CULBERTSON HALL - MAIL SERVICESHVAC IMPROVEMENT & WINDOW REPLACEMENT
CONSTRUCTION DOCUMENTS JANUARY 24, 2016
ABA/CACTADD'LADDMADJAFFAHUAIBALTALUMANODAPPROXARCHAUTOA/VAVG
BDBOBLDGBLKGBRGBSMTBTWNBOWBUR
CABCBCCCDXCFCHCIPCIRCCJCLCLGCLRCMUCOCOLCONCCONSTCONTCONTRCOORDCPTCTCTRCTRDCW
DBLDEGDEMODEPTDFDIADIMDISPDLDNDRDSDTLDWG
EAEIFS
EJELEVELECTENCLEQEQUIP(E)/EXISTESTETREWCEXHEXPEXT
FBOFDFDN
Anchor BoltAir ConditioningAcoustical Ceiling TileAdditionalAddendumAdjacentAbove Finished FloorAir Handling UnitAir Infiltration BarrierAlternativeAluminumAnodizedApproximate(ly)Architect(ural)AutomaticAudio / VisualAverage
BoardBottom OfBuildingBlockingBearingBasementBetweenBottom of WallBuilt Up Roof
CabinetCatch BasinCenter to CenterExterior Grade PlywoodCubic FeetChannelCast In PlaceCircumferenceControl JointCenterlineCeilingClearConcrete Masonry UnitClean OutColumnConcreteConstructionContinuousContractorCoordinateCarpetCeramic TileCenterCenteredCold Water
DoubleDegreeDemolish, DemolitionDepartmentDrinking FountainDiameterDimensionDispenserDead LoadDownDoorDownspoutDetailDrawing
EachExterior InsulationFinish SystemExpansion JointElevationElectric(al)EnclosureEqualEquipmentExistingEstimateExisting to RemainElectric Water CoolerExhaustExpansionExterior
Furnished By OthersFloor DrainFoundation
FEFECFINFIXFLEXFLRFLUORFOFTFTGFV
GAGBGCGALVGLGLU LAMGWB
HBHCHD BDHDRHDRWHMHORIZHRHTHTGHTRHVAC
HW
IDININCINFOINSULINT
JSTJT
LLAVLBLFLLLTWTLVL
MAGMANUFMASMAT'LMAXMECHMEDMEMBMEZZMDFMINMIRMISCMOMTDMTL
N/ANIC#NOMNTS
OCODOHOPNGOPP
PART BDPERFPERIMPERPPKGP/L
Fire ExtinguisherFire Extinguisher CabinetFinish(ed)FixtureFlexibleFloor DrainFluorescentFace OfFoot (Feet)FootingField Verify
GaugeGrab BarGeneral ContractorGalvanizedGlassGlue Laminated BeamGypsum Wall Board
Hose BibbHollow CoreHard BoardHeaderHardwareHollow MetalHorizontalHourHeightHeatingHeaterHeating, Ventilating,Air ConditioningHot Water
Inside DiameterInchIncludeInformationInsulationInterior
JoistJoint
LengthLavatoryPoundLineal/Linear FeetLive LoadLightweightLaminated Veneer Lumber
MagneticManufacturerMasonryMaterialMaximumMechanicalMediumMembraneMezzanineMedium Density FiberboardMinimumMirror(ed)MiscellaneousMasonry OpeningMountedMetal
Not ApplicableNot In ContractNumberNominalNot to Scale
On CenterOutside DiameterOverheadOpeningOpposite
Particle BoardPerforatedPerimeterPerpendicularParkingProperty Line
PLPLAMPLWDPNLPNTPREFABPREFINPSFPSIPSLPTPTDPVCPVMT
QTY
RRADRCPRDRDWDRE:RECPTREFREFGREINFREQDRESREVRMRO
SANSCHEDSDSFSGSHTSHTGSHWRSIMSIPSNTSOGSPECSSSSDSTDSTLSTORSTRUCTSUB FLR
TT>BTELTHRUTJITOTOWTPTSTATTVTYP
UNFINUGUNO
VACVCTVERTVB
WW/WBWCWDWNDWW/OWPW/RWTWWF
YD
PlatePlastic LaminatePlywoodPanelPaintPrefabricatedPrefinishedPounds per Square FootPounds per Square InchParallel Strand LumberPointPaper Towel DispenserPolyvinyl ChloridePavement
Quantity
RiserRadiusReflected Ceiling PlanRoof DrainRedwoodRegardingReceptacleReferenceRefrigeratorReinforce(d), (ing)RequiredResilientRevision, RevisedRoomRough Opening
SanitaryScheduleSoap DispenserSquare FeetSupply GrilleSheetSheathingShowerSimilarStructual Insulated PanelSealantSlab on GradeSpecificationsStainless SteelSee Structural DrawingsStandardSteelStorageStructuralSubfloor
TreadTongue and GrooveTest BoreTelephoneThroughTruss Joist IncorporatedTop OfTop of WallToilet Paper DispenserThermostatTelevisionTypical
UnfinishedUndergroundUnless Noted Otherwise
Vacuum OutletVinyl Composite TileVerticalVapor Barrier
WidthWithWhite BoardWater ClosetWoodWindowWithoutWaterproofWater ResistantWeightWelded Wire Fabric
Yard
ABBREVIATIONS
G0.0 COVER / GENERAL INFORMATION / SPECIFICATIONS
DRAWING INDEXGENERAL
ARCHITECTURALA1.1 PLANS, SECTION, DETAILSA1.2 WINDOWS & WINDOW DETAILS
MECHANICAL
ELECTRICAL
MD1.1 FIRST FLOOR PLAN - DEMOLITIONM2.0 BASEMENT PLAN - PIPINGM2.1 FIRST FLOOR PLAN - HVACM2.2 SECOND FLOOR / ROOF PLAN - PIPINGM3.1 MECHANICAL SCHEDULES & DETAILS
E1.0 BASEMENT PLAN - POWERE1.1 MAIN LEVEL PLAN - POWERE1.2 ROOF PLAN - POWERE1.3 ELECTRICAL SCHEDULES & DETAILS
CIVILNOT APPLICABLE
STRUCTURALNOT APPLICABLE
GENERAL NOTES1. Do not scale drawings. If critical dimensions do not appear on the drawings, notify the Architect.2. Contractor to field verify all dimensions and existing conditions prior to beginning work. Start of work indicates acceptance of existing
conditions.3. If discrepancies exist between drawings or between the drawings and the specifications, notify the Architect immediately for clarification.4. All dimensions are to face of framing, masonry or concrete wall, centerline of column, or finished floor, unless noted otherwise.5. Provide all components and accessories needed for a complete and finished installation. Coordinate with Owner on all "Owner-Provided"
equipment and furnishings. Coordinate all work with Subcontractors prior to beginning work.6. Provide blocking for all wall-mounted casework, millwork, grab bars, hardware, equipment, etc.7. Maintain a clean and safe work site at all times. No radios or music players allowed on site.8. All areas used for construction and staging shall be restored to their existing conditions upon project completion.9. All building entrances and stairwells are to remain open and unobstructed to allow access and egress at all times.10. Notify MSU Project Manager in writing of any expected disruptions in service or changes in construction schedule at least 72 hours in
advance.11. Do not block any roads, sidewalks or access to garbage dumpsters.12. Contractor is responsible for purchasing parking permits from MSU. Coordinate parking with MSU13. The specifications included are an integral part of these Construction Documents. It is the responsibility of the Contractor to review all
information.
Montana State UniversityP.O. Box 172760, Bozeman, MT 59717 Contact: Bill Mackin, 406.994.6377
PROJECT TEAMOWNER
ARCHITECT
MECHANICAL
Architecture 118, LLC115 East Oak Street, Bozeman, MT 59715Contact: Scott Hedglin, 406.599.7549
Consulting Design Solutions, Inc.7540 Churchill Road, Manhattan, MT 59741Contact: Curt Smit, 406.282.7082
ELECTRICALConsulting Design Solutions, Inc.7540 Churchill Road, Manhattan, MT 59741Contact: Scott Elders, 406.282.7082
HVAC Renovation and window replacement at southern end of first floor.
SUMMARY OF WORK
VICINITY MAP
PROJECT SITE
MSU - Culbertson Hall, Bozeman, MT
CODE INFORMATION
International Building Code (IBC) 2012International Existing Building Code 2012International Mechanical Code (IMC) 2012National Electrical Code (NEC) 2014Uniform Plumbing Code (UPC) 2012International Fire Code (IFC) 2012International Energy Conservation Code (IECC) 2012International Fuel Gas Code (IFGC) 2012ANSI A117.1
APPLICABLE CODES PROJECT INFORMATIONType of Project: HVAC Renovation &
Window ReplacementType of Construction: II-B (existing)Occupancy Group (Use): BAutomatic Sprinkler System: NoFire Alarm System: YesAffected Area: N/AOccupant Load: N/AExits Required: N/AExits Provided: No Change
Not ApplicablePARKING REQUIREMENTS
HAZARDOUS MATERIALSNOTICE:1. SOME AREAS OF JOHNSTONE COMPLEX HAVE BEEN TESTED FOR ASBESTOS. FULL REPORTS ARE AVAILABLE AT MSU WORK CONTROL / FACILITIES. SUMMARY:
A. FLOOR TILE & MASTIC - KNOWN ASBESTOS CONTENTB. CARPETING - BLACK MASTIC UNDER CARPET - KNOWN ASBESTOS CONTENTC. WINDOW GLAZING CAULK (WINDOW PUTTY) - KNOWN ASBESTOS CONTENTD. PIPE INSULATION - KNOWN ASBESTOS CONTENTE. PLASTER CEILING & WALLS - UNKNOWN
2. SPECIFIC MATERIALS WITHIN THE PROJECT LIMITS HAVE NOT BEEN TESTED FOR ASBESTOS. IF SUSPECT MATERIALS ARE ENCOUNTERED, DO NOT DISTURB AND NOTIFY MSU PROJECT MANAGER IMMEDIATELY .
SPECIFICATIONSDIVISION 00: SEE PROJECT MANUAL - BY MSUDIVISION 01: SEE PROJECT MANUALDIVISION 02: EXISTING CONDITIONS024100 SELECTIVE DEMOLITIONA. Items indicated to be removed and salvaged remain Owner's property. Carefully detach from existing construction, in a manner to
prevent damage, and deliver to Owner.B. Owner will occupy portions of building immediately adjacent to work area. Conduct work activities so Owner's operations will not be
disrupted. All work, material storage, and staging shall occur within Construction Limits shown (except incidental work in adjacent areas).
C. Protect walls, ceilings, floors, and other existing finish work that are to remain. Cover and protect, furniture, furnishings, and equipment that have not been removed.
D. Patch and repair existing surfaces as needed.E. Neatly cut openings and holes plumb, square, and true to dimensions required. Use cutting methods least likely to damage construction
to remain or adjoining construction.F. Remove demolition waste materials from Project site.G. Clean construction area at conclusion of work. Return construction area to cleanliness existing before work began.H. Complete MSU standard form 097 "Project Close-out Checklist" prior to application for final payment.
DIVISION 06: WOOD, PLASTICS, AND COMPOSITES062000 FINISH CARPENTRYA. Material: Paint-grade softwood lumber. Kiln-dried.B. Profiles: Standard profiles that are substantially similar to profiles indicated on drawings.C. Install finish carpentry level, plumb, true, and aligned with adjacent materials. Scribe and cut to fit adjoining work. Refinish and seal
cuts.D. Install standing and running trim with minimum number of joints practical, using full-length pieces from maximum lengths of lumber
available. Do not use pieces less than 24 inches long except where necessary. Stagger joints in adjacent and related trim. Cope at returns and inside corners and miter at outside corners.
064023 INTERIOR ARCHITECTURAL WOODWORKA. Quality Standard: Architectural Woodwork Institute's "Architectural Woodwork Quality Standards."B. Materials: Custom grade, pine or poplar suitable for paint.C. Installation: Install to comply with referenced standard. Install level, plumb, true, and straight. Scribe to fit adjoining work.
DIVISION 07: THERMAL AND MOISTURE PROTECTION075000 MEMBRANE ROOFINGA. Patch roof assembly as needed matching existing materials.B. Existing roof warranty shall be maintained. Provide manufacturer’s written warranty upon completion of roof work.C. Contact for more information (provided by MSU): Bill Mackin, 406-994-6377.079200 JOINT SEALANTSA. Compatibility: Provide sealants, joint fillers, and other related materials that are compatible with one another and with joint substrates.B. Sealant for General Exterior Use: Single-component, neutral-curing silicone, ASTM C920, Type S, Grade NS, Class 25, for Use NT.
Sikaflex-1A; color:C. Sealant for General Interior Use: Single-component, mildew-resistant sealant, ASTM C920, Type S, Grade NS, Class 25, for Use NT.D. Comply with ASTM C1193. Sonolastic NP1; color:E. Do not proceed with installation when ambient and substrate temperatures are outside limits permitted by joint-sealant manufacturer or
are below 40 degrees F.
DIVISION 08: OPENINGS085113 ALUMINUM WINDOWSA. Submittals: Provide Product Data, and Shop Drawings.B. Product: All windows shall be Gerkin Windows & Doors (gerkin.com; 800-475-5061) or Prior Approved Equal similar to existing windows
at west facade of Culbertson Hall.a. Horizontal Sliders: 5045 Series. Sizes as indicated on drawings. Clear anodized aluminum finish (Class I), AAMA 611.b. Fixed: 5500 Series. Sizes as indicated on drawings. Clear anodized aluminum finish (Class I), AAMA 611.
C. Operable Panels: As indicated on drawings.D. Screen: Aluminum mech insect screen at operable panels. Tamper-proof fasteners.E. Glazing: Clear, insulated glass. 1 inch overall thickness. Low-E 366. Window Manufacturer's standard glazing.F. Set units level, plumb, and true to line. Provide proper support and anchor securely in place.G. Set sill members in bed of sealant to provide weathertight construction.H. Install windows and components to drain condensation, water that has penetrated any joints, and moisture migrating within the assembly
to the exterior.I. Adjust operable panels for smooth operation and weathertight closure. Lubricate hardware.J. Remove non-permanent labels and clean all surfaces including glazing.088000 GLAZINGA. Insulating-Glass Certification Program: Provide certification label of IGCC.B. Safety Glazing Labeling: Permanently mark glazing with certification label of the manufacturer. Label shall indicate type of glass,
thickness, and safety glazing standard with which glass complies.C. Warranty: Manufacturer's standard 10-year written warranty.D. Comply with the combined recommendations of manufacturers of glass, sealants, gaskets, and any other glazing materials, unless more
stringent requirements are contained in GANA's "Glazing Manual."E. Replace all glass that has been broken, chipped, cracked, or damaged during construction.F. Remove non-permanent labels and clean all surfaces.
DIVISION 09: FINISHES092900 GYPSUM BOARDA. Material: Interior Gypsum Board, ASTM C1396 / C1396M, Type XB. Thickness: 5/8 inch.C. Edges: Tapered.D. Trim Accessories: ASTM C 1047. Provide cornerbead at outside corners. Accessories as noted on drawings.E. Joints: Paper tape. Ready-mixed, all-purpose joint compound.F. Installation: ASTM C 840. Level 4 finish.095100 ACOUSTICAL CEILINGS - ADDITIVE ALTERNATE #1A. Ceiling Tile: Armstrong "Georgian" #763, or match existing tile in Room 100, or approved substitution.B. Color: White.C. Edge Detail: Square.D. Thickness: 5/8 inch.E. Modular Size: 24 by 48 inches.F. Suspension System: Armstrong "Prelude," 15/16 inch, white, direct hung, ASTM C635, heavy duty.099100 PAINTINGA. Materials: 2-coat PPG Speedhide Latex over compatible primer, or approved substitution.B. Colors: As selected by Architect from Manufacturer's standards.C. Finish: As selected by Architect from Manufacturer's standards.D. Comply with recommendations in MPI's "MPI Architectural Painting Specification Manual" applicable to substrates encountered.
ADDITIVE ALTERNATE #1 (ADD ALT #1):PROVIDE COMPLETE MECHANICAL HEAT RECOVERY VENTILATION SYSTEM AND ALL ASSOCIATED WORK (INCLUDING BUT NOT LIMITED TO: CEILING, LIGHTING, WINDOW, WALL WORK, MECHANICAL EQUIPMENT & DUCTWORK, ELECTRICAL WORK) AS SHOWN (ROOM 100B). MODIFY CEILING AND LIGHTING AS SHOWN. PROVIDE WINDOW TYPE (W6).
ALTERNATE(S)
0"
1"
2"
SHEET
DRAWN BY
REVIEWED BY
1/24
/201
7 5:
48:2
0 PM G0.0
PPA # 15-0079
HV
AC
IM
PR
OV
EM
EN
T &
WIN
DO
WR
EP
LA
CE
ME
NT
JAN. 24, 2016
STH
STH
A118: 15-070
CU
LB
ER
TSO
N H
AL
L
REV DESCRIPTION DATE
DN
A1.2 1
A1.2
2
A1.23
A1.2
4
CLASSROOM101
BULKMAIL103
STORAGE103A
STORAGE101B
STORAGE101A
JANITOR113CU
BATHROOM115RR
OFFICE116
OFFICE114
BREAKROOM100B
MAILSERVICES
100
CLERKOFFICE100A
VESTIBULE199VE
HALLWAY199CO
HALLWAY198CO
STAIRWELL199S1
W5
W6
W7
W4
W3
W2 W1
3A1.1
ADD ALT #1: MODIFY CEILING FOR NEW HRV UNIT
REMOVE (E) WINDOWS & PREP OPENINGS FOR NEW WINDOWS- TYP
NOTES: 1. COORDINATE w/ OWNER ON REMOVAL OR
DISTURBANCE OF (E) VEGETATION.2. REPAIR LANDSCAPING AS NEEDED.
ADD ALT #1: ALIGN FACE OF (N) GWB SOFFIT w/ RETURN @ WINDOW
(E) PLASTER CEILING TO REMAIN (+/- 8'-6" A.F.F.)
ADD ALT #1: PATCH (E) CEILING AS NEEDED
(N) 2x4 ACT (+/- 7'-6" A.F.F.)
ADD ALT #1: (N) GWB (3-5/8" METAL FRAMING) HEADER (+/- 7'-5" A.F.F.)
CONCEAL PIPING IN WALL CAVITY-DEMO/PATCH/REPAIR WALL AS NEEDED
ADD ALT #1: PROVIDE CLOSURE- re: DETAIL
NOTE:COORDINATE ALL WORK OCCURING IN ROOM 103 DURING MONTH OF JULY w/ OCCUPANT-RESTRICTIONS MAY APPLY
7'-4"
F.V
.
CONCEAL PIPING IN WALL CAVITY-DEMO/PATCH/REPAIR WALL AS NEEDED
CONCEAL PIPING & WIRING IN WALL CAVITY-COORDINATE LOCATION w/ (E) ELECTRICAL, (E) PIPE, (E) BASEBOARD HEATER, AND TUNNEL BELOW- DEMO WALL AS NEEDED- PROVIDE FULL HEIGHT PLYWOOD COVER PANEL w/ BEVELED EDGES & DECORATIVE FASTENERS FOR FUTURE ACCESS- PAINT
APPROX LINE OF TUNNEL BELOW
ADD ALT #1: COORDINATE PENETRATIONS THRU WALL w/ HVAC- re: MECH
REMOVE (E) WINDOWS & PREP OPENINGS FOR NEW WINDOWS- TYP
REMOVE (E) WINDOWS & PREP OPENINGS FOR NEW WINDOWS- TYP
REMOVE (E) WINDOWS & PREP OPENINGS FOR NEW WINDOWS-TYP
ADDITIVE ALTERNATE #1:PROVIDE COMPLETE MECHANICAL HEAT RECOVERY VENTILATION SYSTEM AND ALL ASSOCIATED WORK (INCLUDING BUT NOT LIMITED TO: CEILING, LIGHTING, WINDOW, WALL WORK, MECHANICAL EQUIPMENT & DUCTWORK, ELECTRICAL WORK) AS SHOWN (ROOM 100B). MODIFY CEILING AS SHOWN. PROVIDE FIXED WINDOW UNIT (W6).
3A1.1
BUILDING MOVEMENT JOINT
NEW MECH EQUIP on NEW ROOF CURB- re: MECH- PATCH & REPAIR ROOF MEMBRANE
(E) 60-MIL, FULLY-ADHERED EPDM ROOF
LINE OF WALL BELOW
LINE
OF S
TRUC
TURE
BEL
OW
10'-8
" (10
'-0" M
IN)
5'-4"
(E) EXHAUST FAN TO REMAIN
FUTURE MECH. UNITS (APPROX).
LINE
OF S
TRUC
TURE
BEL
OW
PROVIDE (5) 30"x30" WALKWAY PADS-COMPATIBLE w/ (E) ROOF MEMBRANE-COORDINATE FINAL LOCATION w/ ARCHITECT/ENGINEER
ENTRY FLOOR100'-0"
1ST FLOOR101'-9"
BASEMENT93'-9"
STEAM ROOM91'-0"
2ND FLOOR110'-7"
2'-9"
6'-3"
1'-9"
8'-10
"8'-
10"
11'-5
"
3RD FLOOR119'-5"
DIRT FLOOR AREA
BSMT AREA TUNNEL AREA
BUILDING MOVEMENT JOINT
NEW MECH EQUIP on NEW ROOF CURB AREA
CONCEAL PIPING & WIRING IN (E) WALL
CONCEPTUAL ROUTING OF PIPING
9'-10
"
HALLWAY199CO
MAILSERVICES
100
CLASSROOM101
CONCEPTUAL ROUTING OF PIPING
1"5"
COOR
D. w
/ HVA
C
1'-11
"
(E) STRUCTURE
(N) A.C.T. SYSTEM
(N) HEADER-5/8" TYPE 'X' GWB on3-5/8" METAL FRAMING
(E) SUSPENDED PLASTER CEILING TO REMAIN
WD TRIM- PAINT
ALUMINUM WINDOW SYSTEM w/ SUBFRAME & 1" INSUL ALUM PANEL-
CAULK PERIMETER- TYP
(E) STRUCTURE
(E) PLASTER WALL ASSEMBLY
SEALANT
HVAC DUCT & LOUVER- re: MECH
REMOVE (E) METAL SILL
(N) A.C.T. CEILING- COORDINATE HEIGHT w/ HVAC DUCT ROUTING
INFILL w/ GWB on METAL FRAMING
(E) STONE MASONRY- DO NOT DISTURB
REMOVE (E) PLASTER CEILIING- re: FLOOR PLAN
(E) STEEL LINTEL- DO NOT DISTURB
NOTES:1. REVIEW CONDITIONS w/ ARCHITECT AT COMPLETION OF
DEMOLITION2. SEE WINDOW DETAILS FOR ADDITIONAL INFORMATION
SEALANT w/ BACKER ROD
ALUMINUM WINDOW SYSTEM w/ SUBFRAME-CAULK PERIMETER, BOTH SIDES- TYP
(E) INTERIOR WALL
INFILL w/ GWB on METAL FRAMING
ROOM 100B
ROOM 100
SEALANT- ALL EDGES
STONE MASONRY BELOW
NOTES:1. REVIEW CONDITIONS w/ ARCHITECT AT COMPLETION OF
DEMOLITION2. SEE WINDOW DETAILS FOR ADDITIONAL INFORMATION
1" INSUL METAL PANEL
LINE OF (E) CONDITIONS TO BE REMOVED (HEAD & SILL)
0"
1"
2"
SHEET
DRAWN BY
REVIEWED BY
1/24
/201
7 5:
48:1
8 PM A1.1
PPA # 15-0079
HV
AC
IM
PR
OV
EM
EN
T &
WIN
DO
WR
EP
LA
CE
ME
NT
JAN. 24, 2016
STH
STH
A118: 15-070
CU
LB
ER
TSO
N H
AL
L
1/8" = 1'-0"1 1ST FLOOR
1/8" = 1'-0"2 ROOF PLAN
1/8" = 1'-0"3 CONCEPTUAL BUILDING SECTION
N
1 1/2" = 1'-0"4 ADD ALT #1 - HEADER & SOFFIT 1 1/2" = 1'-0"5 ADD ALT #1 - HVAC & WINDOW AT STONE
1 1/2" = 1'-0"6 ADD ALT #1 - PLAN DETAIL @ (E) WALL / WINDOW INTERFACE
REV DESCRIPTION DATE
22'-3" F.V.
EQ EQ EQ EQ EQ EQ EQ
1'-6"
F.V
.
W2ALUM
W5ALUM
W4ALUM
9'-2" F.V.
EQ EQ EQ EQ EQ
1'-6"
F.V
.
W6ALUM
6'-3"
F.V
.
1'-6"
4'-9"
EQ EQ EQ EQ EQ4'-1" F.V.
W1ALUM
6'-3"
F.V
.
1'-6"
4'-9"
13'-0" F.V. 9'-2" F.V.
EQ EQ EQ EQ EQ
1'-6"
F.V
.
W7ALUM
ADD ALT #1: 1" INSUL ALUM PANEL (MAPES or SIM, MATCH WINDOW FINISH)- COORDINATE w/ MECH LOUVER
FIXED FIXED SLIDER
FIXED FIXED FIXED FIXED FIXED
SLIDER SLIDER SLIDER SLIDER SLIDERSLIDER
SLIDER FIXED SLIDER
FIXED
SLIDER FIXED SLIDER
W3ALUM
2'-0" F.V.
3'-4"
F.V
.
FIXE
D
2'-0" F.V.
4'-8"
F.V
.
FIXE
D
BASE BID: MATCH WINDOW TYPE W7
W3 W4NIC NIC NIC NIC NIC NIC NICNIC
REUSE (E) LOUVER PENETRATION- SEE MECH
REMOVE (E) EXHAUST FAN
NICNIC
STONE VENEER WALL
W5
STONE VENEER WALL
W6 W7W1 W2
(E) DOOR TO REMAIN
ALUMINUM WINDOW SYSTEM w/ SUBFRAME- CAULK PERIMETER, BOTH SIDES- TYP
(E) FINISH TO REMAIN
(E) STRUCTURE(E) PLASTER WALL ASSEMBLY
SHIMS & LOW-PRESSURE EXPANDING FOAM INSULATION
LINE OF (E) CONDITIONS TO BE REMOVED- NEW SYSTEM TO CONCEAL JOINT LINE
SEALANT w/ BACKER ROD
PATCH/REPAIR/INFILL AS NEEDED-MATCH (E) ADJACENT SURFACE1/8"x3/4" ALUM PLATE TRIM
1/2"
ALIG
N
(E) STEEL LINTEL- DO NOT DISTURB
(E) PLASTER CEILING TO REMAIN
(E) STRUCTURE
SHIMS & LOW-PRESSURE EXPANDING FOAM INSULATION
SEALANT w/ BACKER RODPATCH/REPAIR/INFILL AS NEEDED-MATCH (E) ADJACENT SURFACE1/8"x3/4" ALUM PLATE TRIM
1/2"
ALUMINUM WINDOW SYSTEM w/ SUBFRAME- CAULK PERIMETER, BOTH SIDES- TYP
LINE OF (E) CONDITIONS TO BE REMOVED- NEW SYSTEM TO CONCEAL JOINT LINE
(E) STONE MASONRY-DO NOT DISTURB
ALIG
N
ALUMINUM WINDOW SYSTEM w/ SUBFRAME- CAULK PERIMETER, BOTH SIDES- TYP
(E) FINISH TO REMAIN
(E) STRUCTURE(E) PLASTER WALL ASSEMBLY
SHIMS & LOW-PRESSURE EXPANDING FOAM INSULATION
LINE OF (E) CONDITIONS TO BE REMOVED- NEW SYSTEM TO CONCEAL JOINT LINE
SEALANT w/ BACKER ROD
PATCH/REPAIR/INFILL AS NEEDED-MATCH (E) ADJACENT SURFACE1/8"x3/4" ALUM PLATE TRIM
1/2"
ALIG
N
ALUMINUM WINDOW SYSTEM w/ SUBFRAME- CAULK PERIMETER, BOTH SIDES- TYP
(E) METAL SILL TO REMAIN
(E) STRUCTURE(E) PLASTER WALL ASSEMBLY
SHIMS (SET IN SEALANT) & LOW-PRESSURE EXPANDING FOAM INSULATION
LINE OF (E) CONDITIONS TO BE REMOVED- NEW SYSTEM TO CONCEAL JOINT LINE
ALUM 'Z' FLASHING- MATCH WINDOW ASSEMBLY
1/8"x3/4" ALUM PLATE TRIMSEALANT
(E) STONE MASONRY-DO NOT DISTURB
ALUMINUM WINDOW SYSTEM w/ SUBFRAME- CAULK PERIMETER-TYP
(E) METAL SILL TO REMAIN
(E) STRUCTURE(E) PLASTER WALL ASSEMBLY
SHIMS (SET IN SEALANT) & LOW-PRESSURE EXPANDING FOAM INSULATION
LINE OF (E) CONDITIONS TO BE REMOVED- NEW SYSTEM TO CONCEAL JOINT LINE
1/8"x3/4" ALUM PLATE TRIM
ALUMINUM WINDOW SYSTEM w/ SUBFRAME- CAULK PERIMETER, BOTH SIDES- TYP
(E) FINISH TO REMAIN
(E) STRUCTURE(E) PLASTER WALL ASSEMBLY
SHIMS & LOW-PRESSURE EXPANDING FOAM INSULATION
LINE OF (E) CONDITIONS TO BE REMOVED- NEW SYSTEM TO CONCEAL JOINT LINE
SEALANT w/ BACKER RODPATCH/REPAIR/INFILL AS NEEDED-MATCH (E) ADJACENT SURFACE1/8"x3/4" ALUM PLATE TRIM
(E) STONE MASONRY-DO NOT DISTURB
ALIG
N
1/2"
0"
1"
2"
SHEET
DRAWN BY
REVIEWED BY
1/24
/201
7 5:
48:1
9 PM A1.2
PPA # 15-0079
HV
AC
IM
PR
OV
EM
EN
T &
WIN
DO
WR
EP
LA
CE
ME
NT
JAN. 24, 2016
EML
STH
A118: 15-070
CU
LB
ER
TSO
N H
AL
L
1/4" = 1'-0"5 WINDOW TYPES
1/8" = 1'-0"1 WEST
1/8" = 1'-0"2 SOUTH 1/8" = 1'-0"3 EAST
1/8" = 1'-0"4 NORTH
3" = 1'-0"6 HEAD - TYP 3" = 1'-0"9 HEAD @ STONE
3" = 1'-0"7 JAMB - TYP
3" = 1'-0"8 SILL - TYP 3" = 1'-0"11 SILL @ STONE
3" = 1'-0"10 JAMB @ STONE
REV DESCRIPTION DATE
225
DESCRIPTION DESCRIPTION
AMPS POLES WATTS # A B C # WATTS AMPS POLES20 1 (E) DOCK HOIST 1 0 2
20 1 (E) RM 103 N OUTLETS 3 0 4
20 1 HRV1-1 (ALTERNATE BID) 252 5 252 6
20 1 EDH1-1 (ALTERNATE BIT) 1512 7 1512 8
20 2 FCU1-1, FCU1-2, FCU 1-3, FCU1-4, FCU1-7, BS1-2 300 9 300 10
- - ---- 300 11 300 12
20 2 FCU1-5, FCU1-6, BS1-1 250 13 250 14
- - ---- 250 15 250 16
45 3 CU1-1 2516 17 2516 18
- - ---- 2516 19 2516 20
- - ---- 2516 21 2516 22
20 1 RCPT: ROOF SERVICE 180 23 180 24
25 0 26
27 0 28
29 0 30
31 0 32
33 0 34
35 0 36
37 0 38
39 0 40
41 0 42
4278 3066 3248
TOTAL LOADS: 10592 WATTS
DEMAND:
29 AMPS
(EXISTING) PANEL '00' AMPS MLO 208Y/120V VOLT 3 PHASE 4 WIRE FLUSH MOUNTING