SD
24"x12"
24"/12"
12" o
GENERAL NOTES:MECHANICAL SYMBOL LEGENDABBREVIATIONS
FIRE DAMPER
FLEXIBLE DUCT
ACOUSTICAL DUCT LINING
FLEXIBLE CONNECTION
MANUAL BALANCING DAMPER
SMOKE DAMPER
MITERED ELBOW (ALL MITERED ELBOWS ARE TO HAVEVANES EXCEPT TRANSFER AIR SOUND ELBOW)
EXISTING DUCT TO BE REMOVED
CONNECT NEW DUCT TO EXISTING DUCT
SUPPLY DUCT, SECTION
EXHAUST DUCT, SECTION
RETURN DUCT, SECTION
DUCT TRANSITION
OR REGISTER
STANDARD RADIUS ELBOW
SHORT RADIUS VANED ELBOW (ALL SHORT RADIUS ELBOWS ARE
TO HAVE VANES PER SMACNA)
CEILING RETURN AIR REGISTER OR TRANSFER AIR GRILLE
INDICATES A RECTANGULAR DUCT SIZE (WIDTH x DEPTH)
INDICATES A FLAT OVAL DUCT SIZE (WIDTH x DEPTH)
INDICATES A ROUND DUCT SIZE
IF THROW IS SOMETHING OTHER THAN 4-WAY)CEILING DIFFUSERS (ARROWS DENOTE THROW PATTERN
DUCTED EXHAUST REGISTER
SIDEWALL EXHAUST OR RETURN AIR GRILLE
SIDEWALL SUPPLY REGISTER
T
ACCESS DOOR
SEE CONTROL DRAWINGS FOR TYPEROOM THERMOSTAT/TEMP. TRANSMITTER LOCATION ONLY
DUCT MOUNTED STATIC PRESSURE PROBE
###
XX - ## NUMBERS REFER TO SPECIFIC EQUIPMENT
SYMBOL INDICATES NEW EQUIPMENT
EQUIPMENT SYMBOLS
IDENTIFIED IN EQUIPMENT SCHEDULE
CFM
SYMBOL INDICATES GRILLE OR
DIFFUSER IDENTIFIED IN EQUIPMENT
SCHEDULE
SIDEWALL GRILLE DIMENSION WHERE SHOWN ON
PLANS
LETTERS REFER TO THE EQUIPMENT TYPE
ACCESS DOOR
AIR CONDITIONING UNIT
ABOVE FINISHED FLOOR
ACOUSTIC LINING
ACU
AD
AFF
AL
BOP
BOD
BOTTOM OF PIPE
BOTTOM OF DUCT
CUBIC FEET PER MINUTE CLEANOUT
CFM CO
MOTOR CONTROL CENTERMCC
NOT APPLICABLE
NOT IN CONTRACT
NUMBER (QUANTITY)
NA
NIC
NO.
OUTSIDE AIR
OPPOSED BLADE DAMPER
OA
OBD
PSIG
PRV PRESSURE REDUCING VALVE
POUNDS PER SQUARE INCH GAGE
QUADRANT
QUANTITYQTY
QUAD
RETURN AIRR.A.
SMOKE CONTROL DAMPER SCD
EXHAUST EXH
FLAT TOP
FEET PER MINUTE
FT
FPM
DEGREES FAHRENHEIT
FAN COIL UNIT
FLOOR DRAIN
FLEXIBLE
FCU FD
FLEX
°F
TOPT TOP OF PIPE TRAPEZE
VENT THRU ROOFVTR
VEL
VAV VARIABLE AIR VOLUME
VELOCITY
GALLONS PER HOUR GALLONS PER MINUTE
GPH GPM
HAND DAMPER (VOLUME DAMPER)
HIGH EFFICIENCY PARTICULATE AIR (FILTER)
HD
HEPA
INCHESIN
MAKE-UP WATER
CONDENSATE DRAIN
PIPING SYMBOLS
PLUG VALVE
VALVE SYMBOLS
GATE VALVE
GLOBE VALVE
SAFETY VALVE OR PRESSURE RELIEF
MANUAL AIR VENT
BALL VALVE
VALVE IN RISE
WCO
WH
WALL CLEANOUT
WALL HYDRANT
V
VAC
VOLTS
VOLTS, ALTERNATING CURRENT
TP TOTAL PRESSURE (INCHES OF WATER)
SP STATIC PRESSURE (INCHES OF WATER)
Rh
RPM
RELATIVE HUMIDITY
REVOLUTIONS PER MINUTE
KWH
KW KILOWATT
KILOWATT HOUR
HB HOSE BIBB
FS FLOOR SINK
FCO FLOOR CLEANOUT
ENT ENTERING
DX DIRECT EXPANSION
BTU
BTUH
BRITISH THERMAL UNIT
BTU PER HOUR
BHP BRAKE HORSEPOWER
DUCTWORK SYMBOLS
SECTION SYMBOLS
SDVV SINGLE DUCT VARIABLE VOLUME
ST SOUND TRAP
TYP. TYPICAL
CONT. CONTINUATION
D DRAIN
EMCS ENERGY MANAGEMENT CONTROL SYSTEM
FT. FEET
F.G. FILTER GAUGE
FB FLAT BOTTOM
MA MAIN AIR (CONTROLS)
NOTE: NOT ALL ABBREVIATIONS AND SYMBOLS
APPLY TO THIS PROJECT.
COMBINATION FIRE/SMOKE DAMPER
DUCTED RETURN REGISTER
DUCT MOUNTED SMOKE DETECTOR
1HR FIRE BARRIER (VERIFY WITH ARCHITECTURAL
DRAWINGS)
CD
ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN FURRED CHASES OR
SUSPENDED CEILINGS, UNLESS OTHERWISE NOTED.
PROVIDE ACCESS PANELS OR DOORS IN INACCESSIBLE CEILINGS AND/OR CHASES FOR ALL VALVES,
TRAPS, DAMPERS, CLEANOUTS, COILS, FANS, CONTROLS, ETC. THEY SHALL BE FURNISHED UNDER
DIVISION 23 AND INSTALLED UNDER THE ARCHITECTURAL SPECIFICATION. ACCESS DOOR RATING SHALL
MATCH CLASSIFICATION OF WALL AND CEILING FIRE RATING.
COORDINATE THE LOCATION OF ALL DIFFUSERS, GRILLES, REGISTERS, ACCESS DOORS, ETC., WITH THE
ARCHITECTURAL REFLECTED CEILING PLAN(S).
ALL ROUND RUNOUTS AND DROPS TO DIFFUSERS SHALL BE THE SAME NOMINAL SIZE AS THE SCHEDULED
DIFFUSER NECK SIZE.
THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR INDICATED. ALL DUCT SIZES
SHOWN ON DRAWINGS ARE NET INSIDE DIMENSIONS. PROVIDE ONE INCH ACOUSTICAL LINING IN LOW
VELOCITY RECTANGULAR DUCTWORK UNLESS NOTED OTHERWISE ON THE DRAWINGS. SEE
SPECIFICATIONS.
PROVIDE TURNING VANES IN ALL SQUARE ELBOWS, EXCEPT TRANSFER AIR SOUND ELBOWS.
THE CFM OF EACH DIFFUSER, REGISTER, ETC., IS INDICATED AS A NUMBER NEXT TO THE SYMBOL
DESIGNATION ON THE DRAWINGS.
REFER TO THE ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF ALL FIRE RATED AND/OR SMOKE
RATED WALLS AND ASSEMBLIES. PROVIDE APPROVED FIRE DAMPERS IN ALL REQUIRED PENETRATIONS
FOR DUCTWORK, GRILLES, REGISTERS AND DIFFUSERS. ALL PIPE AND DUCTWORK PENETRATIONS OF
FIRE, SMOKE AND FULL HEIGHT WALLS SHALL BE CAULKED AIRTIGHT TO THE ADJACENT STRUCTURE BY
MEANS OF U.L. APPROVED FIRE PROOF CAULKING MATERIAL.
CONTRACTOR SHALL COORDINATE ALL DUCTWORK, PIPING, PLUMBING AND FIRE PROTECTION PIPING
WITH STRUCTURAL AND ELECTRICAL SYSTEMS AND SHALL PROVIDE NECESSARY OFFSETS TO AVOID
CONFLICTS AND TO MAINTAIN EQUIPMENT ACCESS AND SERVICEABILITY.
CONTRACTOR SHALL FURNISH ALL NECESSARY STRUCTURES, INSERTS, SLEEVES, AND HANGING DEVICES
FOR INSTALLATION OF MECHANICAL AND PLUMBING EQUIPMENT, DUCTWORK AND PIPING, ETC.
CONTRACTOR SHALL COORDINATE WITH GENERAL CONTRACTOR AND ALL BUILDING TRADES TO AVOID
CONFLICTS AND TO MAINTAIN EQUIPMENT ACCESS AND SERVICEABILITY.
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL NECESSARY MISCELLANEOUS ANGLES,
CHANNELS, UNISTRUT, ETC., AS MAY BE REQUIRED TO ADEQUATELY SUPPORT THE MECHANICAL PIPING,
DUCTWORK, AND EQUIPMENT IN A MANNER APPROVED BY THE ARCHITECT, WHICH WILL NOT OVERLOAD
THE BUILDING STRUCTURAL SYSTEM.
CONTRACTOR SHALL PROVIDE RETURN AIR OR TRANSFER AIR OPENINGS IN FULL HEIGHT WALLS SIZED AT
350 FPM (UNLESS OTHERWISE SPECIFICALLY SHOWN ON THE DRAWINGS) TO CREATE AND/OR MAINTAIN A
RETURN AIR PATH AS REQUIRED. FIRE DAMPERS AND/OR SMOKE DAMPERS SHALL BE PROVIDED IN SUCH
OPENINGS WHERE REQUIRED BY NOTE #10.
SEAL ALL TRANSVERSE JOINTS, LONGITUDINAL SEAMS, DUCT WALL PENETRATIONS AND FITTING
CONNECTIONS ON ALL DUCT SYSTEMS.
MECHANICAL ITEMS SUCH AS ROOF DRAINS, FLOOR DRAINS, PLUMBING FIXTURES, ETC. SHOWN ON THE
ARCHITECTURAL DRAWINGS BUT NOT SHOWN ON THE MECHANICAL DRAWINGS SHALL BE INCLUDED IN
THE PROJECT. THESE ITEMS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR INCLUSION
IN ADDENDUM.
1.
2.
3.
4
5
6.
7.
8.
9.
10.
11.
12.
13.
14.
F.DPR
S.DPR
F/S DPR
XX - ###x#
SINGLE LINE PIPE SYMBOLS
ELBOW - DOWN
ELBOW - UP
PIPE RISE - DROP
ELBOW - DOWN TO TEE
TEE - DOWN
TEE - UP
ELBOW - UP TO TEE
END CAP
FLEX CONNECTION
PIPE REDUCER - CONCENTRIC
PIPE REDUCER - ECCENTRIC
PIPE STRAINERUNION - SCREWED
AIR VENT - AUTOMATIC
AIR VENT - MANUAL
GAUGE - DIFFERENTIALGAUGE - PRESSURE
GAUGE - PRESSURE
GAUGE - PRESSURE WITH COCK
GAUGE - TEMPERATURE
PIPE - CAPPED WITH SHUT-OFF VALVE
PIPE ANCHOR
PIPE EXPANSION JOINT
P
PS
A
F
PS
TS
PIPE GUIDE
SENSOR - FLOW
SWITCH - FLOW
SWITCH - PRESSURE
SWITCH - TEMPERATURE
TEMPERATURE - PRESSURE TEST FITTING
THERMOMETER
THERMOMETER WELL
SECTION NUMBER
DRAWING NUMBER WHERE DETAILED
DETAIL LOCATION
DRAWING NUMBER WHERE DETAILED
X#X###
X#/X### DETAIL LOCATION X#
SECTION LOCATION X#SECTION
DETAIL
SCALE
SCALE
FITTING SYMBOLS
RS REFRIGERATION SUCTION
RL REFRIGERATION LIQUID
VALVE - BALL LEVER
VALVE - GATE MANUAL
VALVE - GLOBE MANUAL
VALVE - GLOBE LEVER
VALVE - PLUG LEVER
VALVE - PLUG MANUAL
VALVE - PRESSURE RELIEF
R REFRIGERATION
MU
DRAIND
SINGLE LINE PIPE SYMBOLS
THE DEMOLITION DRAWINGS REFLECT INFORMATION ON EXISTING BUILDING SERVICES GATHERED BY SITE
INSPECTION, DISCUSSIONS WITH MAINTENANCE PERSONNEL AND PREVIOUS CONSTRUCTION DRAWINGS. THE
EXACT LOCATION, ARRANGEMENT, AND SIZES OF PIPE LINES AND DUCTWORK IN THE EXISTING BUILDING MAY BE
DIFFERENT FROM THAT SHOWN ON THESE DRAWINGS.
THE CONTRACTOR SHALL COORDINATE THE SHUTDOWN OF EXISTING BUILDING SERVICES FOR REMOVALS
WITH OWNER AUTHORIZED REPRESENTATIVE AND SHALL CONFORM TO THEIR REQUIREMENTS.
DISRUPTION OF NORMAL SCHOOL ACTIVITIES ARE TO BE KEPT TO AN ABSOLUTE MINIMUM. DUST, DEBRIS, AND
FUMES SHALL BE CONTROLLED SO AS NOT TO AFFECT THE HEALTH AND SAFETY OF OCCUPIED AREAS WITHIN
THE SCHOOL CENTER WHICH ARE OUTSIDE THE AREA OF WORK. COORDINATE WITH THE ARCHITECT AND THE
OWNER'S REPRESENTATIVE WITH REGARD TO ALL ACTIVITIES TO BE CONDUCTED OUTSIDE OF THE REMODEL
AREA WHICH MAY AFFECT THE OPERATION OF THE SCHOOL.
THE CONTRACTOR SHALL PRESENT AN AREA BY AREA WORK PLAN WELL IN ADVANCE TO THE ARCHITECT AND
THE OWNER'S AUTHORIZED REPRESENTATIVE FOR APPROVAL PRIOR TO BEGINNING WORK. THE WORK PLAN
SHALL INCLUDE AN OUTLINE OF ALL ACTIVITIES OF ALL SUBCONTRACTORS. THE CONTRACTOR SHALL
COORDINATE WITH THE OWNER'S AUTHORIZED REPRESENTATIVE TO ESTABLISH ACCEPTABLE ROUTING AND
ACCESS WITHIN THE SCHOOL FOR MATERIALS REQUIRED FOR THE NEW INSTALLATION.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF ALL TRADES INCLUDING MECHANICAL,
PLUMBING, ELECTRICAL, FURNITURE, AND ARCHITECTURAL. ANY DISCREPANCIES SHALL BE REPORTED
IMMEDIATELY TO THE ARCHITECT PRIOR TO START OF WORK.
ALL NEW TO EXISTING DUCT CONNECTIONS SHALL BE FIELD VERIFIED PRIOR TO ORDERING AND FABRICATING
NEW DUCTWORK OR DAMPERS
A
B
C
D
E
F
GENERAL DEMO NOTES:
ACCESS DOORAD
AIR HANDLING UNIT AHU
COMPRESSED AIR CONDENSATE DRAIN
CA CD
DETAIL REFERENCE
SECTION AND DETAIL TITLES
2HR FIRE BARRIER (VERIFY WITH ARCHITECTURAL
DRAWINGS)2HR SMOKE BARRIER (VERIFY WITH ARCHITECTURAL
DRAWINGS)
RISE IN DUCT
TFOE
C
I N
EI
L D
ESN
SAXATS
E
RE
ENIGN
LAOSSEFO
RP
ET
ABBAS SHIRIAN
102840
PROJECT
1
A
2 3 4 5
B
C
D
1 2 3 4 5
SEAL
REVISIONS
SHEET NO
DRAWING NAME
PROJECT NO:
REVIEWED BY
DATE
VE
GA
ISD
CA
RE
ER
TE
CH
NO
LOG
Y B
UIL
DIN
G20
0 LO
NG
HO
RN
ST
.V
EG
A, T
X 7
9 092
14-0424.002
01.29.2016
Addendum 01
DATE
1/29
/201
6 11
:24:
08 A
M
M001a
MECHANICALLEGEND
RLM
Digitally signed by Abbas ShirianDate: 2016.01.29 11:29:11-07'00'
AG-RTU-01
20"x
20"
32"x18"
RTU ON16" CURB
20"X20" TO AG BLDG
1" ACOUSTICAL LINING
2" RIGID POLYSTYRENEINSULATION
4" THICK CONCRETEHOUSEKEEPING PAD
RTU ON16" CURB
AG-RTU-0132"x18"
18"x
18"
2" RIGID POLYSTYRENEINSULATION
18"X18" TO AG BLDG
SMOKE DETECTOR ANDSAMPLING TUBES
4" THICK CONCRETEHOUSEKEEPING PAD
TFOE
C
I N
EI
L D
ESN
SAXATS
E
RE
ENIGN
LAOSSEFO
RP
ET
ABBAS SHIRIAN
102840
PROJECT
1
A
2 3 4 5
B
C
D
1 2 3 4 5
SEAL
REVISIONS
SHEET NO
DRAWING NAME
PROJECT NO:
REVIEWED BY
DATE
VE
GA
ISD
CA
RE
ER
TE
CH
NO
LOG
Y B
UIL
DIN
G20
0 LO
NG
HO
RN
ST
.V
EG
A, T
X 7
9 092
14-0424.002
01.29.2016
Addendum 01
DATE
1/29
/201
6 11
:24:
10 A
M
M301a
MECHANICALSECTIONS
RLB
SCALE: 3/8" = 1'-0"1 AG SHOP - RTU DUCTWORK - 01SCALE: 3/8" = 1'-0"2 AG SHOP - RTU DUCTWORK - 02
SECTION A
SECTION B
W X L
ROUND
DUCT
DIAMETER
MAJOR AXIS
WHEN MOUNTED
ON MAJOR AXIS
MINOR AXIS
WHEN MOUNTED
ON MAJOR AXIS
W
L
D 3/4D
FLAT OVAL DUCT
ROUND OR FLAT OVAL DUCT, 8" +
8" X 12"
12" X 12"
14" X 20"
8" - 12"
13" X 18"
19" +
8" - 16"
17" - 24"
25" +
8" - 11"
12" - 13"
14" +
W
SECTION C
RECTANGULAR DUCTS
NOTE:
DUCT ACCESS DOORS SHALL
BE PROVIDED AT EACH
FIRE DAMPER, SMOKE DAMPER,
DUCT MOUNTED EQUIPMENT,
AND AS REQUIRED FOR DUCT
CLEANING AND INSPECTION
DUCT DIMENSION ON WHICH
ACCESS DOOR IS PLACED
OUTSIDE FRAME
W X L
6" - 8"
9" - 12"
13" - 15"
16" - 33"
34" - 66"
67" +
5" X 12"
8" X 8"
12" X 12"
14" X 14"
(2) 14" X 14"
(3) 14" X 14"
SCALE = NONE
DUCT ACCESS DOOR DETAIL
BOLT AND WING NUT AT MAX.
3" O.C.
TACK WELD BOLT TO DUCT
PROVIDE GASKET BETWEEN
DUCT AND ACCESS DOOR
HANDLE
INSULATE COVER AS REQUIRED
BY DUCT INSULATION SPEC.
MIN. 20 GA FRAME WELDED TO
DUCT
PRESSURE SENSITIVE LATCH
FOR VACUUM RELEASE
RETAINER CHAIN
MIN. 22 GA GALV. STEEL
FRAME
FRAME SECURED TO DUCT
WITH 5/8" NOTCHED
KNOCK-OVER EDGES ON ALL
SIDES
CONTINUOUS HINGE
CAM LATCH
MIN. 22 GA DOOR
C5
C
B
B
3
1
4
5
2
9 7
6
7
4
12
9
10
13
11
10
3
9L
1
2
3
4
5
6
7
8
9
10
11
12
13
A5SCALE = NONE
20 30
30
RISE
PLAN
NOTES
1. ANGLE A=30 MAXIMUM WHEN AIR FLOWS IN
DIRECTION OF ARROS. (SUPPLY AIR)
2. ANGLE A=15 WHEN AIR FLOWS IN OPPOSITE
DIRECTION OF ARROS (R.A. OR EXHAUST)
20°
A°
A°
A°
A°
3.73xH
FBFT
FT FB
A°A°
A°
A°
PLAN VIEW PLAN VIEW PLAN VIEW
TRANSITION
w/ EQUIPMENT
ELEVATION
PLAN
DUCT OFFSET
FT FB
FBFT
A°
A° A°
A°
ELEVATION ELEVATION ELEVATION BRANCH DUCT
PLAN
45°
LOW PRESSURE DUCT FITTING DETAIL
W
1/2 W
(4"MIN.)
PLAN A
A
B
C
(1) NECK DIA. MIN.
PROVIDE HAND DAMPER
WITH ACCESS DOOR
WHERE SHOWN ON PLANS
BRANCH
DUCT
BRANCH
MAIN
FIXED CEILINGS
SECTION A
FLEX DUCT. DIAMETER EQUAL
TO DIFFUSER NECK SIZE (MAX.
LENGTH 4'-0")
SPIN IN FITTING
W/HAND DAMPER
SECTION B
LAY-IN CEILINGS
PLAN B
RIGID DUCT WHERE
RUN-OUT EXCEEDS
4'-0"
PROVIDE HAND DAMPER
WITH ACCESS DOOR
WHERE SHOWN ON
PLANS
SHEET METAL
PLENUM
RIGID DUCT WHERE
RUN-OUT EXCEEDS
4'-0"FLEX. DUCT FOR
LAY-IN CEILING
APPLICATION
EXHAUST/DUCTED RETURN
GRILLE. SEE FLOOR PLAN
FOR SIZE, TYPE, AND
LOCATION
SCALE = NONEC3
DIFFUSER AND REGISTER CONNECTION DETAIL
SECTION C
RETURN/EXHAUST REGISTER
FOR LAY-IN AND FIXED CEILINGS
PLAN C
SCALE = NONEB3GROUND MOUNTED DUCT SUPPORT DETAIL
P-1000
UNISTRUT
3"X3"X1/16"
STEEL PLATE TYP.
MIN. 6" GREATER THAN
DUCT DIMENSION AS
SHOWN ON PLANS
6"x6"x1/4" PLATE
4'-0" O.C.
12'-0" O.C.
SCALE = NONEC1FLUE THRU ROOF DETAIL
1
1
FLUE HEIGHT SHALL BE NO LESS THAN 3'-0" ABOVE THE HORIZONTAL ROOF
PLANE. SHOULD ANY OBSTRUCTION WITHIN A 10 FOOT RADIUS OF THE FLUE
PROJECT ABOVE THE HORIZONTAL ROOF PLANE, THE FLUE SHALL EXTEND TO 3'-0"
ABOVE THE OBSTRUCTION. OBSTRUCTIONS INCLUDE BUT ARE NOT LIMITED TO
ITEMS SUCH AS PARAPETS, WALLS, AIR INTAKES, AND ROOF SLOPES.
OPEN BELOW
RAIN CAP
FLASH AND
COUNTERFLASH
METAL ROOF
JACK
TYPE L FLUE CAP
TYPE B VENT
SOLDER
METAL RAIN CAP
1" MIN. CLEARANCE
CEILING
9"
SCALE = NONE
IN-LINE FAN DETAILA1
PLAN
ELEVATION
1
4 3
27
6
12
5
43
8
7
IN-LINE FAN
SIDE MOUNTED MOTOR WHERE CEILING SPACE IS LIMITED
ACOUSTICALLY LINED DUCT UNLESS NOTED OTHERWISE ON PLAN
FLEXIBLE DUCT CONNECTION (TYPICAL)
TYPICAL VIBRATION ISOLATOR
1/2" STEEL ALL-THREAD SUPPORT RODS SECURELY ANCHORED
TO STRUCTURE ABOVE IN A MANNER APPROVED BY THE
STRUCTURAL ENGINEER
BELT GUARD ON BELT-DRIVE FANS (TYPICAL)
ACCESS DOOR IN HOUSING TO FAN
1
2
3
4
5
6
7
8 CLEAR FROM ALL PIPING
CONTAINING WATER
6'-0" OR TO
SURFACE CLEAR FOR
CONDUIT
RECESSED OF SURFACE
MOUNTED ELECTRICAL
PANEL
6'-0" OR TO
SURFACE CLEAR FOR
CONDUIT
STRUCTURE
CEILING WALL
42" MINIMUM IN
COMPLIANCE WITH
ARTICLE 110 IN THE NEC
3'-6"x6'-6"
HIGH
MINIMUM
FLOOR
EXCLUSIVELY DEDICATED
ELECTRICAL SPACE. NO PIPING OR
DUCT SHALL BE ALLOWED WITHIN
THESE AREAS
ELECTRICAL SPACE. NO WATER PIPING
SHALL BE ALLOWED WITHIN THESE
AREAS
CLEARANCE REQUIREMENTS AT ELECTRICAL PANELSA3 SCALE = NONE
TFOE
C
I N
EI
L D
ESN
SAXATS
E
RE
ENIGN
LAOSSEFO
RP
ET
ABBAS SHIRIAN
102840
PROJECT
1
A
2 3 4 5
B
C
D
1 2 3 4 5
SEAL
REVISIONS
SHEET NO
DRAWING NAME
PROJECT NO:
REVIEWED BY
DATE
VE
GA
ISD
CA
RE
ER
TE
CH
NO
LOG
Y B
UIL
DIN
G20
0 LO
NG
HO
RN
ST
.V
EG
A, T
X 7
9 092
14-0424.002
01.29.2016
Addendum 01
DATE
1/29
/201
6 11
:24:
13 A
M
M501a
MECHANICALDETAILS
RLM
LA LEVEL ALARM
AT ANALYTICAL TRANSMITTER
AY ANALYTICAL SIGNAL CONVERTER
ACV ANALYTICAL CONTROL VALVE
AIT ANALYTICAL INDICATING CONTROLLER
EY VOLTAGE SIGNAL CONVERTER
IY CURRENT SIGNAL CONVERTER
HS HAND SWITCH
FIT FLOW INDICATING TRANSMITTER
FET FLOW ELEMENT\TRANSMITTER
ESL VOLTAGE SWITCH LOW (24 VAC OR LESS)
II CURRENT INDICATOR
IT CURRENT TRANSMITTER
IS CURRENT SWITCH
IA CURRENT ALARM
FA FLOW ALARM
HSI HAND SWITCH INDICATOR
HK MANUAL VARIABLE CONTROL
FY FLOW SIGNAL CONVERTER
FT FLOW TRANSMITTER
FS FLOW SWITCH
FI FLOW INDICATOR
FE FLOW ELEMENT
FCV FLOW CONTROL VALVE
ET VOLTAGE TRANSMITTER
ES VOLTAGE SWITCH (CONTROL RELAY)
EA VOLTAGE ALARM
EI VOLTAGE INDICATOR
PY PRESSURE SIGNAL CONVERTER
PDT PRESSURE DIFFERENTIAL TRANSMITTER
PS PRESSURE SWITCH
PA PRESSURE ALARM
PT PRESSURE TRANSMITTER
PIT PRESSURE INDICATING TRANSMITTER
PIS PRESSURE INDICATING SWITCH
PI PRESSURE INDICATOR
PDS PRESSURE DIFFERENTIAL SWITCH
PDI PRESSURE DIFFERENTIAL INDICATOR
PCV PRESSURE CONTROL VALVE
MV MANUAL HAND VALVE
LT LEVEL TRANSMITTER
LS LEVEL SWITCH
LE LEVEL ELEMENT
LY LEVEL SIGNAL CONVERTER
LIT LEVEL INDICATING TRANSMITTER
LIC LEVEL INDICATING CONTROLLER
LCV LEVEL CONTROL VALVE
LC LEVEL CONTROLLER (STAND ALONE)
VA VIBRATION ALARM
VS VIBRATION SWITCH
XV SOLENOID VALVE
YS SMOKE DETECTOR
VA VIBRATION ALARM
VS VIBRATION SWITCH
YCD SMOKE DAMPER
TT TEMPERATURE TRANSMITTER
TS TEMPERATURE SWITCH
TIC TEMPERATURE INDICATING CONTROLLER
TIT TEMPERATURE INDICATING TRANSMITTER
TI TEMPERATURE INDICATOR
TET TEMPERATURE ELEMENT TRANSMITTER
TE TEMPERATURE ELEMENT
TCV TEMPERATURE CONTROL VALVE
TC TEMPERATURE CONTROLLER
TA TEMPERATURE ALARM
SCM SPEED CONTROL MANUAL
TSL FREEZE STAT
SC SPEED CONTROL
INSTRUMENTATION SOCIETY OF AMERICA TABLE
INSTRUMENTATION TYPE ABBREVIATION LIST
AIC ANALYTICAL INDICATING CONTROLLER
AET ANALYTICAL ELEMENT TRANSMITTER
A
AC ANALYTICAL CONTROLLER
AI ANALYTICAL INDICATOR
AE ANALYTICAL ELEMENT
AA ANALYTICAL ALARM
CODE DESCRIPTION
VARIABLE
FINAL CONTROL ELEMENT
CODE DESCRIPTION
KC TIME CLOCK
JY POWER SIGNAL CONVERTER
JIT POWER INDICATING TRANSMITTER
TOTALIZE
CHANGE
CONNECTION
CODE DESCRIPTION
VIEWING DEVICE
PRIMARY ELEMENT
NORMALLY CLOSED OVERLOAD CONTACTS
ABBREVIATIONS
IA INSTRUMENTATION AIRDDC DIRECT DIGITAL CONTROLC COMMON VALVE PORTF.O FAIL OPENF.C FAIL CLOSEDSR SPRING RANGETR THROTTLING RANGEPH PREHEATHR HEAT RECOVERYCPA CONTROL POINT ADJUSTMENTSPDT SINGLE POLE DOUBLE THROWDPDT DOUBLE THROW DOUBLE POLEDA DIRECT ACTINGRA REVERSE ACTING
EP COIL IN MOTOR STARTER
TRANSFORMER
R
C
OL
HOA
CONTACT NORMALLY OPEN
PILOT LIGHT (COLOR INDICATION)
COIL IN MOTOR STARTER
CONTACT NORMALLY CLOSED
SWITCH
FUSE
HAND-OFF-AUTO SWITCH
I UNDEFINED INTERLOCK LOGIC
GENERAL INSTRUMENT OR FUNCTION SYMBOLS
FIELD
MOUNTED MOUNTED
PANEL AUXILIARY
LOCATION
ACCESSIBLE INACCESSIBLE
LOCATION
AUXILIARY
DISCRETE INSTRUMENTS
SHARED DISPLAY, SHARED CONTROL
PROGRAMMABLE LOGIC CONTROL
OR DIRECT DIGITAL CONTROL
COMPUTER FUNCTION
DUAL (MULTI)
FUNCTION INSTRUMENT
INDICATING LIGHTS, ALARMS OR HORNS
CONTROL VALVE BODY/ DAMPER SYMBOLS
GENERAL SYMBOL
ANGLE
BUTTERFLY
ROTARY VALVE
THREE - WAY
FOUR - WAY
GLOBE
PARALLEL BLADE
OPPOSED BLADE
TEMPERATURE
DUCT MOUNTED AVERAGING
WELL MOUNTED
ELEMENT/SENSOR ELEMENT/SENSOR
ELEMENT/SENSOR ELEMENT/SENSOR
SURFACE MOUNTED
PRESSURE
DIRECT MOUNTED
ELEMENT/SENSOR
DIFFERENTIAL PRESSURE
ELEMENT/SENSOR
LEVEL
FLOAT TYPE PADDLE TYPE
LEVEL TRANSMITTER
TANK MOUNTED
SONIC OR
RADIOACTIVE
FLOW
ORIFICE PLATETURBINE OR
PROPELLER
TYPE
SENSOR
VORTEX
TYPE
TARGET
SENSOR TRANSMITTER
MAGNETIC
TYPE
M
TRANSIT TIME
SONIC FLOWMETER
"DOPPLER" OR
~
FLOW ARROW
XXX INDICATES
AIR TYPE
INSTRUMENT NAMING CONVENTION
XXX - FUNCTION ID
NNN - DEVICE NUMBER
ZZZ - USER CHOICE
CURRENT
CURRENT SENSOR/TRANSMITTER
LINE LEGEND
INTERNAL SYSTEM LINK
ELECTRICAL SIGNAL
PNEUMATIC SIGNAL
YI EQUIPMENT STATUS
YA EQUIPMENT ALARM
ZI POSITION INDICATOR
ZS POSITION SWITCH
ZC POSITION CONTROL
AAA - UNIT ASSOCIATION OR
PROCESS CODE
PROCESS CODES
TW COOLING TOWER OR CONDENSER WATERCHW CHILLED WATERSCHW SECONDARY CHILLED WATERHW HOT WATERSHW SECONDARY HOT WATERSTM STEAM
AAA-NNN
XXX
ZZZ
NT HUMIDITY TRANSMITTER
FMS SYSTEM OPERATING CONSTRAINTS
THE FMS CONTROL SYSTEM SHALL OPERATE WITHIN THE FOLLOWING SYSTEM CONSTRAINTS FOR CONTROL:
SUPPLY AIR DRYBULB TEMPERATURE
MIXED AIR DRYBULB TEMPERATURE
WATER TEMPERATURE
DUCT STATIC PRESSURE
SUPPLY/ RETURN AIR VOLUME
OUTSIDE AIR/ RELIEF AIR VOLUME
BUILDING PRESSURE
ROOM TEMPERATURE
ROOM AIR VOLUME
HUMIDITY LEVEL
WATER TEMPERATURE
WATER DIFFERENTIAL PRESSURE
+/- 0.5°F OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
~
~
~
FT
~
~
FT
~
~
FE
~
~
FE
~
~
FEFE
~
~
~
~
~
L
L
L
TE
L
~
~
~
~
PD
TETE
TE
~
~~
~
~
~
~
~
~
~
~~
~
~
~
+/- 0.5°F OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
+/- 1.0 PSI OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
+/- 0.5°F OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
+/- 0.1" W.C. OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
+/- 2.5% OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
+/- 2.5% OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
+/- 0.01" W.C. OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
+/- 1.0°F OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
+/- 2.5% OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
+/- 2.5% R.H. OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
+/- 1.0°F OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
FIRST LETTER SUCCEEDING LETTERS (3)
MEASURING OR MODIFIER READOUT OR OUTPUT MODIFIER
INITIATING PASSIVE FUNCTION FUNCTION
ANALYSIS ALARM
B BURNER FLAME USER CHOICE USER CHOICE USER CHOICE
C CONDUCTIVITY CONTROL (13)
D DENSITY DIFFERENTIAL
E VOLTAGE SENSOR
F FLOW RATE RATIO FRACTION
G GAUGE GLASS,
H HAND HIGH
I CURRENT INDICATE
J POWER SCAN
K TIME TIME RATE OF CONTROL STATION
L LEVEL LIGHT LOW
M MOTION MOMENTARY MIDDLE
INTERMEDIATE
N HUMIDITY USER DEFINED USER DEFINED USER DEFINED
O USER CHOICE ORIFICE RESTRICTION
P PRESSURE, VACUUM POINT (TEST)
Q QUANTITY INTEGRATE,
R RADIATION RECORD
S SPEED, FREQUENCY SAFETY SWITCH
T TEMPERATURE TRANSMIT
U MULTI-VARIABLE MULTI-FUNCTION MULTI-FUNCTION MULTI-FUNCTION
V VIBRATION, MECHANICAL VALVE, DAMPER
ANALYSIS LOUVER
W WEIGHT, FORCE WELL
X UNCLASSIFIED X-AXIS UNCLASSIFIED UNCLASSIFIED UNCLASSIFIED
Y EVENT, STATE OR Y-AXIS RELAY, COMPUTE
PRESENCE CONVERT
Z POSITION Z-AXIS DRIVER, ACTUATOR
DIMENSION UNCLASSIFIED
TFOE
C
I N
EI
L D
ESN
SAXATS
E
RE
ENIGN
LAOSSEFO
RP
ET
ABBAS SHIRIAN
102840
PROJECT
1
A
2 3 4 5
B
C
D
1 2 3 4 5
SEAL
REVISIONS
SHEET NO
DRAWING NAME
PROJECT NO:
REVIEWED BY
DATE
VE
GA
ISD
CA
RE
ER
TE
CH
NO
LOG
Y B
UIL
DIN
G20
0 LO
NG
HO
RN
ST
.V
EG
A, T
X 7
9 092
14-0424.002
01.29.2016
Addendum 01
DATE
1/29
/201
6 11
:24:
27 A
M
MI001a
MECHANICALINSTRUMENTATIONLEGEND
RLM
~
~
ESEF-01
ISEF-01
EF-01
HS
EF-01
II
TITFCU-01
TTFCU-01
FCU-01
TI
FCVRTU-02
YSRTU-01
TTRTU-01
PDIRTU-01
FCVRTU-01
TTRTU-03
TTRTU-04I
FU
RN
AC
E
X
D
EACH AIR HANDLING UNIT SHALL BE FURNISHED WITH FACTORY DDC CONTROLS FOR THE AIR HANDLING UNIT. THE AIR HANDLING UNIT SHALLBE CONNECTED TO THE FMS THROUGH A FMS COMMUNICATIONS TRUNK USING A BACNET COMMUNICATIONS CONNECTION. THE FMSCONTRACTOR SHALL COORDINATE COMMUNICATIONS REQUIREMENTS WITH THE AIR HANDLING UNIT MANUFACTURER. THE CONTRACTORSHALL PROVIDE INSTALLATION FOR ALL FIELD INSTALLED DEVICES FURNISHED WITH THE MECHANICAL EQUIPMENT. REFER TOSPECIFICATIONS FOR MORE INFORMATION. REFER TO SEQUENCE OF OPERATIONS FOR CONTROL FUNCTIONALITY.
R.A
S.A
FACTORY DDCCONTROL PANEL
E.A
O.A
LOCATE SENSORWHERE SHOWNON THE PLANS
1
LINE
E.A
ST
AR
T/S
TO
P
(DO) ST
AT
US
(DI)
BACKDRAFT
RETURN
CONTROLLER
C
R
AIR
FACTORY
RO
OM
TE
MP
.
(AI)
BARROMETRIC
MS
NC
FMS NETWORK
GENERAL
SYSTEM STATUS DISPLAYTHE FMS SHALL PROVIDE OPERATING STATUS FOR ALL SYSTEMS CONTROLLED BY THE FMS. THE DISPLAYS SHALL INCLUDE ALL POINTS INDICATED ON THE DRAWINGS AND ANY OTHERSREQUIRED TO ACHIEVE THE SEQUENCE OF OPERATIONS. THE FMS SHALL BE ABLE TO INTEGRATE SYSTEM DIAGNOSTICS INTO CONTROL ACTION DECISIONS. THIS SHALL ALSO INCLUDETHE ABILITY TO DESIGNATE INDIVIDUAL UNITS AS BEING IN MAINTENANCE MODE TO AVOID GENERATING ALARMS. ALL SYSTEM CONTROL AND STATUS EVENTS SHALL BE RECORDED, ATTHE OPERATOR'S SELECTION, IN THE FMS EVENT LOG TO FACILITATE TROUBLESHOOTING. ALL DETECTED ALARMS OR FAILURES SHALL INITIATE AN ALARM WITHIN THE FMS.
POWER FAILURE RECOVERYTHE FMS SHALL CONTAIN A POWER FAILURE RECOVERY MODE (OPERATOR ADJUSTABLE). THE POWER FAILURE RECOVERY CAPABILITY SHALL RETURN THE SYSTEM TO ITS LAST STATE(BEFORE THE BUILDING LOST POWER).
OCCUPANCY CONTROLTHE FMS SHALL BE SETUP WITH AN OCCUPANCY SCHEDULE FOR DIFFERENT AREAS OF THE BUILDING. THE OWNER SHALL BE INTERVIEWED BY THE CONTRACTOR AT START-UP TOESTABLISH THESE SCHEDULES. SOME AREAS OF THE BUILDING SHALL BE SETUP TO BE CONTINUOUSLY OCCUPIED.
EMERGENCY OUTDOOR AIR OVERRIDETHE FMS SHALL HAVE AN EMERGENCY OUTDOOR AIR OVERRIDE SWITCH ON THE MAIN GRAPHIC AT THE OPERATOR WORKSTATION WHICH WILL ALLOW THE OPERATOR TO SHUTDOWNTHE OUTSIDE AIR INTAKE DAMPERS AND RELIEF DAMPERS FOR ALL AIR HANDLING UNITS IN THE EVENT THAT TOXIC ODORS ARE DETECTED OUTSIDE. WHEN THE OUTSIDE AIR ANDRELIEF DAMPERS FULLY CLOSE, THE RETURN AIR DAMPER SHALL FULLY OPEN. THE OUTSIDE AIR INTAKE DAMPERS FOR ALL UNITS SHALL REMAIN CLOSED UNTIL THE OPERATORRESETS THE OVERRIDE
PACKAGED ROOFTOP AIR HANDLING UNIT
GENERALTHE AIR HANDLING UNIT SHALL BE FURNISHED WITH A COMPLETE FACTORY PACKAGED DDC CONTROL SYSTEM. THE FMS SHALL INTEGRATE THE AIR HANDLING UNIT CONTROLS INTOTHE FMS USING AN OPEN PROTOCOL COMMUNICATION NETWORK CONNECTION BETWEEN THE TWO SYSTEMS. THE FOLLOWING SEQUENCE OF OPERATIONS SHALL BE USED AS ADESIGN BASIS GUIDELINE FOR CONTROL OF THE UNIT HOWEVER THE EXACT SEQUENCE OF OPERATIONS SHALL BE IN ACCORDANCE WITH THE MANUFACTURER'S STANDARD FACTORYSEQUENCE OF CONTROL FOR THE SPECIFIED UNIT. REFER TO THE AIR HANDLING UNIT MANUFACTURER'S SUBMITTAL AND O&M MANUAL FOR EXACT SEQUENCE DETAILS.
MIXED AIR DAMPER CONTROLTHE AIR HANDLING UNIT CONTROL SYSTEM SHALL MODULATE THE MIXED AIR DAMPERS TO MAINTAIN THE SUPPLY AIR TEMPERATURE AT SET POINT. WHENEVER THE OUTSIDE AIRTEMPERATURE IS GREATER THAN THE RETURN AIR TEMPERATURE AND MECHANICAL COOLING IS REQUIRED, THE MIXED AIR DAMPERS SHALL BE IN THEIR NORMAL POSITION (FULLRETURN AIR WITH MINIMUM OUTSIDE AIR). WHEN THE AIR HANDLING UNIT IS STOPPED, THE CONTROL SYSTEM SHALL CLOSE ALL OUTSIDE AIR DAMPERS AND THE RELIEF DAMPER ANDOPEN THE RETURN AIR DAMPER.
MINIMUM OUTSIDE AIR CONTROLTHE MINIMUM OUTSIDE AIR VOLUME SHALL BE CONTROLLED BY THE AIR HANDLING UNIT CONTROL SYSTEM THROUGH THE MINIMUM OUTSIDE AIR DAMPER POSITION SETPOINT. THECONTROL SYSTEM SHALL NOT MODULATE THE OUTSIDE AIR DAMPER BELOW MINIMUM OUTSIDE AIR DAMPER POSITION SETPOINT. IF THE AIR HANDLING UNIT IS STOPPED, THECONTROL SYSTEM SHALL CLOSE THE DAMPER.
TEMPERATURE CONTROLTHE AIR HANDLING UNIT CONTROL SYSTEM SHALL MODULATE THE GAS FIRED FURNACE AND STAGE THE CONDENSING UNIT TO MAINTAIN THE SPACE TEMPERATURE SETPOINT. THEFMS SHALL PREVENT SIMULTANEOUS HEATING AND COOLING. THE COOLING SETPOINTS SHALL BE 76 °F (ADJUSTABLE) FOR OCCUPIED PERIODS AND 85°F (ADJUSTABLE) DURINGUNOCCUPIED PERIODS. THE HEATING SETPOINTS SHALL BE 72°F (ADJUSTABLE) FOR OCCUPIED PERIODS AND 55°F (A DJUSTABLE) FOR UNOCCUPIED PERIODS.
SUPPLY FAN CONTROLTHE SUPPLY FAN SHALL BE STARTED AND STOPPED BY THE FMS SYSTEM BASED ON AN OCCUPANCY SCHEDULE FOR THE SPACE PROGRAMMED INTO THE FMS. THE FAN SHALLOPERATE CONTINUOUSLY DURING OCCUPIED PERIODS. IF DURING UNOCCUPIED PERIODS, THE SPACE TEMPERATURE RISES ABOVE THE UNOCCUPIED COOLING SETPOINT OR FALLSBELOW THE UNOCCUPIED HEATING SETPOINT, THE AIR HANDLING UNIT SHALL START AND OPERATE TO CHANGE THE SPACE TEMPERATURE 2°F (ADJUSTABLE) BEFORE STOPPING. I FDURING UNOCCUPIED PERIODS, THE SPACE OCCUPANCY SWITCH IS ACTIVATED, THE AIR HANDLING UNIT SHALL START AND OPERATE FOR A PERIOD OF TWO HOURS BEFORE STOPPING.
SUPPLY FAN MONITORINGTHE FAN OPERATION SHALL BE INDICATED TO THE AIR HANDLING UNIT CONTROL SYSTEM THROUGH A CURRENT SWITCH OR OTHER FLOW INDICATOR. IF AN ALARM CONDITION ISDETECTED, THE FMS SHALL INITIATE AN ALARM.
SMOKE DETECTORSA SMOKE DETECTOR LOCATED IN THE SUPPLY AIR STREAM, SHALL STOP THE FAN THROUGH THE FIRE ALARM SYSTEM IF AN ALARM CONDITION IS DETECTED. WHEN THE FAN ISSTOPPED, THE AIR HANDLING UNIT CONTROL SYSTEM SHALL POSITION THE DAMPERS TO THEIR NORMAL STATE.
START/STOP OPTIMIZATION AND MORNING WARM-UPTHE FMS SHALL BE PROGRAMMED WITH A SELF-ADJUSTING START/STOP OPTIMIZATION SEQUENCE WHICH SHALL PROVIDE THE OPTIMUM START TIME FOR THE UNIT IN ORDER TO HAVETHE SPACE TEMPERATURE AT THE OCCUPIED SETPOINT WHEN SCHEDULED OCCUPANCY IS TO OCCUR EACH DAY. IF THE SPACE REQUIRES HEATING TO REACH THE OCCUPIED SPACETEMPERATURE SETPOINT, THE FMS SHALL OPERATE THE UNIT USING A MORNING WARM-UP CYCLE. DURING THE MORNING WARM-UP CYCLE, THE UNIT SHALL OPERATE WITH THEOUTSIDE AIR AND RELIEF AIR DAMPER CLOSED WITH THE RETURN AIR DAMPER FULLY OPEN. THE UNIT SHALL OPERATE THE FURNACE TO MAINTAIN THE SPACE TEMPERATURE ATSETPOINT. ONCE THE SPACE TEMPERATURE OCCUPIED SETPOINT IS REACHED, THE UNIT SHALL RETURN TO NORMAL OCCUPIED CONTROL.
GENERAL EXHAUST FANS
EACH FAN SHALL OPERATE BASED ON THE OCCUPANCY SCHEDULE IN THE FMS. THE FAN SHALL OPERATE CONTINUOUSLY DURING OCCUPIED PERIODS. THE FAN OPERATION SHALL BEINDICATED TO THE FMS THROUGH A CURRENT SWITCH INSTALLED IN THE MOTOR STARTER. IF A FAN FAILURE IS DETECTED, THE FMS SHALL STOP THE FAN AND INITIATE AN ALARM.
TYPICAL SPLIT SYSTEM
EACH UNIT SHALL BE PROVIDED WITH A FACTORY PACKAGED CONTROL SYSTEM WHICH SHALL CONTROL THE UNIT TO MAINTAIN THE SPACE TEMPERATURE AT SETPOINT. THE FMSSHALL MONITOR THE SPACE TEMPERATURE THROUGH A SEPARATE SPACE TEMPERATURE SENSOR AND SHALL INITIATE AN ALARM IF THE SPACE TEMPERATURE RISES ABOVE THESPACE HIGH TEMPERATURE ALARM SETPOINT.
KITCHEN MAKE-UP AIR SYSTEM
MAKE-UP AIR UNIT CONTROLTHE MAKE-UP AIR SYSTEM SHALL BE CONTROLLED THROUGH THE FACTORY PACKAGED CONTROL SYSTEM TO MAINTAIN THE SUPPLY AIR TEMPERATURE AT SETPOINT ANYTIME THEUNIT IS OPERATING. THE FMS SHALL MONITOR THE SUPPLY AIR TEMPERATURE IN THE UNIT AND SHALL INITIATE AN ALARM IF THE SUPPLY AIR TEMPERATURE FALLS BELOW 40°F(ADJUSTABLE). THE OPERATION OF THE KITCHEN HOOD MAKE-UP AIR UNIT WILL BE INTERLOCKED WITH THE OPERATION OF THE KITCHEN HOOD EXHAUST FAN(S) AND FIRESUPPRESSION SYSTEM. UNDER NORMAL OPERATING CONDITIONS- THE MAKEUP AIR UNIT SHALL BE STARTED WITH A SINGLE FAN ON/OFF SWITCH. THE MAKEUP AIR UNIT ANDASSOCIATED KITCHEN HOOD EXHAUST FAN WILL OPERATE TOGETHER.
FIRE SUPPRESSION SYSTEMIF THE HOOD FIRE SUPPRESSION SYSTEM ENTERS A FIRE CONDITION, THE MAKE UP AIR UNIT FAN SHALL BE DE-ENERGIZED. THE HOOD EXHAUST FAN SHALL CONTINUE TO OPERATE (ORSTART OPERATION) UNDER THIS CONDITION. ADDITIONALLY, AN ELECTRICAL SHUNT TRIP CIRCUIT BREAKER AND GAS SOLENOID VALVE SERVING ALL APPLIANCES BELOW THE HOODSHALL DE-ENERGIZED REMOVING POWER AND GAS SERVICE TO THE APPLIANCES.
TYPICAL EXHAUST FAN CONTROL DIAGRAM
TYPICAL SPLIT SYSTEM CONTROL DIAGRAM
SHEET KEYED NOTES1. THE PACKAGED ROOFTOP UNITS SHALL BE CONNECTED TO
THE FMS NETWORK THROUGH A BACNET NETWORKCONNECTION AS INDICATED. THE CONTRACTOR SHALLCOORDINATE WITH THE UNIT MANUFACTURER AND SUBMIT APROPOSED LIST OF POINTS FOR REVIEW AND APPROVAL PRIORTO INSTALLATION. THE FOLLOWING POINTS SHALL BEINTEGRATED INTO AND MONITORED BY THE FMS IF AVAILABLEIN THE UNIT CONTROLLER.
A. SYSTEM SETPOINTSB. SYSTEM DIAGNOSTICSC. SYSTEM SENSOR INPUTSD. SUPPLY FAN MODE STATUSE. SUPPLY FAN STATUSF. UNIT HEAT/COOL MODEG. ZONE TEMPERATUREH. ECONOMIZER POSITIONI. MINIMUM OUTSIDE AIR DAMPER POSITIONJ. ECONOMIZER SETPOINTK. ON/OFF STATUS OF COMPRESSORSL. HEATING OUTPUTM. REFRIGERANT EVAPORATOR TEMPERATUREN. SATURATED CONDENSER TEMPERATUREO. OUTSIDE AIR TEMPERATUREP. RETURN AIR TEMPERATUREQ. SUPPLY AIR TEMPERATURE
THE FOLLOWING POINTS SHALL BE INTEGRATED INTO ANDCONTROLLED BY THE FMS:
A. COOLING SETPOINTB. HEATING SETPOINTC. ZONE TEMPERATURE SETPOINTD. ZONE VALUESE. ECONOMIZER ENABLE/DISABLEF. ECONOMIZER SETPOINTG. ECONOMIZER MINIMUM POSITIONH. DIAGNOSTICS RESETI. UNIT PRIORITY SHUTDOWNJ. SUPPLY FAN MODEK. OCCUPANCY
TYPICAL PACKAGED ROOFTOP CAV AIR HANDLING UNIT CONTROL DIAGRAM
SEQUENCE OF OPERATIONS TFOE
C
I N
EI
L D
ESN
SAXATS
E
RE
ENIGN
LAOSSEFO
RP
ET
ABBAS SHIRIAN
102840
PROJECT
1
A
2 3 4 5
B
C
D
1 2 3 4 5
SEAL
REVISIONS
SHEET NO
DRAWING NAME
PROJECT NO:
REVIEWED BY
DATE
VE
GA
ISD
CA
RE
ER
TE
CH
NO
LOG
Y B
UIL
DIN
G20
0 LO
NG
HO
RN
ST
.V
EG
A, T
X 7
9 092
14-0424.002
01.29.2016
Addendum 01
DATE
1/29
/201
6 11
:24:
29 A
M
MI601a
MECHANICALDIAGRAMS(CONTROLS)
RLM
TFOE
C
I N
EI
L D
ESN
SAXATS
E
RE
ENIGN
LAOSSEFO
RP
ET
ABBAS SHIRIAN
102840
PROJECT
1
A
2 3 4 5
B
C
D
1 2 3 4 5
SEAL
REVISIONS
SHEET NO
DRAWING NAME
PROJECT NO:
REVIEWED BY
DATE
VE
GA
ISD
CA
RE
ER
TE
CH
NO
LOG
Y B
UIL
DIN
G20
0 LO
NG
HO
RN
ST
.V
EG
A, T
X 7
9 092
14-0424.002
01.29.2016
Addendum 01
DATE
1/29
/201
6 11
:24:
24 A
M
M701a
MECHANICALSCHEDULES
RLM
AG BLDG - PACKAGED ROOFTOP UNIT (DX/GAS)
SYMBOL MANUFACTURER MODEL NO. GROSSTONS OA CFM TYPE
SUPPLY FAN DX COOLING HEATING DATA (GAS HEAT)APPROXIMATE
OPERATINGWEIGHT (LBS.)
ELECTRICAL
NOTESSA CFM BHP HP ESP
(WG)AIR
FLOWOD
AMB.
ENT. AIR LVG. AIR TOTAL
CAP. (MBH)SEN CAP.
(MBH) SEERAIR DATA GAS CAPACITY
V PH HZ MCA MOCPDB WB DB WB AIR
FLOWEAT(F)
LAT(F)
HEATING S/LINPUT (MBH)
HEATING SITEOUTPUT (MBH)
AG-RTU-01 TRANE YHC067 5.0 785 FC 2,000 0.58 1.0 0.5 2,000 100 84 63 61 54 56.0 47.0 17.2 2,000 48.0 78.0 80 55 1150 460 3 60 15.2 20.0
FURNISH W/ 16" TALL ROOF CURB, HAIL GUARDS,ECONOMIZER, BAORMETRIC RELIEF, FACTORY MOUNTEDFUSED DISCONNECT, NON-POWERED CONVIENCEOUTLET
AG BLDG - EXHAUST FANS
SYMBOL MANUFACTURER & MODEL NO. AREA SERVED TYPE CFM S.P.(IN. WC)
FANRPM BHP
MOTOR DATA OPERATINGWEIGHT (LBS.) DAMPER NOTES
HP VOLT PHASE HZ FLAAG-EF-01 GREENHECK - SQ-99-VG BOYS109-GIRLS110 DIRECT DRIVE INLINE FAN 720 0.5 1,656 0.21 1/4 115 1 60 3.7 50 BACKDRAFT ELEC DISCONNECT
AG-EF-02 GREENHECK - SBE-3H30-3 SHOP 105 SIDE WALL BELT DRIVE FAN 4,300 0.2 628 0.29 1/3 115 1 60 7.2 90 NONEGALVANIZED STEEL DRIVE FRAME ASSEMBLY,STATIC RESISTANT BELTS - CORROSION RESISTANT FASTENERS,ELEC DISCONNECT, NEMA 1, TOGGLE SWITCH
AG-EF-03 GREENHECK - SBE-3H30-3 SHOP 105 SIDE WALL BELT DRIVE FAN 4,300 0.2 628 0.29 1/3 115 1 60 7.2 90 NONEGALVANIZED STEEL DRIVE FRAME ASSEMBLY,STATIC RESISTANT BELTS - CORROSION RESISTANT FASTENERS,ELEC DISCONNECT, NEMA 1, TOGGLE SWITCH
AG-EF-04 GREENHECK - SBE-3H30-3 SHOP 105 SIDE WALL BELT DRIVE FAN 4,300 0.2 628 0.29 1/3 115 1 60 7.2 90 NONEGALVANIZED STEEL DRIVE FRAME ASSEMBLY,STATIC RESISTANT BELTS - CORROSION RESISTANT FASTENERS,ELEC DISCONNECT, NEMA 1, TOGGLE SWITCH
AG-EF-05 GREENHECK - SBE-3H30-3 SHOP 105 SIDE WALL BELT DRIVE FAN 4,300 0.2 628 0.29 1/3 115 1 60 7.2 90 NONE GALVANIZED STEEL DRIVE FRAME ASSEMBLY,STATIC RESISTANT BELTS - CORROSION RESISTANT FASTENERS,ELEC DISCONNECT, NEMA 1, TOGGLE SWITCH
AG BLDG - GAS FIRED UNIT HEATER
SYMBOLMANUFACTURER
& MODEL NO. LOCATION
SEELLEVEL MIN
INPUT(MBH)
SEEL LEVEL MINOUTPUT(MBH)
AIR FLOWCFM
ELECTRICAL DATA
WEIGHT(LBS.) NOTESVOLT PHASE HZ MOTOR HP MOTOR RPM
AG-UH-01 TRANE GTND003 TOOL RM-106 30 21 370 115 1 60 1/20 1,650 70 UNIT MOUNTED 24 VOLT THERMOSTAT, ELEC. INTERMITTENT,SPARK IGNITION, ALUMINUM HT EXHCHANGER, 4" DIA. TYPE B VENT, 1/2" GAS CONN.
AG BLDG - RADAINT TUBE HEATER
SYMBOL MANUFACTURER &MODEL NO.
AREASERVED
SEE LEVEL MININPUT (MBH)
SEE LEVEL MINOUTPUT (MBH)
ELEC TUBEDIAMETER
(in)
TOTAL TUBELENGTH (FT)
MOUNTINGHEIGHT (FT) NOTE
VOLT PH HZ FLAAMPS
AG-RH-01 SPACE RAY - LTU125 SHOP -105 125 105 115 1 60 2.6 4 30 14 THERMOSTAT, ELEC. DIRECT SPARK IGNITION, TWO STAGE GAS VALVE, 4" DIA. TYPE B VENT WITH BRIEDERT TYPE L CAP, HORIZONTAL DUCTED COMBUSTION AIR WITH LESLIE VERSACAP,1/2" GAS CONN., 3 FT STAINLESS STEEL FLEXIBLE GAS LINE
AG-RH-02 SPACE RAY - LTU125 SHOP -105 125 105 115 1 60 2.6 4 30 14 THERMOSTAT, ELEC. DIRECT SPARK IGNITION, TWO STAGE GAS VALVE, 4" DIA. TYPE B VENT WITH BRIEDERT TYPE L CAP, HORIZONTAL DUCTED COMBUSTION AIR WITH LESLIE VERSACAP,1/2" GAS CONN., 3 FT STAINLESS STEEL FLEXIBLE GAS LINE
AG-RH-02 SPACE RAY - LTU125 SHOP -105 125 105 115 1 60 2.6 4 30 14 THERMOSTAT, ELEC. DIRECT SPARK IGNITION, TWO STAGE GAS VALVE, 4" DIA. TYPE B VENT WITH BRIEDERT TYPE L CAP, HORIZONTAL DUCTED COMBUSTION AIR WITH LESLIE VERSACAP,1/2" GAS CONN., 3 FT STAINLESS STEEL FLEXIBLE GAS LINE
AG-RH-04 SPACE RAY - LTU125 SHOP -105 125 105 115 1 60 2.6 4 30 14 THERMOSTAT, ELEC. DIRECT SPARK IGNITION, TWO STAGE GAS VALVE, 4" DIA. TYPE B VENT WITH BRIEDERT TYPE L CAP, HORIZONTAL DUCTED COMBUSTION AIR WITH LESLIE VERSACAP,1/2" GAS CONN., 3 FT STAINLESS STEEL FLEXIBLE GAS LINE
AG-RH-05 SPACE RAY - LTU125 SHOP -105 125 105 115 1 60 2.6 4 30 14 THERMOSTAT, ELEC. DIRECT SPARK IGNITION, TWO STAGE GAS VALVE, 4" DIA. TYPE B VENT WITH BRIEDERT TYPE L CAP, HORIZONTAL DUCTED COMBUSTION AIR WITH LESLIE VERSACAP,1/2" GAS CONN., 3 FT STAINLESS STEEL FLEXIBLE GAS LINE
AG-RH-06 SPACE RAY - LTU125 SHOP -105 125 105 115 1 60 2.6 4 30 14 THERMOSTAT, ELEC. DIRECT SPARK IGNITION, TWO STAGE GAS VALVE, 4" DIA. TYPE B VENT WITH BRIEDERT TYPE L CAP, HORIZONTAL DUCTED COMBUSTION AIR WITH LESLIE VERSACAP,1/2" GAS CONN., 3 FT STAINLESS STEEL FLEXIBLE GAS LINE
AG-RH-07 SPACE RAY - LTU125 SHOP -105 125 105 115 1 60 2.6 4 30 14 THERMOSTAT, ELEC. DIRECT SPARK IGNITION, TWO STAGE GAS VALVE, 4" DIA. TYPE B VENT WITH BRIEDERT TYPE L CAP, HORIZONTAL DUCTED COMBUSTION AIR WITH LESLIE VERSACAP,1/2" GAS CONN., 3 FT STAINLESS STEEL FLEXIBLE GAS LINE
AG-RH-08 SPACE RAY - LTU125 SHOP -105 125 105 115 1 60 2.6 4 30 14 THERMOSTAT, ELEC. DIRECT SPARK IGNITION, TWO STAGE GAS VALVE, 4" DIA. TYPE B VENT WITH BRIEDERT TYPE L CAP, HORIZONTAL DUCTED COMBUSTION AIR WITH LESLIE VERSACAP,1/2" GAS CONN., 3 FT STAINLESS STEEL FLEXIBLE GAS LINE
AG BLDG - MOTORIZED DAMPER
SYMBOLMANUFACTURER &
MODEL NO. LOCATION W (IN) IN (IN)PRESSURE
DROP (IN.WG) DRIVE ARP. ACTUATOR ACT QTY. ACT TYPEAG-MD-01 GREENHECK VCD-23 SHOP 105 192 24 0.004 DRIVE-CC-41-2FIL-2 MS4120F1006 2 120VAC - SPRING RETURN
AG BLDG - SPLIT SYSTEM INDOOR UNITS
SYMBOL MANUFACTURER MODEL NO. NOMINALTON
AREASERVED
AIR FLOWCFM
COOLING HEATING PIPING SIZE ELEC PHSYSICAL DIMENSIONSNOTESOUTSIDE
TEMPINDOOR DB
TEMPINDOOR WB
TEMPTOTALBTUH
SENSIBLEBTUH
OUTSIDETEMP
INDOORDB TEMP
TOTALBTUH
RSDIA
RLDIA
DRAINDIA V/PH/HZ PWOER
CONSUMPTIONWEIGHT
(LB)WIDTH
(IN)LENGTH
(IN)HEIGHT
(IN)
AG-FC-01 MITSUBISHI PKA-A18HA4 1.5 ELEC-107 425 104 F 80 F 67 F 18,000 12,200 17 F 59 F 19,000 1/2" 1/4" 5/8" 115/1/60 FROM AG-CU-01 29 36 10 12FURNISH W/ WIRED 7-DAY PROG T'STAT,CONDENSATE PUMP - SAUERMANNMODEL SI3100, CONNECT TO AG-CU-01, R-410A REFRIGERANT, ELECDISCONNECT BY DIV 26
AG BLDG - SPLIT SYSTEM OUTDOOR UNITS
SYMBOL MANUFACTURER MODEL NO. NOMINALTON
COOLING HEATING ELEC PHYSICAL DIMENSION PIPE SIZESNOTESOUTDOOR
TEMPTOTALBTUH
OUTDOORTEMP
TOTALBTUH V/PH/HZ MCA MOP WEIGHT
(LB)WIDTH
(IN)LENGTH
(IN)HIGHT(I
N)RSDIA
RLDIA
AG-CU-01 MITSUBISHI PUZ-A18NHA4 1.5 104 F 18,000 17 F 19,000 115/1/60 13 15 90 32 12 24 1/2" 1/4" FURNISH W/ LO AMBIENT KIT (HEATING TO 5°F AMBIENT) AND WIND BAFFLE BAFFL E, INTERLOCK W/ AG-FC-01
ALL SELECTIONS BASEDON 3,600 FT ELEVATION.
R
EX
A
X
3
a
WALL
CEILING
WALL
CEILING
OS
OS
208Y/120VT1A
75kVA
K-4
E4E3
A
DRAWING NUMBER WHERE TAKEN
DRAWING NUMBER WHERE DETAILED
SECTION/ELEVATION LETTER OR DETAIL NUMBER
A
E4
6
E4
+44"
DRAWING NUMBER WHERE DETAILED
SECTION/ELEVATION LETTER OR DETAIL NUMBER
VAV-9
(NOT ALL SYMBOLS APPLY TO THIS PROJECT)
NORTH ARROW OR MATCH ARCHITECT'S
SCALE BAR OR MATCH ARCHITECT'S
SURFACE
WALL
CEILING
+44"
UON
ONE-LINE DIAGRAM
SPD
3000/5
CIRCUIT BREAKER; TRIP SETTING/FRAME SIZE OR NO. OF
POLES. SETTINGS AND PROTECTION AS NOTED ON PLANS
DRAWOUT CIRCUIT BREAKER
MEDIUM VOLTAGE DRAWOUT CIRCUIT
BREAKER
POTENTIAL TRANSFORMER.
DISCONNECT SWITCH. "300A"
DENOTES AMPERAGE RATING
FUSE. "300A" DENOTES AMPERAGE
RATING
GROUND CONNECTION
TRANSFER SWITCH. SEE PLANS
FOR TYPE OF SWITCH
SURGE ARRESTOR
SURGE PROTECTIVE DEVICE
KILOWATT METER
ELECTRONIC METER
KIRK KEY INTERLOCK No.1
RELAY No.1
AMMETER SWITCH
AMMETER
VOLTMETER SWITCH
VOLTMETER
DELTA CONNECTED
WYE CONNECTED
LIGHTING
RECESSED MOUNTED LUMINAIRE. SMALL CASE "a"
DENOTES SWITCHING, NUMBER "3" DENOTES BRANCH
CIRCUITING. SYMBOL "A" DENOTES LUMINAIRE TYPE
WALL MOUNTED LUMINAIRES
STRIP LUMINAIRE
LINEAR DIRECT/INDIRECT LUMINAIRE. CABLE
OR STEM MOUNTED
DOWN LIGHT LUMINAIRE; CEILING MOUNTED
EXIT LUMINAIRE. SHADED SIDE INDICATES
FACE SIDE. PROVIDE DIRECTIONAL ARROW(S)
AS INDICATED ON PLANS
EMERGENCY BATTERY PACK LUMINAIRE
(BUG-EYE/FROG-EYE)
DOUBLE HEAD, POLE MOUNTED LUMINAIRE
TRACK MOUNTED LUMINAIRES
SURFACE
AS
DETAILED
CEILING
EXTERIOR
WALL
DEMOLITION
DASHED SYMBOL INDICATES EXISTING DEVICE OR
EQUIPMENT TO BE REMOVED
SOLID SYMBOL, LIGHTER IN COLOR INDICATES EXISTING
DEVICE OR EQUIPMENT TO REMAIN
EXISTING CONDUIT TO BE REUSED
REMOVE EXISTING RACEWAY IN ALL ACCESSIBLE AREAS.
CAPPED AND ABANDONED IF IN UNACCESSIBLE AREA
SYMBOL DEFINITION
REFERENCE TAGS
KEYED NOTE REFERENCE
MECHANICAL EQUIPMENT REFERENCE
DENOTES MOUNTING HEIGHT AFF
KITCHEN EQUIPMENT REFERENCE
MEDICAL EQUIPMENT REFERENCE
GENERAL DRAWING SYMBOLS
TRIP SETTING
FRAME SIZE
300
400
VARIES
RE
FE
R T
O L
IGH
TIN
G S
CH
ED
ULE
EMERGENCY, CRITICALEC
EMERGENCY, LIFE SAFETYEL
EMERGENCY, EQUIPMENTEQ
TELEVISIONTV
EXISTINGEX
GROUND FAULT PROTECTIONGFP
SWITCHSW
FEEDERFDR
UNDERGROUND ELECTRICUGE
MANHOLEMH
MIXED MEDIAMM
UNDERGROUNDU/G
POWER MONITORING AND CONTROL SYSTEMPMCS
AUTOMATIC TRANSFER SWITCH CONTROLATSC
TEMPORARYTEMP
SECURITYSEC
DEFINITIONABBREV.
ABBREVIATIONS
A
ADA
AFF
AFG
AWG
ANSI
AIC
C
CCTV
CLF
CO
GFI
GND
HOA
G OR GFCI
FACP
AMPS, AMPERE, AMPERAGE
ABOVE FINISHED GRADE
ABOVE FINISHED FLOOR
AMERICANS WITH DISABILITIES ACT
AVAILABLE INTERRUPTING CURRENT
AMERICAN NATIONAL STANDARDS INSTITUTE
GROUND FAULT CIRCUIT INTERRUPTER
HAND-OFF-AUTOMATIC.
GROUND.
GROUND FAULT INTERRUPTER
CURRENT LIMITING FUSE
AMERICAN WIRE GAUGE
CLOSED CIRCUIT TELEVISION
FIRE ALARM CONTROL PANEL
CONDUIT ONLY
CONDUIT
HP
IEEE
KV
KVA
KW
KWH
MVA
MCC
NEC
NEMA
NIC
NFPA
NM
P
PA
PC
NC
POLE
KILOVOLT AMPS
NATIONAL FIRE PROTECTION ASSOCIATION
PHOTOCELL
PUBLIC ADDRESS
NEW MEXICO
NOT IN CONTRACT
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURERS
MOTOR CONTROL CENTER
MEGAVOLT AMPS
NORMALLY CLOSED
KILOWATT HOUR.
KILOWATT
HORSEPOWER
KILOVOLT
TVSS
UPS
UON
V
VFD
XFER
XFMR (TRANSF)
VARIABLE FREQUENCY DRIVE
UNINTERRUPTABLE POWER SUPPLY
TRANSIENT VOLTAGE SURGE SUPPRESSER
TRANSFORMER
TRANSFER
UNLESS OTHERWISE NOTED
VOLTS, VOLTAGE
TTB TELEPHONE TERMINAL BOARD
INSTITUTE OF ELECTRICAL AND ELECTRONICS
CEILING MOUNTED OCCUPANCY SENSOR; TYPE AS
INDICATED ON PLANS
GENERATOR
a =
2 =
3 =
4 =
P =
M =
K =
WP =
T =
D =
AC ABOVE COUNTER
AL ALUMINUM
ATS AUTOMATIC TRANSFER SWITCH
CKT CIRCUIT
CU COPPER
DL DAY-LIGHTING
DIA DIAMETER
FA FIRE ALARM
KCMIL THOUSAND CIRCULAR MILS
MAX MAXIMUM
MIN MINIMUM
NEUT NEUTRAL
PH PHASE
RSC RIGID STEEL CONDUIT
UC UNDER COUNTER
WP WEATHERPROOF
WALL MOUNTED OCCUPANCY SENSOR; TYPE
AS INDICATED ON PLANS
HATCHING INDICATES EMERGENCY LIGHTING.
HATCH WILL BE MODIFIED FOR EACH
LUMINAIRE TYPE. EMERGENCY LUMINAIRE
DESIGNATED WITH "E" IN TYPE DESIGNATION.
VARIES
SURFACE MOUNTED LUMINAIRE.
LUMINAIRE TYPE AS INDICATED ON PLANS
FIRE ALARM
REFER TO
DEMOLITION PLANS
FOR ADDITIONAL
INFORMATION
FUT FUTURE
LSIG LONG TIME, SHORT TIME, INSTANTANEOUS,
N NEW
W WALL MOUNTED
NL NORMAL
MTS MANUAL TRANSFER SWITCH
UL UNDERWRITERS' LABORATORIES
EMERGENCYE
IG ISOLATED GROUND
KVAR KILOVOLT AMPS REACTIVE
NO NORMALLY OPEN
SURGE PROTECTIVE DEVICESPD
REFER TO LUMINAIRE SCHEDULE FOR ALL LUMINAIRE TYPES WHETHER WALL MOUNTED OR CEILING
MOUNTED.
GROUND FAULT PROTECTION
SHUNT TRIP OPERATORTYP. TYPICAL
300
400
TRIP SETTING
FRAME SIZE
300A
300A
N/A NOT APPLICABLE
O/H OVERHEAD
GEN GENERATOR
ENGINE GENERATOREG
SYMBOL DESCRIPTIONMOUNTING
HT.LOC.
SINGLE HEAD, POLE MOUNTED LUMINAIRE
MOUNTINGHT.LOC.
DOUBLE FACE EXIT LUMINAIRE. SHADED SIDE
INDICATES FACE SIDE. PROVIDE DIRECTIONAL
ARROW(S) AS INDICATED ON PLANS
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION NOTES
ASSOCIATION
AND GROUND FAULT PROTECTION
ENGINEERS
300
400
NORTH
ELECTRICAL SYMBOL LEGEND
E3 E4
6
TRANSFORMER. TRANSFORMER NAME, TRANSFORMER kVA
RATING, PRIMARY VOLTAGE AND WIRING CONFIGURATION,
SECONDARY VOLTAGE, K RATING (IF APPLICABLE)
G
ST
0 10' 20' 40' 80'
1" = 40'-0"
DEVICE INDICATOR LETTER. "X" EQUALS DESIGNATION
BELOW
(TYPICAL FOR MOST SWITCH TYPES):
SMALL CASE LETTER DENOTES SWITCHING
CONTROL
DOUBLE POLE TOGGLE SWITCH
THREE-WAY TOGGLE SWITCH
FOUR-WAY TOGGLE SWITCH
PILOT LIGHT TOGGLE SWITCH
MOMENTARY CONTACT SWITCH
KEY OPERATED SWITCH
WEATHERPROOF TOGGLE SWITCH
MANUAL MOTOR STARTER SWITCH WITH THERMAL
OVERLOAD PROTECTION
DIMMER SWITCH
FACP
FAA
F
F
S
C
B
P
I
R/F
F
R
U
PS
TS
FS
PIV
M
R
MM
R
FIRE ALARM CONTROL PANEL
-WALL
+44"WALL
+80"
UONWALL
CEILING
UNDER
FLOOR
SEE
PLANS
AT DUCT
VARIESPIPE
SEE
PLANSVARIES
SEE
PLANS
FIRE ALARM ANNUNCIATOR PANEL
PULL STATION
FIREMAN'S TELEPHONE OUTLET
HORN NOTIFICATION
SPEAKER NOTIFICATION
CHIME NOTIFICATION
COMBINATION SPEAKER AND CHIME NOTIFICATION
SPEAKER/HORN WITH STROBE LIGHT
STROBE LIGHT ONLY
BELL (GONG)
PHOTOELECTRIC SMOKE DETECTOR
IONIZATION SMOKE DETECTOR
COMBINATION RATE OF RISE / FIXED TEMPERATURE
FIXED TEMERATURE; TEMPERATURE AS NOTED
ON PLANS OR SPECIFICATIONS
RATE OF RISE ONLY
UNDER FLOOR SMOKE DETECTOR
DUCT DETECTOR
FIRE/SMOKE DAMPER
PRESSURE SWITCH
TAMPER SWITCH
FLOW SWITCH
POST INDICATOR VALVE
MAGNETIC DOOR HOLDER
CONTROL RELAY
MONITOR MODULE
REMOTE ALARM INDICATING LIGHT
ADDRESSABLE/SUPERVISED RELAY
KW
M
K1
R1
AS
A
VS
V
VFD CONNECTION
MOTOR CONNECTION
UPS
5
VFD
J
T
5
30/3R
0/1
1/30/3R
F
30/1
30/3R
DEVICES
CODE SIZE JUNCTION BOX
WALL MOUNTED CODE SIZE J-BOX
CODE SIZE PULLBOX (OR AS SIZED ON PLAN)
ENCLOSED CIRCUIT BREAKER.
AMPERAGE/NEMA ENCLOSURE RATING, 3 POLE
UON
NON-FUSED DISCONNECT SWITCH.
AMPERAGE/NEMA ENCLOSURE RATING, 3 POLE
UON
FUSED DISCONNECT SWITCH.
AMPERAGE/NEMA ENCLOSURE RATING, 3 POLE
UON
MOTOR STARTER. STARTER SIZE INDICATED
BY NUMBER/NEMA ENCLOSURE RATING,
SINGLE SPEED UON
COMBINATION FUSIBLE DISCONNECT SWITCH
AND MOTOR STARTER. NEMA STARTER
SIZE/AMPERAGE/NEMA ENCLOSURE RATING, 3
POLE UON
MOTOR. NUMBER INDICATES HORSEPOWER
RATING FOR 1HP AND LARGER
THERMOSTAT
PHOTOCELL
LIGHTNING PROTECTION AIR TERMINAL
PUSHBUTTON (EMERGENCY POWER OFF - EPO)
SYMBOL DESCRIPTIONMOUNTING
+44"
UON
N/A
VARIES
HT.LOC.
WALL
ROOF
VARIES
N/A
VARIES
MULTI-OULET ASSEMBLY (SURFACE MOUNTED
RACEWAY) VARIES
SEE
PLANS
VARIES
SEE
PLANS
MOTOR. "F" INDICATES FRACTIONAL
HORSEPOWER
VARIES
SEE
PLANS
VARIES
SEE
PLANS
VARIES
DEVICE INDICATOR LETTER. "X" EQUALS DESIGNATION BELOW
(TYPICAL FOR MOST RECEPTACLE TYPES):
BLANK FOR NORMAL POWERG = GFCI RATED
IG = ISOLATED GROUND
T = TAMPERPROOF
WG = WEATHERPROOF AND GFCI
WP = WEATHERPROOF (IN-USE COVER)
CL = CLOCK
TV = TELEVISION
+18",
UON
FLUSH
IN FLOOR DUPLEX RECEPTACLE.
CONFIGURATION AS INDICATED ON PLANS
IN FLOOR DOUBLE DUPLEX (QUADPLEX) RECEPTACLE.
CONFIGURATION AS INDICATED ON PLANS
CEILING MOUNTED DUPLEX RECEPTACLE
CEILING MOUNTED DOUBLE DUPLEX
(QUADPLEX) RECEPTACLE
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE
DOUBLE DUPLEX (QUADPLEX) RECEPTACLE
EMERGENCY DOUBLE DUPLEX (QUADPLEX)
RECEPTACLE
SPECIAL PURPOSE RECEPTACLE. NEMA
CONFIGURATION AND AMPERAGE AS NOTED ON
PLANS
COMBINATION POWER/COMMUNICATION POLE.
CONFIGURATION AS NOTED ON PLANS
FLOOR
CEILING
WALL,
UON
IN FLOOR EMERGENCY DUPLEX RECEPTACLE.
CONFIGURATION AS INDICATED ON PLANS
CEILING MOUNTED EMERGENCY DUPLEX RECEPTACLE
EMERGENCY DUPLEX RECEPTACLE
COMBINATION POWER/COMMUNICATION IN
CEILING OUTLET. CONFIGURATION AS
INDICATED ON PLANS
COMBINATION DUPLEX RECEPTACLE AND
COMMUNICATIONS FLOORBOX. DEVICE
CONFIGURATION AS INDICATED ON PLANS.
X
X
X
X
X
X
X
X
X
X
X
X
X
X
J
P
IN FLOOR EMERGENCY DOUBLE DUPLEX
(QUADPLEX) RECEPTACLE. CONFIGURATION AS INDICATED ON
PLANS
X
A, B, C, = SEQUENCE OF PANELS OF THIS TYPE
1, 2, 3, . . = SUBFED PANEL
1, 2, 3, . . = FLOOR LEVEL
HL
T
BLANK FOR NORMAL POWER
ELECEQ
= EMERGENCY-LIFE SAFETY-BRANCH= EMERGENCY-CRITICAL-BRANCH= EMERGENCY-EQUIPMENT-BRANCH
GROUND BAR
MAIN SWITCHBOARD. DASHED LINES INDICATE CLEARANCES.
VARIABLE FREQUENCY DRIVE
SYMBOL
EQUIPMENTDESCRIPTION
EQUIPMENT NAMING CONVENTION
= HIGH VOLTAGE PANELBOARD (480Y/277V)= LOW VOLTAGE PANELBOARD (208Y/120V)
= TRANSFORMER= DISTRIBUTION BOARDDB= MAIN SWITCH BOARDMSB
MCC = MOTOR CONTROL CENTER
= UNINTERRUPTABLE POWER SUPPLYUPS= POWER DISTRIBUTION UNIT
ATS = AUTOMATIC TRANSFER SWITCHPDU
= ISOLATED PANELBOARDI
B = BUSWAY
MSB
FLUSH MOUNTED PANELBOARD. DASHED LINES INDICATE CLEARANCES.
SURFACE MOUNTED PANELBOARD. DASHED LINES INDICATE CLEARANCES.
H1A
L1A
MCCMOTOR CONTROL CENTER. DASHED LINES INDICATE CLEARANCES.
T1A
UNINTERRUPTABLE POWER SUPPLY. DASHED LINES INDICATE
CLEARANCES.
AUTOMATIC TRANSFER SWITCH. DASHED LINES INDICATE CLEARANCES.
DRY TYPE TRANSFORMER (15kVA OR ABOVE), WITH EQUIPMENT TAG
(TAG INSIDE OR OUTSIDE, DEPENDING ON SIZE). IN MOST CASES,
ACTUAL SIZE SHOWN ON PLANS (ELECTRICAL ROOMS).
E = EMERGENCY
DISTRIBUTION BOARD. DASHED LINES INDICATE CLEARANCES.DB
UPS-A
ATS-1
EXAMPLES:
A. SES1 (SERVICE ENTRANCE SECTION #1)
B. 1H1A (SERVED FROM SES#1, 480/277 NORMAL, LEVEL 1, FIRST BOARD)
C. 1EQH1A (SERVED FROM MAIN EMER SWBD #1, 480/277 EQUIP POWER, LEVEL 1, FIRST
BOARD)
SES
G
= GROUND
= HOT/PHASE
= NEUTRAL
= SWITCH LEG
CONDUCTOR IDENTIFICATION SYMBOLS. REFER TO PLANS FOR
COMBINATION USE. CONDUCTOR IDENTIFICATION MOSTLY USED IN
HOMERUN LOCATION, BUT CAN ALSO BE USED IN BRANCH
CIRCUITING WHERE APPLIED. GROUND CONDUCTORS WILL BE
INSTALLED IN ALL RACEWAYS WHETHER SHOWN OR NOT.
LA-1
HOMERUN FROM EQUIPMENT LOCATION. THE CIRCUIT NUMBER
ADJACENT TO HOMERUN INDICATES PANEL SOURCE AND
INDIVIDUAL SINGLE POLE CIRCUIT BREAKER(S). CONDUCTOR
IDENTIFICATION SYMBOL INDICATES NUMBER OF CONDUCTORS IN
HOMERUN. MINIMUM #12 CONDUCTORS AND 3/4" RACEWAY PATH
WILL BE PROVIDED IN HOMERUN UON. ALL HOMERUNS WILL
INCLUDE GROUND CONDUCTOR.
LA-1,3
HOMERUN FROM EQUIPMENT LOCATION. THE CIRCUIT NUMBER
ADJACENT TO HOMERUN INDICATES PANEL SOURCE AND INDIVIDUAL
TWO OR THREE POLE CIRCUIT BREAKERS. CONDUCTOR
IDENTIFICATION SYMBOL INDICATES NUMBER OF CONDUCTORS IN
HOMERUN. MINIMUM #12 CONDUCTORS AND 3/4" RACEWAY PATH
WILL BE PROVIDED IN HOMERUN UON. NEUTRAL MAY BE USED
WHERE INDICATED ON PLAN. ALL HOMERUNS WILL INCLUDE
GROUND CONDUCTOR.
LA-5,7,9
CONCEALED RACEWAY BETWEEN DEVICES AND OR EQUIPMENT
IN WALLS OR IN CEILING SPACE
UNDERGROUND RACEWAY BETWEEN DEVICES AND OR
EQUIPMENT
EXPOSED RACEWAY BETWEEN DEVICES AND OR EQUIPMENT
ON WALLS OR CEILINGS
CONDUIT TURNSDOWN UP
B BUSWAY
GROUNDING CONDUCTORG
CABLE TRAY - POWER AND TELECOMMUNICATIONS
T TELECOMMUNICATIONS RACEWAY
D DATA RACEWAY
FA FIRE ALARM RACEWAY
CONDUIT STUBBED AND CAPPED
VOICE/DATA COMBINATION RACEWAYV/D
BRANCH CIRCUIT GENERAL INFORMATION:BRANCH CIRCUITS FROM OVERCURRENT PROTECTION (20A) TO FURTHEST DEVICESHALL NOT EXCEED 75 FEET FOR #12AWG COPPER AND 150 FEET FOR #10AWG
COPPER; MEASURED ALONG CONDUCTORS ROUTING PATH. BRANCH CIRCUITS
EXCEEDING 150 FEET WILL BE SIZED SO THAT VOLTAGE DROP DOES NOT EXCEED 5%.
LA-1,3
LA-5,7,9
HOMERUN FROM EQUIPMENT LOCATION. THE CIRCUIT NUMBER
ADJACENT TO HOMERUN INDICATES PANEL SOURCE AND INDIVIDUAL
SINGLE POLE CIRCUIT BREAKER(S). SYMBOL REPRESENTS A MULTI-
BRANCH CIRCUIT. NUMBER OF CONDUCTORS IN HOMERUN WILL
INCLUDE A SEPERATE NEUTRAL FOR EACH CIRCUIT PHASE
CONDUCTOR. MINIMUM #12 CONDUCTORS AND 3/4" RACEWAY PATH
WILL BE PROVIDED IN HOMERUN UON. ALL HOMERUNS WILL
INCLUDE GROUND CONDUCTOR.
RACEWAY & CONDUCTORS
CURRENT TRANFORMER, NUMBER
"3000/5" DENOTES RATIO.
WG WEATHERPROOF AND GFCI
R REMOVED/REMOVAL
RC ROOM CONTROLLER
FAA FIRE ALARM ANNUNCIATOR
FMS FACILITY MANAGEMENT SYSTEM
GROUND FAULT EQUIPMENT PROTECTIONGFEP
CB CIRCUIT BREAKER
D DIMMING
DC DIRECT CURRENT
UPS
NUMBER OR MAIN EMERG SWBD NUMBER= SERVICE ENTRANCE SECTION
(SB=SUB-BASEMENT, B=BASEMENT, M=MEZZANINE,
P=PENTHOUSE)
CEILING MOUNTED EMERGENCY DOUBLE
DUPLEX (QUADPLEX) RECEPTACLEX
PC
DL DAY-LIGHTING SENSOR; TYPE AS INDICATED
ON PLANS
PP POWER PACK; TYPE AS INDICATED
ON PLANS
SURFACE
BT
BR
BEAM TRANSMITTER
BEAM RECEIVERVARIES
CEILING OR
WALL
FATCFIRE ALARM TERMINAL CABINET (EQUIP. NAMING
CONVENTION PER PLANS)
480V
CL CLOCK
CB
FATC FIRE ALARM TERMINAL CABINET
UPDATED: 06/08/2015
A/V AUDIO/VISUAL
DRY TYPE TRANSFORMER (LESS THAN 15kVA), WITH NO EQUIPMENT TAG. SIZE,
TYPE AND LOCATION NOTED ON PLANS.
A/C ALTERNATING CURRENT
SYMBOL DESCRIPTION
DESCRIPTIONSYMBOL
T
VFD
TFOE
I N
SAXATS
E
RE
ENIGN
LAOSSEFO
RP
ET
JOHN F. HECK IV
82984
I SG
ER D
E
RET
PROJECT
1
A
2 3 4 5
B
C
D
1 2 3 4 5
SEAL
REVISIONS
SHEET NO
DRAWING NAME
PROJECT NO:
REVIEWED BY
DATE
VE
GA
ISD
CA
RE
ER
TE
CH
NO
LOG
Y B
UIL
DIN
G20
0 LO
NG
HO
RN
ST
.V
EG
A, T
X 7
9 092
14-0424.002
01.29.2016
Addendum 01
DATE
1/29
/201
6 12
:41:
23 P
M
E002a
ELECTRICALLEGEND
Approver
John Heck2016.01.29 13:47:22-07'00'
A B C D E F G
1
2
3
4
5
K-3544HIGHLINE
C_TOILETS
VITREOUS CHINA
K-3544HIGHLINE
C_TOILETS
VITREOUS CHINA
K-3544HIGHLINE
C_TOILETS
VITREOUS CHINA
OS
OS
OS
OSOS
OS
OS
RC
RC
ARb ARb ARb
ARb
ARb
BL
A1Fb A1Fb
A1Fb A1Fb
EGEG
EGEG
EGE
AL02
AL03
AL02
AL02
AL03
EL02
AL02
AL02 AL02
BVL BVL
BVL BVL
BVL BVL
BVL BVL
BVL BVL
BVL BVL
aa
b b
b b
b b
b b
a a
3,aEM EM EM
BVL
c
BVL
c
BVL
d
BVL
d
BVL
e
BVL
e
BVL
c
BVL
c
BVL
d
BVL
d
BVL
e
BVL
e
BVL
e
BVL
e
BVL
a
BVLBVL
a
BVL
a
BVL
d
BVL
d
BVL
c
BVL
c
BVL
a
BVL
a
BVL
e
BVL
e
BVL
a
BVL
a
BVL
d
BVL
d
BVL
a
BVL
a
BVL
c
BVL
c
BVL
a
AL02
EM 3,a
BVL
aEM
AL02EM
a
EM
EM EM
EM
EM
EM
3,abcd
e
AL02
3,a
3,a
DPHAG - 1FLE
AL08AL08
DPHAG - 3
DPHAG - 3.
.
DPHAG - 5 DPHAG - 7 DPHAG - 9 DPHAG - 11
DPHAG - 1FLE
BL BL
EM
DPHAG
BL AL07
AL04
BL EM
A1Fb A1Fb
AL04AL04
AL02AL02
K K
EMEM
EM EM
AL03
ARaD ARaD ARaD
ARaD ARaD ARaD
ARaD ARaD ARaD
AL02
AL02
AL06AL05AL05
EEM
DPHAG - 1FLE
DPHAG - 1FLE
AL08
AL08
DPHAG - 13
FLEDPHAG - 1
AL08
FLEDPHAG - 1
AL08
105
SHOP
101
HALLWAY
102
CLASSROOM
103
STORAGE
104
OFFICE
110
GIRLS109
BOYS
108
JANITOR
106
TOOLSTORAGE
107
ELEC./COMP.
A2
E500a
BL
TFOE
I N
SAXATS
E
RE
ENIGN
LAOSSEFO
RP
ET
JOHN F. HECK IV
82984
I SG
ER D
E
RET
PROJECT
1
A
2 3 4 5
B
C
D
1 2 3 4 5
SEAL
REVISIONS
SHEET NO
DRAWING NAME
PROJECT NO:
REVIEWED BY
DATE
VE
GA
ISD
CA
RE
ER
TE
CH
NO
LOG
Y B
UIL
DIN
G20
0 LO
NG
HO
RN
ST
.V
EG
A, T
X 7
9 092
14-0424.002
01.29.2016
Addendum 01
DATE
1/29
/201
6 12
:41:
28 P
M
EL101
AG SHOPLIGHTING PLAN
Approver
GENERAL SHEET NOTES
SHEET KEYNOTES
SCALE: 1/8" = 1'-0"B1 AG SHOP LIGHTING PLAN0' 4' 8' 16'
NORTH
AL02 ONE SWITCH; SWITCH TYPE AS INDICATED. WILL CONTROL THE LUMINAIRES INROOM.
AL03 WALL-MOUNTED OCCUPANCY SENSOR, WATT STOPPER PW-100 OR APPROVEDEQUAL. LOCATE PER MANUFACTURER'S RECOMMENDATIONS. SHOWN HERE FORBID PURPOSES.
AL04 CEILING-MOUNTED SENSOR, WATT STOPPER DT-355 OR APPROVED EQUAL.LOCATE PER MANUFACTURER'S RECOMMENDATIONS. SHOWN HERE FOR BIDPURPOSES.
AL05 LIGHTING ROOM CONTROLLERS FOR LIGHTING CONTROL SYSTEM IN THIS ROOM.REFER TO SHEET E500a FOR WIRING DIAGRAM AND ADDITIONAL INFORMATIONON ROOM CONTROLLER TYPE.
AL06 CEILING-MOUNTED OCCUPANCY SENSOR, LOCATE PER MANUFACTURER'SRECOMMENDATIONS. SHOWN HERE FOR BID PURPOSES. REFER TO SHEETE500a FOR WIRING DIAGRAM AND ADDITIONAL INFORMATION ON SENSOR TYPE.
AL07 ONE PROGRAMMABLE TIME CLOCK WITH ROOF MOUNTED PHOTO CELL AND 4POLE CONTACTOR FOR EXTERIOR BUILDING LIGHTINGTO BE CONTROLLEDSEPARATELY. REFER TO DETAIL D2 ON SHEET E500a FOR ADDITIONALINFORMATION.
AL08 LUMINAIRE WILL BE CONNECTED TO LIGHTING BATTERY INVERTER "BAG1"LOCATED IN ELECTRICAL ROOM 107. REFER TO DETAIL B2 ON SHEET E500a FORTYPICAL EMERGENCY LIGHTING BATTERY INVERTER DIAGRAM.
EL02 ONE SWITCH; SWITCH TYPE AS INDICATED. WILL CONTROL THE LUMINAIRES INROOM.
A. ALL EXIT SIGNS, TYPES "E" OR "EG", WILL BE CONNECTED TO CIRCUIT SERVING THEROOM THEY ARE LOCATED IN AND FROM NO OTHER CIRCUIT.
B. REFER TO SHEET E701a FOR ELECTRICAL LUMINAIRE SCHEDULE.C. REFER TO SHEET EP103 FOR ELECTRICAL ROOMS AND ELECTRICAL EQUIPMENT
LAYOUT.D. REFER TO SHEET E500a FOR LIGHTING DIAGRAMS AND SEQUENCE OF OPERATION.E. REFER TO DETAIL C4 ON SHEET E500a FOR LUMINAIRE MOUNTING.F. REFER TO ARCHITECTURAL SHEET AE501 FOR ADDITIONAL CEILING GRID MOUNTING
SUPPORT INFORMATION. ALL LUMINAIRES WILL BE SECURELY SUPPORTEDSEPARATELY FROM CEILING GRIDS TO CEILING STRUCTURE.
G. REFER TO ARCHITECTURAL SHEETS FOR EXTERIOR LIGHTING ELEVATIONS.H. ALL EXTERIOR BUILDING LUMINAIRES WILL BE ROUTED THROUGH A TIME CLOCK AND
CONTACTOR LOCATED IN THE ELECTRICAL ROOM WHERE THE PANEL FEEDINGTHOSE LUMINAIRES IS LOCATED. REFER TO DIAGRAM D2 ON SHEET E500a FORADDITIONAL INFORMATION.
I. ALL LUMINAIRES IN DASHED AREA WILL BE CONNECTED TO CIRCUIT INDICATED UNLESSOTHERWISE NOTED.
John Heck2016.01.29 13:47:15-07'00'
A B C D E F G
1
2
3
4
5
K-3544HIGHLINE
C_TOILETS
VITREOUS CHINA
K-3544HIGHLINE
C_TOILETS
VITREOUS CHINA
K-3544HIGHLINE
C_TOILETS
VITREOUS CHINA F
F
J
F F
F F
J
F
P
P P
R/F
R/FP
F
F
FF
FF
TS
FS
J
G G
WG
WG
WG
T
T
T T T T
T T T T
T T
T T
T
AG-CU-01 AP01
DPHAG - 2,4,6
AG-RTU-01 AP01
EP21AP02AP03
AG-FC-01
AP01
LAG1 - 37
AP04
LAG1 - 34
LAG1 - 35
LAG1 - 39
LAG1 - 41
LAG1 - 36
LAG1 - 38
LAG2 - 74LAG2 - 76
LAG2 - 78
LAG2 - 80 LAG2 - 82 LAG2 - 84
LAG2 - 79
LAG2 - 81
11
11
1
2
2
2
2 2LAG1 - 1
LAG1 - 2
3 3
3
LAG1 - 3
LAG1 - 40,42
WG
3
3
4
LAG2 - 40
AP05
AF03
T
G
FACP
DWH-1
AP09
G GG
G G
G
G
G
G
G GGG G
G
AF02AF02
AP09
AP06
AP09
AP09
AP08
AP09
AP09
AP09AP08 AP09
AP07
AP09
AP08
AP06
AP09
AP09
AP08
AP09
AP07
AP09
AP08
AP08
AP09
AP09
AP08AP09
AP08AP09
AP08
AP09
AP09
AF01
AG-AC-1AD-1
AP10AP01
ILP-1
WG
G
AP09
AP08
G
AP09
LAG2
HOT BOX PIV
FA
FA
LAG1 - 6,8
AP14AP13AP13
14
LAG1 - 14
14
LAG1 - 12
LAG1 - 10
LAG1 - 4
G
LAG2 - 42
LAG1 - 55,57
LAG2 - 30 LAG1 - 11 LAG2 - 28 LAG1 - 51,53
LAG2 - 26
LAG1 - 43,45
LAG1 - 13LAG1 - 47,49
LAG2 - 24
LAG2 - 22
LAG2 - 37,39
105
SHOP
101
HALLWAY
102
CLASSROOM
103
STORAGE
104
OFFICE
110
GIRLS109
BOYS
108
JANITOR
106
TOOLSTORAGE
107
ELEC./COMP.
LAG1 - 15
LAG2 - 33,35LAG2 - 20
WG
LAG1 - 1818
LAG2 - 18
LAG2 - 29,31
LAG1 - 17
LAG2 - 16
LAG2 - 14
LAG2 - 21,23
LAG1 - 19
LAG2 - 12
LAG1 - 21
LAG2 - 17,19
LAG2 - 10
LAG2 - 13,15
LAG2 - 8
LAG2 - 6
LAG2 - 9,11
LAG1 - 23
LAG2 - 4
LAG2 - 5,7
LAG2 - 2
LAG2 - 1,3LAG2 - 32LAG2 - 34
LAG1 - 25
LAG1 - 59,61
LAG2 - 36
LAG1 - 27
LAG1 - 9
LAG2 - 38
LAG1 - 16
WG16
LAG1 - 68,70,72
LAG1 - 66
LAG1 - 74,76,78
LAG1 - 79,81,83
LAG1 - 80,82,84
LAG1 - 73,75,77
LAG1 - 62
LAG1 - 64
LAG1 - 63,65
LAG2 - 25,27
AP12
AP11
AP12
AP11
AP08
LAG1 - 7
EP101A3
LAG1 - 5
TAG2
TAG1
LAG1
107
ELEC./COMP.
DPHAG
AP16AP15
AP17
TFOE
I N
SAXATS
E
RE
ENIGN
LAOSSEFO
RP
ET
JOHN F. HECK IV
82984
I SG
ER D
E
RET
PROJECT
1
A
2 3 4 5
B
C
D
1 2 3 4 5
SEAL
REVISIONS
SHEET NO
DRAWING NAME
PROJECT NO:
REVIEWED BY
DATE
VE
GA
ISD
CA
RE
ER
TE
CH
NO
LOG
Y B
UIL
DIN
G20
0 LO
NG
HO
RN
ST
.V
EG
A, T
X 7
9 092
14-0424.002
01.29.2016
Addendum 01
DATE
1/29
/201
6 12
:41:
33 P
M
EP101
AG SHOP POWERPLAN
Approver
0' 4' 8' 16'
NORTH
SCALE: 1/8" = 1'-0"B1 AG SHOP POWER PLAN
GENERAL SHEET NOTES
A. GFCI RECEPTACLES WILL BE INSTALLED AT ALL LOCATIONS AS REQUIRED BY THE LATEST VERSION OF NEC, STATE AND LOCAL CODES WHETHER INDICATED ON PLANS OR NOT. SOME LOCATIONS WILL BE WITHIN 6'-0" OF SINKS, EXTERIOR DOORS AND WET
LOCATIONS. ALL EXTERIOR RECEPTACLE LOCATIONS WILL BE GFCI RATED AND WEATHERPROOF.
SHEET KEYNOTES
AF01 FIRE ALARM CONTROL PANEL (FACP). REFER TO FIRE ALARM RISER DIAGRAMON SHEET E603A FOR ADDTIONAL INFORMATION.
AF02 COORDINATE FLOW AND TAMPER SWITCH LOCATION WITH PLUMBINGDRAWINGS. PROVIDE INDICATOR LIGHT TO INDICATE LOCATION OF FLOW ANDTAMPER SWITCHES THAT ARE ABOVE THE CEILING.
AF03 REFER TO SHEET SERIES "MH" FOR LOCATION OF FIRE SMOKE DAMPERS OFDUCT DETECTOR LOCATIONS. PROVIDE INDICATED LIGHT AT CEILING LEVEL TOIDENTIFY LOCATION OF DEVICE.
AP01 REFER TO SHEET E701A FOR ADDITIONAL ELECTRICAL CONNECTIONREQUIREMENTS. REFER TO "M700" SHEET SERIES FOR MECHANICAL /ELECTRICAL INFORMATION.
AP02 EXTEND POWER CIRCUIT TO CONDENSING UNIT ON GROUND.AP03 CONDENSATE LIFT PUMP.AP04 RECEPTACLE IS GFCI AND WEATHER PROOF AND WILL BE PART OF UNIT.
CONTRACTOR WILL PROVIDE CIRCUIT INDICATED.AP05 EXTEND POWER CIRCUIT TO FAN COIL UNIT INSIDE OF BUILDING. REFER TO
SHEET E701A FOR ADDITIONAL ELECTRICAL CONNECTION REQUIREMENTS.AP06 DEVICE WILL BE RATED FOR 208-240V, 3PH & 50A. (4) #8 & (1) #10 GND IN 1 1/2"
CONDUIT. MOUNT AT 42" A.F.F.AP07 DEVICE WILL BE RATED FOR 208-240V, 3PH, & 30A. (4) #8 & (1) #10 GND IN 1 1/2"
CONDUIT. MOUNT AT 42" A.F.F.AP08 DEVICE WILL BE RATED FOR 208-240V, 1PH & 50A. (3) #8 & (1) #10 GND IN 1 1/4"
CONDUIT. MOUNT AT 42" A.F.F.AP09 DEVICE WILL BE RATED FOR 120V, 1PH & 30A. (2) #10 & (1) #10 GND IN 1"
CONDUIT. MOUNT AT 42" A.F.F.AP10 JUNCTION BOX WILL SERVE AD-1 AND ALSO HEAT TAPE ASSOCIATED WITH AC-1.AP11 PROVIDE A DROP CORD REEL RATED FOR 208V, 1PH & 50A. SECURLEY MOUNT
TO CEILING STRUCTURE. DROP CORD WILL REACH 42" A.F.F. FROM FLOOR.AP12 PROVIDE A DROP CORD REEL RATED FOR 120V, 1PH & 30A. SECURLEY MOUNT
TO CEILING STRUCTURE. DROP CORD WILL REACH 42" A.F.F. FROM FLOOR.AP13 PROVIDE A 1" CONDUIT TO FACP FOR FIRE ALARM CONNECTION TO SITE
EQUIPMENT. REFER TO SHEET E60X FOR ADDITIONAL INFORMATION. (NOTE FORBEL - FIRE ALARM DIAGRAM SHEET)
AP14 PROVIDE A 1" CONDUIT WITH (2) #10 & (1) #10 GND FOR EACH CIRCUITINDICATED.
AP15 TIME CLOCK, PROVIDE A 277V CIRCUIT. REFER TO SHEET EL103 AND DIAGRAMD2 ON SHEET E500a FOR ADDITIONAL INFORMATION.
AP16 BATTERY INVERTER, PROVIDE 277V CIRCUIT. REFER TO SHEET EL103 ANDDIAGRAM B2 ON SHEET E500a FOR ADDITIONAL INFORMATION.
AP17 MAIN GROUNDING ELECTRODE GROUND BAR. REFER TO DETAIL A4 ON SHEETE500a AND ELECTRICAL GROUNDING DIAGRAM ON SHEET E602 FOR ADDITIONALINFORMATION.
EP21 EXTEND POWER CIRCUIT TO CONDENSING UNIT ON ROOF. REFER TO EP-141CFOR ADDITIONAL INFORMATION.
SCALE: 1/4" = 1'-0"A3 ENLARGED ELEC./COMP 107
John Heck2016.01.29 13:47:08-07'00'
(TYP.)HANGER WIRES
CORNERS OF FIXTURE.
NO. 12 GAUGE WIRE HANGER TOBUILDING FRAMING OR STRUCTURALMEMBERS). SUSPEND FROM ALL FOUR
CEILING SYSTEM
LAY-IN LUMINAIRE
SEISMIC FIXTURE CLAMPS:REQUIRED AT ALL (4) LUMINAIRECORNERS WITH (2) #10 SELF-TAPPINGSCREWS. AGI SEISMIC PRODUCTSOR EQUAL. AC 184 COMPLIANT.
(TYP.)HANGER WIRESCEILING SYSTEM
BOLT CONNECTION WITH
COMPRESSION SPADE LUG
FITTING (TYPICAL)
TO SERVICE ENTRANCE GROUND
2700V INSULATORS
STAND-OFFS
COPPER BUS BAR
(REFER TO DIAGRAM AND
KEYED NOTE ON SHEET E-602.)
DEVICE AND OUTLET BOX TYPES
PER PLANS
CORD INSULATION
AND CONDUCTORS
PER PLANS
CORD REEL
BALL STOP
CHANNEL
THREADED ROD OR
APPROVED EQUIVALENT
CORD GRIP
7'-0" AFF
(MIN)
SUSPENDED
CEILING
CORD & PLUG
NEMA 5-20R
CEILING OUTLET
ASSEMBLY TO CONSIST OF THE FOLLOWING COMPONENTS
(BASIS OF DESIGN):
- HUBBELL #HBLC40123--REEL W/MOUNTING BASE
AND 12/3 WIRE LEADS
- HUBBELL #3059H--PORTABLE OUTLET BOX
- HUBBELL #3061H--LIFTING COVER WITH GFCI DEVICE PLATE
- HUBBELL #074011335--STAINLESS STEEL CORD GRIP
Hot
120/277
CAT5eLMRJ-Watt Stopper Cable
REFER TO SHEET SERIES "EL" FOR QUANTITIES AND ADDITIONAL INFORMATION
ROOM CONTROLLERLMRC-212
LMDC-100
SEE INSTALLATION INSTRUCTIONSFOR TERMINATION TYPE.
LIGHTING CONTROL DESCRIPTIONLoad (a) ALL Inboard Lamps = Manual-ON/Auto-OFFLoad (b) ALL Outboard Lamps = Manual-ON/Auto-OFF
LightingLoad(a)
Neutral
LightingLoad(b)
Two Button SwitchLMSW-102
LightingLoads(a), (b)
Watt Stopper
b
a = INNER LAMPS
b = OUTER LAMPS
LIGHTING CONTROLDESCRIPTION PLACARD MOUNT ADJACENT TO SWITCHES
a
Two Button SwitchLMSW-102
Watt Stopper
RJ45(TYPICAL)
LightingLoads(a), (b) b
a
Two Button SwitchLMSW-102
Watt Stopper
LightingLoads(a), (b) b
a
LIGHTING BATTERYINVERTER
LIGHTING BATTERY INVERTER WILL BE RATED FOR500VA OR AS INDICATED ON PLAN. INVERTER WILLOPERATE IN THE EVENT OF AN EMERGENCY.INVERTER LOCATED IN THE ELECTRICAL ROOM.
YELLOW
EMERGENCYLOAD
120V
277V
RED
INVERTERHOT
INVERTERNEUTRAL
TO PANEL FOR CONSTANT POWERREFER TO PLANS FOR CIRCUIT ANDOTHER INFORMATION
CIRCUIT (HOT/NEUTRAL)FROM LIGHTING PANEL FOR
MULTIPLE ROOMS ANDCONTROL IN EACH ROOM
WHITE
BLUE
INDIVIDUAL ROOM
SINGLE ROOM AND CONTROL ON ONE LIGHTING CIRCUIT AND ONE INVERTER
2 AMP / OR 4 WIRECONTROL DIAGRAM
ABOVE FOR THISUNIT
4 POLE
CONTACTOR
LIGHTING CONTACTOR - ELECTRICAL ROOM 107
CONTROL SEQUENCE:
(a) ON AUTOMATICALLY SELECTED ASTRONOMIC SETTING.
(b) OFF AT PRESET TIME; COORDINATE WITH OWNER'S REPRESENTATIVE.
SPARE
SPARE
DPHAG-1
SPARE
C
2.0A FUSE
PC
(18"x18"x6" HINGED COVERED PULLBOX)
NEMA TYPE1 ENCLOSURE 277V
TIMECLOCK
TERMINALBLOCK
TIMECLOCK WILL INCORPORATE
AN H-O-A SWITCH FOR MANUAL AND
AUTOMATIC CONTROL
DPHAG-8
PHOTOCELL ON
ROOF
TFOE
I N
SAXATS
E
RE
ENIGN
LAOSSEFO
RP
ET
JOHN F. HECK IV
82984
I SG
ER D
E
RET
PROJECT
1
A
2 3 4 5
B
C
D
1 2 3 4 5
SEAL
REVISIONS
SHEET NO
DRAWING NAME
PROJECT NO:
REVIEWED BY
DATE
VE
GA
ISD
CA
RE
ER
TE
CH
NO
LOG
Y B
UIL
DIN
G20
0 LO
NG
HO
RN
ST
.V
EG
A, T
X 7
9 092
14-0424.002
01.29.2016
Addendum 01
DATE
1/29
/201
6 12
:43:
53 P
M
E500a
ELECTRICALDETAILS ANDDIAGRAMS
Approver
SCALE: NO SCALEC4 LUMINAIRE SUPPORT DETAIL
SCALE: NO SCALEA4 MAIN GROUNDING ELECTRODE BUS BAR DETAIL
SCALE: NO SCALEB4 DROP CORD REEL DETAIL
SCALE: NO SCALEA2 WATT STOPPER "DLM" WIRING DIAGRAM
SCALE: NO SCALEB2 EMERGENCY LIGHTING BATTERY INVERTER DIAGRAM
SCALE: NO SCALED2 EXTERIOR LIGHTING TIME CLOCK DIAGRAM
LIGHTING SEQUENCE OF OPERATION
A. CLASSROOM
1. UNOCCUPIED MODE:
WHEN ROOM IS UNOCCUPIED, ALL LIGHTING SHALL BE DISABLED AND DE-ENERGIZED BY
OCCUPANCY SENSOR IN ROOM.
2. OCCUPIED MODE:
a. LIGHTING CONTROL IN ROOM WILL BE ENABLED BY SWITCHES IN ROOM. NO LUMINAIRES WILL
AUTOMATICALLY ENERGIZE.
b. DURING OCCUPANCY AT THREE BUTTON SWITCH:
- TOP BUTTON (a) WILL CONTROL INBOARD LAMP(S) OF LUMINAIRES IN ENTRIE OF
CLASSROOM.
- BOTTOM BUTTON (b) WILL CONTROL OUTBOARD LAMPS OF LUMINAIRES IN ENTIRE
CLASSROOM.
c. WHEN PERSONNEL LEAVE THE ROOM AND OCCUPANCY SENSOR TIMES OUT, THE SYSTEM
SHALL RESET TO THE UNOCCUPIED MODE.
B. RESTROOMS, SMALL AND LARGE:
DUAL TECHNOLOGY (ULTRASONIC/INFRARED) CEILING MOUNTED SENSOR WILL CONTROL LUMINAIRES
ON AND OFF AUTOMATICALLY. KEYED SWITCH WILL BE SECONDARY MEANS OF CONTROL.
C. STORAGE & JANITOR ROOMS:
WALL MOUNTED OCCUPANCY SENSOR WILL CONTROL THE LUMINAIRE(S) IN THE ROOM.
D. OFFICES:
1. UNOCCUPIED MODE:
WHEN ROOM IS UNOCCUPIED, ALL LIGHTING SHALL BE DISABLED AND DE-ENERGIZED BY
OCCUPANCY SENSOR IN ROOM.
2. OCCUPIED MODE:
a. LIGHTING CONTROL IN ROOM WILL BE ENABLED BY SWITCHES IN ROOM. NO LUMINAIRES WILL
AUTOMATICALLY ENERGIZE.
b. WHEN PERSONNEL LEAVE THE ROOM AND OCCUPANCY SENSOR TIMES OUT, THE SYSTEM
SHALL RESET TO THE UNOCCUPIED MODE.
E. CORRIDOR:
1. LOCAL CONTROL OF LUMINAIRES WILL BE VIA TOGGLE SWITCH.
F. EXTERIOR BUILDING LIGHTING:
1. ALL EXTERIOR BUILDING LIGHTING WILL BE PROGRAMMED TO COME ON A 1/2 HOUR BEFORE
DUSK AND OFF A 1/2 HOUR AFTER DAWN.
John Heck2016.01.29 13:46:40-07'00'
"MSB2"
1
"DPHAG"
480Y/277V, 3PH, 4W, 400A MAIN BUS
DEVICESMINIMUM
BUS BRACINGMINIMUM
35KAIC
35KA
26
60A3P
SPD
5
225A3P
225A3P
GROUND BUS3
60Y
480V
208Y/120V
3
"TAG1"150kVAK-4 RATED
225
11
225A3P
4
225A3P
2
400Y
400A3P
400A3P
2
M
8
7
400Y
6
225A3P
400A
PANEL"LAG1"
(2 SECT)
480V
208Y/120V
3
"TAG2"150kVAK-4 RATED
225
400Y
400A
PANEL"LAG2"
(2 SECT)
25
40
35
30
45
50
60
70
90
80
125
100
200
175
225
250
150
300
350
450
400
700
600
800
1000
500
1200
1600
2500
2000
3000
NOTE:
NOTESDESIGNATION
35Y
40Y
30Y
45Y
50Y
60Y
70Y
80Y
90Y
125Y
100Y
175Y
200Y
225Y
250Y
150Y
300Y
350Y
450Y
400Y
600Y
700Y
800Y
1000Y
500Y
1200Y
1600Y
2000Y
2500Y
3000Y
THREE PHASE THREE WIRE & GROUND FEEDER
FEEDER SCHEDULE
25Y
20Y
EQUIPMENT BONDING JUMPER FOR SEPARATELY DERIVED SYSTEMS PER
NEC 250.66 (PROVIDE CONDUCTOR GROUND BELOW INSTEAD OF FEEDER GROUND FOR THREE PHASE,
4-WIRE SYSTEMS INDICATED ABOVE)
20
4000
4000Y
5000Y
CONDUCTORS
4#6
(3) 4-600 KCMIL
(4) 4-600 KCMIL
(5) 4-600 KCMIL
(8) 4-500 KCMIL
(6) 4-600 KCMIL
(10) 4-600 KCMIL
(12) 4-600 KCMIL
(2) 4-250 KCMIL
(2) 4-350 KCMIL
(2) 4-500 KCMIL
(2) 4-600 KCMIL
(3) 4-400 KCMIL
4-250 KCMIL
(2) 4#4/0
4-350 KCMIL
4-500 KCMIL
4-600 KCMIL
4#4
4#4
4#2
4#2
4#1/0
4#2/0
4#3/0
4#4/0
4#1
4#10
4#10
4#12
4#8
4#8
4#8
4#8
GROUND
(3) 3/0
(4) 4/0
(5) 250 KCMIL
(6) 350 KCMIL
(8) 400 KCMIL
(10) 500 KCMIL
(12) 700 KCMIL
4
(2) 2
(2) 1
(2) 1
(2) 2
(2) 1/0
(3) 2/0
2
4
2
6
6
4
6
6
8
8
8
8
10
10
12
10
10
10
10
10
CONDUIT
(3) 4"
(4) 4"
(5) 4"
(6) 4"
(8) 4"
(10) 4"
(12) 4"
3"
(2) 3"
(2) 4"
(2) 4"
(3) 3"
(2) 3"
(2) 2 1/2"
4"
3"
4"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
2 1/2"
1 1/2"
2"
2"
2"
3/4"
3/4"
1"
3/4"
3/4"
3/4"
3/4"
3/4"
(6) 3-600 KCMIL
(8) 3-500 KCMIL
(10) 3-600 KCMIL
(5) 3-600 KCMIL
(2) 3-600 KCMIL
(4) 3-600 KCMIL
(3) 3-600 KCMIL
(3) 3-400 KCMIL
(2) 3-250 KCMIL
(2) 3-500 KCMIL
(2) 3-350 KCMIL
3-600 KCMIL
(2) 3#4/0
3#1
3#2
3#2/0
3#1/0
3#4/0
3#3/0
3-250 KCMIL
3-500 KCMIL
3-350 KCMIL
3#10
3#8
3#10
3#8
3#8
3#6
3#4
3#8
3#2
3#4
3#12
(8)400 KCMIL
(6)350 KCMIL
(10)500 KCMIL
2
(2) 2
(2) 1
(2) 1
(2) 2
(5)250 KCMIL
(4) 4/0
(3) 3/0
(3) 2/0
(2) 1/0
4
2
4
4
6
6
6
6
8
10
10
10
10
10
10
10
8
8
8
12
(6) 4"
(8) 4"
(10) 4"
4"
(2) 4"
(2) 3"
(2) 3"
(3) 3"
(5) 4"
(4) 4"
(3) 4"
(2) 4"
(2) 2 1/2"
1 1/2"
1 1/4"
1 1/2"
2 1/2"
2"
3"
4"
3"
2"
3/4"
1 1/4"
1 1/4"
1 1/4"
1"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
8
6
THREE PHASE FOUR WIRE & GROUND FEEDER
ALL CONDUCTORS ARE COPPER, TYPE THWN/THHN UNLESS OTHERWISE NOTED.
100Y-E
THREE PHASE FOUR WIRE 200% NEUTRAL & GROUND FEEDER
150Y-E
225Y-E
350Y-E
500Y-E
400Y-E
3-250 KCMIL,
2-250 KCMIL NEUT.
(2) 3#3/0,
(2) 2#3/0 NEUT.
(2) 3#4/0,
(2) 2#4/0 NEUT.
(2) 3-350 KCMIL,
(2) 2-350KCMIL NEUT.
3#2, 1#4/0 NEUTRAL
3#2/0, 2#2/0 NEUT.
(2) 2
(2) 2
8
(2) 2
4
6 2"
2 1/2"
2"
(2) 3"
(2) 2 1/2"
(2) 2 1/2"
20YS THRU 100YS
125YS THRU 150YS
4175YS THRU 200YS
2225YS THRU 300YS
1/0350YS THRU 500YS
2/0600YS THRU 700YS
GROUNDDESIGNATION
800YS THRU 5000YS 3/0
TFOE
I N
SAXATS
E
RE
ENIGN
LAOSSEFO
RP
ET
JOHN F. HECK IV
82984
I SG
ER D
E
RET
PROJECT
1
A
2 3 4 5
B
C
D
1 2 3 4 5
SEAL
REVISIONS
SHEET NO
DRAWING NAME
PROJECT NO:
REVIEWED BY
DATE
VE
GA
ISD
CA
RE
ER
TE
CH
NO
LOG
Y B
UIL
DIN
G20
0 LO
NG
HO
RN
ST
.V
EG
A, T
X 7
9 092
14-0424.002
01.29.2016
Addendum 01
DATE
1/29
/201
6 12
:43:
53 P
M
E600a
ELECTRICALONE-LINEDIAGRAM
Approver
SCALE: NO SCALEC2 ELECTRICAL ONE-LINE DIAGRAM
SCALE: NO SCALEA1 COPPER FEEDER SCHEDULE
GENERAL SHEET NOTES
SHEET KEYNOTES
1. ALL IN SQUARE DASHED AREA ARE A PART OF EARLY WORK PACKAGE PHASE OF THIS PROJECT.
2. MOLDED CASE, THERMAL-MAGNETIC CIRCUIT BREAKERS, 100% RATED AND LOCKABLE.
3. REFER TO SHEET E-602 FOR GROUNDING INFORMATION FOR THIS EQUIPMENT.
4. PROVIDE SPACE FOR ADDITIONAL CIRCUIT BREAKERS. SIZE AS INDICATED.
5. SPD MOUNTED EXTERNALLY TO SWITCHBOARD / PANELBOARD. REFERENCE SECTION 264313 FOR
ADDITIONAL INFORMATION.
6. PROVIDE SPARE CIRCUIT BREAKER(S). SIZE AS INDICATED.
7. POWER MONITOR MOUNTED EXTERNAL TO SWITCHBOARD. REFER TO SPECIFICATON SECTION 262413
FOR ADDTIONAL INFORMATION.
8. PROVIDE DATA OUTLET FOR USE UTILITY METER AND FUTURE REMOTE MONTIORING.
A. PANELBOARD AIC RATINGS ARE INDICATED ON THE PANEL SCHEDULES.
B. INFORMATION SHOWN IS DIAGRAMMATIC AND IS NOT INTENDED TO REPRESENT PHYSICAL
ARRANGEMENTS, LOCATIONS, ROUTING OR CONNECTIONS. PHYSICAL LAYOUTS ARE TO BE PER FIELD
CONDITIONS AND AS INDICATED ELSEWHERE IN THE ELECTRICAL PLANS.
C. REFERENCE THE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS REGARDING EQUIPMENT AND
INSTALLATION. NOT ALL INFORMATION SHOWN ON THIS DIAGRAM.
D. ALL PANELS WILL HAVE DOOR-IN-DOOR ACCESSIBILITY FOR EACH PANEL.
E. CONTRACTOR WILL MEASURE AND TORQUE ALL PANEL FEEDERS, MEASURE RESISTANCE TO GROUND AT
SERVICE GROUND AND PROVIDE WRITTEN DOCUMENTATION OF TEST RESULTS. CONTRACTOR WILL
COORDINATE TIME SO THAT APSD REPRESENTATIVE IS PRESENT DURING TEST.
F. CONTRACTOR WILL LABEL ALL DISTRIBUTION EQUIPMENT PRIOR TO FINAL OBSERVATION WALK THROUGH.
G. WHEN ALL EQUIPMENT IS INSTALLED REQUIRING PROGRAMMING AND TRAINING HAS BEEN COMPLETED,
THE SCHOOL'S IP ADDRESS WILL NEED TO BE GIVEN TO OWNER'S REPRESENTATIVE FOR ELECTRICAL M&O
USE.
H. REFER TO GROUNDING DIAGRAM ON SHEET E602.
B4SCALE: NO SCALE
B1 VOLTAGE DROP CALCULATIONSCALE: NO SCALE
A2 FAULT CURRENT CALCULATIONSCALE: NO SCALE
ELECTRICAL SERVICE CALCULATION
John Heck2016.01.29 13:46:23-07'00'
~ ~
<5'-0"
2'-4" MINIMUM
BUILDING STRUCTURAL STEEL
NEUTRALGROUND
PANELBOARD WITHFIRST OVERCURRENTDEVICE FOR SEPARATELYDERIVED SYSTEM (SIMILARFOR ALL SUCH PANELBOARDS)
COLD WATERPIPE
GROUND NEUTRAL
DPH2AGEQUIPMENT
TRANSFORMER FORSEPARATELY DERIVEDSYSTEM (SIMILAR FORALL SEPARATELYDERIVED DRY-TYPETRANSFORMERS)
GROUND NEUTRAL
GROUND NEUTRALMAIN GROUNDINGELECTRODEGROUND BAR
TELECOMM ROOM
#4/0
#4/0
#4/0
CW HW
WATERHEATER(TYPICAL)
NEUTRALGROUND
GROUND NEUTRAL
#4/0
COLD WATER PIPE
METER &BACKFLOWPREVENTER(S)
SWITCHBOARD,DISTRIBUTION BOARDOR PANELBOARD
GROUND
#4/0
#4/0
PANELBOARD
#4/0WITH 600VINSULATION
GRADE
GROUNDING ELECTRODECONDUCTOR SCHEDULE
NOTE: ALL CONDUCTORS ARE COPPER.
SERVICECONDUCTOR
SIZE(AWG OR kCMIL)
GROUNDING ELECTRODECONDUCTOR (AWG)
NON K-RATEDTRANSFORMER
<= #2
1/0 OR 1/0
2/0 OR 3/0
OVER 3/0THROUGH 350
OVER 350THROUGH 600
OVER 600THROUGH 1100
OVER 1100
8
6
4
2
1/0
2/0
3/0
21
23
16 14
23
1416
23
23
22
20
18
19
11
23
16
21
17
23
TO MSB2
PF
R
FAA
FSTS
TTB
FACP
SHOP106
120VAC
120VAC
DC
SUP.RET.
CEILING SPACE
5
2
7
TYP.
6
TYP.
1
9
13
11
34
10
8
PIV12
TFOE
I N
SAXATS
E
RE
ENIGN
LAOSSEFO
RP
ET
JOHN F. HECK IV
82984
I SG
ER D
E
RET
PROJECT
1
A
2 3 4 5
B
C
D
1 2 3 4 5
SEAL
REVISIONS
SHEET NO
DRAWING NAME
PROJECT NO:
REVIEWED BY
DATE
VE
GA
ISD
CA
RE
ER
TE
CH
NO
LOG
Y B
UIL
DIN
G20
0 LO
NG
HO
RN
ST
.V
EG
A, T
X 7
9 092
14-0424.002
01.29.2016
Addendum 01
DATE
1/29
/201
6 12
:43:
53 P
M
E601a
ELECTRICALDIAGRAMS
Approver
IT IS THE INTENT OF THESE DOCUMENTS TO SHOW A BASIC REPRESENTATION OF THE FIRE
ALARM SYSTEM. DEVICES INDICATED ON THESE DOCUMENTS ARE IN NO WAY IMPLIED TO BE
COMPREHENSIVE OF THE FINAL DESIGN. IT IS THE RESPONSIBILITY OF THE FIRE ALARM
CONTRACTOR TO PROVIDE A DESIGN/BUILD FIRE ALARM SYSTEM BASED UPON A THOROUGH
REVIEW OF ALL CONTRACT DOCUMENTS. IT IS THE RESPONSIBILITY OF THE FIRE ALARM
CONTRACTOR TO ENSURE THAT THE FIRE ALARM SYSTEM IS CODE COMPLIANT, MEETS THE
REQUIREMENTS OF THE AHJ AND COMPREHENSIVELY COVERS AND INCLUDES ALL NECESSARY
PARTS AND LABOR ASSOCIATED WITH OTHER TRADES AND SYSTEMS IMPACTING THE FIRE ALARM
SYSTEM. NO CHANGE ORDERS SHALL BE APPROVED FOR THE BASE SCOPE OF WORK.
GENERAL SHEET NOTES
SHEET KEYNOTES
1. MINIMUM 3/4" CONDUIT WILL BE USED FOR THIS SYSTEM FIRE ALARM CABLING AS REQUIRED BY THE
FIRE ALARM MANUFACTURER.
2. INDEPENDENTLY SUPERVISE EACH FLOW AND TAMPER SWITCH WITH AN ADDRESSABLE MODULE.
REFER TO FIRE PROTECTION / PLUMBING PLANS FOR EACH LOCATION.
3. DIGITAL COMMUNICATOR FOR CENTRAL STATION MONITORING.
4. CONDUIT AND COMMUNICATIONS CABLING FOR CENTRAL STATION REPORTING.
5. FIRE ALARM SYSTEM F.A.C.P.
6. DUCT SMOKE DETECTOR, FURNISHED BY DIVISION 28, INSTALLED IN DUCT BY DIVISION 23,
CONNECTED, WIRED AND TESTED BY DIVISION 28. REFERENCE MECHANICAL CONTROL DIAGRAMS FOR
MECHANICAL INTERCONNECTIONS. PROVIDE DUCT DETECTORS IN NEW AND EXISTING UNITS WHERE
2000CFM AND ABOVE EXIST. INSTALL PER CODE.
7. FIRE SMOKE DAMPER, ROUTE 120VAC VIA FIRE ALARM ADDRESSABLE RELAY.
8. TELEPHONE TERMINAL BOARD.
9. PROVIDE NEW ANNUNCIATOR PANEL AT ENTRY. FIELD COORDINATE EXACT LOCATION.
10. PROVIDE SURGE PROTECTION FOR CIRCUIT TO FIRE ALARM PANEL.
11. REFER TO SHEET SERIES "EP" FOR CIRCUITS SERVING THIS SYSTEM.
12. PROVIDE CONNECTION TO PIV LOCATED ON SITE. PROVIDE 1" CONDUIT AND CABLING AS DICTATED BY
MANUFACTURER.
13. PROVIDE CONNECTION TO BACK FLOW PREVENTION. PROVIDE 1" CONDUIT AND CABLING AS DICTATED
BY MANUFACTURER.
14. REFER TO ONE-LINE DIAGRAM AND FEEDER SCHEDULE FOR GROUNDED CONDUCTOR SIZE.
15. CONNECT GROUNDING ELECTRODE CONDUCTOR TO GROUND ROD.
16. FOR EQUIPMENT GROUNDING CONDUCTOR SIZE REFER TO ONE-LINE DIAGRAM AND FEEDER
SCHEDULE.
17. PROVIDE GROUNDING ELECTRODE CONDUCTOR SIZE BASED ON THE CONDUCTOR SIZE OF THE
SECONDARY OF THE TRANSFORMER. SIZE PER NEC 250.66 AND PER SCHEDULE ON THIS SHEET.
18. PROVIDE A CONCRETE-ENCASED MAIN GROUNDING ELECTRODE IN THE BUILDING FOUNDATION
AROUND THE ENTIRE PERIMETER OF THE BUILDING. LOCATE ELECTRODE IN THE BOTTOM ONE-THIRD
OF THE FOUNDATION WITH AT LEAST 3 INCHES OF CONCRETE COVER. USE EITHER #4/0 BARE COPPER
CABLE OR #6 OR LARGER STEEL REINFORCING BARS MADE ELECTRICALLY CONTINUOUS USING
EXOTHERMICALLY WELDED #4/0 JUMPERS.
19. BOND EACH PERIMETER STRUCTURAL STEEL COLUMN TO THE CONCRETE-ENCASED MAIN GROUNDING
ELECTRODE. USE EXOTHERMIC WELDS.
20. PROVIDE A 1/4" X 4" X 12" "MAIN GROUNDING ELECTRODE GROUND BAR" FOR SINGLE POINT
GROUNDING. LOCATE AT AN ACCESSIBLE POINT NEAR THE SERVICE ENTRANCE EQUIPMENT. MAKE
OTHER CONNECTIONS TO THE GROUND BAR USING TWO-HOLE COMPRESSION SPADE LUGS THAT
MEET IEEE 837 REQUIREMENTS. LABEL EACH CONNECTION.
21. USE THE "MAIN GROUNDING ELECTRODE GROUND BAR" INSTEAD OF BUILDING STRUCTURAL STEEL IF
THE FIRST OVER CURRENT DEVICE FOR THE SEPARATELY DERIVED SYSTEM IS WITHIN SAME ROOM OF
THE "MAIN GROUNDING ELECTRODE GROUND BAR".
22. INSTALL A 1/4" X 4" COPPER "TELECOMMUNICATIONS GROUNDING BUSBAR" IN EACH
TELECOMMUNICATIONS ROOM. CONNECT CABLES TO THE "TELECOMMUNICATIONS GROUNDING
BUSBAR" USING COMPRESSION SPADE LUGS. LABEL CONDUCTORS PER ANSI-J-STD-607-A. LABEL
EACH CONNECTION. SEE PLAN FOR BAR LENGTH AND LOCATIONS.
23. BONDING JUMPER SIZED PER GROUNDING ELECTRODE CONDUCTOR SCHEDULE THIS SHEET.
24. BOND HOT WATER PIPE TO COLD WATER PIPE AT EACH WATER HEATER WITH A #8 BARE COPPER
CONDUCTOR.
A. FIRE ALARM DIAGRAM INDICATES GENERAL DIAGRAMMATIC CONNECTIONS ONLY. ALL CONNECTIONS
AND INSTALLATION WILL BE PER FIRE ALARM SYSTEM MANUFACTURER'S SHOP DRAWINGS.
B. DEVICE QUANTITIES ARE NOT INDICATED ON THIS DRAWING. REFER TO FLOOR PLANS FOR QUANTITIES
AND LOCATIONS.
C. REFER TO SPECIFICATION SECTION 283111 FOR FIRE ALARM SYSTEM REQUIREMENTS.
D. FIRE ALARM WIRING AND CABLING SHALL BE IN CONFORMANCE WITH NEC AND TYPE SHALL BE AS
RECOMMENDED BY FIRE ALARM SYSTEM MANUFACTURER.
E. SEAL ALL PENETRATIONS THROUGH WALLS, FLOOR, CEILINGS AND ROOF PER ARCHITECTURAL
SPECIFIED REQUIREMENTS. SEAL WILL MATCH THE FIRE RATING OF EACH PENETRATION LOCATION.
F. INSTALL GROUNDING CONNECTIONS TO BUILDING STRUCTURE AND WATER PIPES AT LOCATIONS THAT
ARE VISIBLE AND ACCESSIBLE FOR INSPECTION, MAINTENANCE, AND TESTING.
G. INSTALL AN INSULATED THROAT GROUNDING BUSHING ON EACH METALLIC SERVICE ENTRANCE
CONDUIT. BOND TO SERVICE ENTRANCE EQUIPMENT GROUND BUS USING GROUNDING ELECTRODE
CONDUCTOR.
H. INSTALL AN INSULATED THROAT GROUNDING BUSHING ON EACH METALLIC FEEDER CONDUIT. BOND TO
GROUND BUS USING CONDUCTOR THAT IS SIZED EQUAL TO EQUIPMENT GROUNDING CONDUCTOR.
I. BOND ELECTRICAL EQUIPMENT ENCLOSURES TO GROUND BAR USING SAME SIZE CONDUCTOR AS
FEEDER EQUIPMENT GROUND CONDUCTOR OR FACTORY PROVIDED GREEN SCREW.
J. CLEAN COATED RE-BAR PRIOR TO PERFORMING ELECTRICAL CONNECTION.
SCALE: NO SCALEC2 FIRE ALARM RISER DIAGRAM
A1SCALE: NO SCALE
GROUNDING DIAGRAM
John Heck2016.01.29 13:46:10-07'00'
TFOE
I N
SAXATS
E
RE
ENIGN
LAOSSEFO
RP
ET
JOHN F. HECK IV
82984
I SG
ER D
E
RET
PROJECT
1
A
2 3 4 5
B
C
D
1 2 3 4 5
SEAL
REVISIONS
SHEET NO
DRAWING NAME
PROJECT NO:
REVIEWED BY
DATE
VE
GA
ISD
CA
RE
ER
TE
CH
NO
LOG
Y B
UIL
DIN
G20
0 LO
NG
HO
RN
ST
.V
EG
A, T
X 7
9 092
14-0424.002
01.29.2016
Addendum 01
DATE
1/29
/201
6 12
:43:
58 P
M
E700a
ELECTRICALSCHEDULES
Approver
Notes:
Total Est. Demand Current: 171 ATotal Conn. Current: 294 A
REC 98404 VA 55.08% 54202 VA Total Est. Demand: 61562 VA
MTR 3660 VA 100.00% 3660 VA Total Conn. Load: 105764 VA
NC 3700 VA 100.00% 3700 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 312 A 297 A 278 ATotal Load: 37124 VA 35324 VA 33316 VA
83 2880 VA 4200 VA 8481 2880 VA 4200 VA 8279
REC SHOP 106 30 A 32880 VA 4200 VA
3 50 A REC SHOP 10680
77 2880 VA 4200 VA 7875 2880 VA 4200 VA 7673
REC SHOP 106 30 A 32880 VA 4200 VA
3 50 A REC SHOP 10674
71 SPARE 30 A 1 0 VA 0 VA 7269 0 VA 0 VA 7067
SPARE 50 A 20 VA 0 VA
3 50 A MTR AC-1, EXTERIOR68
65 3640 VA 0 VA 1 20 A MTR AD-1, EXTERIOR 6663
REC DROP CARD, SHOP 106 50 A 23640 VA 2400 VA 1 30 A REC SHOP 106 64
61 3640 VA 2400 VA 1 30 A REC SHOP 106 6259
REC SHOP 106 50 A 23640 VA 0 VA 1 30 A SPARE 60
57 3640 VA 0 VA 1 30 A SPARE 5855
REC SHOP 106 50 A 23640 VA 0 VA 1 20 A SPARE 56
53 3640 VA 0 VA 1 20 A SPARE 5451
REC SHOP 106 50 A 23640 VA 0 VA 1 20 A SPARE 52
49 3640 VA 0 VA 1 20 A SPARE 5047
REC SHOP 106 50 A 23640 VA 0 VA 1 20 A SPARE 48
45 3640 VA 0 VA 1 20 A SPARE 4643
REC SHOP 106 50 A 23640 VA 0 VA 1 20 A SPARE 44
41 MTR RH-AH-01, SHOP 105 20 A 1 312 VA 0 VA 4239 MTR RH-AG-05, SHOP 105 20 A 1 312 VA 0 VA
2 20 A MTR CU-AG-01/FC-AG-0140
37 REC RTU-AG-01 20 A 1 312 VA 696 VA 1 20 A MTR EF-AG-04, SHOP 105 3835 MTR UH-AG-01, TOOL STORAGE 106 20 A 1 300 VA 696 VA 1 20 A MTR EF-AG-02, SHOP 105 3633 SPARE 2 A 1 0 VA 444 VA 1 20 A MTR EF-AG-01, BOYS ROOM 109 3431 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 3229 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 3027 REC SHOP 106 20 A 1 180 VA 0 VA 1 20 A SPARE 2825 REC SHOP 106 20 A 1 180 VA 0 VA 1 20 A SPARE 2623 REC SHOP 106 20 A 1 208 VA 0 VA 1 20 A SPARE 2421 REC SHOP 106 20 A 1 208 VA 0 VA 1 20 A SPARE 2219 REC SHOP 106 20 A 1 180 VA 0 VA 1 20 A SPARE 2017 REC SHOP 106 20 A 1 180 VA 360 VA 1 20 A REC EXTERIOR 1815 REC SHOP 106 20 A 1 180 VA 360 VA 1 20 A REC EXTERIOR 1613 REC SHOP 106 20 A 1 208 VA 568 VA 1 20 A REC EXTERIOR 1411 REC SHOP 106 20 A 1 180 VA 500 VA 1 20 A NC WATER FOUNTAIN, HALLWAY 101 129 REC SHOP 106 20 A 1 180 VA 900 VA 1 20 A MTR DWH-1 / ILP-1, JANITOR 108 107 NC FACP, SHOP 106 20 A 1 200 VA 1500 VA 85 REC TELECOMMUNICATIONS CABINET, STORAGE 103 20 A 1 360 VA 1500 VA
2 20 A NC HOT BOX6
3 REC ROOM 101, 106, 108, 109, 110 20 A 1 1080 VA 360 VA 1 20 A REC ROOM 104, 105, 106 41 REC ROOM 102,103,104 20 A 1 1080 VA 1080 VA 1 20 A REC ROOM 102, 104 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 84Mounting: Surface Wires: 4 Mains Rating: 400 A
Supply From: Phases: 3 Mains Type: MCBLocation: Volts: 120/208 Wye A.I.C. Rating: 10.000
Branch Panel: LAG1
LUMINAIRE SCHEDULE NOTES:
1. MANUFACTURER'S CATALOG NUMBERS REPRESENT MANUFACTURER SERIES. SHOP DRAWING SUBMITTALS WILL INCLUDE ALL PART NUMBERS REPRESENTING ALL ITEMS OF THIS LUMINAIRE SCHEDULE. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO ORDER LUMINAIRES TO INCLUDE ALL PARTS INDICATED ON SCHEDULE FOR EACH
LUMINAIRE. SUBMITTAL WILL CALL OUT EACH PART CLEARLY.
2. LUMINAIRE REQUIRES MOUNTING COORDINATION WITH ARCHITECT PRIOR TO COMMENCEMENT OF ANY WORK. THIS LUMINAIRE MAY REQUIRE A HIGHER OR LOWER MOUNTING FROM THAT PROVIDED ON THIS SCHEDULE OR NOTES ON PLAN DUE TO ARCHITECTURAL REQUIREMENTS OR CONSTRUCTION CONDITIONS.
3. ALL LUMINAIRES ON THIS LUMINAIRE SCHEDULE ARE APPROVED FOR BID ON THIS PROJECT. IF A LUMINAIRE IS SUBMITTED THAT IS NOT ON THIS SCHEDULE, IT WILL BE REJECTED.
4. SHOULD ANY LUMINAIRE BE NOT AVAILABLE AT TIME OF SUBMITTAL, CONTRACTOR WILL USE ONE OF THE OTHER LUMINAIRES INDICATED IN EACH TYPE FOR REPLACEMENT. NO OTHERS WILL BE ACCEPTED.
LUMINAIRE SCHEDULE - AG BLDGTYPE DESCRIPTION VOLTS MOUNTING LAMPS
BALLASTTYPE
EM. BAT.PK. LENS MANUFACTURER/MODEL NOTES
A1Fb 1' x 4' FLUORESCENT HIGH PERFORMANCE LUMINAIRE. LOW PROFILE SPECIFICATION
GRADE TROFFER, COLD ROLLED STEEL HOUSING WITH BAKED MATTE WHITE ENAMEL
FINISH. FLAT STEEL DOOR FRAME.
277 OR 120
MULTI-TAP
(UNV.)
CEILING RECESSED
(GYPSUM BOARD)
(2) 32W F32T8
EXTRA LONG LIFE,
3500° K,
80 CRI MIN.
ELECTRONIC
PROGRAMMED
RAPID START;
≤10% THD,
NORMAL BALLAST
FACTOR
NONE ACRYLIC PRISMATIC
A12.125
LITHONIA # SP8-F-2-32-A12125 1,3,4
ARaD 2' x 4' ARCHITECTURAL/DECORATIVE FLUORESCENT LUMINAIRE. "HIGH EFFICIENCY",
LOW PROFILE, COLD ROLLED STEEL HOUSING, BAKED MATTE WHITE ENAMEL FINISH.
277 OR 120
MULTI-TAP
(UNV.)
CEILING RECESSED
(LAY-IN GRID)
(3) 32W F32T8
EXTRA LONG LIFE,
3500° K,
80 CRI MIN.
ELECTRONIC
PROGRAMMED
RAPID START;
≤10% THD,
NORMAL BALLAST
FACTOR
NONE ACRYLIC FROSTED
CENTER BASKET
LITHONIA # 2VT8-3-32-ADP-MVOLT-GEB10PS-LP835 1,3,4
ARb 2' x 4' ARCHITECTURAL/DECORATIVE FLUORESCENT LUMINAIRE. "HIGH EFFICIENCY",
LOW PROFILE, COLD ROLLED STEEL HOUSING, BAKED MATTE WHITE ENAMEL FINISH.
277 OR 120
MULTI-TAP
(UNV.)
CEILING RECESSED
(LAY-IN GRID)
(2) 32W F32T8
EXTRA LONG LIFE,
3500° K,
80 CRI MIN.
ELECTRONIC
PROGRAMMED
RAPID START;
≤10% THD,
NORMAL BALLAST
FACTOR
NONE ACRYLIC FROSTED
CENTER BASKET
LITHONIA # 2VT8-2-32-ADP-MVOLT-GEB10PS-LP835 1,3,4
BL 4' LONG LIFE LED, HIGH ENERGY EFFICIENT LINEAR STRIP LUMINAIRE. BAKED MATTE
WHITE ENAMEL FINISH.
277 OR 120
MULTI-TAP
(UNV.)
CEILING SURFACE OR SUSPENDED
FROM JOIST OR STRUCTURE
AT 10'-0" A.F.F.
3000 LUMEN
LED, LP835,
3500° K,
80 CRI MIN.
LED DRIVER NONE WHITE ACRYLIC LITHONIA # ZL1N-L48-3000LM-FST-MVOLT-35K-80CRI-WH
METALUX # SNLED-LD1-30-UNV-LW-L835-CD-1-U
COLUMBIA # LCL4-35ML-EU
PHILIPS # LF-4-EZ-38-35-U-LAG
1,2,3,4
BVL 4' EXTREME ENVIROMENT LED, HIGH ENERGY EFFICIENT, ENCLOSED LINEAR STRIP
LUMINAIRE. INDOOR/OUTDOOR VANDAL RESISTANT WITH WIDE DISTRIBUTION.
277 OR 120
MULTI-TAP
(UNV.)
CEILING SURFACE OR SUSPENDED
FROM JOIST OR STRUCTURE
AT 10'-0" A.F.F.
4000 LUMEN LED,
LP835, 3500° K,
80 CRI MIN.
LED DRIVER NONE ACRYLIC FROSTED LITHONIA # FEM4LED-4L/35-IMAFL-SD 1,2,3,4
E LED SINGLE FACED EXIT SIGN, EMERGENCY, DIE CAST ALUMINUM HOUSING WITH
GREEN CHARACTERS, BLACK HOUSING AND BRUSHED ALUMINUM FACE
(DIRECTIONAL ARROWS AS INDICATED ON LIGHTING PLANS). MEETS UL LISTINGS
FOR THIS TYPE OF LUMINAIRE. WITH SELF-CONTAINED, SELF DIAGNOSING,
EMERGENCY BATTERY PACK.
277 OR 120
MULTI-TAP
(UNV.)
CEILING OR WALL SURFACE
8'-6" A.F.F. OR AS DIRECTED
BY ARCHITECT
LED LAMPS NONE NICKEL
CADIMUM
PER MFG.
BRUSHED ALUMINUM
FACE
LITHONIA # LE-S-1-G-ELN-SD
SURE-LITES # CX71SD
DUAL-LITE # SE-S-G-BN-E-I
EVENLITE # CCDS-EM-G-1-AB
1,2,3,4
EG LED SINGLE FACED EXIT SIGN, EMERGENCY, DIE CAST ALUMINUM HOUSING WITH
GREEN CHARACTERS, BLACK HOUSING AND BRUSHED ALUMINUM FACE
(DIRECTIONAL ARROWS AS INDICATED ON LIGHTING PLANS). MEETS UL LISTINGS
FOR THIS TYPE OF LUMINAIRE. WITH SELF-CONTAINED, SELF DIAGNOSING,
EMERGENCY BATTERY PACK. 9-GUAGE STEEL ROD WIRE GUARD PROTECTION.
277 OR 120
MULTI-TAP
(UNV.)
CEILING OR WALL SURFACE
8'-6" A.F.F. OR AS DIRECTED
BY ARCHITECT
LED LAMPS NONE NICKEL
CADMIUM PER
MFG.
BRUSHED ALUMINUM
FACE
LITHONIA # LE-S-1-G-ELN-SD-ELAWG1
SURE-LITES # CX71SD-WG10
DUAL-LITE # SE-S-G-BN-E-I-WGLX
EVENLITE # CCDS-EM-G-1-AB-M990010
1,2,3,4
EM CONTEMPORARY, LOW PROFILE EMERGENCY BATTERY PACK FIXTURE WITH AN
INJECTED MOLDED, HIGH IMPACT, UV STABILIZED THERMOPLASTIC HOUSING, ADA
COMPLIANT, ADJUSTABLE LAMP SOCKETS, SHORT CIRCUIT AND BROWNOUT
PROTECTION, SELF DIAGNOSING SYSTEM.
277 OR 120
MULTI-TAP
(UNV.)
WALL SURFACE 7'-6" A.F.F.
OR AS DIRECTED
BY ARCHITECT
(2) TWO 1.5W LED
LAMPS
LED DRIVER NICKEL
CADMIUM PER
MFG.
ACRYLIC FRESNAL LITHONIA # ELM2-LED-SD
SURE-LITES # LEM2-SD
DUAL-LITE # EV2I
EVENLITE # TCL-2-W-SD
1,2,3,4
FLE ENERGY EFFICIENT, LOW MAINTENCE, LOW PROFILE WALL MOUNTED EXTERIOR
LUMINAIRE. HIGH PERFORMANCE LED WITH SILOCONE SEALED OPTICAL CHAMBER
AND TEMPERED GLASS LENS. THROUGH LIGHTING INVERTER.
277 OR 120
MULTI-TAP
(UNV)
EXTERIOR WALL SURFACE
10'-0" A.F.F. OR AS
DIRECTED BY ARCHITECT
1800 LUMEN
LED, 4000° K,
80 CRI MIN.
LED DRIVER via INVERTER TEMPERED GLASS LITHONIA # OLWX1-LED-20W-40K
LUMARK # XTOR3A-N
ENVOY # DLC-LWP22-3500K
DECO # VINCI-LED-20-40-UNV-BZ
1,2,3,4
John Heck2016.01.29 13:46:02-07'00'
TFOE
I N
SAXATS
E
RE
ENIGN
LAOSSEFO
RP
ET
JOHN F. HECK IV
82984
I SG
ER D
E
RET
PROJECT
1
A
2 3 4 5
B
C
D
1 2 3 4 5
SEAL
REVISIONS
SHEET NO
DRAWING NAME
PROJECT NO:
REVIEWED BY
DATE
VE
GA
ISD
CA
RE
ER
TE
CH
NO
LOG
Y B
UIL
DIN
G20
0 LO
NG
HO
RN
ST
.V
EG
A, T
X 7
9 092
14-0424.002
01.29.2016
Addendum 01
DATE
1/29
/201
6 12
:44:
02 P
M
E701a
ELECTRICALSCHEDULES
Approver
Notes:
Total Est. Demand Current: 194 ATotal Conn. Current: 351 A
Total Est. Demand: 69864 VA
REC 123200 VA 54.06% 66600 VA Total Conn. Load: 126464 VA
MTR 3264 VA 100.00% 3264 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 369 A 369 A 327 ATotal Load: 43600 VA 43600 VA 39264 VA
83 SPARE 20 A 1 0 VA 312 VA 1 20 A MTR RH-AG-08, SHOP 105 8481 MTR EF-AG-05, SHOP 105 20 A 1 696 VA 312 VA 1 20 A MTR RH-AG-07, SHOP 105 8279 MTR EF-AG-03, SHOP 105 20 A 1 696 VA 312 VA 1 20 A MTR RH-AG-06, SHOP 105 8077 SPARE 20 A 1 0 VA 312 VA 1 20 A MTR RH-AG-04, SHOP 105 7875 SPARE 20 A 1 0 VA 312 VA 1 20 A MTR RH-AG-03, SHOP 105 7673 SPARE 20 A 1 0 VA 312 VA 1 20 A MTR RH-AG-02, SHOP 105 7471 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 7269 0 VA 0 VA 1 20 A SPARE 7067
SPARE 50 A 20 VA 0 VA 1 20 A SPARE 68
65 0 VA 0 VA 1 20 A SPARE 6663
SPARE 50 A 20 VA 0 VA 1 20 A SPARE 64
61 0 VA 0 VA 1 20 A SPARE 6259
SPARE 50 A 20 VA 0 VA 1 20 A SPARE 60
57 0 VA 0 VA 1 20 A SPARE 5855
SPARE 50 A 20 VA 0 VA 1 20 A SPARE 56
53 0 VA 0 VA 1 20 A SPARE 5451
SPARE 50 A 20 VA 0 VA 1 20 A SPARE 52
49 0 VA 0 VA 1 20 A SPARE 5047
SPARE 50 A 20 VA 0 VA 1 30 A SPARE 48
45 0 VA 0 VA 1 30 A SPARE 4643
SPARE 50 A 20 VA 0 VA 1 30 A SPARE 44
41 SPARE 20 A 1 0 VA 2400 VA 1 30 A REC SHOP 106 4239 3640 VA 2400 VA 1 30 A REC SHOP 106 4037
REC SHOP 106 50 A 23640 VA 2400 VA 1 30 A REC SHOP 106 38
35 3640 VA 2400 VA 1 30 A REC SHOP 106 3633
REC SHOP 106 50 A 23640 VA 2400 VA 1 30 A REC SHOP 106 34
31 3640 VA 2400 VA 1 30 A REC SHOP 106 3229
REC SHOP 106 50 A 23640 VA 2400 VA 1 30 A REC SHOP 106 30
27 3640 VA 2400 VA 1 30 A REC SHOP 106 2825
REC DROP CARD, SHOP 106 50 A 23640 VA 2400 VA 1 30 A REC SHOP 106 26
23 3640 VA 2400 VA 1 30 A REC SHOP 106 2421
REC SHOP 106 50 A 23640 VA 2400 VA 1 30 A REC SHOP 106 22
19 3640 VA 2400 VA 1 30 A REC SHOP 106 2017
REC SHOP 106 50 A 23640 VA 2400 VA 1 30 A REC SHOP 106 18
15 3640 VA 2400 VA 1 30 A REC SHOP 106 1613
REC SHOP 106 50 A 23640 VA 2400 VA 1 30 A REC SHOP 106 14
11 3640 VA 2400 VA 1 30 A REC SHOP 106 129
REC SHOP 106 50 A 23640 VA 2400 VA 1 30 A REC SHOP 106 10
7 3640 VA 2400 VA 1 30 A REC SHOP 106 85
REC SHOP 106 50 A 23640 VA 2400 VA 1 30 A REC SHOP 106 6
3 3640 VA 2400 VA 1 30 A REC SHOP 106 41
REC SHOP 106 50 A 23640 VA 2400 VA 1 30 A REC SHOP 106 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 84Mounting: Surface Wires: 4 Mains Rating: 400 A
Supply From: Phases: 3 Mains Type: MCBLocation: Volts: 120/208 Wye A.I.C. Rating: 10,000
Branch Panel: LAG2
ELECTRICAL CONNECTIONS FOR MECHANICAL EQUIPMENT SCHEDULE- AG BLDG
EQUIPMENTNUMBER EQUIPMENT DESCRIPTION VOLTAGE PHASE
BRANCH CIRCUITCONDUCTORDESCRIPTION C
ON
DU
IT S
IZE
MOTOR STARTERCHRACTERISTICS
DISCONNECT SWITCHCHARACTERISTICS
KEY NOTEST
AR
TE
R T
YP
E
ST
AR
TE
R S
IZE
OF
F/A
UT
O O
R H
OA
PILOTLIGHT
EXTRACONTACT
S
VO
LTS
FR
AM
E A
MP
S
FU
SE
SIZ
E
SOLIDNEUT. /
GND LUG NE
MA
RA
TIN
G
RE
D
GR
EE
N
NO NCAG-AC-1 AIR COMPRESOR 208 V 3 (4) #8 & (1) #10 GND 1 1/2" - - - - - - - 250 60 C YES 3R B,D
AG-CU-01 SPLIT SYSTEM 115 V 1 (3) #10 & (1) #10 GND 3/4" - - - - - - - 250 30 C YES 3R B,D
AG-FC-01 SPLIT SYSTEM 115 V 1 (3) #10 & (1) #10 GND 3/4" - - - - - - - 250 30 C YES 1 B,D
AG-RTU-01 ROOF TOP UNIT 480 V 3 (4) #10 & (1) #10 GND 3/4" - - - - - - - - - - - - A,B
ELECTRICAL CONNECTIONS FOR MECHANICAL EQUIPMENT SCHEDULE NOTES:
A. STARTER, CONTROL SYSTEM AND DISCONNECTING MEANS FOR UNIT WILL BE FACTORY PROVIDED. CONTRACTOR WILL HAVE ONE POINT OF ELECTRICAL CONNECTION. FOR VFD OR CONTROL EQUIPMENT INFORMATION, REFER TO SHEET SERIES M700.
B. RACEWAY SYSTEM AND CONDUCTORS FOR CONTROLS WILL BE PROVIDED BY DIVISION 26 UNLESS SPECIFICALLY CALLED OUT TO BE PROVIDED BY OTHER SECTIONS OF THESE DOCUMENTS. REFER TO SHEET SERIES "M" FOR CONTROL DIAGRAMS AND ALSO REFER TO
SPECIFICATION SECTION 230549.
C. STARTER, CONTROL SYSTEM FOR UNIT WILL BE FACTORY PROVIDED. CONTRACTOR WILL PROVIDE DISCONNECTING MEANS AND HAVE ONE POINT OF ELECTRICAL CONNECTION. FOR CONTROL EQUIPMENT INFORMATION, REFER TO SHEET SERIES M700
John Heck2016.01.29 13:45:49-07'00'
TFOE
I N
SAXATS
E
RE
ENIGN
LAOSSEFO
RP
ET
JOHN F. HECK IV
82984
I SG
ER D
E
RET
PROJECT
1
A
2 3 4 5
B
C
D
1 2 3 4 5
SEAL
REVISIONS
SHEET NO
DRAWING NAME
PROJECT NO:
REVIEWED BY
DATE
VE
GA
ISD
CA
RE
ER
TE
CH
NO
LOG
Y B
UIL
DIN
G20
0 LO
NG
HO
RN
ST
.V
EG
A, T
X 7
9 092
14-0424.002
01.29.2016
Addendum 01
DATE
1/29
/201
6 12
:44:
04 P
M
E702a
ELECTRICALSCHEDULES
Approver
Notes:
Total Est. Demand Current: 12 A
LTG-EXT 180 VA 125.00% 225 VA Total Conn. Current: 11 A
LTG 4358 VA 125.00% 5448 VA Total Est. Demand: 10083 VA
MTR 4210 VA 100.00% 4210 VA Total Conn. Load: 8948 VA
NC 200 VA 100.00% 200 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 14 A 13 A 9 ATotal Load: 3651 VA 3394 VA 2390 VA
41 SPACE ONLY -- -- 0 VA 0 VA 42
39 SPACE ONLY -- -- 0 VA 0 VA 40
37 SPACE ONLY -- -- 0 VA 0 VA
3 225 A PANEL LAG1 VIA TAG2
38
35 SPACE ONLY -- -- 0 VA 0 VA 36
33 SPACE ONLY -- -- 0 VA 0 VA 34
31 SPACE ONLY -- -- 0 VA 0 VA
3 225 A PANEL LAG1 VIA TAG1
32
29 SPACE ONLY -- -- 0 VA 0 VA -- -- SPACE ONLY 30
27 SPACE ONLY -- -- 0 VA 0 VA -- -- SPACE ONLY 28
25 SPACE ONLY -- -- 0 VA 0 VA -- -- SPACE ONLY 26
23 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 24
21 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 22
19 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 20
17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18
15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16
13 LTG ROOMS 20 A 1 1380 VA 0 VA 1 20 A SPARE 14
11 LTG SHOP 105 20 A 1 490 VA 0 VA 1 20 A SPARE 12
9 LTG SHOP 105 20 A 1 488 VA 500 VA 1 20 A BATTERY INVERTER, ELEC 107 10
7 LTG SHOP 105 20 A 1 488 VA 200 VA 1 20 A NC TIME CLOCK, ELEC 107 8
5 LTG SHOP 105 20 A 1 497 VA 1403 VA 6
3 LTG SHOP 105 20 A 1 1003 VA 1403 VA 4
1 LTG-EXT EXTERIOR BUILDING LIGHTING 20 A 1 180 VA 1403 VA
3 20 A MTR RTU-AG-01, EXTERIOR
2CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 84Mounting: Surface Wires: 4 Mains Rating: 400 A
Supply From: Phases: 3 Mains Type: 400A MCBLocation: Volts: 480/277 Wye A.I.C. Rating: 22,000
Branch Panel: DPHAGROOM 107
"MSB2"
John Heck2016.01.29 13:45:40-07'00'
A B C D E F G
1
2
3
4
5
K-3544HIGHLINE
C_TOILETS
VITREOUS CHINA
K-3544HIGHLINE
C_TOILETS
VITREOUS CHINA
K-3544HIGHLINE
C_TOILETS
VITREOUS CHINA
P1a P1a
P2P1
P5
P4
P3
P3P3
P3FD1
FD1
~
SA
N
SAN
4" SAN
2" SAN
4" SAN
4" SAN
4" VTR
V
V
2" V
2" V
DCOTG
AG-RTU-01
AG-CU-01
CD
3/4" CD
AG-FC-01
AG-RH-05 AG-RH-06 AG-RH-07 AG-RH-08
AG-EF-05AG-EF-04
AG-RH-01AG-RH-02
AG-RH-02
AG-RH-04
AG-EF-03AG-EF-02
105
SHOP
101
HALLWAY
102
CLASSROOM
103
STORAGE
104
OFFICE
110
GIRLS109
BOYS
108
JANITOR
106
TOOLSTORAGE
107
ELEC./COMP.
P7
SAN
4" SAN
2" SAN
1 1/2" VV
TFOE
C
I N
EI
L D
ESN
SAXATS
E
RE
ENIGN
LAOSSEFO
RP
ET
ABBAS SHIRIAN
102840
PROJECT
1
A
2 3 4 5
B
C
D
1 2 3 4 5
SEAL
REVISIONS
SHEET NO
DRAWING NAME
PROJECT NO:
REVIEWED BY
DATE
VE
GA
ISD
CA
RE
ER
TE
CH
NO
LOG
Y B
UIL
DIN
G20
0 LO
NG
HO
RN
ST
.V
EG
A, T
X 7
9 092
14-0424.002
01.29.2016
Addendum 01
DATE
1/29
/201
6 11
:44:
05 A
M
PL101
AG SHOP WASTE& VENT PLAN
AS
GENERAL SHEET NOTES
SHEET KEYNOTES
1. ROUTE PIPING BELOW FLOOR.
2. ROUTE PIPING ABOVE CEILING.
3. ROUTE PIPING BELOW GRADE.
4. SEE CIVIL DRAWINGS FOR CONTINUATION.
5. CONDENSATE DRAIN FROM ROOF TOP UNITS (RTU) SHALL DRAIN TO GRADE IN CODE COMPLIANT
MANNER.
6. CONDENSATE DRAIN FROM AC UNIT SHALL DRAIN TO SERVICE IN CODE COMPLIANT MANNER.
A. SEE SHEET P702 FOR PLUMBING FIXTURE ROUGH-IN SCHEDULE.
B. ALL VERTICAL SANITARY PIPING ABOVE FINISHED FLOOR SHALL HAVE WALL CLEANOUT INSTALLED.
SCALE: 1/8" = 1'-0"A1 AG SHOP WASTE & VENT PLAN
1
12
2
2
3
4
5
6
0' 4' 8' 16'
NORTH
Abbas2016.01.29 11:57:13-07'00'
A B C D E F G
1
2
3
4
5
K-3544HIGHLINE
C_TOILETS
VITREOUS CHINA
K-3544HIGHLINE
C_TOILETS
VITREOUS CHINA
K-3544HIGHLINE
C_TOILETS
VITREOUS CHINA
AG-RTU-01
AG-EF-02 AG-EF-03
AG-RH-01
AG-RH-02 AG-RH-02
AG-RH-04
AG-RH-05 AG-RH-06 AG-RH-07AG-RH-08
AG-EF-05AG-EF-04
AG-CU-01
AG-FC-01
AG-UH-01
AG-EF-01
P1a P1a
P2P1
P10
P9
P3
P3P3
P3
DWH-1
P14
DCWDHW
DC
W
DH
WR
DH
W
~
2" DCW
2" DCW
2" DCW2" DCW1" DHW 3/4" DHWR
~
G G
G
G G G
2 1/2" G
1/2" G
2" G
G
2" G 1 1/2" G 1 1/2" G
2" G
1 1/2" G
1 1/2" G
G
1 1/4" G
P16
3/4" DCW
P16
3/4" DCW
3/4" A
3/4" A
2" A
105
SHOP
101
HALLWAY
102
CLASSROOM
103
STORAGE
104
OFFICE
110
GIRLS109
BOYS
108
JANITOR
106
TOOLSTORAGE
107
ELEC./COMP.
TFOE
C
I N
EI
L D
ESN
SAXATS
E
RE
ENIGN
LAOSSEFO
RP
ET
ABBAS SHIRIAN
102840
PROJECT
1
A
2 3 4 5
B
C
D
1 2 3 4 5
SEAL
REVISIONS
SHEET NO
DRAWING NAME
PROJECT NO:
REVIEWED BY
DATE
VE
GA
ISD
CA
RE
ER
TE
CH
NO
LOG
Y B
UIL
DIN
G20
0 LO
NG
HO
RN
ST
.V
EG
A, T
X 7
9 092
14-0424.002
01.29.2016
Addendum 01
DATE
1/29
/201
6 11
:39:
15 A
M
PP101
AG SHOPPRESSUREPIPING PLAN
AS
GENERAL SHEET NOTES
SHEET KEYNOTES
1. ROUTE PIPING ABOVE CEILING.
2. ROUTE PIPING HIGH IN CEILING SPACE.
3. ROUTE PIPING BELOW GRADE.
4. SEE CIVIL DRAWINGS FOR CONTINUATION.
5. GAS METER/REGULATOR SIZED FOR ____CFH WITH AN ENTERING HIGH PRESSURE AND LEAVING
PRESSURE OF 14" WC. INSTALL PETES PLUGS ON BOTH SIDES OF REGULATOR. REGULATOR SHALL BE
VENT LIMITING TYPE.
6. SEE DETAIL ____ FOR AIR COMPRESSOR DETAIL.
7. VERIFY EXACT LOCATION OF EXISTING GAS LINE.
8. CONDENSATE DRAIN FROM AIR COMPRESSOR SHALL DRAIN TO GRADE IN CODE COMPLIANT MANNER.
9. PROVIDE 18" X 18" ACCESS DOOR.
10. ROUTE FULL SIZE T&P DRAIN RELIEF VALVE TO MOP SINK.
11. FIRE SPRINKLER ALARM VALVE.
A. SEE SHEET P702 FOR PLUMBING FIXTURE ROUGH-IN SCHEDULE.
B. PROVIDE GAS SHUT-OFF VALVE DIRTLEG AND UNION AT GAS FIRED EQUIPMENT.
SCALE: 1/8" = 1'-0"A1 AG SHOP PRESSURE PIPING PLAN
4
7
2
2
22
1
1
1
2
33
3 5
4
9
10
11
8
6
2
0' 4' 8' 16'
NORTH
Abbas2016.01.29 11:57:44-07'00'
4
5
1
5 5
2
3
6
1
2
3
4
5
6
AMES IN-BUILDING RISER. STAINLESS
STEEL TYPE 304. SEE PLANS FOR SIZE AND
SERVICE
DUCTILE, CAST-IRON, OR PVC WATER
SERVICE.
MECHANICAL JOINT FROM SUPPLY PIPE TO
STAINLESS STEEL, CONTINUE INTO
BUILDING WITH STAINLESS STEEL.
CONCRETE THRUST BLOCK SIZED IN
ACCORDANCE WITH UBC IF REQUIRED BY
AHJ
PIPE SLEEVE, SEE SPECIFICATIONS
MEGALUG PIPE RESTRAINT HARNESS
FLOW
4
1
2
3
4
5
6
1
5 5
2
3
6
AMES IN-BUILDING RISER. STAINLESS
STEEL TYPE 304. SEE PLANS FOR SIZE AND
DUCTILE, CAST-IRON, OR PVC WATER
MECHANICAL JOINT FROM SUPPLY PIPE TO
STAINLESS STEEL, CONTINUE INTO
BUILDING WITH STAINLESS STEEL
CONCRETE THRUST BLOCK SIZED IN
ACCORDANCE WITH UBC IF REQUIRED BY
PIPE SLEEVE, SEE SPECIFICATIONS
MEGALUG PIPE RESTRAINT HARNESS
FLOW
1
2
3
4
5
6
7
8
9
10
11
12
13
14
16
4
13
2
12
7
3
2
9
10
5
911
7
8
#
#
#
#
#
#
#
#
#
#
14
FINISH FLOOR
DCW
DHW
DCW
DHW
SAN
NOTE: INSTALL THERMOSTATIC MIXING VALVE ASSEMBLY
IN ACCORDANCE WITH MANUFACTURERS
RECOMMENDATION. PROVIDE PIPING SCHEMATIC WITH
SUBMITTALS
DHC
DHC
G
G
D
EXPANSION TANK P#
FULL SIZED T&P RELIEF VALVE
INDIRECTLY DISCHARGED TO FLOOR SINK,
2X PIPE DIA.
PLUG VALVE W/DIRT LEG
THERMOMETER (TYPICAL)
THERMOSTATIC MIXING VALVE P#
IN-LINE PUMP ILP-#
SEISMIC STRAPPING PER UPC 508.2
(IF REQUIRED)
4" MIN. HOUSEKEEPING PAD
CIRCUIT SETTER/BALANCING VALVE
PETE'S PLUGS (TYPICAL)
HEAT TRAP PER MFG. SPEC'S
UNION (TYPICAL)
COMBUSTION AIR INTAKE AND FLUE BY
MECHANICAL
DOMESTIC WATER HEATER, SEE SPEC'S
6" MIN.## GPM
## GPM
#
#
#
#
#
#
#
#
#
#
1
2
3
4
5
6
7
8
9
10
19
2
8
3
44
106 7 5
SERVICE LINE, SEE SPECIFICATIONS FOR PIPE
MATERIALS.
SAME SIZE AS SERVICE LINE,
THRU 4" PIPE, MAXIMUM 4"
SIZE REQUIRED.
CAST IRON SOIL PIPE RISER
AND FITTINGS.
COMPACTED EARTH, SEE
SPECIFICATIONS.
CLEANOUT WITH HEAVY DUTY SCORIATED
SECURED TOP .
FINISH HARDSCAPE. SEE SITE PLAN
DRAWINGS FOR ELEVATION.
18"X18"X4" THICK CONCRETE COLLAR.
1/8TH BEND.
WYE FITTING.
2" CHAMFER ON ALL COLLARS IN EARTH.
FLOW
7 5
1
2
3
4
5
6
7
8
9
10
8 5 6
44 2
3
9
101
9
10
SERVICE LINE, SEE SPECIFICATIONS FOR
PIPE MATERIALS.
SAME SIZE AS SERVICE LINE,
THRU 4" PIPE, MAXIMUM 4"
SIZE REQUIRED.
CAST IRON SOIL PIPE RISER
AND FITTINGS.
COMPACTED EARTH, SEE
SPECIFICATIONS.
12"-18"
CLEANOUT WITH HEAVY DUTY SCORIATED SECURED TOP .
2" CHAMFER ON ALL COLLARS IN EARTH.
FINISH HARDSCAPE. SEE SITE PLAN DRAWINGS
FOR ELEVATION.
4" THICK CONCRETE PAD.
1/8TH BEND.
WYE FITTING.
FLOW
CLEANOUT PLUG
W/LEAD SEAL
STAINLESS STEEL
ACCESS COVER W/
COUNTERSUNK SCREW
FINISHED WALL
CLEANOUT TEE1
2
3
4
5
6
7
8
2 6
1
3 5
7
4
8
TRAP GUARD WATER SAVING DEVICE
SIZED PER DRAIN (IF SPECIFIED)
FINISHED FLOOR SLOPED IN
ACCORDANCE WITH ARCH.
DRAWINGS. COORDINATE WITH
STRUCTURAL
SEE PLUMBING FLOOR PLANS FOR
SIZING AND P-TRAP REQUIREMENTS
FOUR BAND HEAVY DUTY CLAMP, SEE
SPECIFICATIONS
FLOOR DRAIN WITH ADJUSTABLE
STRAINER, DOUBLE DRAINAGE
FLANGE AND WEEP HOLES. SEE
FLOOR DRAIN SPECIFICATIONS
CLAMP TO 24"x24" 4# LEAD SHEET AND
WATERPROOFING MEMBRANE (NOT
REQUIRED FOR SINGLE POUR
CONSTRUCTION)
CONCRETE FLOOR OF TWO POUR
CAULK AS REQUIRED ON
INSTALLATION ABOVE GRADE
TFOE
C
I N
EI
L D
ESN
SAXATS
E
RE
ENIGN
LAOSSEFO
RP
ET
ABBAS SHIRIAN
102840
PROJECT
1
A
2 3 4 5
B
C
D
1 2 3 4 5
SEAL
REVISIONS
SHEET NO
DRAWING NAME
PROJECT NO:
REVIEWED BY
DATE
VE
GA
ISD
CA
RE
ER
TE
CH
NO
LOG
Y B
UIL
DIN
G20
0 LO
NG
HO
RN
ST
.V
EG
A, T
X 7
9 092
14-0424.002
01.29.2016
Addendum 01
DATE
1/29
/201
6 11
:44:
56 A
M
P500a
PLUMBINGDETAILS
AS
SCALE: 1/4" = 1'-0"1 WATER ENTRY THRU FOOTINGSCALE: 1/4" = 1'-0"2 WATER ENTRY BELOW FOOTING
SCALE: 1/4" = 1'-0"3 $P-06-23 DOMESTIC WATER HEATER Copy 1
SCALE: 1/4" = 1'-0"4 CLEANOUT TO GRADESCALE: 1/4" = 1'-0"5 DOUBLE CLEANOUT TO GRADE
SCALE: 1/4" = 1'-0"6 WALL CLEANOUTSCALE: 1/4" = 1'-0"7 FLOOR DRAIN
Abbas2016.01.29 11:57:27-07'00'
P1 WATER CLOSET:
TYPE: FLOOR MOUNT, SIPHON JET, 1-1/2" TOP-SPUD, 1.28 GALLON PER FLUSH, ELONGATED,
VITREOUS CHINA,
MFG: KOHLER NO. K-4405 "HIGHLINE".
SEAT: SOLID PLASTIC, OPEN FRONT, FIRE RETARDANT, ELONGATED, WITHOUT COVER,
STAINLESS STEEL CHECK HINGE.
MFG: OLSONITE NO. 95.
FLUSH VALVE: EXPOSED, MANUAL, CHROME PLATED, DIAPHRAGM TYPE, FLUSHOMETER, 1.28 GALLON
PER FLUSH.
MFG: SLOAN NO. 111-1.28 "ROYAL"
CARRIER: ZURN, WADE JOSAM OR SMITH (1,000 LBS. CAPACITY)
MTD. HEIGHT: SEE ARCHITECTURAL DRAWINGS.
PLUMBING FIXTURE SPECIFICATIONS
SYMBOL DESCRIPTION
P2 URINAL:
TYPE: WALL MOUNTED, SIPHON JET FLUSHING, VITREOUS CHINA, 3/4" TOP SPUD, LOW
CONSUMPTION, 0.125 GALLON PER FLUSH.
MFG: KOHLER K-4904-ET "BARDON"
CARRIER: FLOOR SUPPORTED, CONCEALED IN WALL.
MFG: ZURN, WADE, JOSAM OR SMITH.
FLUSH VALVE:EXPOSED, MANUAL, CHROME PLATED FLUSHOMETER.
0.125 GALLON PER FLUSH.
MTD HEIGHT: SEE ARCHITECTURAL DRAWINGS.
P2a URINAL (HANDICAP):
TYPE: SAME AS P2 EXCEPT MOUNTING HEIGHT. SEE ARCH. PLANS.
P5 DRINKING FOUNTAIN (HANDICAP):
TYPE: WALL HUNG, ADA COMPLIANT, BI-LEVEL, FRONT PUSH BUTTON, 18 GA. STAINLESS
STEEL, VANDAL RESISTANT CHROME PLATED BUBBLER, VANDAL RESISTANT
BOTTOM PLATES, INLINE STRAINER, WITH BOTTLE FILLING STATION.
MFG: ELKAY EZH20 VRCGRNTL8WSK
ACCESSORY: APRON LKAPREZL
SUPPLIES: 1/2" X 3/8" WHEEL ANGLE STOPS WITH 3/8" O.D. FLEX RISERS.
TRAP: 1-1/4" 17 GA. POLISHED CHROME TUBULAR P-TRAP.
CARRIER:CONCEALED BY ZURN, WADE, JOSAM, OR SMITH.
MTD HEIGHT: SEE ARCHITECTURAL DRAWINGS.
P4 SERVICE SINK:
TYPE: FLOOR MOUNTED, 24" X 24" X 10" DEEP, MOLDED STONE, 3" DRAIN OPENING.
MFG: FIAT NO. MSB-2424.
FAUCET: POLISHED CHROME, WALL MOUNTED 42" ABOVE FLOOR, WALL BRACE, VACUUM
BREAKER, INTEGRAL CHECK STOPS.
MFG: CHICAGO NO. 897-CP-C.
DRAIN: INTEGRAL WITH STAINLESS STEEL STRAINER.
TRAP: 3" CAST IRON "P" TRAP.
ACCESSORIES: HOSE AND HOSE BRACKET NO. 832AA, STAINLESS STEEL, 24" X 3" MOP HANGER NO.
889-CC, VINYL BUMPER GUARD NO. E-77-AA.
P7 WATER HAMMER ARRESTOR:
TYPE: STAINLESS STEEL CONSTRUCTION, PRE-CHARGED, PERMANENTLY SEALED.
SEE SHOCK ABSORBER SCHEDULE FOR UNIT SIZE
MFG: JAY R. SMITH 5000 SERIES.
NOTE: PROVIDE AND INSTALL BEHIND LOCKING 14"X14" ACCESS PANEL.
P8 EXPANSION TANK:
TYPE: PRE-PRESSURED TANK WITH SEALED-IN AIR CHARGE OF 55 PSI.
SIZE: 53 GAL, TOTAL VOLUME, 0.65 MAX. ACCEPTANCE.
MFG: AMTROL NO. ST-80V-C.
P9 WALL HYDRANT:
TYPE: BRONZE HYDRANT, FREEZE-PROOF, INTEGRAL VACUUM BREAKER, WITH LOOSE-KEY,
3/4" INLET AND 3/4" GARDEN HOSE OUTLET, LOOSE KEY HANDLE, VERIFY WALL
THICKNESS BEFORE ORDERING.
MFG: ZURN NO. Z-1310.
TMV THERMOSTATIC MIXING ASSEMBLY (DOMESTIC HOT WATER):
TYPE: HIGH LOW DUAL STAGE THERMOSTATIC WATER MIXING SYSTEM SET FOR 120F.
LARGE AND SMALL TYPE THERMOSTATIC WATER MIXING VALVES, ADJUSTABLE
HIGH TEMPERATURE LIMIT STOP, INLET CHECKSTOPS, WALL SUPPORT, OUTLET
BALL VALVE, 1 GPM MINIMUM FLOW CAPACITY, INLET MANIFOLD PIPING, OUTLET
PRESSURE REGULATING VALVE AND PRESSURE GAUGES, COLOR-COATED
DIAL THERMOMETER (0 TO 140F), FACTORY ASSEMBLED AND TESTED, ROUGH
FINISH.
INLET: 3".
OUTLET: 3".
MFG: LEONARD NO. TM-186-20015020-PRV-RF.
FD1 FLOOR DRAIN:
TYPE: 7" DIAMETER, ROUND TYPE "B" STRAINER. POLISHED BRONZE, CAST IRON BODY WITH
BOTTOM OUTLET, COMBINATION INVERTABLE MEMBRANE CLAMP, DEEP SEAL P-TRAP,
VANDAL-PROOF SECURED TOP, DIAMETER OF OUTLET AS SHOWN ON DRAWINGS.
MFG: ZURN NO. Z-415-B-VP-Z1000.
NOTE: PROVIDE WITH PROSET TRAP GUARD WATER SAVING DEVICE. SIZE AS INDICATED BY
DRAIN.
FS1 FLOOR SINK:
TYPE: CAST IRON BODY WITH WHITE ACID RESISTING ENAMEL BODY INTERIOR, SLOTTED 3/4
LOOSE SET GRATE ALUMINUM ANTI-SPASH DOME STRAINER, DEEP SEAL P-TRAP,
DIAMETER OF OUTLET AS SHOWN ON DRAWINGS.
MFG: ZURN NO. Z-1901-Z1000.
NOTE: PROVIDE WITH PROSET TRAP GUARD WATER SAVING DEVICE. SIZE AS INDICATED BY
DRAIN.
RPZ REDUCED PRESSURE BACKFLOW PREVENTER:
TYPE: 2-1/2" SIZE WITH THREADED CONNECTION, COMPLETE WITH 2 SPRING LOADED CHECK
VALVES, BALL VALVES, TEST COCKS. 12 PSI LOSS AT 80 GPM.
SERVICE:MECH. COOLING TOWER MAKE-UP.
MFG: FEBCO NO. 860Y-AGD.
NOTE: AIR GAP DRAIN SHALL BE PIPED TO NEAREST FLOOR DRAIN, FLOOR SINK, OR AS
INDICATED ON DRAWINGS.
P1a WATER CLOSET (PUBLIC RESTROOMS-HANDICAP):
TYPE: SAME AS Pb EXCEPT MOUNTING HEIGHT. SEE ARCH. PLANS.
P3 LAVATORY (HANDICAP):
TYPE: WALL HUNG, VITREOUS CHINA, 21" X 18" OVERALL DIMENSIONS, 3-HOLE, 4"CENTERS.
MFG: KOHLER NO. K-2005 "KINGSTON".
FAUCET: 4" CENTERS, METAL WRISTBLADE HANDLES, CHROME PLATED, 0.5 GPM LAMINAR FLOW
AERATOR
MFG: CHICAGO No. 802-317CP
SUPPLIES: 1/2" SWEAT WHEEL HANDLE ANGLE STOPS WITH 3/8" O.D. FLEXIBLE RISERS, CHROME
PLATED FINISH.
TRAP: 1-1/4" IN X 1-1/2" OUT, 17 GA, CHROME PLATED, ADJUSTABLE, CLEANOUT PLUG, SEMI-CAST P-TRAP.
MFG: MCGUIRE NO. 8902.
MTD HEIGHT: SEE ARCHITECTURAL DRAWINGS FOR MOUNTING HEIGHT.
NOTE: INSULATE SUPPLY AND WASTE PIPING PER SPECIFICATIONS.
P6 MULTI-STATION HAND SINK:
TYPE: WALL HUNG, 5-STATION, 140 GA. 304 STAINLESS STEEL, ADJUSTABLE LEGS. MOUNTING BRACKET, 102"L X 18"W, 4" CENTER.
MFG: BRADLEY NO. S96-051 (6951A-5)
SERVICE RQRS:SUPPLY AND WASTE, 1-1/4" IPS. SUPPLY VALVE HANDLES REMOVED OR LOCKED OPEN.
FAUCET: 4" CENTER, 4" UNTEGRAL SPOUT, CHROME PLATED, METAL WRISTBLADE HANDLES, 0.5 GPM VANDAL-PROOF AERATOR.
MFG: CHICAGO NO. 802-VE2805-317ABCP
SYMBOLSYMBOL
FLOOR DRAIN/SINK SPECIFICATIONS
SYMBOL DESCRIPTION
PLUMBING FIXTURE SPECIFICATIONSPLUMBING FIXTURE SPECIFICATIONS
PLUMBING ROUGH-IN SCHEDULE
LAVATORY - HANDICAP
SERVICE SINKP4
P3
URINAL
SYMBOL
P2
P1
DESCRIPTION TRAP
WASTE
FLOOR MOUNTED, CORNER TYPE, INTEGRAL CHECK STOPS
1-1/2"
REMARKS
WALL MOUNT, ELECTRONIC FLUSH VALVE, 0.125 GPF
HWCW
VENT
3/4" WALL MOUNT, ELECTRONIC FLUSH VALVE, 0.125 GPFP2a URINAL - HANDICAP
NON-FREEZEP9 WALL HYDRANT
WATER CLOSET - HANDICAP FLOOR MOUNT, CONCEALED MANUAL FLUSH, 1.6 GPF
COUNTERTOP, MANUAL FAUCET, 0.5 GPM LAMINAR AERATOR
PDIP7 WATER HAMMER ARRESTOR INSTALL IN 14"X14" ACCESS PANEL
P1a WATER CLOSET - HANDICAP FLOOR MOUNT, CONCEALED MANUAL FLUSH, 1.6 GPF1"
DRINKING FOUNTAINP5 BI-LEVEL HANDICAPPED ACCESSIBLE
MULTI-STATION HAND SINKP6 WALL HUNG, STAINLESS STEEL
P8 EXPANSION TANK CENTRAL STERILE IHW SYSTEM
-
-
-
-
1/2"
-
1/2"
-
-
-
1/2"1/2"
3/4"
3/4"
3/4"
1/2"
1/2"
3/4"
1" 4"
4"
2"
2"
2"
2"
2"
-
-
-
2"
ROUGH-IN SIZE
2"
2"
2"
2"
1-1/2"
2"
-
-
-
2"
INTEGRAL
INTEGRAL
INTEGRAL
INTEGRAL
1-1/4" X 1-1/2"
1-1/4"
3"
-
-
-
1-1/2" X 1-1/2"
DOMESTIC WATER HEATER SCHEDULE
SYMBOL LOCATION MANUFACTURER/MODEL No.SERVICE SET
POINTTYPE STORAGE
ELECTRICAL DATAOPERATING
WEIGHT POWER
HW RECOVERY
GPH RATE TEMP.RATE
REMARKS
ALL SELECTIONS BASED ON5300 FT. ELEVATION
DWH-1 MECHANICAL RM 140° NATURAL GAS BOCK MODELNo: OT200N-A
100 GAL 253 90°1353 LBS INSTALL ON 4" HOUSE KEEPING PAD, ROUTE T&PRELIEF VALVE TO NEAREST FLOOR SINK,PROVIDE CONDENSATE NEUTRALIZATION KIT
120
PHHz
160
PUMP SCHEDULE
SYMBOL DESCRIPTION MANUFACTURER/MODEL No.
LOCATIONELECTRICAL DATA
TOTAL HEAD(FT) RPM MOTOR HP VOLT
REMARKS
ALL SELECTIONS BASED ON5300 FT. ELEVATION
TYPE FLOWPHASE AMPS
BASIN SIZE
N/AILP-1 INLINE PUMP SIMPLEX 4.5 GPM 35 TACO: 0013-BF33250 1151/6 1 2.0 120° DOMESTIC HOT WATER RETURN, BRONZE FLANGED, 3/4"CONNECTION SIZE. COORDINATE CONNECTION OF BMS WITH
ELECTRICAL
Kw
-120°
BTUH
199,000
MECHANICAL RM
TFOE
C
I N
EI
L D
ESN
SAXATS
E
RE
ENIGN
LAOSSEFO
RP
ET
ABBAS SHIRIAN
102840
PROJECT
1
A
2 3 4 5
B
C
D
1 2 3 4 5
SEAL
REVISIONS
SHEET NO
DRAWING NAME
PROJECT NO:
REVIEWED BY
DATE
VE
GA
ISD
CA
RE
ER
TE
CH
NO
LOG
Y B
UIL
DIN
G20
0 LO
NG
HO
RN
ST
.V
EG
A, T
X 7
9 092
14-0424.002
01.29.2016
Addendum 01
DATE
1/29
/201
6 11
:45:
32 A
M
P700a
PLUMBINGSCHEDULES
AS
Abbas2016.01.29 11:57:02-07'00'
A B C D E F G
1
2
3
4
5
K-3544HIGHLINE
C_TOILETS
VITREOUS CHINA
K-3544HIGHLINE
C_TOILETS
VITREOUS CHINA
K-3544HIGHLINE
C_TOILETS
VITREOUS CHINA
2
2
2
2
IC
S
IC
S
IC
S
IC
S
IC
S
C
S
IC
105
SHOP
101
HALLWAY
102
CLASSROOM
103
STORAGE
104
OFFICE
110
GIRLS109
BOYS
108
JANITOR
106
TOOLSTORAGE
107
ELEC./COMP.
T02
T01
T29
T06
T30TO IDF141
T31
TFOE
I N
SAXATS
E
RE
ENIGN
LAOSSEFO
RP
ET
JOHN F. HECK IV
82984
I SG
ER D
E
RET
PROJECT
1
A
2 3 4 5
B
C
D
1 2 3 4 5
SEAL
REVISIONS
SHEET NO
DRAWING NAME
PROJECT NO:
REVIEWED BY
DRAWN BY
VE
GA
ISD
CA
RE
ER
TE
CH
NO
LOG
Y B
UIL
DIN
G20
0 LO
NG
HO
RN
ST
.V
EG
A, T
X 7
9 092
14-0424.002
TBD
1/29
/201
6 10
:25:
32 A
M
T101
AG SHOPTECHNOLOGYSYSTEMS PLAN
Approver
Author
GENERAL SHEET NOTES
SHEET KEYNOTES
SCALE: 1/8" = 1'-0"A1 AG SHOP TECHNOLOGY SYSTEMS PLAN0' 4' 8' 16'
NORTH
1 01/29/16 ADDENDUM#01
T01 INTERCOM CALL SWITCH. REFER TO SPECIFICATIONS SECTION 27 5123.50 FORADDITIONAL REQUIREMENTS.
T02 WALL MOUNTED CLOCK/SPEAKER COMBO. REFER TO SPECIFICATIONS SECTION27 5313 FOR ADDITIONAL REQUIREMENTS.
T06 PAGING LOUDSPEAKER FOR DISTRIBUTED INTERCOM/PAGING SYSTEM.COORDINATE SIGNAL PULL BOX TYPE AND ROUGH-IN LOCATION WITHEQUIPMENT INSTALLER PRIOR TO COMMENCING ANY WORK. REFER TOSPECIFICATIONS SECTION 27 5123 AND DETAILS ON SHEET T504 FORADDITIONAL REQUIREMENTS.
T29 4-11/16" X 2-5/8" SQ TELECOMMUNICATIONS OUTLET BOX WITH 1" EMT STUB UPTO NEAREST ACCESSIBLE CEILING SPACE. REFER TO GENERAL NOTES FORADDITION REQUIREMENTS.
T30 PROVIDE 36" X 24" X 30" WALL MOUNTED ENCLOSURE. CUBE-IT CPI # 12419-236.MOUNT 32" AFF BOTTOM OF CABINET. PROVIDE FAN KIT CPI # 12804-701.PROVIDE PATCH PANELS AND HORIZONTAL WIRE MANAGEMENT AS NEEDED.
T31 REFERENCE CONDUIT PATHWAY CONTINUATION ON SHEET ES101.
A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS, FLOORS, CEILINGS, AND ROOF AS
PER OWNER, CODE, AND AHJ.
B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL OTHER TRADES.
C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM. CONTRACTOR IS RESPONSIBLE FOR
PROVIDING A COMPLETE END-TO-END WARRANTED SOLUTION FOR THE HORIZONTAL CABLING.
D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.
E. ALL COMMUNICATIONS CABLING TO MEET OR EXCEED CAT6 STANDARDS.
F. TELECOMMUNICATIONS OUTLETS TO BE MOUNTED AT +18" A.F.F. (BOTTOM OF BOX) UNLESS OTHERWISE
NOTED. FOR EXAMPLE, DEVICES SPECIFIED AT +18" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT
FOR POWER RECEPTACLES AND TELECOMMUNICATIONS OUTLETS. DEVICES SPECIFIED AT + 48" A.F.F.
SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR LIGHT SWITCHES ETC.
G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL, THINWALL ELECTRICAL METALLIC
TUBING (TYPE EMT) UNLESS OTHERWISE NOTED. UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE
USED FOR PATHWAYS INDICATED ON THIS SHEET. ALL CONDUITS ARE TO BE, AT A MINIMUM, 1” TRADE SIZE,
UNLESS OTHERWISE NOTED. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO
NEAREST CABLE TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL.
H. CABLE TRAY SYSTEMS SHOWN ON THIS SHEET SHALL BE USED FOR VOICE AND DATA CABLING ONLY. ALL
OTHER SYSTEMS INCLUDING, BUT NOT LIMITED TO, FIRE ALARM, SECURITY, HVAC CONTROL, ETC. SHALL BE
SUPPORTED BY OTHER MEANS. J-HOOKS ATTACHED TO THE CABLE TRAY SUPPORTS WILL BE PERMITTED.
LIKEWISE, ANY CONDUITS PROVIDED FOR VOICE AND DATA CABLING IS NOT TO BE USED BY ANY OTHER
SYSTEM, HENCE, SEPARATE CONDUITS MAY NEED TO BE PROVIDED FOR THE SUPPORT OF THESE
SYSTEMS.
I. NUMBER ADJACENT TO TELECOMMUNICAITONS OUTLET SYMBOL REPRESENTS NUMBER OF CAT 6 CABLES
TO BE INSTALLED AND TERMINATED AT THAT LOCATION. A "B" ADJACENT TO AN OUTLET LOCATION
REPRESENTS A ROUGH-IN ONLY LOCATION, PROVIDE BOX, CONDUIT, AND BLANK FACEPLATE.
J. FOR ALL EXTERIOR WALL-MOUNTED DEVICES, PROVIDE BACKBOX AND EXTENSION RING, TOTAL DEPTH AS
REQUIRED TO MATCH THICKNESS OF COMPLETE WALL & INSULATION ASSEMBLY.
K. WIRELESS ACCESS POINTS IN GYMNASIUM WILL HAVE WIRE GUARDS.
L. ALL CONDUIT TURNS FOR A/V AND IT CONDUITS SHALL BE "SWEEP" TYPE, NO BEND FITTINGS ARE
PERMITTED.
M. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO PROTECT CABLES, REGARDLESS
OF WHETHER THEY TERMINATE IN A DEVICE OR JUNCTION BOX.
N. CONTRACTOR TO VERIFY ALL CABLE COUNTS AND NUMBER OF PATCH PANELS REQUIRED.
O. GROUP DATA OUTLETS TOGETHER WITH POWER OUTLETS (WHERE APPLICABLE). REFER TO "EP" SERIES
SHEETS FOR POWER OUTLET LOCATIONS.
P. FOR ALL OUTLETS INSTALLED IN ARTS/MUSIC/DRAMA AREAS, CLASSROOMS, LABS, MISC. LEARNING AREAS,
OFFICES AND OTHER ACOUSTICALLY-RATED PARTITIONS (AS INDICATED ON ARCHITECTURAL DRAWINGS):
MAINTAIN A MINIMUM OF 12 INCHES SEPARATION BETWEEN OUTLETS ON OPPOSITE SIDES OF PARTITION.
PROVIDE ACOUSTICAL OUTLET BACKER PUTTY (AS MANUFACTURED BY KINETICS NOISE CONTROL, OR
EQUAL). PUTTY PADS SHALL MAINTAIN ACOUSTICAL RATINGS PER ASTM C 919 AND ASTM E 497, AND BE
TESTED TO UL 263 (ASTM E119) AND UL 1479 (ASTM E814) STANDARDS.