CERTIFICATION DATE06/10/2015
DESCRIPTIONProduct Tested: Direct Tension Indicators Standard: ASTM F-959-13Nominal Size: 3/4” Type: 325Finish: PLAIN Heat Number: 11375389 Date Received: 06/10/2015 Date Tested: 06/10/2015
REQUIREMENTS: Minimum – 28 KIPS / Maximum – 34 KIPS
COMPRESSION TEST RESULTS
LOT NUMBER 343Z8(1) 32.8 (6) 33.1 (11) 33.3(2) 32.9 (7) 33.0 (12) 33.1(3) 32.8 (8) 32.9 (13) 32.8(4) 33.1 (9) 33.0 (14) 32.9(5) 33.3 (10) 32.8 (15) 33.3
MEAN COMPRESSION LOAD: 33.01 KIPS / STANDARD DEVIATION: 0.19 KIPSCompression Load Tests were performed on (15) pieces of the submitted Test Specimens and (15) pieceswere found to be in conformance with the compression load requirements of ASTM F-959-13. Thecompression test results above were generated on a Digital Compression Load Analyzer Test System which icalibrated annually on test equipment directly traceable to the National Institute of Standards and Technology All compression load tests are performed in accordance with test method ASTM F-606-13 at a test gap of0.015” with results reported to the nearest 100 lbs.
TLL001-14-09-36001-1
TESTING PERFORMED FOR
DTI MANUFACTURER:
TurnaSure LLC
340 East Maple Avenue, Suite 206Langhorne, PA 19047
REPORT ISSUED TO:
TurnaSure LLC 340 East Maple Avenue, Suite 206
Langhorne, PA 19047
Page 1 of 1
The services performed above were done in accordance with LTI's Quality System Program Manual Revision 20 dated 12/12/12 andISO/IEC 17025. These results relate only to the items tested and this report shall not be reproduced, except in full, without the writtenapproval of Laboratory Testing, Inc. L.T.I. is accredited by Nadcap for NDT and Materials Testing for the test methods and specific
services as listed in the Scopes of Accreditation available at www.labtesting.com and www.eAuditNet.com. The results reported on thistest report represent the actual attributes of the material tested and indicate full compliance with all applicable specification and contractrequirements.
MERCURY CONTAMINATION: During the testing and inspection, the productdid not come in direct contact with mercury or any of its compounds nor withany mercury containing devices employing a single boundary of containment.
NOTE: The recording of false, fictitious or fraudulent statements or entries onthis document may be punishable as a felony under Federal Statutes.
Sherri L. ScheifeleQA Specialist