JCI VRF Selection Transnet
------------------------------------------------------------------------------------------------------------------------------------------------------------
The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 1
JCI VRF Selection Software V1.37 System Report 4/11/2014
Project Name Transnet
Client Name Imogen
Client Address Braamfontein
Memo Selection parameters of the indoor units can be found under the official documents of Indoor unit details; Selection parameters of the outdoor units can be found under the official documents of Outdoor unit details; In any case of unclear problems, please contact with Johnson controls ,inc. Engineers for solutions, This software is just an assistant tool for JCI VRF Selection, we suggest you contact with Johnson controls ,inc. Engineers for confirmation before you adopt the solution given by this software.
1. Material List
Model Unit QTY Memo Price($) Sum Price($)
YVKVXH056WAR--GX set 3 Indoor unit 0 0
YVGVXH056WAR--GX set 1 Indoor unit 0 0
YVGVXH090WAR--GX set 1 Indoor unit 0 0
YVGVXH112WAR--GX set 3 Indoor unit 0 0
YVGVXH140WAR--GX set 1 Indoor unit 0 0
YVGVXH280WAR--GX set 1 Indoor unit 0 0
PB-950JB set 3 Indoor Panel 0 0
YV2VYH106KAS-D-X set 1 Amazon Standard Ambient VRF-380V
Outdoor unit 0 0
FQG-B506A set 1 Branch pipe 0 0
FQG-B730A set 2 Branch pipe 0 0
FQG-B1350A set 6 Branch pipe 0 0
HZG-30A set 1 Outdoor branch pipe 0 0
YR-E14 set 10 Wired controllor 0 0
iGU02 set 1 BacNet Translator 0 0
HCM-01 set 1 BacNet Converter 0 0
R410A Kg 7.5 Ground Floor-7.5 0 0
Total 0
Note: 1 Ammeter should be purchased locally. Note: Tender specified 67 Kw outdoor unit, Actual capacity is 110 Kw
JCI VRF Selection Transnet
------------------------------------------------------------------------------------------------------------------------------------------------------------
The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 2
2. Indoor/Outdoor Match
Outdoor unit Room Indoor unit
Ground Floor--YV2VYH106KAS-D-X
Ind1--YVKVXH056WAR--GX
Ind2--YVKVXH056WAR--GX
Ind3--YVKVXH056WAR--GX
Ind4--YVGVXH056WAR--GX
Ind5--YVGVXH090WAR--GX
Ind6--YVGVXH112WAR--GX
Ind7--YVGVXH112WAR--GX
Ind8--YVGVXH112WAR--GX
Ind9--YVGVXH140WAR--GX
Ind10--YVGVXH280WAR--GX
JCI VRF Selection Transnet
------------------------------------------------------------------------------------------------------------------------------------------------------------
The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 3
3. Indoor Dip switch(0:OFF, 1:ON) When YR-E14 used in group control system , the first unit of group control connection is set as master unit;
Name Model SW01 SW02 SW03 SW07 SW08 CN23 CN30 CN21
Ind1 YVKVXH056WAR-
-GX 00000110 10000000 11000000 11111111 11110111 ON ON OFF
Ind2 YVKVXH056WAR-
-GX 00000110 10000001 11000001 11111111 11110111 ON ON OFF
Ind3 YVKVXH056WAR-
-GX 00000110 10000010 11000010 11111111 11110111 ON ON OFF
Ind4 YVGVXH056WAR-
-GX 00000110 10000011 11000011 11111111 11110111 ON ON OFF
Ind5 YVGVXH090WAR-
-GX 00001001 10000100 11000100 11111111 11110111 ON ON OFF
Ind6 YVGVXH112WAR-
-GX 00001010 10000101 11000101 11111111 11110111 ON ON OFF
Ind7 YVGVXH112WAR-
-GX 00001010 10000110 11000110 11111111 11110111 ON ON OFF
Ind8 YVGVXH112WAR-
-GX 00001010 10000111 11000111 11111111 11110111 ON ON OFF
Ind9 YVGVXH140WAR-
-GX 00001011 10001000 11001000 11111111 11110111 ON ON OFF
Ind10 YVGVXH280WAR-
-GX 00001011 10001001 11001001 11111111 11110111 ON ON OFF
JCI VRF Selection Transnet
------------------------------------------------------------------------------------------------------------------------------------------------------------
The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 4
4. Outdoor Dip switch(0:OFF, 1:ON) The 1st & 2nd bit of BM1 of master unit should be set 0(Off position) before power on , after power on and finishing searching indoor and outdoor address ,set 1st & 2nd bit of BM1 to 1 (On position).
Name Model BM1 BM2 BM3 BM4 BM5
Ground Floor--YV2VYH106KAS-D
-X
YV2VYH045KAS-D-X
11000000 00000000 00000101 00000000 11000011
YV2VYH033KAS-D-X
11000001 00000000 00000011 00000000 11000011
YV2VYH028KAS-D-X
11000010 00000000 00000010 00000000 00110011
JCI VRF Selection Transnet
------------------------------------------------------------------------------------------------------------------------------------------------------------
The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 5
5. Indoor units details 5.1 Ground Floor----YV2VYH106KAS-D-X The outdoor unit's combination is(97.1%),the details of connected indoor units are:
Name Model Cooling Capacity
Heating Capacity
Std Cooling DB/WB
Std Heating DB/WB
Airflow(H) Noise Size Weight
kW kW °C °C m³/h dB(A) mm Kg
Ind1 YVKVXH056WAR-
-GX 5.6 6.3 27/19.4 20/14.5 1200 34/32/30
840*240*840(Panel:950*80*950)
36
Ind2 YVKVXH056WAR-
-GX 5.6 6.3 27/19.4 20/14.5 1200 34/32/30
840*240*840(Panel:950*80*950)
36
Ind3 YVKVXH056WAR-
-GX 5.6 6.3 27/19.4 20/14.5 1200 34/32/30
840*240*840(Panel:950*80*950)
36
Ind4 YVGVXH056WAR-
-GX 5.6 6.3 27/19.4 20/14.5 1600 42/40 970*360*875 56
Ind5 YVGVXH090WAR-
-GX 9 10 27/19.4 20/14.5 2100 45/40 1350*360*875 62
Ind6 YVGVXH112WAR-
-GX 11.2 12.5 27/19.4 20/14.5 2100 45/40 1350*360*875 62
Ind7 YVGVXH112WAR-
-GX 11.2 12.5 27/19.4 20/14.5 2100 45/40 1350*360*875 62
Ind8 YVGVXH112WAR-
-GX 11.2 12.5 27/19.4 20/14.5 2100 45/40 1350*360*875 62
Ind9 YVGVXH140WAR-
-GX 14 16 27/19.4 20/14.5 2100 45/40 1350*360*875 62
Ind10 YVGVXH280WAR-
-GX 28 31.5 27/19.4 20/14.5 4050 54/49 1670*360*880 92
Total 107 120.2
6. Outdoor units details
Name Model Combinatio
n Cooling Capacity
Heating Capacity
Std Cooling DB/WB
Std Heating DB/WB
Max pipe Len Size Weight
% kW kW °C °C m mm Kg
Ground Floor
YV2VYH106KAS-D-X
100 110.1 122.8 35/23.9 8.3/6.1 135 990*1808*750+(1390*
1808*750)*2 968
Name Model Refrigerant
added Power type
Cooling running Cur
Cooling Max Cur
Heating running Cur
Heating Max Cur
Kg A A A A
Ground Floor
YV2VYH106KAS-D-X
30 3N~,380~400V,50/60Hz 49 83.67 50.6 83.67
JCI VRF Selection Transnet
------------------------------------------------------------------------------------------------------------------------------------------------------------
The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 6
7. Piping diagram 7.1 Ground Floor
JCI VRF Selection Transnet
------------------------------------------------------------------------------------------------------------------------------------------------------------
The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 7
8. Wiring diagram 8.1 Ground Floor
JCI VRF Selection Transnet
------------------------------------------------------------------------------------------------------------------------------------------------------------
The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 8
9. BMS diagram
JCI VRF Selection Transnet
------------------------------------------------------------------------------------------------------------------------------------------------------------
The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 9
10. Max pipe Len&Drop
JCI VRF Selection Transnet
------------------------------------------------------------------------------------------------------------------------------------------------------------
The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 10
11. Refrigerant charging