You can hardly find water which has no problem with one of 5 typical contaminants:
Hardness Iron Manganese Natural organic matter (NOM) Smell of ammonia and/or H2S
These problems often come together.
1. Iron and manganese removal on catalytic media (Birm, MTM, Greensand,etc).
2. Softening on strong acid cation resins (ammonia removal is also possible).
3. Organics removal by activated carbon.
4. (Potentially) Ammonia removal on zeolite.
Traditionally – 4 stages
Problems with traditional technology:
• detailed water analysis• deep knowledge and
experience of water experts
• is quite expensive and imperfect
• creates headaches and problems during maintenance
Some facts:In 1999 started production of ECOMIX.
Since 2001 – in Russia, Belarus
Since 2004 – in Germany, Italy, Poland, Scandinavian and Baltic countries
In 2007-2010 600 000 liters of media sold
Lifetime of the media - 3-10 years (average 5 years)
Problems - less than 0,1%
ECOMIX® is a mixture of ion exchange and adsorption materials of different nature
5 components which are created in our Kiev facility
After 1st backwash creates a multilayer arrangement that provides a maximum efficiency of purification.
Quartz sand support bed
Low-crosslinked cation resin
Modified adsorbent for NOM removal
Modified adsorbent for Fe and Mn removal
Inert material for iron removal and correct flow arrangement during
backwash
Two types of the media are available:
• ECOMIX ® А «4-in-1» - more popular, effective in hardness, iron, manganese and ammonia removal. It removes organic at certain level.
• ECOMIX ® C «5-in-1» - is recommended when besides 4 main contaminants significant reduction of organic content is necessary.
Concentration limits
TYPE A
Hardness, ppm
CaCO3 Fe, ppm Mn, ppmCOD, ppm
KMnO4NH4 ppm TDS, ppm
Raw water < 750 < 15 < 3 < 16 <4 < 4000
Filtered water Max 20 < 0,2 < 0,05 < 8 <0,5
No changes
TYPE C
Hardness, ppm
CaCO3 Fe, ppm Mn, ppmCOD, ppm
KMnO4NH4 ppm TDS, ppm
Raw water < 750 < 10 < 3 < 80 <4 < 4000
Filtered water Max 20 < 0,2 < 0,05 < 8 <0,5
No changes
Quality
ECOMIX ® is made of the DOWEX resins, which undergo additional chemical treatment at our site.
In Dec. 2010 - EU sanitary certification
Packing - 25 (12) liter double PE bags
Shipping weight, kg/liter
0,75
Maximum operating temperature, 0C
40
pH 5 - 10
Minimum bed depth, mm
500
Optimum bed depth, mm
800
SPECIFICATIONS
Flow rate, m/h:
service 20 - 25
backwash ( 15-20 min)
13-15
regeneration (45 -65 min)
3 - 5
rinse (15 -20 min) 20 - 25
Free bed volume >40%
Water consumption for regeneration, l
4 - 6
Regeneration solution 8-10 % NaCl
SPECIFICATIONS
Only hardness should be considered for calculations
Regeneration: 100 g NaCl/l media
CAPACITY AND REGENERATION
TYPE A 0,75 eq/l(37,5 gCaCO3/l)TYPE C 0,65 eq/l (32,5 gCaCO3/l)
The most typical applications:
• Residential water treatment for private houses• Commercial treatment for food industry• Pretreatment before RO• Replacement of standard softening for boilers
and steam generators
Main Advantages of the systems with ECOMIX:
• Universal solution. Five major problems of well water are easily solved by just one filter
• High efficiency. Filter is more effective than traditional iron removal systems. Fe < 15 ppm and Mn<3 ppm, rejection– up to 99%.
• Consistent reliability. Efficiency does not depend on pH, organics, chlorine or hydrogen sulfide content. The most reliable technology for iron removal – treats ANY well water.
Main Advantages of the systems with ECOMIX:
• Proven technology. 15 000 systems operating for 12 years all around Europe.
• Easy operation. Simple calculation of capacity – just hardness is taken into consideration. Extremely low salt consumption.
• Compact size – a new concept allows to reduce the overall size of the system substantially so it requires a smaller footprint. Cabinet size unit can serve for the whole house.