Yaskawa Harmonic Mitigation.pdf
description
Transcript of Yaskawa Harmonic Mitigation.pdf
YASKAWA Page. 1
Understanding Input Harmonics
and Techniques to Mitigate Them
Mahesh M. Swamy
Yaskawa Electric America
YASKAWA Page. 2
Organization
• Introduction
• Why VFDs Generate Harmonics?
• Harmonic Limit Calculations per IEEE 519-
1992
• Harmonic Mitigation Techniques
– Passive and Active Means
• Questions and Conclusions
YASKAWA Page. 3
Motivation
• Harmonics cause unnecessary heat in
equipment connected to harmonic source
• System rich in harmonics is generally
associated with poor power factor and low
efficiency
YASKAWA Page. 4
Motivation - Continued
• Harmonics can overload preexisting power factor
correcting capacitors at plant facility and at utility
distribution points
• Harmonics can initiate system resonance that can
severely disrupt operation
• Hence, control of harmonic current is important
and necessary
YASKAWA Page. 5
Risk of Parallel Resonance
XcXL
ih
ih
Resonance occurs when: Xc = XL
Power Factor Capacitors Relieve Load
Parallel Resonance
Current measured at the capacitor,showing 660Hz, (11th harmonic resonance) Figure 5.2
YASKAWA Page. 6
Introduction
• Non-linear loads – current does not
follow applied voltage waveform
YASKAWA Page. 7
Introduction (Contd.)
• To estimate heating effect due to non-linear
currents flowing through circuit breakers and
transformers, linearization is needed
• Resolving non-linear waveform into sinusoidal
components is Harmonic Analysis
• Ratio of harmonic content to fundamental is
defined as harmonic distortion or THD
YASKAWA Page. 8
Why VFDs Generate Harmonics?
3-phaseinput
DCcapacitor
DC link voltage
Phase voltage
Rectifer input current
• Pulsating current due to dc bus capacitor – main source of non-
linearity in input current
• In weak ac systems, during diode conduction ac voltage is clamped
to dc bus voltage – source of non-linearity in input voltage
YASKAWA Page. 9
Definition of THD• Ratio of the square root of the sum of squares of the rms value of
harmonic component to the rms value of the fundamental component is
defined as Total Harmonic Distortion (THD)
• If the waveform under discussion is current, then the THD definition is
called Current Harmonic Distortion. If the waveform under discussion is
voltage, then the THD definition is called Voltage Harmonic Distortion
1
2
2
I
ITHD
n
nn
I
∑∞=
==1
2
2
V
VTHD
n
nn
V
∑∞=
==
YASKAWA Page. 10
Sample Waveforms
Every Wave shape has Harmonic Distortion!
THD = 78.3%THD = 1.2%
YASKAWA Page. 11
Harmonic Limits Per IEEE 519-1992Table 10.3: Current Distortion Limits for General Distribution Systems
(120 V through 69 kV)
Maximum Harmonic Current Distortion in percent of IL Individual Harmonic Order (Odd Harmonics)
ISC/IL <11 11≤h<17 17≤ h<23 23≤h<35 35≤ h TDD <20 4.0 2.0 1.5 0.6 0.3 5.0
20<50 7.0 3.5 2.5 1.0 0.5 8.0 50<100 10.0 4.5 4.0 1.5 0.7 12.0
100<1000 12.0 5.5 5.0 2.0 1.0 15.0 >1000 15.0 7.0 6.0 2.5 1.4 20.0
Even harmonics are limited to 25% of the odd harmonic limits above.
* All power generation equipment is limited to these values of current distortion, regardless of actual Isc / IL ; where Isc is the maximum short circuit current at PCC and IL is the maximum demand load current (fundamental frequency) at PCC.
YASKAWA Page. 12
Harmonic Limits Per IEEE 519-1992
Table 10.2 Low-Voltage System Classification and Distortion Limits
Special Applications * General System Dedicated
System†
Notch Depth 10% 20% 50%
THD (Voltage) 3% 5% 10%
Notch Area (AN
2)‡ 16,400 22,800 36,500
Note: The value of AN for other than 480V systems should be multiplied by V/480.* Special applications include hospitals and airports.† A dedicated system is exclusively dedicated to the converter load.‡ In volt-microseconds at rated voltage and current.
YASKAWA Page. 13
Definitions• PCC - Point of Common Coupling
• Point where harmonic measurement is to be made
• Typically, where the utility power comes into the business
(commercial building or industrial factory)
• Also defined as the point where non-linear load meets the linear
load within a plant – most popular definition used by Consultants
to enforce Drive Manufacturers to meet IEEE519 at VFD input
• TDD – Total Demand Distortion
• Harmonic current distortion in percent of maximum demand load
current. The maximum demand current interval could be either a
15-minute or a 30-minute interval.
YASKAWA Page. 14
Definitions - Continued• ISC: Short-circuit current at PCC
• Defines the size of the customer from Utility’s view point – helps
to distinguish between a Seven-Eleven store from a Steel
manufacturing plant
• IL: Maximum demand load current at fundamental frequency• Need not be the rated load current.
YASKAWA Page. 15
Characteristic Harmonics in Rectifiers
•
• h is harmonic order, k is any integer, q is number of pulses at the
dc bus voltage in one period
• For a six-pulse system, h will be:5th, 7th, 11th, 13th, etc.
• For a twelve-pulse system, h will be:11th, 13th, 23rd, 25th, etc.
• Amplitude of harmonics is 1/h for a three-phase ac to dc rectifier
with no dc bus capacitor
• Harmonics of order other than those given above are called non-
characteristics harmonics and are more common than not
1)( ±⋅= qkh
YASKAWA Page. 16
Application Example for Applying IEEE519
• 480V, 100hp VFD fed from a 1500-kVA transformer of 4% impedanceStep 1: Identify PCC – take default to be at VFD terminals
Step 2: Determine ISC from end user. In its absence, use
transformer kVA rating and percent impedance
Step 3: Determine IL from user. In its absence, use NEC Amps for
rated horsepower condition. Here, use 124A
Step 4: Determine ISC/IL. Look up Table 10.3 to determine limit - 15%
105,4504.04803
10001500)100/(%3
1000
=⋅⋅
⋅=
⋅⋅⋅
=
SC
LLSC
I
ZVkVAI
YASKAWA Page. 17
Application Example for Applying IEEE519
• ISC/IL for the present case is 364.
• From Table 10.3, TDD < 15% of Rated Fundamental Current or 18.6A
in this example; Hence IEEE 519 compliance does not mean 5% TDD
• If maximum demand load current is only 45A due to load condition,
and harmonic distortion is 35% at this operating point, spirit of IEEE
519-1992 is still met since 35% of 45A is 15.8A, which is less than the
allowable 18.6A.
• Don’t forget that voltage distortion limits are more important than
current distortion limits due to the fact that voltage is common to all
customers on the same grid, while current is local to a load
YASKAWA Page. 18
Harmonic Mitigation Techniques
• Active Techniques
• Passive Techniques
• Hybrid Techniques – Combination of Active and
Passive Techniques
YASKAWA Page. 19
Active Mitigation Techniques
• Active Front End
• Boost Converter Topology – Inherently regenerative.
Bulky, and expensive. Conducted EMI is of concern
• Non regenerative type: Inject Current from conducting
phase to non-conducting phase using semiconductor
switches
• Shunt type: Monitors load current and injects mirror
image of load current so that harmonics cancel out.
YASKAWA Page. 20
Passive Mitigation Techniques
• AC Line Inductors (Reactors)
• DC Link Chokes or DC Bus Inductor
• Harmonic Filters – Capacitor based
• Multi-pulse Schemes
YASKAWA Page. 21
Passive Mitigation Techniques
• AC Line Inductors (Reactors)
• Makes discontinuous current continuous
• Helps damp transient surges on line due to
lightning and capacitor switching
• Small and inexpensive
• Causes voltage overlap and reduces dc bus
voltage
YASKAWA Page. 22
Passive Mitigation Techniques
• AC Line Inductors (Reactors)
.
.
THD≈80%
THD≈40%
YASKAWA Page. 23
Issues With AC Line Reactors
• DC Bus Voltage Reduces Due to Overlap of Diode Conduction
πμ
πμ
ωωπ
πμ
πμ
)cos(323)cos(23
)()sin(23 )3/2(
)3/(
⋅⋅⋅⋅=
⋅⋅⋅=
=
−−
+
+ −∫
NLLLO
LLO
VVV
tdtVV
322
⋅⋅⋅⋅
=− LL
dc
VILωμ
YASKAWA Page. 24
Passive Mitigation Techniques• DC Link Chokes (DC Bus Inductor)
• Makes discontinuous current continuous
• Small and inexpensive
• Does NOT Cause overlap phenomenon and so
does not reduces dc bus voltage
• Does not help damp transient surges on line
due to lightning and capacitor switching
YASKAWA Page. 25
Passive Mitigation Techniques
• DC Link Choke (DC Bus Inductor)
.
THD≈80%
THD≈37%
.
YASKAWA Page. 26
Waveform With DC Link Choke
• No overlap of Diode Conduction
Ldc
ππμ
ωωπ
πμ
πμ
NLLLO
LLO
VVV
tdtVV
−−
+
+ −
⋅⋅⋅=
⋅⋅⋅=
= ∫323)cos(23
)()sin(23 )3/2(
)3/(
dcmmcr
mmavgphmcr
ITV
itVL
VVVVtiL
6/33
33
⋅⋅−
=ΔΔ⋅⋅
−=
⋅−=−=
ΔΔ⋅ −−
ππ
ππ
π
YASKAWA Page. 27
0
20
40
60
80
100
120
0 1 2 3 4 5 6 7 8AC equivalent Z (% Impedance)
Inpu
t Cur
rent
TH
D (%
)
AC reactor with DCreactor of 2.75mH
AC reactor only
DC reactor only(with ZSC=0.1%)x
Δ
40.00
-30.00
0
-20.00
-10.00
10.00
20.00
30.00
4.98 5.004.99 4.99 4.99 4.99 4.99 5.00 5.00
THD=92.5%Z=1%
40.00
-30.00
0
-20.00
-10.00
10.00
20.00
30.00
4.98 5.004.99 4.99 4.99 4.99 4.99 5.00 5.00
THD=92.4%Z=1%
30.00
-25.00
0
-20.00
-10.00
10.00
20.00
4.98 5.004.99 4.99 4.99 4.99 4.99 5.00 5.00
THD=44%Z=1%
30.00
-20.00
0
-10.00
10.00
20.00
4.98 5.004.99 4.99 4.99 4.99 4.99 5.00 5.00
THD=59.6%Z=3%
30.00
-20.00
0
-10.00
10.00
20.00
4.98 5.004.99 4.99 4.99 4.99 4.99 5.00 5.00
THD=50.6%Z=3%
25.00
-20.00
0
-15.00
-10.00
-5.00
5.00
10.00
15.00
20.00
4.98 5.004.99 4.99 4.99 4.99 4.99 5.00 5.00
THD=37.3%Z=3%
20.00
-15.00
0
-10.00
-5.00
5.00
10.00
15.00
4.98 5.004.99 4.99 4.99 4.99 4.99 5.00 5.00
THD=33.8%Z=5%
25.00
-20.00
0
-15.00
-10.00
-5.00
5.00
10.00
15.00
20.00
4.98 5.004.99 4.99 4.99 4.99 4.99 5.00 5.00
THD=43.9%Z=5% 25.00
-25.00
0
-20.00
-10.00
10.00
20.00
4.98 5.004.99 4.99 4.99 4.99 4.99 5.00 5.00
THD=37.7%Z=5%
AC Line Reactor vs DC Link Choke
0
20
40
60
80
100
120
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5Inductance (mH)
Inpu
t Cur
rent
TH
D (%
)
AC reactor with DCreactor of 2.75mH
AC reactor only
DC reactor only(with LIN=47μH)x
Δ
40.00
-30.00
0
-20.00
-10.00
10.00
20.00
30.00
4.98 5.004.99 4.99 4.99 4.99 4.99 5.00 5.00THD=92.5%Lac=0.47mH
40.00
-30.00
0
-20.00
-10.00
10.00
20.00
30.00
4.98 5.004.99 4.99 4.99 4.99 4.99 5.00 5.00
THD=92.4%Ldc=0.47mH
30.00
-25.00
0
-20.00
-10.00
10.00
20.00
4.98 5.004.99 4.99 4.99 4.99 4.99 5.00 5.00
THD=44%Lac=0.47mH
30.00
-20.00
0
-10.00
10.00
20.00
4.98 5.004.99 4.99 4.99 4.99 4.99 5.00 5.00
THD=59.6%Lac=1.4mH
25.00
-20.00
0
-15.00
-10.00
-5.00
5.00
10.00
15.00
20.00
4.98 5.004.99 4.99 4.99 4.99 4.99 5.00 5.00
THD=37.3%Lac=1.4mH
20.00
-15.00
0
-10.00
-5.00
5.00
10.00
15.00
4.98 5.004.99 4.99 4.99 4.99 4.99 5.00 5.00
THD=33.8%Lac=2.35mH
25.00
-20.00
0
-15.00
-10.00
-5.00
5.00
10.00
15.00
20.00
4.98 5.004.99 4.99 4.99 4.99 4.99 5.00 5.00
THD=43.9%Lac=2.35mH
40.00
-30.00
0
-20.00
-10.00
10.00
20.00
30.00
4.98 5.004.99 4.99 4.99 4.99 4.99 5.00 5.00
THD=82.9%Ldc=1.4mH
30.00
-20.00
0
-10.00
10.00
20.00
4.98 5.004.99 4.99 4.99 4.99 4.99 5.00 5.00
THD=58.5%Ldc=2.35mH
YASKAWA Page. 28
AC Line Reactor vs DC Link Choke
500
520
540
560
580
600
620
640
0 1 2 3 4 5
Inductance (mH)
Avg
. DC
Bus
Vol
tage
(V)
AC reactor only
xΔ
DC reactor only(with LIN=47μH)
YASKAWA Page. 29
Optimal Solution
• AC Line Inductor Alone Not Optimal because
of Voltage Drop
• DC Link Inductor Alone Does Not Provide
Surge Protection
• Optimal Solution is a Combination of the two –
1% AC Input Inductor + Standard DC Link
Choke
YASKAWA Page. 30
Harmonic Filters
• Capacitor Based Harmonic Filters
• Series Filter – tuned to offer high impedance
to select frequencies
• Shunt Filter – tuned to shunt select
frequencies
• Hybrid Filters – combination of above
• Large, bulky, expensive, and often ineffective
YASKAWA Page. 31
Series Harmonic Filter
• Series Filter
• Designed to handle rated load current
• More often found in single-phase applications
to impede 3rd harmonic current
Lf
Cf
YASKAWA Page. 32
Shunt Harmonic Filter
• Shunt Filter
• Designed to shunt select frequencies
• Draws fundamental frequency current
resulting in leading VA operation
• Need multiple section to be effective
• Does not distinguish between
intended load and other loads
Lf
Cf
YASKAWA Page. 33
Modified Shunt Harmonic Filter• Shunt Filter with Series Impedance
• Add a series inductance to restrict import of harmonics
• MTE’s and Mirus International’s Filter Structure
U
V
W
Lf
Cf
IM
5% ACReactor
5% ACReactor
YASKAWA Page. 34
Hybrid (Broad Band) Harmonic Filter
• Combination of shunt and series filter
• Series inductance and Shunt
Capacitor – over-voltage problem
• Autotransformer used to solve this
• Bulky, expensive
• Capacitor switching needed
Lf
Cf
Auto-transformer
YASKAWA Page. 35
Issues With Harmonic Filters
• All capacitor based shunt type filters draw
leading current and cause over-voltage
• Power Loss, and Higher Stresses on DC Bus
Capacitors – avoid using this
• Generally multiple sections needed
• Bulky and Expensive
• Can cause system resonance
YASKAWA Page. 36
Risk of Parallel Resonance
XcXL
ih
ih
Resonance occurs when: Xc = XL
Power Factor Capacitors Relieve Load
Parallel Resonance
Current measured at the capacitor,showing 660Hz, (11th harmonic resonance) Figure 36.2
YASKAWA Page. 37
Multi-pulse Harmonic Mitigation Technique
• 12-pulse Techniques
• Three-winding isolation transformer
• Hybrid 12-pulse
• Autotransformer based 12-pulse scheme
YASKAWA Page. 38
Three Winding 12-pulse Scheme
• Rated for full power operation – bulky but
ONLY option when input is medium
voltage and drive is of low voltage rating
X1
X2
X3Y1
Y2 Y3
H1
H3H2
L1
L21L31
L11
3-winding isolation transformer
H1
H2
H3
Ldc
VDC IMX1X2X3
U
V
WL2L3
Y1Y2Y3
YASKAWA Page. 39
Three Winding 12-pulse Waveforms
YASKAWA Page. 40
Hybrid 12-pulse Scheme
• Transformer rated for half power – attractive option
X1
X2
X3
L2L3
L1
L21L31
L11
Half power phase-shiftingisolation transformer
H1
H2
H3
Ldc
VDC IMX1X2X3
U
V
W
H1
H3H2
Matching Inductor(half-rated current)
Optional inputinductor, Lin ILM
IxfmrIin
YASKAWA Page. 41
Hybrid 12-pulse Waveforms
Iin
ILmIxfmr
48
1216
Harmonic Order
% D
isto
rtion
With no Lin
With Lin
THD 5 7 11 13 17 19
THD= 6.7% with 5% input reactor;8.8% with no input AC reactor.
YASKAWA Page. 42
Autotransformer 12-pulse Scheme
• Autotransformer configuration
• Needs IPT and ZSBT – bulky and costly
B
A C
b b
a
a
c
c
L2L3
L1
L21
L31
L11
C ited asprior art inUS patent#4,255,784
Inter-phaseTransformer
Inter-phaseTransformer
3-ph acsupply
zero-sequenceblocking
Transformer
CommonCore
YASKAWA Page. 43
Autotransformer 12-pulse Scheme
• Autotransformer configuration
• If loads are isolated and fairly balanced, this is very attractive
3-Ph ACsupply
B
A C
VFD #1 V Motor 1U
W
VFD #2 V Motor 2U
W
b' b
a
a'
c'
c
S'R'
T'
SR
T
YASKAWA Page. 44
Four Winding 18-pulse Scheme
• Transformer is rated for full power operation - bulky and expensive• Cost effective method if primary is MV• Attenuates conducted EMI effectively
X1
X2
X3
H1
H3
H2
L2L3
L1
L21L31
L11
4-winding isolationtransformer
H1
H2
H3
Ldc
VDC IM
X1X2X3
Y1Y2Y3
U
V
W
+20deg
-20deg
Y1
Y2
Y3
Z1
Z2Z3
L22L32
L12Z1Z2Z3
YASKAWA Page. 45
Autotransformer 18-pulse Scheme
• Autotransformer configuration
• Patented by D. Paice – only two US manufacturers licensed at present
H1
H3 H2
L2L3
L1
L21L31
L11
18-pulse autotransformer
Ldc
VDC IM
123
456
U
V
W
L22L32
L12789
12
3
4
56
7
8
9
H1
H2
H3
Input inductor,Lin
I1
I3
I5
Iin
YASKAWA Page. 46
Autotransformer 18-pulse Scheme
• Needs three diode bridges – Yaskawa uses
external diode bridges – makes it expensive
• Needs 7% input reactor for achieving THD levels
of 5% and below – increases cost and space
• With no input reactor, THD observed is about
8.8%
YASKAWA Page. 47
Autotransformer 18-pulse Waveform
IinI1
I3 I5
48
1216
With no Lin
Harmonic Order
% D
isto
rtion With Lin
THD 5 7 11 13 17 19
THD= 5.5% with 5% input reactor;8.7% with no input AC reactor.
YASKAWA Page. 48
Yaskawa’s own 18-pulse Scheme
• Less Complicated Structure
• Low Cost because of standard configuration
• Needs only 1.5% input reactor to bring THD
level to less than 5%
• With no input reactor, THD level observed to be
6.5%
YASKAWA Page. 49
Hybrid 18-pulse Scheme by Yaskawa
• Power rating of isolation transformer is 2/3 of rated output power
• Current through matching inductor is 1/3 of rated input current
• Patent Pending
X1
X2
X3
H1
H3
H2
L2L3
L1
L21L31
L11
2/3 rated phase-shiftingisolation transformer
Ldc
VDC IM
X1X2X3
Y1Y2Y3
U
V
W
-20deg
Y1
Y2Y3
L22L32
L12
+20deg
H1
H2
H3
Input inductor,Lin
Matching Inductor(1/3-rated current)
YASKAWA Page. 50
Hybrid 18-pulse Waveform
V LN
Iin
48
1216
With no Lin
Harmonic Order
% D
isto
r tion With Lin
THD 5 7 11 13 17 19
THD= 4.5% with 1.5% input reactor;6.5% with no input AC reactor.
YASKAWA Page. 51
Power Factor and Harmonics
• Two Definitions of Power Factor Exists
• Displacement Power Factor: Cosine of the
angle between the fundamental voltage and
fundamental current waveform
• For VFDs, this value is almost always unity
(0.99)
YASKAWA Page. 52
Power Factor and Harmonics• True Power Factor
• Ratio of True Power to Total Volt-Ampere
Demanded by Load
• Total Volt-Ampere includes VA demanded by
Harmonic Content in Waveform
kVAkWpf =
2
21
221
1
1
THDdpfpf
THDIkVkW
IIkVkW
IkVkWpf
ntotal
+=
+⋅⋅=
+⋅=
⋅=
∑
YASKAWA Page. 53
Power Factor and Harmonics
• True Power Factor is poor:
.
THD≈80%
THD≈37%
.
78.08.01 2
=+
=dpfpf
937.037.01 2
=+
=dpfpf
YASKAWA Page. 54
Conclusions
• IEEE 519 does not mean THD < 5%
• Find out PCC, ISC, and IL, Apply the
Spirit of IEEE 519 correctly
YASKAWA Page. 55
Conclusions
• Avoid capacitor based harmonic filter
• 12-pulse techniques can achieve low TDD at drive input
– Hybrid 12-pulse is attractive, less bulky and cost-effective
– Isolation transformer based method is best when input is MV
• Use 18-pulse only when Customer demands (Less than
5% TDD)
– Hybrid 18-pulse is attractive
– Isolation transformer based method is best when input is MV