EDC201 / EDC202 / EDC203
Product Manual 51-52-25-155 Revision: 2.0
July 2015
Notices and Trademarks Contacts
ii EDC201 / EDC202 / EDC203 User’s Manual Revision 2.0 July 2015
Notices and Trademarks
Copyright 2015 by Honeywell International Inc. Revision: 2.0, July 2015
While this information is presented in good faith and believed to be accurate, Honeywell disclaims the implied warranties of merchantability and fitness for a particular purpose and makes no express warranties except as may be stated in its written agreement with and for its customers. In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information and specifications in this document are subject to change without notice. Honeywell, PlantScape, Experion PKS, and TotalPlant are registered trademarks of Honeywell International Inc. Other brand or product names are trademarks of their respective owners.
Honeywell International Process Solutions
1250 W Sam Houston Pkwy S Houston, TX 77042
1-800 343-0228
Contacts
Revision 2.0 EDC201 / EDC202 / EDC203 Product Manual iii July 2015
About This Document This document provides descriptions and procedures for the Installation, Configuration, Operation, and Troubleshooting of your the EDC 200 Series Controller.
Revision History EDC201 / EDC202 / EDC203 Product Manual, Document # 51-52-25-155
Rev 1.0 June 2015 First release
Rev 2.0 July 2015 7 segment code added
Reference The following list identifies publications that may contain information relevant to the information in this document.
Document Name Document ID
EDC 200 Series New Wave Controllers Quick Start 51-52-25-156
EDC 200 Series New Wave Controllers Specification 51-52-03-48
Contacts
iv EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
Contacts World Wide Web The following Honeywell web sites may be of interest to Process Solutions customers.
Honeywell Organization WWW Address (URL)
Corporate http://www.honeywell.com
Honeywell Process Solutions http://honeywellprocess.com
Support and Contact Information For Europe, Asia Pacific, North and South America contact details, see back page or refer to the appropriate Honeywell Solution Support web site:
Honeywell Corporate www.honeywellprocess.com
Honeywell Process Solutions https://www.honeywellprocess.com/en-US/explore/products/instrumentation/panel-mounted-controllers-and-programmers
Training Classes http://www.honeywellprocess.com/en-US/training
Telephone and Email Contacts
Area Organization Phone Number
United States and Canada
Honeywell Inc. 1-800-343-0228 Customer Service 1-800-423-9883 Global Technical Support
Global Email Support
Honeywell Process Solutions
ReJu
STh
evision 2.0 uly 2015
Symbol Dhe following t
S
CAU
ED
Definitiontable lists thos
ymbol
UTION
DC201 / EDC2
ns se symbols use
ATTENTIONconsideration
TIP: Identifiesperforming a
REFERENCEinformation o
REFERENCEinformation w
Indicates a sior work (datathe inability to
CAUTION: Inavoided, mayto alert againCAUTION symanual for adrequired infor
WARNING: Iavoided, coulWARNING symanual for adrequired infor
WARNING, RHAZARDOUS60 VDC may
ESD HAZARequipment melectrostatic s
Protective Eprotective ear
202 / EDC203
ed in this docu
: Identifies infon.
s advice or hintask.
E -EXTERNALutside of the b
E - INTERNALwithin the book
tuation which,) on the systeo properly ope
ndicates a potey result in minost unsafe prac
ymbol on the edditional informrmation in the
ndicates a potld result in serymbol on the edditional informrmation in the
Risk of electrS LIVE voltagebe accessible
RD: Danger of ay be sensitivsensitive devic
arth (PE) termrth (green or g
3 Product Man
ument to deno
Definition
ormation that
nts for the use
L: Identifies anbookset.
L: Identifies ankset.
, if not avoidedem being damaerate the proce
entially hazardor or moderatectices. equipment refemation. The symanual.
tentially hazarrious injury or equipment refmation. The symanual.
ical shock: Pes greater thae.
an electro-stave. Observe prces.
minal: Providegreen/yellow)
ual
ote certain con
requires spec
er, often in term
n additional so
n additional so
d, may result iaged or lost, oess.
dous situation e injury. It may
ers the user toymbol appears
rdous situationdeath.
fers the user toymbol appears
Potential shockan 30 Vrms, 42
atic discharge recautions for
ed for connectsupply system
Sym
nditions.
cial
ms of
ource of
ource of
in equipment or may result i
which, if not y also be used
o the product s next to
n, which, if not
o the product s next to
k hazard wher2.4 Vpeak, or
to which handling
tion of the m conductor.
bol Definitions
v
n
d
t
re
s
v
Symbol D
vi
Definitions
Symbol
EDC201
Functinoise ibondedwith na
Earth connecsupplyrequire
Chassthe equsupplyrequire
/ EDC202 / ED
ional earth temmunity imprd to Protectiveational local el
Ground: Function shall be
y in accordancements.
sis Ground: Iduipment shall
y in accordancements.
DC203 Produc
Defin
erminal: Usedrovement. NOTe Earth at the lectrical code
ctional earth bonded to Proe with nationa
dentifies a conbe bonded to e with nationa
ct Manual
nition
for non-safetyTE: This connsource of suprequirements.
connection. otective Earth al and local ele
nnection to theProtective Ea
al and local ele
y purposes sunection shall bpply in accorda.
NOTE: This at the source
ectrical code
e chassis or fraarth at the souectrical code
RevisJu
uch as e ance
of
ame of urce of
sion 2.0 ly 2015
Contents Symbol Definitions
Revision 2.0 EDC201 / EDC202 / EDC203 Product Manual vii July 2015
Contents
1. INTRODUCTION ............................................................................ 1
1.1 Overview ........................................................................................................... 1 Function ................................................................................................................................ 1 Characteristic ........................................................................................................................ 1 Easy to Configure .................................................................................................................. 1 Auto Tuning ........................................................................................................................... 2 Manual/Auto Mode ................................................................................................................ 2 Display .................................................................................................................................. 2 LED ....................................................................................................................................... 5 Function of Keys .................................................................................................................... 5
2. INSTALLATION ............................................................................. 6
2.1 Overview ........................................................................................................... 6 Introduction ........................................................................................................................... 6 Pre-installation Information .................................................................................................... 6
2.2 Condensed Specifications .............................................................................. 7
2.3 Model Number Interpretation ....................................................................... 10 Instruction ............................................................................................................................ 10
2.4 Control and Alarm Relay Contact Information ........................................... 11 Control Relays ..................................................................................................................... 11
2.5 Mounting ......................................................................................................... 11 Physical Considerations ...................................................................................................... 11 Overall Dimensions ............................................................................................................. 11 Panel Cutout Requirements ................................................................................................ 12 Mounting Method ................................................................................................................. 13 Mounting Procedure ............................................................................................................ 13
2.6 Wiring .............................................................................................................. 14 Electrical Considerations ..................................................................................................... 14
2.7 Wiring Diagrams ............................................................................................ 16 Identify Your Wiring Requirements ...................................................................................... 16 Wiring the Controller ............................................................................................................ 16
3. CONFIGURATION ....................................................................... 17
3.1 Overview ......................................................................................................... 17
3.2 Configuration Prompt Hierarchy .................................................................. 18
3.3 Configuration Procedure .............................................................................. 19 Introduction ......................................................................................................................... 19 Procedure ............................................................................................................................ 19
3.4 Input Set Up Group ........................................................................................ 20 Introduction ......................................................................................................................... 20 Function Prompts ................................................................................................................ 20
3.5 Control Set Up Group .................................................................................... 23
Contents Symbol Definitions
viii EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
Introduction .......................................................................................................................... 23 Function Prompts ................................................................................................................. 23
3.6 Tune PAR Set Up Group ............................................................................... 29 Introduction .......................................................................................................................... 29 Function Prompts ................................................................................................................. 29
3.7 ALARM Set Up Group ................................................................................... 30 Introduction .......................................................................................................................... 30 Function Prompts ................................................................................................................. 30
3.8 Auxiliary Set Up Group ................................................................................. 37 Introduction .......................................................................................................................... 37 Function Prompts ................................................................................................................. 37
3.9 OPTION Set Up Group ................................................................................... 38 Introduction .......................................................................................................................... 38 Function Prompts ................................................................................................................. 38
3.10 Configuring Analog Input .......................................................................... 41 Configuring TC Type Input ................................................................................................... 41 Configuring RTD Type Input ................................................................................................. 42 Configuring Analog Input Burnout ........................................................................................ 43 Assign Temperature Unit...................................................................................................... 45
3.11 Configuring Control Algorithm ................................................................. 46 Configuring ON-OFF Control ................................................................................................ 46 Configuring Time Proportion Control .................................................................................... 47 Configuring Three Position Step Control .............................................................................. 48 Configuring Soft Start ........................................................................................................... 49
3.12 Configuring Alarm ...................................................................................... 50 Configuring PV Alarm ........................................................................................................... 50 Configuring Deviation Alarm ................................................................................................. 51 Configuring Output Alarm ..................................................................................................... 53 Configuring Manual Mode Alarm .......................................................................................... 55 Configuring PV Rate of Change Alarm ................................................................................. 56 Configuring Digital Input Alarm ............................................................................................. 57 Configuring TC Warning Alarm ............................................................................................ 58 Configuring TC Failing Alarm ............................................................................................... 59 Configuring Failsafe Alarm ................................................................................................... 60 Configuring Diagnostic Alarm ............................................................................................... 61 Assign Alarm Hysteresis ...................................................................................................... 62 Configuring Alarm Delay ...................................................................................................... 63 Configuring Alarm Latching .................................................................................................. 64 Configuring Alarm Blocking .................................................................................................. 64 Configuring Timer ................................................................................................................. 65
3.13 Configuring Digital Input ........................................................................... 66 Disable DI Function .............................................................................................................. 66 Configuring DI as Control Mode Switch ............................................................................... 67 Configuring DI as Control Direction Switch .......................................................................... 67 Configuring DI as Keypad Locking Switch DI ....................................................................... 68 Configuring DI as Timer Initiating Trigger ............................................................................. 68 Configuring DI as Alarm Acknowledging Switch ................................................................... 69 Configuring DI as Auto Tuning Initiating Trigger ................................................................... 70
Contents Symbol Definitions
Revision 2.0 EDC201 / EDC202 / EDC203 Product Manual ix July 2015
4. MONITORING AND OPERATING THE CONTROLLER ............. 71
4.1 Overview ......................................................................................................... 71
4.2 Operator Interface .......................................................................................... 71
4.3 Monitoring Your Controller ........................................................................... 72 Annunciators ....................................................................................................................... 72 Viewing the operating parameters ....................................................................................... 73 Diagnostic Messages .......................................................................................................... 73
4.4 Controller Mode ............................................................................................. 74 Operation Mode ................................................................................................................... 74 Control Mode ....................................................................................................................... 74
4.5 Setting Operation Level ................................................................................ 75 Procedure ............................................................................................................................ 75
4.6 Setting Operation Password......................................................................... 76 Procedure ............................................................................................................................ 76
4.7 Setting Parameter Mask ................................................................................ 77
4.8 Reseting to Factory Default .......................................................................... 78
4.9 Testing Display .............................................................................................. 78
4.10 Setting Power Frequency .......................................................................... 79
4.11 Setting Decimal Point Location ................................................................ 80
4.12 Examing Product Information ................................................................... 80
4.13 Acknowledge Alarms ................................................................................. 81
4.14 Setting Auto Tuning ................................................................................... 82 Initiating Auto Tuning ........................................................................................................... 82 Starting Through Keypad .................................................................................................... 82 Stopping Auto Tuning .......................................................................................................... 84
4.15 Switch Manual/Auto Mode......................................................................... 84 Preliminary Steps ................................................................................................................ 84 Procedure ............................................................................................................................ 84
4.16 Setting SP ................................................................................................... 84 Preliminary Steps ................................................................................................................ 84 Procedure ............................................................................................................................ 84
4.17 Setting Timer .............................................................................................. 85 Viewing the Timer Current Status ........................................................................................ 85 Start Timer .......................................................................................................................... 85 Resetting Timer ................................................................................................................... 86
4.18 Setting Output Value .................................................................................. 86 In Auto Mode ....................................................................................................................... 86 AT is Processing ................................................................................................................. 86 In Man Mode ....................................................................................................................... 87
Contents Symbol Definitions
x EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
5. TROUBLESHOOTING/SERVICE ................................................ 88
5.1 Troubleshooting Aids ................................................................................... 88
5.2 Power-up Tests .............................................................................................. 89
5.3 Background Tests ......................................................................................... 89 Diagnose System Error ........................................................................................................ 89 Confirm System Error ........................................................................................................... 90
6. APPENDIX A LOOK-UP TABLE FOR 7 SEGMENT CHARACTER AND ASSOCIATED ENGLISH WORD.......................................................... 91
Contents Tables
Revision 2.0 EDC201 / EDC202 / EDC203 Product Manual xi July 2015
Tables Table 1-1: EDC201/ EDC202/ EDC203 Operator Interface (all display items shown) .... 4 Table 1-2: Function of LED Indicators ............................................................................. 5 Table 1-3: Function of Keys ............................................................................................. 5 Table 2-1: Condensed Specifications .............................................................................. 8 Table 2-2: TC/RTD Types and Scope .............................................................................. 8 Table 2-3: Environmental and Operating Conditions ....................................................... 9 Table 2-4: Model Number Interpretation ........................................................................ 10 Table 2-5: Permissible Wiring Bundling ......................................................................... 15 Table 3-1: Set Up Parameter Reference ....................................................................... 40 Table 4-1 Lower Display Key Parameter Prompts ......................................................... 73 Table 4-2: Diagnostic Messages .................................................................................... 73 Table 6-1 7 Segment Character and Associated English Word .................................... 91
Contents Figures
xii EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
Figures Figure 1-1: EDC201 Operator Interface ........................................................................... 2 Figure 1-2: EDC202 Operator Interface ........................................................................... 3 Figure 1-3: EDC203 Operator Interface ........................................................................... 4 Figure 2-1: Overall Dimensions ..................................................................................... 11 Figure 2-2: Panel Cutout Requirements ........................................................................ 12 Figure 2-3: Composite Wiring Diagram Figure .............................................................. 16 Figure 3-1: Configuration Prompt Hierarchy .................................................................. 18 Figure 4-1: Operator Interface (EDC201, EDC202) ....................................................... 71 Figure 4-2 Operator Interface (EDC203) ....................................................................... 72
Revision 2.0 EDC201 / EDC202 / EDC203 Product Manual 1 July 2015
1. Introduction
1.1 Overview Function
The EDC 200 series are microprocessor-based stand-alone temperature controllers. They combine a high degree of functionality and operating simplicity. EDC 200 series controllers are available in the following three panel mount sizes: • EDC201:1/16 DIN • EDC202:1/8 DIN • EDC203:1/4 DIN This instrument is an ideal controller for regulating temperature in numerous heating and cooling applications, as well as in metal working, food, pharmaceuticals, semiconductor, testing and environmental work. The EDC 200 series monitor and control temperatures in applications such as environmental chambers, plastic processing machines, furnaces and ovens, and packaging machinery.
Characteristic
Input Type • One analog input
The analog input supports thermocouples (TC) or resistive temperature detector (RTD - two input method). Analog Input accuracy: ±0.5%;
• One digital input The digital input supports external dry contacts or isolated solid state contacts.
Output Type • One control output: Electromechanical relay output or SSR driver output. • Alarm outputs.
One alarm output ( EDC201) Two alarm outputs ( EDC201 and EDC203)
Display 7-segment display
Power Supply • 100-240 VAC 50Hz or 60 Hz (-15% to 10%) • 24 V DC (-20% to 20%)
Easy to Configure The controller supports two configuration levels, operator level and configuration level, that make parameter configuration simpler. Inadvertent controller configuration can be prevented by hiding some parameters. A 4-digit security code prevents unauthorized modifications.
1. Introd1.1. Over
2
Auto Tu
Manual/•
•
Display
uction rview
uning Auto tuning isetting of PIDduring initial
/Auto Mode In Manual moOperators dirvariable is disincreasing or control outpuoutput). In Auto modeThe controllereference the
1
2
3
4
EDC201
s used for autD tuning param
start-up of the
ode ectly control tsplayed on thedecreasing th
ut automaticall
e r generates thcurrent PV an
/ EDC202 / ED
o-tuning of yometers. Auto te system.
the controller e controller. T
he limits allowly (0 to 100%
he final contrond the target S
Figure 1-1:
DC203 Produc
our process antuning is initia
output level iThe percent ouwed by the outp
for a time pro
l output automSet Point value
: EDC201 O
ct Manual
nd automatic iated by the use
n the Manual utput may be cput value. Theoportioning ou
matically usinges.
perator Inte
identification er at the contr
mode of operchanged by ope controller wutput or -5 to
g internal algo
erface
RevisJu
and controlleroller, typically
ration and the perators by
will generate th105% for a cu
orithms that
6
5
sion 2.0 ly 2015
r y
output
he final urrent
ReJu
evision 2.0 uly 2015
ED
1
2
3
4
DC201 / EDC2
Figu
202 / EDC203
re 1-2: EDC2
3 Product Man
202 Operato
ual
or Interface
1.
5
6
. Introduction1.1. Overview
3
n w
3
1. Introd1.1. Over
4
Callout
1
2
3
4
5
6
1
2
3
4
uction rview
Item
Navigation B
Temperature
LED Indicato
Keys
Upper Displa
Lower Displa
Table 1-1
EDC201
Bar
e Unit
ors
ay
ay
: EDC201/ E
/ EDC202 / ED
Figure 1-3:
Description
In normal ope
In configuratio
Selected syst
Indicate the sManual/Auto Indicators for
Refer to Table
In normal ope
In configuratio
In normal ope
In configuratio
EDC202/ EDC
DC203 Produc
: EDC203 O
n
erating mode,
on mode, sele
tem temperatu
tatus of externcontrol mode.specific inform
e 1-3: Functio
erating mode,
on mode, the s
erating mode,
on mode, sele
C203 Opera
ct Manual
perator Inte
it is not displa
ected Set Up G
ure unit
nal output, aut Refer to Tabl
mation.
n of Keys for s
the 4-digit cur
selected para
the 4-digit Set
ected paramet
ator Interface
erface
ayed.
Group Name is
to tuning, alarle 1-2: Functio
specific inform
rrent PV value
meter name is
t Point value i
er value is dis
e (all displa
RevisJu
s displayed.
rm output and on of LED
mation.
e is displayed.
s displayed.
s displayed.
splayed.
y items sho
5
6
sion 2.0 ly 2015
own)
5
6
ReJu
LE
LE
OU
AT
MA
A/
AL
AL
Fu
Ke
evision 2.0 uly 2015
ED The fo
ED Indicator
UT
T
AN(EDC201)
/M( EDC202,E
LM1
LM2( EDC202
unction of KThe fo
ey Fu
In n
In cpre
In nvar
In c
To
To
In n
In c
Lon
ED
ollowing table
r F
Ine
Inth
InwE
EDC203) Ino
In
2,EDC203) Ino
Keys ollowing table
nction
normal operat
configuration mess the key to
normal operatrious functions
configuration m
increase the v
decrease the
normal operat
configuration m
ng press the k
DC201 / EDC2
shows each L
Function
ndicates the enabled when t
ndicates the ehe light is on.
ndicates the stwhen the light iEDC201)
ndicates the stn. Manual con
ndicates the o
ndicates the on.(Applicable
Tabl
shows each k
ting mode, lon
mode, long prcycle through
tion mode, shos.
mode, short p
values for the
values for the
ting mode, sho
mode, short p
key to enable A
202 / EDC203
LED indicator
nable or disabthe light is on.
nable or disab
tatus of Manuis on. It is Auto
tatus of Manuntrol mode wh
utput status of
utput status ofto EDC202, E
le 1-2: Funct
key on the ope
g press the ke
ress the key to the menu item
ort press the k
ress the key to
selected para
e selected par
ort press the k
ress the key to
Auto Tuning w
Table 1-3:
3 Product Man
r on the operat
ble status of ex.
ble status of a
al or Auto cono control mod
al or Auto conen M is on.(A
f Alarm1. The
f Alarm2. TheEDC203)
tion of LED
erator interface
ey to enter the
o switch back tms.
key to switch t
o cycle param
ameter or swit
rameter or swi
key to switch A
o save and co
when the enab
Function of
ual
tor interface an
xternal output
uto tuning. Au
ntrol mode. Ine when the lig
ntrol mode. Aupplicable to E
re is a alarm o
re is a alarm o
Indicators
e and defines
e configuration
to the normal
he lower displ
meters in a set
ch to the next
tch back to th
Auto/ Manual c
onfirm settings
ble conditions
f Keys
1.
nd defines its
t. The externa
uto tuning is en
Manual controght is off.(Appl
uto control modDC202, EDC2
output when th
output when th
its function.
n mode.
operating mod
lay parameter
up group.
t item.
e previous ite
control mode.
s.
are fulfilled.
. Introduction1.1. Overview
5
function.
l output is
nabled when
ol mode licable to
de when A is 203)
he light is on.
he light is
de, short
rs or enable
m.
n w
5
6 EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
2. Installation
2.1 Overview Introduction
Installation of the EDC 200 series consists of mounting and wiring the controller according to the instructions provided in this section. Read the pre-installation information, check the model number interpretation, become familiar with your model selection, then proceed with installation.
Pre-installation Information If the controller has not been removed from its shipping carton, inspect the carton for damage then remove the controller.
• Inspect the unit for any obvious shipping damage and report any damage due to transit to the carrier. • Make sure a bag containing mounting hardware is included in the carton with the controller. • Check that the model number shown on the product agrees with what you have ordered.
2. Installation 2.2. Condensed Specifications
Revision 2.0 EDC201 / EDC202 / EDC203 Product Manual 7 July 2015
2.2 Condensed Specifications Honeywell recommends that you review and adhere to the operating limits listed in Table 2-1: Condensed Specifications, Table 2-2: TC/RTD Types and Scope, and Table 2-3: Environmental and Operating Conditions when operating your controller.
Specifications
Inputs Input Type TC: E, J,K,Platinel II,Ni-Ni-Moly,R,S,T
RTD: PT100,PT100(Low)
Input Sampling Time TC:250ms
RTD:350ms
Control Relay output Dry contact /NO
5A@ 30 VDC or 250 VAC
SSR Driver Output 24VDC/20 mA
Algorithm ON-OFF
Time proportioning
TPSC
Alarm Outputs Dry contact/NO
5A@ 30 VDC or 250 VAC
Mode PROCESS VARIABLE
DEVIATION
OUTPUT
CONTROL MODEALARM
PV RATE OF CHANGE
DIGITAL INPUT
THERMOCOUPLE WARNING
THERMOCOUPLE FAILING
FAILSAFE
SYSTEM DIAGNOSTIC
TIMER ALARM
LED PV/SP indicator 4-digit, 7-segment display
Indication accuracy 0.5%
Alarm relay status Alarm1 or Alarm2
2. Installation 2.2. Condensed Specifications
8 EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
Specifications
Control Mode Auto or Manual
Units of temperature ºF or ºC
Control relay status Output
Auto tuning status Operating status
Menu 7 LED indicators
Certification CE EMC: EN 61326-1 2006
Low Voltage Directive: EN 61010-1 2010
(Both are "Self Declared")
UL ANSI/UL 61010-1 Third Edition
CSA CAN/CSA-C22.2 No. 61010-1-12 Third Edition
Table 2-1: Condensed Specifications
TC/RTD Types and Scope
Units: C
TC E Thermocouple High 270 to 1000
J Thermocouple High -18 to 871
K Thermocouple High -18 to 1316
Ni-Ni-Moly Thermocouple High 0 to 1371
Platinel II Thermocouple High 0 to 1380
R Thermocouple 18 to 1704
S Thermocouple -18 to 1704
T Thermocouple High -184 to 371
RTD PT100(Low) -184 to 149
PT100 -184 to 649
Table 2-2: TC/RTD Types and Scope
2. Installation 2.2. Condensed Specifications
Revision 2.0 EDC201 / EDC202 / EDC203 Product Manual 9 July 2015
Environmental and Operating Conditions
Parameter Reference Rated Operative Limits
Transportation and Storage
Ambient Temperature
25 ± 3°C
77 ± 5°F
15 to +55°C
58 to 131°F
0 to +55°C
32 to 131°F
-40 to +66°C
-40 to 151°F
Relative Humidity 10 to 55*(*) 10 to 90*(*) 5 to 90*(*) 5 to 95*(*)
IP or NEMA Rating Front Panel IP54 NEMA 3R
Vibration Frequency (Hz)
Acceleration (g)
0
0
0 to 200
0.6
0 to 200
0.5
Mechanical Shock Acceleration (g)
Duration (ms)
0
0
5
30
5
30
20
30
Table 2-3: Environmental and Operating Conditions
ATTENTION * The maximum moisture rating only applies up to 40 °C (104 °F). For higher temperatures, the RH specification is derated to maintain constant moisture content.
2. Installation 2.3. Model Number Interpretation
10 EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
2.3 Model Number Interpretation Instruction
• Select the desired Key Number. The arrow to the right marks the selections available. • Make one selection each from Tables I through II using the column below the proper arrow. A dot (•)
denotes unrestricted availability. A letter denotes restricted availability.
Key Numbers Table I Table II
E D C 2 0 _ - _ _ _ - _ _
KEY NUMBER
Description Selection Availability
Size 48 x 48 mm (1/16 DIN), 1x AI, 1x ALM, 1x DI EDC201 ↓
48 x 96 mm (1/8 DIN), 1x AI, 2x ALM, 1x DI EDC202 ↓
96 x 96 (1/4 DIN), 1x AI, 2x ALM, 1x DI EDC203 ↓
Table I
Power 100-240 VAC Power 24 VDC Power
0 _ _ 1 _ _
· · ·
Control Output
Relay, Dry Contact / N.O., 5A @ 30 Vdc or 250 VAC SSR Drive, 24 VDC @ 20 mA
_ 0 _ _ 1 _
· · ·
Future None _ _ 0 · · ·
TABLE II
Future None 0 _ · · ·
Future None _ 0 · · ·
Table 2-4: Model Number Interpretation
2. Installation 2.4. Control and Alarm Relay Contact Information
Revision 2.0 EDC201 / EDC202 / EDC203 Product Manual 11 July 2015
2.4 Control and Alarm Relay Contact Information Control Relays
ATTENTION Control relays operate in the standard control mode (that is, energized when output state is on).
2.5 Mounting Physical Considerations
The controller can be mounted on either a vertical or tilted panel using the mounting kit supplied. Adequate access space must be available at the back of the panel for installation and servicing activities. Overall dimensions and panel cutout requirements for mounting the controller are shown in Figure 2-2: Panel Cutout Requirements.
Overall Dimensions
Figure 2-1: Overall Dimensions
2. Installation 2.5. Mounting
12 EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
Panel Cutout Requirements
Figure 2-2: Panel Cutout Requirements
2. Installation 2.5. Mounting
Revision 2.0 EDC201 / EDC202 / EDC203 Product Manual 13 July 2015
Mounting Method
Before mounting the controller, refer to the nameplate on the outside of the case and make a note of the model number. It will help later when selecting the proper wiring configuration.
Mounting Procedure
1. Orient the case properly and slide it through the panel hole from the front.
2. Insert the prongs of the clips into the two holes on the left and right side of case.
3. Tighten screws to secure the mounting kit against the panel.
CAUTION
Over tightening will cause mounting kit damage and a loose fit will result in improper unit installation.
2. Installation 2.6. Wiring
14 EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
2.6 Wiring Electrical Considerations
Line voltage wiring This controller is considered “rack and panel mounted equipment” per EN61010-1, Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use, Part 1: General Requirements. Conformity with 72/23/EEC, the Low Voltage Directive requires the user to provide adequate protection against a shock hazard. The user shall install this controller in an enclosure that limits OPERATOR access to the rear terminals.
Mains Power Supply Each controller size supports two power supply types. One mode type is suitable for connection to 100 to 240 Vac power supply mains, the other is suitable for connection to 24 Vdc power supply mains. There is a built-in 33V, 750mA self recovery fuse for 24 Vdc applications. It is the user’s responsibility to provide a switch and non-time delay (North America), quick-acting, high breaking capacity, Type F (Europe), 1/2A, 250V fuse(s), or circuit breaker for 100-240 Vac applications. The switch or circuit breaker shall be located in close proximity to the controller, within easy reach of the OPERATOR. The switch or circuit breaker shall be marked as the disconnecting device for the controller.
CAUTION
Applying 100-240 Vac to an instrument rated for 24 Vdc will severely damage the instrument and is a fire and smoke hazard.
When applying power to multiple instruments, make certain that sufficient current is supplied. Otherwise, the instruments may not start up normally due to the voltage drop caused by the in-rush current.
Control/Alarm Circuit Wiring The insulation of wires connected to the Control/Alarm terminals shall be rated for the highest voltage involved. Extra Low Voltage (ELV) wiring (input, current output, and low voltage Control/Alarm circuits) shall be separated from HAZARDOUS LIVE (>30 Vac, 42.4 Vpeak, or 60 Vdc) wiring per Permissible Wiring Bundling, Table 2-5.
Electrical Noise Precautions Electrical noise is composed of unabated electrical signals, which produce undesirable effects in measurements and control circuits. Digital equipment is especially sensitive to the effects of electrical noise. Your controller has built-in circuits to reduce the effect of electrical noise from various sources. If there is a need to further reduce these effects: Separate External Wiring—Separate connecting wires into bundles (See Permissible Wiring Bundling - Table 2-5) and route the individual bundles through separate conduit metal trays. Use Suppression Devices—For additional noise protection, you may want to add suppression devices at the external source. Appropriate suppression devices are commercially available.
ATTENTION For additional noise information, refer to document number 51-52-05-01, How
2. Installation 2.6. Wiring
Revision 2.0 EDC201 / EDC202 / EDC203 Product Manual 15 July 2015
to Apply Digital Instrumentation in Severe Electrical Noise Environments.
Permissible Wiring Bundling
Table 2-5: Permissible Wiring Bundling
Bundle No. Wire Functions
1
• Line power wiring • Earth ground wiring • Line voltage control relay output wiring • Line voltage alarm wiring
2
Analog signal wire, such as: • Input signal wire (thermocouple, 4 to 20 mA, etc.) • 4-20 mA output signal wiring
Digital input signals
3 • Low voltage alarm relay output wiring • Low voltage wiring to solid state type control circuits • Low voltage wiring to open collector type control circuits
2. Installation 2.7. Wiring Diagrams
16 EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
2.7 Wiring Diagrams Identify Your Wiring Requirements
To determine the appropriate diagrams for wiring your controller, refer to the model number interpretation in this section. The model number of the controller is on the outside of the case.
Wiring the Controller
Figure 2-3: Composite Wiring Diagram Figure
Callout Details
1 AC Line Voltage Terminals
2 Alarm Terminals
3 Control Input Terminals
4 TC/RTD Input Terminals
5 Reserved Terminals
6 Switching Value Terminals
Revision 2.0 EDC201 / EDC202 / EDC203 Product Manual 17 July 2015
3. Configuration
3.1 Overview Configuration is a dedicated operation where you use straightforward keystroke sequences to select and establish (configure) pertinent control data best suited for your application. To assist you in the configuration process, there are prompts that appear in the top, upper and lower displays. These prompts let you know what group of configuration data (Set Up prompts) you are working with and also, the specific parameters (Function prompts) associated with each group.
3. Configuration 3.2. Configuration Prompt Hierarchy
18 EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
3.2 Configuration Prompt Hierarchy Figure 3-1: Configuration Prompt Hierarchy
ReJu
3In
PrSt
evision 2.0 uly 2015
.3 Cntroduction
Each oare shoIf you tells yo
rocedure tep
1 Enter S
2 Select
3 Select Param
4 ChangSelecti
5 Enter tSelecti
6 Exit Co
ED
Configura
of the Set Up gown in Table 3want to changou the keys to
Action
Set Up Mode
any Set Up G
a Function eter
e the Value oron
the Value or on
onfiguration
DC201 / EDC2
ation Pro
groups and the3-1 that followge any of thes
o press to get t
Long
Group
r
Long
withoperthan
202 / EDC203
ocedure
eir functions aw this procedue selections oo any Set Up
Press
g press
or
g press or
out any key ration more n 30s.
3 Product Man
are pre-configure. r values, follogroup and any
Top DisGroup ti
Upper D
Sequenttitles sho3-1 Conthe Set of paramproceed
Upper Dwithin thLower Dfor the fiUp grouSequentpromptsselectedwant to
Incremeselectionprompt.
Enters vafter ano
The conreturns t
3
ual
gured at the fac
ow the below py associated F
Re
play= INP (Thtle)
Display=TYPE
tially displays own in the profiguration ProUp group title
meters you wad to the next st
Display = the fihat Set Up groDisplay = the cirst function prp. tially displays
s of the Set Upd. Stop at the fchange, then
ents or decremn that appears
value or selectother key is pr
ntroller exits Coto Normal Ope
3. C.3. Configurat
ctory. The fac
procedure. ThFunction param
esult
his is the first S
the other Set ompt hierarchympt Hierarchythat describes
ant to configuretep.
irst Function poup. current value orompt of the s
the other funcp group you hafunction promproceed to the
ments the values for the selec
tion made intoressed.
onfiguration Meration Mode.
Configurationion Procedure
19
ctory settings
his procedure meter prompt.
Set Up
Up group y in Figure y. Stop at s the group e. Then
prompt
or selection elected Set
ction ave pt that you e next step.
e or cted function
o memory
Mode and
n e
9
.
3. Configuration 3.4. Input Set Up Group
20 EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
3.4 Input Set Up Group Introduction
This data deals with various parameters required to configure the Input.
Function Prompts
Set up Group
Function Prompt
7-Segment Code Default
Value Selection or Range of Setting
7-Segment Code Parameter
Definition Top Display Upper Display Lower Display
Input
TYPE TYPE Disable
Disable DISB Disabled
E EH E Thermocouple High
J JH J Thermocouple High
N NNMH Ni-Ni-Moly Thermocouple High
KH KH K Thermocouple High
P PLH P Thermocouple
R R R Thermocouple
S S S Thermocouple
T TH T Thermocouple High
PT100 100 100 Ohm RTD High
PT100(Low) 100L 100 Ohm RTD Low
Rhi ANH 100 -999 ~ 9999 100
Input high range value. Input high range of TC and RTD input types are generated by searching the corresponding table automatically depending on the input type. It cannot be modified.
3. Configuration 3.4. Input Set Up Group
Revision 2.0 EDC201 / EDC202 / EDC203 Product Manual 21 July 2015
Set up Group
Function Prompt
7-Segment Code Default
Value Selection or Range of Setting
7-Segment Code Parameter
Definition Top Display Upper Display Lower Display
Rlow ANL 0 -999 ~ 9999 0
Input low range value. Input high range of TC and RTD input types are generated by searching the corresponding table automatically depending on the input type. It cannot be modified.
RATIO RATO 1 -20.00 ~ 20.00 Ratio on input.
BIAS BIAS 0 -999 ~ 9999
Bias is used to compensate the input for drift of an input value due to deterioration of a sensor, or some other cause. Select the Bias value you want on the Input.
FILTER FILT 0 0 ~ 120s
A software digital filter is provided for the Input to smooth the input signal. 0 means filtering prohibited.
BURNOUT BRN FS FS FS
Pre-configured Failsafe output (selected in the CONTROL Set up Group) applied if a failed input is detected (does not apply for an input out of range).
3. Configuration 3.4. Input Set Up Group
22 EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
Set up Group
Function Prompt
7-Segment Code Default
Value Selection or Range of Setting
7-Segment Code Parameter
Definition Top Display Upper Display Lower Display
UP UP
UPSCALE BURNOUT will force the Input signal to the full scale value when the sensor fails.
The maximum permissible PV value shall be:
The maximum value = Ratio *(High Range + 1% of range span) + Bias;
Which shall not be greater than (High Range + 10% of range span)
DOWN DOWN
DOWNSCALE BURNOUT will force the Input signal to the lower range value when the sensor fails.
The minimum permissible PV value shall be:
The minimum value = Ratio*(Low Range – 1% of range span) + Bias;
Which shall not be less than (Low Range – 10% of range span)
NO FS NO FS
No configured Failsafe output applied if failed input is detected. This selection provides input failure detection and alarm.
3. Configuration 3.5. Control Set Up Group
Revision 2.0 EDC201 / EDC202 / EDC203 Product Manual 23 July 2015
3.5 Control Set Up Group Introduction
The functions listed in this group deal with how the controller will control the process including: Control algorithm, Cycle time, Set Point Limits, Output Direction and Limits, Deadband, Soft Start and Timer period.
Function Prompts
Set up Group
Function Prompt
7-Segment Code
Default Value
Selection or Range of Setting
7-Segment Code Parameter
Definition Top Display Upper Display Lower Display
Control CTL ALG ALGC ON-OFF
ON-OFF ONOFF
The difference(PV–SP) of Process Variable (PV) and the Set Point (SP) determines the output. The output can be either ON (100 %) or OFF (0%).
In direct acting control, when the error signal is positive, the output is 100 %; and when the error signal is negative, the output is 0 %. If the control action is reverse, the opposite is true.
Time A TImA
Time Proportional Output based on PID A has a resolution of 3.33 msec. Cycle Time is adjustable from 1 to 120 seconds.
3. Configuration 3.5. Control Set Up Group
24 EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
Set up Group
Function Prompt
7-Segment Code
Default Value
Selection or Range of Setting
7-Segment Code Parameter
Definition Top Display Upper Display Lower Display
Time B TImB
Proportional Output based on PID B has a resolution of 3.33 msec. Cycle Time is adjustable from 1 to 120 seconds.
Unlike the PID A equation, the controller gives only an integral response to a setpoint change, with no effect on the output due to the gain or rate action, and it gives full response to PV changes. Otherwise controller action is as described for the PID A equation.
3. Configuration 3.5. Control Set Up Group
Revision 2.0 EDC201 / EDC202 / EDC203 Product Manual 25 July 2015
Set up Group
Function Prompt
7-Segment Code
Default Value
Selection or Range of Setting
7-Segment Code Parameter
Definition Top Display Upper Display Lower Display
TPSC TPSC
The Three Position Step Control algorithm allows the control of a valve (or other actuator) with an electric motor driven by two controller relay outputs.
The Three Position Step Control algorithm provides an output display (OUT) which is an estimated motor position, since the motor is not using any slidewire feedback. Although this output indication is only an approximation, it is “corrected” each time the controller drives the motor to one of its stops (0 % or 100 %).
CYC Time CYCT 1 1~ 120
Cycle time used for time proportioning control. If the control output type is RLY, Units: s; if the control out type is SSR driver, Units: 1/3s
ACTION ACTN
CONTROL OUTPUT DIRECTION: Select direct or reverse output action.
3. Configuration 3.5. Control Set Up Group
26 EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
Set up Group
Function Prompt
7-Segment Code
Default Value
Selection or Range of Setting
7-Segment Code Parameter
Definition Top Display Upper Display Lower Display
REVERSE
Reverse REVR
REVERSE ACTING CONTROL: Based on the PID control, the controller’s output decreases as the process variable increases.
Direct DIRT
DIRECT ACTING CONTROL—Based on the PID control, the controller’s output increases as the process variable increases.
RLYSTATE RLST OFF
OFF OFF
It is used for controlling the digital output. Digital output de-energizes when the control output is 0%.
ON ON
It is used for controlling digital output. Digital output energizes when control output is 0%.
Minimun On Time
MIOT 3 1 ~ 6
Keeps the high level enabled for set time each time the output is enabled.
ATTENTION Only applicable for ON/OFF control.
3. Configuration 3.5. Control Set Up Group
Revision 2.0 EDC201 / EDC202 / EDC203 Product Manual 27 July 2015
Set up Group
Function Prompt
7-Segment Code
Default Value
Selection or Range of Setting
7-Segment Code Parameter
Definition Top Display Upper Display Lower Display
OUT HYST HYS 2% 0 ~ 100% of PV span
HYSTERESIS (OUTPUT RELAY) is an adjustable overlap of the ON/OFF states of each control output. This is the difference between the value of the process variable at which the control outputs energize and the value at which they de-energize.
ATTENTION Only applicable for ON/OFF control.
DEADBAND DB 1% 0.5 ~ 5.0%
DEADBAND is an adjustable gap between the operating ranges of output 1 and output 2 in which neither output operates (positive value) or both outputs operate (negative value).
Apply to TPSC.
FAILMODE FLMD Latch
Latch LA
Controller goes to Manual mode; output goes to failsafe value.
No Latch NOLA
Controller stays in last mode that was being used (Automatic or Manual); output goes to failsafe value.
FAILSAFE FLSF 0 0 ~ 100% Failsafe output value.
3. Configuration 3.5. Control Set Up Group
28 EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
Set up Group
Function Prompt
7-Segment Code
Default Value
Selection or Range of Setting
7-Segment Code Parameter
Definition Top Display Upper Display Lower Display
Motor TI MTRT 5 5 ~ 1800s
MOTOR TIME – Appears only when “TPSC” (Three Position Step Control) is selected as the Control Algorithm. This is the time it takes the motor to travel from 0 to 100 % (fully closed to fully open). This time can usually be found on the nameplate of the motor.
Soft Start SFST DISABLE
DISABLE DISB Disable the soft-start feature.
ENABLE EABL Enable the soft-start feature.
Output Limit CLIM 0% 0% ~ 100%
Soft Start Output Power Limit is the limit output applied to the heater or the machine at power up.
Set Point SP 0 Same as PV Range
Soft Start Set Point is the threshold for the Soft Start Timer.
Soft Start function ends when the PV reaches the Soft Start Set Point or the Timer elapses.
3. Configuration 3.6. Tune PAR Set Up Group
Revision 2.0 EDC201 / EDC202 / EDC203 Product Manual 29 July 2015
Set up Group
Function Prompt
7-Segment Code
Default Value
Selection or Range of Setting
7-Segment Code Parameter
Definition Top Display Upper Display Lower Display
PERIOD PERI 0 0:00min ~ 99.59min
PERIOD allows you to configure the length of timeout period.
Soft Start function ends when the PV is above the Soft Start Set Point or the Timer elapses.
3.6 Tune PAR Set Up Group Introduction
Tuning consists of establishing the appropriate values for the tuning constants you are using so that your controller responds correctly to changes in process variable and Set Point. You can start with predetermined values but you will have to watch the system to see how to modify them. The Accutune feature automatically selects Gain, Rate, and Reset on demand.
ATTENTION Because this group contains functions that have to do with security and lockout, we recommend that you configure this group last, after all other configuration data has been loaded.
Function Prompts
Set up Group
Function Prompt
7-Segment Code Default
Value Selection or Range of Setting
7-Segment Code Parameter
Definition Top Display Upper Display Lower Display
Tune Para
P P 1 0.001 ~ 1000 PID gain.
I I 10 0 ~ 3200s Integral coefficient of PID
D D 0 0 ~ 999s Differential coefficient of PID
3. Configuration 3.7. ALARM Set Up Group
30 EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
3.7 ALARM Set Up Group Introduction
An alarm is an indication that an event that you have configured (for example—Process Variable) has exceeded one or more alarm limits. There is one alarm available for EDC201.There are two alarms available for EDC202 and EDC203. Each alarm has two Set Points. You can configure each of these two Set Points to alarm on various controller parameters. There are two alarm output selections, High and Low. You can configure each Set Point to alarm either High or Low. These are called single alarms. You can also configure the two Set Points to alarm on the same event and to alarm both high and low. A single adjustable Hysteresis of 0 % to 100 % is configurable for the alarm Set Point. The prompts for the Alarm Outputs appear whether or not the alarm relays are physically present. This allows the Alarm status to be shown on the display.
Function Prompts
Set up Group
Function Prompt
7-Segment Code Default
Value Selection or Range of Setting
7-Segment Code Parameter
Definition Top Display Upper Display Lower Display
Alarms
11TYPE AL11 None
None NONE NO ALARM
PV PV PROCESS VARIABLE
DEV DEV DEVIATION
Output OUT OUTPUT
MANUAL Man ALARM ON MANUAL MODE
PV RATE PVRT PV RATE OF CHANGE
DIG INP DIN DIGITAL INPUT
TCWARN TCWN THERMOCOUPLE WARNING
TCFAIL TCFL THERMOCOUPLE FAILING
FSAFE FS FAILSAFE
Diagnostic DIAG SYSTEM DIAGNOSTIC
11SEL SE11 HIGH HI HIGH ALARM
LOW LO LOW ALARM
3. Configuration 3.7. ALARM Set Up Group
Revision 2.0 EDC201 / EDC202 / EDC203 Product Manual 31 July 2015
Set up Group
Function Prompt
7-Segment Code Default
Value Selection or Range of Setting
7-Segment Code Parameter
Definition Top Display Upper Display Lower Display
11VAL VL11 ALARM 11 SET POINT VALUE
12TYPE AL12 None None NONE NO ALARM
PV PV PROCESS VARIABLE
DEV DEV DEVIATION
Output OUT OUTPUT
MANUAL Man ALARM ON MANUAL MODE
PV RATE PVRT PV RATE OF CHANGE
DIG INP DIN DIGITAL INPUT
TCWARN TCWN THERMOCOUPLE WARNING
TCFAIL TCFL THERMOCOUPLE FAILING
FSAFE FS FAILSAFE
Diagnostic DIAG SYSTEM DIAGNOSTIC
12SEL SE12 HIGH HI HIGH ALARM
LOW LO LOW ALARM
12VAL VL12 ALARM 12 SET POINT VALUE
21TYPE AL21 None NONE
This configuration is not available on EDC201.
PV PV
PROCESS VARIABLE. This configuration is not available on EDC201.
DEV DEV
DEVIATION. This configuration is not available on EDC201.
3. Configuration 3.7. ALARM Set Up Group
32 EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
Set up Group
Function Prompt
7-Segment Code Default
Value Selection or Range of Setting
7-Segment Code Parameter
Definition Top Display Upper Display Lower Display
Output OUT
This configuration is not available on EDC201.
MANUAL Man
ALARM ON MANUAL MODE. This configuration is not available on EDC201.
PV RATE PVRT
PV RATE OF CHANGE. This configuration is not available on EDC201.
DIG INP DIN
DIGITAL INPUT This configuration is not available on EDC201.
TCWARN TCWN
THERMOCOUPLE WARNING This configuration is not available on EDC201.
TCFAIL TCFL
THERMOCOUPLE FAILING This configuration is not available on EDC201.
FSAFE FS
FAILSAFE. This configuration is not available on EDC201.
Diagnostic DIAG
SYSTEM DIAGNOSTIC This configuration is not available on EDC201.
21SEL SE21 HIGH HI
HIGH ALARM This configuration is not available on EDC201.
LOW LO
LOW ALARM. This configuration is not available on EDC201.
3. Configuration 3.7. ALARM Set Up Group
Revision 2.0 EDC201 / EDC202 / EDC203 Product Manual 33 July 2015
Set up Group
Function Prompt
7-Segment Code Default
Value Selection or Range of Setting
7-Segment Code Parameter
Definition Top Display Upper Display Lower Display
21VAL VL21
Alarm 21 Set Point value. This configuration is not available on EDC201.
22TYPE AL22 None NONE
NO ALARM. This configuration is not available on EDC201.
PV PV
This configuration is not available on EDC201.
DEV DEV
DEVIATION. This configuration is not available on EDC201.
Output OUT
OUTPUT. This configuration is not available on EDC201.
MANUAL Man
ALARM ON MANUAL MODE. This configuration is not available on EDC201.
PV RATE PVRT
PV RATE OF CHANGE. This configuration is not available on EDC201.
DIG INP DIN
DIGITAL INPUT. This configuration is not available on EDC201.
TCWARN TCWN
THERMOCOUPLE WARNING. This configuration is not available on EDC201.
TCFAIL TCFL
THERMOCOUPLE FAILING. This configuration is not available on EDC201.
FSAFE FS
FAILSAFE. This configuration is not available on EDC201.
3. Configuration 3.7. ALARM Set Up Group
34 EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
Set up Group
Function Prompt
7-Segment Code Default
Value Selection or Range of Setting
7-Segment Code Parameter
Definition Top Display Upper Display Lower Display
Diagnostic DIAG
SYSTEM DIAGNOSTIC. This configuration is not available on EDC201.
22SEL SE22 HIGH HI
HIGH ALARM. This configuration is not available on EDC201.
LOW LO
LOW ALARM. This configuration is not available on EDC201.
22VAL VL22 - -
ALARM 22 SET POINT VALUE。This configuration is not available on EDC201.
ALHYST HYSA 1% 0-100% OF SPAN
ALARM HYSTERESIS—A single adjustable hysteresis is provided on alarms such that when the alarm is OFF it activates at exactly the alarm Set Point; when the alarm is ON, it will not deactivate until the variable is 0.0 % to 100 % away from the alarm Set Point.
ALARM DELAY
DLYA 0 0 ~ 30s
Configurable alarm trigger delay time allows you to force the trigger time of an alarm to delay for a time period of from 0 to 30 seconds in an alarm condition.
3. Configuration 3.7. ALARM Set Up Group
Revision 2.0 EDC201 / EDC202 / EDC203 Product Manual 35 July 2015
Set up Group
Function Prompt
7-Segment Code Default
Value Selection or Range of Setting
7-Segment Code Parameter
Definition Top Display Upper Display Lower Display
LATCH SEL
LACH
LATCH Yes/ No
Alarm output is configured to be Latching.
When the alarm condition disappears, an acknowledge signal is needed to reset the alarm status.
NoLATCH
Alarm output is configured to be Non-latching.
When an alarm condition is met, the alarm is triggered; when the alarm condition is cleared, the alarm is automatically reset.
BLOCK BLK DISABLE
DISABLE DISB Disables alarm blocking
ALARM1 ALM1 Blocks Alarm 1 only.
ALARM2 ALM2
Blocks Alarm 2 only. This configuration is not available on EDC201.
ALARM12 AM12
Blocks both alarms. This configuration is not available on EDC201.
TIMER TMR Disable DISABLE DISB Disable the timer.
ENABLE EABL Enable the timer.
START STAT KEY KEY KEY
START allows you to select whether the timer starts with the keyboard (A/M OK key). This configuration is not available on EDC201.
3. Configuration 3.7. ALARM Set Up Group
36 EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
Set up Group
Function Prompt
7-Segment Code Default
Value Selection or Range of Setting
7-Segment Code Parameter
Definition Top Display Upper Display Lower Display
ALARM2 ALM2
START allows you to select whether the timer starts with the Alarm 2. This configuration is not available on EDC201.
PERIOD PERI 0:00min ~ 9:59hrs
PERIOD allows you to configure the length of the timeout period (from 0 to 9 hours:59 minutes).
3. Configuration 3.8. Auxiliary Set Up Group
Revision 2.0 EDC201 / EDC202 / EDC203 Product Manual 37 July 2015
3.8 Auxiliary Set Up Group Introduction
The Auxiliary group lets you configure the Auxiliary Output to be a specific selection with desired scaling. Accutune III automatically calculates GAIN, RATE, and RESET TIME (PID) tuning constants for your control loop. When initiated on demand, the Accutune algorithm measures a process step response and automatically generates the PID tuning constants needed for no overshoot on your process. It operates with PIDA, PIDB, PD+MR and Three Position Step Control Algorithm.
Function Prompts
Set up Group
Function Prompt
7-Segment Code Default
Value
Selection or Range of Setting
7-Segment Code Parameter
Definition
Auxiliary
DIG IN
DIN None NONE NONE NO DIGITAL INPUT SELECTIONS
A|M AM Switch Automatic /Manual operating mode.
Direction DIR
The controller will scan the current action direction and redirect to the opposite direction.
LOCK LOCK
KEYBOARD LOCKOUT. Contact closure disables all keys.
Timer TMR
The timer is started once the rising-edge of a digital input is detected.
ACK ACK
Alarm acknowledgement configuration. The system acknowledges the alarm once the rising edge of digital input is detected.
AT AT
ON/OFF the ACCUTUNE. If the rising-edge of a digital input is detected, the system will start Accutune if the start condition has been met and Accutune is not running.
ACCUTUNE
AT Disable DISABLE DISB/ TUNE Disables the Accutune function.
3. Configuration 3.9. OPTION Set Up Group
38 EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
3.9 OPTION Set Up Group Introduction
This group includes selections for Decimal place, Units of temperature, Power frequency, system staus, lockout attribute, operating level and password.
Function Prompts
Set up Group
Function Prompt
7-Segment Code
Default Value
Selection or Range of Setting
7-Segment Code
Parameter Definition
Top Display Upper Display Lower Display
Option
PWR FREQ
HZ 50 HZ 50HZ 50HZ Power Frequency
60HZ 60HZ Power Frequency
DECIMAL
DECI None None NONE No Decimal Place
One 1
1 decimal place. ATTENTION Auto-ranging will occur for selections of one, two or three decimal places. For example, should the instrument be configured for two decimal places and the PV exceeds 99.99, then the display will change to a single decimal place so that values of 100.0 and above can be shown.
Two 2
2 decimal places. ATTENTION Auto-ranging will occur for selections of one, two or three decimal places. For example, should the instrument be configured for two decimal places and the PV exceeds 99.99, then the display will change to a single decimal place so that values of 100.0 and above can be shown.
ReJu
SG
T
evision 2.0 uly 2015
Set up Group
FuPro
Top Display
TEMUN
STA
LO
ED
nction ompt
7-SCo
Up
MP IT
UNI
ATUS
STA
CKOUT
LOC
DC201 / EDC2
Segment ode
DV
per Display
T D
A
CK N
202 / EDC203
Default Value
Seor of Se
Low
Thr
DEG C DE
DE
FirmVer
HarVer
Err
DisTes
ResFacDef
None Non
All
3 Product Man
lection Range
tting
7-SCo
wer Display
ree 3
G C DEG
G F DEG
mware rsion
FWV
rdware rsion
HWV
or Code ERC
splay st
TES
set to ctory fault
DEF
ne NON
but SP EII
ual
Segment ode
PD
3Awoptfttsvc
GC D
GF D
VN F
VN H
CD E
ST T
FT
RoF
NE D
SP
L
w
3. C3.9. OPTION
Parameter Definition
3 decimal placATTENTION Awill occur for sone, two or thrplaces. For exhe instrument
for two decimahe PV exceedhe display wil
single decimalvalues of 100.0can be shown.
Degrees Celsi
Degrees Fahre
Firmware vers
Hardware vers
Error code.
Testing LED d
Restoring the cof the instrumeFactory Setting
Disable the Lo
Lock all keys e
or which is used
ConfigurationSet Up Group
39
ces. Auto-ranging selections of ree decimal ample, shouldt be configuredal places and ds 99.99, thenl change to a place so that0 and above .
us
enheit
sion.
sion.
isplay.
configuration ent back to thegs.
ockout function
except
for editing SP
n p
9
d d
t
e
n.
.
3. Configuration 3.9. OPTION Set Up Group
40 EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
Set up Group
Function Prompt
7-Segment Code
Default Value
Selection or Range of Setting
7-Segment Code
Parameter Definition
Top Display Upper Display Lower Display
ALL ALL
Contact closure disables all keys for operator level. Lower display shows LOCK if a key is pressed. Long press Setup key and input the Configurator level password to unlock keys.
OPERATING LEVEL
OPLV None Oper OPER Operator level.
CFG CFG Configuration level.
Mask MASK
Customizing parameter mask. Determine the hide/ unhide and configurable/ unconfigurable features for different operation levels.
PASSWORD
PASS Oper OPER Setting the operator level password.
Config CFG Setting the configuration level password.
Table 3-1: Set Up Parameter Reference
ReJu
3Co
Pr
PrSt
1
evision 2.0 uly 2015
.10 Cononfiguring T
This seRanges
reliminary S• The co• The us
rocedure tep
1 Select Type( TParam
2 Select Type
3 Select RangeParam
4 Select RangeParam
5 Select Ratio(RParam
6 ChangValue (
7 Select Functioapplica
8 ChangValue (
9 Select Functioapplica
10 Exit Co
ED
nfiguring TC Type Inpection describs, Bias, Ratio
Steps ontroller is in tser has the acc
Action
‘Input TYPE)’ Functeter
the intended T
‘High (Rhi)’ Functioeter
‘Low (Rlow)’ Functieter
‘Input RATO)’ Functioneter (if applica
e the Input Ra(if applicable)
‘Input Bias(BIon Parameter able)
e the Input Bia(if applicable)
‘Filter(FILT)’ on Parameter able)
onfiguration
DC201 / EDC2
Analog put
es the proceduand Filter.
the Configuracess to set para
tion Long
TC
n
ion
n able)
atio
AS)’ (if
as
(if
Long withomore
202 / EDC203
Input
ure of configu
ation Mode. ameters.
Press
press
or
or
or
press ut any key opthan 30s.
3 Product Man
uring TC Type
TopGro
Up
Low
Up
LowHigAck
Up
LowLowAck
Up
LowInp
-
Up
LowInp
-
Up
LowInp
or eration
TheandMo
3.1
ual
e Input, includ
p Display= INPoup title)
per Display=T
wer Display=in
per Display=
wer Display= tgh Range knowledge the
per Display=
wer Display= tw Range knowledge the
per Display=
wer Display= tput Ratio
per Display=
wer Display= tput Bias
per Display=
wer Display= tput Filter
e controller exd returns to thode.
3. C0. Configuring
ding Input Typ
Result
P (This is the
TYPE
ntended TC T
ANH
the current va
e Value
ANL
the current va
e Value
RATO
the current va
BIAS
the current va
FILT
the current va
xits Configurate Normal Ope
Configurationg Analog Inpu
41
pe, Input
first Set Up
ype
lue of TC
lue of TC
lue of TC
lue of TC
lue of TC
tion Mode eration
n t
1
3. Config3.10. Con
42
Configu
Prelimin• •
ProceduStep
1
2
3
4
5
6
7
8
9
10
guration nfiguring Analo
uring RTD TyThis section dRanges, Bias,
nary Steps The controlleThe user has t
ure Actio
Select ‘Input Type( TYPE)’Parameter
Select the inteType
Select ‘High Range(Rhi)’ FParameter
Select ‘Low Range(Rlow)’Parameter
Select ‘Input Ratio(RATO)’ FParameter (if
Change the InValue (if appli
Select ‘Input BFunction Paraapplicable)
Change the InValue (if appli
Select ‘Filter(FFunction Paraapplicable)
Exit Configura
og Input
EDC201
ype Input describes the p, Ratio and Fil
r is in the Conthe access to s
on
Function
ended RTD
Function
’ Function
Function applicable)
nput Ratio icable)
Bias(BIAS)’ ameter (if
nput Bias icable)
FILT)’ ameter (if
ation
/ EDC202 / ED
procedure of clter.
nfiguration Mset parameters
Pr
Long press
or
or
or
Long press without any more than 3
DC203 Produc
configuring R
Mode. s.
ress
r
r
r
or key operation0s.
ct Manual
RTD Type Inpu
Top DispUp Grou
Upper Di
Lower Di
Upper Di
Lower DiRTD HigAcknowle
Upper Di
Lower DiRTD LowAcknowle
Upper Di
Lower DiRTD Inpu
-
Upper Di
Lower DiRTD Inpu
-
Upper Di
Lower DiRTD Inpu
The contand returMode.
ut, including I
Resul
play= INP (Thip title)
isplay=TYPE
isplay=100 or
isplay= ANH
isplay= the cuh Range edge the Valu
isplay= ANL
isplay= the cuw Range edge the Valu
isplay= RATO
isplay= the cuut Ratio
isplay= BIAS
isplay= the cuut Bias
isplay= FILT
isplay= the cuut Filter
troller exits Corns to the Norm
RevisJu
Input Type, In
lt
s is the first S
100L
urrent value of
ue
urrent value of
ue
urrent value of
urrent value of
urrent value of
onfiguration Mmal Operation
sion 2.0 ly 2015
nput
Set
ode n
ReJu
Co
Pr
Pr
St
evision 2.0 uly 2015
onfiguring AThis se
reliminary S• The co• The us
rocedure Config
tep
1 Enter S
2 Select Functio
3 Select Param
4 Select Mode
5 Select Functio
6 Changvalue (
7 Select Functio
8 ChangMode v
9 Exit Co
ED
Analog Inpuection describ
Steps ontroller is in tser has the acc
guring FailSaf
Action
Set Up Mode
‘Burnout(BRN)on Parameter
‘FS(FS)’ Funceter
Control Set U
‘Failsafe(FLSFon Parameter
e the Failsafe(if applicable)
‘Failsafe Modon Parameter
e the Failsafevalue (if applic
onfiguration
DC201 / EDC2
ut Burnout es the procedu
the Configuracess to set para
fe Mode
Long
)’
ction
Up
F)’
e
de’
e cable)
Longwithmore
202 / EDC203
ure of configu
ation Mode. ameters.
Press
g press
or
or
or
g press out any key oe than 30s.
3 Product Man
uring Burnout
TU
U
U
Lm
L
T
U
L
U
L
or peration
TaM
3.1
ual
Mode for An
Top Display= IUp Group title)
Upper Display
Upper Display
Lower Displaymode
Lower Display
Top Display= C
Upper Display
Lower Display
Upper Display
Lower Display
The controller and returns toMode.
3. C0. Configuring
nalog Input.
Result
INP (This is th)
y=TYPE
y= BRN
y= the current
y= FS
CON
y=FLSF
y= intended Fa
y=FLMD
y= LA or NOLA
exits Configuthe Normal O
Configurationg Analog Inpu
43
he first Set
Burnout
ailsafe value
ration Mode Operation
n t
3
3. Config3.10. Con
44
Step
1
2 S
3 S
4
Step
1
2
3
4
guration nfiguring Analo
Configuring N
Actio
Enter Set Up
Select ‘BurnouFunction Para
Select ‘No Failsafe(NOFS)Parameter
Exit Configura
Configuring U
Action
Enter Set Up
Select ‘BurnoFunction Para
Select ‘UpscaBurnout(UP)’ FParameter
Exit Configura
og Input
EDC201
No FailSafe M
n
Mode
ut(BRN)’ ameter
)’ Function
ation
Upscale Burno
n
Mode L
ut(BRN)’ ameter
ale Function
ation Lwm
/ EDC202 / ED
Mode
Pre
Long press
or
Long press without any kmore than 30
out Mode
Press
Long press
or
Long press without any kemore than 30s
DC203 Produc
ess
or ey operation s.
s
or y operation .
ct Manual
Top DisplaGroup title
Upper Dis
Upper Dis
Lower Dis
Lower Dis
The controand returnMode.
Top DisplayGroup title)
Upper Displa
Upper Displa
Lower Displa
Lower Displa
The controllereturns to th
Result
ay= INP (Thise)
splay=TYPE
splay= BRN
splay= the curr
splay= NOFS
oller exits Conns to the Norm
Result
= INP (This is
ay=TYPE
ay= BRN
ay= the curren
ay= UP
er exits Confige Normal Ope
RevisJu
t
is the first Se
rent Burnout m
nfiguration Momal Operation
the first Set U
nt Burnout mo
guration Modeeration Mode.
sion 2.0 ly 2015
et Up
mode
ode
Up
ode
e and
ReJu
St
As
Pr
PrSt
1
2
3
4
5
evision 2.0 uly 2015
Config
tep
1 Enter S
2 Select Functio
3 Select BurnouFunctio
4 Exit Co
ssign TempThis se
reliminary S• The co• The us
rocedure tep
1 Enter S
2 Select Mode
3 Select (UNIT)’ Parame
4 Changevalue
5 Exit Co
ED
guring Downs
Action
Set Up Mode
‘Burnout(BRN)on Parameter
‘Downscale ut(DOWN)’ on Parameter
onfiguration
perature Uniection describ
Steps ontroller is in tser has the acc
Action
Set Up Mode
Option Set Up
‘Temp Unit Function eter
e the ‘Temp U
onfiguration
DC201 / EDC2
cale Burnout
Long pre
)’
Long prewithout amore tha
t es the procedu
the Configuracess to set para
Long p
p
Unit’
Long pwithouoperat
202 / EDC203
Mode
Press
ess
or
ess any key operatan 30s.
ure of configu
ation Mode. ameters.
Press
press
or
press ut any key tion more than
3 Product Man
Top DGrou
Uppe
Uppe
Lowe
Lowe
or tion
The creturn
uring Tempera
Top Grou
Uppe
Top
Uppe
Lowe
or
n 30s.
The and
3.1
ual
R
Display= INP (p title)
er Display=TYP
er Display= BR
er Display= the
er Display= DO
controller exitsns to the Norm
ature Unit.
R
Display= INP up title)
er Display=TYP
Display= OPT
er Display= UN
er Display= in
controller exitsreturns to the
3. C0. Configuring
Result
(This is the firs
PE
RN
e current Burn
OWN
s Configurationmal Operation
Result
(This is the fir
PE
T
NIT
ntended Temp
s ConfiguratioNormal Opera
Configurationg Analog Inpu
45
st Set Up
nout mode
n Mode and Mode.
rst Set Up
Unit
on Mode ation Mode.
n t
5
3. Config3.11. Con
46
3.11 Configu
Prelimin• •
ProceduStep A
1
2 SG
3 SV
4 S
5 C
6 ST
7 CO
8 SS
9 CV
10
guration nfiguring Cont
Configuuring ON-OFThis section d
nary Steps The controlleThe user has t
ure Action
Enter Set Up
Select ControGroup
Select the ONValue
Select the ‘OuHysteresis(HYSFunction Para
Change the ‘OHysteresis’ Va
Select the ‘MiTime (MIOT)’ FParameter
Change the ‘MOn Time’ Valu
Select the ‘ReState(RLST)’ FParameter
Change the ‘RValue
Exit Configura
trol Algorithm
EDC201
ring ConFF Control describes the p
r is in the Conthe access to s
Mode
l Set Up
N-OFF
utput S)’
ameter
Output alue
nimum On Function
Minimum ue
elay Function
Relay State’
ation
/ EDC202 / ED
ntrol Algo
procedure of c
nfiguration Mset parameters
Press
Long press
or
or
or
Long press without any more than 3
DC203 Produc
orithm
configuring C
Mode. s.
r
r
r
or key operation
30s.
ct Manual
ontrol Algorit
Result
Top DispUp Grou
Upper Di
Top Disp
Upper Di
Lower Di
Upper Di
Lower DiHysteres
Upper Di
Lower DiTime Val
Upper Di
Lower DiValue
n The contand returMode.
thm.
play= INP (Thip title)
isplay=TYPE
play= CON
isplay= ALGC
isplay=ONFF
isplay= HYS
isplay=intendesis Value
isplay= MIOT
isplay=intendelue
isplay= RLST
isplay=intende
troller exits Corns to the Norm
RevisJu
s is the first S
ed Output
ed Minimun O
ed Relay State
onfiguration Mmal Operation
sion 2.0 ly 2015
Set
On
e
ode n
ReJu
Co
Pr
PrSt
2
3
4
8
9
1
evision 2.0 uly 2015
onfiguring TThis se
reliminary S• The co• The us
rocedure tep
1 Enter S
2 Select Group
3 Select Time B
4 Select State(RParame
5 ChangeValue
6 Select SecondFunctio
7 ChangeSecond
8 Select Functio
9 ChangeValue
10 Exit Co
ED
Time Proporection describ
Steps ontroller is in tser has the acc
Action
Set Up Mode
Control Set U
Time A(TIMA) B(TIMB) Value
the ‘Relay RLST)’ Functioneter
e the ‘Relay S
the ‘Cycle ds (CYCT)’ on Parameter
e the ‘Cycle ds’ Value
the ‘Action (ACon Parameter
e the ‘Action’
onfiguration
DC201 / EDC2
rtion Controes the procedu
the Configuracess to set para
Long
Up
or
n
State’
CTN)’
Long withomore
202 / EDC203
ol ure of configu
ation Mode. ameters.
Press
press
or
or
or
or
press out any key ope than 30s.
3 Product Man
uring Time Pro
or peration
3.11. Co
ual
oportion Cont
Top Display=Up Group title
Upper Displa
Top Display=
Upper Displa
Lower Displa
Upper Displa
Lower DisplaValue
Upper Displa
Lower DisplaSeconds Valu
Upper Displa
Lower Displa
The controlleMode and retOperation Mo
3. Configuring Con
trol.
Result
= INP (This is te)
y=TYPE
= CON
y= ALGC
y= TIMA or TI
y= RLST
y=intended R
y= CYCT
y=intended Cyue
y= ACTN
y=intended Ac
r exits Configuturns to the Noode.
Configurationntrol Algorithm
47
the first Set
MB
elay State
ycle
ction Value
uration ormal
n m
7
3. Config3.11. Con
48
Configu
Prelimin• •
ProceduStep
1
2 SG
3 SV
4 S‘
5 CV
6 S(
7 CV
8 S
9 CV
10
guration nfiguring Cont
uring Three This section d
nary Steps The controlleThe user has t
ure Actio
Enter Set Up
Select ControGroup
Select TPSC(Value
Select the ‘Deadband(DBParameter
Change the ‘DValue
Select the ‘Mo(MTRT)’ FunctioParameter
Change the ‘MValue.
Select the ‘AcFunction Para
Change the ‘AValue
Exit Configura
trol Algorithm
EDC201
Position Stedescribes the p
r is in the Conthe access to s
on
Mode
l Set Up
TPSC)
B)’ Function
Deadband’
otor Time on
Motor Time’
ction (ACTN)’ ameter
Action’
ation
/ EDC202 / ED
ep Controlprocedure of c
nfiguration Mset parameters
Pre
Long press
or
or
or
or
Long press without any operation m
DC203 Produc
configuring Th
Mode. s.
ess
r
r
r
r
or key ore than 30s.
ct Manual
hree Position
Top DisplaGroup title
Upper Dis
Top Displa
Upper Dis
Lower Dis
Upper Dis
Lower Dis
Upper Dis
Lower DisValue
Upper Dis
Lower Dis
The controand returnMode
Step Control.
Result
ay= INP (Thise)
splay=TYPE
ay= CON
splay= ALGC
splay= TPSC
splay= DB
splay=intended
splay= MTRT
splay=intended
splay= ACTN
splay=intended
oller exits Conns to the Norm
RevisJu
t
is the first Se
d Deadband V
d Motor Time
d Action Value
nfiguration Momal Operation
sion 2.0 ly 2015
et Up
Value
e
ode
ReJu
Co
Pr
PrSt
2
3
4
8
9
evision 2.0 uly 2015
onfiguring SThis se
reliminary S• The co• The us
rocedure tep
1 Enter S
2 Select Group
3 Select (SFST)’ Parame
4 ChangeValue
5 Select Functio
6 ChangeValue
7 Select Functio
8 ChangeValue
9 Exit Co
ED
Soft Start ection describ
Steps ontroller is in tser has the acc
Action
Set Up Mode
Control Set U
the ‘Soft StartFunction eter
e the Soft Sta
the Set Point on Parameter
e the Set Poin
the Period (PEon Parameter
e the Period
onfiguration
DC201 / EDC2
es the procedu
the Configuracess to set para
Long
Up
t
rt
(SP)
nt
ERI)
Long withoopera
202 / EDC203
ure of configu
ation Mode. ameters.
Press
press
or
or
or
press out any key ation more tha
3 Product Man
uring Soft Star
TopGro
Up
Top
Up
Up
Low
Up
Low
Up
Low
or
an 30s.
TheandMo
3.11. Co
ual
rt functon.
p Display= INPoup title)
per Display=T
p Display= CO
per Display= A
per Display= S
wer Display=in
per Display= S
wer Display=in
per Display= P
wer Display=in
e controller exd returns to thode.
3. Configuring Con
Result
P (This is the
TYPE
ON
ALGC
SFST
ntended Soft S
SP
ntended Set P
PERI
ntended Perio
xits Configurate Normal Ope
Configurationntrol Algorithm
49
first Set Up
Start Value
Point Value
od Value
tion Mode eration
n m
9
3. Config3.12. Con
50
3.12 Configu
Prelimin• •
ProceduStep
1
2 SGT
3 S
4 SAS
5 CA
6 S
V
7 CS
8 S
9 C
10 S
11 C
12 S
guration nfiguring Alarm
Configuuring PV AlaThis section d
nary Steps The controlleThe user has t
ure Action
Enter Set Up
Select ALARMGroup and AlaType FunctionParameter
Select the ‘PV
Select the ‘HigAlarm (SE11 ,SE21 or AM22)Function Para
Change the ‘HAlarm’ Value
Select the ‘AlaPoint (VL11, VLVL21, or VL22)
Change the ‘ASet Point’ Val
Select the ‘AlaHysteresis (HYFunction Para
Change the ‘AHysteresis’ Va
Select the ‘AlaDelay (DLYA)’ Parameter
Change the ‘ADelay’ Value
Select the ‘AlaLatch (LACH)’ FParameter
m
EDC201
ring Alararm describes the p
r is in the Conthe access to s
n
Mode L
M Set Up arm n
V (PV)’
gh/Low SE12,
)’ ameter
High/Low
arm Set L12, ’
Alarm ue
arm YSA)’ ameter
Alarm alue
arm Function
Alarm
arm Function
/ EDC202 / ED
rm
procedure of c
nfiguration Mset parameters
Pres
Long press
>
or
or
or
or
or
DC203 Produc
configuring PV
Mode. s.
ss
ct Manual
V Alarm.
Top DisplaGroup title
Upper Dis
Top Displa
Upper DisAL22
Lower Dis
Upper DisAM22
Lower Dis
Upper Dis
Lower DisValue
Upper Dis
Lower DisHysteresis
Upper Dis
Lower DisValue
Upper Dis
Result
ay= INP (Thise)
splay=TYPE
ay= ALM
splay= AL11 ,
splay=PV
splay= SE11 ,
splay=L0 or H1
splay= VL11, VL
splay=intended
splay= HYSA
splay=intendeds Value
splay= DLYA
splay=intended
splay= LACH
RevisJu
t
is the first Se
AL12, AL21 o
SE12, SE21 o
1
L12, VL21, or V
d Alarm Set P
d Alarm
d Alarm Delay
sion 2.0 ly 2015
et Up
or
or
VL22
Point
y
ReJu
St
1
1
Co
Pr
PrSt
evision 2.0 uly 2015
tep
13 ChangeLatch’ V
14 Exit Co
onfiguring DThis se
reliminary S• The co• The us
rocedure tep
1 Enter S
2 Select Group Functio
3 Select
DEV (D
4 Select Alarm SE21 oParam
5 ChangAlarm V
6 Select Point (Vor VL22
7 ChangPoint V
8 Select (AM11 oParamAM12)
9 ChangValue
ED
Action
e the ‘Alarm Value
onfiguration
Deviation Alection describ
Steps ontroller is in tser has the acc
Action
Set Up Mode
ALARM Set Uand Alarm Ty
on Parameter
the DEV (DEV
DEV)
the High/Low (SE11 , SE12,
or AM22) Functeter
e the High/LowValue
the Alarm SetVL11, VL12, VL2)
e the Alarm SValue
the Alarm Staor AM12) Funceter (AM11 or
e the Alarm S
DC201 / EDC2
Long prwithout more th
larm es the procedu
the Configuracess to set para
Long
Up ype
)
,
tion
w
t L21,
Set
ate ction
State
202 / EDC203
Press
or
ress any key operaan 30s.
ure of configu
ation Mode. ameters.
Press
g press
>
or
or
or
or
3 Product Man
LowVa
or ation
TheandMo
uring Deviatio
ToU
U
To
U
Lo
UAM
Lo
U
LoVa
U
LoAl
ual
wer Display=inlue
e controller exd returns to thode.
on Alarm.
op Display= INp Group title)
pper Display=
op Display= A
pper Display=
ower Display=
pper Display=M22
ower Display=
pper Display=
ower Display=alue
pper Display=
ower Display=larm Value
3. C3.12. Con
Result
ntended Alarm
xits Configurate Normal Ope
Result
NP (This is the
=TYPE
ALM
= AL11 or AL12
= DEV
= SE11 , SE12,
=L0 or H1
= VL11, VL12, V
=intended Alar
= AM11 or AM12
=intended High
Configurationfiguring Alarm
51
m Latch
tion Mode eration
e first Set
2
, SE21 or
VL21, or VL22
rm Set Point
2
h or Low
n m
1
3. Config3.12. Con
52
Step
10
11
12
13
14
15
16
guration nfiguring Alarm
Actio
Select the AlaHysteresis (HYFunction Para
Change the AHysteresis Va
Select the Ala(DLYA) FunctioParameter
Change the AValue
Select the Ala(LACH) FunctioParameter
Change the AValue
Exit Configura
m
EDC201
on
arm YSA) ameter
Alarm alue
arm Delay on
Alarm Delay
arm Latch on
Alarm Latch
ation
/ EDC202 / ED
Pr
o
o
o
Long presswithout anymore than 3
DC203 Produc
ress
or
or
or
s or y key operatio30s.
ct Manual
Upper Di
Lower DiHysteres
Upper Di
Lower DiValue
Upper Di
Lower DiValue
n The contand returMode.
Resul
isplay= HYSA
isplay=intendesis Value
isplay= DLYA
isplay=intende
isplay= LACH
isplay=intende
troller exits Corns to the Norm
RevisJu
lt
ed Alarm
ed Alarm Dela
ed Alarm Latc
onfiguration Mmal Operation
sion 2.0 ly 2015
ay
h
ode n
ReJu
Co
Pr
PrSt
1
1
1
1
evision 2.0 uly 2015
onfiguring OThis se
reliminary S• The co• The us
rocedure tep
1 Enter S
2 Select Group Type’ FParam
3 Select (OUT)’
4 Select Alarm SE21 oFunctio
5 ChangAlarm’
6 Select (AM11 oFunctio
7 ChangState’ V
8 Select HystereFunctio
9 ChangHystere
10 Select (DLYA)’ Param
11 ChangDelay’
12 Select (LACH)’ Param
13 ChangLatch’
ED
Output Alarmection describ
Steps ontroller is in tser has the acc
Action
Set Up Mode
ALARM Set Uand ‘Alarm
Function eter
the ‘Output
the ‘High/Low(SE11 , SE12,
or AM22)’ on Parameter
e the ‘High/LoValue
the ‘Alarm Staor AM12)’ on Parameter
e the ‘Alarm Value
the ‘Alarm esis (HYSA)’ on Parameter
e the ‘Alarm esis’ Value
the ‘Alarm DeFunction eter
e the ‘Alarm Value
the ‘Alarm LaFunction eter
e the ‘Alarm Value
DC201 / EDC2
m es the procedu
the Configuracess to set para
Long p
Up
w ,
ow
ate
elay
tch
202 / EDC203
ure of configu
ation Mode. ameters.
Press
press
>
or
or
or
or
or
or
3 Product Man
uring Output A
ToU
U
To
U
Lo
UAM
Lo
U
LoAl
U
LoHy
U
LoVa
U
LoVa
ual
Alarm.
op Display= INp Group title)
pper Display=
op Display= A
pper Display=
ower Display=
pper Display=M22
ower Display=
pper Display=
ower Display=larm Value
pper Display=
ower Display=ysteresis Valu
pper Display=
ower Display=alue
pper Display=
ower Display=alue
3. C3.12. Con
Result
NP (This is the
=TYPE
ALM
= AL11 or AL12
= OUT
= SE11 , SE12,
=L0 or H1
= AM11 or AM12
=intended High
= HYSA
=intended Alarue
= DLYA
=intended Alar
= LACH
=intended Alar
Configurationfiguring Alarm
53
e first Set
2
, SE21 or
2
h or Low
rm
rm Delay
rm Latch
n m
3
3. Config3.12. Con
54
Step
14
guration nfiguring Alarm
Actio
Exit Configura
m
EDC201
n
ation
/ EDC202 / ED
Pre
Long press without any kmore than 30
DC203 Produc
ess
or ey operation s.
ct Manual
The contand returMode.
Resul
troller exits Corns to the Norm
RevisJu
lt
onfiguration Mmal Operation
sion 2.0 ly 2015
ode n
ReJu
Co
Pr
PrSt
2
3
4
5
6
7
8
evision 2.0 uly 2015
onfiguring MThis se
reliminary S• The co• The us
rocedure tep
1 Enter S
2 Select Group Functio
3 Select (MAN)’
4 Select (DLYA)’ Parame
5 ChangeDelay’
6 Select (LACH)’ Parame
7 ChangeLatch’ V
8 Exit Co
ED
Manual Modection describ
Steps ontroller is in tser has the acc
Action
Set Up Mode
ALARM Set Uand ‘Alarm Ty
on Parameter
the ‘Manual M
the ‘Alarm DeFunction eter
e the ‘Alarm Value
the ‘Alarm LatFunction eter
e the ‘Alarm Value
onfiguration
DC201 / EDC2
de Alarm es the procedu
the Configuracess to set para
Long
Up ype’
Mode
elay
tch
Long withomore
202 / EDC203
ure of configu
ation Mode. ameters.
Press
press
or
or
or
press ut any key opthan 30s.
3 Product Man
uring Manual
TopGro
Up
Top
Up
Low
Up
LowVa
Up
LowVa
or eration
TheandMo
ual
Mode Alarm.
p Display= INPoup title)
per Display=T
p Display= AL
per Display= A
wer Display=
per Display= D
wer Display=inlue
per Display= L
wer Display=inlue
e controller exd returns to thode
3. C3.12. Con
Result
P (This is the
TYPE
LM
AL11 or AL12
MAN
DLYA
ntended Alarm
LACH
ntended Alarm
xits Configurate Normal Ope
Configurationfiguring Alarm
55
first Set Up
m Delay
m Latch
tion Mode eration
n m
5
3. Config3.12. Con
56
Configu
Prelimin• •
ProceduStep
1
2
3
4
5
6
7
8
9
10
11
12
guration nfiguring Alarm
uring PV RatThis section d
nary Steps The controlleThe user has t
ure Actio
Enter Set Up
Select ALARMGroup and ‘AlFunction Para
Select the ‘PV(PVRT)’
Select the ‘Ala(AM11 or AM12Parameter
Change the ‘AState’ Value
Select the ‘AlaHysteresis (HYFunction Para
Change the ‘AHysteresis’ Va
Select the ‘Ala(DLYA)’ FunctioParameter
Change the ‘ADelay’ Value
Select the ‘Ala(LACH)’ FunctioParameter
Change the ‘ALatch’ Value
Exit Configura
m
EDC201
te of Changdescribes the p
r is in the Conthe access to s
on
Mode
M Set Up larm Type’ ameter
V Rate
arm State 2)’ Function
Alarm
arm YSA)’ ameter
Alarm alue
arm Delay on
Alarm
arm Latch on
Alarm
ation
/ EDC202 / ED
e Alarm procedure of c
nfiguration Mset parameters
Pr
Long press
or
or
or
or
or
Long press without any more than 3
DC203 Produc
configuring PV
Mode. s.
ress
r
r
r
r
r
or key operation0s.
ct Manual
V Rate of Cha
Top DisUp Grou
Upper D
Top Dis
Upper D
Lower D
Upper D
Lower DAlarm V
Upper D
Lower DHystere
Upper D
Lower DValue
Upper D
Lower DValue
The conand retuMode.
ange Alarm.
Resu
splay= INP (Thup title)
Display=TYPE
splay= ALM
Display= AL11
Display= PVRT
Display= AM11
Display=intendValue
Display= HYSA
Display=intendesis Value
Display= DLYA
Display=intend
Display= LACH
Display=intend
ntroller exits Curns to the No
RevisJu
ult
his is the first S
or AL12
or AM12
ded High or Lo
ded Alarm
ded Alarm Del
ded Alarm Lat
Configuration Mormal Operatio
sion 2.0 ly 2015
Set
ow
lay
ch
Mode on
ReJu
Co
Pr
PrSt
1
1
1
evision 2.0 uly 2015
onfiguring DThis se
reliminary S• The co• The us
rocedure tep
1 Enter S
2 Select Group Functio
3 Select (DIG)’
4 Select (AM11 oParam
5 ChangState’ V
6 Select HystereFunctio
7 ChangHystere
8 Select (DLYA)’ Param
9 ChangDelay’
10 Select (LACH)’ Param
11 ChangLatch’
12 Exit Co
ED
Digital Inputection describ
Steps ontroller is in tser has the acc
Action
Set Up Mode
ALARM Set Uand ‘Alarm Ty
on Parameter
the ‘Digital Inp
the ‘Alarm Staor AM12)’ Funceter
e the ‘Alarm Value
the ‘Alarm esis (HYSA)’ on Parameter
e the ‘Alarm esis’ Value
the ‘Alarm DeFunction eter
e the ‘Alarm Value
the ‘Alarm LaFunction eter
e the ‘Alarm Value
onfiguration
DC201 / EDC2
t Alarm es the procedu
the Configuracess to set para
Long
Up ype’
put
ate ction
elay
atch
Long withomore
202 / EDC203
ure of configu
ation Mode. ameters.
Press
press
or
or
or
or
or
press ut any key opthan 30s.
3 Product Man
uring Digital I
ToU
U
To
U
Lo
U
LoAl
U
LoHy
U
LoVa
U
LoVa
or eration
ThanM
ual
Input Alarm.
op Display= INp Group title)
pper Display=
op Display= A
pper Display=
ower Display=
pper Display=
ower Display=larm Value
pper Display=
ower Display=ysteresis Valu
pper Display=
ower Display=alue
pper Display=
ower Display=alue
he controller end returns to tode.
3. C3.12. Con
Result
NP (This is the
=TYPE
ALM
= AL11 or AL12
= PVRT
= AM11 or AM12
=intended High
= HYSA
=intended Alarue
= DLYA
=intended Alar
= LACH
=intended Alar
exits Configurahe Normal Op
Configurationfiguring Alarm
57
e first Set
2
2
h or Low
rm
rm Delay
rm Latch
ation Mode peration
n m
7
3. Config3.12. Con
58
Configu
Prelimin• •
ProceduStep
1
2
3
4
5 V
6
7 V
8
guration nfiguring Alarm
uring TC WaThis section d
nary Steps The controlleThe user has t
ure Actio
Enter Set Up
Select ALARMGroup and AlaFunction Para
Select the TC(TCWN)
Select the Ala(DLYA) FunctioParameter
Change the AValue
Select the Ala(LACH) FunctioParameter
Change the AValue
Exit Configura
m
EDC201
arning Alarmdescribes the p
r is in the Conthe access to s
on
Mode
M Set Up arm Type ameter
C Warning
arm Delay on
Alarm Delay
arm Latch on
Alarm Latch
ation
/ EDC202 / ED
m procedure of c
nfiguration Mset parameters
P
Long press
o
o
o
Long press without any more than 3
DC203 Produc
configuring TC
Mode. s.
Press
r
r
r
or key operation
30s.
ct Manual
C Warning Al
Top DiUp Gro
Upper
Top Di
Upper
Lower
Upper
Lower Value
Upper
Lower Value
n The coMode aOperat
larm.
Resu
isplay= INP (Toup title)
Display=TYPE
isplay= ALM
Display= AL1
Display= TCW
Display= DLYA
Display=inten
Display= LACH
Display=inten
ontroller exits Cand returns totion Mode.
RevisJu
ult
This is the first
E
1 or AL12
WN
A
nded Alarm De
H
nded Alarm La
Configuration o the Normal
sion 2.0 ly 2015
t Set
elay
atch
ReJu
Co
Pr
PrSt
2
3
4
8
evision 2.0 uly 2015
onfiguring TThis se
reliminary S• The co• The us
rocedure tep
1 Enter S
2 Select Group Functio
3 Select (TCFL)’
4 Select (DLYA)’ Parame
5 ChangeDelay’
6 Select (LACH)’ Parame
7 ChangeLatch’ V
8 Exit Co
ED
TC Failing Aection describ
Steps ontroller is in tser has the acc
Action
Set Up Mode
ALARM Set Uand ‘Alarm Ty
on Parameter
the ‘TC Fail
the ‘Alarm DeFunction eter
e the ‘Alarm Value
the ‘Alarm LatFunction eter
e the ‘Alarm Value
onfiguration
DC201 / EDC2
Alarm es the procedu
the Configuracess to set para
Long
Up ype’
elay
tch
Long withoopera
202 / EDC203
ure of configu
ation Mode. ameters.
Press
press
or
or
or
press out any key ation more tha
3 Product Man
uring TC Fail
TopGro
Up
Top
Up
Low
Up
LowVa
Up
LowVa
or
an 30s.
TheandMo
ual
Alarm.
p Display= INPoup title)
per Display=T
p Display= AL
per Display= A
wer Display=
per Display= D
wer Display=inlue
per Display= L
wer Display=inlue
e controller exd returns to thode
3. C3.12. Con
Result
P (This is the
TYPE
LM
AL11 or AL12
TCFL
DLYA
ntended Alarm
LACH
ntended Alarm
xits Configurate Normal Ope
Configurationfiguring Alarm
59
first Set Up
m Delay
m Latch
tion Mode eration
n m
9
3. Config3.12. Con
60
Configu
Prelimin• •
ProceduStep
1 E
2 SGF
3 S
4 S(P
5 CD
6 S(P
7 CL
8 E
guration nfiguring Alarm
uring FailsafThis section d
nary Steps The controlleThe user has t
ure Actio
Enter Set Up M
Select ALARMGroup and ‘AlFunction Para
Select the ‘Fa
Select the ‘Ala(DLYA)’ FunctioParameter
Change the ‘ADelay’ Value
Select the ‘Ala(LACH)’ FunctioParameter
Change the ‘ALatch’ Value
Exit Configura
m
EDC201
fe Alarm describes the p
r is in the Conthe access to s
n
Mode
M Set Up arm Type’
ameter
ilsafe (FS)’
arm Delay on
Alarm
arm Latch on
Alarm
ation
/ EDC202 / ED
procedure of c
nfiguration Mset parameters
Pres
Long press
or
or
or
Long press without any koperation mo
DC203 Produc
configuring Fa
Mode. s.
ss
or key re than 30s.
ct Manual
ailsafe Alarm.
Top DisplayGroup title)
Upper Disp
Top Display
Upper Disp
Lower Disp
Upper Disp
Lower DispValue
Upper Disp
Lower Disp
The controland returns
.
Result
y= INP (This is
lay=TYPE
y= ALM
lay= AL11 or
lay= FS
lay= DLYA
lay=intended A
lay= LACH
lay=intended A
ler exits Confi to the Norma
RevisJu
s the first Set
AL12
Alarm Delay
Alarm Latch V
guration Modeal Operation M
sion 2.0 ly 2015
Up
Value
e Mode.
ReJu
Co
Pr
PrSt
2
3
4
8
evision 2.0 uly 2015
onfiguring DThis se
reliminary S• The co• The us
rocedure tep
1 Enter S
2 Select Group Functio
3 Select (DIAG)’
4 Select (DLYA)’ Parame
5 ChangeDelay’
6 Select (LACH)’ Parame
7 ChangeLatch’ V
8 Exit Co
ED
Diagnostic Aection describ
Steps ontroller is in tser has the acc
Action
Set Up Mode
ALARM Set Uand Alarm Ty
on Parameter
the ‘Diagnosti
the ‘Alarm DeFunction eter
e the ‘Alarm Value
the ‘Alarm LatFunction eter
e the ‘Alarm Value
onfiguration
DC201 / EDC2
Alarm es the procedu
the Configuracess to set para
Long
Up ype
ic
elay
tch
Long withoopera
202 / EDC203
ure of configu
ation Mode. ameters.
Press
press
or
or
or
press out any key ation more tha
3 Product Man
uring Diagnos
TopGro
Up
Top
Up
Low
Up
LowVa
Up
LowVa
or
an 30s.
TheandMo
ual
stic Alarm.
p Display= INPoup title)
per Display=T
p Display= AL
per Display= A
wer Display=
per Display= D
wer Display=inlue
per Display= L
wer Display=inlue
e controller exd returns to thode.
3. C3.12. Con
Result
P (This is the
TYPE
LM
AL11 or AL12
DIAG
DLYA
ntended Alarm
LACH
ntended Alarm
xits Configurate Normal Ope
Configurationfiguring Alarm
61
first Set Up
m Delay
m Latch
tion Mode eration
n m
1
3. Config3.12. Con
62
Assign
Prelimin• • •
ProceduStep
1 E
2 SGF
3 S
4 SHF
5 CH
6 E
guration nfiguring Alarm
Alarm HysteThis section d
nary Steps The controlleThe user has tAlarm Type s
ure Actio
Enter Set Up M
Select ALARMGroup and ‘AlFunction Para
Select the ‘Ala
Select the ‘AlaHysteresis (HYFunction Para
Change the ‘AHysteresis’ Va
Exit Configura
m
EDC201
eresis describes the p
r is in the Conthe access to sselected suppo
n
Mode
M Set Up arm Type’
ameter
arm Type’
arm YSA)’ ameter
Alarm alue
ation
/ EDC202 / ED
procedure of c
nfiguration Mset parametersort hysteresis a
Pres
Long press
or
or
Long press without any koperation mo
DC203 Produc
configuring A
Mode. s. assignment.
ss
or key re than 30s.
ct Manual
Alarm Hysteres
Top DisplayGroup title)
Upper Disp
Top Display
Upper Disp
Lower DispValue
Upper Disp
Lower DispValue
The controland returns
sis.
Result
y= INP (This is
lay=TYPE
y= ALM
lay= AL11 or
lay= intended
lay= HYSA
lay=intended A
ler exits Confi to the Norma
RevisJu
s the first Set
AL12
d Alarm Type
Alarm Hystere
guration Modeal Operation M
sion 2.0 ly 2015
Up
esis
e Mode.
ReJu
Co
Pr
Pr
St
2
3
4
evision 2.0 uly 2015
onfiguring AThis se
reliminary S• The co• The us
rocedure
tep
1 Enter S
2 Select Group Type’ FParame
3 Select (DLYA)’ Parame
4 ChangeDelay’
5 Exit Co
ED
Alarm Delayection describ
Steps ontroller is in tser has the acc
Action
Set Up Mode
ALARM Set Uand ‘Alarm
Function eter
the ‘Alarm DeFunction eter
e the ‘Alarm Value
onfiguration
DC201 / EDC2
y es the procedu
the Configuracess to set para
Long p
Up
elay
Long pwithoumore t
202 / EDC203
ure of configu
ation Mode. ameters.
Press
press
or
press t any key opehan 30s.
3 Product Man
uring Alarm D
Top Grou
Upp
Top
Upp
Upp
LowValu
or ration
The and Mod
ual
Delay.
Display= INPup title)
per Display=TY
Display= ALM
per Display= AL
per Display= DL
wer Display=intue
controller exitreturns to the
de.
3. C3.12. Con
Result
P (This is the fi
YPE
M
L11 or AL12
LYA
tended Alarm
ts Configuratioe Normal Oper
Configurationfiguring Alarm
63
rst Set Up
Delay
on Mode ration
n m
3
3. Config3.12. Con
64
Configu
Prelimin• •
ProceduStep
1
2 SG
3 S(
4 C
5
Configu
Prelimin• •
ProceduStep
1
2 SGT
3 S
guration nfiguring Alarm
uring Alarm This section d
nary Steps The controlleThe user has t
ure Actio
Enter Set Up
Select ALARMGroup and ‘AlFunction Para
Select the ‘Ala(LACH)’ FunctioParameter
Change the ‘ALatch’ Value
Exit Configura
uring Alarm This section d
nary Steps The controlleThe user has t
ure Action
Enter Set Up
Select ALARMGroup and ‘AlType’ FunctioParameter
Select the ‘AlaBlocking (BLK)Function Para
m
EDC201
Latching describes the p
r is in the Conthe access to s
on
Mode
M Set Up arm Type’
ameter
arm Latch on
Alarm
ation
Blocking describes the p
r is in the Conthe access to s
n
Mode L
M Set Up arm n
arm )’ ameter
/ EDC202 / ED
procedure of c
nfiguration Mset parameters
Pre
Long press
or
Long press without any operation m
procedure of c
nfiguration Mset parameters
Pres
Long press
DC203 Produc
configuring A
Mode. s.
ess
r
or key ore than 30s.
configuring A
Mode. s.
ss
ct Manual
Alarm Latching
Top DisplaGroup title
Upper Dis
Top Displa
Upper Dis
Upper Dis
Lower DisValue
The controand returnMode
Alarm Blocking
Top DisplayGroup title)
Upper Disp
Top Display
Upper Disp
Upper Disp
g.
Result
ay= INP (Thise)
splay=TYPE
ay= ALM
splay= AL11 or
splay= LACH
splay=intended
oller exits Conns to the Norm
g.
Result
y= INP (This i)
play=TYPE
y= ALM
play= AL11 or
play= BLK
RevisJu
t
is the first Se
r AL12
d Alarm Latch
nfiguration Momal Operation
t
s the first Set
AL12
sion 2.0 ly 2015
et Up
ode
Up
ReJu
St
4
Co
Pr
PrSt
2
3
4
evision 2.0 uly 2015
tep
4 ChangeBlockin
5 Exit Co
onfiguring TThis se
reliminary S• The co• The us
rocedure tep
1 Enter S
2 Select Group Functio
3 Select Functio
4 Select (EABL)’ Parame
5 Select Functio
6 ChangeValue
7 Exit Co
ED
Action
e the ‘Alarm ng’ Value
onfiguration
Timer ection describ
Steps ontroller is in tser has the acc
Action
Set Up Mode
ALARM Set Uand ‘Alarm Ty
on Parameter
the ‘Timer (TMon Parameter
the ‘ENABLE Function eter
the ‘Period (peon Parameter
e the ‘Period’
onfiguration
DC201 / EDC2
Long prwithout more th
es the procedu
the Configuracess to set para
Long
Up ype’
MR)’
eri)’
Long withomore
202 / EDC203
Press
or
ress any key operaan 30s.
ure of configu
ation Mode. ameters.
Press
press
or
press out any key ope than 30s.
3 Product Man
LowValu
or ation
The and Mod
uring Timer.
TU
U
T
U
U
L
U
LV
or peration
TaM
ual
wer Display=intue
controller exitreturns to the
de.
Top Display= IUp Group title)
Upper Display
Top Display= A
Upper Display
Upper Display
Lower Display
Upper Display
Lower DisplayValue
The controller and returns to Mode
3. C3.12. Con
Result
tended Alarm
ts Configuratioe Normal Oper
Result
INP (This is th)
y=TYPE
ALM
y= AL11 or AL
y= TMR
y= EABL
y= peri
y=intended Tim
exits Configuthe Normal O
Configurationfiguring Alarm
65
Blocking
on Mode ration
he first Set
12
mer Period
ration Mode Operation
n m
5
3. Config3.13. Con
66
3.13 Disable
Prelimin• •
ProceduStep
1
2 SG
3 S
4
guration nfiguring Digit
Configu DI FunctionThis section d
nary Steps The controlleThe user has t
ure Actio
Enter Set Up
Select AUX SGroup and ‘DiInput(DIG)’ FuParameter
Select NONE(
Exit Configura
al Input
EDC201
ring Digin describes the p
r is in the Conthe access to s
n
Mode
et Up igital nction
(NONE)
ation
/ EDC202 / ED
ital Input
procedure of d
nfiguration Mset parameters
Pre
Long press
or
Long press without any kmore than 30
DC203 Produc
t
disabling DI fu
Mode. s.
ess
or ey operation s.
ct Manual
function.
Top DisplaGroup title
Upper Dis
Top Displa
Upper Dis
Lower Dis
The controand returnMode.
Result
ay= INP (Thise)
splay=TYPE
ay= AUX
splay= DIG
splay=NONE
oller exits Conns to the Norm
RevisJu
t
is the first Se
nfiguration Momal Operation
sion 2.0 ly 2015
et Up
ode
ReJu
Co
Pr
PrSt
2
3
4
Co
Pr
PrSt
2
3
4
evision 2.0 uly 2015
onfiguring DThis se
reliminary S• The co• The us
rocedure tep
1 Enter S
2 Select Group Input(DParame
3 Select
4 Exit Co
onfiguring DThis se
reliminary S• The co• The us
rocedure tep
1 Enter S
2 Select Group Input(DParame
3 Select
4 Exit Co
ED
DI as Controection describ
Steps ontroller is in tser has the acc
Action
Set Up Mode
AUX Set Up and ‘Digital
DIG)’ Function eter
Auto/MAN (AM
onfiguration
DI as Controection describ
Steps ontroller is in tser has the acc
Action
Set Up Mode
AUX Set Up and ‘Digital
DIG)’ Function eter
Direction (DIR
onfiguration
DC201 / EDC2
ol Mode Swies the procedu
the Configuracess to set para
Long pr
M)
Long prwithout more th
ol Direction es the procedu
the Configuracess to set para
Long
R)
Long withoopera
202 / EDC203
itch ure of configu
ation Mode. ameters.
Press
ress
or
ress any key operaan 30s.
Switch ure of configu
ation Mode. ameters.
Press
press
or
press out any key ation more tha
3 Product Man
uring DI as Co
Top Grou
Upp
Top
Upp
Low
or ation
The and Mod
uring DI as Co
TopGro
Up
Top
Up
Low
or
an 30s.
TheandMo
3.1
ual
ontrol Mode S
Display= INPup title)
per Display=TY
Display= AUX
per Display= DI
wer Display= A
controller exitreturns to the
de.
ontrol Directio
p Display= INPoup title)
per Display=T
p Display= AU
per Display= D
wer Display=
e controller exd returns to thode.
3. C13. Configurin
Switch.
Result
P (This is the fi
YPE
X
IG
AM
ts Configuratioe Normal Oper
on Switch.
Result
P (This is the
TYPE
UX
DIG
DIR
xits Configurate Normal Ope
Configurationng Digital Input
67
rst Set Up
on Mode ration
first Set Up
tion Mode eration
n t
7
3. Config3.13. Con
68
Configu
Prelimin• •
ProceduStep
1
2 SG
3 S
4
Configu
Prelimin• •
ProceduStep
1
2 SG
3 S
4
guration nfiguring Digit
uring DI as KThis section d
nary Steps The controlleThe user has t
ure Actio
Enter Set Up
Select AUX SGroup and ‘DiInput(DIG)’ FuParameter
Select LOCK
Exit Configura
uring DI as TThis section d
nary Steps The controlleThe user has t
ure Action
Enter Set Up
Select AUX SGroup and ‘DiInput(DIG)’ FuParameter
Select Timer (
Exit Configura
al Input
EDC201
Keypad Locdescribes the p
r is in the Conthe access to s
n
Mode
et Up igital nction
(LOCK)
ation
Timer Initiatdescribes the p
r is in the Conthe access to s
Mode Lo
et Up igital nction
(TMR)
ation Lowimo
/ EDC202 / ED
king Switchprocedure of c
nfiguration Mset parameters
Pres
Long press
or
Long press without any kmore than 30
ing Triggerprocedure of c
nfiguration Mset parameters
Press
ong press
or
ong press thout any keyore than 30s.
DC203 Produc
h DI configuring D
Mode. s.
ss
or ey operation s.
configuring D
Mode. s.
or y operation
ct Manual
DI as Keypad L
Top DisplayGroup title)
Upper Disp
Top Display
Upper Disp
Lower Disp
The controand returnsMode.
DI as Timer Ini
Top Display= Group title)
Upper Display
Top Display=
Upper Display
Lower Display
The controllerreturns to the
Locking Switc
Result
y= INP (This i)
play=TYPE
y= AUX
play= DIG
play= LOCK
ller exits Confs to the Norma
itiating Trigge
Result
INP (This is t
y=TYPE
AUX
y= DIG
y= TMR
r exits Configu Normal Oper
RevisJu
ch.
t
s the first Set
figuration Modal Operation
er.
the first Set Up
uration Mode aration Mode
sion 2.0 ly 2015
Up
de
p
and
ReJu
Co
Pr
PrSt
2
3
4
evision 2.0 uly 2015
onfiguring DThis se
reliminary S• The co• The us
rocedure tep
1 Enter S
2 Select Group Input(DParame
3 Select
4 Exit Co
ED
DI as Alarm ection describ
Steps ontroller is in tser has the acc
Action
Set Up Mode
AUX Set Up and Digital
DIG) Function eter
ACK (ACK)
onfiguration
DC201 / EDC2
Acknowledes the procedu
the Configuracess to set para
Long
Long withomore
202 / EDC203
ging Switchure of configu
ation Mode. ameters.
Press
press
or
press out any key ope than 30s.
3 Product Man
h uring DI as Al
ToU
U
To
U
Lo
or peration
ThanM
3.1
ual
larm Acknowl
op Display= INp Group title)
pper Display=
op Display= A
pper Display=
ower Display=
he controller end returns to tode.
3. C13. Configurin
ledging.
Result
NP (This is the
=TYPE
AUX
= DIG
=ACK
exits Configurahe Normal Op
Configurationng Digital Input
69
e first Set
ation Mode peration
n t
9
3. Config3.13. Con
70
Configu
Prelimin• •
ProceduStep
1
2 SG
3 S
4
guration nfiguring Digit
uring DI as AThis section d
nary Steps The controlleThe user has t
ure Actio
Enter Set Up
Select AUX SGroup and ‘DiInput(DIG)’ FuParameter
Select AT (AT)
Exit Configura
al Input
EDC201
Auto Tuningdescribes the p
r is in the Conthe access to s
on
Mode
et Up igital nction
)
ation
/ EDC202 / ED
g Initiating Tprocedure of c
nfiguration Mset parameters
Pres
Long press
or
Long press or without anoperation m30s.
DC203 Produc
Trigger configuring D
Mode. s.
ss
r
ny key ore than
ct Manual
DI as AT Initia
Top DisplayGroup title)
Upper Displa
Top Display
Upper Displa
Lower Displa
The controllereturns to th
ating Trigger.
Result
= INP (This is
ay=TYPE
= AUX
ay= DIG
ay=AT
er exits Confige Normal Ope
RevisJu
the first Set U
guration Modeeration Mode.
sion 2.0 ly 2015
Up
e and
ReJu
4
4
evision 2.0 uly 2015
4
.1 OThis seincludiparame
.2 OFigure
ED
4. Moni
Overviewection gives ying an Operateter configura
Operator 4-1 and Figu
DC201 / EDC2
itoring a
w ou all the infoor Interface ov
ation mode, se
Interfaceure 4-2 provide
Figure 4-1
202 / EDC203
and Ope
ormation neceverview, how
etting the time
e e the view of t
: Operator I
3 Product Man
erating
ssary to help yw to switch beter and monitor
the Operator I
Interface (ED
ual
the Co
you monitor atween normal ring the displa
Interfaces.
DC201, EDC
ntroller
and operate yooperation mo
ays.
C202)
71
r
our controllerde and
1
4. Monito4.3. Mon
72
4.3 Annunc
oring and Opeitoring Your C
Monitciators The following
Annu
ALM1 2 3 4
OUT1 2
MAN
AT
[None], F o
erating the CoController
EDC201
toring Yo
g annunciator
nciator
4
or C
ontroller
/ EDC202 / ED
Figure 4-2
our Cont
functions hav
A visual in
A visual in
On: ManuOff: Autom
Accutunin
A visual in[None]—NF—DegreC—Degre
DC203 Produc
Operator In
troller
ve been provid
ndication of ea
ndication of the
al Mode matic Mode
g in progress
ndication of theNo temperatures Fahrenheit
ees Celsius
ct Manual
terface (EDC
ded to help mo
Indication
ach alarm
e control relay
e temperaturee unit annunct
C203)
onitor the con
ys
e units ciator
RevisJu
ntroller:
sion 2.0 ly 2015
4. Monitoring and Operating the Controller 4.3. Monitoring Your Controller
Revision 2.0 EDC201 / EDC202 / EDC203 Product Manual 73 July 2015
Viewing the operating parameters Press the LOWER DISPLAY key to scroll through the operating parameters listed in Table 4-1 Lower Display Key Parameter Prompts. The lower display will show only those parameters and their values that apply to your specific model.
Lower Display
7-Segment Code
Description
Tx.xx .Tx xx Time that remains on timer in Hours.Minutes.
Mxxx Mxxx Output value is percent; for Three Position Step control, this is an estimated motor position and shown with no decimal place.
ASTR ASTR When AT is enabled and AT process is not operating
ASTP ASTP When AT is enabled and AT process is operating
ALM ALM Alarm is triggered and configured as Latch
Fail Fail Failsafe — conditions for failsafe are:
… EEROM Test Failed
… Scratch Pad RAM Test Failed
… Configuration Test Failed
… Field or Factory Cal Test Failed
Table 4-1 Lower Display Key Parameter Prompts
Diagnostic Messages The EDC 200 Series performs background tests to verify data and memory integrity. If there is a malfunction, a diagnostic message will be shown on the lower display. In the case of more than one simultaneous malfunction, only the highest priority diagnostic message will be displayed. Table 4-2: Diagnostic Messages shows the error messages in order of priority. If any of these diagnostic messages appear on the lower display, refer to Chapter 5 Troubleshooting/ Service for information on how to correct the problem.
Prompt Description
LOCK The lockout feature has been enabled to prevent unauthorized changes of certain functions or parameters.
EDxx Power on error
FCxx Configure and calibration check error
ECxx IO control error
Table 4-2: Diagnostic Messages
4. Monitoring and Operating the Controller 4.4. Controller Mode
74 EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
4.4 Controller Mode Operation Mode
Controller is typically running in two operation modes, normal operation mode and parameter configuration mode.
Mode Definitions
Operation Mode Definition
Normal Operation In normal operation mode, the controller displays the PV, SP/Output. In this mode you can process the following: • Start /Stop the Auto Tuning process, • Switch between Manual Mode and Auto Mode.
In Manual Mode, SP tracks PV. The operator directly controls the controller output level. In Auto Mode, you can adjust the Set Point.
• Operate the Timer • View and acknowledge Failsafe and Alarms.
Parameter Configuration In the configuration mode, the configurator configures the function parameters in authorized Set up Groups and enter “Mask” mode.
Control Mode
Mode Definitions
Control Mode Definition
AUTOMATIC with LOCAL SET POINT
In automatic local mode, the controller operates from the local Set Points and automatically adjusts the output to maintain the PV at the desired value. In this mode you can adjust the Set Point.
Manual In Manual mode, the operator directly controls the controller output level. The process variable and the percent output are displayed. The configured High and Low Output Limits are disregarded and the operator can change the output value, using the increment and decrement keys, to the limits allowed by the output type (0 % to 100 % for a time proportioning output or –5 % to 105 % for a current output).
ReJu
4
Pr
St
2
3
4
8
evision 2.0 uly 2015
.5 SThere or mod
rocedure
tep
1 Enter S
2 OPTEntlevel set
3
4 Set Opeconfigur
5
6 Switch t
7 Set the
8
ED
Setting Oare two operadify the operat
Action
Set up Mode
ter operation tting mode
eration level orator level
the digit
value
DC201 / EDC2
perationating levels fortion level usin
Long pr
r
202 / EDC203
n Level r parameters, ng the followin
Press
ress
or
4.
3 Product Man
configurator lng procedure.
Top D
Top D
Uppe
Lowe
Uppe
Lowe
Confi• If
n• If
to
Monitoring a4
ual
level and oper.
Display = OPT
Display = OPT
er Display= OP
er Display= OP
er Display =PA
er Display =00
irm the input vf the passwordormal operatinf you enter theo Step 4.
and Operating 4.5. Setting O
rator level.You
Result
T
T
LV
ER/CFG
SS
00
value. d is correct, reng mode.
e wrong passw
the Controllerperation Leve
75
u can set up
eturn to
word, return
r el
5
4. Monito4.6. Setti
76
4.6
ProceduStep
1 E
2 Ese
3
4 Sco
5
6 S
7 S
8
oring and Openg Operation
SettinChange to oppassword of o0000. The con
ure Action
Enter Set up M
Enter operationetting mode
Set Operation lonfigurator lev
Switch the digit
Set the value
erating the CoPassword
EDC201
ng Operaerator or confoperator and cnfigurator pas
n
Mode Lo
n level
level or vel
t
ontroller
/ EDC202 / ED
ation Pasfigurator levelconfigurator lessword can no
Pres
ong press
or
DC203 Produc
ssword l for authority evel. The passot be changed
ss
ct Manual
management sword of operabefore the ope
Top Display
Top Display
Upper Displa
Lower Displa
Upper Displa
Confirm the • If the pas
normal o• If you en
to Step 4
purpose or chator and confierator passwo
Result
= OPT
= OPT
ay= PASS
ay= OPER/CFG
ay= OPER/CFG
input value. ssword is corre
operating modeter the wrong
4.
RevisJu
hange the defaigurator are boord is changed
ect, return to e. password, ret
sion 2.0 ly 2015
ault oth
d.
turn
ReJu
4
Pr
PrSt
2
3
4
evision 2.0 uly 2015
.7 SThe paMask m
reliminary SThe co
rocedure tep
1 Enter S
2 Enter opsetting m
3 Enter M
4
5
6 Switch S
7 Set Ma
ED
Setting Paarameter settinmode can only
Steps ontroller is in p
Action
Set up Mode
peration level mode
Mask Mode.
Set up parame
ask Value
DC201 / EDC2
arameterng can be set ty be entered in
parameter con
Long p
eter
202 / EDC203
r Mask to allow accesn the configur
nfiguration mo
Press
press
or
or
or
4.
3 Product Man
ss or configuraration level wi
ode and the us
Top Dis
Top Dis
Upper D
Lower D
Enter S
Top Dis
Upper D
Lower DNote:Configucase, oparameDisplayConfiguparame
Monitoring a4
ual
ation by differithout a passw
ser has the acc
R
splay = OPT
splay = OPT
Display=OPLV
Display=MASK
Set up Mode
splay= current
Display=curre
Display=Param00: Hide the p
urable only forperator could
eter but could y the parameteurator level caeters.
and Operating 4.7. Setting Pa
rent operatingword.
cess to set the
Result
V
K
t Set up group
nt Set up para
meter Mask Vparameter; 10r configurator lview the valunot modify the
er and both Opn configure th
the Controllerarameter Mask
77
g levels.
parameters.
p
ameter
alue 0: level, in this e of the e value 11: perator and
he
r k
7
4. Monito4.8. Rese
78
4.8
Prelimin• •
ProceduStep
1
2 SG
3 S
4 ST
5
4.9
Prelimin• •
ProceduStep
1
2 SG
3 S
oring and Opeeting to Factor
ResetThis section d
nary Steps The controlleThe user has t
ure Actio
Enter Set Up
Select OPT SGroup
Select Status(Function Para
Select Reset tTest (TEST)
Exit Configura
Testing This section d
nary Steps The controlleThe user has t
ure Actio
Enter Set Up
Select OPT SGroup
Select Status(Function Para
erating the Cory Default
EDC201
ting to Fdescribes the p
r is in the Conthe access to s
on
Mode
et Up
(STA) ameter
to Display
ation
Display describes the p
r is in the Conthe access to s
on
Mode
et Up
(STA) ameter
ontroller
/ EDC202 / ED
actory Dprocedure of r
nfiguration Mset parameters
Pre
Long press
or
Long press without any operation m
procedure of r
nfiguration Mset parameters
Pre
Long press
DC203 Produc
Default resetting confi
Mode. s.
ess
r
or key ore than 30s.
resetting to Te
Mode. s.
ess
ct Manual
figuration to fa
Top DisplaGroup title
Upper Dis
Top Displa
Upper Dis
Upper Dis
Lower Dis
All the pardefault va
The controand returnMode.
esting Display
Top DisplaGroup title
Upper Dis
Top Displa
Upper Dis
Upper Dis
actory default
Result
ay= INP (Thise)
splay=TYPE
ay= OPT
splay= HZ
splay= STA
splay= TEST
rameters are rlue
oller exits Conns to the Norm
y.
Result
ay= INP (Thise)
splay=TYPE
ay= OPT
splay= HZ
splay= STA
RevisJu
settings.
t
is the first Se
reset to factory
nfiguration Momal Operation
t
is the first Se
sion 2.0 ly 2015
et Up
y
ode
et Up
ReJu
St
4
4
Pr
PrSt
2
3
4
evision 2.0 uly 2015
tep
4 Select Test (T
5 Exit Co
.10 SettThis se
reliminary S• The co• The us
rocedure tep
1 Enter S
2 Select Group
3 Select (HZ)
4 Exit Co
ED
Action
Reset to DispEST)
onfiguration
ting Powection describ
Steps ontroller is in tser has the acc
Action
Set Up Mode
OPT Set Up
Power Freque
onfiguration
DC201 / EDC2
play
Long withoopera
wer Freques the procedu
the Configuracess to set para
Long
ency
Long withoopera
202 / EDC203
Press
or
press out any key ation more tha
uency ure of setting
ation Mode. ameters.
Press
press
or
press out any key ation more tha
4.
3 Product Man
Low
All ind
or
an 30s.
TheandMo
Power Freque
TopGro
Up
Top
Up
LowFre
or
an 30s.
TheandMo
Monitoring a4.10
ual
wer Display=
the LEDs on ticate the LED
e controller exd returns to thode.
ency.
p Display= INPoup title)
per Display=T
p Display= OP
per Display= H
wer Display=equency Value
e controller exd returns to thode.
and Operating 0. Setting Pow
Result
TEST
the screen areD Status
xits Configurate Normal Ope
Result
P (This is the
TYPE
PT
HZ
Intended Powe
xits Configurate Normal Ope
the Controllerwer Frequency
79
e “on” to
tion Mode eration
first Set Up
wer
tion Mode eration
r y
9
4. Monito4.11. Set
80
4.11
Prelimin• •
ProceduStep
1
2 SG
3 S
4 S
5
4.12
Prelimin• •
ProceduStep
1 E
2 SG
3 SF
oring and Opetting Decimal P
SettinThis section d
nary Steps The controlleThe user has t
ure Actio
Enter Set Up
Select OPT SGroup
Select the DecPlace (DECI) FParameter
Select the DecPlace value
Exit Configura
ExamingThis section d
nary Steps The controlleThe user has t
ure Actio
Enter Set Up M
Select OPT SeGroup
Select Status(Function Para
erating the CoPoint Location
EDC201
ng Decimdescribes the p
r is in the Conthe access to s
on
Mode
et Up
cimal Function
cimal
ation
g Producdescribes the p
r is in the Conthe access to s
n
Mode
et Up
(STA) ameter
ontroller n
/ EDC202 / ED
mal Pointprocedure of s
nfiguration Mset parameters
Pre
Long press
or
Long press without any operation m
ct Informprocedure of e
nfiguration Mset parameters
Pres
Long press
DC203 Produc
t Locatiosetting Decim
Mode. s.
ess
r
or key ore than 30s.
mation examing the P
Mode. s.
ss
ct Manual
on mal Point Locat
Top DisplaGroup title
Upper Dis
Top Displa
Upper Dis
Upper Dis
Lower DisValue
The controand returnMode.
Product Inform
Top DisplayGroup title)
Upper Disp
Top Display
Upper Disp
Upper Disp
tion.
Result
ay= INP (Thise)
splay=TYPE
ay= OPT
splay= HZ
splay= DECI
splay= Intende
oller exits Conns to the Norm
mation.
Result
y= INP (This is
lay=TYPE
y= OPT
lay= HZ
lay= STA
RevisJu
t
is the first Se
ed Decimal Pl
nfiguration Momal Operation
s the first Set
sion 2.0 ly 2015
et Up
ace
ode
Up
ReJu
St
4
5
4
Pr
PrSt
evision 2.0 uly 2015
tep
4 Select Version
5 Enter th
.13 AAlarm
• If Latcturns o
• If Latc
reliminary S• Latch f• An ala
alarm ialarm d
rocedure tep
1 Switchto showmessa
2 Acknow
ED
Action
Firmware n (FIRM)
he Selection
Acknowlecan be set as
ching functionoff when alarmching function
Steps function is en
arm has been tis acknowledgdisappears.
Action
the lower dispw the alarm ge.
wledge the ala
DC201 / EDC2
edge AlaNo Latching
n is disabled, thm disappears.n is enabled, th
abled. In the Striggered. Theged, it will sto
play
arm.
202 / EDC203
Press
or
rms or Latching. hat is LACH=
hat is LACH=
Set Up Mode,e Alarm LED kop blinking if t
Press
4.
3 Product Man
Lowe
Uppe
Lowe
=NO, the ALM
=YES, use the
, LACH=YESkeeps blinkingthe alarm is st
Lower D
If the alablinking;If alarm
Monitoring a
ual
R
er Display= FW
er Display= FW
er Display=Sy
M LED lights
following pro
S. g when the alatill active or th
Re
Display= ALM
arm is still acti; disappears, A
and Operating 4.13. Acknow
Result
WVN
WVN
ystem Firmwar
up when alarm
ocedure.
arm occurs. Whe LED turns
esult
ive, ALM LED
ALM LED=off.
the Controllerwledge Alarms
81
re Version
m occurs and
When the off if the
= stops
r s
1
4. Monito4.14. Set
82
4.14
Initiatin
Prelimin
ProceduStep
1
2 SG
3 S
4 S
5
Starting
Prelimin
ProceduStep
1
2
oring and Opetting Auto Tun
SettinThis section i
g Auto Tuni
nary Steps The user has t
ure Actio
Enter Set Up
Select AUX SGroup
Select ACCUTFunction Para
Select Tune(T
Exit Configura
g Through K
nary Steps The operatingCurrent contrACCUTUNEACCUTUNEThe controlleManual opera
ure Actio
In Normal OpMode, switch display to shoof Auto Tunin
Start Auto Tun
erating the Coing
EDC201
ng Auto Tintroduces the
ing
the access to s
on
Mode
et Up
TUNE (AT) ameter
TUNE)
ation
Keypad
g level of the crol selection isE=TUNEAuto E= TUNE.
r is in Auto opation mode.
on
eration the lower
ow the status g
ning
ontroller
/ EDC202 / ED
Tuning e procedure of
set parameters
Pre
Long press
or
Long press without any operation m
controller is cs a PID. ALGCTuning funct
peration mode
Pres
DC203 Produc
f initiating Aut
s.
ess
r
or key ore than 30s.
onfigurator leC=Time A or tion is enabled
e and MAN L
ss
Lo•
•
A
ct Manual
to Tuning.
Top DisplaGroup title
Upper Dis
Top Displa
Upper Dis
Upper Dis
Lower Dis
The controand returnMode.
evel. Time B.
d. That is in co
LED is off. Au
ower Display =If Auto Tuninshows up ASIf Auto Tuninshows up ASlower display
Auto Tuning is
Result
ay= INP (Thise)
splay=TYPE
ay= AUX
splay= DIN
splay= AT
splay= TUNE
oller exits Conns to the Norm
onfiguration m
uto Tuning can
Result
= ASTR ng is not runniSTR; ng is running, STP. If Auto Ty shows up AS
started.
RevisJu
t
is the first Se
nfiguration Momal Operation
mode,
n not be starte
ing, lower disp
lower display Tuning is runniSTP.
sion 2.0 ly 2015
et Up
ode
d in
play
ing,
4. Monitoring and Operating the Controller 4.14. Setting Auto Tuning
Revision 2.0 EDC201 / EDC202 / EDC203 Product Manual 83 July 2015
System detects the rising edge of the digital input and sends the command to start the Auto Tuning process. If the prerequisite of Auto Tuning is not met, the lower display will show up Error (ERR) after short pressing, otherwise, the Auto Tuning process is started.
4. Monito4.15. Sw
84
Stoppin
Prelimin
ProceduStep
1
2
4.15 Prelimin
ProceduStep
1
4.16 Prelimin
ProceduStep
1
oring and Opeitch Manual/A
ng Auto Tun
nary Steps Auto Tuning
ure Actio
In Normal OpMode, switch display to shostatus of Auto
Stop Auto Tu
Switcnary Steps The controlle
ure Actio
Switch ManuaMode
Settinnary Steps In the automaWith setting l
ure Action
In the lower dselect the SP which needs tup.
erating the CoAuto Mode
EDC201
ning
is started.
on
peration the lower
ow the o Tuning
ning
ch Manua
r is in the Nor
on
al / Auto
ng SP
atic mode, Leflevel of SP va
n
isplay, value
to be set
ontroller
/ EDC202 / ED
Press
al/Auto M
rmal Operatio
Pres
ft Display= Malue.
Press
DC203 Produc
Lower • If A
=AT
• If AAu
Auto
Mode
on Mode.
ss
Le•
•
MAN LED off.
Lo
ct Manual
Display = ATSAuto Tuning isTSR;
Auto Tuning isuto Tuning is ru
Tuning is stop
eft Display = MIn Auto ModIn Manual M
ower Display=
Result
SP s not running,
s running, loweunning, lower
pped.
Result
MAN is on or oe: MAN Led is
Mode: MAN Le
Result
Current SP v
RevisJu
lower display
er display = ATdisplay =ATSP
off s off; d is on.
value of the sy
sion 2.0 ly 2015
TSP. If P.
ystem
ReJu
4
Vi
Pr
PrSt
St
Pr
PrSt
evision 2.0 uly 2015
2 Set SP
.17 SThe Tidisplay
iewing the T
reliminary STimer upper l
rocedure tep
1 Switchvalue.
tart Timer
reliminary STimer
rocedure tep
1 Start th
ED
P value.
Setting Tiimer provides y is Time Rem
Timer Curre
Steps is enabled. TMlimit value.
Action
to the timer o
Steps is ready to sta
Action
he timer.
DC201 / EDC2
imer a configurabl
maining.
nt Status
MR= ENABL
output
art.
202 / EDC203
or
le Time-out pe
LEPERI= In th
Press
Press
4.
3 Product Man
Lower Dis
• Short the SP
• Long pthe SP
• Long p
short pthe sto
eriod of from
he Set up mod
Lower Di
• If theDisp
• If therema
If the tim
Lower Dtime is d
Monitoring a
ual
splay= current
press P value;
press P value;
press
press opped digit pla
0 to 9 hours:
de, TMR=ENA
Re
splay= TX.XX
e timer is readplay=configura
e timer is runnaining time is d
mer is timed-ou
Re
Display = T” logdisplayed.
and Operating 4.17.
t set SP value
or
or
or
or ace.
59 minutes. T
ABLE, PERI=
esult
X
dy to start, Lowated Timer cyc
ning, “T” logo fdisplayed. ut, 0 is display
esult
go flashes and
the Controller Setting Timer
85
to adjust
to adjust
and then
to adjust
The Timer
= the timer
wer cle.
flashes and
yed.
d remaining
r r
5
4. Monito4.18. Set
86
Resettin
Prelimin
ProceduStep
1
4.18
In Auto
Prelimin
ProceduStep
1
2
AT is Pr
Prelimin
ProceduStep
1
2
3
4
oring and Opetting Output Va
ng Timer
nary Steps Timer is time
ure Actio
Reset the Tim
Setting OThis section i
Mode
nary Steps In Normal Op
ure Actio
Select SP
Change the SSelection
rocessing
nary Steps In Normal Op
ure Actio
Select PV or S
Select ManuaMode
Change the Por Selection
Enter the ValuSelection
erating the Coalue
EDC201
ed-out that is L
on
mer.
Output Vintroduces the
peration Mode
on
SP Value or
peration Mode
on
SP
al Control
PV/SP Value
ue or
ontroller
/ EDC202 / ED
Lower Display
Pres
Value e procedure of
e, MAN LED
Pre
o
e, AT LED is
Pr
o
DC203 Produc
y = .T 0 00.
ss
L
f setting outpu
is off and Low
ess
or
on and Lower
ress
or
ct Manual
ower Display
ut value.
wer Display=
Lower Disp
Lower Disp
r Display= cu
Lower Discurrent va
MAN LED
Lower Dis
Enters valmemory a
Result
= T+ set timer
current PV va
Result
play= Current
play = Intended
urrent PV and
Result
splay= Intendealue
D is on and AT
splay = Intende
lue or selectioafter another k
RevisJu
r period
alue.
t
SP value
d SP value
SP value.
t
ed PV or SP
T LED is off
ed PV or SP v
on made into key is pressed
sion 2.0 ly 2015
value
.
ReJu
In
Pr
PrSt
evision 2.0 uly 2015
n Man Mode
reliminary SIn Nor
rocedure tep
1 Select
2 Chang
ED
Steps rmal Operation
Action
SP
e the Output V
DC201 / EDC2
n Mode, Man
Value
202 / EDC203
LED is on an
Press
or
4.
3 Product Man
nd Upper Disp
Low
Upval
LowOU
Monitoring a
ual
play= current P
Re
wer Display=M
per Display= Iue
wer Display=InUT LED blinks
and Operating 4.18. Setting
PV Lower Dis
esult
.MXX X
Intended PV c
ntended Outp
the Controllerg Output Value
87
splay= SP.
current
ut value
r e
7
88 EDC201 / EDC202 / EDC203 Product Manual Revision 2.0 July 2015
5. Troubleshooting/Service Instrument performance can be adversely affected by installation and application problems as well as by hardware problems. We recommend that you investigate the problems in the following order:
• Installation related problems Read the Installation section in this manual to make sure the EDC 200 has been properly installed.
• Application related problems Review the application of the controller; then, if necessary, direct your questions to the local sales office.
• Hardware and software related problems Use the troubleshooting error message prompts and controller failure symptoms to identify typical failures which may occur in the controller. Follow the troubleshooting procedures to correct them.
5.1 Troubleshooting Aids An error message can occur:
• At power-up. • When the Status Tests are requested. • During continuous background tests while in normal operation.
Check installation If a set of symptoms still persists, refer to Section 2 - Installation and ensure proper installation and proper use of the controller in the system. Customer support If you cannot solve the problem using the troubleshooting procedures listed in this section, you can get technical assistance by dialing 1-800-423-9883 USA and Canada. An engineer will discuss your problem with you.Please have your complete model number, serial number, and Software version available.The model and serial numbers can be found on the chassis nameplate. The software version can be viewed under Setup Group Status.If it is determined that a hardware problem exists, a replacement controller or part will be shipped with instructions for returning the defective unit. Do not return your controller without authorization from Honeywells Technical Assistance Center or until the replacement has been received. Please refer to the Honeywell website: http://www.honeywell.com/ps.
ReJu
5
5
Di
evision 2.0 uly 2015
Determ
Step
1
2
Determ
Step
1
2
Please 200 yo
.2 PWhen and Dacontrolor onlynormal
.3 BEDC 2malfun
iagnose SysWhen gone to
Step
1
2
ED
mining the fir
A
Select OPTGroup
Read the f
mining the ha
A
Select OPTGroup
Read the hversion
give these nuou have and he
Power-uppower is applatabase powerller will switcy display an erlly.
Backgrou200 performs onction, a “Fail
stem Error required, the ro Failsafe.
A
Select OPTGroup
Read the e
DC201 / EDC2
rmware versi
Action
TION Set Up
irmware verio
ardware vers
Action
TION Set Up
hardware
umbers to the Celp them deter
p Tests lied, the contror on self-checkch into the failrror code. If th
und Testsongoing backgl” will be disp
results of thes
Action
TION Set Up
error code
202 / EDC203
ion
P
n
sion
P
Customer Suprmine a soluti
oller will run k. Power on selsafe mode. Inhe diagnostic
s ground tests to
played in the lo
se tests can be
P
3 Product Man
Press
Press
pport person. Ion to your pro
three diagnoself-check runs
n failsafe modetests performe
o verify data aower display.
e checked to d
Press
5
ual
Upper Displ
Lower Displ
Upper Displ
Lower Displ
Upper Displ
Lower Displ
Upper Displ
Lower Displ
It will indicateoblem.
tic tests, inclus once. If the de, the system ed successfull
and memory i
determine the r
Upper Displ
Lower Displ
Upper Displ
Lower Displ
5. Troublesho5.2. Po
Result
ay = STA
ay = FMVN
ay = FMVN
ay = VERSIO
Result
ay = STA
ay = HWVN
ay = HWVN
ay = VERSIO
e which versio
uding CPU, RAdiagnostic teswill not start uly, the control
integrity. If th
reason the con
Result
ay = STA
ay = ERCD
ay = ERCD
ay = Error cod
ooting/Serviceower-up Tests
89
N
N
on of EDC
AM, Flash ts failed, the up properly ller runs
ere is a
ntroller has
de
e s
9
5. Troub5.3. Back
90
Confirm
Prelimin
Step
1 Ss
2 Am
leshooting/Skground Tests
Check the errerror code, pr
Error Co
ED01
ED02
ED03
ED04
ED05
ED06
ED0A
FC01
FC02
EC03
m System ErAfter troublesthe “Fail” me
nary Steps When the sysmessage and The controlle
Actio
Switch the lowshow the Fail m
Acknowledge tmessage
ervice s
EDC201
ror code paramrobable cause
ode
Failur
Failur
Failur
Failur
Failur
verific
Failur
Param
Verific
Input
rror shooting the sessage.
stem is in the Fcurrent paramr is in Normal
on
wer display to message.
the Failsafe
/ EDC202 / ED
meter to view and troublesh
re on restoring
re on reading F
re on reading d
re on reading c
re on reading v
cation code Co
re on reading p
meter Configu
cation data err
Failure
specific failure
Failsafe modemeter values ar
l Operating M
Pres
DC203 Produc
all of the errohooting proced
Prob
g factory defau
FCT data
digital sign
configuration d
verification co
omparison erro
product code
ration error
ror
e, you can pro
e, that is, whenre shown on th
Mode.
ss
Lo
Lo
ct Manual
or informationdure.
bable Cause
ult setting
data
de
or
oceed with the
n a serious mahe lower displ
ower Display=
ower Display=
. The followin
e following pro
alfunction occlay.
Result
FaIl
“FaIl” messa
RevisJu
ng table lists th
ocedure to con
curs, there is a
age disappears
sion 2.0 ly 2015
he
nfirm
a Fail
s
Revision 2.0 EDC201 / EDC202 / EDC203 Product Manual 91 July 2015
6. Appendix A Look-up Table for 7 Segment Character and Associated English Word
A B C D E F G H I J K L M
A B C D E F G H I J K L M
N O P Q R S T U V W X Y Z
N O P Q R S T U V W X Y Z
Table 6-1 7 Segment Character and Associated English Word
7 Segment Code
Abbreviation of the Associated English Word
Full Name of the Associated English Word
DISB DISB DISABLE
EABL EABL ENABLE
FILT FILT FILTER
ACTN ACTN ACTION
REVR REVR Reverse
DIRT DIRT Direct
DB DB DEADBAND
FLMD FLMD FAILMODE
FLSF FLSF FAILSAFE
PERI PERI PERIOD
RLST RLST RLYSTATE
Table 6-2 Examples for 7 Segment Code and Associated English Word
For more information To learn more about PI New Wave Controllers, visit www.honeywellprocess.com Or contact your Honeywell Account Manager
Process Solutions Honeywell
1250 W Sam Houston Pkwy S Houston, TX 77042
Honeywell Control Systems Ltd Honeywell House, Skimped Hill Lane Bracknell, England, RG12 1EB
51-52-25-155 Rev.2.0 July 2015 ©2015 Honeywell International Inc.
Shanghai City Centre, 100 Jungi Road Shanghai, China 20061 www.honeywellprocess.com
Sales and Service For application assistance, current specifications, pricing, or name of the nearest Authorized Distributor, contact one of the offices below.
ASIA PACIFIC Honeywell Process Solutions, (TAC) [email protected] Australia Honeywell Limited Phone: +(61) 7-3846 1255 FAX: +(61) 7-3840 6481 Toll Free 1300-36-39-36 Toll Free Fax: 1300-36-04-70 China – PRC - Shanghai Honeywell China Inc. Phone: (86-21) 5257-4568 Fax: (86-21) 6237-2826 Singapore Honeywell Pte Ltd. Phone: +(65) 6580 3278 Fax: +(65) 6445-3033 South Korea Honeywell Korea Co Ltd Phone: +(822) 799 6114 Fax: +(822) 792 9015
EMEA Honeywell Process Solutions, Phone: + 80012026455 or +44 (0)1344 656000 Email: (Sales) [email protected] or (TAC) [email protected]
AMERICAS Honeywell Process Solutions, Phone: (TAC) 1-800-423-9883 or 215/641-3610 (Sales) 1-800-343-0228 Email: (Sales) [email protected] or (TAC) [email protected]
Specifications are subject to change without notice.