440; 53/120
12; 123
yes500440
610.000
2.53g
10.00020.000
Aanyyes
IP20/IP40V2
+55°C / 95%RH-25/+55-55/+55
1/350.75/35
1/350.75/35
4.5yesyesyesyesyesyes
-/yesyes
1812512
VDEyesA.10
Series
Standards Tripping characteristics Nominal current ACalibration temperature °CNumber of poles Neutral pole protected Nominal voltage Un AC 1P V 1P+N V 2P V 3P/3P+N/4P V DC 1P (1) VDC 2P (in series) (1) VDCFrequency Hz Hz HzMaximum service voltage Ubmax between two wires VMinimum service voltage Ubmin VSelectivity class (IEC 60898) Isolator application IEC 60947-2 Rated insulation voltage Pollution degree 2 V Pollution degree 3 VImpulse withstand test voltage kVInsulation resistance MOhmDielectric rigidity kVVibrations resistance (in x, y, z direction)(IEC 77/16.3) Endurance electrical at Un, In mechanical Utilisation category (IEC 60947-2)Mounting position (for all devices): any except upside downIncoming top or bottomProtection degree (outside / inside enclosure with door)Self-extinguish degree (according to UL94)Tropicalisation (according to EN/IEC 60068-2 / DIN 40046) °C/RHOperating temperature °CStorage temperature °CTerminal capacity Rigid cable min/max (top) mm2
Flexible cable min*/max (top) mm2
Rigid cable min/max (bottom) mm2
Flexible cable min*/max (bottom) mm2
(*Flexible cable 0.75/1/1.5 mm2 with cable lug) Torque NmAdd-on devices Auxiliary contacts (side add-on) Undervoltage release Shunt trip Remote drive Panel board switch Busbar systems Pin (top/bottom) Fork (top/bottom) Accessories Dimensions, weights, packaging (HxDxW) 86x68xW mm/mod. Weight/mod. g Package mod.ApprovalsCE-marking Page
Technical data MCB’s
A.27
A
Technical data
(2) EN/IEC 60898-2 and VDE0641-2/3
E90S
EN/IEC 60898B,C,D
B 6-63, C/D 0.5-6330
1/2/3/4, 1+N, 3+Nyes
240/41524041541548
11050/60
DC: magn.trip +40%400: magn.trip +50%250/440; 53/120
12; 123
yes500440
610.000
2.53g
10.00020.000
Aanyyes
IP20/IP40V2
+55°C / 95%RH-25/+55-55/+55
1/350.75/35
1/350.75/35
4.5yesyesyesyesyes
yes/yes-/yesyes
1812012
VDEyesA.12
E90X
EN/IEC 608983-5In/5-10In/10-20InB 6-63, C/D 0.5-63
401/2/3/4
-240/415
-41541548110
50/60DC: magn.trip +40%400: magn.trip +50%250/440; 53/120
12; 123
yes500440
610.000
2.53g
10.00020.000
Aanyyes
IP20/IP40V2
+55°C / 95%RH-25/+55-55/+55
1/350.75/35
1/350.75/35
4.5yesyesyesyesyes
yes/yes-/yesyes
1812012-
yesA.14
E90S UC
(2)B, C
B 6-63, C 0.5-63301/2-
240/415-
415-
220440
50/60 and DCDC: magn.trip +40%400: magn.trip +50%250/440; 250/440
12; 123
yes5004406
10.0002.55g
100020.000
Aany
follow polarityIP20/IP40
V2+55°C/95% RH
-25/+55-55/+55
1/350.75/25
1/350.75/25
4.5 yesyes yes yes yes
yes/yes-/yesyes
1812512-
yesA.16
E880/E880-S
EN/IEC 60947-23-5In/5-10In/10-20In
80 upto 12540
1/2/3/4-
240/415-
41541548
11050/60
DC: magn.trip +40%400: magn.trip +50%250/440; 53/120
12; 12-
yes5004406
10.0002.53g
400010.000
Aanyyes
IP20/IP40V2
+55°C/95% RH-25/+55-55/+55
70-
70-
5 yes-
yes - ---
yes
272108-
yesA.18/A.20
S90
EN/IEC 60898, E DIN VDE 0645F,Cs, E
F ,E 10/100 and Cs 20/100E 20°C, F and Cs 30°C
1, 3x1, 1+N, 3, 3+Nno
230230
-400
--
50/60--
250/440 207
----4
10.000-
3g4.0004.000
Bany
bottom onlyIP20/IP40
V0-
-25/+55-55/+551.5/35
-2.5/50
-
4yes -------
273508
VDE for E-char.yesA.22
A.28
Min
iatu
re c
ircu
it b
reak
ers
A
Short-circuit capacity of MCB’s
Series
Short-circuit capacity AC (kA) Icn 1P 230/400V 1P+N 230V 2P 230/400V 3P/3P+N/4P 230/400V Ics (service) Icu (ultimate) 1P 127V 240V 415V 1P+N/2P 127V 240V 2P 415V 3P, 4P 240V 415V 440V Ics (service) NEMA AB1 (120/240V)Short-circuit capacity DC (kA) Icu (ultimate) 1P ≤ 60V ≤ 220V 2P ≤ 125V ≤ 440V Ics (service)Page
E90N
3333
100% Icn-53-
105
105-
75% Icu10
-----
A.6
E90E
4.54.54.54.5
100% Icn-63
15106
106-
75% Icu14
-----
A.8
E90
6666
100% Icn2010330201020106
75% Icu20
20-
25-
100% IcuA.10
IEC
6089
8IE
C 60
947-
2IE
C 60
947-
2
A.29
A
Short-circuit capacity
E880
------66
10106
106-
100% Icu-
----
100% IcuA.18
E880S
------
10; D7.54.5-
B/C 15B/C 10; D7.5
B/C 15B/C 10; D7.5
-100% Icu
-
----
100% IcuA.20
E90X
-----
5050/25/20/15(1)
--
50/50/40/30(1)
50/25/20/15(1)
50/50/40/30(1)
50/25/20/15(1)
50/20/15/10(1)
50% Icu-
25-
30-
100% IcuA.12
E90SUC
6 (220VDC)(2)
-6 (440VDC)(3)
-100% Icn
-6(5)
---
6(5)
-----
--
10(4)
-10(4)
A.16
S90
25252525 -
----------------
A.22
E90S
10101010
75% Icn30154
403015301510
50% Icu30
25-
30-
100% IcuA.10
(1) 0.5-4A/6-25A/32-40A/50-63A(2) 10 (125VDC)(3) 10 (250VDC)(4) T=4ms(5) 4.5kA for 50A & 63A
A.30
Min
iatu
re c
ircu
it b
reak
ers
A
EN/IEC 60898 standard Circuit breakers are intended for the protection
against overcurrents of wiring installations in
buildings and similar applications:
They are designed for use by uninstructed people
and for not being maintained.
Tripping characteristic curves
Magnetic release
An electromagnet with plunger ensures
instantaneous tripping in case of short circuit. The
IEC 898 distinguishes three different types, following
the current for instantaneous release: type B, C, D.
Thermal release
The release is initiated by a bimetal strip in case of
overload.
The standard defines the range of release for
specific overload values.
Reference ambient temperature is 30°C
EN/IEC 60947-2 standard Low voltage switchgear and controlgear
Part 2: circuit breakers
This standard applies to circuit breakers, the main
contacts of which are intended to be connected to
circuits, the rated voltage of which does not exceed
1000V ac or 1500V dc.
Circuit breakers for use in industrial
environments (for use by instructed people).
Tripping characteristic curves
Magnetic release
An electromagnet with plunger ensures instantane-
ous tripping in case of short circuit.
The standard leaves the calibration of magnetic
release to manufacturer' s decision.
AEG Low Voltage offers instantaneous tripping
ranges
- release B: 4 In
- release C: 8.5 In (7.5 In for 63A)
- release D: 14 In
Thermal release
The release is initiated by a bimetal strip in case of
overload.
The standard defines the range of release for two
special overload values. Reference ambient
temperature is 40°C for E90X and 50°C for E90/E90S.
Applications
Only for resistive loads such as: - electrical heating - water heater - stovesUsual loads such as: - lighting - socket outlets - small motorsControl and protection of circuits having important transient inrush currents (large motors)
Test Tripping current time
B 3 In 0.1 < t < 45s (In ≤ 32A) 5 In 0.1 < t < 90s (In ≤ 32A) t < 0.1s
C 5 In 0.1 < t < 15s (In ≤ 32A) 10 In 0.1 < t < 30s (In ≤ 32A) t < 0.1s
D 10 In 0.1 < t < 4s(1) (In ≤ 32A) 20 In 0.1 < t < 8s (In ≤ 32A) t < 0.1s(1)if In ≤ 10A, t < 8s
Test Tripping current time
1.13 In t ≥ 1h (In ≤ 63A) t ≥ 2h (In > 63A) 1.45 In t < 1h (In ≤ 63A) t < 2h (In > 63A) 2.55 In 1s < t < 60s (In ≤ 32A) 1s < t < 120s (In > 32A)
Test Tripping current time
1.05 In t ≥ 1h (In ≤ 63A) t ≥ 2h (In > 63A) 1.30 In t < 1h (In ≤ 63A) t < 2h (In > 63A)
B C D
A.31
A
MC
B’s
Influence of ambient temperature The thermal calibration of the MCB's was carried
out at an ambient temperature of 30°C. Ambient
temperatures different from 30°C influence the
bimetal and this results in earlier or later thermal
tripping (see curve).
Voltage drop and energy loss
In (A)
0.5123468
10131620253240506380
100125
Voltage drop (V)
2.2301.2700.6200.5200.3700.2600.1600.1600.1550.1620.1380.1280.0960.1000.0900.0820.0750.0750.076
Energy loss (W)
1.1151.2721.2401.5571.4881.5701.2421.5602.0112.5862.7603.1883.0724.0004.5005.1606.0007.5009.500
Inner resistant (mΩ)
4458.01272.0310.0173.093.043.619.415.611.910.16.95.13.02.51.81.30.90.750.6
0.5 - 6A 10A
16 - 40A 50 - 63A
: 1P (Single pole): mP (Multipole)
A.32
Min
iatu
re c
ircu
it b
reak
ers
A
Notes
A.33
A
Com
pact Unibis™
MC
B’S
Miniature circuit breakers A
B
N
C
D
E
F
G
H
I
J
K
L
M
O
X
BenefitsSeries EC 91E NR - Miniature circuit breakers Series EC 91 NR - Miniature circuit breakers Series EC 91S NR - Miniature circuit breakers Series EC 911 - Miniature circuit breakers Series EC 91E - Miniature circuit breakers Series EC 90 - Miniature circuit breakers Series DA 41N - Miniature circuit breakers Series CA - Unibis™ Interface auxiliary VBS - Busbar System DimensionsTechnical data
A.34A.36A.37A.38A.39A.40A.42A.44A.45A.46A.47A.48
Quick overview
Pageno. Series Applications Poles
Add-ondevices
Trippingcurve
Ratingcurrent
(A)Short-circuit capacity
(kA)
A.36 EC 91E NR 1+N(1mod) yes B-C 2 - 40 4.5 6
A.37 EC 91 NR 1+N(1mod) yes B-C 2 - 40 6 7.5
A.38 EC 91S NR 1+N(1mod) yes B-C 2 - 40 10(1) 10
A.39 EC 9111P+1P(1mod) yes B-C 2 - 40 6 6
A.40 EC 90E 2, 3, 4 yes B-C 2 - 40 4.5 6
A.42 EC 90 2, 3, 4 yes B-C 2 - 40 6 7.5
A.44 DA 41N 1+N(1mod) yes C 6 - 40 4.5
domestic
commercial
B: 3-5 In
C: 5-10 In
(1) Icn1 = 6kA
EN/IEC 60898-1
EN/IEC 60947-2
A.34
Min
iatu
re c
ircu
it b
reak
ers
A
Benefits of the compact Unibis™ MCB’S• 2 circuits in 1 module• Unibis™: the solution for space problemsUnibis™ MCB’s are one of the latest introductions in the AEG MCB’s range and are developed to reduce the size of the distribution board to the minimum.The performances are upgraded to 10kA.
Brandnew design:
2P in 1 module, 3 and 4P in 2 modules
Complete range: from 4.5–6–10kA(1), 2–40 Amps, B and C curves
100% compatible with all AEG MCB’s auxiliaries and accessories
100% Elfaplus quality and reliability
VDE certified
2Pin
1 mod
1P+1Pin
1 mod
1P+Nin
1 mod
3Pin
2 mod
4Pin
2 mod
(1) 10kA at 230V
4.5kA 6kA 10kA(1)
3 performances up to 10kA
Question:A.34 - A.46,
products needed for photography
A.35
A
Series EC
.., DA
..
Green or red fl ag on toggle with isolation applications
Correct information about the real position. Minimum 5mm distance between open contacts is ensured.
Part of the family
Unibis™ MCB’s fi t perfectly in the AEG MCB’s range.
Safety terminals IP20
The capacity of Unibis™ terminals has been doubled. Connection possibilities: (2 x 4mm2)or (1 x 4mm2) + (1 x 6mm2).
Full functionality
A small auxiliary contact is the interface to the com-plete functionality of the AEG MCB’s auxiliaries and accessories.
Easy to replace
Double clips make it easy to replace the MCB’s, especially when a busbar is installed.
High performance clips
To fi x the MCB to the DIN rail.
Userfriendly
All screws are on the same level to work fast and easy.
High performance torque
Up to 3Nm.
quality and reliability guaranteed
IN2 x 2P/1 mod.
OUT1 x 2P/2 mod.
Benefits of the compact Unibis™ MCB’SSaving up to 50% space in distribution boards!
Replacing standard MCB’s by compact
Unibis™ MCB’s
A.36
Min
iatu
re c
ircu
it b
reak
ers
A
Series EC 91E NR
Compact MCB’s
EN/IEC 60898-1 45003
EN/IEC 60947-2 6kA
Performances
Thermal setting In (A) 2-40Rated voltage AC Un (V) 230Minimum operating voltage UBmin (V) 12Tripping characteristics B-CSelectivity class 3Mechanical/electrical endurance 20000/10000(1)
Tropicalisation acc. to EN/IEC 60068-2 55°C at 95% RHTerminal capacity flexible/rigid cable (mm²) 10-16(2)
Poles 1P+N (1 mod)Weight (g) 125(1) 8000 for 32 and 40A
Short-circuit capacity
Acc. to EN/IEC 60898-1Poles V Icn/Ics (kA)
1P+N 230 4.5
Acc. to EN/IEC 60947-2 Poles V Icu (kA)
1P+N 230 6
Attention: do not use on IT net confi guration
Series EC 91E NR - 4.5kA - characteristics B-C
B CIn (A) Cat. No. Ref. No. Cat. No. Ref. No. Pack.
1P + N 2 EC91E B02NR 692874 EC91E C02NR 692856 121 mod. 4 EC91E B04NR 692875 EC91E C04NR 692857 12
6 EC91E B06NR 692876 EC91E C06NR 692858 1210 EC91E B10NR 692877 EC91E C10NR 692859 1216 EC91E B16NR 692878 EC91E C16NR 692860 1220 EC91E B20NR 692879 EC91E C20NR 692861 1225 EC91E B25NR 692880 EC91E C25NR 692862 1232 EC91E B32NR 692881 EC91E C32NR 692863 1240 EC91E B40NR 692882 EC91E C40NR 692864 12
Auxiliary contacts CA pg. A.45Auxiliary contacts pg. A.24
Other auxiliaries pg. A.24
Busbars pg. A.46Dimensions pg. A.47
Applications
Approvals / Marking
Add-on devices
NFA
Auxiliaries CA, H
NFNUVR..NLVS
When coupling an add-on device (Remote release NF, undervotage trip NUVR.., remote drive NFA) to the MCB, an universal CA auxiliary has to be coupled fi rst as interface.
A.37
A
Series EC 91S NR/ EC 91 NR
Series EC 91 NR
Compact MCB’s
EN/IEC 60898-1 60003
EN/IEC 60947-2 7.5kA
Performances
Thermal setting In (A) 2-40Rated voltage AC Un (V) 230Minimum operating voltage UBmin (V) 12Tripping characteristics B-CSelectivity class 3Mechanical/electrical endurance 20000/10000(1)
Tropicalisation acc. to EN/IEC 60068-2 55°C at 95% RHTerminal capacity flexible/rigid cable (mm²) 10-16(2)
Poles 1P+N (1 mod)Weight (g) 125(1) 8000 for 32 and 40A
Short-circuit capacity
Acc. to EN/IEC 60898-1Poles V Icn/Ics (kA)
1P+N 230 6
Acc. to EN/IEC 60947-2 Poles V Icu (kA)
1P+N 230 7.5
Attention: do not use on IT net confi guration
Series EC 91 NR - 6kA - characteristics B-C
B CIn (A) Cat. No. Ref. No. Cat. No. Ref. No. Pack.
2x 1P+N 2 EC91 B02NR 692883 EC91 C02NR 692865 124 EC91 B04NR 692884 EC91 C04NR 692866 126 EC91 B06NR 692885 EC91 C06NR 692867 1210 EC91 B10NR 692886 EC91 C10NR 692868 1213 EC91 B13NR 692602 EC91 C13NR 692601 1216 EC91 B16NR 692887 EC91 C16NR 692869 1220 EC91 B20NR 692888 EC91 C20NR 692870 1225 EC91 B25NR 692889 EC91 C25NR 692871 1232 EC91 B32NR 692890 EC91 C32NR 692872 1240 EC91 B40NR 692891 EC91 C40NR 692873 12
Auxiliary contacts CA pg. A.45Auxiliary contacts pg. A.24
Other auxiliaries pg. A.24
Busbars pg. A.46Dimensions pg. A.47
Applications
Approvals / Marking
Add-on devices
NFA
Auxiliaries CA, H
NFNUVR..NLVS
When coupling an add-on device (Remote release NF, undervotage trip NUVR.., remote drive NFA) to the MCB, an universal CA auxiliary has to be coupled fi rst as interface.
A.38
Min
iatu
re c
ircu
it b
reak
ers
A
Series EC 91S NR
Compact MCB’s
EN/IEC 60898-1 100003
EN/IEC 60947-2 10kA
Performances
Thermal setting In (A) 2-40Rated voltage AC Un (V) 230Minimum operating voltage UBmin (V) 12Tripping characteristics B-CSelectivity class 3Mechanical/electrical endurance 20000/10000(1)
Tropicalisation acc. to EN/IEC 60068-2 55°C at 95% RHTerminal capacity flexible/rigid cable (mm²) 10-16(2)
Poles 1+N (1 mod)Weight (g) 125(1) 8000 for 32 and 40A
Short-circuit capacity
Acc. to EN/IEC 60898-1Poles V Icn/Ics (kA)
1P+N 230 10
Acc. to EN/IEC 60947-2 Poles V Icu (kA)
1P+N 230 10
(2) lcn1 = 6kA
Attention: do not use on IT net confi guration
Series EC 91SNR - 10kA - characteristics B-C
B CIn (A) Cat. No. Ref. No. Cat. No. Ref. No. Pack.
1P + N 2 EC91S B02NR 693027 EC91S C02NR 692946 121 mod. 4 EC91S B04NR 693028 EC91S C04NR 692947 12
6 EC91S B06NR 693029 EC91S C06NR 692948 1210 EC91S B10NR 693030 EC91S C10NR 692949 1216 EC91S B16NR 693031 EC91S C16NR 692950 1220 EC91S B20NR 693032 EC91S C20NR 692951 1225 EC91S B25NR 693033 EC91S C25NR 692952 1232 EC91S B32NR 693034 EC91S C32NR 692953 1240 EC91S B40NR 693035 EC91S C40NR 692954 12
Auxiliary contacts CA pg. A.45Auxiliary contacts pg. A.24
Other auxiliaries pg. A.24
Busbars pg. A.46Dimensions pg. A.47
Applications
Approvals / Marking
Add-on devices
NFA
Auxiliaries CA, H
NFNUVR..NLVS
When coupling an add-on device (Remote release NF, undervotage trip NUVR.., remote drive NFA) to the MCB, an universal CA auxiliary has to be coupled fi rst as interface.
A.39
A
Series EC 91S NR/ EC 911
Series EC 911
Compact MCB’s
EN/IEC 60898-1 60003
EN/IEC 60947-2 6kA
Performances
Thermal setting In (A) 2-40Rated voltage AC Un (V) 230Minimum operating voltage UBmin (V) 12Tripping characteristics B-CSelectivity class 3Mechanical/electrical endurance 20000/10000(1)
Tropicalisation acc. to EN/IEC 60068-2 55°C at 95% RHTerminal capacity flexible/rigid cable (mm²) 10-16(2)
Poles 1P+1P (1 mod)Weight (g) 125(1) 8000 for 32 and 40A
Short-circuit capacity
Acc. to EN/IEC 60898-1Poles V Icn/Ics (kA)
1+1 230 6
Acc. to EN/IEC 60947-2 Poles V Icu (kA)
1+1 230 6
Attention: do not use on IT net confi guration
Series EC 911- 6kA - characteristics B-C
B CIn (A) Cat. No. Ref. No. Cat. No. Ref. No. Pack.
1P+1P 2 EC 911 B02 692581 EC 911 C02 692591 121 mod. 4 EC 911 B04 692582 EC 911 C04 692592 12
6 EC 911 B06 692583 EC 911 C06 692593 1210 EC 911 B10 692584 EC 911 C10 692594 1213 EC 911 B13 692585 EC 911 C13 692595 1216 EC 911 B16 692586 EC 911 C16 692596 1220 EC 911 B20 692587 EC 911 C20 692597 1225 EC 911 B25 692588 EC 911 C25 692598 1232 EC 911 B32 692589 EC 911 C32 692599 1240 EC 911 B40 692590 EC 911 C40 692603 12
Auxiliary contacts CA pg. A.45Auxiliary contacts pg. A.24
Other auxiliaries pg. A.24
Busbars pg. A.46Dimensions pg. A.47
Applications
Approvals / Marking
Add-on devices
NFA
Auxiliaries CA, H
NFNUVR..NLVS
When coupling an add-on device (Remote release NF, undervotage trip NUVR.., remote drive NFA) to the MCB, an universal CA auxiliary has to be coupled fi rst as interface.
A.40
Min
iatu
re c
ircu
it b
reak
ers
A
Series EC 90E
Compact MCB’s
EN/IEC 60898-1 45003
EN/IEC 60947-2 6kA
Performances
Thermal setting In (A) 2-40Rated voltage AC Un (V) 230/415Minimum operating voltage UBmin (V) 12Tripping characteristics B-CSelectivity class 3Mechanical/electrical endurance 20000/10000(1)
Tropicalisation acc. to EN/IEC 60068-2 55°C at 95% RHTerminal capacity flexible/rigid cable (mm²) 10-16Poles 2, 3, 4Weight (g) 160(1) 8000 for 32 and 40A
Short-circuit capacity
Acc. to EN/IEC 60898-1Poles V Icn/Ics (kA)
2P 240/415 4.5
3P 240/415 4.5
4P 240/415 4.5
Acc. to EN/IEC 60947-2 Poles V Icu (kA)
2P 240/415 4.5
3P 240/415 4.5
4P 240/415 4.5
Auxiliary contacts CA pg. A.45Auxiliary contacts pg. A.24
Other auxiliaries pg. A.24
Busbars pg. A.46Dimensions pg. A.47
Applications
Approvals / Marking
Add-on devices
NFA
Auxiliaries CA, H
NFNUVR..NLVS
When coupling an add-on device (Remote release NF, undervotage trip NUVR.., remote drive NFA) to the MCB, an universal CA auxiliary has to be coupled fi rst as interface.
A.41
A
Series EC 90E
EC 90E- 4.5kA - characteristics B-C
B CIn (A) Cat. No. Ref. No. Cat. No. Ref. No. Pack.
2P 2 EC 92 E B02 692973 EC 92 E C02 692892 121 mod. 4 EC 92 E B04 692974 EC 92 E C04 692893 12
6 EC 92 E B06 692975 EC 92 E C06 692894 1210 EC 92 E B10 692976 EC 92 E C10 692895 1216 EC 92 E B16 692977 EC 92 E C16 692896 1220 EC 92 E B20 692978 EC 92 E C20 692897 1225 EC 92 E B25 692979 EC 92 E C25 692898 1232 EC 92 E B32 692980 EC 92 E C32 692899 1240 EC 92 E B40 692981 EC 92 E C40 692900 12
3P 2 EC 93 E B02 692982 EC 93 E C02 692901 61 mod. 4 EC 93 E B04 692983 EC 93 E C04 692902 6
6 EC 93 E B06 692984 EC 93 E C06 692903 610 EC 93 E B10 692985 EC 93 E C10 692904 616 EC 93 E B16 692986 EC 93 E C16 692905 620 EC 93 E B20 692987 EC 93 E C20 692906 625 EC 93 E B25 692988 EC 93 E C25 692907 632 EC 93 E B32 692989 EC 93 E C32 692908 640 EC 93 E B40 692990 EC 93 E C40 692909 6
4P 2 EC 94 E B02 692991 EC 94 E C02 692910 61 mod. 4 EC 94 E B04 692992 EC 94 E C04 692911 6
6 EC 94 E B06 692993 EC 94 E C06 692912 610 EC 94 E B10 692994 EC 94 E C10 692913 616 EC 94 E B16 692995 EC 94 E C16 692914 620 EC 94 E B20 692996 EC 94 E C20 692915 625 EC 94 E B25 692997 EC 94 E C25 692916 632 EC 94 E B32 692998 EC 94 E C32 692917 640 EC 94 E B40 692999 EC 94 E C40 692918 6
A.42
Min
iatu
re c
ircu
it b
reak
ers
A
Series EC 90
Compact MCB’s
EN/IEC 60898-1 60003
EN/IEC 60947-2 7.5kA
Performances
Thermal setting In (A) 2-40Rated voltage AC Un (V) 240/415Minimum operating voltage UBmin (V) 12Tripping characteristics B-CSelectivity class 3Mechanical/electrical endurance 20000/10000(1)
Tropicalisation acc. to EN/IEC 60068-2 55°C at 95% RHTerminal capacity flexible/rigid cable (mm²) 10-16Poles 2, 3, 4Weight (g) 160(1) 8000 for 32 and 40A
Short-circuit capacity
Acc. to EN/IEC 60898-1Poles V Icn/Ics (kA)
2P 240/415 6
3P 240/415 6
4P 240/415 6
Acc. to EN/IEC 60947-2 Poles V Icu (kA)
2P 240/415 7.5
3P 240/415 7.5
4P 240/415 7.5
Auxiliary contacts CA pg. A.45Auxiliary contacts pg. A.24
Other auxiliaries pg. A.24
Busbars pg. A.46Dimensions pg. A.47
Applications
Approvals / Marking
Add-on devices
NFA
Auxiliaries CA, H
NFNUVR..NLVS
When coupling an add-on device (Remote re-lease nf, undervotage trip NUVR.., remote drive NFA) to the MCB, an universal CA auxiliary has to be coupled fi rst as interface.
A.43
A
Series EC 90
EC 90- 6kA - characteristics B-C
B CIn (A) Cat. No. Ref. No. Cat. No. Ref. No. Pack.
2 EC 92 B02 693000 EC 92 C02 692919 124 EC 92 B04 693001 EC 92 C04 692920 126 EC 92 B06 693002 EC 92 C06 692921 12
10 EC 92 B10 693003 EC 92 C10 692922 1216 EC 92 B16 693004 EC 92 C16 692923 1220 EC 92 B20 693005 EC 92 C20 692924 1225 EC 92 B25 693006 EC 92 C25 692925 1232 EC 92 B32 693007 EC 92 C32 692926 1240 EC 92 B40 693008 EC 92 C40 692927 12
2 EC 93 B02 693009 EC 93 C02 692928 64 EC 93 B04 693010 EC 93 C04 692929 66 EC 93 B06 693011 EC 93 C06 692930 6
10 EC 93 B10 693012 EC 93 C10 692931 616 EC 93 B16 693013 EC 93 C16 692932 620 EC 93 B20 693014 EC 93 C20 692933 625 EC 93 B25 693015 EC 93 C25 692934 632 EC 93 B32 693016 EC 93 C32 692935 640 EC 93 B40 693017 EC 93 C40 692936 6
2 EC 94 B02 693018 EC 94 C02 692937 64 EC 94 B04 693019 EC 94 C04 692938 66 EC 94 B06 693020 EC 94 C06 692939 6
10 EC 94 B10 693021 EC 94 C10 692940 616 EC 94 B16 693022 EC 94 C16 692941 620 EC 94 B20 693023 EC 94 C20 692942 625 EC 94 B25 693024 EC 94 C25 692943 632 EC 94 B32 693025 EC 94 C32 692944 640 EC 94 B40 693026 EC 94 C40 692945 6
A.44
Min
iatu
re c
ircu
it b
reak
ers
A
Series DA 41 N
Compact MCB’s
EN/IEC 60898-1 45003
Performances
Thermal setting In (A) 2-40Rated voltage AC Un (V) 230Minimum operating voltage UBmin (V) 12Tripping characteristics CSelectivity class 3Mechanical/electrical endurance 20000/10000(1)
Tropicalisation acc. to EN/IEC 60068-2 55°C at 95% RHTerminal capacity flexible/rigid cable (mm²) 10-16(2)
Poles 1P+N (1 mod)Weight (g) 125(1) 8000 for 32 and 40A
Short-circuit capacity
Acc. to EN/IEC 60898-1Poles V Icn/Ics (kA)
1P+N 230 4.5
Series DA 41 N- 4.5kA - characteristics B-C
CIn (A) Cat. No. Ref. No. Pack.
1P + N 6 DA 41 N C06 693079 121 mod. 10 DA 41 N C10 693080 12
16 DA 41 N C16 693081 1220 DA 41 N C20 693082 1225 DA 41 N C25 693083 1232 DA 41 N C32 693084 1240 DA 41 N C40 692600 12
Busbars pg. A.46Dimensions pg. A.47
Applications
Approvals / Marking
A.45
A
Series DA 41 N/Auxiliary
Series CA - Unibis™ Interface EN/IEC 62019• Common for all modular protection devices: MCB’s and RCBO’s up to 63 A, RCCB’s up
to 100A and mains disconnect switches type ASTER (ASTM).• Can be coupled on both sides of MCB’s(1) and modular switches type ASTM.• Version with golden contacts, available for low current as well as low voltage
applications.• Stack-on left or right up to 4 CA units.• Permits the pass-through of busbars, pin & fork, top and bottom, just changing the
position of the base of the auxiliaries.
Auxiliary
Performances
Change-over contacts 1Rated current In (A) 5Rated voltage AC Un (V) 240Electrical endurance 10000Terminal capacity flexible/rigid cable (mm²) 2.5Weight (g) 70
ApplicationThe auxiliary contact Unibis™ has a double function: 1. The standard function as auxiliary monitoring contact for which it has beendeveloped.2. The interface function, which allows the use of all auxiliaries in combination with the Unibis™ MCB range.Example: to couple the undervoltage release NUVR to a Unibis™ MCB, the CAH 672977 has to be added in between the MCB and the NUVR as interface.
The auxiliary contacts are units to be added on to protection devices. They allow infor-mation to be monitored from a distance about the protection devices.
Auxiliary contact CA H (function H)Provides the status of the protection device, OPEN/CLOSED.Signal or auxiliary contact CA S/H (function S/H)This auxiliary can act as an auxiliary contact (function H) or as a signalcontact (function S).The user can change the function at the moment of installation.Used as signal contact (function S) it provides the information about theautomatic tripping of the protection devices: overload or short-circuit for MCB’s, earth leakage tripping for RCD’s.• The device has a test button on the front to simulate the function
(acting as a function H or S)• Reset button for the contacts (function S)• Tripping signal on the front (function S)
Applications
Approvals / Marking
Add-on devices Coupling(1)
Busbar pass-through
Stack-on
(1) 3P Unibis™ MCB’S accept CA only on the left side
H S
Series CA - Unibis™ Interface
Function Cat. No. Ref. No. Pack.
1/2 mod. H CA UN H 672977 1/40S/H CA UN S/H 672978 1/40
A.46
Min
iatu
re c
ircu
it b
reak
ers
A
Busbar system
Rails
ParticularityThe double angled shape of the busbar is designed to avoid an additional terminal to realise a derivation with wiring till 10mm² and Ith = max. 63A.
Technical data
Rail Copper (oxygen free)Insulation strip Plastic
Self extinguishing V-0Heat resistant >96 °C
Dielectric strength 36kV/mmto DIN 53481/1.2
Creepage resistance / tracking index to IEC 60439Insulation group 415V, Group C
to BS/EN 60439-1
Insulated pin type busbar - double angled shape
Ref. No. Pack.
Supply: 1P 10 mm² 13x1 pole phase - grey - double angled 646091 1/20Distribution: 1P 10 mm² 13x1 pole neutral - blue - double angled 646092 1/20
A.47
A
Busbar system / Dim
ensions
Dimensional drawings
646091 - 646092Double angled
Miniature Circuit Breakers - Series EC 91.NR, EC911, EC90
Insulated pin busbars
Miniature Circuit Breakers - Series DA 41 N Auxiliary interface - Series CA
A.48
Min
iatu
re c
ircu
it b
reak
ers
A
Technical data of MCB’sSeries EC 91E NR EC 91 NR
Standards EN/IEC 60898-1 EN/IEC 60898-1Tripping characteristics B,C B,C Nominal current (In) 2-40 2-40Calibration temperature (°C) 30 30Number of poles (# mod) 1+N (1 mod) 1+N (1 mod)Neutral pole protected - -Nominal voltage Un AC 1P+N (V) 230 230
1P+1P (V) - -2P (V) - -3P (V) -4P (V) -
Nominal voltage Un DC 2P (V ) - -Frequency (Hz) 50/60 50/60
in DC Thresh. magn. + 40% Thresh. magn. + 40%for 400 Hz Thresh. magn. + 50% Thresh. magn. + 50%
Maximum service voltage Ub max (V) 250 250Minimum service voltage Ub min (V) 12 12Selectivity class (EN 60898-1) 3 3Rated insulation voltage Pollution degree 2 (V) 500 500
Pollution degree 3 (V) 400 400Impulse withstand test voltage (kV) 6 6Insulation resistance (MΩ) 1000 1000Dielectric rigidity (kV) 2.5 2.5Vibration resistance (in x,y,z direction) (IEC 77/16.3) (g) 3 3Endurance Electrical at Un,In 10000(1) 10000(1)
Mechanical 20000 20000Utilisation category (EN 60947-2) A AMounting position: vertical/horizontal any anyIncoming top or bottom yes yesProtection degree (outside/inside enclosure with door) IP20/IP40 IP20/IP40Selfextinguish degree (acc. UL 94) V2 V2Tropicalisation (acc. EN 60068-2/DIN 40046) +55°C/95%RH +55°C/95%RHOperating temperature (°C) -25/+55 -25/+55Storage temperature (°C) -55/+55 -55/+55Terminal capacity Rigid cable min/max (top) (mm²) 1/16(2) 1/16(2)
Flexible cable min/max (top) (mm²) 1/10(2) 1/10(2)
Rigid cable min/max (bottom) (mm²) 1/16(2) 1/16(2)
Flexible cable min/max (bottom) (mm²) 1/10(2) 1/10(2)
Torque (Nm) 3 3Add-on devices Auxiliary contacts yes yes
Under voltage trip NUVR yes(3) yes(3)
Remote release NF yes(3) yes(3)
Remote drive NFA yes(3) yes(3)
Panelboard switch NLVS yes(3) yes(3)
Busbar systems Pin (top/bottom) yes/yes yes/yesFork (top/bottom) no/no no/no
Accessories yes yesWidth per mod. (mm) 18 18Weight per mod. (gr) 125 125Package 12 12Approvals KEMA, IMQ VDE, KEMA, IMQCE- marking yes yesPage A.36 A.37
Short-circuit capacity of MCB’sSeries EC 91E NR EC 91 NR
Short-circuit capacity AC (kA) (kA)EN/IEC 60898-1 1P+N 230 V 4.5 6
1P+1P 230 V - -2P 400 V - -3P 400 V - -4P 400 V - -
EN 60947-2 Ics (service) 1P+N 230 V 6 7.51P+1P 230 V - -2P 415 V - -3P 415 V - -4P 415 V - -
Short-circuit capacity DCEN 60947-2 lcu 2P 96 V
(1) 8000 for 32 and 40 A(2) Also accepting (2x4mm²) or (1x4mm²)+(1x6mm²)(3) Requires CA auxiliary contact as interface
(4) Icn1= 6kA
A.49
A
Technical data
EC 91S NR EC 911 EC 90E EC 90 DA 41N
EN/IEC 60898-1 EN/IEC 60898-1 EN/IEC 60898-1 EN/IEC 60898-1 EN/IEC 60898-1B,C B,C B,C B,C C
2-40 2-40 2-40 2-40 2-4030 30 30 30 30
1+N (1 mod) 1P+1P (1 mod) 2 (1 mod), 3&4 (2 mod) 2 (1 mod), 3&4 (2 mod) 1+N (1 mod)- - - - -
230 - - - 230- 230 - - -- - 400 400 -- - 400 400 -- - 400 400 -- - 96 96 -
50/60 50/60 50/60 50/60 50/60Thresh. magn. + 40% Thresh. magn. + 40% Thresh. magn. + 40% Thresh. magn. + 40% Thresh. magn. + 40%Thresh. magn. + 50% Thresh. magn. + 50% Thresh. magn. + 50% Thresh. magn. + 50% Thresh. magn. + 50%
250 250/440 250/440 250/440 25012 12 12 12 123 3 3 3 3
500 500 500 500 500400 400 400 400 400
6 6 6 6 61000(1) 1000 10000 10000 1000
2.5 2.5 2.5 2.5 2.53 3 3 3 3
10000(1) 10000(1) 10000(1) 10000(1) 10000(1)
20000 20000 20000 20000 20000A A A A A
any any any any anyyes yes yes yes yes
IP20/IP40 IP20/IP40 IP20/IP40 IP20/IP40 IP20/IP40V2 V2 V2 V2 V2
+55°C/95%RH +55°C/95%RH +55°C/95%RH +55°C/95%RH +55°C/95%RH-25/+55 -25/+55 -25/+55 -25/+55 -25/+55-55/+55 -55/+55 -55/+55 -55/+55 -55/+551/16(2) 1/16(2) 1/16(2) 1/16(2) 1/16(2)
1/10(2) 1/10(2) 1/10(2) 1/10(2) 1/10(2)
1/16(2) 1/16(2) 1/16(2) 1/16(2) 1/16(2)
1/10(2) 1/10(2) 1/10(2) 1/10(2) 1/10(2)
3 3 3 3 3yes yes yes yes noyes(3) yes(3) yes(3) yes(3) noyes(3) yes(3) yes(3) yes(3) noyes(3) yes(3) yes(3) yes(3) noyes(3) yes(3) yes(3) yes(3) no
yes/yes yes/yes yes/yes yes/yes yes/yesno/no no/no no/no no/no no/noyes yes yes yes yes18 18 18/36 18/36 18
125 160 160/320 160/320 12512 12/6 12/6 12/6 12
KEMA VDE, IMQ IMQ, NF VDE, IMQ, NF, CEBEC IMQ, KEMAyes yes yes yes yesA.38 A.39 A.40 A.42 A.44
EC 91S NR EC 911 EC 90E EC 90 DA 41N
(kA) (kA) (kA) (kA) (kA)10(4) - - - 4.5
- 6 - - -- - 4.5 6 -- - 4.5 6 -- - 4.5 6 -
10 - - - -- 6 - - -- - 6 7.5 -- - 6 7.5 -- - 6 7.5 -
4.5 6
(1) 8000 for 32 and 40 A (2) Also accepting (2x4mm²) or (1x4mm²)+(1x6mm²)(3) Requires CA auxiliary contact as interface
(4) Icn1= 6kA
A.50
Min
iatu
re c
ircu
it b
reak
ers
A
Characteristics according to IEC/EN 60898-1
Miniature Circuit Breakers (MCB) are intended for the protection of wiring installations against both overloads and short-circuits in domestic or commercial wiring installations where operation is possible by uninstructed people.
Magnetic release An electromagnet with plunger ensures instanta neous tripping in the event of short-circuit. The standard distinguishes two different types, follo wing the current for instantaneous release: type B and C.
lcn
(A)
Test
current
Tripping
time
Applications
B 3 x ln 0.1 < t < 45s (In ≤ 32A) Only for resistive loads such as:0.1 < t < 90s (In > 32A) - electrical heating
5 x ln t < 0.1s - water heater- stoves
C 5 x ln 0.1 < t < 15s (In ≤ 32A) Usual loads such as:0.1 < t < 30s (In > 32A) - lighting
10 x ln t < 0.1s - socket-outlets- small motors
Thermal release The release is initiated by a bimetal strip in case of overload. The standard defi nes the range of releases for specifi c overload values.Reference ambient temperature is 30°C.
Test current Tripping time
1.13 x ln t ≥ 1h (ln ≤ 63A)t ≥ 2h (ln > 63A)
1.45 x ln t < 1h (ln ≤ 63A)t < 2h (ln > 63A)
2.55 x ln 1s < t < 60s (ln ≤ 32A)1s < t < 120s (ln > 32A)
Tripping characteristic curves (EN/IEC 60898-1)
Influence of ambient airtemperature on the rated current
The maximum value of the current which can fl ow through an MCB depends of the nominal current of the MCB, the conductor cross-section as well as of theambient air temperature.
The values shown in the diagram below are for devices in free air. For devices installed with other modular devices in the same switchboard a correction factor (K) shall be applied relative to the mounting situation of the MCB, the ambient temperature and the number of main circuits in the installation (EN 60439-1):
No. of rows in enclosure K
2 or 3 0.94 or 5 0.86 to 9 0.7> 10 0.6
Calculation exampleWithin a distribution panel consisting of eight rows each 6 of 2 pole C16 with an operating ambient temperature of 45°C, which is the highest temperature at which the MCB can operate without unwanted tripping.
CalculationThe correction factor K=0.7, for use in an eight rows installation: 16A x 0.7= 11.2AAs the MCB is working at 45°C, another factor shall beapplied (90% = 0.9):In at 45°C = In at 30°C x 0.9 = 11.2A x 0.9 = 10.1A
The thermal calibration of the MCB’s was carried out at an ambient temperature of 30°C. Ambient temperatures different from 30°C infl uence the bimetal and this results in earlier or later thermal tripping.
16-40A(1)
(1) Other ratings see page A.31
A.51
A
Unibis
TM M
CB
's
Tripping current as a function of the frequency
All MCB’s are designed to work at frequencies of 50-60 Hz, therefore to work at different values, consideration must be given to the variation of the tripping characteristics.The thermal tripping does not change with variation of the frequency but the magnetic tripping values can be up to 50% higher than the ones at 50-60 Hz.For DC current magnetic tripping is 50% higher.
Tripping current variations
60Hz 100Hz 200Hz 300Hz 400Hz
1 1.1 1.2 1.4 1.5
Power lossesThe power losses are calculated by measuring the voltage drop between the incoming and the outgoing terminals of the device at rated current.
Power losses per poleIn
(A)
Voltage drop
(V)
Energy loss Pw
(W)
Resistance Z
(mOhm)2 0.55 1.1 275.004 0.34 1.35 84.386 0.25 1.52 42.22
10 0.16 1.64 16.4016 0.13 2.1 8.2020 0.13 2.52 6.3025 0.12 3.1 4.9632 0.12 3.8 3.7140 0.11 4.46 2.79
Toggle(1)
The toggle permits to switch the MCB ON or OFF
Printing on the toggle provides information of the real contact position.
0-OFFContacts in open position. Ensures a distance between contacts > 5mm in theUnibis™ range.
I-ONContacts in closed position. Ensures continuity in the main circuit.