ZTE USapphire Container
Data Center Production
Description
CDC6240
ZTE USapphire Container Data Center Production Description
ZTE Confidential & Proprietary 1
ZTE USapphire Container Data Center Production
Description
Version Date Author Reviewer Notes
V1.0 2016/05/12 Draft
© 2017 ZTE Corporation. All rights reserved.
ZTE CONFIDENTIAL: This document contains proprietary information of ZTE and is not to be disclosed or used
without the prior written permission of ZTE.
Due to update and improvement of ZTE products and technologies, information in this document is subjected to
change without notice.
ZTE USapphire Container Data Center Production Description
2 ZTE Confidential & Proprietary
TABLE OF CONTENTS
1 Overview ............................................................................................................ 5
2 Standard ............................................................................................................. 6
3 CDC 6240 Introduction ...................................................................................... 8
3.1 Datasheet ............................................................................................................ 8
3.2 Specification ........................................................................................................ 9
3.2.1 Structure .............................................................................................................. 9
3.2.2 Power Supply ..................................................................................................... 12
3.2.3 Air Condition ...................................................................................................... 15
3.2.4 Monitoring System ............................................................................................. 16
3.2.5 Fire Extinguishing System .................................................................................. 19
3.2.6 Grounding .......................................................................................................... 21
3.2.7 Lighting System ................................................................................................. 22
3.2.8 Cable and pipe route .......................................................................................... 23
4 Component Introduction ................................................................................. 24
4.1 Cabinet .............................................................................................................. 24
4.2 Power Supply and Distribution System .............................................................. 26
4.2.1 PDU ................................................................................................................... 26
4.2.2 UPS ................................................................................................................... 27
4.2.3 Battery ............................................................................................................... 28
4.3 Air Condition ...................................................................................................... 29
4.4 Monitor system .................................................................................................. 31
4.4.1 Collector ............................................................................................................ 31
4.4.2 Monitor server .................................................................................................... 31
4.4.3 Switch ................................................................................................................ 32
4.4.4 Water Sensor ..................................................................................................... 32
4.4.5 NVR ................................................................................................................... 33
4.4.6 IP camera .......................................................................................................... 34
4.5 Access Control System ...................................................................................... 35
4.5.1 Access controller................................................................................................ 35
4.5.2 Card Reader ...................................................................................................... 36
4.6 Fire Extinguishing System .................................................................................. 37
4.7 Installation on site .............................................................................................. 38
ZTE USapphire Container Data Center Production Description
ZTE Confidential & Proprietary 3
FIGURES
Figure 3-1 Front side ............................................................................................................. 9
Figure 3-2 Back side ............................................................................................................10
Figure 3-3 Right Side............................................................................................................10
Figure 3-4 Left Side ..............................................................................................................10
Figure 3-5 in Side .................................................................................................................10
Figure 3-6 Power Rack .........................................................................................................12
Figure 2-7 Power Diagram ...................................................................................................13
Figure 3-8 Air Condition Layout ............................................................................................15
Figure 3-9 Access Control and Video Surveillance System ..................................................16
Figure 3-10 Monitor Box .......................................................................................................17
Figure 3-11 Monitoring System Diagram ..............................................................................18
Figure 3-12 PC web user interface (WebUI) .........................................................................19
Figure 3-13 Fire Extinguishing System 1 ..............................................................................19
Figure 3-14 Fire Extinguishing System 2 ..............................................................................20
Figure 3-15 Ground Points ...................................................................................................21
Figure 3-16 Lighting System .................................................................................................22
Figure 3-17 Humidifier Inlet Pipe and Condensation Water Outlet Pipe ................................23
Figure 3-18 Power Cable and Signal Cable Inlet ..................................................................24
Figure 4-1 Cabinet Dimension 1 ...........................................................................................24
Figure 4-2 Cabinet Dimension 2 ...........................................................................................25
Figure 4-3 PDU ....................................................................................................................26
Figure 4-4 UPS.....................................................................................................................27
Figure 4-5 Battery .................................................................................................................28
Figure 4-6 Air Condition Indoor Unit .....................................................................................29
Figure 4-7 Air Condition Outdoor Unit ...................................................................................30
Figure 4-8 Collector ..............................................................................................................31
Figure 4-9 Monitor Server .....................................................................................................31
Figure 4-10 Switch ...............................................................................................................32
ZTE USapphire Container Data Center Production Description
4 ZTE Confidential & Proprietary
Figure 4-11 Water Sensor ....................................................................................................32
Figure 4-12 Network Video Recorder ...................................................................................33
Figure 4-13 Camera .............................................................................................................34
Figure 4-14 Access Controller ..............................................................................................35
Figure 4-15 Card Reader ......................................................................................................36
Figure 4-16 Fire Extinguishing Controller..............................................................................37
Figure 4-17 Installation flow ..................................................................................................38
ZTE USapphire Container Data Center Production Description
ZTE Confidential & Proprietary 5
1 Overview
This document describes the CDC6240 all in one container data center product typical
configuration and application scenarios for marketing and Technical support people
reference.
Table 1-1 Abbreviation
Name Definition
CDC container data center
6240 40-ft
ZTE USapphire Container Data Center Production Description
6 ZTE Confidential & Proprietary
2 Standard
Design Specifications of the Electronic Information System Equipment Room
(GB50174-2008)
Fireproof Specifications of the Internal Decoration & Design of the Building (GB50222-95
(2001 Revised Version)
Fireproof specification s of the Construction Design (GB50016-2012)
Design Specifications of the Heating Ventilation & Air Conditioning (GB50019-2003)
Design Specifications of the Power Supply System (GB50052-2009)
Lighting Protection Specifications of the Construction Buildings (GB50057-2010)
Electronic Information System Lighting Protection Specifications of the Construction
Buildings (GB50343-2012)
Engineering Design Specifications of the Integrated Cabling System (GB50311-2011)
Design Specifications of the Gas Fire Distinguishing System (GB50370-2005)
Design Specification of the Automatic Alarm System for the Fire Disaster
(GB50116-2008)
Design Specifications of Configuring the Construction Distinguishers (GB50140-2005)
Construction Illumination Design Standard (GB50034-2004)
Construction and Acceptance Specifications of the Electronic Information System
Equipment Room (GB50462-2008)
Universal Specifications of the PC Site (GB/T2887-2011)
Construction and Acceptance Specifications of the Gas Fire Distinguishing System
(GB50263-2007)
Anti-static Engineering Technology Specifications (DG/TJ08-83-2009)
ZTE USapphire Container Data Center Production Description
ZTE Confidential & Proprietary 7
External Size and Rated Weight of the Container (GB1413-85)
Storage under the Electrical and Electronic product Application Environment Condition
(GB/T4798.1-2005)
Transportation under the Electrical and Electronic product Application Environment
Condition (GB/T4798.1-2008)
EMC Section 6-4: Radiation Standards for the Universal Standard Industry Environment
(EN 61000-6-4-2001)
Radio Disturbance Threshold and Measurement Methods of the Information Technology
Equipment (EN55022)
Acoustic, Description, Measurement and Evaluation of the Environment Noise (ISO
1996-1, ISO 1996-2, and ISO 1996-3)
Electrical Equipment of the Construction Buildings (IEC60364)
ZTE USapphire Container Data Center Production Description
8 ZTE Confidential & Proprietary
3 CDC 6240 Introduction
3.1 Datasheet
Table 3-1 Datasheet
Subsystem Equipment Specification
Structure
Container 12192mm(L)×2438mm(W)x 2896mm(H)
Protection level IP56
weight 20t with IT equipments
heat insulation
performance 60minutes
cabinet 600mm(W)×1000mm(D)x2000mm(H),42U
Operating
environment
Temperature cold aisle 10℃~30℃
Humidity 20%~80%
Ambient
environment
requirement
Temperature -40℃~55℃,air conditioner with low
temperature components optional
Humidity 5%~95%
Power supply
Power input Two 400A/3P,380V/50HZ
rack power density 6KW
UPS Modular UPS,N+1,100KVA
Battery backup time for 10 minutes
Air condition cooling capacity AC in-row, Max 23kw/pcs,3+1 backup
Refrigerant R410a
Fire
extinguishing
system
Type HFC-227ea/FM200
function
automatic fire detection
automatic alarming
automatic emergency gas release
overall fire resistance duration of 60 minutes
ZTE USapphire Container Data Center Production Description
ZTE Confidential & Proprietary 9
Monitor system
Access Controller &
Card Reader
1) access controller
It generate alarm when the door is forced
open, or door open overtime, and controller
forced open illegally, Infrared double
monitoring detection.
2) card reader with IC card input
IPC
IP camera with infrared Motion detection,
block alarm fuction.130M pixel, and 30m
coverage
NVR Network video recorder,1month storage,2 or
3 months optional
Temperature &
Humidity Sensor
Temperature scope:-10~70℃,Accuracy:±
1℃(FS)
Humidity scope:0~100%RH:accuracy±
3%RH(FS)
Water Sensor water leakage detection and alarm
3.2 Specification
3.2.1 Structure
Figure 3-1 Front side
ZTE USapphire Container Data Center Production Description
10 ZTE Confidential & Proprietary
Figure 3-2 Back side
Figure 3-3 Right Side
Figure 3-4 Left Side
Figure 3-5 in Side
ZTE USapphire Container Data Center Production Description
ZTE Confidential & Proprietary 11
Description:
1. The 40-feet container supports the marine transportation
2. The box body uses the galvanized steel, whose surface uses the three-layer of
paint and is coated with anti-solar radiation coatings.
3. The container exterior is made of 2mm thick steel plates, interior side use
50-mm-thick rock wool with a high melting point, interior bottom use 50-mm-thick
rock wool with a high melting point.
4. The equipment is configured with stainless steel doors that are used for the refined
marine fire-proof doors with double-sealing function. The size of the outlet door is
1200mm wide and 2150mm high, and the size of the inlet door is 900mm wide and
2150mm high. The door frames use the stainless steel, and the inner frame is filled
with rock wool for insulation, whose security level is A-level watertight security +
A-level fireproof and A-level anti-theft. The doorknob uses the protruding handles to
prevent the handles from being damaged during the process when the equipment is
transported in and out of the dock.
5. The equipment outside the box and the ingress/egress boxes have the waterproof
design, including access control, fire buttons, fire alarm lights, gas discharge
instructions, acoustic alarm, outdoor control switch, ingress/egress line pipes, and
air-conditioning pipes. The protection class reaches the IP56.
6. The bottom of the box uses the 5-mm-thick steel . The power cable, air-conditioning
cool media pipes, and humidification pipes in the internal of the box are routed on
the bridges on the bottom of the box. The bottom of the box is configured with the
single-direction floor drains to prevent the water from being gathered
ZTE USapphire Container Data Center Production Description
12 ZTE Confidential & Proprietary
7. The ground inside the box uses the load-bearing steel flooring, whose surface is
coated with permanent PVC.
8. The equipotential grounding is made for the whole part inside the box. After being
installed, all the equipment is connected to the equipotential grounding box, and
then to the container through the lead.
9. All the galvanized mesh bridges, optical fiber alignment bridges, and bridge
installation components are installed on top of the box.
10. The threaded lugs of the fixed cabinets are installed inside the corners of the box to
ensure the security of the land and sea transportation.
11. Small exhaust fans and dampers are configured. When the fire disaster takes place,
the eruption of the heptafluoropropane gas ensures that the fire should not be
leaked from the exhaust fan to the external to achieve full annihilation extinguishing.
In the case of no fire, the polluted air and hydrogen are discharged out of the room.
3.2.2 Power Supply
Figure 3-6 Power Rack
1
Power supply rack is putting at the end of the container .Two main power supply input or
one main power supply and one diesel Generator.
Output1 provide power supply to the air condition, lights, sockets, fire controller;
Output2 route into the UPS and provide power supply for IT racks PDU A/PDU B,
access controller, video;
ZTE USapphire Container Data Center Production Description
ZTE Confidential & Proprietary 13
The main input and branch output(optional)real time monitoring include power voltage,
power current, power factor, total consumption and so on;
The C level SPD with the maximum discharge current of 40 kA is installed in front of the
input of the power distribution rack.
Figure 3-7 Power Diagram
Table 3-2 Power Configuration
NO.(Part A) equipment
1 AC1 D32A/3P
2 AC2 D32A/3P
3 AC3 D32A/3P
4 AC4 D32A/3P
5 Light C10A/1P
6 Fan C10A/1P
7 Fire suppression C10A/1P
ZTE USapphire Container Data Center Production Description
14 ZTE Confidential & Proprietary
Table 3-3 Power Configuration
NO.(Part B) equipment
1 rack1a 40A/1P
2 rack2a 40A/1P
3 rack3a 40A/1P
4 rack4a 40A/1P
5 rack5a 40A/1P
6 rack6a 40A/1P
7 rack7a 40A/1P
8 rack8a 40A/1P
9 rack9a 40A/1P
10 rack10a 40A/1P
11 Reserved 40A/1P
12 Reserved 10A/1P
Table 3-4 Power Configuration
NO.(Part C) equipment
1 rack1b 40A/1P
2 rack2b 40A/1P
3 rack3b 40A/1P
4 rack4b 40A/1P
5 rack5b 40A/1P
6 rack6b 40A/1P
7 rack7b 40A/1P
8 rack8b 40A/1P
9 rack9b 40A/1P
10 rack10b 40A/1P
11 Reserved 40A/1P
12 Reserved 10A/1P
ZTE USapphire Container Data Center Production Description
ZTE Confidential & Proprietary 15
3.2.3 Air Condition
Figure 3-8 Air Condition Layout
3 42165 7 8
(1)(2)(3)(4)air condition indoor unit*4
(5)(6)(7)(8)air condition outdoor unit*4
Description:
1. The refrigeration system uses the in-row air-conditioning mode and regards the
environmental refrigerant R410a as refrigerant.
2. The in-row air-conditioning system sends the air in the front and returns the air on
the back. The G4-level filter that is convenient for exchange is installed and
equipped with the pressure sensors according to the design to detect the running
situation of the filter. It makes alarm and uploads the alarm to the alarm platform
when the filter is clogged or there are other blockage cases.
3. The front and rear doors of the in-row air-conditioning system are configured in
densely foramen mode. The opening rate is larger than 80%.
4. The direction of connecting the pipes of the refrigerant inside the in-row
air-conditioning system is downside under the rear bottom. The pipes are
connected to the outdoor machines of the air-conditioning system through the
hot/cool aisles to ensure that the operation space is sufficient between the
refrigerant piping with the internal structure parts inside the air-conditioning or the
base frames.
5. The in-row air-conditioning system can use the air blow/return mode to control the
ZTE USapphire Container Data Center Production Description
16 ZTE Confidential & Proprietary
temperature (that can be set on the site).
6. The in-row air-conditioning system uses the copper pipe aluminum fins, and the
hydrophilic fins are located in the suction side of the fan.
7. The indoor machines of the in-row air-conditioning system uses EC fans, and these
fans are evenly paved in the outlet. It can automatically adjust the fan rotation
according to the temperature of the return/supply air. Meanwhile, it supports the
manual speed adjustment mode. The outlet has the security shield so that it can be
disassembled easily and the fans can be easily maintained.
8. The rotation of the fans of the outdoor machines of the in-row air-conditioning
system should be able to automatically adjusted according to parameters such as
room temperature and condensing pressure to realize the more effective energy
saving effect, reduce the number of times when the fans are enabled, and improve
the reliability.
9. The in-row air-conditioning system has the power breakdown memory function. It
can be automatically enabled after being powered off exceptionally to restore its
running state before the power-off.
3.2.4 Monitoring System
Figure 3-9 Access Control and Video Surveillance System
1
2
3
(1) Card reader*1
(2)(3) IP cameral*2
ZTE USapphire Container Data Center Production Description
ZTE Confidential & Proprietary 17
Figure 3-10 Monitor Box
1
Table 3-5 Monitor Box Inside
Item Specification
switch Data Transmission to monitor server
collector
Collect information from temperature
&humidity sensor, league detector, air
condition,power distribution rack and transmit
to monitor server via switch.
Monitor server
manage container data center and can
display a real time status, and generate alarm
from power supply subsystem, environment
subsystem, security subsystem
NVR receives video from IP camera, save and
manage the video.
ZTE Container monitoring system has advantages of rich interface configuration, a
variety of alarm functions, open protocol interface, large-capacity data acquisition and
intelligent data storage and analysis ability. Embedded power management system can
manage and record power consumption of the entire rack service area, at the same time
external access through the network is allowed; Temperature, humidity, smoke detection
and monitoring and so on, are all integrated with the intrusion detection alarm system to
manage intensively, monitor remotely and ensure high reliability.
ZTE USapphire Container Data Center Production Description
18 ZTE Confidential & Proprietary
Figure 3-11 Monitoring System Diagram
Temperature&humidity League detection TACPDR Diesel Generator Fuel level sensorSmoke sensor
Fire detection&
suppression
Heat sensor
Collector
NVR IP camera UPS Alarm box
Switch
iDCIM server
ReaderIP camera
The monitoring system is mainly involved in the monitoring of environment, a variety of
power equipment, and security subsystem. The monitoring objects of each subsystem
are as follows:
1. iDCM
iDCM is management system deployed by ZTE to manage container data center and can
display a real time status, and generate alarm from power supply subsystem,
environment subsystem, security subsystem.
The iDCM support local control from PC or PAD (touch panel), remote control from web,
and collect information from each subsystem and transmit to NMS and send SMS and
email to the terminals. Each subsystem can connect to the iDCM through switch over
modbus, SNMP, and TCP/IP.
2. Power supply monitoring subsystem
Air cooled precise condition (TAC), UPS, PDR (power distribution rack), batteries.
3. Environment monitoring subsystem
Temperature and humidity sensors are installed in front side and back side of each IT
rack for monitoring the temperature and humidity, it is a rack level monitoring.
Water leakage senor is installed down the floor around the container interior for
ZTE USapphire Container Data Center Production Description
ZTE Confidential & Proprietary 19
monitoring the water leakage at bottom of the container.
4. Security Monitoring Subsystem
Access controller & card reader, IPC (IP camera), NVR (Network Video Recorder)
Figure 3-12 PC web user interface (WebUI)
3.2.5 Fire Extinguishing System
Figure 3-13 Fire Extinguishing System 1
1 2
3
ZTE USapphire Container Data Center Production Description
20 ZTE Confidential & Proprietary
1. cylinder*1
2. Gas extinguishing controller *1, emergency start and stop button*1, Manual or auto
switch*1
3. Access controller*1
Table 3-6 Fire Extinguishing Specification
Item Specification
Access controller Receive information from card reader and
control the secure and reliable access control
Gas extinguishing controller
Put in the monitoring rack, controls the gas
release and trig fire alarm, and install in
monitor rack
cylinder
consists of an extinguishing agent vessel, an
inlet pipe, a pressure enunciator, and a
solenoid valve driver, and gas
Figure 3-14 Fire Extinguishing System 2
31 2
1. (1) (2) smoker sensor *1/heater sensor*1
2. (3) Audible and visual alarm *1+ gas release indicator*1
Table 3-7 Fire Extinguishing Specification
Item Specification
ZTE USapphire Container Data Center Production Description
ZTE Confidential & Proprietary 21
Item Specification
gas release indicator
install at the top of the hot aisle and cold aisle
doors,When fire occur, the fire extinguishing
equipment releases extinguishing agent into
container and the
gas release indicator displays "DON'T
ENTER"
audible and visual alarm
next to the gas release indicator,When fire
occur, the audible and visual alarm generates
flash signals and audible signals
heat detector
install at both hot aisle and cold aisle. It
monitors the ambient temperature in real time.
It works with the red indicator blinks. When
the ambient temperature exceeds the alarm
threshold, it trigs alarm and
the red indicator is still on.
smoke detector
install at both hot aisle and cold aisle. It
monitors the ambient temperature in real time.
It works with the red indicator blinks. When
the smoke density exceeds the alarm
threshold, it trigs alarm and
the red indicator is still on.
3.2.6 Grounding
Figure 3-15 Ground Points
Ground point1
Ground point2 Ground point3
Ground point4
ZTE USapphire Container Data Center Production Description
22 ZTE Confidential & Proprietary
Ground Point
There are four ground points which are welded on the container. They should be welded
with earth ground, and the ground resistance should be less than or equal to 1Ω.
3.2.7 Lighting System
Figure 3-16 Lighting System
1
2
1. light*9
2. Emergency light*2
The lights are separated averagely at hot aisle and cold aisle, and switches are installed
near the door of both side. And also It has emergency lights installed on the top of door.
ZTE USapphire Container Data Center Production Description
ZTE Confidential & Proprietary 23
3.2.8 Cable and pipe route
Figure 3-17 Humidifier Inlet Pipe and Condensation Water Outlet Pipe
312
(1) Inlet pipe for AC humidifier
(2) Outlet pipe for condensation water.
(3) pipe for refrigerant
There are two pipe routes near the air condition condenser, one is inlet pipe for AC
humidifier and another is outlet pipe for condensation water.
There are 8 pipe routes from air condition condenser to AC indoor unit.
ZTE USapphire Container Data Center Production Description
24 ZTE Confidential & Proprietary
Figure 3-18 Power Cable and Signal Cable Inlet
1 2
(1) Main power cable routing
(2) Signal and fiber cable routing
4 Component Introduction
4.1 Cabinet
Figure 4-1 Cabinet Dimension 1
ZTE USapphire Container Data Center Production Description
ZTE Confidential & Proprietary 25
Figure 4-2 Cabinet Dimension 2
Table 4-1 Cabinet Dimension
height dimensions(mm) depth dimension(mm)
H1 H2 H3 T1 T2 T3 T4 T5
1998.5 1912 1774 1024 912 935 87 850
ZTE USapphire Container Data Center Production Description
26 ZTE Confidential & Proprietary
4.2 Power Supply and Distribution System
4.2.1 iPDU
Figure 4-3 iPDU
Table 4-2 PDU Specification
Item specification
input voltage/frequency 220VAC 50HZ
input rate 40A
output voltage/frequency 220VAC 50HZ
output rate 18*IEC C13,16A
dimensions(L*W*D) 1532*62*44mm
ZTE USapphire Container Data Center Production Description
ZTE Confidential & Proprietary 27
4.2.2 UPS
Figure 4-4 UPS
Table 4-3 UPS Specification
Item Specification
Capacity 105KVA (90KVA+15KVA)
module 15KVA
Power factor 0.8
Voltage 380V/220V
Frequency 50(1±0.5%)Hz
Efficiency 94%
Dimension(W*D*H) 600mm×2000mm×1000mm
Weight(kg) 200
ZTE USapphire Container Data Center Production Description
28 ZTE Confidential & Proprietary
4.2.3 Battery
Figure 4-5 Battery
Table 4-4 Battery Specification
Item Specification
Voltage (V) 12
Nominal Capacity (AH) 100
Quantity 40
Dimensions
(mm)
Width 173±1
Depth 330±3
Height 212±2
Terminal T11
Weight (kg) 31
Dimensions W x H x D 800mm x 2000mm x 1000 mm
ZTE USapphire Container Data Center Production Description
ZTE Confidential & Proprietary 29
4.3 Air Condition
Figure 4-6 Air Condition Indoor Unit
Table 4-5 AC Indoor Specification
Item Specification
Condition Return air37℃/ 24%RH,
Power system 380V 3Ph 50Hz
capacity(kW) 23.6
FLA - A 22.2
EC Fan performance
Air volume - m³/h 5000
Fan quantity 6
Humidifier performance
Humidifier capacity - kg/h 3
Pipe dimension
liquid pipe- mm 12.7
Gas pipe - mm 19
ZTE USapphire Container Data Center Production Description
30 ZTE Confidential & Proprietary
Item Specification
Condition Return air37℃/ 24%RH,
Humidifier inlet pipe G1/2"
Condensation water pipe - OD, mm 6
dimension(W*D*H) 300mm*1000mm*2000mm
Weight (kg) 150
Figure 4-7 Air Condition Outdoor Unit
Table 4-6 AC Outdoor Unit Specification
Item Specification
Compressor quantity 1
Outdoor unit FLA -A 15.3
Fan quantity 1
Outdoor unit dimensions(L*D*H) 1200mm*700mm*1250mm
Weight(kg) 120
ZTE USapphire Container Data Center Production Description
ZTE Confidential & Proprietary 31
4.4 Monitor system
4.4.1 Collector
Figure 4-8 Collector
Table 4-7 Collector Specification
Item specification
dimensions(W*H*D) 440mm*42.4mm*250mm
Form factor 1U
interface
15*RS485
1*RS232
1*10/100M
Power AC 100-240VAC/50-60Hz
weight <5kg
4.4.2 Monitor server
Figure 4-9 Monitor Server
Table 4-8 Monitor Server Specification
Item specification
ZTE USapphire Container Data Center Production Description
32 ZTE Confidential & Proprietary
Item specification
dimensions(W*H*D) 434mm*42.4mm*394mm
Form factor 1U
processors Xeon E3-1220
memory 1*4G DDR3
Hard disk 2*500GB
Power 250W
4.4.3 Switch
Figure 4-10 Switch
Table 4-9 Switch Specification
Item specification
Transmission
speed 10Mbps/100Mbps
Port 16*FE RJ45 + 2*GE Combo
dimension(H*W*D) 43.6mm*442mm*220mm
Power voltage and
frequency 100V~240V,50Hz~60Hz
Power
consumption 317W
weight 3.8kg
4.4.4 Water Sensor
Figure 4-11 Water Sensor
ZTE USapphire Container Data Center Production Description
ZTE Confidential & Proprietary 33
Table 4-10 Water Sensor Specification
Item Specification
Cable diameter 5.0mm
Sensing cable length 20m
conductor resistance 20Ω/100m
The maximum ambient temperature 85℃
Power voltage 12VDC
Power consumption 3W
4.4.5 NVR
Figure 4-12 Network Video Recorder
Table 4-11 Network Video Recorder Specification
Item Specification
dimensions(W*H*D) 445mm*45mm*290mm
chassis 1U
processors Xeon E3-1220
Hard disk 3TB
Port 2*SATA,1*eSATA
Power 40W
ZTE USapphire Container Data Center Production Description
34 ZTE Confidential & Proprietary
4.4.6 IP camera
Figure 4-13 Camera
Table 4-12 Camera Specification
Item Specification
Image Sensor 1/3" Progressive Scan CMOS
Max. Resolution 1280 x 960
Network Storage NAS (Support NFS,SMB/CIFS)
Communication Interface 1 RJ45 10M/100M Ethernet interface
Operating Conditions
-30 °C – 60 °C (-22 °F – 140 °F)
Humidity 95% or less (non-condensing)
Power Supply
12 V DC ± 10%
PoE (802.3af)
Power Consumption 5W
Ingress Protection level IP66
IR Range 30 meters
Weight 500g
ZTE USapphire Container Data Center Production Description
ZTE Confidential & Proprietary 35
4.5 Access Control System
4.5.1 Access controller
Figure 4-14 Access Controller
Table 4-13 Access Controller Specification
Item Specification
Communication protocol RS485、RS422、RS232、10/100M TCP/IP
Function
It generate alarm when the door is forced open, or door
open overtime, and controller forced open illegally,
Infrared double monitoring detection
Support max register 8100
Power supply 12VDC
Dimension(L*W*D) 215mm*180mm*30mm。
ZTE USapphire Container Data Center Production Description
36 ZTE Confidential & Proprietary
4.5.2 Card Reader
Figure 4-15 Card Reader
Table 4-14 Card Reader Specification
Item Specification
RF 13.56MHz±5%
Card reading Distance 20~60mm
Service life 350,000 times
Electric current ≤100mA
Power voltage 12VDC
dimension(W*H*D) 44mm*112mm*18mm
ZTE USapphire Container Data Center Production Description
ZTE Confidential & Proprietary 37
4.6 Fire Extinguishing System
Figure 4-16 Fire Extinguishing Controller
Approved to EN12094-1, EN54-2 and EN54-4
Three detection zones as standard
Any single zone or any combinations of zones can be configured to release
Configurable first stage sounder delays
Configurable detection delays
Zero time delay upon manual release option
Compatible with I.S. barriers
Non-latching zone input option to receive signals from other systems such as aspirating
equipment
Configurable extinguishant delays up to 60 seconds in 5 second steps
Configurable extinguishant duration up to 5 minutes in 5 second steps
Countdown timer shows time remaining until release
Supports up to seven, four wire status indicators
Built in Extract Fan control
ZTE USapphire Container Data Center Production Description
38 ZTE Confidential & Proprietary
4.7 Installation on site
Figure 4-17 Installation flow
1. Bury the grounding grid
2. Pour the cement foundation
3.Embed the water inlet pipes and
mains power pipes of the peripheral
air conditioning system
Lift the container and
connecting it with the dock
Put the container in its place
1.Weld the grounding grid
2.Inlet of power lines and weak
power lines
Install the rainproof shed and
stepping