YORKGround Floor

10
JCI VRF Selection Transnet ------------------------------------------------------------------------------------------------------------------------------------------------------------ The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 1 JCI VRF Selection Software V1.37 System Report 4/11/2014 Project Name Transnet Client Name Imogen Client Address Braamfontein Memo Selection parameters of the indoor units can be found under the official documents of Indoor unit details; Selection parameters of the outdoor units can be found under the official documents of Outdoor unit details; In any case of unclear problems, please contact with Johnson controls ,inc. Engineers for solutions, This software is just an assistant tool for JCI VRF Selection, we suggest you contact with Johnson controls ,inc. Engineers for confirmation before you adopt the solution given by this software. 1. Material List Model Unit QTY Memo Price($) Sum Price($) YVKVXH056WAR--GX set 3 Indoor unit 0 0 YVGVXH056WAR--GX set 1 Indoor unit 0 0 YVGVXH090WAR--GX set 1 Indoor unit 0 0 YVGVXH112WAR--GX set 3 Indoor unit 0 0 YVGVXH140WAR--GX set 1 Indoor unit 0 0 YVGVXH280WAR--GX set 1 Indoor unit 0 0 PB-950JB set 3 Indoor Panel 0 0 YV2VYH106KAS-D-X set 1 Amazon Standard Ambient VRF-380V Outdoor unit 0 0 FQG-B506A set 1 Branch pipe 0 0 FQG-B730A set 2 Branch pipe 0 0 FQG-B1350A set 6 Branch pipe 0 0 HZG-30A set 1 Outdoor branch pipe 0 0 YR-E14 set 10 Wired controllor 0 0 iGU02 set 1 BacNet Translator 0 0 HCM-01 set 1 BacNet Converter 0 0 R410A Kg 7.5 Ground Floor-7.5 0 0 Total 0 Note: 1 Ammeter should be purchased locally. Note: Tender specified 67 Kw outdoor unit, Actual capacity is 110 Kw

Transcript of YORKGround Floor

Page 1: YORKGround Floor

JCI VRF Selection Transnet

------------------------------------------------------------------------------------------------------------------------------------------------------------

The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 1

JCI VRF Selection Software V1.37 System Report 4/11/2014

Project Name Transnet

Client Name Imogen

Client Address Braamfontein

Memo Selection parameters of the indoor units can be found under the official documents of Indoor unit details; Selection parameters of the outdoor units can be found under the official documents of Outdoor unit details; In any case of unclear problems, please contact with Johnson controls ,inc. Engineers for solutions, This software is just an assistant tool for JCI VRF Selection, we suggest you contact with Johnson controls ,inc. Engineers for confirmation before you adopt the solution given by this software.

1. Material List

Model Unit QTY Memo Price($) Sum Price($)

YVKVXH056WAR--GX set 3 Indoor unit 0 0

YVGVXH056WAR--GX set 1 Indoor unit 0 0

YVGVXH090WAR--GX set 1 Indoor unit 0 0

YVGVXH112WAR--GX set 3 Indoor unit 0 0

YVGVXH140WAR--GX set 1 Indoor unit 0 0

YVGVXH280WAR--GX set 1 Indoor unit 0 0

PB-950JB set 3 Indoor Panel 0 0

YV2VYH106KAS-D-X set 1 Amazon Standard Ambient VRF-380V

Outdoor unit 0 0

FQG-B506A set 1 Branch pipe 0 0

FQG-B730A set 2 Branch pipe 0 0

FQG-B1350A set 6 Branch pipe 0 0

HZG-30A set 1 Outdoor branch pipe 0 0

YR-E14 set 10 Wired controllor 0 0

iGU02 set 1 BacNet Translator 0 0

HCM-01 set 1 BacNet Converter 0 0

R410A Kg 7.5 Ground Floor-7.5 0 0

Total 0

Note: 1 Ammeter should be purchased locally. Note: Tender specified 67 Kw outdoor unit, Actual capacity is 110 Kw

Page 2: YORKGround Floor

JCI VRF Selection Transnet

------------------------------------------------------------------------------------------------------------------------------------------------------------

The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 2

2. Indoor/Outdoor Match

Outdoor unit Room Indoor unit

Ground Floor--YV2VYH106KAS-D-X

Ind1--YVKVXH056WAR--GX

Ind2--YVKVXH056WAR--GX

Ind3--YVKVXH056WAR--GX

Ind4--YVGVXH056WAR--GX

Ind5--YVGVXH090WAR--GX

Ind6--YVGVXH112WAR--GX

Ind7--YVGVXH112WAR--GX

Ind8--YVGVXH112WAR--GX

Ind9--YVGVXH140WAR--GX

Ind10--YVGVXH280WAR--GX

Page 3: YORKGround Floor

JCI VRF Selection Transnet

------------------------------------------------------------------------------------------------------------------------------------------------------------

The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 3

3. Indoor Dip switch(0:OFF, 1:ON) When YR-E14 used in group control system , the first unit of group control connection is set as master unit;

Name Model SW01 SW02 SW03 SW07 SW08 CN23 CN30 CN21

Ind1 YVKVXH056WAR-

-GX 00000110 10000000 11000000 11111111 11110111 ON ON OFF

Ind2 YVKVXH056WAR-

-GX 00000110 10000001 11000001 11111111 11110111 ON ON OFF

Ind3 YVKVXH056WAR-

-GX 00000110 10000010 11000010 11111111 11110111 ON ON OFF

Ind4 YVGVXH056WAR-

-GX 00000110 10000011 11000011 11111111 11110111 ON ON OFF

Ind5 YVGVXH090WAR-

-GX 00001001 10000100 11000100 11111111 11110111 ON ON OFF

Ind6 YVGVXH112WAR-

-GX 00001010 10000101 11000101 11111111 11110111 ON ON OFF

Ind7 YVGVXH112WAR-

-GX 00001010 10000110 11000110 11111111 11110111 ON ON OFF

Ind8 YVGVXH112WAR-

-GX 00001010 10000111 11000111 11111111 11110111 ON ON OFF

Ind9 YVGVXH140WAR-

-GX 00001011 10001000 11001000 11111111 11110111 ON ON OFF

Ind10 YVGVXH280WAR-

-GX 00001011 10001001 11001001 11111111 11110111 ON ON OFF

Page 4: YORKGround Floor

JCI VRF Selection Transnet

------------------------------------------------------------------------------------------------------------------------------------------------------------

The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 4

4. Outdoor Dip switch(0:OFF, 1:ON) The 1st & 2nd bit of BM1 of master unit should be set 0(Off position) before power on , after power on and finishing searching indoor and outdoor address ,set 1st & 2nd bit of BM1 to 1 (On position).

Name Model BM1 BM2 BM3 BM4 BM5

Ground Floor--YV2VYH106KAS-D

-X

YV2VYH045KAS-D-X

11000000 00000000 00000101 00000000 11000011

YV2VYH033KAS-D-X

11000001 00000000 00000011 00000000 11000011

YV2VYH028KAS-D-X

11000010 00000000 00000010 00000000 00110011

Page 5: YORKGround Floor

JCI VRF Selection Transnet

------------------------------------------------------------------------------------------------------------------------------------------------------------

The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 5

5. Indoor units details 5.1 Ground Floor----YV2VYH106KAS-D-X The outdoor unit's combination is(97.1%),the details of connected indoor units are:

Name Model Cooling Capacity

Heating Capacity

Std Cooling DB/WB

Std Heating DB/WB

Airflow(H) Noise Size Weight

kW kW °C °C m³/h dB(A) mm Kg

Ind1 YVKVXH056WAR-

-GX 5.6 6.3 27/19.4 20/14.5 1200 34/32/30

840*240*840(Panel:950*80*950)

36

Ind2 YVKVXH056WAR-

-GX 5.6 6.3 27/19.4 20/14.5 1200 34/32/30

840*240*840(Panel:950*80*950)

36

Ind3 YVKVXH056WAR-

-GX 5.6 6.3 27/19.4 20/14.5 1200 34/32/30

840*240*840(Panel:950*80*950)

36

Ind4 YVGVXH056WAR-

-GX 5.6 6.3 27/19.4 20/14.5 1600 42/40 970*360*875 56

Ind5 YVGVXH090WAR-

-GX 9 10 27/19.4 20/14.5 2100 45/40 1350*360*875 62

Ind6 YVGVXH112WAR-

-GX 11.2 12.5 27/19.4 20/14.5 2100 45/40 1350*360*875 62

Ind7 YVGVXH112WAR-

-GX 11.2 12.5 27/19.4 20/14.5 2100 45/40 1350*360*875 62

Ind8 YVGVXH112WAR-

-GX 11.2 12.5 27/19.4 20/14.5 2100 45/40 1350*360*875 62

Ind9 YVGVXH140WAR-

-GX 14 16 27/19.4 20/14.5 2100 45/40 1350*360*875 62

Ind10 YVGVXH280WAR-

-GX 28 31.5 27/19.4 20/14.5 4050 54/49 1670*360*880 92

Total 107 120.2

6. Outdoor units details

Name Model Combinatio

n Cooling Capacity

Heating Capacity

Std Cooling DB/WB

Std Heating DB/WB

Max pipe Len Size Weight

% kW kW °C °C m mm Kg

Ground Floor

YV2VYH106KAS-D-X

100 110.1 122.8 35/23.9 8.3/6.1 135 990*1808*750+(1390*

1808*750)*2 968

Name Model Refrigerant

added Power type

Cooling running Cur

Cooling Max Cur

Heating running Cur

Heating Max Cur

Kg A A A A

Ground Floor

YV2VYH106KAS-D-X

30 3N~,380~400V,50/60Hz 49 83.67 50.6 83.67

Page 6: YORKGround Floor

JCI VRF Selection Transnet

------------------------------------------------------------------------------------------------------------------------------------------------------------

The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 6

7. Piping diagram 7.1 Ground Floor

Page 7: YORKGround Floor

JCI VRF Selection Transnet

------------------------------------------------------------------------------------------------------------------------------------------------------------

The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 7

8. Wiring diagram 8.1 Ground Floor

Page 8: YORKGround Floor

JCI VRF Selection Transnet

------------------------------------------------------------------------------------------------------------------------------------------------------------

The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 8

9. BMS diagram

Page 9: YORKGround Floor

JCI VRF Selection Transnet

------------------------------------------------------------------------------------------------------------------------------------------------------------

The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 9

10. Max pipe Len&Drop

Page 10: YORKGround Floor

JCI VRF Selection Transnet

------------------------------------------------------------------------------------------------------------------------------------------------------------

The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 10

11. Refrigerant charging