Certificate No. 03/0183 Detail Sheet 2/ Xtratherm Thin-R Pitched Roof Board CERTIFICATE NO. 03/0183 DETAIL SHEET 2 Xtratherm Thin-R Pitched Roof Board (XT/PR Grade) PRODUCT DESCRIPTION: This Detail Sheet relates to Xtratherm Thin-R Pitched Roof Board, as defined in NSAI Agrément Certificate 03/0183. Xtratherm Thin-R Pitched Roof Board uses Polyisocyanurate (Polyiso), a thermoset closed cell rigid foam insulation manufactured in accordance with I.S. EN 13165:2012+A2:2016,Thermal insulation products for buildings – Factory made rigid polyurethane foam (PU) products Specification, having regard to the description of Polyisocyanurate (PIR) in paragraph 1 of the scope of the standard. During the manufacturing process, liquid raw materials expanded by blowing agents are applied between trilaminate aluminium foil facings. 1.1 ASSESSMENT In the opinion of NSAI Agrément, Xtratherm Thin-R Pitched Roof Board if used in accordance with this Detail Sheet, meets the requirements of the Building Regulations 1997 - 2017 as indicated in Section 1.2 of Certificate 03/0183. USE: The product is used for the thermal insulation of pitched and tiled roofs constructed in accordance with ICP 2:2002 Code of practice for slating and tiling. It can be used between, below, below and between, above or above and between rafters. It also facilitates the control of surface and interstitial condensation in roofs. 1.2 BUILDING REGULATIONS 1997 to 2017 This matter is dealt with in NSAI Agrément Certificate 03/0183.

Transcript of Xtratherm Thin-R Pitched Roof Board (XT/PR Grade) · 2021. 4. 30. · Pitched Roof Board if used in...

Page 1: Xtratherm Thin-R Pitched Roof Board (XT/PR Grade) · 2021. 4. 30. · Pitched Roof Board if used in accordance with this Detail Sheet, meets the requirements of the Building ... 2.2.2

Certificate No. 03/0183 Detail Sheet 2/ Xtratherm Thin-R Pitched Roof Board

CERTIFICATE NO. 03/0183 DETAIL SHEET 2

Xtratherm Thin-R Pitched Roof Board (XT/PR Grade)

PRODUCT DESCRIPTION: This Detail Sheet relates to Xtratherm Thin-R Pitched Roof Board, as defined in NSAI Agrément Certificate 03/0183. Xtratherm Thin-R Pitched Roof Board uses Polyisocyanurate (Polyiso), a thermoset closed cell rigid foam insulation manufactured in accordance with I.S. EN 13165:2012+A2:2016,Thermal insulation products for buildings – Factory made rigid polyurethane foam (PU) products – Specification, having regard to the description of Polyisocyanurate (PIR) in paragraph 1 of the scope of the standard. During the manufacturing process, liquid raw materials expanded by blowing agents are applied between trilaminate aluminium foil facings.

1.1 ASSESSMENT In the opinion of NSAI Agrément, Xtratherm Thin-R Pitched Roof Board if used in accordance with this Detail Sheet, meets the requirements of the Building Regulations 1997 - 2017 as indicated in Section 1.2 of Certificate 03/0183.

USE: The product is used for the thermal insulation of pitched and tiled roofs constructed in accordance with ICP 2:2002 Code of practice for slating and tiling. It can be used between, below, below and between, above or above and between rafters. It also facilitates the control of surface and interstitial condensation in roofs.

1.2 BUILDING REGULATIONS 1997 to 2017 This matter is dealt with in NSAI Agrément Certificate 03/0183.

Page 2: Xtratherm Thin-R Pitched Roof Board (XT/PR Grade) · 2021. 4. 30. · Pitched Roof Board if used in accordance with this Detail Sheet, meets the requirements of the Building ... 2.2.2

Certificate No. 03/0183 Detail Sheet 2/ Xtratherm Thin-R Pitched Roof Board

2.1 PRODUCT DESCRIPTION Xtratherm Thin-R Pitched Roof Board consists of a rigid Polyiso foam core with low emissivity trilaminate aluminium foil facings both sides. The edges of the boards are square, T&G or rebated. The system is an efficient single or double layer system combining insulation above and/or between and/or below rafters to form a roof that has many advantages over traditional methods of insulating at roof level providing a high level of thermal insulation in new and existing pitched roofs. Manufactured to I.S. EN 13165:2012 and tested to ensure compliance with the requirements for compressive strength, water vapour transmission, thermal conductivity, thermal resistance and dimensional stability. Xtratherm Thin-R Pitched Roof Boards are placed above and/or below and/or between rafters in conjunction with vapour permeable roof tile underlay, treated timber counter battens and tiling battens on roofs which have been designed in accordance with SR 82:2017, Slating and Tiling - Code of Practice. The XT/PR board does not contain either CFC or HCFC gases and has zero Ozone Depletion Potential. Table 1 shows the Xtratherm Thin-R Pitched Roof Board product range.

Length 2400mm Width 1200mm Thickness 25, 30, 35, 40, 45, 50, 55, 60, 65, 70,

75, 80, 90, 100, 120, 125, 140, 150, 165, 180mm

Grade PIR Other sizes are available subject to quantity

Table 1: Product Range The following ancillary products are used with the boards: Vapour permeably underlays used in conjunction

with Xtratherm Thin-R Pitched Roof Board should be subject to current certification and installed in accordance with manufacturer’s instructions for warm roof applications. Helifix Inskew or other approved proprietary

fixings should be used in accordance with SR 82:2017 and manufacturer’s instructions.

Names of approved fixings and addresses of suppliers are available from Xtratherm Ltd.

2.2 INSTALLATION 2.2.1 General Installation must be in accordance with the relevant clauses of SR 82:2017 and the manufacturer’s instructions, and can be carried out in all conditions normal for roof construction.

The boards are light to handle and can be easily cut or shaped. The boards will not support the weight of operatives and care must be taken during tiling. Cavity barriers should be provided at the junction of the external wall and roof space in accordance with the requirements of Part B of the Building Regulations 1997 to 2017.

2.2.2 Procedure – Single/Double Layer Over Rafters

(Warm Roof) Ensure that the Xtratherm Thin-R Pitched Roof Board has been continued to roof height to engage with the roof insulation. The insulation must be continuous to provide a complete envelope to reduce the risk of thermal bridging and condensation risk. A treated timber stop rail, the same thickness as the Xtratherm Thin-R Pitched Roof Board, is fixed to the rafters close to the eaves to provide a firm fixing point for the counter battens. The Xtratherm Thin-R Pitched Roof Boards are laid over the rafters commencing at the stop rail. The boards should be tightly butted and positioned in a staggered pattern with all the joints running from eaves to ridge occurring over the rafters. Repeat the procedure using crawling boards until the entire area from eaves to ridge has been covered. The insulation will not support operatives. Any gaps in the insulation must be sealed with flexible sealant or expanding foam. Use large headed clout nails to hold boards temporarily in place until the counter battens secure them. Treated counter battens are fixed through the insulation into the rafter with Helifix Inskew (or other approved proprietary) fixings at the appropriate centres, taking account of the specific roof design, e.g. pitch, weight of slates/tiles and location of the building. Additional Xtratherm XT/PR can be placed between the counter-battens to improve U values. The vapour permeable roof tile underlay is laid in accordance with its NSAI Agrément Certificate and manufacturer’s instructions. Slating and tiling is installed in accordance with SR 82:2017. When the relevant space is to be used as a living area, the Xtratherm Thin-R Pitched Roof Board should be covered with 12.5mm plasterboard. 2.2.3 Procedure – Double Layer Over and Between

Rafters (Warm Roof) Xtratherm Thin-R Pitched Roof Board is used as a double layer when insulation values required create an excessive thickness for a single layer application. The first layer of Xtratherm Thin-R Pitched Roof Board is cut to size and placed between the rafters on timber batten carriers or sarking clips that are nailed up the slope of the roof. The upper face of the board should be kept flush with the top of the rafter. The second layer

Page 3: Xtratherm Thin-R Pitched Roof Board (XT/PR Grade) · 2021. 4. 30. · Pitched Roof Board if used in accordance with this Detail Sheet, meets the requirements of the Building ... 2.2.2

Certificate No. 03/0183 Detail Sheet 2/ Xtratherm Thin-R Pitched Roof Board

over the rafters is applied as previously detailed in Section 2.2.2 of this Detail Sheet. 2.2.4 Procedure – Ventilated Roofs (Cold Roof) Warm pitched roofs as described in Section 2.2.3 of this Certificate may be the best solution for pitched roof insulation, but it is only suitable for new construction and some limited refurbishments where the roof covering is to be replaced. Placing the Xtratherm Thin-R Pitched Roof board between and/or below the rafter is another solution. This type of construction creates a ‘cold roof’ and because of the risk of interstitial condensation, Building Regulations require a continuous 50mm ventilation space is maintained. Care should be taken to ensure the ventilation space is not reduced and battens fixed to the rafters may be used as a retaining stop. In many constructions it may be necessary to fix only one layer of Xtratherm Thin-R Pitched Roof Board between the rafters to achieve the relevant U-value, however where the requirement is for very low U-values or to reduce the effects of thermal bridging, a second layer fixed to the rafters over the first layer may be appropriate. As in the solution for ‘warm roof’ when the relevant space is to be used as a living area, the Xtratherm Thin-R Pitched Roof Board should be covered with 12.5mm plasterboard.

Figure 1: Ventilated Roof Detail

In accordance with the Building Regulations, a 50mm ventilation space should be maintained between the sarking felt and the insulation, unless a breather membrane is used allowing for a reduction in the recommended airspace. Refer to manufacturer’s instructions and conditions of the NSAI Agrément Certificate. On-site trimming of boards where necessary to maintain continuity of insulation at rooflights, roof windows or other opes is easily executed using a fine tooth saw of builder’s knife. Figures 1 and 2 show installation details.

Figure 2: Warm Roof Detail

Thin-R Pitched Roof Board between rafters

Continuous ventilation gap

Soffit ventilation

Insulation between rafters

Thin-R Pitched Roof Board over rafters

Slip board

Page 4: Xtratherm Thin-R Pitched Roof Board (XT/PR Grade) · 2021. 4. 30. · Pitched Roof Board if used in accordance with this Detail Sheet, meets the requirements of the Building ... 2.2.2

Certificate No. 03/0183 Detail Sheet 2/ Xtratherm Thin-R Pitched Roof Board

3. GENERAL 3.1 Xtratherm Thin-R Pitched Roof Board when installed in accordance with this Detail Sheet, is effective in reducing the U-value (thermal transmittance) of new and existing pitched roof constructions. It is essential that such roofs are designed and constructed to prevent moisture penetration having regard to the Driving Rain Index. 3.2 Roofs subject to the relevant requirements of the Building Regulations 1997 to 2017 should be constructed in accordance with SR 82:2017. 3.3 During installation, boards must not be walked on except over supporting timbers. The boards have insufficient nail holding ability to be considered as an alternative to timber sarking. 3.4 Roof tile underlays must be approved by the manufacturer and be the subject of a current NSAI Agrément Certificate for such use. Underlays should be installed in accordance with, and within the limits of, that Certificate.

3.5 Moisture entering the roof must be minimised using a minimum of 500 gauge polyethylene with sealed gaps, placed under the inclined ceiling. Gaps in the ceiling should be minimised and service openings should be sealed.

3.6 The manufacturer has taken the responsibility of CE marking the products in accordance with harmonised standard I.S. EN 13165:2012+A2:2016, Thermal insulation products for buildings - Factory made rigid polyurethane foam (PU) products - Specification. An asterisk (*) appearing in this Certificate indicates that data shown is given in the manufacturer’s Declaration of Performance. Reference should be made to the latest version of the manufactures DoP for current information on any essential characteristics declared by the manufacturer.

4.1 BEHAVIOUR IN FIRE Combustibility –Xtratherm Thin-R Pitched Roof Board has a reaction to fire classification of NPD to IS EN 13501-1. The boards are combustible and must be protected from naked flames and other ignition sources during and after installation. The use of Xtratherm Thin-R Pitched Roof Board will not affect the fire rating obtained by the tiled/slated roof when assessed or tested to BS 476-3:2004 fire tests on building materials and structures – Classification and method of test for external fire exposure to roofs. Toxicity – Negligible when used in a ground floor construction. As Xtratherm Thin-R Pitched Roof Board XT/PR is manufactured without the use of CFC or HCFC gases, there is no release of such gas on burning.

4.2 STRENGTH Xtratherm Thin-R Pitched Roof Board when installed in accordance with this Detail Sheet and the manufacturer’s instructions, will resist the loads likely to be met during installation and in service.

4.3 RESISTANCE TO WIND LOAD The resistance to wind uplift depends on many factors peculiar to each project. The effect of wind loading should be calculated in accordance with I.S. EN 1991-1-4, Eurocode 1: Actions on structures - Part 1-4: General

actions - Wind actions, using the appropriate basic wind speed shown on the map in Diagram 1 of TGD to Part A of the Building Regulations 1997 to 2017. Xtratherm Thin-R Pitched Roof Board, when installed in accordance with this Detail Sheet, will have sufficient resistance to wind uplift. 4.4 RESISTANCE TO MOISTURE Xtratherm Thin-R Pitched Roof Board will not be adversely affected by rain during installation or by wind driven snow or rain penetrating the tiling in service. Water absorption is low and the influence on the thermal conductivity value is minimal. 4.5 CONDENSATION RISK The risk of interstitial condensation will be minimal under normal conditions of use. The boards have an intrinsically high vapour resistance and, when installed with tightly butted joints, filled/sealed joints and gaps will provide a continuous convection free envelope of high vapour resistance. Therefore, a suitable underlay may be laid over the insulation without ventilated airspace. Where high humidity may be expected, a vapour control layer should be used unless a condensation risk assessment in accordance with BS 5250:2011+A1:2016 shows that it is not necessary. The risk of interstitial condensation is greatest when the building is drying out after construction. To prevent condensation problem

Page 5: Xtratherm Thin-R Pitched Roof Board (XT/PR Grade) · 2021. 4. 30. · Pitched Roof Board if used in accordance with this Detail Sheet, meets the requirements of the Building ... 2.2.2

Certificate No. 03/0183 Detail Sheet 2/ Xtratherm Thin-R Pitched Roof Board

arising, additional ventilation, other than normally required, may be needed.

4.6 THERMAL INSULATION The aged thermal conductivity ‘90/90’ value of Xtratherm Thin-R Pitched Roof Board, when measured in accordance with IS EN 12667:2001, and calculated in accordance with Annex C of I.S. EN 13165:2012 is 0.022* W/m.K. The required maximum U-values for pitched roofs can be obtained with Xtratherm Thin-R Pitched Roof Board constructions as indicated in Table 3 and Table 4. The DoEHLG publication Limiting Thermal Bridging & Air Infiltration – Acceptable Construction Details gives guidance on limiting cold bridging and should be referred to. 4.7 DURABILITY Xtratherm Thin-R Pitched Roof Boards are rot-proof and durable. As roof insulation, Xtratherm Thin-R Pitched Roof Boards are judged to be stable and will remain

effective as an insulation system for the life of the building, so long as it is installed in accordance with this

Detail Sheet. 4.8 MAINTENANCE AND REPAIR Damaged boards can be easily replaced prior to the installation of counter battens. The product is light to handle and can be easily cut, but care must be taken to prevent damage. Since the board will not support the weight of operatives appropriate care must be taken during tiling/slating.

Property Declared Value Test Method

Reaction to Fire NPD* EN 13501

Dimensional Stability DS(70,90)4* EN 1604

Density 32 kg/m3 EN 1602

Compressive Strength CS (10/Y) 150* EN 826

Thermal Conductivity 0.022* W/mK EN 12667 Thermal Resistance - 35 mm - 40 mm - 60 mm - 80 mm - 100 mm - 120 mm - 140 mm - 165 mm - 180 mm

1.60 m2K/W 1.83 m2K/W 2.74 m2K/W 3.65 m2K/W 4.57 m2K/W 5.48 m2K/W 6.39 m2K/W 7.53 m2K/W 8.22 m2K/W

Table 2: Physical Properties of Xtratherm Thin-R Pitched Roof Board

Insulation above rafter Insulation above and

between rafterInsulation above and

between battens

U-value (W/m2K) 400mm centres 400mm centres 400mm centres

0.20 100 40/80 60/60

0.25 75 40/50 40/50

600mm centres 600mm centres 600mm centres

0.20 100 40/75 50/60

0.25 75 40/40 40/50

Table 3: Pitched Roof Constructions – Typical U-values – Warm Roof

Insulation in slope of rafter Insulation in slope of rafter

U-value (W/m2K) 400mm Centres 400mm Centres

0.20 80 + 90 100/40

0.25 60 + 70 80/30

0.35 90 50/25

600mm Centres 600mm Centres

0.20 70 + 80 90/40

0.25 60 + 60 80/30

0.35 80 50/25

Table 4: Pitched Roof Constructions – Typical U-values – Ventilated roof

Page 6: Xtratherm Thin-R Pitched Roof Board (XT/PR Grade) · 2021. 4. 30. · Pitched Roof Board if used in accordance with this Detail Sheet, meets the requirements of the Building ... 2.2.2

Certificate No. 03/0183 / Xtratherm Thin-R Insulation Products

THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENTTHE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENTTHE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENTTHE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENTTHE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENTTHE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENTTHE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENTTHE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENTTHE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENTTHE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENTTHE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENTTHE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENTTHE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENTTHE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENTTHE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENTTHE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD THE IRISH AGRÉMENT BOARD

This Certificate No. 03/0183 is accordingly granted by the NSAI to Xtratherm Ltd. on behalf of NSAI Agrément. Date of Issue: July 2003 Signed Seán Balfe Director of NSAI Agrément Readers may check that the status of this Certificate has not changed by contacting NSAI Agrément , NSAI, 1 Swift Square, Northwood, Santry, Dublin 9, Ireland. Telephone: (01) 807 3800. Fax: (01) 807 3842. www.nsai.ie Revisions: April 2010 Inclusion of 4 Thin-R insulation products. Revision: January 2018 Product specification updated to reflect manufactures Declaration of Performance. 13th January 2021: General revision.