SummeryNAMEOFWORKAMOUNTPart-ICIVILWORKACOLDSTOREWITHPRECOOLING&RIPENINGA.MAINBUILDINGB1.0COLDSTOREWITHPRECOOLING&RIPENINGB.ROADWORK:CPRE ENGINEERED BUILDINGGRANDTOTALCOSTOF(A+B)I.EMAINBUILDING+ROADWORK,Rs..Part IIPLANT & MACHINARYCOLDSTOREWITHPRECOOLING&RIPENINGA)INSULATEDPANELB)REFRIGERATIONSYSTEMC)OTHER MACHINARYTOTALOFPART IIPart IIIHT/LT POWER SUPPLY WORK1.0TRANSFORMER & HT/LT WORK2.0RELATEDELECTRICALSFORREF.SYSTEMTOTALOFPART IIIGRANDTOTAL64

&C63&R&"Tahoma,Regular"&8BANANA PACKHOUSE RIPENING FACILITY FOR EXPORT&L&"Tahoma"&8&C&"Tahoma"&8Madhya Pradesh State Agricultural Marketing Board (MP Mandi Board)&R&"Tahoma"&8

BOQ CVILCivil Works ( Banana Pack house )( The bidder must quote as per detailed specifications in the respective annexures with supply, installation, testing & commissioning. )Based on Basic Design & Layout by Consultant, the Architectural and Structural Designing of the Civil Works Up to Plinth are in the Scope of Work of the BidderNO.ITEM CODE.DESCRIPTION OF ITEMS.QTY.UNITRATEAMOUNTA - EARTH WORK.A-1Excavation for foundation in earth, soils of all types sand, gravel and soft murum upto a depth of 1.5 M including removing the excavated material upto a distance of 100 m beyond the building area stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filing, ramming, watering (including shoring and strutting) etc. complete (Lift up to 2.50 m) Spec. No. BD.A. 1 Page No. 259.410Cum.A-2Excavation for foundation in hard murum including removing the excavated material upto distance of 100 m. beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring, strutting complete. (Lift upto 1.50 m.) Spec. No. : Bd.A 2 Page no. 259.200Cum.A-3Excavation for foundation in hard rock by chiseling, weighing etc. including trimming and leveling the bed, removing the excavated material up to a distance of 100 meter beyond the building area and all lifts, stacking as directed, dewatering and back filling complete. (Lift up to 1.5 m.) Spec. No. Bd.A6. Page No. 260.R.OCum.A-44Back Filling in footing with approved excavated materials in 15 cm. To 20 cm. Layers including watering and compaction etc. complete. (above 1.50 Meters lift) Spec. No. 6 Page No. 15.1500Cum.A-54Filling in plinth and floors with contractor's soil, sand or murum in 15 cm to 20 cm. Layers including watering and compaction etc. complete. Spec. No.7 Page No. 151500Cum.A-6Providing dry trap / granite / quartzite / gneiss rubble stone soling in single layer of 23 cm. Thick below Plinth Concrete layer including hand packing and compacting complete. Spec. No. BD.A. 12. Page No.264.500Sq M.SUB TOTAL EARTH WORK.Total Rs.B - P.C.C. WORK.B-15.3.2Providing and laying in situ cement concrete (150 mm thk.) M-10/1:3:6 of trap/granite/quartzite/gneiss metal for foundation including dewatering, form work, compacting, roughening them if special finish is to be provided, finishing if required and curing etc. complete (4.42 bag/cum) Spec. No. 3 Page No. 17432CUMSUB TOTAL P.C.C. WORK.C - R.C.C. WORK.C-15.3.2Providing and laying in situ cement concrete M-20 of trap/granite /quartzite /gneiss metal for reinforced cement concrete work in foundation like footings of reinforced cement concrete columns and steel stanchion including bailing out water, form work, compaction and finishing, curing etc. complete. (Excluding steel reinforcement and structural steel) (7.60 bag/cum) Spec. No. 3 Page No. 17110CUMC-25.3.3Providing and casting in situ cement concrete M-20 of trap/granite/quartzite gneiss metal for reinforced cement concrete columns up to plinth level as per detailed designs and drawing or as directed including centering, formwork, compacting and finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening the surface if special finish is to be provided and curing etc. complete. (Excluding reinforcement) (7.60 bag/cum) Spec. No. : 4 Page No.17CU.MBasement50cumSuperstructure6cumC-35.4.1Providing and casting in situ cement concrete M-20 of trap/granite/quartzite gneiss metal for reinforced cement concrete plinth beams as per detailed designs and drawing or as directed including centering, formwork, compaction and roughening the surface of special finishing to be proved and curing etc. complete (Excluding reinforcement). (7.60 bag/cum) Spec. No. 11 Page No.1892CU.MBasement80cumC-45.4.1Providing and casting in situ cement concrete M-20 of trap/granite/quartzite /gneiss metal for reinforced cement concrete floor/ roof beams and slabs and landings as per detailed designs and drawings, including centering, formwork, compacting and roughening the surface if special finish is to be provided and curing etc. complete (Excluding reinforcement). (7.60 bag/cum) Spec No. 11. Page No. 18.70CUMC-95.4.10Providing and fixing in position Mild steel and H.Y.S.D. bar reinforcement of various diameters for reinforced cement concrete pile caps, footings, foundation, slabs, beams, columns, canopies, stair case, newels, chajjas, lintels, pardis, copings, fins arches etc. as per detailed designs, drawings and schedules including cutting, bending, hookin the bars, binding with wires or tack welding and supporting as required complete. Spec. No. : 13. Bd.F17 Page No. 1945M.T.SUB TOTAL R.C.C. WORK.Total Rs.D - MASONRY WORK.D-16Providing coursed brick masonry in cement mortar 1:6 in plinth of inner walls / in plinth of external walls including bailing out water manually, striking joints on unexposed faces and watering complete. Spec. No. 2 A Page No. 25.152CUMD-26Providing second class burnt Brick masonry with conventional/Indian standard type bricks in cement mortar 1:6 in superstructure including striking joints, racking out joints, watering and scaffolding complete. Spec. No. 2B Page No. 25.110CUMD-36Providing second class burnt Brick masonry with conventional/Indian standard type bricks in cement mortar 1:6 in half brick thick wall including mild steel longitudinal reinforcement of 2 bars of 6 mm. Diameter at every third course, property bent and bounded at ends including scaffolding racking out joints and watering complete. Spec. No. 9 Page No. 26.70SQMD-418Providing internal cement plaster 12 mm. Thk. In single coat in cement mortar 1:5 with neeru finishing to concrete or brick surfaces, in all positions including scaffolding and curing complete. Spec. No. : 1.III Page No. 54.600SQMD-518Providing internal cement plaster 12 mm. Thk. In single coat in cement mortar 1:5 without neeru finishing to concrete or brick surfaces, in all positions including scaffolding and curing complete. Spec. No. : 1.III. Page No. 54.335SQMD-618Providing sand faced plaster externally in cement mortar using Kharsalia / kasaba or similar type of sand, in all positions including base coat of 15 mm. Thick in cement mortar 1:4 using water proofing compound at 1 kg. Per cement bag, curing the same of the base than 2 days and keeping the surface of the base coat rough to receive the sand faced treatment 10 mm. thick in cement mortar 1:4 finishing the surface by taking out grains and curing for fourteen days scaffolding etc. complete. Spec. No. 9 Page no. 55.1100SQMSUB TOTAL MASONRY WORK.Total Rs.E - FLOORING.E-1Providing and casting in situ m-15 (1:2:4) grade light Reinforced Tremix Flooring 120 mm thick in Cold stores & grading packing hall including providing and binding in position reinforcements as directed. Casting floor concrete in bays by using girder, vibrator, vacuum departingmechanical trawling till perfectly leveled, smooth integrated cement finish is achieved, curing and making good, rate shall include cost of appropriate concrete hardener, expansion joints bituminous felt and excluding cost of reinforcement.2200SQ.ME-214Providing and laying polished kotah stone flooring 25 mm to 30 mm thick and 4 cm. To 55 cm. Wide in plain pattern on a bed of 1:6 cement mortar including cement float, filling joints with neat cement slurry, curing, polishing and cleaning complete. Spec. No. 18 Page No. 48.50SQ.ME-314Providing and fixing in required positions skirting or dado kotah stone slabs 25 mm. To 30 mm. Thick and 30 cm. Wide on 1:4 cement plaster including cement float, filling joints with neat cement slurry, curing, rubbing, polishing and cleaning complete. Spec. No. 17 Page No. 47.20RME-6Providing sills of polished kotah stone 25 mm. To 30 mm. Thick bed of 1:4 cement mortar including cement float, filling joints with slurry, curing, polishing and cleaning complete.ROSQ.M.E-714Providing 25 mm./30 mm. Thick partitions of machine cut both side polished black/ brown Granite stone slab of approved shapes, quality and colour for urinals, including cutting holes of required size in the appropriate places to receive pipes etc. fixing in cement mortar 1:3 curing and cleaning complete. Spec. No. 17 Page No. 47.8SQ.M.E-914Providing and fixing ceramic tiles of approved quality and size 7 mm thick for dado and skirting in required position with ready made adhesive mortar of approved quality on plaster of 1:2 cement mortar including joint filling with white / colour cement slurry cleaning curing complete. Spec. No.18 Page No. 48.450SQ.M.SUB TOTAL FLOORING.Total Rs.0F- DOORS AND WINDOWS.F-110Providing and fixing solid core flush door in single/double leaf 35 mm. Thick, decorative types, of exterior grade, as per detailed drawing including country teak wood door frame (100 mm x 80 mm ), approved P.V.C. laminate on both faces with/without glazing in the positions shown on the drawings or as directed, all necessary beads, moldings and lipping, wrought iron hold fasts, chromium plated fixtures and fastening without/with brass mortise lock/aldrops, tadipatti, chromium plated handles on both sides etc. complete. (with door frame) Spec. No. 1. Page No. 33.6SQMProviding and fixing waterproof marine flush door panels for bath and w.c. (8 nos.) with 1 mm thk laminate finish on both sides.11sqmF-20Providing and fixing aluminium sliding window of various sizes as per detailed drawings fabricated powder coating with or without ventilator including fabrication, glazing with plain / clear glass panels of approved type and quality, all fixtures and fastening complete with guard bars 10 cm. center to center. Spec. No. 30. Page No. 37.5SQMF-30Providing and fixing rolling steel shutters fabricated from 18 gauge steel laths with side guides, bottom rail, brackets, door suspension shafts, including rolling springs, locking arrangements and housing box at the top including mechanical gear operating arrangement and one coat of red lead primer and two coat of enyamal paint of approved shade and quality. Spec. No. 5 Page No. 40.18SQMF-4Providing and fixing mosquito proof and fly proof S.S. mesh to windows, ventilators with removable teak wood frame ( 25 mm x 50 mm ) including fixing of mesh of with teak wood lipping of 12 mm x 50 mm and including painting, l etc. complete. As directed by Engineer in charge.ROSQMF-5Providing and fixing in position M.S. frame door shutters fixed with fly proof S.S. mesh as per drawing and design and complete with necessary chrome plated fittings and fixtures and three coats of oil paint etc. complete . As directed by Engineer in charge.(including teak wood frame)ROSQMF-6Providing and fixing in position 8 S.W.G. wire weld mesh 50 x 50 mm jali in M.S. angle frame 50 x 50 x 5 as per drawing and design including one coat of primer and two coats of oil paint as per drawing and instructions of Engineer in charge.10SQMSUB TOTAL DOORS AND WINDOWS.Total Rs.H - COLOURING WORK.H-119Providing and applying two coats of water proof cement paint of approved manufacture and of approved colour over a coat of white wash on new plastered surfaces including scaffolding if necessary, cleaning and preparing the surface, watering for two days complete. Spec. No. 27 Page No. 58.1100SQMH-218Providing and applying washable oil bound distemper of approved colour and shade to new surfaces in two coats over a primer coat including scaffolding, preparing the surfaces complete. Spec. No. 2. Page No. 56.935SQMSUB TOTAL COLOURING WORK.Total Rs.I - ANCILLARY WORK.I-10Providing preconstructional anti termite treatment to all excavated surfaces, back fill in immediate contact with foundation, and treating the top surface of plinth filling at the rate of 5 ltrs. Of emulsion concentrate of 0.5 percent of Chicropyriphox per Sq m. of surface area with ten years guarantee bond as per I.S. 6313 (part II) -1973 (as per item No. 22.41, 22,42 and 22,43 of schedule of rates of National Building Organization). Spec. Sr. No. 7 Page 68.2400SQMI-15Providing and installing in position fabricated M.s. entrance gate (weight approx 50 kg/sq m) including I.S.J. side posts, heavy duty hinges, pad locks, and tower bolts and including three coats of oil paint to all steel surfaces all as per instructions of Engineer in charge.12SQMSUB TOTAL ANCILLARY WORK.Total Rs.J - WATER SUPPLY AND SANITATION.J-1Providing and hoisting in position 1 nos. of 10000 ltr capacity P.V.C. water tanks of approved quality and make over a brick masonry platform with plaster and top concrete complete with all necessary connections as per instructions of Engineer in charge.1no.J-2Providing and constructing under ground R.C.C. water tank in M: 250 concrete as per design, inside dimension as 3.0 x 2.0 x 1.5 m with R.C.C. roof slab with inspection covers, central R.C.C. partition wall, smooth water proof plastering from inside and sand faced plastering from out side and with all necessary inlet and outlet pipe connections etc. as per design, drawing and instructions of Engineer in charge.1no.J-324Providing and fixing on walls / ceiling / floors, of Diameter given below 'B' class having embossed as ISI Mark galvanized iron pipes with screwed, sockets, joints and necessary galvanized iron fittings such as sockets, back nuts, elbows, bends, tees, reducers, enlargers, plugs, clamps etc. including necessary drilling holes in walls, slabs etc. and remaking good the demolished portion to restore the same in original condition neatly and applying anti corrosive primer oil paint and two coats of all painting complete. Spec. No. 3 Page No. 69.a. For 50 dia. 'B' class G.I. Pipe line.10RMb. For 40 dia. 'B' class G.I. Pipe line.20RMc. For 25 dia. 'B' class G.I. Pipe line.40RMd. For 15 dia. 'B' class G.I. Pipe line.60RMJ-4Providing and fixing screw down gun metal / brass wheeled stop taps of various diameters including necessary sockets, union nut complete.a. For 50 dia. Stop taps.2no.b. For 40 dia. stop taps4no.c. For 25 dia. Stop taps6no.d. For 15 dia. Stop taps.4no.J-523Providing and fixing Orissa Pattern type white glazed earthenware 580 x 440 mm. Water closet pan including tarp cast iron soil and vent pipes upto the outside face of the wall, 1:2 lime concrete / 1:5:10 cement concrete bedding, 10 liters PVC low level flushing cistern with fitting, inlet pipe with stop tap / brackets for fixing the cistern, 32 mm. diameter P.V.C. flush pipe with fitting and cistern 20 mm. diameter P.V.C. overflow pipe with mosquito proof coupling and pull, painting of the cistern and pipes and cutting and making good walls and floors. Spec. No. 9. Page No. 70.5no.J-623Providing and fixing white glazed earthenware half stall type group of three urinals with cistern including P.C.C. soil pipe, C.I. Trap and soil pipe connection upto face of wall complete. Spec. No. As directed by Engineer in charge. Spec.Sr. No. 34 Page No. 74.1no.J-7Providing and laying 100 mm. Diameter half round white glazed stone earthenware pipes in 1:5:10 cement concrete bedding including bends, necessary excavation etc. complete. As per instruction from Architect4RMJ-8Providing and fixing white glazed earthenware wash Hand Basin of 55 cm. X 40 cm. Size including single cold water pillar tap / brackets, rubber plugs and brass chain, stop tap and necessary P.V.C. pipe connections including P.V.C. waste pipe and without bottled trap upto the outside face of the wall. As per instruction from Architect2no.J-924Providing and fixing 10 cm. Cast iron Nhani Trap including grating, bend and piece of cast iron pipe upto the outsie face of the wall complete (with 45 cm. Arm). Spec. No. 8 Page No. 70.4no.J-1024Providing and fixing 15 cm. Cast iron Nahani Trap including grating, bend and piece of cast iron pipe upto the outside face of the wall complete (with 45 cm. Arm). Spec. No. 8 Page No. 70.2no.J-11Providing and fixing of required diameter cast iron soil / vent / waste pipes with necessary fixtures and fitting such as bends, tees, single junction, double junction, slotted vent offsets on walls or in the ground including filling joints with lead with red lead oil paint coat and two coats of anti corrosive paint including fixing the pipe on walls by means of nails driven through lugs in wooden holder / battens and supported on ground floor by C.C. 1:2:4 of 30 cm. x 30 cm. size blocks complete.a. 100 dia. C.I. Pipe.20RMb. 80 dia. C.I. Pipe.12RMJ-12Providing and fixing 15 cm. X 10 cm. Salt glazed stone ware gully trap in cement concrete 1:4:8 outside the building including cast iron grating in the sink, connecting glazed stoneware pipe, brick masonry chamber with cast iron grating for the gully trap, and precast R.C.C. cover with frame fixed with cement mortar.4no.J-13Providing and laying 100 mm. Diameter salt glazed stone ware pipes including fittings such as bends, tees, single junction, double junctions, laying, jointing including excavation and refilling the trenches complete. As per instruction from Architect4RMJ-14Providing and laying R.C.C. concrete pipes of I.S. N.P. class of 150 mm. Diameter in proper line, level and slope including necessary collars, excavation, laying fixing with collars in cement mortar 1:1 etc. complete including excavation and refilling the trenches.25RMJ-156Providing and constructing Brick masonry in cement mortar 1:6 for Inspection Chamber various sizes given below including 1:4:8 cement concrete foundation, 1:2:4 cement concrete channels half round S.W.G. pipes, with plastering brick masonry inside and outside with cement mortar 1:4 and inside neat cement finish including 75 mm. thick R.C.C. cover etc. complete depth upto 1.20 m. Spec. No. 2. Page No. 25.a. 60 cm. X 45 cm.4no.b. 90 cm. X 45 cm.1no.J-166Providing and constructing Brick masonry in cement mortar 1:6 for intercepting chamber 90 cm. X 45 cm. Including 1:4:8 cement concrete foundation, 1:2:4 cement concrete channels half round S.W.G. pipes, channels / half round glazed stone ware intercepting trap with roding pipe set in 1:4:8 C.C. block with plastering brick masonry inside and out side with cement mortar 1:$ and inside neat cement finish including 75 mm. thick R.C.C. cover etc. complete. depth upto 1.20 m. Spec. No. 2 Page No. 25.1no.J-17Providing and fixing Hume pipe septic tank 900 mm. Diameter with vent pipe and cap including necessary fittings including excavation and laying. And constructing man holes chambers with cover on top of the septic tank openings. With plaster etc. complete. As per instruction from Architect1no.J-18Providing soak pit of size 150 cm. X 150 cm. 150 cm. Including excavation and filling with brick bats. As per instruction from Architect1no.SUB TOTAL WATER SUPPLY AND SANITATION.Total Rs.TOTAL OF CIVIL WORK1.0 COLD STORE WITH PRECOOLING & RIPENING B. ROAD WORK:SR. NO.DESCRIPTION OF ITEMQUANTITYUNITRATEAMOUNT, RS1Excavation for roadway by manually in earth soil of all sorts sand, gravel or soft murum including dressing section to the required grade, camber and side slopes and conveying the excavated materials with all lifts upto a lead of 50m. and spreading for embankment or stacking as directed.450Cu.Mt2Supplying Soft murum at the road site including conveying & stacking complete.135Cu.Mt3Supplying 15 cm to 23 cm trap/ granite/quartzite /gneiss stone rubble at the road site including conveying & stacking complete.135Cu.Mt4Supplying 80mm trap/ granite/quartzite/ gneiss stone rubble at the road site including conveying & stacking complete.135Cu.Mt5Supplying 60 mm trap/ granite/quartzite/ gneiss stone rubble at the road site including conveying & stacking complete.135Cu.Mt6Supplying Soft murum at the road site including conveying & stacking complete.60Cu.Mt7Spreading gravel/ sand / soft murum/ hard murum over rubble soling/ WBM surface etc complete.135Cu.Mt8Laying 15 cm to 23 cm trap/ granite/ quartzite/ gneiss rubble soling including hand packing with rubble chips complete. Excluding cost of material.135Cu.Mt9Spreading of 60mm/80mm metal including sectioning complete.270Cu.Mt10Compacting murum (uo to 300mm loose) incuding artificial watering complete.900Sqm11Compacting the over size metal up to 200mm loose with vibratory roller incuding artificial watering complete.900Sqm12Compacting the size metal up to 100mm loose with vibratory roller incuding artificial watering complete.900Sqm13Providing & laying 75mm thk. Compected BBM over exisiting WBM surface including picking the road metalled surface thorughly cleaning the WBM surface by using mechanical broom or approved equipment, spreading 40mm size meatle (hand broken by bringing blasted rubble on site of work) at the rate of .09 cum/sqm compacting metale with roller & bitumen is then spred at the rate of 2 kg/sqm spreading 12mm meatle at the rate of 0.018 cum/sqm the surface shall be lightly rolled so that metal pieces gate embeded in the betumen layer & rolling shall continue untile entire surface is throughly compacted etc complete. With 60/70 grade900Sqm14Providing 20mm thk. Premix bituminous carpet including supplying all materials, preparing & cleaning the base heating bitumen, applying tack coat at0.975 kg/sqm mixing hot bitumen and chips laying the carpet and compacting complete. With 30/40 grade900Sqm15Carting of soil300CumCIVIL WORKS FOR ONE COLD STORE WITH PRECOOLING & RIPENINGB ROAD WORK, RSGRAND TOTAL COST OF (A + B) I.E MAIN BUILDING + ROAD WORK, Rs..

&L&"Tahoma"&8&C&"Tahoma"&8&R&"Tahoma"&8BANANA PACKHOUSE RIPENING FACILITY FOR EXPORT&L&"Tahoma"&8&C&"Tahoma"&8Madhya Pradesh State Agricultural Marketing Board (MP Mandi Board)&R&"Tahoma"&8

PEBC. PEB WORKSr. No.DescriptionUnitQtyRateAmount1Design, Fabrication and Erection of Primary Steel Structures - as per above mentioned specifications, dimensions and design standards. For shed size 62 X 30 X 4.5 mtrM.Ton342Design, Fabrication and Erection of Secondary Steel Structures - (Purling & Grits) - as per above mentioned specifications, dimensions and design standards.M.Ton13.5483Design, Fabrication and Erection of Sag & Bracing Rods - (Including Primary and Secondary Framing, foundation bolts, fasteners etc) - as per above mentioned specifications, dimensions and design standards.M.Ton3.414Supply and Fixing of 0.47mm thick,AZ 150 and 550 Mpa, Bare Galvalume, Roofing SheetsSqmtr21355Supply and Fixing of 0.47mm thick,AZ 150 and 550 Mpa,Colour Coated Galvalume,Sides Cladding sheets 2.5 MtrSqmtr3206Supply and Fixing of 0.47mm thick,AZ 150 and 550 Mpa,Bare Galvalume,Profile RidgeRmtr357Supply and Fixing of 0.47mm thick,AZ 150 and 550 Mpa,Colour Coated Galvalume,Eave GutterRmtr708Supply and Fixing of 0.47mm thick,AZ 150 and 550 Mpa,Colour Coated Galvalume,Downtake PipesRmtr1609Supply & Fixing of 0.47mm thk, AZ 150, and 550 MPa, Color Coated Galvalume - ROOFING ACCESSORIES (Flashings, Corner trims, etc)Lot1Total

&L&"Tahoma"&8&C&"Tahoma"&8&R&"Tahoma"&8BANANA PACKHOUSE RIPENING FACILITY FOR EXPORT&L&"Tahoma"&8&C&"Tahoma"&8Madhya Pradesh State Agricultural Marketing Board (MP Mandi Board)&R&"Tahoma"&8

Sheet2PARTIIIHT/LTPOWERSUPPLYSYSTEM1.0COLDSTOREWITHPRECOOLING&RIPENINGSr.No.ItemdescriptionQty.UnitRateTotalAmount,Rs.1Tappingof11KVpowersupplyfromMPEBOHlinepolewithHVcable-connectiontolineconductor,cablesupports,GIpipesleeveforcableprotection,allrequiredclamps,brackets,accessories,hardware,GIearthconductors,earthing,etc.completeasperapplicablestandards,rules,norms,guidelinesoflocalauthorities,statutoryrequirements,includingliasoningwithMPEBandtesting,approvalsfromallauthoritiesconcerned.AllM.S.itemstobedulypaintedwithred-oxidezincchromateprimerand2coatsofaluminiumpaint.Portionsembeddedingroundtobepaintedwith2coatsofbituminouspaint.1Set211KV,Aluminumconductor,XLPEinsulated,PVCsheathed,screened,armouredcableasperIS,toberunonpole,laidinreadyexcavatedtrench/hume-pipeetc.includingsealingofpipe-ends.i)3CX90sq.mm.150RMii)3CX120sq.mmRORM311KVHeatshrinkingtypeterminationforabovecableincludingcablegland,cablelugsandallrequiredaccessoriesincludingearthing.INDOOR:-i)3CX90sq.mm.2No.ii)3CX120sq.mmRONo.OUTDOOR:-i)3CX90sq.mm.2No.ii)3CX120sq.mm1No.4MSEBapprovedoutdoorcompacttype11KVmeteringcubiclehavingcableentry&terminationarrangementforbothincomingandoutgoingconnections.with3nos.CTs,3nos.PTs,arrangementforfixingelectronicTODmeter,necessaryterminalblocks,earthingterminals,mountingstand,foundationbolts,hardware,allaccessoriesetc.,earthingofCT,PT,body,cablearmouretc.asperMPEBnormsusingblackpaintedcopperflat,completeasperapplicablestandards,rules,norms,guidelinesoflocalauthorities,statutoryrequirementsetc.includingliasoning,coordinationwithMPEBandtesting,approvalsfromallauthoritiesconcerned.Necessarycable-supports,pipesleeveforcable,allrequiredclamps,brackets,accessories,mountingstructure,foundationbolts,hardwareetc.shallalsobeprovided.1Job5ConcretefoundationandgroutingasrequiredformeteringcubiclewithheightabovegroundasperMPEBnorms.1No.6MPEBapprovedelectronicTODmeterincludingliasoning,coordinationetc.withMSEBandtesting,approvalsfromauthoritiesasrequired.1No.72-polestructurewithheight/clearancesasperrules,usingRSJ100X116poles(min.length9m.)with10mm.thk.base-plateinM20PCC1.5mtr.deepfoundationand300mm.dia.muffing,interconnectionfrommeteringcubicle,1setof3nos.11KVclasslighteningarrestors,1setof11KV,200Amp.singlebreakverticallymountedA.B.switch,1setof11KVD.O.fuseswithoperatingrod,interconnectionfromDOFtotransformerwithalkathynepipeinsulatedconductor,11KVinsulatorsasrequired,ACSRconductorasrequired,M.S.channels,cross-bracings,supportingstructureandallrequiredclamps,connectors,hardware,accessories,doubleearthingof3nos.LA,4Pstructure,GOD,DOFusing40X6mmGIflat,completeasperapplicablestandards,rules,norms,guidelinesoflocalauthorities,statutoryrequirementsincludingliasoning,testing,approvalsfromallauthoritiesconcerned.AllM.S.itemstobedulypaintedwithred-oxidezincchromateprimerand2coatsofaluminiumpaint.Portionsembeddedingroundtobepaintedwith2coatsofbituminouspaint1Job8a315KVA,3ph.50Hz.11KV/433VtransformerasperIS:2026andotherapplicablestandards,vectorgroupDyn11,withoff-circuittapchangeswitchhavingconstantKVAtapsin6stepsof2.5%,lowlossgrainorientedsiliconsteellaminations,copperwoundwithminimumclassAinsulation,ONANcoolingwithmaximum50/55deg.temperatureriseofoil/winding,outdoortypeHVbushings,LVcableboxsuitablefor2nos.3.5CX90sq.mm.AYFYcables,outdoortypeLVneutralbushing,radiators,fittingsandaccessoriesasperISincludingconservator,localwindingandoiltemperatureindicatorsetc.completewithfirstfillofoilasperIS:335with10%extrafortoppingupatsite,doubleearthingofneutralandtransformerbodyusing40X6mmGIconductoretc.asperapplicablestandards,rules,norms,guidelinesoflocalauthorities,statutoryrequirements,includingliasoning,testing,approvalsfromallauthoritiesconcerned.ThejobincludesthedismantlingoftheexistingtransformeratIndapursiteandreplacingitwithnewoneasspecifiedinthetenderalongwithallnecessaryaccessories.Thebiddershalladdonthechargesforthiswork.PleasenotethattheexistingtransformeristhepropertyofMSAMBandmustbehandedoverbacktoMSAMBinworkingcondition.1No.8bSameas(8a)above,butofrating500KVAandwithLVcableboxsuitablefor3.5CX150sq.mmcable.x3nos..RONo.9400Amp.3poleACB(50KA)withearthfaultrelay,ammeter,voltmeter&indicatinglampsinoutdoorweather-proofsheet-steelpowdercoatedenclosurehavingcanopy,withterminalextensions,cableentry&exitboxessuitablefor2nos.3.5CX90sq.mmAYFYincomimgcablesaswellas2nos.3.5Cx90sq.mm.Outgoingcables,mountingstructure,accessories,hardwareetc.includingmountingframe,concretegrouting,doubleearthingusing40X6mmGIflat,completeasperstatutoryrequirementsfortransformerLVisolation.1No.10Earthingstationsincludingtest-linkasperIS:3043using:a)600x600x6mm.GIplateelectrodewith50x6mm.GIstripuptogroundlevel.17No.b)600X600X3mm.copperplateelectrodewith25X3mm.copperstripuptogroundlevelfortransformerneutral.4No.Theearthelectrodeshallbeburiedatadepthof3m.belowGL.Theearthconnection,testlink,pipeandfunnelshallbehousedinamasonrychamberapproximately350mm.lengthx350mm.widex300mm.deep.Themasonrychambershallheprovidedwithacastiron(CI)coverrestingoveraCIframeembeddedinmasonry.Thechambertopshallbeatleast100mm.abovethegroundlevel.Theearthingstationsshallbecompleteasperapplicablestandards,rules,norms,guidelines.Minimumspacingbetweenadjacentearthelectrodesshallbe3mtr.Earthelectrodesshallbeinterconnectedusing50X6mmGIconductorburiedingroundatadepthof150mm.11Switchyardfencingof2.5mtr.heightcomprising8SWGG.I.wire40mm.meshchainlink,verticalsupportsof50x50x6mm.MSangleat2mtr.interval,40x40x5mm.M.S.angleattop,middleandbottomsoastoformaframe,230mm.thk.400mm.heightbrickwalldulyplasteredandpainted,2nos.leaftypegates3mtr.wide,2.5mtr.height,madeoutof40mm.dia.G.I.pipe,8SWGGIchainlink,M.S.anglesetc.along-withlockingarrangementand2nos.RSJgatesupports,earthingoffenceverticalsupports,gatesetc.Fencingandgatesshallbepaintedwithred-oxideprimerand2coatsofaluminiumpaint.Supply,spreadingandlevelingof40mm.size,150mm.thk.stonegravelinfencedareaisincluded.Theclearances,fencing,gates,graveletc.shallbeasperapplicablestandards,rules,norms,guidelinesofElectricityBoard.1Set12175KVA,3ph.&neutral,50Hz.415V,0.8pf,heavydutywater-cooledDiesel-GeneratorofKirloskarCumminsmakesetwithcableboxsuitablefor2no.3.5CX90sq.mm.AYFYcable,neutralearthingterminal,heavydutybatteries,enginemountedalternatorforbatterycharging,manualcontrolpanel,localindicators,fueltank,channelbaseframe,anti-vibrationpads,completewithallrequiredequipment,accessories,fittings,controls,safetydevices,exhaustpiping,fuelpiping,silencer,doubleearthingofneutralandbodyetc.asperapplicablestandards,rules,norms,guidelinesoflocalauthorities,statutoryrequirements,includingliasoning,testing,approvalsfromallauthoritiesconcerned.1No.13MainPowerDistributionBoard(PDB):-Panelshallbetotallyenclosedcubicletypefreestanding,floor-mounting,compartmentalizedandmodularinconstruction,expandableonbothsides,fabricatedoutof14gaugeCRCAsheetsteeldulypretreatedandpaintedwith2coatsofred-oxidezinc-chromateprimerandpaintedwithsyntheticenamelpaintorpowdercoated.PanelshallhaveseparateMSEB/DGsupplychange-over&incomersectionwithdoorinterlockandisolatedhorizontal/verticalbus-barchambers.Bakelite/acrylicshroudswithdangerlablesshallbeprovidedasrequiredtocoverlivepartsandbusbarsforsafetypurpose.Separatecable-alleysshallbeprovided.Componentlayoutinindividualmodulesshallbespaciouswithadequateclearancesforeaseofoperationandmaintenance.Capacitormoduleswhenprovidedshallhaveadequatecoolingarrangementsuchaslouvresatrearandsides.Cableentryshallbetoporbottomaspersiteconditions.Aluminiumanodizedlabelsshallbeprovidedforcomponentsandfeeders.40x6mmGIearthbusbarshallbeprovidedalongpanellengthwithterminalsbroughtoutatbothends.Necessaryfoundationframe/pedestal/mountingstructure,sheetmetalblankingcovers,foundationboltsandallrequiredmaterial/accessoriesetc.shallbeincluded.VendorshallsubmitdetailedSLD,G.A.&dimensionaldrawings,BOMandwiringdiagramforOwner'sapproval.PanelshallbemanufacturedandtestedinanapprovedmannerasperIS:8623andotherapplicablestandards.1SetMCCshallconsistoffollowingfeeders:A.Change-oversection(i)400Ampfourpoleswitch-fuseload-breakchange-overswitchwithsuitablecable-entryandterminationarrangementfor2nos.3.5CX90sq.mm.AYFYcableseachforMSEBandDGsupplies.(Total2nos.cables)-1no.(ii)3Nos.supplyonLEDtypeindicationlampswith3Nos.HRCfusesforMSEBandDGsupplyonindication.2sets(iii)315/5Amp.,10VAY-ph.CTonMSEBsupplysideforAPFCpanel-1no.B.Incomer(i)400AmpACB(50KA)withOL,SC,EFprotections,operatinghandleanddoorinterlock,etc.-1no.(ii)0to500Vvoltmeter,voltmeterselectorswitch,3Nos.HRCfusesetc.1set(iii)0to200Amp.ammeter,ammeterselectorswitch,3Nos.630/5Amp.,10VACTs,shortinglinksetc.1set(iv)Copperneutrallink-1no.(v)Busbars1set50X6mm.maincopperbusbarswithred,yellow,blue,blackcolourheatshrinkablePVCsleevesandmountedonepoxy/SMCinsulatorsupportsoftestedqualityasperIS.Otherverticalcopperbusbarsshallberatedfortotalcompartmentratingwithcurrentdensityof1.5Amp.persq.mm.Minimumsize50X6mm.Minimumclearanceonallsidesofeachbusbarshallbe25mm.C.OutgoingFeedersCables/wiresusedforswitchgearpowerconnectionsshallbePVCinsulatedmulti-strandcopperconductorasperISwithcurrentratingatleast40%morethanfeederFLC.Minimumwiresizeshallbe2.5sq.mm.(tobeusedupto16Amp.MCBfeeder).Forfeederratingabove63Amp,busbarsshallbeused.(i)200AmpTPMCCBwithprotections,operatinghandleanddoorinterlock.neutrallinketc.formachineroom,andrefrigerationsystems1nos.(ii)63AmpMCBwithprotections,operatinghandleanddoorinterlock.neutrallinketc.forAirconditioningsystem1no.(iii)100Amp.MCBwithprotections,operatinghandleanddoorlock,neutrallinketcforGrading&PackingHall.(iv)100AmpMCBwithprotections,operatinghandle&doorlock,neutrallinketcforcompletelighting.(v)63Amp.MCBasspare14LTCapacitorAPFCPanel1SetAutomaticpowerfactorcorrectioncompartmentalized,modular,cubicletypetotallyenclosedpanelgenerallyaspermainPDBspecificationasunder:A)Incomer:(i)150AmpMCCBwithOL,SCprotections,operatinghandle,doorinterlocketc.1no.(ii)SupplyonLEDtypeindicationlampswithHRCfuses3nos.(iii)Auto/Manualswitch1no.(iv)APFCrelay(Syntron/Syconmake)1no.(v)0-60sec.Timerformanualoperation1set(vi)0to500Vvoltmeter,voltmeterselectorswitch,3Nos.HRCfusesetc.-1set(vii)0to160Amp.ammeter,ammeterselectorswitch,3Nos.200/5Amp.,10VACTs,shortinglinksetc1set.(viii)TPNCopperbusbars40X6mm1set(ix)Copperneutrallink1no.(x)Othercomponents,fansetc.forcompletion-LotB)OutgoingFeeders:i)200AmpautoswitchwithcontactorforTranformer1no.C)Capacitormodules(i)25.0KVARcapacitormodulewithcapacitor,63Amp.SFU(fuseratingaspercapacitormfr.recommendation),63Amp.contactor,start,stoppush-buttons,indicationlamp,controlfuseswitchgear,othercomponentsetc.6nos.(ii)25KVARcapacitormoduleasabovebutwithoutcapacitorbank-2nos.151.1KVgradePVCinsulated,PVCsheathed,muilti-strandAlorCuconductorasspecified,armouredcablesasperIS:1554,tobelaidinexcavatedtrenches,humepipes,readymadecabletrenches,cabletrays,onwall/structurewithnecessarydressing,clamping,cleating,taggingetc.a)3.5CX90sq.mm.-Aluminium100Mb)4CX6sq.mm.Copper50Mc)4CX4sq.mm.Copper50Md)4CX2.5sq.mm.Copper1000Me)4Cx1.5sq.mm.Copper1500M16LTcableendterminationusingheavydutycrimpingtypelugs,bi-metaltreatmentincaseofconnectionbetweendissimilarmetals,,brassnickelplateddoublecompressioncableglands,PVCtape,PVCsleevesetc.a)3.5CX90sq.mm.-Aluminium8No.b)4CX6sq.mm.Copper10No.c)4CX4sq.mm.Copper10No.d)4CX2.5sq.mm.-Copper75No.e)3Cx1.5sq.mm.CopperRONo.1714gaugeGItrayswithgalvanizingasperIS:2629,IS:2633,IS:4759etc.tobemountedintrenches,wall,beam,structureetc.includingaccessories,hardware,anchorfasteners,brackets,supportsetc.aspersiterequirement.Traysizesasunder:a)300mmperforatedtypewithGIcover100Mb)150mmperforatedtypewithGIcover150Mc)100mmperforatedtypewithGIcover75M18EarthingasperIS:3043usingconductorsoffollowingsizesinclusiveofbrazing,welding,jointing,clamping,hardware,bituminouspaintatjoints,connectiontoequipmentandallrequiredmaterial,tobelaidinoutdoortrenchatadepthofminimum600mm,indoorinconduit,traysoronfloor/wall/ceiling/roof/structureetc.withclampingat500mm.intervals.Allelectricalequipment,metalcasings,frames,electricalpanels,lightingpanels,cranerails,tracks,metalpipes,conduits,cabletraysetc.shallbeearthedattwopoints.Steelcolumns,metallicstaircases,ladders,handrailsetc.shallbeearthedusingsingleearthconductorbondedtoeachcomponentwithendsconnectedtotwodifferentpointsoftheearthgrid.Metallicsheaths,screens,armourofcablesshallbeearthedatbothendsofcable.Lightingfixtures,fans,switch-sockets,switch-GAIC,junctionboxesetc.shallbeearthedbymeansofseparateearthcontinuityconductortoberunalonglightingcable,conduit,casing-capingetc.Neutralconnectionsandmetallicconduits/pipesshallnotbeusedforequipmentearthing.(Note:Sub-stationearthingnotincludedunderthisitemasitiscoveredunderresp.items)a)50x6GIstrip80Mb)25x3Copper40Mc)8SWGGIwireROMd)12SWGGIwire400M19LighteningprotectionsystemforbuildingasperIS:2309inclusiveofbrazing,welding,jointing,clamping,hardware,bituminouspaintatjoints,completeasperapplicablestandards,rules,norms,guidelinesetc.,comprisingof:a)Verticalairterminalsincludingrigidandstrongmountingarrangementtosustainallweatherconditions,windloadetc.andallrequiredmaterial.1No.b)Horizontal/Verticalrooftopconductor25x3mm.copperfixedoninsulatedsupportsat750mmintervalalongbuildingperipheryAllmetallicitemswithinaradiusoftwometresshallbebondedtothelighteningprotectionconductor.Lightningdownconductorsshallbedirectlyconnectedtoearthelectrodeswithminimumbends.Alljointsshallbeofbrazedtype.Downconductorsshallnotbeconnectedtootherearthingconductorsabovegroundlevel.40M20Lightingpanels(LP)(i)50Amp.4P-ELMCBasincomerand10Amp.SPMCB-10nos.asoutgoingfeedersforCOLDSTOREWITHPRECOOLING&RIPENINGs3nos.(ii)40Amp.4P-ELMCBasincomerand10Amp.SPMCB-12nos.asoutgoingfeedersforOffice,Store,&Machineroom2no.iii)50Amp.4PELMCBasincomerand10Amp.SPMCBforGradingHall&Despatchdock1nos.iv)40Amp.4PELMCBasincomerand10Amp.SPMCBforAnterooms1&22nos.LPsshallbewithIP:42protection,factoryfabricatedoutofCRCAsheet,powdercoated,withmetaldoor,topandbottomremovableglandplates,universalmounting,completewithcopperbusbars,earthbus,terminalsforlooping,cable-ties,shroudstocoverliveterminals,frontblankingplatewithcutoutforMCBoperationandallaccessoriesetc.Rateshallbeinclusiveofmountingstructureandallrequiredmaterialforinstallation.1Set21LightingFixtures/fansa)1x40Wgeneralpurposeboxtypechanneltubefittingswithtransparentacryliccover,lamp,mountinghardware,JBforlooping,andallaccessoriesforpackinghall100No.b)2x40Wgeneralpurposeboxtypechanneltubefittingswithtransparentacryliccover,lamp,mountinghardware,JBforlooping,andallaccessoriesforpackinghall40No.c)Self-containedemergencylightunit20Wwithsealedre-chargeablebattery,battery-chargeretc.completeinallrespectsforautomaticswitchonincaseofsupplyfailure.4No.d)Ceilingfan1200mm.sizewithregulatorandallaccessoriesincludinganchorfastenerwithfan-hookinceiling.25No.e)Exhaustfan450mm.sizeincludingmountingframe,hardwareandallaccessoriesetc.4No.Note:Aboveratesshallbeinclusiveofallrequiredmaterial/accessoriesegGIpipebrackets,clamps,M.S.conduit-pipesforsuspension,ball-socketjoints,threepointceiling-roses,junction-boxes,PVC/woodenmountingblocksetc.22Streetlightfixtures(i)150WHPSVoutdoortypeweatherproofcastaluminiumenclosurelightfixturewithlamp,ballast,capacitorandallrequiredaccessories,hardwareetc.forpolemounting10No.(ii)9mtr.swagedtypemediumgaugeweldedpoleasperISwithbaseplate,earthingstud,junction-boxwithMCB,terminalsetc.,1mtr.lengthlampbracket,polecap,wiringfromjbtolampusing2.5sq.mm.PVCinsulatedflexiblecopperwireetc.completefor150WHPSVlampfixing.10No.23PointwiringfromGradinghallLPtoswitch-boardtolight/fan-pointsinPVCconduitsonwall/ceilinginclusiveofmains,sub-mains,sunmicatopwoodenswitch-boardwith5Amp.pianoswitchforeachlightfixture,650VgradePVCinsulatedflexiblecopperwiresasspecifiedbelowetc.14SWGcopperearthwiretobeusedfromsw.boardtofitting.Rateshallbeinclusiveofconduitaccessories,clamps,saddles,junctionboxes,spacersandallrequiredmaterial.

Note:1no.5amp.5pinplug-socket&piano-switchshallbeprovidedoneachswitch-boardandshallbeconsideredashalfpointandpaidathalftheunitrate.

WireSizes(i)LPtosw.board-3nos.2.5sq.mm.(ii)Sw.boardtolight2nos.1.5sq.mm.Neutralforindividualcircuitshallberunseparately.Colourcode:-Ph-Red,Neutral-Black,Earth-Green125No.241ph.5Amp.2pin/3pinplugsocketwithpiano-switchonsunmicatopwoodenboardincludingwiringinPVCconduitasperItem(24a)aboveinGradinghall&Anterooms&Receptionareas).10No.2563Amp.TPN+Emetal-cladindustrialplugsocketDBwith63Amp.4P-MCBinsheetmetalboxforwelding/miscellaneoussockets2No.261ph,16Ametal-clad3pinplugsocketDBwith16ADPMCBinsheetmetalboxforutilitypowersocketsinmachinerooms5No.27Structuralsteelforcablesupports,baseframes,mountingframes,brackets,variousothersupports,miscellaneousrequirementsetc.Themaximumsizesofsectionsshallbeasunder.a)ISMC100b)ISA75X75X6c)25X6mmM.S.flatd)6mm.thk.chequeredplateROMT28HumepipesoffollowingIDtobelaidbelowgroundincludingjointingandsealingofendstopreventwateringressa)300mm.ROMb)250mm.ROMc)200mm.ROMd)150mm.ROM29ProvidingmanholewithmasonrychamberandCIcoverforlayingorwithdrawalofcablesinhumepipes.5No.30Providingandlayingin600mm.(W)X1000mm.(D)trenchwithsandlayer150mm.thickandsinglebricklayeroncabletopincludingrefillingthetrench,levellingandprovidingmetalcablemarkersat3mtr.intervals.ROM31Taking6inchboreinrockysoiluptominimum3mtr.depthorasrequiredforGIpipeearthelectrode.RONo.32FireFightingandSafetyequipmenta)Firefightingsystemasperstatutoryrequirementoffirefighting&safetydepartmentwithprovisionoflatestequipments.1Setb)Portable5kgcapacitydrytypefireextinguishersuitableforelectricalfireasperISandasrecommendedbyTAC.5No.c)Floormountedbucketstandwith4nos13litrebucketshungonhooks.Thestandshallbe1.5mLx1.0mHmadeoutofMSangleframedulypaintedwithredoxideprimerand2coatsofredcolourfinishpaint.2Setd)Antiskidchequeredtype415Vgradeblackrubbermat1000mmwideasperIS5424forpanels,switchesetc.1Sete)Firstaidboxwithcontentsasperstandardrequirements.2No.f)ShocktreatmentchartinEnglish,HindiandGujaratiwithwoodenframeandglasscover.2No.g)Metallicpermanentlyinscribeddanger.GAIC11KVand415V.2No.h)Insulatedhandglovespairs11KVand415V.2No.TOTAL,RS.TOTALINWORDS:2.0RELATEDELECTRICALSFORREFRIGERATIONSYSTEM:-Sr.No.ItemdescriptionQty.UnitUnitRate,Rs.TotalAmount,Rs.1MainPower&MotorControlPanel(PMCP)1SetPanelshallbetotallyenclosedcubicletypefreestanding,floor-mounting,compartmentalizedandmodularinconstruction,expandableonbothsides,fabricatedoutof14gaugeCRCAsheetsteeldulypretreatedandpaintedwith2coatsofred-oxidezinc-chromateprimerandpaintedwithsyntheticenamelpaint/powdercoated.Panelshallhaveseparateincomersectionwithdoorinterlockandisolatedhorizontal/verticalbus-barchambers.Bakelite/acrylicshroudswithdangerouvershallbeprovidedasrequiredtocoverlivepartsandbusbarsforsafetypurpose.Separatecable-alleysshallbeprovided.Componentlayoutinindividualmodulesshallbespaciouswithadequateclearancesforeaseofoperationandmaintenance.Capacitormoduleswhenprovidedshallhaveadequatecoolingarrangementsuchasouversatrearandsides.Cableentryshallbetoporbottomaspersiteconditions.Aluminiumanodizedlabelsshallbeprovidedforcomponentsandfeeders.25x6mmGIearthbusbarshallbeprovidedalongpanellengthwithterminalsbroughtoutatbothends.Necessaryfoundationframe/pedestal/mountingstructure,sheetmetalblankingcovers,foundationboltsandallrequiredmaterial/accessoriesetc.shallbeincluded.Blankmodules-3Nos.blankmoduleswithoutanycomponentssuitablefor3.7K.W.motorstartersshallbeprovided.VendorshallsubmitdetailedSLD,G.A.&dimensionaldrawings,BOMandwiringdiagramforOwnersapproval.PanelshallbemanufacturedandtestedinanapprovedmannerasperIS:8623andotherapplicablestandards.Panelshallconsistoffollowingfeeders:(i)Incomer125AmpTPNwithfuses,operatinghandleanddoorinterlock,etc.1no.(ii)0to500Vvoltmeter,voltmeterselectorswitch,3Nos.HRCfusesetc.1set(iii)0to200Amp.Ammeter,ammeterselectorswitch,3Nos.315/5Amp.,10VACTs,shortinglinksetc.-1set(iv)SupplyonLEDtypeindicationlampwithHRCfuseetc.-1set(v)Copperneutrallink-1set(vi)Busbars25X6mm.Maincopperbusbarswithred,yellow,blue,blackcolourheatshrinkablePVCsleevesandmountedonepoxy/SMCinsulatorsupportsoftestedqualityasperIS.Otherverticalcopperbusbarsshallberatedfortotalcompartmentratingwithcurrentdensityof1.5Amp.Persq.mm.Minimumsize25X3mm.Minimumclearanceonallsidesofeachbusbarshallbe25mm.(Incomingcablesize95sq.mmx3.5CAYFYOutgoingFeeders-1seta)Motorratingupto7.5KW-DOLstartercomprisingofTP-MCB,SPPR(onlyforcompressorandcondensormotors),1no.contactor,1no.OLR,controlMCB,start/stoppush-buttons,selector-switches,motorONindicationlamp,terminalsetc.b)Motorratingabove7.5KW-StardeltastartercomprisingofTP-MCB,SPPR(onlyforcompressorandcondensormotors),3nos.contactors,1no.OLR,electronicstardeltatimer,controlMCB,start/stoppush-buttons,selector-switches,motorONindicationlamp,terminalsetc.c)TP-MCBshallbesuitableformotordutyandratingshallbeco-ordinatedwithOLRratingaspermanufacturers recommendations.j)ContactorshallbeAC3dutywithcurrentratingatleast10%morethanmotorFLC.Minimumcontactorrating12amp.-OLRshallhaveSPPfeaturewithmaximumsettingat-least10%morethanmotorFLC.-Cables/wiresusedforswitchgearpowerconnectionsshallbePVCinsulatedmulti-strandcopperconductorasperISwithcurrentratingatleast40%morethanfeederFLC.Minimumwiresizeshallbe2.5sq.mm.(tobeusedupto3.7KW).Feedersasreqd.forfollowingsystems1)7.0TRx2nos.ref.Systemforpre-cooling-2sets2)4.5TRx1nos.ref.SystemforeachCOLDSTOREWITHPRECOOLING&RIPENINGI-1set2a)5.0TRx4nos.ref.systemforeachripeningchamber-4sets3)Aircurtains-4Nos.4)4P-MCBfeederforref.Vansocket1no.5)32Amp.1no.6)4P-MCBfeederforlighting-32Amp1no.7)4PMCBfeederspare-32Amp.-1no.8)Anyothermotor,4P-MCBandDP-MCBfeedersaspersystemreqmt.9)MCBs,relays,timers,switches,push-buttons,indicationlamps,alarms,controls,instrumentation,necessarycircuitryetc.aspersystemrequirementforcontrolandinterlockingofcompressors,fans,pumps,solenoidvalves,levelswitches,pressureswitches,heatersetc.1setasrequired2TPNisolators(MCBtype)suitableformotordutyinoutdoortypemetalenclosureformotorslocatedoutsidemachineroom.1setasrequired1Set31.1KVgradePVCinsulated,PVCsheathed,AlorCustrandedconductorasspecified,armouredcablesasperIS:1554,tobelaidinreadymadecabletrenches,cabletrays,onwall/structurewithnecessarydressing,clamping,cleating,taggingetc.includingnecessarymaterial.1setasrequired1Seta)2CX1.5sq.mmCopper(lightingfixtures,alarmsystemandmisc.1ph.Smallpowerreqmt.Eg.Solenoids)b)2CX2.5sq.mmCopperc)3CX2.5sq.mm.Copper(1runformotorsupto3.7KW,lightingpanel,switch-boardand1ph.15Asocketsinrefrigeratedareas)d)3CX4sq.mm.Copper(1runformotorsupto7.5KWDOLand2runsformotorsupto12.5KW-SD)e)3CX6sq.mm.Copper(2runsformotorsupto15KW-SD)f)3CX16sq.mmAluminium(2runsformotorsupto22KW-SD)1)4CX2.5sq.mm.Copper2)4CX4sq.mm.CopperI)4CX6sq.mm.Copper(forref.vansocket)j)4CX16sq.mmAluminium3)4CX25sq.mmAluminiuml)Anyotherpowercablesasperscopeandsystemreqmt.m)Coppercontrolcablesofsize1.5sq.mm.Aspersystemreqmt.n)Instrumentationcablesaspersystemreqmt.4LTcableendterminationusingheavydutytinnedcopperlugs,brassnickelplateddoublecompressioncableglands,PVCtape,PVCsleevesetc.1Seta)2CX1.5sq.mmCopperb)2CX2.5sq.mmCopperc)3CX2.5sq.mm.Copperd)3CX4sq.mm.Coppere)3CX6sq.mm.Copperf)3CX16sq.mmAluminium4)4CX2.5sq.mm.Copper5)4CX4sq.mm.CopperI)4CX6sq.mm.Copperj)4CX16sq.mmAluminium6)4CX25sq.mmAluminiuml)Anyotherpowercablesasperscopeandsystemreqmt.m)Coppercontrolcablesofsize1.5sq.mm.Aspersystemreqmt.n)Instrumentationcablesaspersystemreqmt.1set514gaugeGSperforatedtraysofrequiredsizeswithaccessories,tobemountedintrenches,oronwall,beam,structureincludingsteelsupports,hardware,anchorfastenersetc.aspersiterequirement..1set1Set6EarthingasperIS:3043usingconductorsoffollowingsizesinclusiveofbrazing,welding,jointing,clamping,hardware,bituminouspaintatjoints,connectiontoequipmentandallrequiredmaterial,tobelaidalongconduit,traysoronfloor/wall/ceiling/roof/structureetc.withclampingat500mm.Intervals.Allelectricalequipment,metalcasings,frames,electricalpanels,cranerails,tracks,metalpipes,conduits,cabletraysetc.shallbeindependentlyearthedattwopoints.Metallicsheaths,screens,armourofcablesshallbeearthedatbothendsofcable.Neutralconnectionsandmetallicconduits/pipesshallnotbeusedforequipmentearthing.1Seta)32x6mmGIstrip(MCCpanel)b)25x3mmGIstrip(Sub-gridalongcable-trays,motorsabove3.7KWupto30KW,MCB-DBs,lightingpanelsetc.)c)8SWGGIwire(motorsupto3.7KW,powerisolators,JBs,lightingpolesetc.)d)12SWGGIwire(fieldeqpt.Likesolenoidvalves,LPBSetc.)e)14SWGCuwire(lightingfixtures,1ph.Utility-socketsetc.)-1set7LightingPanel1No.Lightingpanelwith32ADPELMCBasincomingand6ASP-MCB6nos.asoutgoingfeedersLPshallbewithIP:42protection,factoryfabricatedoutofCRCAsheet,powdercoated,withmetaldoor,topandbottomremovableglandplates,universalmounting,completewithcopperbusbars,earthbus,terminalsforlooping,cable-ties,shroudstocoverliveterminals,frontblankingplatewithcutoutforMCBoperationandallaccessoriesetc.Rateshallbeinclusiveofmountingstructureandallrequiredmaterialforinstallation.8Lightingfixturesa)1x40Wgeneralpurposeboxtypechanneltubefittingswithtransparentacryliccover,lamp,mountinghardware,JBforlooping,andallaccessoriesforanteroomasperrequirement1Setb)1x18WCFLfittingsuitableforcold-storageroomapplication,withacryliccoverincludinglamp,mountinghardware,JBforlooping,andallaccessoriesasperrequirement.1Setc)Selfcontainedemergencylightunit20Wwithsealedre-chargeablebattery,battery-chargeretc.completeinallrespectsforautomaticswitchonincaseofsupplyfailure.2SetNote:Aboveratesshallbeinclusiveofallrequiredmaterial/mountingaccessorieseg.Brackets,clamps,M.S.blackconduit-pipesforsuspension,ball-socketjoints,threepointceiling-roses,junction-boxes,mountingblocksetc.9MSpowdercoatedswitch-boardwithnecessarypianoswitchesforlightfittings(oneswitchformax.2nos.fittings)and1no.singleph.5amp.5pin.Socket+switchAsperrequirement1Set1032Amp.TPN+Emetal-cladindustrialplugsocketDBwith32Amp.4P-MCBforref.Van1Set11Emergencyalarmsystem(230VAC)forcoldchamberswithinputsignalsfromswitcheslocatedinsidecoldchambersneareachdoor.Thesystemshallcompriseofswitches,JBs,150mm.Gongbell/hooter,visualindicationtoindicatetheoriginofalarmsignal,test/accept/resetpush-buttons,UPS(backupfor1hour),necessarywiringandallrequiredmaterial,accessories.1SetTOTAL,Rs.TOTAL,INWORDS:

Sheet3C. PEB WORKSr. No.DescriptionUnitQtyRateAmount1Design, Fabrication and Erection of Primary Steel Structures - as per above mentioned specifications, dimensions and design standards. For shed size 62 X 30 X 4.5 mtrM.Ton342Design, Fabrication and Erection of Secondary Steel Structures - (Purling & Grits) - as per above mentioned specifications, dimensions and design standards.M.Ton13.5483Design, Fabrication and Erection of Sag & Bracing Rods - (Including Primary and Secondary Framing, foundation bolts, fasteners etc) - as per above mentioned specifications, dimensions and design standards.M.Ton3.414Supply and Fixing of 0.47mm thick,AZ 150 and 550 Mpa, Bare Galvalume, Roofing SheetsSqmtr21355Supply and Fixing of 0.47mm thick,AZ 150 and 550 Mpa,Colour Coated Galvalume,Sides Cladding sheets 2.5 MtrSqmtr3206Supply and Fixing of 0.47mm thick,AZ 150 and 550 Mpa,Bare Galvalume,Profile RidgeRmtr357Supply and Fixing of 0.47mm thick,AZ 150 and 550 Mpa,Colour Coated Galvalume,Eave GutterRmtr708Supply and Fixing of 0.47mm thick,AZ 150 and 550 Mpa,Colour Coated Galvalume,Downtake PipesRmtr1609Supply & Fixing of 0.47mm thk, AZ 150, and 550 MPa, Color Coated Galvalume - ROOFING ACCESSORIES (Flashings, Corner trims, etc)Lot1Total

Ref. PART I: PLANT & MACHINARYA) Insulated Panels & DoorsSr. No.ItemUnitQty.Unit Rate (Rs.)Total Amount(Rs.)1.1Wall & Ceilings PanelsSqM1300100 mm PUF1.2Walls & ceiling PanelsSqM68680 mm PUF1.3Walls & ceiling Panels31160 mm PUFSqM1.4Walls & ceiling Panels71440 mm PUFSqM1.5Floor InsulationRO80 mm PUFSqMSUB TOTAL , RS.Sr. No.ItemUnitQty.Unit Rate (Rs.)Total Amount(Rs.)2.1Manual sliding door of size 1800mm (W) xNos.102400 mm (H) x 80mm thk PUF2.2Motorized OH door of size 2400mm (W) xNos.22800 mm (H) x 80mm thk PUFSUB TOTAL, RS.B) Refrigaretion Machine3.311.7223.442.1309090909Sr.No.DescriptionUnitQuantityUnit Rate, Rs.Total Amount, Rs.1SITC Ref. unit for Cold store comprising of Air Cooled Codensing Unit & Air coil unit as per tender specification Capacity 8.5TR complete with ref. Piping cabling and electrical Panels Temperature & Humidity indicators & controllersNos.62SITC Ref. unit for Pre Cooling Chamber comprising of Air Cooled Codensing Unit & Air coil unit as per tender specification Capacity in 9.5TR Piping cabling and electrical Panels Temperature & Humidity indicators & controllersNos.23SITC Ref. unit for Ripening Chambers comprising of Air Cooled Codensing Unit & Air coil unit as per tender specification of capacity 7.5 TR TR Piping cabling and electrical Panels Temperature & Humidity indicators & controllersNos.84SITC Ref. unit for Air conditioning of Packing & Dispatch dock comprising of Air Cooled Codensing Unit & Air coil unit as per tender specification of capacity 11.0 TR TR. Including Piping, GI Ducting with insualtion, SA/ RA Aluminum extruded Grills & Diffuser, wiring cabling and electrical Panels Temperature indicators & controllersNos.15SITC Ref. unit for Air conditioning of Ante Room comprising of Air Cooled Codensing Unit & Air coil unit as per tender specification of capacity 5.5 TR TR. Including Piping, GI Ducting with insualtion, SA/ RA Aluminum extruded Grills & Diffuser, wiring cabling and electrical Panels Temperature indicators & controllersNos.16SITC Evaporative cooling unit for Processing comprising of Centrifugal Fan fixed in housing, drive motor direct coupled or belt & pulley with water spray sytem as per tender specification of capacity 35000 CFM. Including Water Piping, GI Ducting with insualtion, SA Aluminum extruded Grills & Diffuser, wiring cabling and electrical Panels.set17Ducting & grills and other accessories for Air conditioning AreaLot1TOTALC) OTHER PLANT & MACHINERYSR.NO.DESCRIPTIONOFITEMSQTY.UNITRATEAMOUNT1SpraySystem:1SetChemicaltankpipecover,whitecolor1000LiterwithpipestandChemicaltanktoelectricmotor4mts40mmdia.connectionpipePressuregaugewithSSmaterial1no.0.75inchesdia.valveof316SS10Nos.1.5inchesdia.valveofSS3162Nos.HighPressurewaterpumpof2HPmotorofKirloskarmake1No.MSCclasspipe19mmdia.-24Mts.SpringtypePVCpipe30Mtswithspraynozzles4nos.2RecirculationSystem:1SetChemicalRecyclingpipingwith65mmdia.pipesofSupremebrand-70mInsidepipelinewithholewithfitting12kg.SupremebrandwhitecolorISImarkedwith35mmthickness250MtsStopvalve35mm10nos.Outletvalve100mm6kg.&valves75mm2nosPipelineof100mmdia.8kg.ofSupremebrand40RMts.Pipelinefrombasementtanktorecyclingtank50mmthkofSupremebrand50MtInletletpipeforcleanwaterintherecyclingchamber65mmSupremebrandofwhitecolor50mt150mmpipewithfitting6MtsConnectionpipe,loose65mmthickness9MtsValves65mm5Nos.Electricmotorwithstarteralongwithcables2hpKirloskar2nos.MScoverforrecyclingtankssize1200x1200mm3Nos.3Plastictankforsanitizerof500Lcapacity1No.4BananaTrolley2Nos.5Rollerconveyorsfortransfer3Nos.6Platformweightscale3Nos.7Sanitaryspraynozzlessystem3Set8Handportablevacuummachine1Nos.9SSTables3Nos.10Electricalpanelboards,forindividualmachines1Set11LTcables&layingforitem111Set12BananaHandcuttingsickles25Nos.13Receptionconveyors3Nos.TOTAL,RSSr. No.ItemUnitQty.Unit Rate (Rs.)Total Amount (Rs.)3.1Ethylene gas emission system as per tech. specsNos.1 No.3.2Ventilation system as per tech. Specs.set4 Set3.3Steam type Humidifiers capacity 3 to 4 KWsetROSUB TOTAL, RS.

&L&"Tahoma"&8&C&"Tahoma"&8&R&"Tahoma"&8BANANA PACKHOUSE RIPENING FACILITY FOR EXPORT&L&"Tahoma"&8&C&"Tahoma"&8Madhya Pradesh State Agricultural Marketing Board (MP Mandi Board)&R&"Tahoma"&8

ElectricalPARTIIIHT/LTPOWERSUPPLYSYSTEM1.0COLDSTOREWITHPRECOOLING&RIPENINGSr.No.ItemdescriptionQty.UnitRateTotalAmount,Rs.1Tappingof11KVpowersupplyfromMPEBOHlinepolewithHVcable-connectiontolineconductor,cablesupports,GIpipesleeveforcableprotection,allrequiredclamps,brackets,accessories,hardware,GIearthconductors,earthing,etc.completeasperapplicablestandards,rules,norms,guidelinesoflocalauthorities,statutoryrequirements,includingliasoningwithMPEBandtesting,approvalsfromallauthoritiesconcerned.AllM.S.itemstobedulypaintedwithred-oxidezincchromateprimerand2coatsofaluminiumpaint.Portionsembeddedingroundtobepaintedwith2coatsofbituminouspaint.1Set211KV,Aluminumconductor,XLPEinsulated,PVCsheathed,screened,armouredcableasperIS,toberunonpole,laidinreadyexcavatedtrench/hume-pipeetc.includingsealingofpipe-ends.i)3CX90sq.mm.150RMii)3CX120sq.mmRORM311KVHeatshrinkingtypeterminationforabovecableincludingcablegland,cablelugsandallrequiredaccessoriesincludingearthing.INDOOR:-i)3CX90sq.mm.2No.ii)3CX120sq.mmRONo.OUTDOOR:-i)3CX90sq.mm.2No.ii)3CX120sq.mm1No.4MSEBapprovedoutdoorcompacttype11KVmeteringcubiclehavingcableentry&terminationarrangementforbothincomingandoutgoingconnections.with3nos.CTs,3nos.PTs,arrangementforfixingelectronicTODmeter,necessaryterminalblocks,earthingterminals,mountingstand,foundationbolts,hardware,allaccessoriesetc.,earthingofCT,PT,body,cablearmouretc.asperMPEBnormsusingblackpaintedcopperflat,completeasperapplicablestandards,rules,norms,guidelinesoflocalauthorities,statutoryrequirementsetc.includingliasoning,coordinationwithMPEBandtesting,approvalsfromallauthoritiesconcerned.Necessarycable-supports,pipesleeveforcable,allrequiredclamps,brackets,accessories,mountingstructure,foundationbolts,hardwareetc.shallalsobeprovided.1Job5ConcretefoundationandgroutingasrequiredformeteringcubiclewithheightabovegroundasperMPEBnorms.1No.6MPEBapprovedelectronicTODmeterincludingliasoning,coordinationetc.withMSEBandtesting,approvalsfromauthoritiesasrequired.1No.72-polestructurewithheight/clearancesasperrules,usingRSJ100X116poles(min.length9m.)with10mm.thk.base-plateinM20PCC1.5mtr.deepfoundationand300mm.dia.muffing,interconnectionfrommeteringcubicle,1setof3nos.11KVclasslighteningarrestors,1setof11KV,200Amp.singlebreakverticallymountedA.B.switch,1setof11KVD.O.fuseswithoperatingrod,interconnectionfromDOFtotransformerwithalkathynepipeinsulatedconductor,11KVinsulatorsasrequired,ACSRconductorasrequired,M.S.channels,cross-bracings,supportingstructureandallrequiredclamps,connectors,hardware,accessories,doubleearthingof3nos.LA,4Pstructure,GOD,DOFusing40X6mmGIflat,completeasperapplicablestandards,rules,norms,guidelinesoflocalauthorities,statutoryrequirementsincludingliasoning,testing,approvalsfromallauthoritiesconcerned.AllM.S.itemstobedulypaintedwithred-oxidezincchromateprimerand2coatsofaluminiumpaint.Portionsembeddedingroundtobepaintedwith2coatsofbituminouspaint1Job8a315KVA,3ph.50Hz.11KV/433VtransformerasperIS:2026andotherapplicablestandards,vectorgroupDyn11,withoff-circuittapchangeswitchhavingconstantKVAtapsin6stepsof2.5%,lowlossgrainorientedsiliconsteellaminations,copperwoundwithminimumclassAinsulation,ONANcoolingwithmaximum50/55deg.temperatureriseofoil/winding,outdoortypeHVbushings,LVcableboxsuitablefor2nos.3.5CX90sq.mm.AYFYcables,outdoortypeLVneutralbushing,radiators,fittingsandaccessoriesasperISincludingconservator,localwindingandoiltemperatureindicatorsetc.completewithfirstfillofoilasperIS:335with10%extrafortoppingupatsite,doubleearthingofneutralandtransformerbodyusing40X6mmGIconductoretc.asperapplicablestandards,rules,norms,guidelinesoflocalauthorities,statutoryrequirements,includingliasoning,testing,approvalsfromallauthoritiesconcerned.ThejobincludesthedismantlingoftheexistingtransformeratIndapursiteandreplacingitwithnewoneasspecifiedinthetenderalongwithallnecessaryaccessories.Thebiddershalladdonthechargesforthiswork.PleasenotethattheexistingtransformeristhepropertyofMSAMBandmustbehandedoverbacktoMSAMBinworkingcondition.1No.8bSameas(8a)above,butofrating500KVAandwithLVcableboxsuitablefor3.5CX150sq.mmcable.x3nos..RONo.9400Amp.3poleACB(50KA)withearthfaultrelay,ammeter,voltmeter&indicatinglampsinoutdoorweather-proofsheet-steelpowdercoatedenclosurehavingcanopy,withterminalextensions,cableentry&exitboxessuitablefor2nos.3.5CX90sq.mmAYFYincomimgcablesaswellas2nos.3.5Cx90sq.mm.Outgoingcables,mountingstructure,accessories,hardwareetc.includingmountingframe,concretegrouting,doubleearthingusing40X6mmGIflat,completeasperstatutoryrequirementsfortransformerLVisolation.1No.10Earthingstationsincludingtest-linkasperIS:3043using:a)600x600x6mm.GIplateelectrodewith50x6mm.GIstripuptogroundlevel.17No.b)600X600X3mm.copperplateelectrodewith25X3mm.copperstripuptogroundlevelfortransformerneutral.4No.Theearthelectrodeshallbeburiedatadepthof3m.belowGL.Theearthconnection,testlink,pipeandfunnelshallbehousedinamasonrychamberapproximately350mm.lengthx350mm.widex300mm.deep.Themasonrychambershallheprovidedwithacastiron(CI)coverrestingoveraCIframeembeddedinmasonry.Thechambertopshallbeatleast100mm.abovethegroundlevel.Theearthingstationsshallbecompleteasperapplicablestandards,rules,norms,guidelines.Minimumspacingbetweenadjacentearthelectrodesshallbe3mtr.Earthelectrodesshallbeinterconnectedusing50X6mmGIconductorburiedingroundatadepthof150mm.11Switchyardfencingof2.5mtr.heightcomprising8SWGG.I.wire40mm.meshchainlink,verticalsupportsof50x50x6mm.MSangleat2mtr.interval,40x40x5mm.M.S.angleattop,middleandbottomsoastoformaframe,230mm.thk.400mm.heightbrickwalldulyplasteredandpainted,2nos.leaftypegates3mtr.wide,2.5mtr.height,madeoutof40mm.dia.G.I.pipe,8SWGGIchainlink,M.S.anglesetc.along-withlockingarrangementand2nos.RSJgatesupports,earthingoffenceverticalsupports,gatesetc.Fencingandgatesshallbepaintedwithred-oxideprimerand2coatsofaluminiumpaint.Supply,spreadingandlevelingof40mm.size,150mm.thk.stonegravelinfencedareaisincluded.Theclearances,fencing,gates,graveletc.shallbeasperapplicablestandards,rules,norms,guidelinesofElectricityBoard.1Set12175KVA,3ph.&neutral,50Hz.415V,0.8pf,heavydutywater-cooledDiesel-GeneratorofKirloskarCumminsmakesetwithcableboxsuitablefor2no.3.5CX90sq.mm.AYFYcable,neutralearthingterminal,heavydutybatteries,enginemountedalternatorforbatterycharging,manualcontrolpanel,localindicators,fueltank,channelbaseframe,anti-vibrationpads,completewithallrequiredequipment,accessories,fittings,controls,safetydevices,exhaustpiping,fuelpiping,silencer,doubleearthingofneutralandbodyetc.asperapplicablestandards,rules,norms,guidelinesoflocalauthorities,statutoryrequirements,includingliasoning,testing,approvalsfromallauthoritiesconcerned.1No.13MainPowerDistributionBoard(PDB):-Panelshallbetotallyenclosedcubicletypefreestanding,floor-mounting,compartmentalizedandmodularinconstruction,expandableonbothsides,fabricatedoutof14gaugeCRCAsheetsteeldulypretreatedandpaintedwith2coatsofred-oxidezinc-chromateprimerandpaintedwithsyntheticenamelpaintorpowdercoated.PanelshallhaveseparateMSEB/DGsupplychange-over&incomersectionwithdoorinterlockandisolatedhorizontal/verticalbus-barchambers.Bakelite/acrylicshroudswithdangerlablesshallbeprovidedasrequiredtocoverlivepartsandbusbarsforsafetypurpose.Separatecable-alleysshallbeprovided.Componentlayoutinindividualmodulesshallbespaciouswithadequateclearancesforeaseofoperationandmaintenance.Capacitormoduleswhenprovidedshallhaveadequatecoolingarrangementsuchaslouvresatrearandsides.Cableentryshallbetoporbottomaspersiteconditions.Aluminiumanodizedlabelsshallbeprovidedforcomponentsandfeeders.40x6mmGIearthbusbarshallbeprovidedalongpanellengthwithterminalsbroughtoutatbothends.Necessaryfoundationframe/pedestal/mountingstructure,sheetmetalblankingcovers,foundationboltsandallrequiredmaterial/accessoriesetc.shallbeincluded.VendorshallsubmitdetailedSLD,G.A.&dimensionaldrawings,BOMandwiringdiagramforOwner'sapproval.PanelshallbemanufacturedandtestedinanapprovedmannerasperIS:8623andotherapplicablestandards.1SetMCCshallconsistoffollowingfeeders:A.Change-oversection(i)400Ampfourpoleswitch-fuseload-breakchange-overswitchwithsuitablecable-entryandterminationarrangementfor2nos.3.5CX90sq.mm.AYFYcableseachforMSEBandDGsupplies.(Total2nos.cables)-1no.(ii)3Nos.supplyonLEDtypeindicationlampswith3Nos.HRCfusesforMSEBandDGsupplyonindication.2sets(iii)315/5Amp.,10VAY-ph.CTonMSEBsupplysideforAPFCpanel-1no.B.Incomer(i)400AmpACB(50KA)withOL,SC,EFprotections,operatinghandleanddoorinterlock,etc.-1no.(ii)0to500Vvoltmeter,voltmeterselectorswitch,3Nos.HRCfusesetc.1set(iii)0to200Amp.ammeter,ammeterselectorswitch,3Nos.630/5Amp.,10VACTs,shortinglinksetc.1set(iv)Copperneutrallink-1no.(v)Busbars1set50X6mm.maincopperbusbarswithred,yellow,blue,blackcolourheatshrinkablePVCsleevesandmountedonepoxy/SMCinsulatorsupportsoftestedqualityasperIS.Otherverticalcopperbusbarsshallberatedfortotalcompartmentratingwithcurrentdensityof1.5Amp.persq.mm.Minimumsize50X6mm.Minimumclearanceonallsidesofeachbusbarshallbe25mm.C.OutgoingFeedersCables/wiresusedforswitchgearpowerconnectionsshallbePVCinsulatedmulti-strandcopperconductorasperISwithcurrentratingatleast40%morethanfeederFLC.Minimumwiresizeshallbe2.5sq.mm.(tobeusedupto16Amp.MCBfeeder).Forfeederratingabove63Amp,busbarsshallbeused.(i)200AmpTPMCCBwithprotections,operatinghandleanddoorinterlock.neutrallinketc.formachineroom,andrefrigerationsystems1nos.(ii)63AmpMCBwithprotections,operatinghandleanddoorinterlock.neutrallinketc.forAirconditioningsystem1no.(iii)100Amp.MCBwithprotections,operatinghandleanddoorlock,neutrallinketcforGrading&PackingHall.(iv)100AmpMCBwithprotections,operatinghandle&doorlock,neutrallinketcforcompletelighting.(v)63Amp.MCBasspare14LTCapacitorAPFCPanel1SetAutomaticpowerfactorcorrectioncompartmentalized,modular,cubicletypetotallyenclosedpanelgenerallyaspermainPDBspecificationasunder:A)Incomer:(i)150AmpMCCBwithOL,SCprotections,operatinghandle,doorinterlocketc.1no.(ii)SupplyonLEDtypeindicationlampswithHRCfuses3nos.(iii)Auto/Manualswitch1no.(iv)APFCrelay(Syntron/Syconmake)1no.(v)0-60sec.Timerformanualoperation1set(vi)0to500Vvoltmeter,voltmeterselectorswitch,3Nos.HRCfusesetc.-1set(vii)0to160Amp.ammeter,ammeterselectorswitch,3Nos.200/5Amp.,10VACTs,shortinglinksetc1set.(viii)TPNCopperbusbars40X6mm1set(ix)Copperneutrallink1no.(x)Othercomponents,fansetc.forcompletion-LotB)OutgoingFeeders:i)200AmpautoswitchwithcontactorforTranformer1no.C)Capacitormodules(i)25.0KVARcapacitormodulewithcapacitor,63Amp.SFU(fuseratingaspercapacitormfr.recommendation),63Amp.contactor,start,stoppush-buttons,indicationlamp,controlfuseswitchgear,othercomponentsetc.6nos.(ii)25KVARcapacitormoduleasabovebutwithoutcapacitorbank-2nos.151.1KVgradePVCinsulated,PVCsheathed,muilti-strandAlorCuconductorasspecified,armouredcablesasperIS:1554,tobelaidinexcavatedtrenches,humepipes,readymadecabletrenches,cabletrays,onwall/structurewithnecessarydressing,clamping,cleating,taggingetc.a)3.5CX90sq.mm.-Aluminium100Mb)4CX6sq.mm.Copper50Mc)4CX4sq.mm.Copper50Md)4CX2.5sq.mm.Copper1000Me)4Cx1.5sq.mm.Copper1500M16LTcableendterminationusingheavydutycrimpingtypelugs,bi-metaltreatmentincaseofconnectionbetweendissimilarmetals,,brassnickelplateddoublecompressioncableglands,PVCtape,PVCsleevesetc.a)3.5CX90sq.mm.-Aluminium8No.b)4CX6sq.mm.Copper10No.c)4CX4sq.mm.Copper10No.d)4CX2.5sq.mm.-Copper75No.e)3Cx1.5sq.mm.CopperRONo.1714gaugeGItrayswithgalvanizingasperIS:2629,IS:2633,IS:4759etc.tobemountedintrenches,wall,beam,structureetc.includingaccessories,hardware,anchorfasteners,brackets,supportsetc.aspersiterequirement.Traysizesasunder:a)300mmperforatedtypewithGIcover100Mb)150mmperforatedtypewithGIcover150Mc)100mmperforatedtypewithGIcover75M18EarthingasperIS:3043usingconductorsoffollowingsizesinclusiveofbrazing,welding,jointing,clamping,hardware,bituminouspaintatjoints,connectiontoequipmentandallrequiredmaterial,tobelaidinoutdoortrenchatadepthofminimum600mm,indoorinconduit,traysoronfloor/wall/ceiling/roof/structureetc.withclampingat500mm.intervals.Allelectricalequipment,metalcasings,frames,electricalpanels,lightingpanels,cranerails,tracks,metalpipes,conduits,cabletraysetc.shallbeearthedattwopoints.Steelcolumns,metallicstaircases,ladders,handrailsetc.shallbeearthedusingsingleearthconductorbondedtoeachcomponentwithendsconnectedtotwodifferentpointsoftheearthgrid.Metallicsheaths,screens,armourofcablesshallbeearthedatbothendsofcable.Lightingfixtures,fans,switch-sockets,switch-GAIC,junctionboxesetc.shallbeearthedbymeansofseparateearthcontinuityconductortoberunalonglightingcable,conduit,casing-capingetc.Neutralconnectionsandmetallicconduits/pipesshallnotbeusedforequipmentearthing.(Note:Sub-stationearthingnotincludedunderthisitemasitiscoveredunderresp.items)a)50x6GIstrip80Mb)25x3Copper40Mc)8SWGGIwireROMd)12SWGGIwire400M19LighteningprotectionsystemforbuildingasperIS:2309inclusiveofbrazing,welding,jointing,clamping,hardware,bituminouspaintatjoints,completeasperapplicablestandards,rules,norms,guidelinesetc.,comprisingof:a)Verticalairterminalsincludingrigidandstrongmountingarrangementtosustainallweatherconditions,windloadetc.andallrequiredmaterial.1No.b)Horizontal/Verticalrooftopconductor25x3mm.copperfixedoninsulatedsupportsat750mmintervalalongbuildingperipheryAllmetallicitemswithinaradiusoftwometresshallbebondedtothelighteningprotectionconductor.Lightningdownconductorsshallbedirectlyconnectedtoearthelectrodeswithminimumbends.Alljointsshallbeofbrazedtype.Downconductorsshallnotbeconnectedtootherearthingconductorsabovegroundlevel.40M20Lightingpanels(LP)(i)50Amp.4P-ELMCBasincomerand10Amp.SPMCB-10nos.asoutgoingfeedersforCOLDSTOREWITHPRECOOLING&RIPENINGs3nos.(ii)40Amp.4P-ELMCBasincomerand10Amp.SPMCB-12nos.asoutgoingfeedersforOffice,Store,&Machineroom2no.iii)50Amp.4PELMCBasincomerand10Amp.SPMCBforGradingHall&Despatchdock1nos.iv)40Amp.4PELMCBasincomerand10Amp.SPMCBforAnterooms1&22nos.LPsshallbewithIP:42protection,factoryfabricatedoutofCRCAsheet,powdercoated,withmetaldoor,topandbottomremovableglandplates,universalmounting,completewithcopperbusbars,earthbus,terminalsforlooping,cable-ties,shroudstocoverliveterminals,frontblankingplatewithcutoutforMCBoperationandallaccessoriesetc.Rateshallbeinclusiveofmountingstructureandallrequiredmaterialforinstallation.1Set21LightingFixtures/fansa)1x40Wgeneralpurposeboxtypechanneltubefittingswithtransparentacryliccover,lamp,mountinghardware,JBforlooping,andallaccessoriesforpackinghall100No.b)2x40Wgeneralpurposeboxtypechanneltubefittingswithtransparentacryliccover,lamp,mountinghardware,JBforlooping,andallaccessoriesforpackinghall40No.c)Self-containedemergencylightunit20Wwithsealedre-chargeablebattery,battery-chargeretc.completeinallrespectsforautomaticswitchonincaseofsupplyfailure.4No.d)Ceilingfan1200mm.sizewithregulatorandallaccessoriesincludinganchorfastenerwithfan-hookinceiling.25No.e)Exhaustfan450mm.sizeincludingmountingframe,hardwareandallaccessoriesetc.4No.Note:Aboveratesshallbeinclusiveofallrequiredmaterial/accessoriesegGIpipebrackets,clamps,M.S.conduit-pipesforsuspension,ball-socketjoints,threepointceiling-roses,junction-boxes,PVC/woodenmountingblocksetc.22Streetlightfixtures(i)150WHPSVoutdoortypeweatherproofcastaluminiumenclosurelightfixturewithlamp,ballast,capacitorandallrequiredaccessories,hardwareetc.forpolemounting10No.(ii)9mtr.swagedtypemediumgaugeweldedpoleasperISwithbaseplate,earthingstud,junction-boxwithMCB,terminalsetc.,1mtr.lengthlampbracket,polecap,wiringfromjbtolampusing2.5sq.mm.PVCinsulatedflexiblecopperwireetc.completefor150WHPSVlampfixing.10No.23PointwiringfromGradinghallLPtoswitch-boardtolight/fan-pointsinPVCconduitsonwall/ceilinginclusiveofmains,sub-mains,sunmicatopwoodenswitch-boardwith5Amp.pianoswitchforeachlightfixture,650VgradePVCinsulatedflexiblecopperwiresasspecifiedbelowetc.14SWGcopperearthwiretobeusedfromsw.boardtofitting.Rateshallbeinclusiveofconduitaccessories,clamps,saddles,junctionboxes,spacersandallrequiredmaterial.

Note:1no.5amp.5pinplug-socket&piano-switchshallbeprovidedoneachswitch-boardandshallbeconsideredashalfpointandpaidathalftheunitrate.

WireSizes(i)LPtosw.board-3nos.2.5sq.mm.(ii)Sw.boardtolight2nos.1.5sq.mm.Neutralforindividualcircuitshallberunseparately.Colourcode:-Ph-Red,Neutral-Black,Earth-Green125No.241ph.5Amp.2pin/3pinplugsocketwithpiano-switchonsunmicatopwoodenboardincludingwiringinPVCconduitasperItem(24a)aboveinGradinghall&Anterooms&Receptionareas).10No.2563Amp.TPN+Emetal-cladindustrialplugsocketDBwith63Amp.4P-MCBinsheetmetalboxforwelding/miscellaneoussockets2No.261ph,16Ametal-clad3pinplugsocketDBwith16ADPMCBinsheetmetalboxforutilitypowersocketsinmachinerooms5No.27Structuralsteelforcablesupports,baseframes,mountingframes,brackets,variousothersupports,miscellaneousrequirementsetc.Themaximumsizesofsectionsshallbeasunder.a)ISMC100b)ISA75X75X6c)25X6mmM.S.flatd)6mm.thk.chequeredplateROMT28HumepipesoffollowingIDtobelaidbelowgroundincludingjointingandsealingofendstopreventwateringressa)300mm.ROMb)250mm.ROMc)200mm.ROMd)150mm.ROM29ProvidingmanholewithmasonrychamberandCIcoverforlayingorwithdrawalofcablesinhumepipes.5No.30Providingandlayingin600mm.(W)X1000mm.(D)trenchwithsandlayer150mm.thickandsinglebricklayeroncabletopincludingrefillingthetrench,levellingandprovidingmetalcablemarkersat3mtr.intervals.ROM31Taking6inchboreinrockysoiluptominimum3mtr.depthorasrequiredforGIpipeearthelectrode.RONo.32FireFightingandSafetyequipmenta)Firefightingsystemasperstatutoryrequirementoffirefighting&safetydepartmentwithprovisionoflatestequipments.1Setb)Portable5kgcapacitydrytypefireextinguishersuitableforelectricalfireasperISandasrecommendedbyTAC.5No.c)Floormountedbucketstandwith4nos13litrebucketshungonhooks.Thestandshallbe1.5mLx1.0mHmadeoutofMSangleframedulypaintedwithredoxideprimerand2coatsofredcolourfinishpaint.2Setd)Antiskidchequeredtype415Vgradeblackrubbermat1000mmwideasperIS5424forpanels,switchesetc.1Sete)Firstaidboxwithcontentsasperstandardrequirements.2No.f)ShocktreatmentchartinEnglish,HindiandGujaratiwithwoodenframeandglasscover.2No.g)Metallicpermanentlyinscribeddanger.GAIC11KVand415V.2No.h)Insulatedhandglovespairs11KVand415V.2No.TOTAL,RS.TOTALINWORDS:2.0RELATEDELECTRICALSFORREFRIGERATIONSYSTEM:-Sr.No.ItemdescriptionQty.UnitUnitRate,Rs.TotalAmount,Rs.1MainPower&MotorControlPanel(PMCP)1SetPanelshallbetotallyenclosedcubicletypefreestanding,floor-mounting,compartmentalizedandmodularinconstruction,expandableonbothsides,fabricatedoutof14gaugeCRCAsheetsteeldulypretreatedandpaintedwith2coatsofred-oxidezinc-chromateprimerandpaintedwithsyntheticenamelpaint/powdercoated.Panelshallhaveseparateincomersectionwithdoorinterlockandisolatedhorizontal/verticalbus-barchambers.Bakelite/acrylicshroudswithdangerouvershallbeprovidedasrequiredtocoverlivepartsandbusbarsforsafetypurpose.Separatecable-alleysshallbeprovided.Componentlayoutinindividualmodulesshallbespaciouswithadequateclearancesforeaseofoperationandmaintenance.Capacitormoduleswhenprovidedshallhaveadequatecoolingarrangementsuchasouversatrearandsides.Cableentryshallbetoporbottomaspersiteconditions.Aluminiumanodizedlabelsshallbeprovidedforcomponentsandfeeders.25x6mmGIearthbusbarshallbeprovidedalongpanellengthwithterminalsbroughtoutatbothends.Necessaryfoundationframe/pedestal/mountingstructure,sheetmetalblankingcovers,foundationboltsandallrequiredmaterial/accessoriesetc.shallbeincluded.Blankmodules-3Nos.blankmoduleswithoutanycomponentssuitablefor3.7K.W.motorstartersshallbeprovided.VendorshallsubmitdetailedSLD,G.A.&dimensionaldrawings,BOMandwiringdiagramforOwnersapproval.PanelshallbemanufacturedandtestedinanapprovedmannerasperIS:8623andotherapplicablestandards.Panelshallconsistoffollowingfeeders:(i)Incomer125AmpTPNwithfuses,operatinghandleanddoorinterlock,etc.1no.(ii)0to500Vvoltmeter,voltmeterselectorswitch,3Nos.HRCfusesetc.1set(iii)0to200Amp.Ammeter,ammeterselectorswitch,3Nos.315/5Amp.,10VACTs,shortinglinksetc.-1set(iv)SupplyonLEDtypeindicationlampwithHRCfuseetc.-1set(v)Copperneutrallink-1set(vi)Busbars25X6mm.Maincopperbusbarswithred,yellow,blue,blackcolourheatshrinkablePVCsleevesandmountedonepoxy/SMCinsulatorsupportsoftestedqualityasperIS.Otherverticalcopperbusbarsshallberatedfortotalcompartmentratingwithcurrentdensityof1.5Amp.Persq.mm.Minimumsize25X3mm.Minimumclearanceonallsidesofeachbusbarshallbe25mm.(Incomingcablesize95sq.mmx3.5CAYFYOutgoingFeeders-1seta)Motorratingupto7.5KW-DOLstartercomprisingofTP-MCB,SPPR(onlyforcompressorandcondensormotors),1no.contactor,1no.OLR,controlMCB,start/stoppush-buttons,selector-switches,motorONindicationlamp,terminalsetc.b)Motorratingabove7.5KW-StardeltastartercomprisingofTP-MCB,SPPR(onlyforcompressorandcondensormotors),3nos.contactors,1no.OLR,electronicstardeltatimer,controlMCB,start/stoppush-buttons,selector-switches,motorONindicationlamp,terminalsetc.c)TP-MCBshallbesuitableformotordutyandratingshallbeco-ordinatedwithOLRratingaspermanufacturers recommendations.j)ContactorshallbeAC3dutywithcurrentratingatleast10%morethanmotorFLC.Minimumcontactorrating12amp.-OLRshallhaveSPPfeaturewithmaximumsettingat-least10%morethanmotorFLC.-Cables/wiresusedforswitchgearpowerconnectionsshallbePVCinsulatedmulti-strandcopperconductorasperISwithcurrentratingatleast40%morethanfeederFLC.Minimumwiresizeshallbe2.5sq.mm.(tobeusedupto3.7KW).Feedersasreqd.forfollowingsystems1)7.0TRx2nos.ref.Systemforpre-cooling-2sets2)4.5TRx1nos.ref.SystemforeachCOLDSTOREWITHPRECOOLING&RIPENINGI-1set2a)5.0TRx4nos.ref.systemforeachripeningchamber-4sets3)Aircurtains-4Nos.4)4P-MCBfeederforref.Vansocket1no.5)32Amp.1no.6)4P-MCBfeederforlighting-32Amp1no.7)4PMCBfeederspare-32Amp.-1no.8)Anyothermotor,4P-MCBandDP-MCBfeedersaspersystemreqmt.9)MCBs,relays,timers,switches,push-buttons,indicationlamps,alarms,controls,instrumentation,necessarycircuitryetc.aspersystemrequirementforcontrolandinterlockingofcompressors,fans,pumps,solenoidvalves,levelswitches,pressureswitches,heatersetc.1setasrequired2TPNisolators(MCBtype)suitableformotordutyinoutdoortypemetalenclosureformotorslocatedoutsidemachineroom.1setasrequired1Set31.1KVgradePVCinsulated,PVCsheathed,AlorCustrandedconductorasspecified,armouredcablesasperIS:1554,tobelaidinreadymadecabletrenches,cabletrays,onwall/structurewithnecessarydressing,clamping,cleating,taggingetc.includingnecessarymaterial.1setasrequired1Seta)2CX1.5sq.mmCopper(lightingfixtures,alarmsystemandmisc.1ph.Smallpowerreqmt.Eg.Solenoids)b)2CX2.5sq.mmCopperc)3CX2.5sq.mm.Copper(1runformotorsupto3.7KW,lightingpanel,switch-boardand1ph.15Asocketsinrefrigeratedareas)d)3CX4sq.mm.Copper(1runformotorsupto7.5KWDOLand2runsformotorsupto12.5KW-SD)e)3CX6sq.mm.Copper(2runsformotorsupto15KW-SD)f)3CX16sq.mmAluminium(2runsformotorsupto22KW-SD)1)4CX2.5sq.mm.Copper2)4CX4sq.mm.CopperI)4CX6sq.mm.Copper(forref.vansocket)j)4CX16sq.mmAluminium3)4CX25sq.mmAluminiuml)Anyotherpowercablesasperscopeandsystemreqmt.m)Coppercontrolcablesofsize1.5sq.mm.Aspersystemreqmt.n)Instrumentationcablesaspersystemreqmt.4LTcableendterminationusingheavydutytinnedcopperlugs,brassnickelplateddoublecompressioncableglands,PVCtape,PVCsleevesetc.1Seta)2CX1.5sq.mmCopperb)2CX2.5sq.mmCopperc)3CX2.5sq.mm.Copperd)3CX4sq.mm.Coppere)3CX6sq.mm.Copperf)3CX16sq.mmAluminium4)4CX2.5sq.mm.Copper5)4CX4sq.mm.CopperI)4CX6sq.mm.Copperj)4CX16sq.mmAluminium6)4CX25sq.mmAluminiuml)Anyotherpowercablesasperscopeandsystemreqmt.m)Coppercontrolcablesofsize1.5sq.mm.Aspersystemreqmt.n)Instrumentationcablesaspersystemreqmt.1set514gaugeGSperforatedtraysofrequiredsizeswithaccessories,tobemountedintrenches,oronwall,beam,structureincludingsteelsupports,hardware,anchorfastenersetc.aspersiterequirement..1set1Set6EarthingasperIS:3043usingconductorsoffollowingsizesinclusiveofbrazing,welding,jointing,clamping,hardware,bituminouspaintatjoints,connectiontoequipmentandallrequiredmaterial,tobelaidalongconduit,traysoronfloor/wall/ceiling/roof/structureetc.withclampingat500mm.Intervals.Allelectricalequipment,metalcasings,frames,electricalpanels,cranerails,tracks,metalpipes,conduits,cabletraysetc.shallbeindependentlyearthedattwopoints.Metallicsheaths,screens,armourofcablesshallbeearthedatbothendsofcable.Neutralconnectionsandmetallicconduits/pipesshallnotbeusedforequipmentearthing.1Seta)32x6mmGIstrip(MCCpanel)b)25x3mmGIstrip(Sub-gridalongcable-trays,motorsabove3.7KWupto30KW,MCB-DBs,lightingpanelsetc.)c)8SWGGIwire(motorsupto3.7KW,powerisolators,JBs,lightingpolesetc.)d)12SWGGIwire(fieldeqpt.Likesolenoidvalves,LPBSetc.)e)14SWGCuwire(lightingfixtures,1ph.Utility-socketsetc.)-1set7LightingPanel1No.Lightingpanelwith32ADPELMCBasincomingand6ASP-MCB6nos.asoutgoingfeedersLPshallbewithIP:42protection,factoryfabricatedoutofCRCAsheet,powdercoated,withmetaldoor,topandbottomremovableglandplates,universalmounting,completewithcopperbusbars,earthbus,terminalsforlooping,cable-ties,shroudstocoverliveterminals,frontblankingplatewithcutoutforMCBoperationandallaccessoriesetc.Rateshallbeinclusiveofmountingstructureandallrequiredmaterialforinstallation.8Lightingfixturesa)1x40Wgeneralpurposeboxtypechanneltubefittingswithtransparentacryliccover,lamp,mountinghardware,JBforlooping,andallaccessoriesforanteroomasperrequirement1Setb)1x18WCFLfittingsuitableforcold-storageroomapplication,withacryliccoverincludinglamp,mountinghardware,JBforlooping,andallaccessoriesasperrequirement.1Setc)Selfcontainedemergencylightunit20Wwithsealedre-chargeablebattery,battery-chargeretc.completeinallrespectsforautomaticswitchonincaseofsupplyfailure.2SetNote:Aboveratesshallbeinclusiveofallrequiredmaterial/mountingaccessorieseg.Brackets,clamps,M.S.blackconduit-pipesforsuspension,ball-socketjoints,threepointceiling-roses,junction-boxes,mountingblocksetc.9MSpowdercoatedswitch-boardwithnecessarypianoswitchesforlightfittings(oneswitchformax.2nos.fittings)and1no.singleph.5amp.5pin.Socket+switchAsperrequirement1Set1032Amp.TPN+Emetal-cladindustrialplugsocketDBwith32Amp.4P-MCBforref.Van1Set11Emergencyalarmsystem(230VAC)forcoldchamberswithinputsignalsfromswitcheslocatedinsidecoldchambersneareachdoor.Thesystemshallcompriseofswitches,JBs,150mm.Gongbell/hooter,visualindicationtoindicatetheoriginofalarmsignal,test/accept/resetpush-buttons,UPS(backupfor1hour),necessarywiringandallrequiredmaterial,accessories.1SetTOTAL,Rs.TOTAL,INWORDS:

&R&"Tahoma,Regular"&8BANANA PACKHOUSE RIPENING FACILITY FOR EXPORT&C&"Tahoma,Regular"&8Madhya Pradesh State Agricultural Marketing Board (MP Mandi Board)

Sheet1