GeneralSpecifications
YS1500Indicating Controller
Yokogawa Electric Corporation2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan
GS 01B08C02-01EN
GS 01B08C02-01EN©Copyright Jun. 2014 (YK)
1st Edition Jun.13, 2014 (YK)
n GENERALThe YS1500 Indicating Controller incorporates fundamental control functions required for PID control. Necessary func-tions can be selected in accordance with the user’s purpose. The available functions include those functions necessary for input signal processing, such as square root extraction and linear segment conversion, and feed-forward calculation.Single-loop, cascade and selector mode is also available.Standard models are smaller and lighter than earlier series, requiring less space for installation, and are compliant with international safety standards including the CE Mark and FM*, CSA* nonincendive (optional) approvals. For easy replacement of earlier controllers, models requiring the same panel cutout dimensions and depth as those of earlier mod-els are also offered. *: To be approved.
n FEATURES•Excellentlegibilitythankstoafull-dot,TFTLCD:Highvis-ibilityofthedisplayscreenisensuredevenindirectsunlightintheearlymorningandlateafternoon.Theusercanfreelyaccessadesiredoperationdisplayfrommeter,trenddisplay,bargraph,alarm,andeventdisplays.Allparameterscanbesetviathefrontpaneldisplay.
•Functionselectionmode(needsnoprogramming):Themulti-functioncontrollermodeallowscontroltobeselectedfromfrequentlyusedfunctions(single-loop,cascade,orselectorcontrol)withoutprogramming.Functionassign-mentstodigitalandanaloginputs/outputs(DIs,DOs,AIs,andAOs)canbedeterminedbyparametersettings.
•Fail-safe:ThankstodualCPU(oneforcontrolandonefordis-play),displayandmanualoperationsareenabledevenduringafailureofeitherCPU.ThehardmanualcircuitincorporatedindependentlyfromthedigitalcircuitsenablesthecontrolleroutputtobeadjustedmanuallyduringafailureofadigitalcircuitincludingbothCPUs.(Thehardmanualcircuitisnotincorporatedwhenthesuffixcode-2xxoptionisspecified.)
•Nonvolatilememoryformemorybackup:Nobatteryorca-pacitorisusedformemorybackup,facilitatingmaintenance.
•AC/DCdualpowersupplywithwideoperatingvoltagerangetoensurestabilityagainstsupplyvoltagefluctuations:CanbedrivenbyeitheranAC(100V)orDC(24V)powersup-ply.Furthermore,theDCpowersupplyenablesreceivingpowerwithoutpolarity.(Mustbespecifieduponorderingifusinga220VACpowersupply.)
•250mmdepth(forbasictypesonly)•Dust-andsplash-proofIP54faceplate(forbasictypeonly)
•CEMark(forbasictypeandYS100complianttypeonly)•FMNonincendiveexplosionprotection(optionalforbasic
type only) (Tobeapproved)•CSANonincendiveexplosionprotection(optionalforbasictype,compatibletypeforYS100(withYS100case))(Tobeapproved)
•Communication(optional)-Ethernet(Modbus/TCP;forbasictypeonly)-RS485(PCLink,ModbusandYSprotocol;unavailableforYS80internalunit-compatibletype)
-DCS-LCScommunication•CompatibilitywithYS100Series:Settingandcontrolopera-tionscanbedonewiththesamefeel.Forbasic-typecases,terminal-to-terminalpitchesdifferbutthesignal-to-terminalarrangement is almost the same.
Type Model and Suffix Codes (x: Depending on speci-
fications)
Analog Inputs Analog Outputs Digital Inputs and Outputs
(*1)1–5 V Direct inputs (*2) 1–5 V 4–20 mA
Basic type YS1500-x0x 4 - 2 1 6
CompatibletypeforYS100 YS1500-x2x(/Ax) 4 (3) (1) 2 1 6
CompatibletypeforYS80internalunit YS1500-x3x 4 - 2 1 6
CompatibletypeforEBSandI YS1500-x3x 4 - 2 1 6
CompatibletypeforEKandHOMAC YS1500-x3x 4 - 2 1 6
CompatibletypeforYS80(CompatiblesizeforYS80withYS100terminal)
YS1500-x4x(/Ax) 4 (3) (1) 2 1 6
Compatibletypefor100line(withYS100 terminal)
YS1500-x5x(/Ax) 4 (3) (1) 2 1 6
*1: EachcanbeusedaseitheraDIorDObyaparametersetting.*2: Onefromamongfouranaloginputscanbeusedforadirectinput(Option/Axwherex=01to08).
Functional
Enhancement
2
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 01B08C02-01EN Jun.13,2014-00
n DISPLAY AND SETTING FUNCTIONS
Display Functions(1) Display SpecificationsYS1500displaysarecomposedofthefollowingthreegroupsandtheindividualfunctionscanbesetupviadisplaysfortherespectivesettings:
Operationdisplays
LOOPdisplaysTRENDdisplaysALARMdisplaysDUALdisplayMETER displayFAILdisplay
Tuning displays
PIDsettingsSTC settingsParametersettingsInput/output data display
Engineer-ing
FunctionsettingsInputspecificationsettingsPasswordsettingLine-segmentcharacterizerfunctionsettingsOperationdisplaysettingsLCDsettingsCommunication settingsDI/DOsettings
(2) Operation DisplayslBar Graph Displays (in LOOP and DUAL displays)
Scaledivisions Upto20
Digitsofscalemarkings Upto7digits(includingdecimalpoint and sign)
Displaypositionofscalemarkings
At0%and100%positions
Units Upto7alphanumericcharacters
PVbargraphresolution 0.5%
SVpointerresolution 0.5%
Alarmsettingpointerresolution
0.5%
MVbargraphresolution 1.25%
PVoverflowdisplay Above100%
PVunderflowdisplay Below0%
lMeter Displays (in METER displays)
Scaledivisions Automaticsettingbasedonupperandlowerscalelimits(readingfactorcanbemodified).Scale graduation
Scale markings
Readingfactor
Digitsofscalemarkings
Upto4digits(includingdecimalpointand sign)
Displaypositionofscale markings
At0%and100%positions
Units Upto7alphanumericcharacters
PVpointerresolution 0.5%
SVpointerresolution 0.5%
Alarmsettingpointerresolution
0.5%
MVpointerresolution 1.25%
lTag Number and Digital Value Displays
Displaycharactersfortagnumbers
Alphanumericcharacters
Displaydigitsoftagnumbers
Upto12
DisplaydigitsofPVandSVdigitalindications
Upto7(includingdecimalpointandsign)
DisplaydigitsofMVdigitalindica-tions
Upto6(includingdecimalpointandsign)
lTrend Display Specifications Kinds of TRENDdis-plays
TREND1 Candisplaythetrendcurvesforthreevariables:PV1,SV1,andMV1.ThesePV1,SV1,andMV1curvescanbehiddenandshownindividually.ScalingcanbeperformedforPV1andSV1fordisplay.
TREND2 Candisplaythetrendcurvesforthreevariables:PV2,SV2,andMV2.ThesePV2,SV2,andMV2curvescanbehiddenandshownindividually.ScalingcanbeperformedforPV2andSV2fordisplay.
TREND3 CandisplayonthesamegraphthetrendcurvesoffourvariablesarbitrarilychosenbytheuserfromPV1,SV1,MV1,PV2,SV2,MV2,X1–X8,andY1–Y4.ScalingcanbeperformedforchosenPVsandSVsfordisplay.
lTrend Display Time Span1.5,7.5,15,or45minutes;or1.5,7.5,15,or45hours
lEvent Display SpecificationsTheeventdisplaymeansthatauser-definedmessagewill appear on the current operation display when a predefinedeventoccurs.TheeventdisplaycanbeclosedbypressingtheSHIFTkeyforthreesecondsandthemessagescanberedis-playedintheALARMdisplay.Uptofiveeventmessagescanbeset.Tousethiseventdisplayfunction,specifythemessagesandcorrespondingevents(flagstatuses)insidetheeventdisplaysettingsinYSS1000settingsoftware.
lManual SV and MV ChangesViaoperationdisplays,SVandMVcanbechangedus-ingkeysonthefrontpanel.
RateofmanualSVincrements/decrements
40seconds/fullscale
RateofmanualMVincrements/decrements
Normal:40seconds/fullscaleFASTmode:4seconds/fullscale
lDisplay during FailureThedisplayisautomaticallyswitchedtotheFAILdisplayuponafailure.Fordetails,seethe“Self-diagnostics”section.
3
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 01B08C02-01EN Jun.13,2014-00
Names of Elements
(1) Front Panel
No. Name1 ColorLCD,120×320pixels*1
2 FAILlamp(redLED)
3 ALMlamp(yellowLED)
4 C(cascade),A(automatic),andM(manual)modekeyswithrespectivemodeindicators(greenLEDforC,greenforA,yellowforM)
5 SVincreasekey
6 SVdecreasekey
7 PFkeyandLEDindicator
8 Pagekey
9 MVincreasekey
10 MVdecreasekey
11 Fastchange/SHIFTkey
12 Taglabel(advisablepositiontopaste)
*1Thebacklightbrightnesscanbeadjusted,andthebacklightcanbeturnedoff.
(2) Inner Panel behind Swing-up Front Panel
No. Name Remarks1 Computer link connector
(PROGRAMMER):Communicationcableconnectorusedwhendownloading,uploading,andview-ing the parameters using the YSS1000 SettingSoftwareforYS1000Series
2 ConnectorforYS110standbymanualstation(MANUALSTA)
ForconnectingtheYS110standbymanual station
3 Internal-unitreleaselever Usedwhendrawingouttheinternalunit
4 Hardmanualoperationwheel(HARDMANUAL)
Usedtosettheoutputlevel
5 MVbalancelamp(BAL[green])
Lightsupwhenthecontroloutputagreeswiththehardmanualoutputlevel.
6 Hardmanualselectorswitch(ON/OFF)
Usedtoswitchovertheoutput(MV)tothelevelsetbythehardmanualopera-tion wheel
7 Internal-unitfixingscrew Usedtopreventtheinternalunitfrombeingdrawnout
8 LEDandswitchforrepair Contactusforrepair.
②③
④
⑤
⑥
⑦
⑧
⑫
①
⑨⑩⑪
③⑤
⑥
④
①
②
⑦
⑧
Front PanelControl Output Backup (For suffix code -1xx)Thehardmanualwheelbehindthefrontpanelenablesmanual operations in an emergency.Outputbalancingbeforeaswitchoverfrom/tohardmanualispossible.Note:ConnectingtheYS110standbymanualstationenablestheinternalunittobereplacedwithoutinterruptingthe4–20mADCcontroloutput(Y1).(Replacementoftheinternalunit,however,shouldbeperformedbyaYokoga-waauthorizedserviceperson.)
4
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 01B08C02-01EN Jun.13,2014-00
n FUNCTION SPECIFICATIONS(1) Controller ModesThecontrollermodeisselectedfromsingle-loopmode,cascade mode, or selector mode.
Controller Mode Description
Single-loop mode Basiccontrolmodulepreassembledwithauxiliarycontrolfunctions
Cascade mode Cascadecontrolmodulepreassembledwithauxiliarycontrolfunctions
Selector mode Selectorcontrolmodulepreassembledwithauxiliarycontrolfunctions
(2) Control TypesThecontroltypecanbeselectedbyaparameterfromPID,PD,sample-and-holdPI,andbatchPID.
(3) Control ParametersCommon Parameters for PID, PD, Sample-and-hold PI,
Batch PID
Parameter Setting Range
Proportionalband,PB 0.1to999.9(%)
Integral time, TI (*1) 1 to 9999 (seconds)
Derivativetime,TD(*2) 0 to 9999 (seconds)
Parameters Specific to PD
Parameter Setting RangeFirst-orderlagtimeconstant(*3) 1 to 9999 (seconds)
Manual reset, MR –6.3to106.3(%)
Parameters Specific to Sample-and-hold PI
Parameter Setting Range
Sample period, STM 0 to 9999 (seconds)
Controltimespan,SWD 0 to 9999 (seconds)
*1: NeedsnosettingforPDcontrol.*2: Asettingfrom1to9999iseffectiveand0means
OFF.*3: Toavoidabruptchangesinoutputwhentheopera-
tionmodeischanged,follow-upactionstakeplacewithfirst-orderlagdelay.Settheparametertoanintegral time.
(4) Operation Modes•Operationmodeswitchingbydigitalinputs:Infunctionselectionmode,switchingfunctionscanbeassigned to digital inputs.Fordetails,seethe“FunctionAssignmentstoDigitalInputs”section.
•Digitaloutputsofoperationmodestatuses:Infunctionselectionmode,statusindicatingfunctionscanbeassignedtodigitalinputs.Fordetails,seethe“FunctionAssignmentstoDigitalOutputs”section.
(5) Control and Input/Output Calculation PeriodControl period 100 ms
Control Add-on FunctionsThefollowingfunctionscanbeaddedtocontrolactionsbysimpleparametersettings:
Adjustablesetpointfilters
Selftuning(STC)
Non-linearPIDcontrol
PIDcontrolwithresetbias
Outputlimiters
Alarmdetection
Remote cascade setpoint input
Auxiliary control functionsThefollowingfunctionscanbeaddedtocontrolactionsbysimpleparametersettings;however,theavailableadd-onfunctionsdifferdependingonthecontrollermode:
Single-loop Mode
Cascade Mode
Selector Mode
Feed-forwardcontrol
P P
Outputtracking P P P
PresetMV P P P
PVtracking P
SVtracking P
Operationmodeswitchingbydigitalinputs
P P P
Inputfilter P P P
Square-rootextrac-tion
P P P
Ten-segment linear-izerfunction
P P P
Ratio operation P P P
5
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 01B08C02-01EN Jun.13,2014-00
Communication FunctionsCommunication with Host SystemsCommunicationwithvarioushostsystemsincludingYokogawa’sDCSssuchastheCENTUMCS3000andprogrammablelogiccontrollerssuchastheFA-M3,issupported.
Host Sys-tem
Link Device in Host System
YS1700 Communication Functions
Option ProtocolCENTUMCS3000orVP
ALR121(directconnection)
RS-485(/A31) YS protocol
FA-M3 UTlinkmodule PClink
PLCorPCfromothervendors
RS-485 connection Modbus
Ethernet connection Ethernet(/A34) Modbus/TCP
•Communicationcapabilities:Readaccesstovariousmeasuredvalues,andreadandwriteaccesstovariousparametersispossible.Writeaccesscanbedisabled.
•Computermode:Inadditiontothepreviouslymentionednormaloperationmodes,therearetwooperationmodesforcontrolbyanhostsystem.InDDCmode,thecontroloutputMVisdi-rectlymanipulatedbythehostsystem.InSPCmode,thecontrolsetpointSVismanipulatedbythehostsystem.
•Backupmodeaftercommunicationfault:Themodeintowhichthecontrollershouldfallwhencom-municationwiththehostsystemhascontinuouslybeenlostforapresettimeperiod,canbeselectedbetweenMANorAUT.
Function Selection Mode – Input/Output Settings(1) Digital Inputs/Outputs (DI/DO) SettingsEachDI/DOterminalonthemainunitcanbeusedfreelyaseitheraDIorDO.
(2) Function Assignments to Digital InputsOneofthefollowingfunctionscanbeassignedtoeachDI.Availablefunctionsdifferdependingonthecontrollermodeasshowninthetable.
Controller modeFunction
Single-loop
Cascade Selector
CAS↔AUTOremoteswitching P
CAS/AUTO↔MANremote switching
P
Internal cascade connectionopen↔close
P
Second loop setpoint re-mote↔local
P
Loopselect(OFF=firstloop;ON=secondloop)
P
PresetMVoutputON↔OFF P P P
OutputtrackingON↔OFF P P P
PresetMVoutputONandmode=MAN
P P P
Self-tuningremoteON↔OFFswitching
P P P
Momentary trigger to change mode to M mode
P P P
Momentary trigger to change modetoAmode
P P P
Momentary trigger to change mode to C mode
P P P
LCDbacklightOFF P P P
(3) Function Assignments to Digital OutputsOneofthefollowingstatusoutputfunctionscanbeas-signedtoeachDO.Availablefunctionsdifferdependingonthecontrollermodeasshowninthetable.
Controller modeFunction
Single-loop
Cascade Selector
HighlimitalarmforPV1 P P P
LowlimitalarmforPV1 P P P
High-highlimitalarmforPV1 P P P
Low-lowlimitalarmforPV1 P P P
Deviationalarmforvariable1 P P P
VelocityalarmforPV1 P P P
HighlimitalarmforPV2 P P
LowlimitalarmforPV2 P P
High-highlimitalarmforPV2 P P
Low-lowlimitalarmforPV2 P P
Deviationalarmforvariable2 P P
VelocityalarmforPV2 P P
Deviationalarmforvariable1orVelocityalarmforPV1
P P P
Deviationalarmforvariable2orVelocityalarmforPV2
P P
Loop1alarm P P P
Loop2alarm P P
Cmode(notA/M)identificationstatusoutput
P P P
Mmode(notC/A)identificationstatusoutput
P P P
Internal cascade open/close status output
P
Loop2setpointremote/local status
P
(4) Analog Output (Transmission) SettingsThefollowingvariablescanbeassignedtoanalogout-putsfortransmission:
PV1andPV2SV1andSV2MVAnaloginput1toAnaloginput4*AvailableonlyforthebasictypewithexpandableI/O.
Input/Output Signal ComputationsInfunctionselectionmode,input/outputcomputationscanbeenabledbysimpleparametersettings.Inprogrammode,thesecomputationscanbeincludedintheuserprogram.•Inputsignalcomputations:Squarerootextractionwithvariablelowcutoff10-segmentlinearizerfunctionFirst-orderlagExternalcascadesetpointcomputationSetpoint ratioFeed-forwardinputcomputationOthersignalprocessing
6
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 01B08C02-01EN Jun.13,2014-00
Self-tuning•Loopssubjecttoself-tuning:Thetablebelowshowsthelooptobeself-tunedineachmode.
Controller Mode Subject to Self-tuning
Single-loop mode Loop1
Cascade mode • Internalcascadeopen:Loop2• Internalcascadeclose:Loop1
Selector mode Selected loop
Alarm FunctionsThefollowingprocessalarmscanbedetected.Forotheralarms,seethe“Self-diagnostics”section.
Item Setting Range RemarksPVhigh-limitandhigh-high-limit alarm setpoint (*1)
–6.3to106.3% Settings are valuesinengineering units.
PVlow-limitandlow-low-limitalarm setpoint (*1)Absolutedeviationalarm(*1) 0.0to106.3%
Velocityalarm(*2) 0.0to106.3%
*1: Alarmhysteresis=0.1to20.0%*2: Velocityalarmtimesetting:1to9,999seconds
•Contactstatusduringalarm:Closeoropenasselectedbytheuser.
•Contactstatusduringpowerfailure:Open.
Item Service Indication When Alarm Setpoint is Set or When Alarm Has Oc-
curred
Remarks
AlarmSetpoint Pointers
PVhigh-limitand low-limit alarm setpoint
Yellow pointer InLOOP,DUAL,andMETER displaysPVhigh-high-
limit and low-low-limit alarm setpoint
Orangepointer
AlarmIndications
ALMlamp Lightsupinyellow ―
Alarmoccur-rence indication
AlarmindicationonLOOPdisplay
―
Alarmnamedisplay
DisplayonALARM ―
Tagnumberin-versiondisplay
Inversionandalternating display oftagnumbersinall displays
Enabledanddisabledbyaparameter.
Activedisplay ChangeofPVbaranditsbackgroundcolors
Alarmtypeto cause the activedisplayistobesetbya parameter.
Response to Power Recovery after FailureThe responsetoapowerrecoverydependsonthedura-tionofthefailureand start mode setting.
Start Mode Duration of Failure
Less than ap-prox. 2 s
Approx. 2 s or longer
AUT HOTstart
M-COLD(equiva-lent to TM1 and TM2 in YS100)
HOTstart M-COLDstart
A-COLD HOTstart A-COLDstart
C-COLD HOTstart C-COLDstart
COLD HOTstart COLDrestart
Response to Power Recovery
Response to Power Recovery
HOT start M-COLD start A-COLD start C-COLD start COLD restart
C,A,orMmode Remains the same as beforepowerfailure.
See note.
MV Remains the same as beforepowerfailure.
–6.3%
SV Remainsthesameasbeforepowerfailure.
Parametersinclud-ingP,I,andD
Remainsthesameasbeforepowerfailure.
Dynamiccomputa-tionssuchasfirst-order lag delays
Continuously per-formed.
Initialized
STC result parameter Initialization
Note: MmodeatanM-COLDstart,AmodeatanA-COLDstart,CmodeataC-COLDstart,andthesameasbeforethepowerfailure,ataCOLDrestart.
7
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 01B08C02-01EN Jun.13,2014-00
Self-diagnostics(1) System Failure•Causesofsystemfailure:VarioushardwarefailuressuchasmainCPUfailure,displayCPUfailure,A/Dconversionerror,D/Aconver-sion error, and memory error
•Responsetosystemfailure:TheFAILlamplightsup;theFAILcontactopens(asisthecasewithpowerfailure);analogoutputsareheld(Y1canbechangedmanually);anddigitaloutputsareheld.
(2) Alarms•Alarmtypes:Systemalarms,processalarms(seethe“AlarmFunc-tions[forFunctionSelectionMode]”sectionfordetails),self-tuningalarms
•Responsetoalarms:Seethetableshowingthealarmindicationsinthe“AlarmFunctions(forFunctionSelectionMode)”section.
Display upon System FailureUponsystemfailure,thedisplaychangestotheFAILdisplay.InthecaseofamainCPUfailure,thedisplayCPUshowstheFAILdisplayandallowsmanualoperationsinMmode.AlsointhecaseofadisplayCPUfailure,themainCPUshowstheFAILdisplayandallowsmanualoperations in M mode.*ExceptcasesofclockstoppingorsimultaneousfailureofthemainanddisplayCPUs
SecurityThe parameterscanbepassword-protected.
n Hardware SpecificationsInput/Output SpecificationsAnalog Inputs
Input Type Function Selection Mode1to5VDC 4 points
Directinput(op-tional, *1)
Availablefor1pointfromabove
Input resistance 1MΩorlarger
*1: TobespecifiedfrommV,thermocouple,RTD,potentiom-eter,two-wiretransmitter,isolator,orfrequencyinput.
Analog Outputs
Output Type Function Selection Mode4to20mA 1 point
1to5VDC 2 points
Load Resistance Function Selection Mode4to20mA 0to750Ω
Load Resistance Function Selection Mode1to5VDC Atleast2kΩ(seenote)
Note: UseavoltageoutputfortheYS1700mainunittoconnecttoanSIHNpanelmeter(2kΩ).
Digital Inputs
Item Function Selection ModeDigitalinputs 6 points (shared use with digital outputs)
Input Type ON OFFNo-voltagecon-tacts (*1, *2)
Close (resistance at 200Ωorless)
Open(resistanceat100kΩorlarger)
Voltagecontacts(*2)
Low(inputvoltagebetween–0.5to1VDC)
High(inputvoltagebetween+4.5to30VDC)
*1: Inputcontactrating:5VDC,20mAormore. Minimumpulsewidth:120ms*2: Thesameterminalscanbeconnectedtobothno-
voltageandvoltagecontacts.
Digital Outputs
Item Function Selection ModeDigitaloutputs(main unit)
6 points (shared use with digital inputs)
Transistor contacts
Rating:30VDC,200mA(resistanceload)
FAILoutput(*1)
1 point
Transistor contacts
Rating:30VDC,200mA(resistanceload)
*1: Normallyclosed(NC)andopenduringpowerfailureorsystemfailure.
Transmitter Power Supply
Item SpecificationSupplyvoltage 25to25.5VDC
Load 60mAorless(30mAorlessifthedirectinput option is included)
Short-circuit pro-tection
80mA±10mA
Others Noeffectofashort-circuitonthecontrolcircuit.Notisolatedfromthecontrolcircuit.250Wresistorforconversioninto1-to-5Vsig-nalmustbepreparedexternallyifnecessary.
8
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 01B08C02-01EN Jun.13,2014-00
Standard SpecificationsStandard Working ConditionsAmbienttemperature23°C±2°CRelativehumidity:50%±10%Powersupply:-AC(100V)DC(24V)dualpowerdrivemodels:24VDC±10%or100VAC±10%,50/60Hz
-220VACpowerdrivemodels:135VDC±10%or220VAC±10%,50/60Hz
Item SpecificationI/Oconversionaccuracy
1to5Vinputs ±0.1%ofspan(*1)
Directinputs ±0.5%or±(2×|directinputcard’saccuracy|+0.1%)(*1)
Analogvoltageoutputs ±0.1%ofspan
Analogcurrentoutputs ±0.2%ofspan
Allowableinputvoltage
1to5VmVorTCdirectinputTwo-wire transmitter
±30VDC–0.5to4VDC+40mADC
Warm-up time 1minute(timeneededafterpower-onuntilthereadingsfallwithintheratedaccuracy)or3minutesfordirect input
Current dissipation and power consumption
AC(100V)DC(24V)dualpowerdriven:750mA(20to132VDC)30VA(80to138VAC)
220VACpowerdriven:110mA(120to340VDC)30VA(138to264VAC)
Insulation resistance 100MΩat500VDCbetweeninputterminals and ground terminal, and betweenpowersupplyterminalsandground terminal
Withstand voltage
Between input/output terminal and ground terminal
1000VACforoneminute(Inthecaseofsuffixcodes-x0xor-x2x)
500VACforoneminute(Inthecaseofsuffixcodes-x3x,-x4x,or-x5x)
Between power supply terminal(L,N) and (all I/Oterminaland ground terminal)
3000VACforoneminute(Inthecaseofsuffixcodes-x0xor-x2x)
Between power supply terminal(L,N)and ground terminal
1500VACforoneminute
LCDreplacementperiod 8 years*1: MeasurementcategoryinaccordancewithIEC/
EN61010-1,IEC/EN61010-2-030,andCAN/CSA-C22.2No.61010-1,CAN/CSA-C22.2No.61010-2-030:O(other)
Signal-to-signal Isolation
Item Basic typeAnalogI/Osignals - Notisolatedfromthecontrolcircuit
- Channel-to-channel not isolated, minus lines connected to common- IsolatedfromothertypesofI/Osignals
Directinput - Isolatedfromcontrolcircuitexceptfornon-isolated two-wire transmitter input- Isolatedfrompowersupplycircuit- IsolatedfromothertypesofI/Osignals
DigitalI/Osignals - Isolatedfromcontrolcircuit- IsolatedfromothertypesofI/Osignals- Channel-to-channel isolated (see note)
FAILsignal - Isolatedfromcontrolcircuit- IsolatedfromothertypesofI/Osignals
Communication
Powersupply
Ground
Note: WithintheterminalsontheexpandableI/O,theminuswiresoftheindividualdigitalinputsarecon-nected to the same common line, and so are the digitaloutputs.Thus,theexpandedDIsandDOsarechannel-to-channelnon-isolatedbutthoseDIsareisolatedfromthoseDOs.
Power Supply RatingsWhenusedwithinthesupplyvoltagerangesbelow,theYS1700iscompliantwiththeFM/CSAnonincendiveandSafetystandards.ForAC(100V)andDC(24VDC)dualpowerdrivemodels:
-24to120VDC(±10%),nopolarity,750mAMAX-100to120VAC(±10%),50/60Hz(±3Hz),30VAMAXFor220VACpowerdrivemodels:-135to190VDC(±10%),nopolarity,110mAMAX-220to240VAC(±10%),50/60Hz(±3Hz),30VAMAX
9
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 01B08C02-01EN Jun.13,2014-00
Normal Working, Transportation, and Storage Conditions
Item Normal Working Transportation and Storage
Ambienttemperature
0to50°C –20to60°C
Ambientrela-tivehumidity
5to90%(nocondensationallowed)
5to95%(nocondensation allowed)
Powersupplyvoltage(AC)(*1)
80to138VAC(forAC[100V]orDC[24V]dualdrivemodels)138to264VAC(for220VACdrivemodels)
–
Powersupplyfrequency(AC)
50/60Hz±3Hz –
Powersupplyvoltage(DC)(*1)
20to132VDC(forAC[100V]orDC[24V]dualdrivemodels)120to340VDC(for220VACdrivemodels)
–
Continuous vibration
5to14Hzwithamplitudeof0.625mmorless;14to150Hzwithaccelerationof4.9m/s2 or less alongorthogonal3directionsfor2hourseach
Transient vibration
14.7 m/s2for15secondsorless
Mechanical impact
49 m/s2(5G)orlessfor11msorless
Packagefall 1 m or less
Magneticfield 400A/morless
Toxicgases Nocorrosivegasesmustbepresent.
Installation height
Atelevationof2000morless
Atmosphericpressure
86to106kPa
*1: DiffersfromtheconditionsmeetingtheCEsafetystandard,FM/CSAnonincendivestandardsandCSAsafetystandards.
Effect of Variations in Working Conditions
Item SpecificationEffectoffluctuationsinpowersupply
|Accuracy|
Effectofinputlead-wireresist-ance
0.13%(per1kΩ)
Effectofloadresistance |Accuracy|/52kΩto∞,1to5Voutput0to750Ω,4to20mA
Commonmodenoiserejectionratio
83dBfor(1to5Vinputs),50/60Hz
Seriesmodenoiserejectionratio
46dB(1to5Vinputs),50/60Hz
Effectofmagneticfield |Accuracy|/5(400A/m,50/60HzorDC)
Effectofambienttemperaturechanges
|Accuracy|(per10°Cchangewithin0to50°C)
Effectofambienthumiditychanges
|Accuracy|(50%to93%RHat40°C)
Communication Specifications
Item Programmer Communication (with YSS1000)
RS-485 DCS-LCS Ethernet
Electrical specifications
RS-232C compliant EIARS-485compliant Yokogawa proprietary IEEE802.3 compliant10BASE-T/100BASE-TX
Connection Dedicatedconnectorbehindthefrontpanel
Screw terminals at the rear (5 signal and 1 ground terminals)
Screw terminals at the rear (2 terminals)
RJ45 connector at the rear
Numberofcontrollers that canbelinked
1 Max.31controllersperport 8controllersperLCScard, 4 controllers per SCIUcard
Max.4cascadedtiers(10BASE-T),max.2cascad-edtiers(100BASE-TX)(*1)Numberofconnections:2
Applicablecable
ModelA1053UR(dedicatedUSB–RS-232Cadaptercable)
Shieldedtwist-paircablewithcoresizeof0.5to1.25mm2(AWG20to16)
ModelSCCD(dedicatedshieldedtwist-paircable)
10BASE-T/100BASE-TXcable
Cablelength Approx.2.7m Max.1200m(1.25mm2) Max.100m 100 m (*2)
Protocol Proprietaryprotocol PClink,Modbus,YSprotocol,Peer-to-Peercom-munication
Proprietaryprotocol Modbus/TCP
*1:Numberofcascadedhubconnections*2:Maximumsegmentlength(hub-to-YS1700cablelength)
10
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 01B08C02-01EN Jun.13,2014-00
Direct Input Specification
Item mV Input Thermocouple InputOptioncode /A01 /A02
Input signal –50to+150mVDC
ANSI/JISthermocoupletype K, T, J, E, B, R, or S,orIEC/ANSItypeN
Measurablespan 10to100mVDC
10to63mV(equivalentemf)
Zeroelevationofmeasurement range
Within 3 times thespanor±50mV,whicheveris smaller
Within 3 times the span or±25mV,whicheverissmaller
Measurement range Canbemodifiedviaanengineeringdisplay.
Input resistance 1MΩ(3kΩduringpowerfailure)
Externalinputresist-ance
500Ωorless
Allowableinputvolt-age and current
–0.5to4VDC
Input linearizer Notprovided Provided
Ratedaccuracyofconversionto1to5Voutput
±0.2%ofspan ±0.2%ofspanor±20μVininputequivalent,whicheverislarger
Referencejunctioncompensation (RJC)
— ±1°Corless(*1)
*1: RJCisnotperformedforaTypeBelement.ExceptforTypeB,ifthemeasuredtemperatureisbelow0°C,thentheerroristheproductofthevalueabovemultipliedbythefollowingconstantK:K=(emfper1°Cataround0°C)/(emfper1°Catthemeasuredtemperature)
Item RTD PotentiometerOptioncode /A03 /A04
Input signal Pt100(IPTS-68:JIS’89),JPt100(JIS’89),Pt100(ITS-90:JIS ’97), Pt50(JIS’81)3-wire measurement current:1mA
Three-wire potentiometer
Measurablespan
10to650°C(Pt100)10to500°C(JPt100)
Totalresistance:100to2000ΩSpan:80to2000Ω
Zeroelevationofmeasure-ment range
Within 5 times the span
Within50%ofthetotalresist-ance
Measurement range
Canbemodifiedviaanengineeringdisplay.
Externalinputresistance
10Ωorlessper wire (*2)
10Ωorlessperwire
Input linearizer Provided Notprovided
Rated accu-racyofconver-sionto1to5Voutput
±0.2%ofspanor±0.2°C,whicheverislarger
±0.2%ofspan
*2: 10Ωperwire,or(temperaturemeasurementspan)x0.4Ω,whicheverissmaller.
Item Input Isolator Two-wire Transmitter or Non-isolated 2-
wire transmitter InputOptioncode /A05 /A06or/A07
Input signal 1to5VDC 4to20mADCfromtransmitter (with its powersuppliedfromtheYS1700)
Input resistance 1MΩ(100kΩdur-ingpowerfailure)
250Ω
Externalinputresistance
— RL=(20–[minimumworkingvoltageoftransmitter])/0.02A(Ω)or less
Allowableinputvoltageorcur-rent
±30VDC 40mADC
Input linearizer Notprovided
Rated accuracy ofconversionto1to5Voutput
±0.2%ofspanorless
Item Frequency InputOptionCode /A08
Input signal Two-wirecontact,voltagepulse,orcurrentpulse (can supply transmitter power) Three-wirevoltagepulsewithtransmitterpowersupply
Inputfrequency 0to10kHz(0to10HzwhentheinputfilterissettoON.)
100%frequency 0.1to10kHz(0.1to10HzwhentheinputfilterissettoON.)
Zeroelevation 0to50%of100%inputfrequency
Measurement range
Canbemodifiedviaanengineeringdisplay.
Low-inputcutofflevel
Canbesettoalevelfrom0.01Hz(or1%ofmaximumfrequency)to100%
Minimum input pulse width
On:60μsOff:60μs(inputfrequencyfrom0to6kHz)On:30μsOff:30μs(inputfrequencyfrom6to10kHz)
Inputsignallevel Contactinput:RelayortransistorinputOpen-closedetectionlevels:Openif100kΩorlarger,closedif200ΩorlessContactcapacity:15VDC,15mAorlargerVoltage/currentpulseinput:Lowif–1to+8V;Highif+3to+24VPulseheight:3Vorhigher(inputfrequencyfrom0to6kHz),5Vorhigher(inputfrequencyfrom6to10kHz)
Internal load resist-ance(forcurrentpulse)
Canbeselectedfrom200Ω,500Ω,and1kΩ(tobespecifieduponordering).
Inputfilter Whethertoenable10msfilterforanovolt-agecontactcanbeselected(tobespecifiedupon ordering).
Transmitter power supply
Canbeselectedbetween12VDC,30mAand24VDC,30mA(tobespecifieduponordering).
Ratedaccuracyofconversionto1to5Voutput
±0.2%ofspanorless
11
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 01B08C02-01EN Jun.13,2014-00
n SAFETY COMPLIANCE
Item Compliance RemarksGen-eralsafetystandards
Compliant with IEC/EN61010-1, IEC/EN61010-2-030Overvoltagecategory:IIPollutionDegree:2Measurementcategory:O(other)Ratedvoltagetoearthofmeasuringcircuitterminal:33VACrms(50/60Hz)or70VDCCompliantwithCAN/CSA-C22.2NO.61010-1andCAN/CSA-C22.2NO.61010-2-030Overvoltagecategory:IIPollutionDegree:2Measurementcategory:O(other)
Onlyforthemodels with suffixcode-x0xor-x2xForsuffixcode:-x0xor-x2xand/CSAoption,compliant with CSA.
EMC stand-ards
EN61326ClassAEN55011ClassA,Group1EN6100-3-2EN6100-3-3Note:Theunitundertestingcan continuously work with accuracywithin±20%oftherange throughout the test. EMCRegulatoryArrangementinAustraliaandNewZealandEN55011ClassA,Group1KCmarking:Electromagneticwaveinterferencepreventionstandard,electromagneticwaveprotection standard compliance
Item Compliance RemarksApprovalforuseinhazardous areas
FMnonincendiveNo.3611Locations:ClassI,Division2,GroupsA,B,C,andD;ClassI,Zone2, Group IICTemperature Code T4CSAnonincendiveC22.2No.213-M1987Locations:ClassI,Division2,GroupsA,B,C,andDTemperature Code T4
Nonincen-diveelectricdeviceusablein hazardous area(onlyforthe models with option codes /FM,/CSA)(Tobeapproved)
Precautions for Safety Compliance 1.Aninternalunit,ifusedalone,cannotcomplywiththesafe-tystandards.Onlyacompletesetofaninternalunithousedinasafety-compliantcaseorasafety-complianthousing,iscompliantwiththesafetystandardslistedabove.
2.Thefollowingactionsthatinvolveremovalandre-instal-lationoftheinternalunitfrom/inthecase,requiredsafetychecksmandatedbytheIEC/EN61010-1safetystandard.TheseactionsmustbeperformedbyaYokogawaengineerorYokogawa-authorizedtechnician,andtestsforsafetychecks(suchasawithstandingvoltagetest)mustbeper-formed.Whentheusercarriesoutanyoneoftheseactionsatownresponsibility,thesafety-complianceislost.(1)Removingtheinternalunitfromthecaseorre-installing
the internal unit in the case or housing.(2) Replacing or installing the power supply unit, dis
playunit,oroptionboard.(3) Changing the setup switch positions on the main
boardoroptionboard.(4)Anyothermaintenanceorrepairworktodetach
theinternalunitfromthecase.
12
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 01B08C02-01EN Jun.13,2014-00
n FUNCTION BLOCK DIAGRAM(1) Function Selection Mode: Single-loop ModeThediagrambelowshowsthedefaultDI/O1to6selection,function,andanalogoutput(Y2,Y3)settings(canbemodifiedbychangingtheparameters).
T R K1
Square root extraction and
low cutoff adjustable C L C1
Square root extraction and low cutoff adjustable
P L C1
Input filter F L G
Input filter P L G1
Deviation alarm D L1
Control elements C N T1, A L G1
Preset MV P M V1
Output limiters M H1, M L1
Input filter C L G1
10-segment line conversion
Process variable alarms P H1, P L1, H H1, L L1,
V L1
Ratio and bias C G N1 ( C I N1+ C B I1 )+
C B O1
Input filter T L G
Gain and bias F G N ( F I N+ F B I ) + F B O
DI function selection DI1
(Parameter DI1F : Function not set)
Cascade setting input X2
Measurement input X1
Feed forword input X4
SV key
PV display
SV display
D I n= OPEN ( A U T)
PF key operation
( C M O D1 = C A S)
D I n= CLOSE ( C A S)
C/A external switching (Note 1) D I n F =E- A U T
Self-tuning S T C
STC start (Note 1) D I n F = S T C
Parameter P F K E Y = S T C
F F1
S V1 P V1
C I N1
C S W1 O N
O F F
C S R1 O N
O F F
P S R1 O N
O F F
F X1 O N
O F F
F I N
F S W O N
O F F
F O N
O N O F F
D I n= CLOSE
D I n= CLOSE
Output tracking (Note 1) D I n F =E- T R K
Preset MV switching (Note 1) D I n F =E- P M V
Output preset MV and MAN (Note 1)
D I n F =E- M P M V
D I n= OPEN
D I n= OPEN
Switching by pressing “C” (Note 1) D I n F = T R- C A S Switching by pressing “A” (Note 1) D I n F = T R- A U T Switching by pressing “M” (Note 1) D I n F = T R- M A N
D I n F, D I n (n=1 , 7 , 8 , 9 , 1 0)
C, A/M external switching (Note 1) D I n F =E- M A N
Backlight OFF (Note 1) D I n F = L C D- O F F
D I n= OPEN
< > MV key
D I n= CLOSE
MV display Note 1: One of them can be selected.
Moreover, changing DI/DO function assignment enables multiple contacts to be selected.
D O1 PV high-limit alarm output (Parameter
DO1F = PH1)
D O2 PV low-limit alarm output (Parameter
DO2F = PL1)
D O 3 PV velocity/
deviation alarm output
(Parameter DO3F = DL1VL1)
D O 4 C/A·M status
output (Parameter
DO4F = CAS)
D O 5 C·A/M status
output(Parameter
DO5F = CASAUT)
Y1 MV output 1 (4–20 mA)
Y2 MV output 2
(1–5 V) (Parameter Y2S = MV1)
Y 3 SV output
(1–5 V) (Parameter Y3S = SV1)
LCD backlight
F P
Output tracking input X3
–
+
13
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 01B08C02-01EN Jun.13,2014-00
(2) Function Selection Mode: Cascade ModeThediagrambelowshowsthedefaultDI/O1to6selection,function,andanalogoutput(Y2,Y3)settings(canbemodifiedbychangingtheparameters).
O N
< > MV key
O N
1
S V2 P V2
+
–
+
( C M O D1 = C A S)
LOOP 1 Display “C” mode key
DI function selection DI1
(Parameter DI1F : Function not set)
Cascade setting input X2
Measurement input 1 X1
Measurement input 2 X3
Feed forward input/output tracking input
X4
Square root extraction and low cutoff adjustable
C L C1
Square root extraction and low cutoff adjustable
P L C1
Square root extraction and low cutoff adjustable
P L C2
Input filter C L G1
Input filter P L G2
Input filter P L G1
Input filter F L G
Input filter T L G
10-segment line conversion
10-segment line conversion
Ratio and bias C G N1 ( C I N1+ C B I1 )+
C B O1
Gain and bias F G N ( F I N+ F B I ) + F B O
SV key
PV1 display
SV1 display
LOOP 1 Display “A” mode key
PF key operation
STC start (Note 1) D I n F = S T C
Parameter P F K E Y = S T C
P F
Deviation alarm D L1
Control elements1 C N T1, A L G1
Limiters M H1, M L1
Process variable alarms P H1, P L1, H H1, L L1,
V L1
Self-tuning S T C
Closed
Open
SV key
Closed D I n=CLOSE Open
D I n=OPEN
D O1 Loop 1 alarm
output (Parameter
DO1F = 1-ALM)
D O2 Loop 2 alarm
output (Parameter
DO2F = 2-ALM)
D O 3 O/C status
output (Parameter
DO3F = O/C)
D O 4 C/A·M status
output (Parameter
DO4F = CAS)
D O 5 C·A/M status
output (Parameter
DO5F = CASAUT)
Y1 MV output 1 (4–20 mA)
Y2 MV output 2
(1–5 V) (Parameter Y2S = MV)
Y 3 SV output
(1–5 V) (Parameter Y3S = SV1)
T R K1
LCD backlight
Output limiters M H2, M L2
Control element 2 C N T2, A L G2
Preset MV P M V1
Deviation alarm D L2
Process variable alarms P H2, P L2, H H2, L L2,
V L2
Internal cascade O/C switching (Note 1) DInF =E-O/C
D I1=OPEN
D I1=CLOSE
D I1=OPEN
D I1=CLOSE
“M” mode key on LOOP 1 or LOOP 2 Display
(n=1 , 7 , 8 , 9 , 1 0)
Note 1: One of them can be selected. Moreover, changing DI/DO function assignment enables multiple contacts to be used.
Output preset MV and MAN (Note 1)
DInF =E-MPMV Switching by pressing “C” (Note 1) DInF =TR-CAS Switching by pressing “A” (Note 1) DInF =TR-AUT Switching by pressing “M” (Note 1) DInF =TR-MAN
Output tracking (Note 1) DInF =E-TRK
Preset MV switching (Note 1) DInF =E-PMV
Backlight OFF (Note 1) DInF =LCD-OFF
MV display
D I n F , D I n
C I N1
C S R1
O F F
C S W1 O N
O F F
P S R1 O N
O F F
F X1 O N
O F F
F I N
F S W O N
O F F
F O N
O N
O F F
P S R2 O N
O F F
F X2
O F F
S V
F F1
P V1
–
+
14
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 01B08C02-01EN Jun.13,2014-00
(3) Function Selection Mode: Selector ModeThediagrambelowshowsthedefaultDI/O1to6selection,function,andanalogoutput(Y2,Y3)settings(canbemodifiedbychangingtheparameters).
MV key
-
DI function selection DI1
(Parameter DI1F : Function not set)
Cascade setting input 1 X2
Measurement input 1 X1
Cascade setting input 2/output tracking input
X4 Measurement input 2
X3
Square root extraction and low cutoff adjustable
C L C1
Square root extraction and low cutoff adjustable
P L C1
Square root extraction and low cutoff adjustable
C L C2
Square root extraction and low cutoff adjustable
P L C2
Input filter C L G1
Input filter P L G1
Input filter C L G2
Input filter T L G
Input filter P L G2
Ratio and bias C G N1 ( C I N1+ C B I1 ) +
C B O1
Ratio and bias C G N2 ( C I N2+ C B I2 ) +
C B O2
10-segment line conversion
10-segment line conversion
SV key SV key PV1 display
SV1 display
PV2 display
SV2 display
Deviation alarm D L1
Deviation alarm D L2 Control
elements 1 C N T1, A L G1
Input alarms P H1, P L1, H H1, L L1,
V L1
Input alarms P H2, P L2, H H2, L L2,
V L2
Self- tuning S T C Control element 2
C N T1, A L G1
Parameter P F K E Y = S T C
STC start (Note 1) DInF =STC
P F
< >
Note 1: One of them can be selected. Moreover, changing DI/DO function assignment enables multiple contacts to be used.
DO1Loop 1 alarm
output (Parameter
DO1F = 1-ALM)
DO2Loop 2 alarm
output (Parameter
DO2F = 2-ALM)
DO3 R/L status
output (Parameter
DO3F = L/R)
DO4 C/A·M status
output (Parameter
DO4F = CAS)
DO5 C·A/M status
output (Parameter
DO5F = CASAUT)
Y1 MV output 1 (4–20 mA)
Y2 MV output 2
(1–5 V) (Parameter Y2S = MV)
Y 3 SV output
(1–5 V) (Parameter Y3S = SV1)
LCD backlight
Selector selection (Note 1)
DInF =E-SEL
Switching by pressing “C” (Note 1) DInF =TR-CAS
Switching by pressing “A” (Note 1) DInF =TR-AUT
Switching by pressing “M” (Note 1) DInF =TR-MAN
Tracking switching (Note 1) DInF =E-TRK
Output preset MV and MAN (Note 1)
DInF =E-MPMV
Preset MV switching (Note 1) DInF =E-PMV
Backlight OFF (Note 1) DInF =LCD-OFF
D I n F, D I n (n=1 , 7 , 8 , 9 , 1 0)
MV display
T R K1
Preset MV P M V1
Output limiters M H1, M L1
D I1= O PEN
D I1=CLOSE
D I1= O PEN
“M” mode key on LOOP 1 or LOOP 2 Display
D I1=CLOSE
2 1
DI1=CLOSE→AUT
S S W
Auto-selector A T S E L
D I1= O PEN→1
O F F
S V1 P V1
S V2 P V2
O F F
L(CLOSE) R( O PEN)
( C M O D1 = C A S)
LOOP 1 Display “C” mode key LOOP 1 Display
“A” mode key
Selector’s secondary SV L/R switching (Note 1)
D I nF =E-R/L
C I N1
C S R1 O N
O F F
C S W1 O N
P S R1 O N
O F F
F X1 O N
O F F
P S R2 O N
O F F
F X2 O N
O F F
C I N2
C S R2 O N
O F F
C S W2 O N
+
+
-
Selector (Note 1)DInF=E-LPSEL
DI open: Output the computation result of Loop 2DI close: Output the computation result of Loop 1
15
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 01B08C02-01EN Jun.13,2014-00
n Terminal Layout (Basic type)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
L
N
G
Single-loop mode Cascade mode Selector mode +-+-+-+-+-+-Transmitter Power supply (24V DC) (*2)
Communication SG
Communication SDA ( -)
Communication SDB ( +)
Communication RDA ( -)or LCS ( +)
Communication RDB ( +)or LCS ( -)
+-
+-+-+-+-+-+-+-+-+-+-Ground (GND)
+-+-+-+-+-+-Transmitter Power supply (24V DC) (*2)
Communication SG
Communication SDA ( -)
Communication SDB ( +)
Communication RDA ( -)or LCS ( +)
Communication RDB ( +)or LCS ( -)
+-
+-+-+-+-+-+-+-+-+-+-Ground (GND)
+-+-+-+-+-+-Transmitter Power supply (24V DC) (*2)
Communication SG
Communication SDA ( -)
Communication SDB ( +)
Communication RDA ( -)or LCS ( +)
Communication RDB ( +)or LCS ( -)
+-
+-+-+-+-+-+-+-+-+-+-Ground (GND)
PV (1-5V DC)
Cascade setting input(1-5V DC)
Tracking input (1-5V DC)
Feedforward input (1-5V DC)(*5)
Direct input signal output ( * 1)
Fail output
Direct input ( * 3)
MV1 (4 p 20mA DC)
MV2 (*4) (1-5V DC)
SV (*4) (1-5V DC)
PV1 high limit alarm output (*4)
PV1 low limit alarm output (*4)
Deviation alarm output
C/A·M status output
C·A/M status output
Action mode switching input
Power supply
PV1 (1-5V DC)
Cascade setting input(1-5V DC)
PV2 (1-5V DC)
Feedforward input (1-5V DC)(*5)
Direct input signal output ( * 1)
Fail output
Direct input ( * 3)
MV1 (4 p 20mA DC)
MV2 (*4) (1-5V DC)
SV (*4) (1-5V DC)
First loop alarm output
Second loop alarm output
O/C status output
C/A·M status output
C·A/M status output
Action mode switching input
Power supply
PV1 (1-5V DC)
Cascade setting input 1(1-5V DC)
PV2 (1-5V DC)
Cascade set point input 2 (1-5V DC)(*6)
Direct input signal output ( * 1)
Fail output
Direct input ( * 3)
MV1 (4 p 20mA DC)
MV2 (*4) (1-5V DC)
SV (*4) (1-5V DC)
First loop alarm output
Second loop alarm output
L/R status output
C/A·M status output
C·A/M status output
Action mode switching input
Power supply
Terminal No.
(*4)
(*4)
(*4)
(*4)
(*1)Ifdirectinput(optionalspecifications)isprovided,analoginput5becomesdirectinputsignaloutput.(*2)Forconnectingtwowiretransmitters:see“ConnectionofTransmitterPowerSupply”describedlater.(*3)Fordirectinputconnection:see“DirectInputWiring”describedlater.(*4)Thesesettingsaredefault.Theycanbechangedbyparameters.(*5)Iffeedforwardinputisnotused,theterminalscanbeusedforoutputtrackinginput.(*6)Ifcascadesettinginput2isnotused,theterminalscanbeusedforoutputtrackinginput.
16
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 01B08C02-01EN Jun.13,2014-00
Direct Input Terminals
Terminal number19 21 20
mVinput(optionalcode/A01)Isolator(optionalcode/A05) + -
Thermocoupleinput(optionalcode/A02)+ -RJC
RTDinput(optionalcode/A03)
A B B
Matchthewiringresistancesofterminals19and21witheach other.
Potentiometerinput(optionalcode/A04) 100% 0%
Matchthewiringresistancesofterminals19and20witheach other.
Frequencyinput(optionalcode/A08)
Two-wiretype(voltage,contact) + -
Powerfeedtype,two-wired Signal PowerSupply
Powerfeedtype,three-wired + PowerSupply -
Two-wire transmitter input (optionalcode/A06,/A07)
Supplyvoltagerequired + -
Caseof4to20mAsignalnotrequiringsupplypower - +
Connection of Transmitter Power Supply
-
+24 V DC
supply voltage
250Ω3W
Analoginput 1
1250Ω3W -
+
2
5
6
13
Analoginput 3
17
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 01B08C02-01EN Jun.13,2014-00
n DIMENSIONS (Basic type)
TrigonometryUnit: mmGeneral tolerance = ±(value of tolerance class IT18 based on JIS B 0401-1998) / 2
Note 1: If a nameplate, etc. is installed within 60 mm above the instrument, the height of the nameplate, etc. must be 30 mm or less from the panel surface.
Note 2: To ensure good air ventilation, allow space of 100 mm or more at the top and bottom of the panel.Note 3: For the YS100 compatible type, YS80 internal unit compatible type, EBS, I, EK, and HOMAC compatible
types, YS80 compatible type, and 100 Line compatible type, refer to the relevant separate outline view.
Panel Cutout Width for Side-by-side Mounting
1004932860788716644572500428356284212140
141312111098765432
L(mm)Number of instruments to be mounted
Pane Cutout Dimensions
25024.6
1313
136.
4
162.
4
60
144
6072
6
67
56
For single mounting:
68+0.70
137+2 0
For side-by-side mounting:
137+2 0
L+10
0908E.ai
Note 1Instrument panel thickness: 2.3 to 25 mm
Clamp bracket
Clamp bracket
When swung up
220
or m
ore
220
or m
ore
Weight: 1.6 kg
18
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 01B08C02-01EN Jun.13,2014-00
n STRUCTURE, MOUNTING (Basic type)
Item SpecificationCase protection class Dust-andsplash-proof(IP54-compliant)faceplate
Note:Notapplicableinside-by-sidemulti-unitinstallationorcompatibletypes.
Mounting Indoor panel mounting
Panelmountingdevice Mountingbracketstobeused(atthetopandbottom).
Panelcutout 137+2×68+0.7mm
Wiring terminals Signal wirings M4 screw terminals
Powersupplyandground terminals
M4 screw terminals
Dimensions 144×72×250mm(HxWxDfrompanelplate)
Weight 1.6 kg
19
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 01B08C02-01EN Jun.13,2014-00Subjecttochangewithoutnotice.
n Model and Suffix Codes Model Suffix Code Optional Code Remarks
YS1500 Indicating controller
Use-1 With hard manual unit-2 Without hard manual unit
Type
0 Basic type 2 CompatibletypeforYS100(withYS100case)3 CompatibletypeforYS80internalunit/compatibletypeforEBS,I,EK,andHOMAC(*1)4 CompatibletypeforYS80(compatiblesizeforYS80withYS100terminal)5 Compatibletypefor100line(withYS100terminal)(*2)
Powersupply0 100VAC,24VDCcommonpower1 220VACpower
Directinput(*3)
/A01 mVinput/A02 Thermocouple input /A03 RTDinput/A04 Potentiometerinput/A05 Isolator /A06 Two-wire transmitter input (isolated) /A07 Two-wire transmitter input (non-isolated) /A08 Frequencyinput/DF DirectinputwithFahrenheittemperaturerangefunction(*8)
Communication/A31 RS-485communication(PC-link,Modbus,YSprotocol)(*4)/A32 DCS-LCScommunication(*5)/A34 Ethernetcommunication(Modbus/TCP)(*6)
Certification/FM FMnonincendiveapproved(FMClassI,DIV2)(*7)(Tobeapproved)/CSA CSAsafetyandnonincendiveapproved(ClassI,DIV2)(*9)(Tobeapproved)
*1 ThistypecanbeconnectedtotheYS80housing(modelSHUP).(TheEK/HOMACcompatiblehousing(SHUP-420)andEBS/Iseries-compatiblehous-ing(SHUP-100)aresoldseparately.)
*2 The100line-compatiblehousing(modelYS006)issoldseparately.*3 Directinputoptionscanbecombinedonlywiththesuffixcodes“-x2x,”“-x4x,”or“-x5x.”Selectionofmultipleoptionsisnotpossible.*4 Acombinationwithsuffixcode“-x3x”isnotpossible.Optionalcodes/A31and/A32cannotbesimultaneouslyspecified.
Pleasespecifythecommunicationoptions/A31(RS-485communication)todirectlycommunicatewiththeCENTUMCS3000/VP.*5 Optionalcodes/A31and/A32cannotbesimultaneouslyspecified.Pleasespecifythecommunicationoptions/A32(DCS-LCScommunication)tocom-
municatewiththeCENTUMCS3000/VPthroughtheSCIU.*6 Optionalcodes/A34canbespecifiedonlyforsuffixcodes“-x0x.”*7 Thisoptioncanbecombinedonlywithsuffixcodes“-x0x.”*8 Thisoptioncanbecombinedonlywithoptioncode/A02or/A03.Ifoptioncode/DFisspecified,Fahrenheittemperaturerangecanbeavailablefordirect
inputrangeinadditiontoCentigradetemperaturerange.IncaseofspecifyingFahrenheittemperaturerangefordirectinput,optioncode/DFisrequired.WhenthedirectinputtemperaturerangemaybechangedtoFahrenheittemperaturerangeaftershipment,alsospecifyoptioncode/DF.
*9 Thisoptioncanbecombinedonlywithsuffixcodes“-x0x,”“-x2x.”
n Accessories
Item NamePart
Number/Model
Q’ty Remarks
Metal clamps
L4041RA 2 ForYS1500-x0xE9760RJ 2 ForYS1500-x2xE9760RN 2E9760RJ 1 ForYS1500-x4xE9760RP 1
Tag plate seals L4041UA 4 50×3.5mm
Range entry seals 4 34×2mm
RJC sensor L3501RA 1 Availableonlyforproductswithoptionalcode/A02
Ferritecore A1179MN 1Fordirectinputcable(Supplied with products withoptionalcode/A0x.)
YS1500/YS1700 OperationGuide - 1 A4size
* Productuser’smanualscanbedownloadedorviewedatthefollow-ingURL.Toviewtheuser’smanual,youneedtouseAdobeReader7orlaterbyAdobeSystems.
http://www.yokogawa.com/ns/ys/im/
n Items to Be Specified at the Time of OrderingModel,suffixcode,andoptionalcodes,whennecessary,arerequiredtobespecified.Eachcustomercanspecifyonetagnumberforthe12al-phanumericalsymbolstobeusedonthemainratingplate.Directinputspeccanbespecified(onlyfortheoptionalcodeslistedinthetablebelow).
Optional Code Item to Be Specified/A01 Measurement range, Burnout
/A02 Thermocouple’s compliance standard and type, Measurement range, Burnout
/A03Resistance temperature detector’s com-pliance standard, type, and resistance valueat0°C.Measurement range, Burnout
/A04 Totalresistance,0%resistance,100%resistance,Burnout
/A08Measurement range, Transmitter power supply(12VDC/24VDC),Inputfilter(ON/OFF),Currentpulseloadresistance(200Ω,500Ω,1kΩ)
n Accessories (sold separately)Product name Model Remarks
SHUPstandardhousing SHUP-000 AvailableforYS1xx0-x3x(ReplaceforYS80Series)SHUPlonghousing SHUP-100 AvailableforYS1xx0-x3x(ReplaceforISeriesorEBSSeries)SHUPEK/HOMAChousing SHUP-420 AvailableforYS1xx0-x3x(ReplaceforEKorHOMACSeries)100Linepneumaticinstrumentreplacehousing YS006 AvailableforYS1xx0-x5x(Replacefor100Linepneumaticinstrument)120Ωterminatingresistor(*10) YS020 ForRS-485communication250Ωshuntresistor YS021 Forabuilt-in24Vtransmitterpowersupply*10 TheYS1500hasabuilt-interminatingresistor,whichcanbeselectedforusebysettingtherelevantparameter.Ifaterminatingresistorisusedinanother
deviceattheterminationofthesamecommunicationsystem,anexternalterminatingresistorneedstobeprovidedtomatchtheterminatingresistanceoftheYS1500’sbuilt-interminatingresistor.